Loading...
384 1st ST - ENERGY SHEETS E^S ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-1655 OFFICE COPY Reissued April 2014 This report is subject to renewal April 1, 2016. 1 (800)423-6587 I (562)699-0543 A Subsidiary of the International Code Council® DIVISION:07 00 00—THERMAL AND MOISTURE roofs. The foam plastic insulation is a two-component, PROTECTION open-cell, one-to-one by volume spray foam system with a Section:07 21 00—Thermal Insulation nominal density of 0.5 pcf (8 kg/m3). The insulation is produced in the field by combining a polymeric REPORT HOLDER: isocyanate (A component) with a polymeric resin blend BAYER MATERIALSCIENCE LLC (B component). The insulation components have a shelf BAY BAY ROAD life of six months when stored at temperatures between 2400 SPRING STUBNER SPRING,TEXAS 77389 65°F(18°C)and 85°F(29°C)before installation. (800)221-3626 3.2 Surface-burning Characteristics: The insulation, at a maximum thickness of 4 inches (102 mm)and a nominal density of 0.5 pcf(8 kg/m3), has a EVALUATION SUBJECT: flame spread index of less than 25 and a smoke-developed BAYSEALTM OC SPRAY-APPLIED POLYURETHANE index of less than 450 when tested in accordance with INSULATION ASTM E84. Thicknesses up to 12 inches (305 mm)for wall cavities and 16 inches (406 mm) for ceiling cavities are 1.0 EVALUATION SCOPE recognized based on room corner fire testing in Compliance with the following codes: accordance with NFPA 286, when covered with minimum /2-inch-thick (13 mm) gypsum board or an equivalent • 2012 and 2009 International Building Code®(IBC) thermal barrier complying with and installed in accordance • 2012 and 2009 International Residential Code®(IRC) with the applicable code. in 2012 and 2009 International Energy Conservation 3.3 Thermal Resistance(R-values): Code®(IECC) The insulation has thermal resistance(R-value), at a mean • Other Codes(see Section 8.0) temperature of 75°F(24°C),as shown in Table 1. Properties evaluated: 3.4 BaysealT" IC Coating: • Surface-burning characteristics BaysealTM IC intumescent coating is manufactured by ■ Physical properties Bayer MaterialScience and is a water-based latex coating with a specific gravity of 1.31. BaysealTM IC is supplied in • Thermal resistance 5-gallon (19 L) pails and 55-gallon (208 L) drums and has • Attic and crawl space applications a shelf life of 12 months when stored in a factory-sealed • Fire-resistance-rated construction container at temperatures between 50°F (10°C) and 100°F (38°C). ■ Exterior walls in Types I through IV construction 3.5 Paint to Protect®DC315 Fireproof Paint: • Air permeability Paint to Protect® DC 315 Fireproof Paint is manufactured 2.0 USES by International Fireproof Technology, Inc., and is a water- The BaysealT"" OC insulation is used as a nonstructural based coating supplied in 5-gallon (19 L) pails and thermal insulating material in Type I, II, Ill, IV and V 55-gallon (208 L) drums. The coating material has a shelf construction (IBC) and dwellings under the IRC. See life of 24 months when stored in factory-sealed containers Section 4.5 for use in Type I, II, Ill and IV construction.The at temperatures between 50°F(10°C)and 90°F(32°C). insulation is for use in wall cavities, floor assemblies, 3.6 TPR2 Fireshell®BMS-TC Intumescent Coating: ceiling assemblies or attics and crawl spaces when TPR 2 one- installed in accordance with Section 4.3. The insulation TPR Fireshell BMS-TC Intumescent Coating is a one may be used in wall assemblies in fire-resistive-rated component, water-based polymer coating. The coating is construction as described in Sections 3.8 and 4.4. supplied in 5-gallon (19 L) pails and 55-gallon (208 L) drums and has a shelf life of one year when stored in a 3.0 DESCRIPTION factory-sealed container at temperatures of 50°F (10°C) or 3.1 General: above. BaysealTM OC is a spray-applied cellular polyurethane 3.7 TPR2 Fireshell®BMS-IC Intumescent Coating: foam plastic insulation that is installed in stud wall TPR2 Fireshell® BMS-IC Intumescent Coating is a one- assemblies, ceilings, floors, crawlspaces and cavities of component, water-based polymer coating. The coating is ICC-ES Evaluation Reports are not to be construed a.%representing aesthetics or any other attributes not specifically addressed,nor are they to be construed 4:g�" as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as -�-S to any finding or other matter in this report,or as to any product covered by the report. Copyright 0 2014 Page 1 of 4 ESR-1655 ; Most Widely Accepted and Trusted Page 2 of 5 supplied in 5-gallon (19 L) pails and 55-gallon (208 L) 22 wet mils (0.56 mm) [14 dry mils(0.36 mm)], at a rate of drums and has a shelf life of one year when stored in a 1.37 gallons (5.2L) per 100 square feet (9.2 m2). The factory-sealed container at temperatures of 50°F (10°C) or coating must be applied over the BaysealTM OC insulation above. in accordance with the coating manufacturer's instructions 3.8 Fire-resistance-rated Construction: and this report. Surfaces to be coated must be dry, clean and free of dirt, loose debris and other substances that Bayseallm OC spray-applied foam insulation is recognized could interfere with adhesion of the coating. The coating is for use in a limited load-bearing, one-hour, fire-resistance- applied in one coat by airless spray equipment at ambient rated wall assembly when installed as described in temperatures above 50°F (10°C) and relative humidity of Section 4.4. less than 70 percent. 3.9 Air Permeability: 4.2.2.2 Application with TPR2 Fireshell® BMS-TC BaysealTM OC spray-applied polyurethane insulation, at a Intumescent Coating: The prescriptive 15-minute thermal minimum thickness of 3.5 inches (89 mm), is considered barrier may be omitted when installation is in accordance air-impermeable insulation in accordance with Sections with this section. The insulation and coating may be used R806 and R202 of the IRC based on testing in accordance in lieu of the code-prescribed 15-minute thermal barrier. with ASTM E283. The foam plastic insulation thickness must not exceed 71/2 inches(191 mm) in walls and 91/2 inches (241 mm) in 4.0 INSTALLATION ceilings, and the insulation must be covered with 20 wet 4.1 General: mils (0.5 mm) [12 dry mils (0.30 mm)] of TPR2 Fireshell® BaysealTM OC insulation must be installed in accordance BMS-TC intumescent coating applied in a single coat a2a with the manufacturer's published installation instructions rate of 1.25 gallons (4.75L) per 100 square feet (9.2 m2). and this report.A copy of the instructions must be available Surfaces to be coated must be dry, clean and free of dirt, at all times on the jobsite during installation. loose debris and other substances that could interfere with adhesion of the coating. The coating is applied in one coat The substrates to which the insulation is applied must be by airless spray equipment, medium knap roller or brush at clean, dry and free of frost, ice, loose debris, or ambient temperatures above 62°F and 95°F (16°C and contaminates that will interfere with adhesion of the spray 35°C)and relative humidity of less than 70 percent. foam insulation. 4.3 Attics and Crawl Spaces: The insulation must be protected from the weather during 4.3.1 Application with a Prescriptive Ignition Barrier: and after application. The insulation must not be applied in electrical boxes. When Bayseal TM OC insulation is installed within attics or crawl spaces where entry is made only for service of The insulation is applied in passes having a maximum utilities, an ignition barrier must be installed in accordance thickness of 6 inches (152 mm) per pass. Multiple passes with IBC Section 2603.4.1.6 and IRC Sections R316.5.3 are made to obtain the desired thickness, which is not to and R316.5.4, as applicable. The ignition barrier must be exceed 12 inches(305 mm)for wall cavities and 16 inches consistent with the requirements for the type of (406 mm) for ceiling cavities. The insulation must not be construction required by the applicable code, and must be used in areas that have a maximum service temperature installed in a manner so that the foam plastic insulation is greater than 180°F (82°C). The foam plastic insulation not exposed. BaysealTM OC insulation, as described in this must not be used in electrical outlet or junction boxes or in section, may be installed in unvented attics in accordance contact with rain, water or soil. The substrate must be free with IRC Section R806. The attic or crawl space area must of moisture, frost or ice, loose scales, rust, oil and grease. be separated from the interior of the building by an 4.2 Thermal Barrier: approved 15-minute thermal barrier as described in Section 4.2.1. 4.2.1 Application with a Prescriptive Thermal Barrier: The BaysealTM OC insulation, with a maximum nominal 4.3.2 Application without a Prescriptive Ignition thickness of 12 inches (305 mm) for wall cavities and Barrier: Where the spray-applied insulation is installed in 16 inches(406 mm)for ceiling cavities, must be separated accordance with Sections 4.3.2.1, 4.3.2.2 or 4.3.2.3 the from the interior of the building by an approved thermal following conditions apply: barrier of 1/2-inch-thick (12.7 mm) gypsum wallboard or a) Entry to the attic or crawl space is to service utilities, an equivalent 15-minute thermal barrier complying with and no storage is permitted. and installed in accordance with the applicable code. b) There are no interconnected attic or crawl space areas. Exception: within an attic or crawl space, installation must be in accordance with Section 4.3. c) Air in the attic or crawl space is not circulated to other 4.2.2 Application without a Prescriptive Thermal parts of the building. Barrier: d) Attic ventilation is provided when required by IBC ® Section 1203.2 or IRC Section R806, except when air- 4.2.2.1 Application with Paint to Protect DC-315 impermeable insulation is permitted in unvented attics intumescent Coating: The prescriptive 15-minute thermal in accordance with the 2012 IRC Section R806.5(2009 barrier may be omitted when installation is in accordance IRC Section R806.4). Under-floor (crawl space) with this section.The insulation and coating may be spray- ventilation is provided when required by IBC Section applied to the interior facing of walls, the underside of roof 1203.3 or IRC Section R408.1,as applicable. sheathing or roof rafters, and in crawl spaces, and may be left exposed as an interior finish without a prescribed e) Combustion air is provide® in accordance with 15-minute thermal barrier or prescribed ignition barrier. International Mechanical Code Section 701. The thickness of the foam plastic applied to the underside 4.3.2.1 Application with Bayseal IC Intumescent of the roof sheathing must not exceed 111/2 inches Coating: In attics, BaysealTM OC insulation may be spray- (292 mm). The thickness of the foam plastic applied to applied to the underside of roof sheathing or roof rafters; vertical wall surfaces must not exceed 10 inches(254 mm). and in crawl spaces, BaysealTM OC insulation may be The foam plastic must be covered on all surfaces with DC spray-applied to the underside of floors as described in this 315 Fireproof Paint at a minimum wet film thickness of section. The thickness of the foam plastic applied to the ESR-1655 I Most Widely Accepted and Trusted Page 3 of 5 underside of the top space must not exceed 16 inches compound in accordance with ASTM C840 or GA216.The (406 mm). The thickness of the foam plastic applied to interior cavity is filled with BaysealTM OC spray-applied vertical surfaces must not exceed 111/4 inches (286 mm). foam insulation. All foam plastic surfaces must be covered with 7.5 wet mils Opposite Face: One layer of 5/8-inch-thick (15.9 mm) (0.2 mm) [4 dry mils (0.10 mm)] of the BaysealTM IC Type X gypsum wallboard must be applied in the same intumescent coating described in Section 3.4. The manner as for the initial face. The horizontal joints in the BaysealTM IC intumescent coating must be applied over gypsum wallboard on the opposite face must be staggered the Bayseal MOC insulation in accordance with the a minimum of 8 inches (203 mm)from the horizontal joints manufacturer's instructions and this report. Surfaces to be in the wallboard on the initial face. If the intention is for use coated must be dry, clean, and free of dirt, loose debris as an exterior wall,code-complying sheathing and a code- and any other substances that could interfere with complying exterior wall covering must be installed in adhesion of the coating. The Baysealm IC coating is accordance with the applicable code. applied with a medium-size nap roller, soft brush or conventional airless spray equipment at a rate of 0.5 gallon 4.4.2 Axial Load Design:Axial loads applied to the wall (1.9L) per 100 square feet (9.2 m2). The coating must be assembly must be limited to the lesser of the following: applied when ambient and substrate temperatures are 1. 2,756 pounds(122 642 N)per stud. above 50°F(10°C)and requires a 24-hour curing time after 2. A maximum of 51 application. BaysealTM OC insulation, as described in this percent of the load calculated in section, may be installed in unvented conditioned attics in accordance with Sections 3.6 and 3.7 of the accordance with the 2009 IRC Section R806.4 or the 2012 ANSI/AF&PA NDS. IRC Section R806.5.The attic or crawl space area must be 4.5 Exterior Walls in Types I, II, Ill and IV separated from the interior of the building by an approved Construction: 15 minute thermal barrier as described in Section 4.2.1. When used on exterior walls of Type I, II, Ill and IV 4.3.2.2 Application with TPR2 Fireshell® BMS-IC construction, must comply with Section 2603.5 of the IBC Intumescent Coating: In attics, BaysealTM OC insulation and this section (Section 4.5), and the insulation must be may be spray-applied to the underside of roof rafters; and installed at a maximum thickness of 35/8 inches (92 mm) in crawl spaces, BaysealTM OC insulation may be spray- See Table 2 for a description. The potential heat of the applied to the underside of floors as described in this BayseafT""OC spray-applied polyurethane insulation is 488 section. The thickness of the foam plastic applied to the Btu/ft2(5.5 MJ/m2)per inch of thickness. underside of the top space must not exceed 91/2 inches 5.0 CONDITIONS OF USE (241 mm). The thickness of the foam plastic applied to The BaysealTm OC insulation described in this report vertical surfaces must not exceed 7 inches (178 mm). All complies with, or is a suitable alternative to what is foam plastic surfaces must be covered with the TPR2 BMS-IC intumescent coating described in specified in,those codes listed in Section 1.0 of this report, Section 3.7. The intumescent coating must be applied over subject to the following conditions: the BaysealTM OC insulation in accordance with the 5.1 This evaluation report and the manufacturer's manufacturer's instructions and this report. The foam published installation instructions, when required by plastic insulation must be covered with 7 wet mils(0.2 mm) the code official, must be submitted at the time of [4 dry mils (0.10 mm)] of TPR2 Fireshell® BMS-IC permit application. intumescent coating applied in a single coat at a rate of 5.2 Bayseal1"" OC insulation and Bayseal TM IC 0.83 gallon(1.10 L) per 100 square feet(9.2 m2). Surfaces intumescent coating must be installed in accordance to be coated must be dry, clean and free of dirt, loose with the manufacturer's published installation debris and other substances that could interfere with instructions, this report and the applicable code. The adhesion of the coating. The coating is applied in one coat instructions within this report govern if there are any by airless spray equipment, medium knap roller or brush at conflicts between the manufacturer's published ambient temperatures above 70°F (21°C) and relative installation instructions and this report. humidity of less than 70 percent, and requires a 24 hour 5.3 BaysealT"" OC insulation must be separated from the curing time. The attic or crawl space area must be interior of the building by an approved 15 minute separated from the interior of the building by an approved 15-minute thermal barrier as described in Section 4.2.1. thermal barrier, as described in Section 4.2.1, except as noted in Section 4.2.2. 4.3.2.3 Use on Attic Floors: BaysealTM OC insulation 5.4 BaysealTM OC insulation must be protected from the may be installed at a maximum thickness of 111/4 inches weather during and after application. (286 mm)between joists in attic floors. The insulation must be covered on all exposed surfaces with Bayseal TM IC 5.5 BaysealTM OC insulation must be applied by installers intumescent coating as described in Section 4.3.2.1. The certified by Bayer MaterialScience LLC. BaysealTm OC insulation must be separated from the area 5.6 When use is on buildings of Types I, II, Ill and IV beneath the attic by an approved thermal barrier. An construction, installation must be as described in ignition barrier in accordance with IBC Section 2603.4.1.6 Section 4.5 and Table 2. and IRC Section R316.5.3 may be omitted. 5.7 Use of BaysealTM OC insulation in areas where the 4.4 One-hour Fire-resistance-rated Wall Assembly probability of termite infestation is "very heavy" must (Limited Load-bearing): be in accordance with IBC Section 2603.8 or IRC 4.4.1 Initial Face: One layer of 5/8-inch-thick (15.9 mm) Section R318.4,as applicable.. Type X gypsum wallboard must be applied parallel to the 5.8 Jobsite certification and labeling of the insulation must interior face of 2-by-6 wood studs spaced a maximum of comply with IRC Sections N1101.4 and N1101.4.1 16 inches (406 mm) on center. The gypsum boards must and IECC Sections 303.1.1 and 303.1.2, as be attached using Type S, 15/a-inch-long (41 mm) screws applicable. spaced 8 inches (203 mm) on center. All exposed 5.9 In exterior wall applications, a vapor retarder may be wallboard joints must be taped with joint tape, and required by the code official in accordance with IBC compound and screw heads must be covered with joint Section 1405.3 or IRC Section R601.3,as applicable. ESR-1655 I Most Widely Accepted and Trusted Page 4 of 5 5.10 BaysealTM OC insulation is produced in Phoenix, • 2006 International Residential Code®(2006 IRC) Arizona and Spring, Texas, under a quality control • 2006 International Energy Conservation Code® (2006 program with inspections by ICC-ES. IECC) 6.0 EVIDENCE SUBMITTED The products comply with the above-mentioned codes as 6.1 Data in accordance with the ICC-ES Acceptance described in Sections 2.0 through 7.0 of this report, except Criteria for Spray-applied Foam Plastic Insulation as noted below: (AC377), dated June 2012, including reports of tests • Application with a Prescriptive Thermal Barrier: see in accordance with Appendix X of AC377. Section 4.2.1, except the approved thermal barrier must 6.2 Reports of room corner tests in accordance with be installed in accordance with Section R314.4 of the NFPA 286. 2006 IRC. 6.3 Report of air leakage testing in accordance with • Application without a Prescriptive Thermal Barrier: ASTM E283. See Section 4.2.2. 6.4 Report of testing in accordance with ASTM E119. • Application with a Prescriptive Ignition Barrier: See 6.5 Report of potential heat of foam plastic testing in Section 4.3.1 except attics must be vented in accordance with NFPA 259. accordance with Section 1203.2 of the IBC or Section 6.6 Report of fire propagation characteristics testing in R806 of the IRC, and crawl space ventilation must be in accordance with IBC Section 1203.3 or IRC Section accordance with NFPA 285. R408, as applicable. 7.0 IDENTIFICATION • Application without a Prescriptive Ignition Barrier: Components for BaysealTM OC insulation are identified See Section 4.3.2, except attics must be vented in with the manufacturer's name (Bayer MaterialScience, accordance with Section 1203.2 of the IBC or Section LLC), address and telephone number; the product trade R806 of the IRC, and crawl space ventilation must be in name (BaysealTM OC); product type (A or B component); accordance with IBC Section 1203.3 or IRC Section use instructions; the density; the flame-spread and smoke- R408, as applicable and combustion air is provided in developed indices;the evaluation report number(ESR 1655); accordance with 2006 International Mechanical Code® Sections 701 and 703 Intumescent coatings are identified with the • Protection Against Termites: See Section 5.7, except manufacturer's name and address, the product name and use of the insulation in areas where the probability of use instructions. termite infestation is "very heavy" must be in 8.0 OTHER CODES accordance with Section R320.5 of the 2006 IRC. In addition to the codes referenced in Section 1.0, the • Jobsite Certification and Labeling: See Section 5.8, products described in this report were evaluated for except jobsite certification and labeling must comply compliance with the requirements of the following codes: with Sections 102.1.1 and 102.1.1.q, as applicable, of • 2006 International Building Code®(2006 IBC) the 2006 IECC. TABLE 1-THERMAL RESISTANCE(R-VALUES) THICKNESS(inches) R-VALUE(°F.ft2.h/Btu) 1 3.7 2 7.4 3 11 3.5 13 4 15 5 18 5.5 20 6 22 7 25 7.75 27 8 28 9 32 10 35 11 39 12 42 13 46 14 50 15 53 16 56 For SI:1 inch=25.4 mm;1°F.ft2.h/Btu=0.176 110 k.m2/W. 'Calculated R-values are based on tested K-values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. ESR-1655 i Most Widely Accepted and Trusted Page 5 of 5 TABLE 2—NFPA 285 COMPLYING EXTERIOR WALL ASSEMBLIES IN TYPES I,II,III AND IV CONSTRUCTION WALL COMPONENT MATERIALS 1–Concrete wall 2–Concrete masonry wall 3–1 layer 5/8.inch-thick Type X gypsum wallboard complying with ASTM C36 or C1396 on interior, Base Wall System– installed over steel studs,minimum 35/8-inch deep,No.20 gage,C-shaped,spaced a maximum of Use either 1,2 or 3 24 inches on center.Gypsum wallboard must be attached with No.6,1 /4-inch-long self-tapping screws located 8 inches on center along the perimeter and in the field of wallboard.Gypsum wallboard joints must be taped and treated with joint compound in accordance with ASTM C840 or GA-216. Floorline Firestopping 4 pcf mineral wool(e.g.,Thermafiber)in each stud cavity at each floorline attached with Z-clips 1–None Cavity Insulation– 2–Full cavity depth or less of BaysealTm OC insulation applied using exterior sheathing as substrate Use either 1 or 2 or 3 and covering the width of the cavity and inside the stud flange 3-Fiberglass bait insulation(faced or unfaced) Exterior Sheathing–Only for Base , Wall System No.3 1 –5/2.inch-thick,exterior type gypsum sheathing Use either 1 or 2 2–5/8-inch-thick,exterior type gypsum sheathing 1–Brick-standard nominal 4-inch-thick clay brick -Brick veneer anchors–standard types installed a maximum of 24 inches OC vertically on each stud Exterior Wall covering– -Maximum 2 inch air gap between exterior insulation and brick Use either 1 or 2 2–Stucco-minimum 3/4-inch-thick,exterior cement plaster and lath.A secondary water-resistive barrier may be installed between the exterior insulation and the lath.The secondary water-resistive barrier must not be full-coverage asphalt or butyl-based self-adhered membranes. For SI:1 inch=25.5 mm;1 pcf=16.018 kg/m3. USI First Choice 234C Industrial Loop Orange Park,FL 32073 Phone:904-637-4030 Fax:904-278-8020 Contractors Lic.#CBC 1254538 Fed ID#87-0572162 Sales Person Don Lightsey Phone(904)710-9914 Fax(904)278-8020 dlightsey @usiinc.com Attn: Chris Lambertson 34 8/7/2015 Job Address Elite Homes Phone 384 FIRST ST. 355 11th Street (904)349-2803 JACKSONVILLE BEACH , FL 32250 Atlantic Beack, Fl 32233 Fax Job Description MARCO RES.- INSULATION Bid No: BD-37018 V1 We Propose To Furnish And Install The Following: INSULATION Foam Seal/Caulk Foam Sealant Orange at doors,windows&penetrations Foam Sealant White D/W at doors,windows&penetrations Foam Seal/Caulk Base Proposal Total tr - Batts r R19 X 15"Unfaced Batts at exterior framing house R11 X 15"Kraft Faced Batts at sound walls as marked R19 X 15"Unfaced Batts at exterior framing guest hs Batts Base Proposal Total $ 09 OPEN CELL SPF Bayer Bay Seal low density open cell spray foam 5.5"in house roofline Bayer Bay Seal low density open cell spray foam 5.5"in guest roofline Bayer Bay Seal low density open cell spray foam 3.5"in gable&kneewalls Bayer Bay Seal low density open cell spray foam 5.5"in garage ceiling Bayer Bayseal IC ignition barrier sprayed over Bayseal foam sprayed over foam OPEN CELL SPF Base Proposal Total ilielgaPIIW Proposal Total Including Tax This proposal is based upon material prices as of date of proposal.Any change in material prices prior to the execution of this agreement may result in changes to proposal price. Terms and Conditions CONTRACT TERMS NET 15 IIIIIIIIIIIIIIIIIIIIIIIII No. BD-37018 V1 IIIHNIIIIIIIIIINIIINIIIIHIIBIIIIIIIIIIIIIBflIIIIIIIIIIIIBIIIIIIIIIIIIIIIII Page 1 of 2 FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: ECH253815 Builder Name: Elite Custom Homes and Renovations Street: 384 1st Street Permit Office: City,State,Zip: Jacksonville Beach, FL, 32233 Permit Number: Owner: Marco Jurisdiction: 261400111 Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(2900.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame Wood, Exterior R=19.0 2900.00 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (2537.0 sqft.) Insulation Area a.Cathedral/Single Assembly(Unvented)R=0.0 2537.00 ft2 6. Conditioned floor area above grade(ft2) 2537 b. N/A R= ft2 Conditioned floor area below grade(ft') 0 c. NIA R= ft2 11. Ducts R ft2 7. Windows(288.0 sqft.) Description Area a.Sup:Attic, Ret:Attic,AH:Attic 8 185 a. U-Factor: Dbl, U=0.45 288.00 ft2 b.Sup: Attic,Ret:Attic,AH:Attic 8 115 SHGC: SHGC=0.40 b. U-Factor: N/A ftZ 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 30.0 SEER:15.00 b.Central Unit 18.0 SEER:15.00 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 30.0 HSPF:8.30 SHGC: b.Electric Heat Pump 18.0 HSPF:8.30 Area Weighted Average Overhang Depth: 1.500 ft. Area Weighted Average SHGC: 0.400 14. Hot water systems 8. Floor Types (2537.0 sqft.) Insulation Area a. Propane Tankless Cap: 1 gallons EF:0.590 a.Slab-On-Grade Edge Insulation R=0.0 1954.00 ft2 b. Conservation features b. Floor over Garage R=19.0 583.00 ft2 None c.N/A R= ft2 15. Credits Pstat Total Proposed Modified Loads: 71.69 PASS Glass/Floor Area: 0.114 Total Baseline Loads: 71.81 I hereby certify that the plans and specifications covered by Review of the plans and O� CHI TqT� this calculation are in compliance w the Florida Energy specifications covered by this - Q '�° 0�,`,, Code. calculation indicates compliance �4�h,,,' - 1 with the Florida Energy Code. y s> , ,, •`,••.'_= °.'- O PREPARED BY - Before construction is completed �,�, DATE: . �1� .___._ this building will be inspected for V • r . . compliance with Section 553.908 �, '"= I hereby certify that this building, as designed,is in compliance Florida Statutes. \; ����y with the Florida Energy C // .,,OD wE10,,+,''/ OWNER/AGENT: /. `Gi"'' _ BUILDING OFFICIAL .in DATE: 1-- IA.- J"I, DATE: _ -9`'pZ Y1S - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. OFFICE COPY 9/18/2015 1:30 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 6 FORM R405-2014 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the residential Simulated Performance method shall include ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, e-ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst-case orientation, name and version of the compliance software tool, name of individual completing the compliance report(1 page) and an input summary checklist that can be used for field verification (usually 4 pages/may be greater). ❑ Energy Performance Level(EPL) Display Card (one page) ❑ Mandatory Requirements(three pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report(usually one page) 4 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report(usually one page) EnergyGauge®-USRFZB v4.0 9/18/2015 1:45:05 PM Page 1 of 1 FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: ECH253815 Builder Name: Elite Custom Homes and Renovations Street: 384 1st Street Permit Office: City,State,Zip: Jacksonville Beach, FL,32233 Permit Number: Owner Marco Jurisdiction: 261400 III Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(2900.0 sqft.) Insulation Area a. Frame Wood,Exterior R=19.0 2900.00 ft2 2. Single family or multiple family Single-family b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 10. Ceiling Types (2537.0 sqft.) Insulation Area 5. Is this a worst case? No a.Cathedral/Single Assembly(Unvented)R=0.0 2537.00 ft' 6. Conditioned floor area above grade(ft') 2537 b. N/A R= ft2 c. N/A R= ft2 Conditioned floor area below grade(ft2) 0 11. Ducts R ft2 7. Windows(288.0 sqft.) Description Area a. Sup:Attic,Ret:Attic,AH:Attic 8 185 a. U-Factor Dbl, U=0.45 288.00 ft2 b.Sup: Attic,Ret:Attic,AH:Attic 8 115 SHGC: SHGC=0.40 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency a.Central Unit 30.0 SEER:15.00 SHGC: b.Central Unit 18.0 SEER:15.00 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft' a. Electric Heat Pump 30.0 HSPF:8.30 SHGC: b. Electric Heat Pump 18.0 HSPF:8.30 Area Weighted Average Overhang Depth: 1.500 ft. Area Weighted Average SHGC: 0.400 14. Hot water systems a. Propane Tankless Cap: 1 gallons 8. Floor Types (2537.0 sqft.) Insulation Area EF:0.590 a.Slab-On-Grade Edge Insulation R=0.0 1954.00 ft' b. Conservation features b. Floor over Garage R=19.0 583.00 ft' None c. N/A R= ft2 15. Credits Pstat Total Proposed Modified Loads: 71.69 PASS Glass/Floor Area: 0.114 Total Baseline Loads: 71.81 I hereby certify that the plans and specifications covered by Review of the plans and �+�`` -01E ST9T this calculation are in complipn - wit the Flgrida Energy specifications covered by this , v , �O,�h, Code. calculation indicates compliance ,, @a'°�O with the Florida Energy Code. .¢s :.�r f PREPARED BY: L '_'/ Before construction is completed a H '^ . DATE: . __ ' 11., ._ this building will be inspected for t.)o .. fa a compliance with Section 553.908 a . (1:70/.. I hereby certify that this building, as designed,is in co liance Florida Statutes. �ti I� Y Jc,'S r' F o with the Florida Energy Code. G 'COO ��''' OWNER/AGENT:_ ° i�� BUILDING OFFICIAL: DATE: fl'�j�1.-S DATE: - - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 9/18/2015 1:33 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 6 FORM R405-2014 PROJECT Title: ECH253815 Bedrooms: 3 Address Type: Street Address Building Type: User Conditioned Area: 2537 Lot# Owner: Marco Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Elite Custom Homes and Ren Rotate Angle: 0 Street: 384 1st Street Permit Office: Cross Ventilation: County: Duval Jurisdiction: 261400 Ill Whole House Fan: City,State,Zip: Jacksonville Beach, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE IECC Design Temp Int Design Temp Heating Design Daily Temp Design Location PAY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block1 1954 19540 2 Block2 583 5830 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 Living Room 575 5750 No 2 1 Yes Yes Yes 2 Kitchen 220 2200 Yes 2 0 1 Yes Yes Yes 3 Utility Hall 90 900 No 0 0 1 Yes Yes Yes 4 Bathroom 1 85 850 No 0 0 1 Yes Yes Yes 5 Bedroom 1 272 2720 No 0 1 1 Yes Yes Yes 6 Hall 208 2080 No 0 0 1 Yes Yes Yes 7 Bedroom 2 224 2240 No 0 1 1 Yes Yes Yes 8 Bathroom 2 140 1400 No 0 0 1 Yes Yes Yes 9 Dining Room 140 1400 No 0 0 1 Yes Yes Yes 10 Guest Bedroom 391 3910 No 0 1 1 Yes Yes Yes 11 Kitchenette 120 1200 Yes 0 0 1 Yes Yes Yes 12 Guest Bath 72 720 No 0 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio Living Room 65 ft 0 575 ft2 __- 0 1 0 2 Slab-On-Grade Edge Insulatio Kitchen 27 ft 0 220 ft2 ____ 1 0 0 3 Slab-On-Grade Edge Insulatio Utility Hall 5 ft 0 90 ft2 ____ 1 0 0 4 Slab-On-Grade Edge Insulatio Bathroom 1 5 ft 0 85 ft2 ____ 1 0 0 9/18/2015 1:33 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 6 FORM R405-2014 FLOORS ✓ # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 5 Slab-On-Grade Edge Insulatio Bedroom 1 33 ft 0 272 ft2 — 0 0 1 6 Slab-On-Grade Edge Insulatio Hall 8 ft 0 208 ft2 — 0 0 1 7 Slab-On-Grade Edge Insulatio Bedroom 2 30 ft 0 224 ft2 _ 0 0 1 8 Slab-On-Grade Edge Insulatio Bathroom 2 10 ft 0 140 ft2 _ 0 1 0 9 Slab-On-Grade Edge Insulatio Dining Room 10 ft 0 140 ft2 — 0 1 0 10Floor over Garage Guest Bedroom ____ ____ 391 ft2 19 0 1 0 11Floor over Garage Kitchenette ____ _— 120 ft2 19 1 0 0 12FIoor over Garage Guest Bath _-__ ____ 72 ft2 19 1 0 0 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 2749 ft2 0 ft2 Medium 0.85 No 0.9 No 31 22.6 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 2538 ft2 N N CEILING # Ceiling Type Space _— R-Value Area Framing Frac Truss Type 1 Cathedral/Single Assembly(Unventekbest Bath 0 72 ft2 0.11 Wood 2 Cathedral/Single Assembly(UnventKdchenette 0 120 ft2 0.11 Wood 3 Cathedral/Single Assembly(Unve6teebt Bedroom 0 391 ft2 0.11 Wood 4 Cathedral/Single Assembly(Unventliding Room 0 140 ft2 0.11 Wood 5 Cathedral/Single Assembly(Unventl3Athroom 2 0 140 ft2 0.11 Wood 6 Cathedral/Single Assembly(UnventetEdroom 2 0 224 ft2 0.11 Wood 7 Cathedral/Single Assembly(Unvented Hall 0 208 ft2 0.11 Wood 8 Cathedral/Single Assembly(Unvent(labdroom 1 0 272 ft2 0.11 Wood 9 Cathedral/Single Assembly(Unvent8dithroom 1 0 85 ft2 0.11 Wood 10 Cathedral/Single Assembly(Unventddtility Hall 0 90 ft2 0.11 Wood 11 Cathedral/Single Assembly(Unvented{itchen 0 220 ft2 0.11 Wood 12 Cathedral/Single Assembly(Unventading Room 0 575 ft2 0.11 Wood WALLS `/ Adjacent Cavity Width Height Sheathing Framing Solar Below V ..#_-Ornt . To Wall TypP Space R Value Ft In __ Ft In Area R-Value Fraction Absor. Grade% _ 1 N Exterior Frame-Wood Guest Bath 19 8 10 80.0 ft2 0.23 0.75 0 _2 E Exterior Frame-Wood Guest Bath 19 9 10 90.0 ft2 0.23 0.75 0 3 E Exterior Frame-Wood Kitchenette 19 15 10 150.0 ft2 0.23 0.75 0 9/18/2015 1:33 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 6 FORM R405-2014 WALLS / Adjacent Cavity Width Height Sheathing Framing Solar Below Y__! Omt To Wall Type SPaT__ R-Value Ft In .FL_.ln Area R-Value Fraction Absor. Grade% 4 S Exterior Frame-Wood Kitchenette 19 8 10 80.0 ft2 0.23 0.75 0 5 S Exterior Frame-Wood Guest Bedroo 19 17 10 170.0 ft2 0.23 0.75 0 6 W Exterior Frame-Wood Guest Bedroo 19 23 10 230.0 ft2 0.23 0.75 0 7 N Exterior Frame-Wood Guest Bedroo 19 17 10 170.0 ft' 0.23 0.75 0 8 E Exterior Frame-Wood Living Room 19 25 10 250.0 ft' 0.23 0.75 0 9 S Exterior Frame-Wood Living Room 19 23 10 230.0 ft2 0.23 0.75 0 10 W Exterior Frame-Wood Living Room 19 17 10 170.0 ft2 0.23 0.75 0 11 S Exterior Frame-Wood Kitchen 19 17 10 170.0 ft2 0.23 0.75 0 12 W Exterior Frame-Wood Kitchen 19 10 10 100.0 ft2 0.23 0.75 0 13 W Exterior Frame-Wood Utility Hall 19 5 10 50.0 ft2 0.23 0.75 0 14 W Exterior Frame-Wood Bathroom 1 19 5 10 50.0 ft2 0.23 0.75 0 15 W Exterior Frame-Wood Bedroom 1 19 16 10 160.0 ft2 0.23 0.75 0 16 N Exterior Frame-Wood Bedroom 1 19 17 10 170.0 ft2 0.23 0.75 0 17 N Exterior Frame-Wood Hall 19 8 10 80.0 ft2 0.23 0.75 0 18 N Exterior Frame-Wood Bedroom 2 19 14 10 140.0 ft2 0.23 0.75 0 19 E Exterior Frame-Wood Bedroom 2 19 16 10 160.0 ft2 0.23 0.75 0 20 E Exterior Frame-Wood Bathroom 2 19 10 10 100.0 ft2 0.23 0.75 0 21 E Exterior Frame-Wood Dining Room 19 10 10 100.0 ft2 0.23 0.75 0 DOORS # Ornt Door Type Space Storms U-Value Ft Width In FHe ht Area 1 N Wood Guest Bath None .2 .1 .1 .1 ft2 WINDOWS Orientation shown is the entered, Proposed orientation. Wall Overhang V ___# Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 S 5 Vinyl Double(Tinted) Yes 0.45 0.4 24.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 2 W 6 Vinyl Double(Tinted) Yes 0.45 0.4 24.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 3 N 7 Vinyl Double(Tinted) Yes 0.45 0.4 24.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 4 E 8 Vinyl Double(Tinted) Yes 0.45 0.4 12.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 5 S 9 Vinyl Double(Tinted) Yes 0.45 0.4 45.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 6 W 10 Vinyl Double(Tinted) Yes 0.45 0.4 15.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 7 W 10 Vinyl Double(Tinted) Yes 0.45 0.4 20.0 ft2 1 ft 6 in 8 ft 0 in Drapes/blinds None 8 S 11 Vinyl Double(Tinted) Yes 0.45 0.4 12.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 9 W 13 Vinyl Double(Tinted) Yes 0.45 0.4 20.0 ft2 1 ft 6 in 8 ft 0 in Drapes/blinds None 10 W 15 Vinyl Double(Tinted) Yes 0.45 0.4 8.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 11 N 16 Vinyl Double(Tinted) Yes 0.45 0.4 16.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 12 N 17 Vinyl Double(Tinted) Yes 0.45 0.4 20.0 ft2 1 ft 6 in 8 ft 0 in Drapes/blinds None 13 N 18 Vinyl Double(Tinted) Yes 0.45 0.4 16.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 14 E 19 Vinyl Double(Tinted) Yes 0.45 0.4 16.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 15 E 20 Vinyl Double(Tinted) Yes 0.45 0.4 4.0 ft2 1 ft 6 in 6 ft 0 in Drapes/blinds None 16 E 21 Vinyl Double(Tinted) Yes 0.45 0.4 12.0 ft2 1 ft 6 in 4 ft 0 in Drapes/blinds None 9/18/2015 1:33 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 6 FORM R405-2014 GARAGE VFloor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 625 ft2 384 82 76 ft 10 ft 19 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Whorehouse Proposed ACH(50) .000309 2058.8 113.03 212.56 .2933 4.8691 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.3 30 kBtu/hr 1 sys#1 2 Electric Heat Pump None HSPF:8.3 18 kBtu/hr 2 sys#2 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER: 15 30 kBtulhr 900 dm 0.75 1 sys#1 2 Central Unit None SEER: 15 18 kBt lhr 540 dm 0.75 2 sys#2 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Propane Tankless Kitchen 0.59 1 gal 60 gal 120 deg None SOLAR HOT WATER SYSTEM V FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS / —Supply— —Return---- Air CFM 25 CFM25 HVAC# V # Location R-Value Area location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 8 185 82 Attic 63.425 Default Leakage Attic (Default) (Default) 1 1 2 Attic 8 115 ft2 Attic 20 ft2 Default Leakage Attic (Default) (Default) 2 2 9/18/2015 1:33 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 6 FORM R405-2014 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Coolin Jan Feb Mar A r ]Ma [X]Jun X Jul [X]Au X]Sep [ ]Oct [ Nov Dec Heating f X�Jan [X�Feb )( Mar [ t Ar f 1 May [ ]Lunn 1 Jul [ l Aug 4 ]Sep [ ]Oct [X�Nov X Dec Venting [ Jan [ Feb 7( Mar [X Apr [ 1 Ma [ ]Jun [ Jul [ 1 Au [ 1 Sep [X]Oct [X]Nov t 1 Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 9/18/2015 1:33 PM EnergyGaugeV USA-FlaRes2014 Section R405.4.1 Compliant Software Page 6 of 6 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 100 The lower the EnergyPerformance Index, the more efficient the home. 384 1st Street, Jacksonville Beach, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame-Wood. Exterior R=19.0 2900.00 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 10. Ceiling Types Insulation Area a.CathedraUSingle Assembly(Unvented)R=0.0 2537.00 ft2 6. Conditioned floor area(ft2) 2537 b. N/A R= ft2 7. Windows" Description Area c. N/A R= ft2 a. U-Factor. Dbl, U=0.45 288.00 ft2 11. Ducts R ft2 a. Sup:Attic, Ret:Attic,AH:Attic 8 185 SHGC: SHGC=0.40 b. Sup: Attic, Ret:Attic.AH:Attic 8 115 b. U-Factor: N/A ft2 SHGC: 12. Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a. Central Unit 30.0 SEER:15.00 SHGC: b. Central Unit 18.0 SEER:15.00 d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency SHGC: Area Weighted Average Overhang Depth: 1.500 ft. a. Electric Heat Pump 30.0 HSPF:8.30 b. Electric Heat Pump 18.0 HSPF:8.30 Area Weighted Average SHGC: 0.400 8. Floor Types Insulation Area 14. Hot water systems Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 1954.00 ft2 a. Propane EF: 0.59 b. Floor over Garage R=19.0 583.00 ft2 c. N/A R= ft2 b. Conservation features None 15. Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building '.„-.,, 014E Sr,o N Construction through the above energy saving features which will be installed (or exceeded) r'>0 Fo in this home before final inspection. Otherwise, a new EPL Display Card will be completed Ie7',. ';'n based on installed Code compliant features. '.-1- �• Builder Signature: / ✓ �� Date: �. �_/� :it E., 1a Address of Ne e: 3Y/ Arm City/FL Zip: cih - �gS,,"' 3 22 3 3 .•.., ,,, . "Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. "Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 9/18/2015 1:46 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 384 1st Street Permit Number: Jacksonville Beach, FL,32233 MANDATORY REQUIREMENTS See individual code sections for full details. ❑ 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law [Section 553.9085, Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. C R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. o R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2, and 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures: 2. Dampers including exhaust, intake. makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures: 3. Interior doors, if installed at the time of the test,shall be open; 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Heating and cooling systems. if installed at the time of the test, shall be turned off;and 6. Supply and return registers, if installed at the time of the test,shall be fully open. O R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. O R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or AAMANVDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. ❑ R403.1,1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.2.2 Sealing(Mandatory)All ducts, air handlers, and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99, Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa)across the entire system, including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25Pa)across the system, including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test.total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 9/18/2015 1:48 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. r R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. C R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3., O R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight,moisture,equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. C R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 1/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies 0 R403.4.4.1 Storage water heater temperature controls . R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). . R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. O R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. . R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1. Solar Domestic Hot Water System and Component Test Protocol, Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential or Florida Building Code, Mechanical,as applicable. or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. o R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception:Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. O R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62,Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics.crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting,or R-10 otherwise. 0 R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. O R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors, provisions for future expansion or other factors which affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load. but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6. or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 9/18/2015 1:48 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) O R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal. rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data. the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer, in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. O R403.6.1.2 Heating equipment capacity • R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. • R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. • R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. O R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. • R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. • R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building.shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F, and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. • R403.9 Swimming pools, inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16. 2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance • with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters, pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. o R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy, such as a heat pump or • solar energy source computed over an operating season. C RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights C R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. o R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space, R-10 is allowed. 9/18/2015 1:48 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 3 of 3 Jo L abed aeMuoS lue9dwo3 1 b•904/d uo!loaS 4LOZseeleld-vsn v06neo(6iau3 Wd£5l 9LOZ/8 L/6 sloop palamse6 anal Heys saoelda.nd slIeM aoeldai uo palleisu aq Heys aaweq i!e uy aoeldaJid IIendup Jo fool}-qns ail o;papas aq Heys adolanua leWJayl 6u!pl!nq a4ea1auad lei!slooq Jals!6aJ 3VAH wog Jalsi6a OVAH pallelsu!aq Heys saxoq papas lie oq uo!leo!unwwoo Jo leoulaala pu!gaq pallelsu!aq Heys Jaweq ne 041 uo xoq auogd/leouloa13 •sgn4 pue sJaMOys a444 wa4 wail 6ugeiedas pallelsu!Jaweq ne 041 pue paielnsw aq Heys sgn4 pue SJOM014S of luaoepe SIIBM aouapx3 Fenn Jouaaxa uo gnl/ie oqg -6uu!M pue 6u!d!d pu!gaq pualxa Heys coeds algellene O4 sunopoO Appeal uo!iellelsu! uo leU4 uogelnsu!JO 'spell Joualxa u! 6u!gwnld pue 6uuiM punae pi 04 Aneau Ono aq Reis uogelnsu!peg 6uuIM pue 6uigwnld IIem/uP a4104 papas pue 'pales ai `346!4 J!e aq Heys adolanua lewia44 6u!pl!nq eU4 u! pallelsu sajnix4 11461 passaoaa 6ugy611 passaoad -saoeds pauo!4!puoo pue a6eie6 ail uaaM4aq pap!nad aq Heys 6u!leas J!y uogeJedas a6eiee -saoeds A4!neo algel!ene ay;01 swJo4uoo Appeal uogepeisu! uo ley)uogelnsu!Aq pail!l aq !legs sag!neo MaJeu JO '414 01 Ono aq Reis sag!neo MaJeu ui sl4eg sagineo MaJeN paleas aq Heys coeds pauo!4ipuooun Jo Joualxa of sou!uado 44egs enl}pue `suogei4auad Al!I!in 'sl4eis pna suogeglaued `sl4egS pade4 sju!of 6u!ddeuano 41!M iapiela4 ioden ssela e yl!M paianoo aq Heys saoeds iMeJO paluanun u! ypea pasodx3 spleM aoedsIMeJO 044 0l pagoelle A14uauewiad aq !legs uogelnsu! 'uogelnsu!ioog 4o non w pap!nad shell coeds 'Ma° 'uogelnsu!4o a6pa pasodxa Aue le pallelsu aq Reis iaweq J!e ail '6unloap Jooggns lo (sioo14 paJanali4ueo pue ap!siapun yl!M loe1uoo luauewiad uelu!ew o4 pallelsu! aq Reis uogelnsu) a6eie6-anoge 6wpnpu!) sJoo1d Jaweq ne ue apnpu! pue palelnsu!ale s4s!of w!g s4s!of wij 'papas aq Heys 6u!wPJ4 pue s4446!!ANs pue 6u!we.i4 pue sgwef Joop/MOpuM uaailaq coeds ail scoop pue slg6!bis `sMOpuIM paleas aq Heys spell aauN "Jaweq.qe ail y4!M luawu6ge snonu!4uoo pue 4oe4U0o le!4ue4sgns u! pallelsu aq Heys shell paweii X04 uogelnsu adolanua lewJa44 Joualx3 paleas aq Heys shell 4ouaixa Jo do4 044 pue afield do4 04140 uo!4ounf ail 'papas aq Heys afield Il!s pue slleM uogepuno4 0411 Jo uogounf 044 pue pa4elnsu!aq Heys siapeaq pue sJawoa paleas aq Heys saoeds ogle pauo!4!puooun Ol scoop hell aawl Jo snels uMOp dap 's6u!uado ssaooy .paleas aq Heys Jaweq i!e 041 u!sde6 Aue pue uogelnsu! 044 yl!M pau6!le aq Heys 4!41os/6u!l!ao paddoJp Aue w Jaweq i!e ail ogle/6uil!ao .leua4ew 6u!leas e se pasn aq 4ou Heys uogelnsu! algeawiad-Jig 'papas aq !legs Jauieq.ne 041 w s4u!of Jo sNeaig .Jaweq snonwluoo e su!eluoo adolanua lewiayl Joualx3 adolanua 6u!pl!nq ail u! pallelsu!aq Heys Jaweq i!e snonuguoo y JawJeq lewJayl pue Jauieq J!y )I83H8 VI2I311?:I8 1N3NOdINO0 ap!nuosve£'ld :uo!leooi u6!saa iii 00 1.9Z :uo!lolpsunr ooieNl :Jam() :JaqwnN l!uuad ££ZZ£'ld 'ioeag an!nuosvep :d!Z'aleiS :aoy4O l!w.1 ad laaJlS Is 48£ :laaJlS suoilenouaH pue sawoH wolsn3 0193 :aweN Japlln8 9L8£9ZHO3 :aweN loafwd VI2I3111:I81N3NOdINO3 NOI183dSNI NOIIV1fSNI aNy 2I3I2I2IV8 2IIV 1:1:177017318V1 i oZ-5ov8 w ioJ 1.40 l abed ieMl;os lue!ldwoo 1.17.90172:1 uogoas- 41.0Zsa lel3-vsn®a6neoA6iau3 Wd 951.9103/81./6 :31Va - :3V101330 9NIalina ;/ eng :31V0 . i) �, y �'P"9� : a31NI 1d 4.,` 3M QOMr�o // leioolo apoo ago :321n1VNOIS \* 01 papoald pue 1sa1°i l 6uoonpuoo eQ 5� m ) Aped p.ilg;ago Aq pauPs aq , • t a !legs isaa aye;o sonsai aye podal 1..ti zot i uogoas Loon aouepJ000e ? off ; uajunn y Aped pill panoJdde ui s;uawaimbaa apoo l6Jau3 epuold g}wM ue Aq a on uoo a !legs 6ugsal aouel dwoo a ei suowa s nsa aouewao ad ^, 4P 1. P qll g 11 P 11 ./bCS Ky�O�,r leioi o apoo ag1 Aq paiinba� e�agM a6e�leal adolanua anoge ag11eg1 Mao lga�ag I uado nn;aq'legs `!sal ay;;o awg aql le pallelsul;! 'sJals!6aJ wn;a pue Alddns 9 pue :440 pawn;aq Heys'!sal ayl;o awg ague papelsul;! 'swats(s 6wl000 pue 6ulleaH 'g 'paleas pue pasop aq Hegs sio;elguan AAenooai leay pue swa;sAs uogeHluan snonuquoo Jo;scoop Joua;x3 '4 'uado aq Heys'!sal aql;o awg ay;;e pallelsw;! 'sloop Joualul •£ :sainseaw laluoo uonaniqu!papualui puobaq pleas lou lnq 'pasop aq!legs siadwep ant;pue l}eJpoeq 'J!e dnavw 'lsnegxa 6ulpnpu!siadweo .3 'samseaw la;goo uogeJllqu! iagio J0 6ulddulsJagleaM papualu!aq;puoAaq •paleas log lnq 'pasop aq Heys sloop ano;s pue aoeldaJi;'sloop pue sMOpuIM Joualx3 •l :6ugsal 6uuna 'adolanua lewiayl 6ulpinq ay;;o suoge.gauad lie lo uogeaio lake awg Aue le pawiopad aq leegs 6u!;sal leplmo apoo aql of pap!nad pue!set ayl 6ugonpuoo Aped aq;Aq pau6is aq Heys;sal aq;Jo s;insoj aq;;o Uoda ua;luM v'Aped pnyl panadde ue Aq palonpuoo aq Heys 6ugsal'pow apoo ay;!q palnba 0131M (sleosed 0g) •6•M sagow 3'0;o amssaid e _loop Jannolq e y;1.M palonpuoo aq Heys 6ugsal 8 g6nagl£sauoZ a;ewllo u!inoq lad sobuego ne£ 13 pue 1. sauoZ a;ewllo u! nog lad sebuego.ne g 6uipaaoxa jou jo a;ei e6emeal Jle ue bulney se paguan pue palsal aq!!ells l!un 6wIIaMp io 6wpHnq aql •6ul;sal Z•6.4.30421 w10 8d 9 wio ed`d-1S - -- - — 9 ed :(09)H0`d — — --- ed :H O`d wio ed -- -- :V1b9 u43 ed ,d13 :Mold 3NflSS321d 3Sf1OH Elea 1sa11wod !1lnW JO 0I6u!S :(05)WHO :el :u :o :Elea uo!ssaa6ae{ sopiaapeaeu3 a6m{eal s}nnsaei Tsai_ a6mieei adolanuA III 004193 :uogolpsunr aHlnuos)per`]d :uogeoo-1 ubiseG :JagwnN 3!wJad ££33£'id goeag aJ!nuoslpe£ :diZ'aims'40 :aog;o llwiad laaJls lsl 48£ :!ails suogenouaa pue sawoH wolsno al!13 :aweN Japlln9 91.8£93H03 :aweN loalad poylan aoueuwopad pue ani1diaosaad podaH isal a6eje0-1 ado10nu3 NOI13f1211SNO3 ONIalIf18 ?IOl 3003 A3N3131Jd3 AO J3N3 V0INO1d N sane}Joao 1u0JJ erini=a!ea dN'SLKSZH031owaa\OVAH 11oslubuM\sluawnaoaTo• for Z abed S69ZLnSd 9L 0'SL 9LOZ les.ian!un®al!fS-146!21 uos14611M 1 I 1 - L9 LEAL 9l-d°S-SLOZ 1 P31119 r Ienuen to sluawaipbai Ile paw of`d00d Aq panoJdde suogelnole0 £8.0 ow.' leaq alglsuas peon lelsowJagl aoeds OZH u! WO ainssaxd ollelS OZH ul 0i70 ainssaid oilelS 11n19/w16 MD compel moll-IN LIn18/WJO G£0 0 aoloel Moll JI wla 966 Moll ne lenloy wlo 266 moll ne lenloy 11n18 0086Z 6ugooO poi do 9Z asu amleiadwal gn18 Ob68 6ug000 lualel doLP @ 11n18 00Z8Z Indlno 6u!leaH 11n18 0980Z 6uil000 algisuas lndui 6uReeH 8133S S6 '2133 S.Zl. AOUa!oill3 ddSH 99 Aoue!oill3 SLOPL9S lac I2IHV 2J>iWy(N`1)L0-1-108+29£.H-1d0H I!o0 SL017L9S lay IHH`d Zvf0£0-iOdfl Puo0 ZVCO£0-iOdfl 19P°W S3IH3S iOdfl Gflfl 1 @Pail S3183S lOdfl ann 1 @pail pnnH a)19L J pnnel awW LiewwnS ;uawdinb3 6uHooa Ajewwns luawdinb3 6ugeaH uo1 L Z 8HS OLD 1e AlIOedeO Idol -bo21 L9 Z66 (wlo) dAv Ainbd 11n18 PLtLZ Peal Ielol luawdmb3 WO 9£.0 inoy/sa6ueyo Jib' 09L81• 09L8l. (>:4)awnlon 11n18 66LP peal lualeI luawdinb3 9L81 9L81. (Z11) easy gn18 0 (wp 0) Juan IeJlue0 6unooO ugeaH slop gn18 9£Z£ aanlon:4s 0 saoeldaJid a6eJanV Alilenb uollOnalsuo0 6u!zis peo1 }uawdinb3 6uHooa lua1ei paligdw!s PoyfGW gn18 9L9ZZ peon apsuas luawdinb3 uogeJliIU) 86.0 Jagdgllnw 6uims/aleH u elep s,J8Jnloelnuew asn 11n18 8bL8Z peo1 luawdmb3 gn18 0 buidid 11n18 0 Jamol8 11n18 0 uo!leo1l1p!wnH Lnma 0 (wlo 0) Juan leJlua3 1-n18 0 (wlo 0) Juan I8J1uaO 11n18 809L slona gn18 60LP scan@ 11n18 9L991 aJnloruis 11n18 6£0PZ ainlonalS 6u!z!s peoi luawd!nb3 6u!looa aigisuas A.iewwns 6uReaH gob Z9 aoualaj!p aJnls!on % 09 A1!piwnuLl an!lelaH W abueJ Alien A. 81 a1 u6isaa do 9£ ai u6isaa A. SL qp ap!sul do 89 qp apisul do 26 qp aP!sln0 do Z£ qp apISTfO suompuoa u6isaa iewwns suoi;ipuoa u6isea JamM Sfl Id 'aIl!AUOS)1oer :JayleaM uogewio ui u •!sea :saloN ££ZZ£ Id '11oea8 alllAu0S 1Oe£ 'Pe-ITS 1S6 t92 •OUI suo!lenouaH pm SawoH wolsn3 @1113 'aouep!sa ooJelAl :god uofewaoOui 430,0Jd eoae8's eo!UOW :A8 we U.1 swalsAS JIV Pue ieloS s.HZ!N SLOZ'SLdaS :oleo SL8ESZH03 :90!' /C1ell1Ulns loa(oJd eUUe9 eoiuOw Project Summary Job: Sep 15,201 Monica Bacca 1 rY Date: Sep 15,2015 Nick's Solar and Air Systems guest By: Monica S.Bacca Pro-ect Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Notes: Desi• n Information Weather: Jacksonville, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 93 °F Inside db 68 °F Inside db 75 °F Design TD 36 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 52 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 9482 Btuh Structure 10297 Btuh Ducts 1761 Btuh Ducts 2866 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 11242 Btuh Use manufacturer's data n Rate/swing multiplier 0.98 Infiltration Equipment sensible load 12874 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1419 Btuh Ducts 566 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 583 583 Equipment latent load 1985 Btuh Volume(ft') 5830 5830 Air changes/hour 0.58 0.30 Equipment total load 14859 Btuh Equiv.AVF (cfm) 56 29 Req. total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Ruud Make Ruud Trade SUMMIT Trade SUMMIT Model 15PJL18 Cond 15PJL18 AHRI ref 5537044 Coil CF025SDEB++TXV+TDR AHRI ref 5537044 Efficiency 7.7 HSPF Efficiency 11.0 EER, 14 SEER Heating input Sensible cooling 12040 Btuh Heating output 16500 Btuh @ 47°F Latent cooling 5160 Btuh Temperature rise 26 °F Total cooling 17200 Btuh Actual air flow 573 cfm Actual air flow 573 cfm Air flow factor 0.051 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.87 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2015-Sep-18 10:37:57 wrightsoft Right-Suite®Universal 2015 15.0.18 RSU12595 Page 1 A -.A . ca\Documents\Wrightsott HVAC1Demo\ECH253815.rup Calc=MJ8 Front Door faces: N Manual S Compliance Report Job: Sep 15,205 Monica Bacca P P Date: Sep 15,2015 Nick's Solar and Air Systems main By: Monica S.Bacca Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Cooling Equipment Design Conditions Outdoor design DB: 92.8°F Sensible gain: 23186 Btuh Entering coil DB: 77.6°F Outdoor design WB: 77.3°F Latent gain: 4799 Btuh Entering coil WB: 63.7°F Indoor design DB: 75.0°F Total gain: 27984 Btuh Indoor RH: 50% Estimated airflow: 993 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Ruud Model: UPQL-030JAZ+RCFL-H*3621+RGLT-07(E,N)AMKR Actual airflow: 993 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load Total capacity: 0 Btuh 0% of load SHR: 0% Heating Equipment Design Conditions Outdoor design DB: 31.8°F Heat loss: 28748 Btuh Entering coil DB: 67.3°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Ruud Model: UPQL-030JAZ+RCFL-H*3621+RGLT-07(E,N)AMKR Actual airflow: 993 cfm Output capacity: 29800 Btuh 104% of load Capacity balance: 33 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 993 cfm Output capacity: 8.3 kW 98% of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2015-Sep-18 10:37:57 wrightsoft Right-Suites Universal 2015 15.0.18 RSU12595 Page 2 ca\Documents\Wrightsoft HVAC\Demo\ECH253815.rup Calc=MJ8 Front Door faces: N Manual S Compliance Report Job: Sep 15,201 Monica Bacca P Date: Sep 15,2015 Nick's Solar and Air Systems guest By: Monica S.Bacca Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Cooling Equipment Design Conditions Outdoor design DB: 92.8°F Sensible gain: 13163 Btuh Entering coil DB: 76.7°F Outdoor design WB: 77.3°F Latent gain: 1985 Btuh Entering coil WB: 63.3°F Indoor design DB: 75.0°F Total gain: 15149 Btuh Indoor RH: 50% Estimated airflow: 573 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Ruud Model: 15PJL18+CF025SDEB++TXV+TDR Actual airflow: 573 cfm Sensible capacity: 0 Btuh 0% of load Latent capacity: 0 Btuh 0% of load Total capacity: 0 Btuh 0% of load SHR: 0% Heating Equipment Design Conditions Outdoor design DB: 31.8°F Heat loss: 11242 Btuh Entering coil DB: 67.5°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Ruud Model: 15PJL18+CF025SDEB++TXV+TDR Actual airflow: 573 cfm Output capacity: 17200 Btuh 153% of load Capacity balance: 22 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: n/a Model: n/a+n/a Actual airflow: 573 cfm Output capacity: 3.4 kW 103% of load Temp. rise: 13 °F The above equipment was selected in accordance with ACCA Manual S. 2015-Sep-18 10:37:57 wrightsoft Right-Suite®Universal 2015 15.0.18 RSU12595 Page 1 _ca\Documents\Wrightsoft HVAC\Demo\ECH253815.rup Calc=MJ8 Front Door faces: N _ Residential Plans Examiner Review Form Form RPER ACCA for HVAC System Design (Loads. Equipment. Ducts) 15 Mar 0 z 9 As Cacilawg Ccn rs dArrat2 261400 III Header Information Contractor: REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes ii No 0 Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes 0 No ❑ OEM performance data(heating,cooling, blower): Yes 0 No ❑ Building plan#: Manual D Friction Rate Worksheet: Yes 0 No ❑ Duct distribution sketch: Yes ❑ No ❑ Home address(Street or Lot#,Block,Subdivision): 384 1st Street, main HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: 32 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 28748 Btuh Number of bedrooms: 3 Conditioned floor area: 1876 ft2 Summer Design Conditions Number of occupants: 6 Outdoor temperature: 93 °F Indoor temperature: 75 °F Windows Root Grains difference: 52 grub @50% RH Eave overhang depth: 0 ft Sensible heat gain: 23707 Btuh Internal shade: none Ea,,e Latent heat gain: 4907 Btuh Blinds,drapes,etc. Depth Windo:. Total heat gain: 28614 Btuh Number of skylights: 0 HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Cooling Equipment Data Blower Data Equipment ty : Split ASHP Equipment type: Split ASHP Heating cfm: 993 umace,Heat pump,Boiler,etc, Alt ondittoner,Heat pump,etc. Cooling cfm: 993 Model: Ruud Model: Ruud Static pressure: 40 in H2O UPQL-030JAZ UPQL-030JAZ Fan's rated external static pressure for design airflow Heating output capacity: 0 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winter design outdoor conditions Sensible cooling capacity: 0 Btuh Aux.heating output capacity: 28312 Btuh Latent cooling capacity: 0 Btuh HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Design airflow: 993 cfm Longest supply duct: 0 ft Duct Materials Used Equipment design ESP: 0.40 in H2O Longest return duct: 0 ft Trunk duct: Total device pressure losses: -0.2 in H2O Total effective length(TEL): 0 ft Available static pressure(ASP): 0.22 in H2O Friction rate: g in/100ft Branch duct: Round flex vinyl Friction Rate=ASP+(TEL x 10 0) I declare the load calculation.equipment.equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: 1\r 0 0- c , c • Contractor's signature: ` _P 's Date: Reserved for County.Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist -1-1+ wrightsoft Right-Suite®Universal 2015 15.0 18 RSU12595 m Residential Plans Examiner Review Form Form �- RPER 1 ACCA for HVAC System Design (Loads. Equipment, Ducts) 15Mar09 n.ccraQ. raas g Cad (0mm 261400 III Header Information Contractor: REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes ❑ No 0 Mechanical license: or MJ1AE Form*(and supporting worksheets): Yes ❑ No ❑ OEM performance data(heating,cooling,blower): Yes II No 0 Building plan#: Manual D Friction Rate Worksheet: Yes 0 No ❑ Duct distribution sketch: Yes 0 No O Home address(Street or Lot#,Block,Subdivision): 384 1st Street, guest HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: 32 °F Orientation: Front Door faces North Indoor temperature: 68 °F North,East,West,South,Northeast,Northwest,Southeast,Southwest Total heat loss: 11242 Btuh Number of bedrooms: 3 Conditioned floor area: 583 ft2 Summer Design Conditions Number of occupants: 2 Outdoor temperature: 93 °F Indoor temperature: 75 °F Windows Roof Grains difference: 52 gr./lb @50% RH Eave overhang depth: 0 ft Sensible heat gain: 13459 Btuh Internal shade: none Eave Latent heat gain: 2030 Btuh Blinds,drapes,etc. Depth ;,n:iov. Total heat gain: 15489 Btuh Number of skylights: 0 HVAC EQUIPMENT SELECTION (IRC M1401.3) Heating Equipment Data Cooling Equipment Data Blower Data Equipment type: Split ASHP Equipment type: Split ASHP Heating cfm: 573 umace,Heat pump,Boiler,etc. Et' ondioner,Heat pump,etc. Cooling cfm: 573 Model: Ruud Model: Ruud Static pressure: 0.40 in H2O 15PJL18+CF025SDEB++TXV+TDR 15PJL18+CF025SDEB++TXV+TDR Fan's rated extemalstaT icpr pressure for design airflow Heating output capacity:. 0 Btuh Total cooling capacity: 0 Btuh Heat pumps-capacity at winter design outdoor conditions Sensible cooling capacity: 0 Btuh Aux. heating output capacity: 11576 Btuh Latent cooling capacity: 0 Btuh HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1) Design airflow: 573 cfm Longest supply duct: 107 ft Duct Materials Used Equipment design ESP: 0.40 in H2O Longest return duct: 69 ft Trunk duct: Total device pressure losses: -0.3 in H2O Total effective length(TEL): 176 ft Available static pressure(ASP): 0.15 in H2O Friction rate: 0 085 in/100ft Branch duct: Round flex vinyl Friction Rate=ASP+(T x 1 ) I declare the load calculation.equipment.equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification ■ Contractor's printed name: In CC,■ Cee\ Contractor's signature: g 4 J '' t Date: Reserved for County.Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist +I+ wrightsoft Right-Suite®Universal 2015 15.0 18 RSU12595 Job: ECH253815 Monica Bacca Load Short Form Date: Sep 15,2015 Nick's Solar and Air Systems main By: Monica S.Bacca . Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Design Information Htg Clg Infiltration Outside db(°F) 32 93 Method Simplified Inside db (°F) 68 75 Construction quality Average Design TD (°F) 36 18 Fireplaces 0 Daily range - M Inside humidity (%) 50 50 Moisture difference(gr/Ib) 30 52 HEATING EQUIPMENT COOLING EQUIPMENT Make Ruud Make Ruud Trade RUUD UPQL SERIES Trade RUUD UPQL SERIES Model UPQL-030JAZ Cond UPQL-030JAZ AHRI ref 5674075 Coil RCFL-H*3621+RGLT-07(E,N)AMKR AHRI ref 5674075 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 20860 Btuh Heating output 28200 Btuh @ 47°F Latent cooling 8940 Btuh Temperature rise 26 °F Total cooling 29800 Btuh Actual air flow 993 cfm Actual air flow 993 cfm Air flow factor 0.035 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.83 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) B R 1 272 4572 2572 158 110 Bth1/Closet 85 693 280 24 12 Rear hall/CI 90 1194 1167 41 50 Kitchen 220 3139 3851 108 165 DR 140 1593 2177 55 93 Living Room 575 10751 8924 371 382 Bth2/Closet 140 1419 845 49 36 BR2 224 4335 2815 150 121 Hall 130 1052 554 36 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. htsoft 2015-Sep-18 10 age 2 W PI 9 Right-Suited Universal 2015 15.0.18 RSU12595 Page 2 ...ca\Documents 1Wnghtsoft HVAC\Demo\ECH253815 rup Caic=MJ8 Front Door faces: N main d 1876 28748 23186 993 993 Other equip loads 0 0 Equip. @ 0.98 RSM 22676 Latent cooling 4799 TOTALS 1876 28748 27474 993 993 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2015-Sep-18 10 37:57 9 Right-Suite®Universal 2015 15.0 18 RSU12595 Page 3 . ...ca\Documents\Wrightsoft HVAC\Demo\ECH253815.rup Cale=MJ8 Front Door faces: N Load Short Form Job: S5 2 Monica Bacca Date: Sep ep 1 15,,20101 5 Nick's Solar and Air Systems guest By: Monica S.Bacca Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Design Information Htg Clg Infiltration Outside db (°F) 32 93 Method Simplified Inside db (°F) 68 75 Construction quality Average Design TD (°F) 36 18 Fireplaces 0 Daily range - M Inside humidity (%) 50 50 Moisture difference(gr/Ib) 30 52 HEATING EQUIPMENT COOLING EQUIPMENT Make Ruud Make Ruud Trade SUMMIT Trade SUMMIT Model 15PJL18 Cond 15PJL18 AHRI ref 5537044 Coil CF025SDEB++TXV+TDR AHRI ref 5537044 Efficiency 7.7 HSPF Efficiency 11.0 EER, 14 SEER Heating input Sensible cooling 12040 Btuh Heating output 16500 Btuh @ 47°F Latent cooling 5160 Btuh Temperature rise 26 °F Total cooling 17200 Btuh Actual air flow 573 cfm Actual air flow 573 cfm Air flow factor 0.051 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.87 ROOM NAME Area Htg load Cig load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Gst. BR 391 6297 5113 321 223 Gst.Bth 72 1239 599 63 26 Kitchenette 120 3706 7451 189 324 guest d 583 11242 13163 573 573 Other equip loads 0 0 Equip. @ 0.98 RSM 12874 Latent cooling 1985 TOTALS 583 11242 14859 573 573 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2015-Sep-18 10:37'57 +1+ wrightsoft Right-Suite®Universal 2015 15.0.18 RSU12595 Page 1 ...ca\Documents\Wrightsoft HVAC\Demo\ECH253815.rup Calc=MJ8 Front Door faces: N N ___i;/# '\ Level 1 • 0 75 dm IIBR1 BR2 ,,. 79 dm + Hall D 75 dm • . . Bthl/Cbset I. Bth2/Clo6et O50dm -ear haVCl o 36 dm '...-... 49 dm 1 1 _____ U 55 dm O 55 dm 1 47 dm Kitchen DR 47 dm I -444! C 96 din - "°96 dm Living Room VI 096 dm ' 096dm Job#: ECH253815 Scale: 1 : 114 Performed by Monica S. Bacca for: Page 2 Marco Residence Right-Suite®Universal 2015 384 1st Street 15.0.18 RSU12595 Jacksonville Beach, Fl 32233 2015-Sep-18 10:38:31 ...ightsoft HVAC\DemoECH253815.r... N e Level 2 t45 16'cfm Krtch: ette 9.. 107 din �..TM� cfm Gs, 4V 1040 573 dm .t.Bth 63 dm 107 cfm Job#: ECH253815 Scale: 1 : 114 Performed by Monica S. Bacca for: Page 1 Marco Residence Right-Suite®Universal 2015 384 1st Street 15.0.18 RSU12595 Jacksonville Beach, Fl 32233 2015-Sep-18 10:38:31 ...ightsoft HVAC\Demo\ECH253815.r... Duct System Summary Job: S5 2 Monica Bacca 1 Summary Date: Sep ep 1 15,,20101 5 Nick's Solar and Alr Systems main By: Monica S.Bacca • Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Heating Cooling External static pressure 0.40 in H2O 0.40 in H2O Pressure losses 0.18 in H2O 0.18 in H2O Available static pressure 0.22 in H2O 0.22 in H2O Supply/ return available pressure 0.110/0.110 in H2O 0.110/ 0.110 in H2O Lowest friction rate 0 in/100ft 0 in/100ft Actual air flow 993 cfm 993 cfm Total effective length (TEL) 0 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk BR1-A h 1286 79 55 0 0 Ox 0 VIFx 0 0 BR 1-B h 1286 79 55 0 0 Ox 0 VIFx 0 0 BR2 h 1407 75 60 0 0 Ox 0 VIFx 0 0 BR2-B h 1407 75 60 0 0 Ox 0 VIFx 0 0 Bthl/closet h 280 24 12 0 0 Ox 0 VIFx 0 0 Bth2/Closet h 845 49 36 0 0 Ox 0 VIFx 0 0 DR c 1088 28 47 0 0 Ox 0 VIFx 0 0 DR-A c 1088 28 47 0 0 Ox 0 VIFx 0 0 Hall-A h 554 36 24 0 0 Ox 0 VIFx 0 0 Kitchen c 1284 36 55 0 0 Ox 0 VIFx 0 0 Kitchen-A c 1284 36 55 0 0 Ox 0 VIFx 0 0 Kitchen-B c 1284 36 55 0 0 Ox 0 VIFx 0 0 Living Room-A c 2231 93 96 0 0 Ox 0 VIFx 0 0 Living Room-C c 2231 93 96 0 0 Ox 0 VIFx 0 0 Living Room-D c 2231 93 96 0 0 Ox 0 VIFx 0 0 Living Room-E c 2231 93 96 0 0 Ox 0 VIFx 0 0 Rear hall/CI c 1167 41 50 0 0 Ox 0 V1Fx 0 0 Return Branch Detail Table Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb6 Ox 0 993 993 0 0 0 0 Ox 0 VIFx Bold/italic values have been manually overridden 2015-Sep-18 10:37:57 -I-I+ wrightsoft Right-Suite®Universal 2015 15.0.18 RSU12595 Page 2 ...ca\Documents\Wrightsoft HVAC\Demo\ECH253815.rup Calc=MJ8 Front Door faces. N Duct System Summa Monica Bacca Y Summary Job: ECH253815 Date: Sep 15,2015 Nick's Solar and Air Systems guest By: Monica S.Bacca Project Information For: Marco Residence, Elite Custom Homes and Renovations Inc. 384 1st Street, Jacksonville Beach, Fl 32233 Heating Cooling External static pressure 0.40 in H2O 0.40 in H2O Pressure losses 0.25 in H2O 0.25 in H2O Available static pressure 0.15 in H2O 0.15 in H2O Supply / return available pressure 0.091 /0.059 in H2O 0.091 /0.059 in H2O Lowest friction rate 0.085 in/100ft 0.085 in/100ft Actual air flow 573 cfm 573 cfm Total effective length (TEL) 176 ft Supply Branch Detail Table Design Htg CIg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk Gst.BR-A h 2099 107 74 0.087 8.0 Ox 0 VIFx 10.0 95.0 Gst.BR-B h 2099 107 74 0.086 8.0 Ox 0 VIFx 11.7 95.0 Gst. BR-C h 2099 107 74 0.085 8.0 Ox 0 VIFx 12.2 95.0 Gst_Bth h 1239 63 26 0.089 6.0 Ox 0 VIFx 7.6 95.0 Kitchenette c 3726 94 162 0.086 9.0 Ox 0 VIFx 11.2 95.0 Kitchenette A c 3726 94 162 0.091 9.0 Ox 0 VIFx 5.4 95.0 Return Branch Detail Table Grill Htg CIg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb3 Ox 0 573 573 68.5 0.085 536 14.0 Ox 0 VIFx Bold/italic values have been manually overridden wrightsoft 2015-Sep-1810:37:57 9 Right-Suite®Universal 2015 15.0.18 RSU12595 Page e 1 ACC ...ca\Documents\Wrightsoft HVAC1Demo1ECH253815.rup Calc=MJ8 Front Door faces N