152 3RD ST - ENERGY SHEETS Z �
PILE COPY
Hillis 152 3rd St Garage Suite
HVAC Load Calculations
for
Bosco Custom Homes
2158 Mayport Road
Atlantic Beach, FL 32233
EllEiltt oftvart
RHVACRESIDENTIAL
HVAC LOADS
Prepared By:
Jason McDuffie
Home Energy Services
2060 Davis Road
Jacksonville, FL 32218
904-757-3569
Tuesday, January 20, 2015
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services Hillis 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 2
Project Report
General Project Information
Project Title: Hillis 152 3rd St Garage Suite
Project Date: Tuesday, January 20, 2015
Client Name: Bosco Custom Homes
Client Address: 2158 Mayport Road
Client City: Atlantic Beach, FL 32233
Client Phone: 904.241.0320
Client Comment:
Company Name: Home Energy Services
Company Representative: Jason McDuffie
Company Address: 2060 Davis Road
Company City: Jacksonville, FL 32218
Company Phone: 904-757-3569
Company E-Mail Address: ecalcs @hesjax.com
Company Website: www.hesjax.com
I Design Data
Reference City: Jacksonville, Florida
Building Orientation: Front door faces North
Daily Temperature Range: Medium
Latitude: 30 Degrees
Elevation: 26 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 32 29.92 n/a n/a 70 n/a
Summer: 94 77 47% 50% 75 48
I Check Figures
Total Building Supply CFM: 375 CFM Per Square ft.: 1.218
Square ft. of Room Area: 308 Square ft. Per Ton: 403
Volume(ft')of Cond. Space: 2,772
I Building Loads
Total Heating Required Including Ventilation Air: 8,975 Btuh 8.975 MBH
Total Sensible Gain: 8,246 Btuh 90 %
Total Latent Gain: 928 Btuh 10
Total Cooling Required Including Ventilation Air: 9,174 Btuh 0.76 Tons(Based On Sensible + Latent)
Notes —I
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Hillis 152 3rd St Garage Suite.rh9 Tuesday,January 20,2015,4:52 PM
Rhvac Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services 16). Hillis 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 3
Miscellaneous Report
System 1 Main Outdoor Outdoor Outdoor Indoor Indoor Grains
Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 32 29.92 80% n/a 70 n/a
Summer: 94 77 47% 50% 75 48.06
I Duct Sizing Inputs
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Maximum Velocity: 900 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in. 0 in.
Outside Air Data
Winter Summer
Infiltration Specified: 0.250 AC/hr 0.250 AC/hr
12 CFM 12 CFM
Infiltration Actual: 0.250 AC/hr 0.250 AC/hr
Above Grade Volume: X 2,772 Cu.ft. X 2,772 Cu.ft.
693 Cu.ft./hr 693 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 12 CFM 12 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration &Ventilation Sensible Gain Multiplier: 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference)
Infiltration &Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.250 AC/hr(12 CFM)
Summer Infiltration Specified: 0.250 AC/hr(12 CFM)
Duct Load Factor Scenarios for System 1
Attic Duct Duct Surface From
No. Type Description Location Ceding - Leakage Insulation Area _ [T]MDD
1 Supply Main Attic 16B 0.09 6 83 No
1 Return Main Attic 16B 0.15 6 15 No
C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015,4:52 PM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services Hilts 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 4
Load Preview Report
Net ft.' Sen Lat Net Sen Sys Sys Sys Duct Clg Scope Ton /Ton Area Gain Gain Gain, Loss CFM CFM CFMSize
Building 0.76 403 308 8246 928 9,174 8.975 181 375 375
System 1 0.76 403 308 8246 928 9,174 8,975 181 375 375 9x9
Duct Latent 151 151
Zone 1 308 8,246 777 9,023 8,975 181 375 375 9x9
1-Garage Suite 308 8246 777 9,023 8,975 181 375 375 4-6
C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20,2015, 4:52 PM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services Hillis 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 5
Duct Size Preview
Room or Source Minimum Maximum Rough Design SP Duct Duct Htg Ckg Act. Duct
Duct Name Velocity Velocity, Factor L/100 Loss Velocity Length Flow Flow Flow Size
System 1
Supply Runouts
Zone 1
1-Garage Suite Built-In 450 750 0.01 0.1 477.7 181 _ 375 4-6
Other Ducts in System 1
Supply Main Trunk Built-In 650 900 0.003 0.1 667 181 MI 375 9x9
Summary
System 1
Heating Flow: 181
Cooling Flow 375
C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20,2015,4:52 PM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services Hillis 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 6
Total Building Summary Loads
Component Area Sen Lat Sen Total
Description Quan Loss Gain Gain Gain
10D-f: Glazing-French door, double pane low-e glass(e = 56.7 753 0 1,286 1,286
0.10), insulated fiberglass frame, u-value 0.35,
SHGC 0.35
4A-6-o: Glazing-Double pane low-e(e = 0.20 or less), 21.3 283 0 858 858
high performance, operable window, e=0.05 on
surface 2, any frame, u-value 0.35, SHGC 0.35
11J: Door-Metal - Fiberglass Core 18.9 431 0 340 340
12C-Osw: Wall-Frame, R-13 insulation in 2 x 4 stud 353.1 1,222 0 819 819
cavity, no board insulation, siding finish, wood studs
12C-Osw: Part-Frame, R-13 insulation in 2 x 4 stud 198 685 0 342 342
cavity, no board insulation, siding finish, wood studs
16B-30: Roof/Ceiling-Under Attic with Insulation on Attic 308 375 0 532 532
Floor(also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-30 insulation
22A-ph: Floor-Slab on grade, No edge insulation, no 72 3,715 0 0 0
insulation below floor, any floor cover, passive, heavy
moist soil
Subtotals for structure: 7,464 0 4,177 4,177
People: 2 400 460 860
Equipment: 0 2,400 2,400
Lighting: 0 0 0
Ductwork: 1,029 151 968 1,119
Infiltration: Winter CFM: 12, Summer CFM: 12 482 377 241 618
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
Total Building Load Totals: 8,975 928 8,246 9,174
Check Figures
Total Building Supply CFM: 375 CFM Per Square ft.: 1.218
Square ft. of Room Area: 308 Square ft. Per Ton: 403
Volume(ft3)of Cond. Space: 2,772
Building Loads - _ -
Total Heating Required Including Ventilation Air: 8,975 Btuh 8.975 MBH
Total Sensible Gain: 8,246 Btuh 90 %
Total Latent Gain: 928 Btuh 10 %
Total Cooling Required Including Ventilation Air: 9,174 Btuh 0.76 Tons(Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015,4:52 PM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
Home Energy Services Hilts 152 3rd St Garage Suite
Jacksonville,FL 32218 Page 7
Building Pie Chart
Infiltration 5%
Ductwork 11%
Door 5%
Floor 41%
Building
Loss
8,975 Glass 12%
Btuh
Roof 4% Wall 21%
Roof 6% Infiltration 7%
Wall 13% Ductwork 12%
Building
Gain
9,174
Btuh
{ Glass 23%
Equipment 26%
Door 4%
People 9%
152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015, 4:52 PM
Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc
Home Energy Services Hillis 152 3rd St Garage Suite
Jacksonville,FL 32218 C Page 8
System 1 Room Load Summary
IHtg Min Run Run Clg Clg Mi Act
Room Area Sens Htg Duct Duct Sens Lat Cl Sys,
No Name , - Btuh CFM Size V,eI._. Btuh......•_Btuh CF CFM1
--Zone 1---
1 Garage Suite 308 8,975 181 4-6 478 8,246 777 375 375
Duct Latent 151
System 1 total 308 8,975 181 8,246 928 375 375
System 1 Main Trunk Size: 9x9 in.
Velocity: 667 ft./min
Loss per 100 ft.: 0.115 in.wg
Coolin• S stem Summa
Cooling Sensible/Latent Sensible Latent Total
Tons Split Btuh Btuh Btuh
Net Required: 0.76 90% / 10% 8,246 928 9,174
Actual: 1.00 75% /25% 9,000 3,000 12,000
I Equipment Data
Heating System Cooling System
Type: Air Source Heat Pump Air Source Heat Pump
Model: MUZ-HE12NA MUZ-HE12NA
Indoor Model: MSZ-HE12NA
Brand: MR. SLIM MR. SLIM
Description: Air Source Heat Pump Air Source Heat Pump
Efficiency: 8.5 HSPF 18 SEER
Sound: 0 0
Capacity: 12,200 Btuh 12,000 Btuh
Sensible Capacity: n/a 9,000 Btuh
Latent Capacity: n/a 3,000 Btuh
AHRI Reference No.: n/a 7065527
C:\ _Millis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015, 4:52 PM
FILE COPY
FORM 405-10
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Hillis 152 3rd St Garage Suite Builder Name: Bosco Custom Homes
Street: 152 3rd Street Permit Office: Duval //��
City,State,Zip: Atlantic Beach,FL,32233- Permit Number: /5-RAM.- 13 9 &/
Owner: Jurisdiction: 261100
Design Location: FL,Jacksonville
1. New construction or existing New(From Plans) 9. Wall Types(648.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.0 450.00 ft'
b.Frame-Wood,Adjacent R=13.0 198.00 ft'
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 1 d.N/A R= ft'
5 Is this a worst case? No 10.Ceiling Types (308.0 sqft.) Insulation Area
a.Under Attic(Vented) R=30.0 308.00 ft
6. Conditioned floor area above grade(ft') 308 b. N/A R= ft2
Conditioned floor area below grade(ft') 0 c. N/A R= ft2
11.Ducts R ft'
7. Windows(78.0 sqft.) Description Area
a. U-Factor: Dbl,U=0.35 78.01 ft'
SHGC: SHGC=0.35
b. U-Factor N/A ft' 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 12.0 SEER:13.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft' a.Electric Heat Pump 12.0 HSPF:7.70
SHGC:
Area Weighted Average Overhang Depth: 1.000 ft.
Area Weighted Average SHGC: 0.350 14.Hot water systems
8. Floor Types (308.0 sqft.) Insulation Area a.Natural Gas Tankless Cap:1 gallons
EF:0.590
a.Slab-On-Grade Edge Insulation R=0.0 308.00 ft' b. Conservation features
b.N/A R= ft' None
c.N/A R= ft' 15.Credits Pstat
Total Proposed Modified Loads: 9.44 PASS
Glass/Floor Area: 0.253
Total Standard Reference Loads: 15.23
I hereby certify that the plans and specifications covered by Review of the plans and .•••�F'CHTgT•••
this calculation are in compliance with the Florida Energy specifications covered by this `� � ..................A Fp� ,
Code. calculation indicates compliance ,,,°,`• •'•
ne le ervic p ` = .0
with the Florida Energy Code. :',/,,, �(''- `:r.':.,• O
PREPARED BY _ a - Before construction is completed c 1 s •�e-�`.E •
DATE: _ 1/20/2015 this building will be inspected for 61. -�L ,'a
compliance with Section 553.908 ,`.• _ :•'
I hereby certify that this building as ig,ed, is • compliance Florida Statutes. '::f, .... :Y... .,
with the Florida Energy Cod- /j� .,•••CAD .;•
OWNER/AGEN lbw, �•1•a BUILDING OFFICIAL:
DATE: /11' _ DATE:
- Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist
1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 5
A
PROJECT
Title: Hillis 152 3rd St Garage Suite Bedrooms: 1 Address Type: Street Address
Building Type: User Conditioned Area: 308 Lot#
Owner: Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Bosco Custom Homes Rotate Angle: 0 Street: 152 3rd Street
Permit Office: Duval CrossVentilation: County: Duval
Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach,
Family Type: Single-family FL, 32233-
New/Existing: New(From Plans)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium
BLOCKS
Number Name Area Volume
1 Block/ 308 2772
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms lad ID Finished Cooled Heated
1 Main 308 2772 No 2 1 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge lnsulatio Main 72 ft 0 308 ft2 ____ 0.3 0 0.7
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Gable or shed Metal 344 ft2 78 ft2 Light 0.96 No 0.9 No 0 26.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 300 308 ft2 N N
CEILING
✓ # Ceiling Type Space R-Value Area Framing Frac Truss Type
1 Under Attic(Vented) Main 30 308 ft2 0.11 Wood
1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 5
i
•
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
# Omt To Wall Type Space R-ValLip Ft In Ft In Area R-VahIP Frartinn Ahsnr Grade%
1 N Exterior Frame-Wood Main 13 22 0 9 0 198.0 ft2 0 0.23 0.8 0
-
2 E Exterior Frame-Wood Main 13 14 0 9 0 126.0 ft2 0 0.23 0.8 0
-
_ 3 S Garage Frame-Wood Main 13 22 0 9 0 198.0 ft2 0 0.23 0.8 0
4 W Exterior Frame-Wood Main 13 14 0 9 0 126.0 ft2 0 0.23 0.8 0
DOORS
V # Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 N Insulated Main None .6 2.7 7 18.9 ft2
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 N 1 Vinyl Low-E Double Yes 0.35 0.35 37.8 W 1 ft 0 in 10 ft 0 in None None
2 E 2 Vinyl Low-E Double Yes 0.35 0.35 18.9 ft2 1 ft 0 in 10 ft 0 in None None
3 E 2 Vinyl Low-E Double Yes 0.35 0.35 14.3 ft2 1 ft 0 in 10 ft 0 in None None
4 W 4 Vinyl Low-E Double Yes 0.35 0.35 7.0 ft2 1 ft 0 in 10 ft 0 in None None
GARAGE
V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 382.8 ft2 382.8 W 64 ft 8 ft 1
IINFILTRATION
# Scope Method SLA CFM 50 ELA EqLA ACH ACH 50
1 Wholehouse Best Guess .0003 242.4 13.31 25.02 .231 5.246
HEATING SYSTEM
✓ # System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump Through the Wall(Split) HSPF:7.7 12 kBtu/hr 1 Ductless
COOLING SYSTEM
V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Through the Wall(Split) SEER: 13 12 kBtu/hr 360 cfm 0.75 1 Ductless
HOT WATER SYSTEM
V # System Type SubType Location EF Cap Use SetPnt Conservation
1 Natural Gas Tankless Exterior 0.59 1 gal 40 gal 120 deg None
1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 5
1
SOLAR HOT WATER SYSTEM
V FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
TEMPERATURES
Programable Thermostat: Y Ceiling Fans:
Cooling HJan "Feb Mar .A r [ I Ma n Jun n Jul n Au n Se Oct Nov Dec
Heating Jan IX)Feb )()Mar ]Apr [ May Jun Jul Au Sep Oct )C Nov )()Dec
Ventin Jan Feb X,Mar 'X]Apr [ May Jun Jul Aug Sep X Oct Xi Nov Dec
ThermostatSchedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 5
FORM 405-10
Florida Code Compliance Checklist
Florida Department of Business and Professional Regulations
Residential Whole Building Performance Method
ADDRESS: 152 3rd Street PERMIT#:
Atlantic Beach, FL, 32233-
MANDATORY REQUIREMENTS SUMMARY-See individual code sections for full details.
COMPONENT SECTION SUMMARY OF REQUIREMENT(S) CHECK
Air leakage 402.4 To be caulked, gasketed, weatherstripped or otherwise sealed.
Recessed lighting IC-rated as meeting ASTM E 283. Windows and
doors = 0.30 cfm/sq.ft. Testing or visual inspection required.
Fireplaces: gasketed doors &outdoor combustion air. Must complete
envelope leakage report or visually verify Table 402.4.2.
Thermostat& 403.1 At least one thermostat shall be provided for each separate heating
controls and cooling system. Where forced-air furnace is primary system,
programmable thermostat is required. Heat pumps with supplemental
electric heat must prevent supplemental heat when compressor can
meet the load.
Ducts 403.2.2 All ducts, air handlers, filter boxes and building cavities which form the
primary air containment passageways for air distribution systems shall
be considered ducts or plenum chambers, shall be constructed and
sealed in accordance with Section 503.2.7.2 of this code.
403.3.3 Building framing cavities shall not be used as supply ducts.
Water heaters 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies
in Table 403.4.3.2. Provide switch or clearly marked circuit breaker
(electric) or shutoff(gas). Circulating system pipes insulated to =
R-2 +accessible manual OFF switch.
Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical
ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level.
No make-up air from attics, crawlspaces, garages or outdoors adjacent
to pools or spas.
Swimming Pools 403.9 Pool pumps and pool pump motors with a total horsepower(HP)of= 1
&Spas HP shall have the capability of operating at two or more speeds. Spas
and heated pools must have vapor-retardant covers or a liquid cover or
other means proven to reduce heat loss except if 70%of heat from
site-recovered energy. Off/timer switch required. Gas heaters minimum
thermal efficiency=78% (82%after 4/16/13). Heat pump pool heaters
minimum COP=4.0.
Cooling/heating 403.6 Sizing calculation performed &attached. Minimum efficiencies per
Tables 503.2.3. Equipment efficiency verification required. Special
equipment occasion cooling or heating capacity requires separate system or
variable capacity system. Electric heat>10kW must be divided into two
or more stages.
Ceilings/knee walls 405.2.1 R-19 space permitting.
1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 5
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 62
The lower the EnergyPerformance Index, the more efficient the home.
152 3rd Street, Atlantic Beach, FL, 32233-
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.0 450.00 ft=
b. Frame-Wood,Adjacent R=13.0 198.00 ft
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 1 d.N/A R= ft2
10.Ceiling Types Insulation Area
5. Is this a worst case? No a.Under Attic(Vented) R=30.0 308.00 ft2
6. Conditioned floor area(ft2) 308 b.N/A R= ft2
7. Windows" Description Area c. N/A R= ft2
2
a. U-Factor: Dbl,U=0.35 78.01 ft2 11.Ducts R ft
SHGC: SHGC=0.35
b. U-Factor: N/A ft2
SHGC: 12.Cooling systems kBlu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 12.0 SEER:13.00
SHGC:
d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency
SHGC: a. Electric Heat Pump 12.0 HSPF:7.70
Area Weighted Average Overhang Depth: 1.000 ft.
Area Weighted Average SHGC: 0.350
8. Floor Types Insulation Area 14.Hot water systems
2 a.Natural Gas Cap:1 gallons
a.Slab-On-Grade Edge Insulation R=0.0 308.00 ft EF:0.59
b.N/A R= ft2
c.N/A R= ft2 b. Conservation features
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building SHE sT
Construction through the above energy saving features which will be installed (or exceeded) ::';�..........; .....gT6o ;
in this home before final inspection. Otherwise, a new EPL Display Card will be completed : <c3';; r `;.• `::
based on installed Code compliant f- •••..= ,,:.4,;,o
Builder Signature: i` Date: �S o' ;1' _e_w :a eZG
Address of New Home: /S'Z 3'e° .5.7`. City/ Zip: /57 ,�Z233 **-,...e4;............ --Y JgS '•
.•••COD WE'.•••,::
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff.
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software
TABLE 402.4.2
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Hillis 152 3rd St Garage Suite Builder Name: Bosco Custom Homes
Street: 152 3rd Street Permit Office: Duval
City,State,Zip: Atlantic Beach,FL,32233- Permit Number:
Owner: Jurisdiction: 261100
Design Location: FL,Jacksonville
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in
substantial contact and continuous alignment with building
envelope air barrier.
Breaks or joints in the air barrier are filled or repaired.
Air-permeable insulation is not used as a sealing material.
Air-permeable insulation is inside of an air barrier.
Ceiling/attic Air barrier in any dropped ceiling/soffit is substantially aligned with
insulation and any gaps are sealed.
Attic access (except unvented attic), knee wall door, or drop down
stair is sealed.
Walls Corners and headers are insulated.
Junction of foundation and sill plate is sealed.
Windows and doors Space between window/door jambs and framing is sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including Insulation is installed to maintain permanent contact with underside
above-garage and of subfloor decking.
cantilevered floors) Air barrier is installed at any exposed edge of insulation.
Crawl space walls Insulation is permanently attached to walls.
Exposed earth in unvented crawl spaces is covered with Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, knee walls and flue shafts opening
to exterior or unconditioned space are sealed.
Narrow cavities Batts in narrow cavities are cut to fit, or narrow cavities are filled by
sprayed/blown insulation.
Garage separation Air sealing is provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures are air tight, IC rated, and sealed to drywall.
Exception—fixtures in conditioned space.
Plumbing and wiring Insulation is placed between outside and pipes. Batt insulation is
cut to fit around wiring and plumbing, or sprayed/blown insulation
extends behind piping and wiring.
Shower/tub on exterior wall Showers and tubs on exterior walls have insulation and an air
barrier separating them from the exterior wall.
Electrical/phone box on Air barrier extends behind boxes or air sealed-type boxes are
installed.
Common wall Air barrier is installed in common wall between dwelling units.
HVAC register boots HVAC register boots that penetrate building envelope are sealed to
subfloor or drywall.
Fireplace _ Fireplace walls include an air barrier.
EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software