725 ATLANTIC BLVD UNIT 1 VET CLINIC Jacksonville Fire and Rescue Department FIRE PREVENTION DIVISION s ;�
PROJECT NAME: Atlanc East Animal Clinic
ADDRESS: 725 Atlanc Bv. #1
REVIEWED BY: Rey Escanio
DATE: 10/27/2015
Aer inial review,the following excepons were noted in your construcon plans submied to this
oce as part of the building/mechanical permit process:
1. Please correct or provide the following to obtain plans approval. When resubming corrected sheets,
please provide a wrien narrave leer responding to our comments and direcng the plans reviewer
to where the changes have taken place. Revised sheets should be clouded clearly showing areas were
changes or correcons have occurred. If this is an electronic submission please make sure that wrien
narrave is submied under correspondence. Failure to provide response leer will result in a return
for correcons plans review submission.
2. Please include in your code summary reference of applicable Fire Codes to those currently adopted.
Florida is currently using the 5th Edion of the Florida Fire Prevenon Code.Please provide the animal
housing facility subclassicaon per NFPA 150, 2009 edion, chapter 6. Please also provide the
categorizaon of animals per NFPA 150, 6.3.
3. Provide exit door tacle signage (Braille) per N.F.P.A. 101, 7.10.1.3. Provide light-frame truss-type
construcon idencaon signage per FAC 69A-60.0081 or wrien vericaon from a licensed
architect or engineer stang that such structure does not meet the denion of 69A-60.0081
4. Addional comments may be generated during review of resubmission.
PHONE: (904) 255 8560
214 N HOGAN ST. JACKSONVILLE, FLORIDA 32202 FAX: (904)255-8559