152 3RD ST - ENERGY SHEETS Z � PILE COPY Hillis 152 3rd St Garage Suite HVAC Load Calculations for Bosco Custom Homes 2158 Mayport Road Atlantic Beach, FL 32233 EllEiltt oftvart RHVACRESIDENTIAL HVAC LOADS Prepared By: Jason McDuffie Home Energy Services 2060 Davis Road Jacksonville, FL 32218 904-757-3569 Tuesday, January 20, 2015 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Hillis 152 3rd St Garage Suite Jacksonville,FL 32218 Page 2 Project Report General Project Information Project Title: Hillis 152 3rd St Garage Suite Project Date: Tuesday, January 20, 2015 Client Name: Bosco Custom Homes Client Address: 2158 Mayport Road Client City: Atlantic Beach, FL 32233 Client Phone: 904.241.0320 Client Comment: Company Name: Home Energy Services Company Representative: Jason McDuffie Company Address: 2060 Davis Road Company City: Jacksonville, FL 32218 Company Phone: 904-757-3569 Company E-Mail Address: ecalcs @hesjax.com Company Website: www.hesjax.com I Design Data Reference City: Jacksonville, Florida Building Orientation: Front door faces North Daily Temperature Range: Medium Latitude: 30 Degrees Elevation: 26 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 32 29.92 n/a n/a 70 n/a Summer: 94 77 47% 50% 75 48 I Check Figures Total Building Supply CFM: 375 CFM Per Square ft.: 1.218 Square ft. of Room Area: 308 Square ft. Per Ton: 403 Volume(ft')of Cond. Space: 2,772 I Building Loads Total Heating Required Including Ventilation Air: 8,975 Btuh 8.975 MBH Total Sensible Gain: 8,246 Btuh 90 % Total Latent Gain: 928 Btuh 10 Total Cooling Required Including Ventilation Air: 9,174 Btuh 0.76 Tons(Based On Sensible + Latent) Notes —I Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Hillis 152 3rd St Garage Suite.rh9 Tuesday,January 20,2015,4:52 PM Rhvac Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services 16). Hillis 152 3rd St Garage Suite Jacksonville,FL 32218 Page 3 Miscellaneous Report System 1 Main Outdoor Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 32 29.92 80% n/a 70 n/a Summer: 94 77 47% 50% 75 48.06 I Duct Sizing Inputs Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01000 Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air Data Winter Summer Infiltration Specified: 0.250 AC/hr 0.250 AC/hr 12 CFM 12 CFM Infiltration Actual: 0.250 AC/hr 0.250 AC/hr Above Grade Volume: X 2,772 Cu.ft. X 2,772 Cu.ft. 693 Cu.ft./hr 693 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 12 CFM 12 CFM Total Building Ventilation: 0 CFM 0 CFM ---System 1--- Infiltration &Ventilation Sensible Gain Multiplier: 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference) Infiltration &Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 AC/hr(12 CFM) Summer Infiltration Specified: 0.250 AC/hr(12 CFM) Duct Load Factor Scenarios for System 1 Attic Duct Duct Surface From No. Type Description Location Ceding - Leakage Insulation Area _ [T]MDD 1 Supply Main Attic 16B 0.09 6 83 No 1 Return Main Attic 16B 0.15 6 15 No C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015,4:52 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Hilts 152 3rd St Garage Suite Jacksonville,FL 32218 Page 4 Load Preview Report Net ft.' Sen Lat Net Sen Sys Sys Sys Duct Clg Scope Ton /Ton Area Gain Gain Gain, Loss CFM CFM CFMSize Building 0.76 403 308 8246 928 9,174 8.975 181 375 375 System 1 0.76 403 308 8246 928 9,174 8,975 181 375 375 9x9 Duct Latent 151 151 Zone 1 308 8,246 777 9,023 8,975 181 375 375 9x9 1-Garage Suite 308 8246 777 9,023 8,975 181 375 375 4-6 C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20,2015, 4:52 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Hillis 152 3rd St Garage Suite Jacksonville,FL 32218 Page 5 Duct Size Preview Room or Source Minimum Maximum Rough Design SP Duct Duct Htg Ckg Act. Duct Duct Name Velocity Velocity, Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 Supply Runouts Zone 1 1-Garage Suite Built-In 450 750 0.01 0.1 477.7 181 _ 375 4-6 Other Ducts in System 1 Supply Main Trunk Built-In 650 900 0.003 0.1 667 181 MI 375 9x9 Summary System 1 Heating Flow: 181 Cooling Flow 375 C:\...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20,2015,4:52 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Hillis 152 3rd St Garage Suite Jacksonville,FL 32218 Page 6 Total Building Summary Loads Component Area Sen Lat Sen Total Description Quan Loss Gain Gain Gain 10D-f: Glazing-French door, double pane low-e glass(e = 56.7 753 0 1,286 1,286 0.10), insulated fiberglass frame, u-value 0.35, SHGC 0.35 4A-6-o: Glazing-Double pane low-e(e = 0.20 or less), 21.3 283 0 858 858 high performance, operable window, e=0.05 on surface 2, any frame, u-value 0.35, SHGC 0.35 11J: Door-Metal - Fiberglass Core 18.9 431 0 340 340 12C-Osw: Wall-Frame, R-13 insulation in 2 x 4 stud 353.1 1,222 0 819 819 cavity, no board insulation, siding finish, wood studs 12C-Osw: Part-Frame, R-13 insulation in 2 x 4 stud 198 685 0 342 342 cavity, no board insulation, siding finish, wood studs 16B-30: Roof/Ceiling-Under Attic with Insulation on Attic 308 375 0 532 532 Floor(also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane, R-30 insulation 22A-ph: Floor-Slab on grade, No edge insulation, no 72 3,715 0 0 0 insulation below floor, any floor cover, passive, heavy moist soil Subtotals for structure: 7,464 0 4,177 4,177 People: 2 400 460 860 Equipment: 0 2,400 2,400 Lighting: 0 0 0 Ductwork: 1,029 151 968 1,119 Infiltration: Winter CFM: 12, Summer CFM: 12 482 377 241 618 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 Total Building Load Totals: 8,975 928 8,246 9,174 Check Figures Total Building Supply CFM: 375 CFM Per Square ft.: 1.218 Square ft. of Room Area: 308 Square ft. Per Ton: 403 Volume(ft3)of Cond. Space: 2,772 Building Loads - _ - Total Heating Required Including Ventilation Air: 8,975 Btuh 8.975 MBH Total Sensible Gain: 8,246 Btuh 90 % Total Latent Gain: 928 Btuh 10 % Total Cooling Required Including Ventilation Air: 9,174 Btuh 0.76 Tons(Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\ ...\Hillis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015,4:52 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Hilts 152 3rd St Garage Suite Jacksonville,FL 32218 Page 7 Building Pie Chart Infiltration 5% Ductwork 11% Door 5% Floor 41% Building Loss 8,975 Glass 12% Btuh Roof 4% Wall 21% Roof 6% Infiltration 7% Wall 13% Ductwork 12% Building Gain 9,174 Btuh { Glass 23% Equipment 26% Door 4% People 9% 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015, 4:52 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc Home Energy Services Hillis 152 3rd St Garage Suite Jacksonville,FL 32218 C Page 8 System 1 Room Load Summary IHtg Min Run Run Clg Clg Mi Act Room Area Sens Htg Duct Duct Sens Lat Cl Sys, No Name , - Btuh CFM Size V,eI._. Btuh......•_Btuh CF CFM1 --Zone 1--- 1 Garage Suite 308 8,975 181 4-6 478 8,246 777 375 375 Duct Latent 151 System 1 total 308 8,975 181 8,246 928 375 375 System 1 Main Trunk Size: 9x9 in. Velocity: 667 ft./min Loss per 100 ft.: 0.115 in.wg Coolin• S stem Summa Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 0.76 90% / 10% 8,246 928 9,174 Actual: 1.00 75% /25% 9,000 3,000 12,000 I Equipment Data Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: MUZ-HE12NA MUZ-HE12NA Indoor Model: MSZ-HE12NA Brand: MR. SLIM MR. SLIM Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.5 HSPF 18 SEER Sound: 0 0 Capacity: 12,200 Btuh 12,000 Btuh Sensible Capacity: n/a 9,000 Btuh Latent Capacity: n/a 3,000 Btuh AHRI Reference No.: n/a 7065527 C:\ _Millis 152 3rd St Garage Suite.rh9 Tuesday, January 20, 2015, 4:52 PM FILE COPY FORM 405-10 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Hillis 152 3rd St Garage Suite Builder Name: Bosco Custom Homes Street: 152 3rd Street Permit Office: Duval //�� City,State,Zip: Atlantic Beach,FL,32233- Permit Number: /5-RAM.- 13 9 &/ Owner: Jurisdiction: 261100 Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(648.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.0 450.00 ft' b.Frame-Wood,Adjacent R=13.0 198.00 ft' 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d.N/A R= ft' 5 Is this a worst case? No 10.Ceiling Types (308.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 308.00 ft 6. Conditioned floor area above grade(ft') 308 b. N/A R= ft2 Conditioned floor area below grade(ft') 0 c. N/A R= ft2 11.Ducts R ft' 7. Windows(78.0 sqft.) Description Area a. U-Factor: Dbl,U=0.35 78.01 ft' SHGC: SHGC=0.35 b. U-Factor N/A ft' 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 12.0 SEER:13.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft' a.Electric Heat Pump 12.0 HSPF:7.70 SHGC: Area Weighted Average Overhang Depth: 1.000 ft. Area Weighted Average SHGC: 0.350 14.Hot water systems 8. Floor Types (308.0 sqft.) Insulation Area a.Natural Gas Tankless Cap:1 gallons EF:0.590 a.Slab-On-Grade Edge Insulation R=0.0 308.00 ft' b. Conservation features b.N/A R= ft' None c.N/A R= ft' 15.Credits Pstat Total Proposed Modified Loads: 9.44 PASS Glass/Floor Area: 0.253 Total Standard Reference Loads: 15.23 I hereby certify that the plans and specifications covered by Review of the plans and .•••�F'CHTgT••• this calculation are in compliance with the Florida Energy specifications covered by this `� � ..................A Fp� , Code. calculation indicates compliance ,,,°,`• •'• ne le ervic p ` = .0 with the Florida Energy Code. :',/,,, �(''- `:r.':.,• O PREPARED BY _ a - Before construction is completed c 1 s •�e-�`.E • DATE: _ 1/20/2015 this building will be inspected for 61. -�L ,'a compliance with Section 553.908 ,`.• _ :•' I hereby certify that this building as ig,ed, is • compliance Florida Statutes. '::f, .... :Y... ., with the Florida Energy Cod- /j� .,•••CAD .;• OWNER/AGEN lbw, �•1•a BUILDING OFFICIAL: DATE: /11' _ DATE: - Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist 1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 5 A PROJECT Title: Hillis 152 3rd St Garage Suite Bedrooms: 1 Address Type: Street Address Building Type: User Conditioned Area: 308 Lot# Owner: Total Stories: 1 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Bosco Custom Homes Rotate Angle: 0 Street: 152 3rd Street Permit Office: Duval CrossVentilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233- New/Existing: New(From Plans) Comment: CLIMATE IECC Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block/ 308 2772 SPACES Number Name Area Volume Kitchen Occupants Bedrooms lad ID Finished Cooled Heated 1 Main 308 2772 No 2 1 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter R-Value Area Tile Wood Carpet 1 Slab-On-Grade Edge lnsulatio Main 72 ft 0 308 ft2 ____ 0.3 0 0.7 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Metal 344 ft2 78 ft2 Light 0.96 No 0.9 No 0 26.6 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Vented 300 308 ft2 N N CEILING ✓ # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Vented) Main 30 308 ft2 0.11 Wood 1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 5 i • WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below # Omt To Wall Type Space R-ValLip Ft In Ft In Area R-VahIP Frartinn Ahsnr Grade% 1 N Exterior Frame-Wood Main 13 22 0 9 0 198.0 ft2 0 0.23 0.8 0 - 2 E Exterior Frame-Wood Main 13 14 0 9 0 126.0 ft2 0 0.23 0.8 0 - _ 3 S Garage Frame-Wood Main 13 22 0 9 0 198.0 ft2 0 0.23 0.8 0 4 W Exterior Frame-Wood Main 13 14 0 9 0 126.0 ft2 0 0.23 0.8 0 DOORS V # Omt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 N Insulated Main None .6 2.7 7 18.9 ft2 WINDOWS Orientation shown is the entered,Proposed orientation. Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N 1 Vinyl Low-E Double Yes 0.35 0.35 37.8 W 1 ft 0 in 10 ft 0 in None None 2 E 2 Vinyl Low-E Double Yes 0.35 0.35 18.9 ft2 1 ft 0 in 10 ft 0 in None None 3 E 2 Vinyl Low-E Double Yes 0.35 0.35 14.3 ft2 1 ft 0 in 10 ft 0 in None None 4 W 4 Vinyl Low-E Double Yes 0.35 0.35 7.0 ft2 1 ft 0 in 10 ft 0 in None None GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 382.8 ft2 382.8 W 64 ft 8 ft 1 IINFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Best Guess .0003 242.4 13.31 25.02 .231 5.246 HEATING SYSTEM ✓ # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump Through the Wall(Split) HSPF:7.7 12 kBtu/hr 1 Ductless COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit Through the Wall(Split) SEER: 13 12 kBtu/hr 360 cfm 0.75 1 Ductless HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas Tankless Exterior 0.59 1 gal 40 gal 120 deg None 1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 5 1 SOLAR HOT WATER SYSTEM V FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Cooling HJan "Feb Mar .A r [ I Ma n Jun n Jul n Au n Se Oct Nov Dec Heating Jan IX)Feb )()Mar ]Apr [ May Jun Jul Au Sep Oct )C Nov )()Dec Ventin Jan Feb X,Mar 'X]Apr [ May Jun Jul Aug Sep X Oct Xi Nov Dec ThermostatSchedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 5 FORM 405-10 Florida Code Compliance Checklist Florida Department of Business and Professional Regulations Residential Whole Building Performance Method ADDRESS: 152 3rd Street PERMIT#: Atlantic Beach, FL, 32233- MANDATORY REQUIREMENTS SUMMARY-See individual code sections for full details. COMPONENT SECTION SUMMARY OF REQUIREMENT(S) CHECK Air leakage 402.4 To be caulked, gasketed, weatherstripped or otherwise sealed. Recessed lighting IC-rated as meeting ASTM E 283. Windows and doors = 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces: gasketed doors &outdoor combustion air. Must complete envelope leakage report or visually verify Table 402.4.2. Thermostat& 403.1 At least one thermostat shall be provided for each separate heating controls and cooling system. Where forced-air furnace is primary system, programmable thermostat is required. Heat pumps with supplemental electric heat must prevent supplemental heat when compressor can meet the load. Ducts 403.2.2 All ducts, air handlers, filter boxes and building cavities which form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section 503.2.7.2 of this code. 403.3.3 Building framing cavities shall not be used as supply ducts. Water heaters 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly marked circuit breaker (electric) or shutoff(gas). Circulating system pipes insulated to = R-2 +accessible manual OFF switch. Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level. No make-up air from attics, crawlspaces, garages or outdoors adjacent to pools or spas. Swimming Pools 403.9 Pool pumps and pool pump motors with a total horsepower(HP)of= 1 &Spas HP shall have the capability of operating at two or more speeds. Spas and heated pools must have vapor-retardant covers or a liquid cover or other means proven to reduce heat loss except if 70%of heat from site-recovered energy. Off/timer switch required. Gas heaters minimum thermal efficiency=78% (82%after 4/16/13). Heat pump pool heaters minimum COP=4.0. Cooling/heating 403.6 Sizing calculation performed &attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification required. Special equipment occasion cooling or heating capacity requires separate system or variable capacity system. Electric heat>10kW must be divided into two or more stages. Ceilings/knee walls 405.2.1 R-19 space permitting. 1/20/2015 5:28 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 5 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 62 The lower the EnergyPerformance Index, the more efficient the home. 152 3rd Street, Atlantic Beach, FL, 32233- 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.0 450.00 ft= b. Frame-Wood,Adjacent R=13.0 198.00 ft 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d.N/A R= ft2 10.Ceiling Types Insulation Area 5. Is this a worst case? No a.Under Attic(Vented) R=30.0 308.00 ft2 6. Conditioned floor area(ft2) 308 b.N/A R= ft2 7. Windows" Description Area c. N/A R= ft2 2 a. U-Factor: Dbl,U=0.35 78.01 ft2 11.Ducts R ft SHGC: SHGC=0.35 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBlu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 12.0 SEER:13.00 SHGC: d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a. Electric Heat Pump 12.0 HSPF:7.70 Area Weighted Average Overhang Depth: 1.000 ft. Area Weighted Average SHGC: 0.350 8. Floor Types Insulation Area 14.Hot water systems 2 a.Natural Gas Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 308.00 ft EF:0.59 b.N/A R= ft2 c.N/A R= ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building SHE sT Construction through the above energy saving features which will be installed (or exceeded) ::';�..........; .....gT6o ; in this home before final inspection. Otherwise, a new EPL Display Card will be completed : <c3';; r `;.• `:: based on installed Code compliant f- •••..= ,,:.4,;,o Builder Signature: i` Date: �S o' ;1' _e_w :a eZG Address of New Home: /S'Z 3'e° .5.7`. City/ Zip: /57 ,�Z233 **-,...e4;............ --Y JgS '• .•••COD WE'.•••,:: *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software TABLE 402.4.2 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Hillis 152 3rd St Garage Suite Builder Name: Bosco Custom Homes Street: 152 3rd Street Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233- Permit Number: Owner: Jurisdiction: 261100 Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in substantial contact and continuous alignment with building envelope air barrier. Breaks or joints in the air barrier are filled or repaired. Air-permeable insulation is not used as a sealing material. Air-permeable insulation is inside of an air barrier. Ceiling/attic Air barrier in any dropped ceiling/soffit is substantially aligned with insulation and any gaps are sealed. Attic access (except unvented attic), knee wall door, or drop down stair is sealed. Walls Corners and headers are insulated. Junction of foundation and sill plate is sealed. Windows and doors Space between window/door jambs and framing is sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including Insulation is installed to maintain permanent contact with underside above-garage and of subfloor decking. cantilevered floors) Air barrier is installed at any exposed edge of insulation. Crawl space walls Insulation is permanently attached to walls. Exposed earth in unvented crawl spaces is covered with Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, knee walls and flue shafts opening to exterior or unconditioned space are sealed. Narrow cavities Batts in narrow cavities are cut to fit, or narrow cavities are filled by sprayed/blown insulation. Garage separation Air sealing is provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures are air tight, IC rated, and sealed to drywall. Exception—fixtures in conditioned space. Plumbing and wiring Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing, or sprayed/blown insulation extends behind piping and wiring. Shower/tub on exterior wall Showers and tubs on exterior walls have insulation and an air barrier separating them from the exterior wall. Electrical/phone box on Air barrier extends behind boxes or air sealed-type boxes are installed. Common wall Air barrier is installed in common wall between dwelling units. HVAC register boots HVAC register boots that penetrate building envelope are sealed to subfloor or drywall. Fireplace _ Fireplace walls include an air barrier. EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software