1588 OCEAN BLVD - ENERGY SHEETS FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 1588 Ocean Blvd Builder Name: Ossie Homes and Development
Street: 1588 Ocean Blvd Permit Office:
City,State,Zip: Atlantic Beach,FL,32233 Permit Number:
Owner: Jurisdiction: 261100
Design Location: FL,MAYPORT_NS
1. New construction or existing New(From Plans) 9. Wall Types(4217.1 sqft.) Insulation Area
a.Frame
2. Single family or multiple family Single-family Wood,Exterior R=19.0 1967.00 ft2
b. Frame-Wood,Exterior R=13.0 1849.30 ft2
3. Number of units,if multiple family 1 c.Frame-Wood,Adjacent R=13.0 400.75 ft2
4. Number of Bedrooms 5 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (2618.0 sqft.) Insulation Area
a.Under Attic(Vented) R=30.0 2618.00 ft2
6. Conditioned floor area above grade(ft2) 3894 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11.Ducts R ft2
7. Windows(517.0 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Garage 6 501.4
a. U-Factor Dbl,U=0.33 517.00 ft2 b.Sup. Attic,Ret:Attic,AH:Second Floor 6 277.4
SHGC: SHGC=0.23
b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 33.2 SEER:15.00
b.Central Unit 22.8 SEER:15.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a. Electric Heat Pump 33.0 HSPF:8.90
SHGC: b. Electric Heat Pump 22.0 HSPF:8.50
Area Weighted Average Overhang Depth: 3.461 ft.
Area Weighted Average SHGC: 0.230 14.Hot water systems
8. Floor Types (3894.0 sqft Insulation Area a.Natural Gas Tankless Cap:1 gallons.)
EF:0..800 0
a.Slab-On-Grade Edge Insulation R=0.0 2507.00 ft2 b. Conservation features
b.Floor Over Other Space R=0.0 1276.00 ft2 None
c.other(see details) R= 111.00 ft2 15.Credits Pstat
Glass/Floor Area: 0.133 Total Proposed Modified Loads: 85.99 PASS
Total Baseline Loads: 96.67
I hereby certify that the plans and specifications covered by Review of the plans and -'',T> $r.4�
this calculation are in corn.'. .- w' the Florida Energy specifications covered by this ,: 0 McOrp'•.,
Code. calculation indicates compliance of
with the Florida Energy Code. ;ti S ,,r
PREPARED BY: Before construction is completed
DATE: __ ZINErigrAr this building will be inspected for 0'
�t®
compliance with Section 553.908 \ . 47,-_,,, e ;`I hereby certify tha building,as designed,is in compliance Florida Statutes. %
with the Florida Energy Code. •oD WE
OWNER/AGENT: BUILDING OFFICIAL: in',r^ __
DATE: DATE: Q-. . (T''o7 LS_
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
r'"_ COPY
9/8/2015 11:31 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5
,
FORM R405-2014
PROJECT
Title: 1588 Ocean Blvd Bedrooms: 5 Address Type: Street Address
Building Type: User Conditioned Area: 3894 Lot#
Owner: Total Stories: 2 Block/SubDivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Ossie Homes and Developme Rotate Angle: 0 Street: 1588 Ocean Blvd
Permit Office: Cross Ventilation: County: Duval
Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach,
Family Type: Single-family FL, 32233
New/Existing: New(From Plans)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,MAYPORT_NS FL_MAYPORT_NS 2 39 90 70 75 1037 61 Medium
BLOCKS
Number Name Area Volume
1 Blockl 2507 26323.5
2 Block2 1387 13176.5
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms !nil!ID Finished Cooled Heated
1 First Floor 2507 26323.5 Yes 3 2 1 Yes Yes Yes
2 Second Floor 1387 13176.5 No 3 3 1 Yes Yes Yes
FLOORS
✓ # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio First Floor 182 ft 0 2507 ft2 ---- 1 0 0
2 Raised Floor Second Floor ____ ____ 111 ft2 19 1 0 0
3 Floor Over Other Space Second Floor ____ 1276 ft2 0 0 0 1
ROOF
/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Metal 2836 ft2 0 ft2 Medium 0.75 No 0.9 No 0 22.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 300 2618 ft2 N N
9/8/2015 11:31 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
ill
FORM R405-2014
CEILING
V # Ceiling Type Space R-Value Area Framing Frac Truss Type
1 Under Attic(Vented) First Floor 30 1231 ft2 0.11 Wood
2 Under Attic(Vented) Second Floor 30 1387 ft2 0.11 Wood
WALLS
/ Adjacent Cavity Width Height Sheathing Framing Solar Below
V # Ornt--- ----To Wail Type 5 R-Value Ft - In Ft In Area R-Value Fraction Absor. Grade%
1 E Exterior Frame-Wood First Floor 19 36.5 10 6 383.3 ft2 0.23 0.75 0
_ 2 N Exterior Frame-Wood First Floor 19 55 8 10 6 584.5 ft2 0.23 0.75 0
_ 3 W Exterior Frame-Wood First Floor 19 34 6 10 6 362.3 ft2 0.23 0.75 0
4 W Exterior Frame-Wood First Floor 19 7 10 10 6 82.3 ft2 0.23 0.75 0
5 W Exterior Frame-Wood First Floor 19 16 8 10 6 175.0 ft2 0.23 0.75 0
6 W Exterior Frame-Wood First Floor 19 36 2 10 6 379.8 ft2 0.23 0.75 0
7 E Garage Frame-Wood First Floor 13 22 6 10 6 236.3 ft2 0.23 0.75 0
8 S Garage Frame-Wood First Floor 13 15 8 10 6 164.5 ft2 0.23 0.75 0
9 E Exterior Frame-Wood Second Floor 13 53 8 9 6 509.8 ft2 0.23 0.75 0
10 N Exterior Frame-Wood Second Floor 13 43 8 9 6 414.8 ft2 0.23 0.75 0
11 W Exterior Frame-Wood Second Floor 13 53 8 9 6 509.8 ft2 0.23 0.75 0
12 S Exterior Frame-Wood Second Floor 13 43 8 9 6 414.8 ft2 0.23 0.75 0
DOORS
V # Omt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 E Wood First Floor None .46 6 8 48 ft2
2 E Wood First Floor None .46 2 8 8 21.3 ft2
WINDOWS
Orientation shown is the entered,Proposed orientation.
/ Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
. 1 E 1 Vinyl Low-E Double Yes 0.33 0.23 36.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
2 N 2 Vinyl Low-E Double Yes 0.33 0.23 36.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
3 N 2 Vinyl Low-E Double Yes 0.33 0.23 16.0 ft2 1 ft 6 in 3 ft 0 in Drapes/blinds Exterior 5
4 N 2 Vinyl Low-E Double Yes 0.33 0.23 12.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
5 W 3 Vinyl Low-E Double Yes 0.33 0.23 96.0 ft2 8 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5
6 W 3 Vinyl Low-E Double Yes 0.33 0.23 36.0 ft2 8 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5
7 W 4 Vinyl Low-E Double Yes 0.33 0.23 24.0 ft2 8 ft 0 in 2 ft 0 in Drapes/blinds Exterior 5
8 W 5 Vinyl Low-E Double Yes 0.33 0.23 36.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
9 E 9 Vinyl Low-E Double Yes 0.33 0.23 16.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds Exterior 5
10 E 9 Vinyl Low-E Double Yes 0.33 0.23 54.0 ft2 1 ft 6 in 0 ft 6 in Drapes/blinds Exterior 5
11 N 10 Vinyl Low-E Double Yes 0.33 0.23 10.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds Exterior 5
12 N 10 Vinyl Low-E Double Yes 0.33 0.23 36.0 ft2 1 ft 6 in 0 ft 6 in Drapes/blinds Exterior 5
13 W 11 Vinyl Low-E Double Yes 0.33 0.23 45.0 ft2 1 ft 6 in 0 ft 6 in Drapes/blinds Exterior 5
14 W 11 Vinyl Low-E Double Yes 0.33 0.23 24.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
15 S 12 Vinyl Low-E Double Yes 0.33 0.23 30.0 ft2 1 ft 6 in 2 ft 0 in Drapes/blinds Exterior 5
16 S 12 Vinyl Low-E Double Yes 0.33 0.23 10.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds Exterior 5
9/8/2015 11:31 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2014
GARAGE
# Floor Area __ Ceiling Area Exposed Wall Perimeter Avg.Wall Height _ Exposed Wall Insulation
1 475.072 ft' 384 ft2 43 ft 10.5 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EqLA ACH ACH 50
-
1 Wholehouse Proposed ACH(50) .000322 3291.7 180.71 339.85 .3055 5
HEATING SYSTEM
V # System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump Split HSPF:8.9 33 kBtu/hr 1 sysll
2 Electric Heat Pump Split HSPF:8.5 22 kBtu/hr 2 sys#2
COOLING SYSTEM
V it System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER:15 33.2 kBtu/hr 1250 cfm 0.85 1 sysll
2 Central Unit Split SEER:15 22.8 kBtuTr 850 cfm 0.85 2 sys#2
HOT WATER SYSTEM
V . # System Type SubType Location EF Cap Use SetPnt Conservation
1 Natural Gas Tankless Exterior 0.8 1 gal 80 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert U Company Name System Model# Collector Model# Area Volume FEF •
None None ft2
DUCTS
V Supply---- ---Return---- Air CFM 25 CFM25 HVAC#
;f Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool
1
Attic 6 501.4 ft Attic 125.4 ft Default Leakage Garage (Default) (Default) 1 1
2 Attic 6 277.4 ft Attic 69.4 ft2 Default Leakage Second Flo (Default) (Default) 2 2
9/8/2015 11:31 AM EnergyGauge®USA-FlaRes2014 Section R405.4 1 Compliant Software Page 4 of 5
FORM R405-2014
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
Coolin IXIJJ:ril Feb ( Mar (( A r Ma X Jun X Jul X Au X Se Oct Nov Dec Venting X}Feb [XI Mar lX]Apr May Jun Jul Aug Sep �XI Oct �XX Nov Deecc
Venting Jan [[ 1 Feb [X Mar l
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
9/8/2015 11:31 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
•
FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 89
The lower the EnergyPerformance Index,the more efficient the home.
1588 Ocean Blvd, Atlantic Beach, FL, 32233
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Frame Wood,Exterior R=19.0 1967.00 ft�
b.Frame-Wood,Exterior R=13.0 1849.30 ft
3. Number of units,if multiple family 1 c. Frame-Wood,Adjacent R=13.0 400.75 ft2
4. Number of Bedrooms 5 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types Insulation Area
a.Under Attic(Vented) R=30.0 2618.00 ft2
6. Conditioned floor area(ft2) 3894 b.N/A R= ft2
7. Windows" Description Area
C.N/A R= ft s
a. U-Factor Dbl,U=0.33 517.00 ft2 11.Ducts R ft
a.Sup:Attic,Ret:Attic,AH:Garage 6 501.4
SHGC: SHGC=0.23 b.Sup: Attic, Ret:Attic,AH:Second Floor 6 277.4
b. U-Factor: N/A ft2
SHGC: 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 33.2 SEER:15.00
SHGC: b.Central Unit 22.8 SEER:15.00
d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency
SHGC: a.Electric Heat Pump 33.0 HSPF:8.90
Area Weighted Average Overhang Depth: 3.461 ft. b.Electric Heat Pump 22.0 HSPF:8.50
Area Weighted Average SHGC: 0.230
8. Floor Types Insulation Area 14.Hot water systems
Cap:1 gallons
a.Slab-On-Grade Edge Insulation R=0.0 2507.00 ft2 a.Natural Gas p EF:0.8
b.Floor Over Other Space R4.0 1276.00 ft2
c.other(see details) R= 111.00 ft2 b. Conservation features
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building VEST .'
Construction through the above energy saving features which will be installed (or exceeded) 01 .......... ATE
in this home before final ins,_., io Otherwise, a new EPL Display Card will be completed y�i3 .-', ',., ` ,..
based on installed Code ►• •li features. //,? ;„1,/,',/t''‘, . -•r':••,3∎`.p�
. a '.-4.,, . �-..-.,..- 0
Builder Signature: €.--1 Date: Q 6;15, 1t) _c. a
Address of New Hoy /5a-S- 0e-- �i1/ 04A City/FL ip: L `' J
*Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient
mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation,contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
9/8/2015 11:32 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
•
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 1588 Ocean Blvd Builder Name: Ossie Homes and Development
Street: 1588 Ocean Blvd Permit Office:
City,State,Zip: Atlantic Beach,FL,32233 Permit Number:
Owner: Jurisdiction: 261100
Design Location: FL,MAYPORT_NS
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material. (/
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings,drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/door jambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier. ✓
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity ✓
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be l•/!
air tight, IC rated,and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls,or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
/17
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall. ✓✓✓
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
9/8/2015 11:32 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
? =."3,,,,,,,,,t,§
;1E4
: �`h
] !-k|
! !
na
)
S §i§
R `f�
-- ®/ § #&f
['''E. . ' / { ) J f !•
E : I - / \ \i 4t® I �� £ a
, . . _ o! ——, .. / / �] J}_
I ` Ea ;
} ) \ ( ' \k3\k
Li � : . b . f 2/§)
§ • . , . k � i . {\ 1 ){2
_ ■ , i | KIM F
� i 77
k
! k 9 _ . . . i .
k ! f i } } {
� _ : ��
a ,6 .
* ® ..... ...... !
];
�6E � �
--- -2
' &2
¥ � / \
.�
\ .-
f)g
! 9I I
2 `, ■ 3 /§ ■ 7
0 ft e/\ ) \ }\ik =
) f! ! /
!' !—
;
) ''=} !k
i
I
. ».4` .
1— 'k
o 2
b .._r•T
zo 7Ipi
— cITI-h
ito,*z
v„,.....
w
? g
g
'E
U
-I
--J 2 g
%
_____..j...-- ............... m V•cro
cn m 7 o
c 2n
- (..)
E= T.,
._. 0
s
2 ii.
- g -L ___-____
iiL x 0.
0 i
.
.....
t
2 R ■--... g E
, 2: .
.00..
',...! ..,
‘r e r--—1 I .. . . A.,
IS I i r" a
i 6-
ii 13 F. a
• E g"; 1 -, 0
1 - 1 t
m
ij a
,
o i d' i
o
1 , ette Op 1 a ,
o
,IIF
-IL , A .
E'
- o
2 ; z
____.u................p j
E A 2 i
tn ., 9 2:1.1 .9111
i?.SM.i. 4' Le 08 3 n 5
ELO E§
,•■ 4-
ic
•
Manual S Compliance Report Job: 1588 Ocean Blvd
Date: 09107!2015
1st Floor System By: David C Brown
"2f 'f ConsultAir, LLC
Atlantic Beach,Fl 32233 Phone (904)402-1463 Fax (904)800-1222 Web www.LoadCalculations.corn
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Cooling Equipment
Design Conditions
Outdoor design DB: 92.1°F Sensible gain: 27843 Btuh Entering coil DB: 77.5°F
Outdoor design WB: 77.6°F Latent gain: 4591 Btuh Entering coil WB: 63.7°F
Indoor design DB: 75.0°F Total gain: 32434 Btuh
Indoor RH: 50% Estimated airflow: 1250 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Amana Model: ASZ140361B*+AVPTC313714A*
Actual airflow: 1250 cfm
Sensible capacity: 28529 Btuh 102% of load
Latent capacity: 4636 Btuh 101% of load
Total capacity: 33165 Btuh 102% of load SHR: 86%
Heating Equipment
Design Conditions
Outdoor design DB: 38.6°F Heat loss: 27996 Btuh Entering coil DB: 69.0°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Amana Model: ASZ140361B*+AVPTC313714A*
Actual airflow: 1250 cfm
Output capacity: 34800 Btuh 124% of load Capacity balance: 35 °F
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 1250 cfm
Output capacity: 8.0 kW 97%of load Temp. rise: 50 °F
The above equipment was selected in accordance with ACCA Manual S.
wri htsoft' 2015-Sep-08 1142 43
^_ 9 Right-Suite®Universal 2015 15 RSU15431 Page 1
CK Development 1588 Ocean Blvd\1588 Ocean Blvd rup Calc=MJ8 Front Door(aces. E
•
Manual S Compliance Report Job: 1588 Ocean Blvd
Date: 09/0712015
2nd Floor System By: David C Brown
VP:del viat'�"` ConsultAir, LLC
Atlantic Beach,FI 32233 Phone(904)402-1463 Fax (904)800-1222 Web:www LoadCalculations com
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Cooling Equipment
Design Conditions
Outdoor design DB: 92.1°F Sensible gain: 19087 Btuh Entering coil DB: 77.2°F
Outdoor design WB: 77.6°F Latent gain: 3290 Btuh Entering coil WB: 63.6°F
Indoor design DB: 75.0°F Total gain: 22376 Btuh
Indoor RH: 50% Estimated airflow: 850 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Amana Model: ASZ140241A*+AVPTC313714A°
Actual airflow: 850 cfm
Sensible capacity: 19022 Btuh 100% of load
Latent capacity: 3743 Btuh 114% of load
Total capacity: 22765 Btuh 102% of load SHR: 84%
Heating Equipment
Design Conditions
Outdoor design DB: 38.6°F Heat loss: 15611 Btuh Entering coil DB: 69.2°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Amana Model: ASZ140241A`+AVPTC313714A*
Actual airflow: 850 cfm
Output capacity: 24000 Btuh 154% of load Capacity balance: 31 °F
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 850 cfm
Output capacity: 4.6 kW 100%of load Temp. rise: 50 °F
The above equipment was selected in accordance with ACCA Manual S.
Wrl htsoft' 2015-Sep-08114243
�_ 9 Right-SuiteV Universal 2015 15.0.19 RSU15431 Page 2
ACC Development\1588 Ocean Blvd\1588 Ocean Blvd.rup Calc=MJ8 Front Door faces. E
Project Summary Job: 0587/2015 Blvd
J Summary Date: 0910712015
geaver Entire House By: David C Brown
ConsultAir, LLC
Atlantic Beach,Fl 32233 Phone (904)402-1463 Fax (904)800-1222 Web.www LoadCalculations.com
Pro.ect Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Notes:
Desi. n Information
Weather: Mayport Ns, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 °F Outside db 92 °F
Inside db 70 °F Inside db 75 °F
Design TD 31 °F Design TD 17 °F
Daily range L
Relative humidity 50 %
Moisture difference 55 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 32075 Btuh Structure 30280 Btuh
Ducts 11531 Btuh Ducts 16352 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 43607 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 46632 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 4700 Btuh
Ducts 3180 Btuh
Heating Cooling Central vent (0 cfm) 0 Btuh
Area(ft2) 3946 3946 Equipment latent load 7880 Btuh
Volume(ft') 42927 42927
Air changes/hour 0.25 0.13 Equipment total load 54512 Btuh
Equiv.AVF (cfm) 179 93 Req. total capacity at 0.70 SHR 5.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make n/a Make n/a
Trade n/a Trade n/a
Model n/a Cond n/a
AHRI ref n/a Coil n/a
AHRI ref n/a
Efficiency n/a Efficiency n/a
Heating input Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 0 cfm Actual air flow 0 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
d Space thermostat n/a Load sensible heat ratio 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
4 +++ wrightsoft` Right-Suite®Universal 2015 15.0 19 RSU15431 2015-Sep-08 11 43e 1
ACC
Developrnent\1588 Ocean Blvd\1588 Ocean Blvd rup Calc=MJ8 Front Door faces E
4
Building Analysis Job: 1588 Ocean Blvd
Date: 09/07/2015
Entire House By: David C Brown
ConsultAir, LLC
Atlantic Beach.Fl 32233 Phone. (904)402-1463 Fax. (904)800-1222 Web.www.LoadCalculations.corn
Pro'ect Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32773
Desi• n Conditions
Location: Indoor: Heating Cooling
Mayport Ns, FL, US Indoor temperature(°F) 70 75
Elevation: 13 ft Design TD (°F) 31 17
Latitude: 30°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 27.2 55.4
Dry bulb(°F) 39 92 Infiltration:
Daily range(°F) - 15 ( L ) Method Simplified
Wet bulb(°F) - 78 Construction quality Semi-tight
Wind speed(mph) 15.0 7.5 Fireplaces 0
Heatin.
Component Btuh/ft2 Btuh %of load
Walls 2.6 10010 23.0
Glazing 10.4 5654 13.0 "'
Doors 12.2 482 1.1
Ceilings 1.0 2596 6.0
Floors 2.8 7159 16.4
Infiltration 1.5 6175 14.2
Ducts 11531 26.4
Piping 0 0 ....,.
Humidification 0 0 -
Ventilation 0 0
Adjustments 0
Total 43607 100.0
Coolin•
Component Btuh/ft2 Btuh % of load
Walls 1.9 7387 15.8 ..w,
Glazing 19.9 10843 23.3
Doors 12.1 477 1.0
Ceilings 1.7 4514 9.7
Floors 0.0 81 0.2
Infiltration 0.4 1749 3.7
Ducts 16352 35.1
Ventilation 0 0 0..
Internal gains 5230 11.2
Blower 0 0 k<i" .L
Adjustments 0 ---
Total 46632 100.0
Latent Cooling Load= 7880 Btuh
Overall U-value= 0.086 Btuh/ft2-°F
Data entries checked.
'414- wrightsoft 2015-Sep-08 1143 25
Right-Suite®Universal 2015 15.0.19 RSU15431 Page 1
'CCK Develooment11588 Ocean Blvd 11588 Ocean Blvd rup Calc=MJ8 Front Door faces E
AED Assessment Job: 1588 Ocean Blvd
Date: 09/07/2015
Entire House By: David C Brown
ConsultAir, LLC
Atlantic Beach,F]32233 Phone (904)402-1463 Fax (9041 800-1222 Web www.LoadCalculahons.corn
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Design Conditions
Location: Indoor: Heating Cooling
Mayport Ns, FL, US Indoor temperature(°F) 70 75
Elevation: 13 ft Design TD (°F) 31 17
Latitude: 30°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 27.2 55.4
Dry bulb(°F) 39 92 Infiltration:
Daily range(OF) - 15 ( L )
Wet bulb(°F) - 78
Wind speed (mph) 15.0 7.5
Test for Adequate Exposure Diversity
Hourly Glazing Load
1B,
14,
12,000 -
I10,810
__
8,n1
6,1,1
4,s,,
2,000
0 I . _
8 9 10 11 12 13 14 15 16 17 18 19 20
Flour of Day
Harry amaps
Maximum hourly glazing load exceeds average by 51.9%.
House does not have adequate exposure diversity(AED), based on AED limit of 30%.
AED excursion: 2019 Btuh (PFG - 1.3*AFG)
L Wri htso `" 2015 Sep 08 11 43 25
9 Right-Bute®Universal 2015 15.0.19 RSU15431 Page 1
...Develepment11588 Ocean Blvd11588 Ocean Blvd rup Cale=MJ8 Front Door faces: E
Load Short Form Job: 1588 Ocean Blvd
Date: 09/07/2015
gt511943 Entire House By: David C Brown
ConsultAir, LLC
Atlantic Beach.Ft 32233 Phone.(904)402-1463 Fax.(904)800-1222 Web.www.LoadCalculations.corn
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Design Information
Htg Clg Infiltration
Outside db(°F) 39 92 Method Simplified
Inside db(°F) 70 75 Construction quality Semi-tight
Design TD (°F) 31 17 Fireplaces 0
Daily range - L
Inside humidity (%) 50 50
Moisture difference(gr/lb) 27 55
HEATING EQUIPMENT COOLING EQUIPMENT
Make n/a Make n/a
Trade n/a Trade n/a
Model n/a Cond n/a
AHRI ref n/a Coil n/a
AHRI ref n/a
Efficiency n/a Efficiency n/a
Heating input Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 0 cfm Actual air flow 0 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat n/a Load sensible heat ratio 0
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft') (Btuh) (Btuh) (cfm) (cfm)
1st Floor System d 2473 27996 27843 1250 1250
2nd Floor System d 1473 15611 19087 850 850
Entire House d 3946 43607 46632 2100 2100
Other equip loads 0 0
Equip. @ 1.00 RSM 46632
Latent cooling 7880
TOTALS 3946 43607 54512 2100 2100
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
L. 2015-Sep-081143.25
�= wrightsosa-1 l Right-Suite®Universal 2015 15 0 19 RSU15431
Page 1
Developmenl11588 Ocean Blvd\1588 Ocean Blvd rup Calc=MJ8 Front Door faces. E
Component Constructions Job: 158 Blvd
Date: 09/07/2017/201 5
ASUAR Entire House By: David C Brown
''"'' ;:h•^,-,'.,; ConsultAir, LLC
Atlantic Beach,FI 32233 Phone(904)402-1463 Fax:(904)800-1222 Web:www.LoadCalculations.corn
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Design Conditions
Location: Indoor: Heating Cooling
Mayport Ns, FL, US Indoor temperature(°F) 70 75
Elevation: 13 ft Design TD (°F) 31 17
Latitude: 30°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 27.2 55.4
Dry bulb(°F) 39 92 Infiltration:
Daily range(°F) - 15 ( L ) Method Simplified
Wet bulb(°F) - 78 Construction quality Semi-tight
Wind speed(mph) 15.0 7.5 Fireplaces 0
i
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuh/IY-°F B'-°F/Btuh BRA/I!' Ruh BtuM' Stub
Walls
12E-Osw:Frm wall,stucco ext,3/8"wood shth,r-19 cav ins, 1/2" n 590 0.068 19.0 2.14 1260 1.50 883
gypsum board int fish,2"x6"wood frm,16"o.c.stud e 355 0.068 19.0 2.14 757 1.50 530
s 462 0.068 19.0 2.14 986 1.50 691
w 518 0.068 19.0 2.14 1106 1.50 775
all 1925 0.068 19.0 2.14 4109 1.50 2879
Frm wall,Hardie ext,r-13 cav ins, 1/2"gypsum board int fnsh,2"x4" n 346 0.097 13.0 3.05 1055 2.54 877
wood frm,16"o.c.stud:Frm wall,Hardie ext,r-13 cav ins, 1/2" e 411 0.097 13.0 3.05 1256 2.54 1044 •
gypsum board int fish,2"x4"wood frm, 16"o.c.stud s 352 0.097 13.0 3.05 1073 2.54 892
w 412 0.097 13.0 3.05 1257 2.54 1045
all 1520 0.097 13.0 3.05 4642 2.54 3858
Partitions
12C-Osw:Frm wall, 1/2"wood shth,r-13 cav ins,1/2"gypsum board 387 0.091 13.0 2.86 1105 1.47 570
int fnsh,2"x4"wood frm,16"o.c.stud
12C-Osw:Frm wall,stucco ext,r-13 cav ins,2"x4"wood frm,16"o.c. 54 0.091 13.0 2.86 154 1.47 80
stud
Windows
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; n 16 0.330 0 10.4 166 8.37 134
50%outdoor insect screen;1.5 ft overhang(4 ft window ht,3 ft sep.);
6.67 ft head ht
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; n 12 0.330 0 10.4 124 8.37 100
50%outdoor insect screen; 1.5 ft overhang(6 ft window ht,2 ft sep.); n 36 0.330 0 10.4 373 8.37 301
6.67 ft head ht e 18 0.330 0 10.4 181 22.0 385
e 18 0.330 0 10.4 187 22.0 396
w 35 0.330 0 10.4 363 22.0 770
all 119 0.330 0 10.4 1228 16.5 1953
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; n 10 0.330 0 10.4 104 8.37 84
50%outdoor insect screen; 1.5 ft overhang(5 ft window ht,1 ft sep.); s 10 0.330 0 10.4 104 8.37 84
6.67 ft head ht all 20 0.330 0 10.4 207 8.37 167
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; n 36 0.330 0 10.4 373 8.37 301
50%outdoor insect screen;1.5 ft overhang(6 ft window ht,0.5 ft sep.); e 54 0.330 0 10.4 560 20.3 1097
6.67 ft head ht all 90 0.330 0 10.4 933 15.5 1398
1 wr htsofC 2015-Sep-08 11:43:25
�• Right-Suite®Universal 2015 15.0.19 RSU15431
..Development11588 Ocean Btvd11588 Ocean Blvd.rup Cak=MJ8 Front Door faces: E Pape 1
U-value.33 SHGC.23:U-value.33 SHGC.23;5 ft overhang(5 ft e 30 0.330 0 10.4 311 20.3 608
window ht,2 ft sep.);6.67 ft head ht
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; e 8 0.330 0 10.4 83 21.2 169
50%outdoor insect screen;1.5 ft overhang(4 ft window ht,1 ft sep.); e 8 0.330 0 10.4 86 21.2 176
6.67 ft head ht all 16 0.330 0 10.4 169 21.2 346
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; s 30 0.330 0 10.4 311 8.37 251
50%outdoor insect screen;1.5 ft overhang(5 ft window ht,2 ft sep.);
6.67 ft head ht
U-value.33 SHGC.23:U-value.33 SHGC.23;8 ft overhang(8 ft w 24 0.330 0 10.4 249 17.7 424
window ht,2 ft sep.);6.67 ft head ht w 96 0.330 0 10.4 995 17.7 1697
all 120 0.330 0 10.4 1243 17.7 2121
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; w 35 0.330 0 10.4 363 11.5 401
50%outdoor insect screen;8 ft overhang(6 ft window ht,2 ft sep.);
6.67 ft head ht
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; w 24 0.330 0 10.4 249 22.0 528
50%outdoor insect screen;1.5 ft overhang(3 ft window ht,2 ft sep.);
6.67 ft head ht
U-value.33 SHGC.23:U-value.33 SHGC.23;40%blinds 45°,light; w 15 0.330 0 10.4 155 20.0 300
50%outdoor insect screen;1.5 ft overhang(5 ft window ht,0.5 ft sep.); w 31 0.330 0 10.4 319 20.0 616
6.67 ft head ht all 46 0.330 0 10.4 475 20.0 916
Doors
11DO:Door,wd sc type e 18 0.390 0 12.2 220 12.1 218
n 21 0.390 0 12.2 261 12.1 259
all 39 0.390 0 12.2 482 12.1 477
Ceilings
16B-30md:Attic ceiling,mtl roof mat,r-30 ceil ins,1/2"gypsum board 2584 0.032 30.0 1.00 2596 1.75 4514
int fish
Floors
20P-19t:Fir floor,frm flr,17'thkns,tile fir fish,r-19 cav ins,amb ovr 111 0.050 19.0 1.57 174 0.73 81
22A-tpm:Bg floor,heavy dry or light damp soil,on grade depth,tile flr 189 1.180 0 37.1 6984 0 0
fnsh
Al..- wr htsoft- 2015-Sep-0811.43:25
�, Right-Suite®universal 2015 15.0.19 Rsu15431 Page 2
..Development\1588 Ocean Btvd\1588 Ocean Blvd.rup Calc=MJ8 Front Door faces: E
Load Multizone Summary Report Job: 1588 Ocean Blvd
Date: 09/07/2015
"■l-r' By: David C Brown
ConsultAir, LLC
Atlantic Beach,FI 32233 Phone:(904)402-1463 Fax:(904)800-1222 Web:www.LoadCalculations.com
i
Infiltration Summary
Heating Cooling
ZONENAME Volume ACH AVF HTM Volume ACH AVF HTM
W cfm Btuh/ft2 ft cfm Btuh/ft2
1st Floor System 29670 0.20 101 1 .5 29670 0. 11 52 0.4
2nd Floor System 13257 0. 35 78 1 .5 13257 0. 18 41 0.4
Entire House 42927 0.25 179 1 . 5 42927 0. 13 93 0. 4
Load and AVF Summary
ROOM NAME Arca Htg load Clg load HtgAVF CIgAVF
IV Btuh Btuh cfm cfm
Mstr WIC 126 2857 1200 128 54
Linen 9 0 0 0 0
Mstr Bth 155 2245 1052 100 47
Mstr Bdrm 324 2742 4626 122 208
Mstr H2O 26 0 0 0 0
I. Mud Rm 49 571 517 25 23
I Clst 21 667 314 30 14
Foyer 259 2522 1863 113 84
Office 196 4569 3529 204 158
Bth 1 56 88 117 4 5
Office Clst 23 0 0 0 0
Pantry 45 742 358 33 16
Family Rm 248 3252 5076 145 228
Dining Rm 264 5045 5148 225 231
Kit Clst 6 0 0 0 0
Family Kitchen 666 2696 4043 120 182
1st Floor System 2473 27996 27843 1250 1250
Bdrm 3 189 2493 2671 136 119
Clst 3 30 0 0 0 0
Bdrm 2 189 1447 2559 79 114
Clst 2 20 0 0 0 0
H2O 2 19 400 506 22 23
Bth 2 93 588 739 32 33
Laundry 77 107 873 6 39
Bdrm 1 216 2793 2924 152 130
WIC 1 40 877 836 48 37
Chase 2 0 0 0 0
1 Bth 3 51 982 931 53 41
Loft 534 5924 7049 323 314
13 0 0 0 0
2nd Floor System 1473 15611 19087 850 850
Entire House 3946 43607 46632 2100 2100
.� wri htsoft 2015-Sep-081143:25
9 Right-Suite®Universal 2015 15.0.19 RSU15431 Page 1
ACCA Development 11588 Ocean BIvd11588 Ocean Blvd.rup Calc=MJ8 Front Door faces: E
r 6'5U1,413
Duct System Summary
1st Floor System
ConsultAir, LLC Job: 1588 Ocean Blvd
Y 7 Date: 09/07/2015
By: David C Brown
Atlantic Beach,FI 32233 Phone.(904)402-1463 Fax (904)800-1222 Web www.LoadCalculations corn
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Heating Cooling
External static pressure 0.55 in H2O 0.55 in H2O
Pressure losses 0.09 in H2O 0.09 in H2O
Available static pressure 0.46 in H2O 0.46 in H2O
Supply/return available pressure 0.213/0.247 in H2O 0.213/0.247 in H2O
Lowest friction rate 0.097 in/100ft 0.097 in/100ft
Actual air flow 1250 cfm 1250 cfm
Total effective length (TEL) 477 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk
Bth 1 c 117 4 5 0.133 4.0 Ox 0 VIFx 55.9 105.0 st2
clst h 667 30 14 0.140 4.0 Ox 0 VIFx 26.9 125.0 st3
Dining Rm c 2574 113 116 0.103 8.0 Ox 0 VIFx 78.0 130.0 st4
Dining Rm-A c 2574 113 116 0.101 8.0 Ox 0 VIFx 80.7 130.0 st4
Family Kitchen-A c 2022 60 91 0.097 7.0 Ox 0 VIFx 89.0 130.0 st4
Family Kitchen-B c 2022 60 91 0.097 7.0 Ox 0 VIFx 91.0 130.0 st4
Family Rm c 2538 73 114 0.113 8.0 Ox 0 VIFx 68.3 120.0 st4
Family Rm-A c 2538 73 114 0.105 8.0 Ox 0 VIFx 72.9 130.0 st4
Foyer h 2522 113 84 0.129 7.0 Ox 0 VIFx 34.9 130.0 st3
Mstr Bdrm c 2313 61 104 0.144 7.0 Ox 0 VIFx 32.9 115.0 st1
Msir Bdrm-A c 2313 61 104 0.135 7.0 Ox 0 VIFx 43.2 115.0 st1
Mstr Blh h 2245 100 47 0.179 6.0 Ox 0 VIFx 9.5 110.0
Mslr H2O c 0 0 0 0.215 0 Ox 0 VIFx 19.0 80.0
MstrWlc h 2857 128 54 0.150 7.0 Ox0 VIFx 27.0 115.0 st1
Mud Rm h 571 25 23 0.244 4.0 Ox 0 VIFx 12.5 75.0
Office h 2284 102 79 0.108 7.0 Ox 0 VIFx 57.8 140.0 st3
Office-A h 2284 102 79 0.127 7.0 Ox 0 VIFx 58.5 110.0 st2
Pantry h 742 33 16 0.127 5.0 Ox 0 VIFx 57.5 110.0 st2
� wrightsoft
2015-Sep-08 11 age 1
.
9 Right-Suited Universal 2015 15 0 19 RSU15431 Page 1
/CC .Development\1588 Ocean Blvd\1588 Ocean Blvd rup Calc=MJ8 Front Door faces E
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st2 Peak AVF 139 101 0.127 398 8.0 0 x 0 VinIFIx
st3 Peak AVF 244 177 0.108 448 10.0 0 x 0 VinIFIx
st4 Peak AVF 491 641 0.097 599 14.0 0 x 0 VinIFIx
st1 Peak AVF 250 262 0.135 480 10.0 0 x 0 VinIFIx
Return Branch Detail Table
Grill Htg Clg TEL Design ' Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rsbl Ox0 204 158 180.6 0.137 584 8.0 Ox 0 VIFx rt1
rb4 Ox0 696 783 255.6 0.097 561 16.0 Ox 0 VIFx rt3
rb3 Ox0 350 309 234.2 0.105 446 12.0 Ox 0 VIFx rt3
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
rt1 Peak AVF 1250 1250 0.097 707 18.0 0 x 0 ViniFlx
rt3 Peak AVF 1046 1092 0.097 618 18.0 0 x 0 VinIFIx rt1
4
i+ wri htsoft' 2015-Sep-08 11 43 52
+
g Right-Suited Universal 2015 15 0 19 RSU15431 pie 2
1CCN Developmentt1588 Ocean BIvd11588 Ocean Blvd rup Calc=MJB Front Door faces E
Duct System Summary Job: 1587/2015 Blvd
Y Summary Date: 09/0712015
ertsuljr 2nd Floor System By: David C Brown
ConsultAir, LLC
Atlantic Beach.Fl 32233 Phone:(904)402-1463 Fax:(904)800-1222 Web:www.LoadCalculations.com
Project Information
For: OSSI Homes and Development
1588 Ocean Blvd,Atlantic Beach, FL 32223
Heating Cooling
External static pressure 0.55 in H2O 0.55 in H2O
Pressure losses 0.09 in H2O 0.09 in H2O
Available static pressure 0.46 in H2O 0.46 in H2O
Supply /return available pressure 0.237/0.223 in H2O 0.237/0.223 in H2O
Lowest friction rate 0.135 in/100ft 0.135 in/100ft
Actual air flow 850 cfm 850 cfm
Total effective length(TEL) 341 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln(ft) Trunk
Bdrm 1 h 2793 152 130 0.144 8.0 Ox 0 VIFx 34.7 130.0 st5
Bdrm 2 c 2559 79 114 0.288 6.0 Ox 0 VIFx 7.3 75.0
Bdrm 3 h 2493 136 119 0.287 7.0 Ox 0 VIFx 7.6 75.0
Bth 2 c 739 32 33 0.156 5.0 Ox 0 VIFx 22.5 130.0 st5
Bth 3 h 982 53 41 0.288 5.0 Ox 0 VIFx 7.5 75.0
H2O 2 c 506 22 23 0.164 4.0 Ox 0 VIFx 24.6 120.0 st5
Laundry c 873 6 39 0.153 5.0 Ox0 VIFx 25.3 130.0 st5
Loft h 1975 108 105 0.135 7.0 Ox0 VIFx 30.8 145.0 st6
Loft-A h 1975 108 105 0.142 7.0 Ox 0 VIFx 26.9 140.0 st6
Loft-B h 1975 108 105 0.141 7.0 Ox0 VIFx 28.9 140.0 st6
WIC 1 h 877 48 37 0.143 5.0 Ox 0 VIFx 36.0 130.0 st5
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st6 Peak AVF 323 314 0.135 591 10.0 0 x 0 VinIFIx
st5 Peak AVF 259 262 0.143 592 9.0 0 x 0 VinIFIx I
.` -}if wrightsoft 2o1s Sep os 11 ag s3
f' 7 Right-Suite®Universal 2015 15 Q19 RSU 15431 Faye 3
ACCA Development\1588 Ocean Blvd\1588 Ocean Blvd rup Calc=MJ8 Front Door faces: E
Return Branch Detail Table
Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox 0 133 169 148.9 0.149 485 8.0 Ox 0 VIFx rt2
rb10 Ox 0 200 167 164.8 0.135 452 9.0 Ox 0 VIFx rt2
rb8 Ox 0 328 353 136.9 0.163 647 10.0 Ox 0 VIFx rt2
rb9 Ox 0 189 160 135.2 0.165 542 8.0 Ox 0 VIFx rt2
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
rt2 Peak AVF 850 850 0.135 609 16.0 0 x 0 ViniFlx
4
4
4 2015-Sep-08 11 43 52
. wrightsot Right-Suite®Universal 2015 15.0.19 RSU15431 Page 4
ACC Development11588 Ocean Blvd\1588 Ocean Blvd.rup Calc=MJ8 Front Door faces. E