312 4TH ST - ENERGY SHEETS Regante 312 4th St HVAC Load Calculations for Bosco Custom Homes ElitaLSrAtWirl RHVAC HVAG LOADS Prepared By: Jason McDuffie Home Energy Services 2060 Davis Rd. Jacksonville, FL 32218 904 757-3569 Tuesday, June 16, 2015 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Regante 312 4th St Jacksonville,FL 32218 Page 2 Project Report General Project Information Project Title: Regante 312 4th St Designed By: Alexa Laughren Project Date: Tuesday, June 16, 2015 Project Comment: This equipment can be replaced in name or by equal or greater SEER or HSFP as stated on the FL. Energy Code Client Name: Bosco Custom Homes Company Name: Home Energy Services Company Representative: Jason McDuffie Company Address: 2060 Davis Rd. Company City: Jacksonville, FL 32218 Company Phone: 904 757-3569 Company E-Mail Address: ecalcs @hesjax.com Company Website: www.hesjax.com Company Comment: to Reference City: Jacksonville, Florida Building Orientation: Front door faces North Daily Temperature Range: Medium Latitude: 30 Degrees Elevation: 26 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 32 29.92 n/a n/a 70 n/a Summer: 95 77 45% 50% 75 46 Check Figures Total Building Supply CFM: 1,142 CFM Per Square ft.: 0.645 Square ft. of Room Area: 1,770 Square ft. Per Ton: 742 Volume (ft3)of Cond. Space: 14,156 Building Loads Total Heating Required Including Ventilation Air: 22,425 Btuh 22.425 MBH Total Sensible Gain: 25,097 Btuh 88 % Total Latent Gain: 3,527 Btuh 12 % Total Cooling Required Including Ventilation Air: 28,624 Btuh 2.39 Tons (Based On Sensible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads .� Elite Software Development,Inc. Home Energy Services Regante 312 4th St Jacksonville.FL 32218 RS Page 3 Miscellaneous Report System 1 Main Outdoor Outdoor Outdoor Indoor Indoor Grains Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb _ Difference Winter: 32 29.92 80% n/a 70 n/a ' Summer: 95 77 45% 50% 75 46.43 System 2 2nd Floor Outdoor Outdoor Outdoor Indoor Indoor r- rains' Input Data Dry Bulb Wet Bulb Rel.Hum Rel.Hum D r,Bulb Difference Winter: 32 29.92 80% n/a 70 n/a Summer: 95 77 45% 50% 75 46.43 Duct Sizing Inputs _.... Main Trunk Runouts J Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.01000 0.01000 Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft. Minimum Velocity: 550 ft./min 450 ft./min Maximum Velocity: 600 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. O u tside Air Data - _ Winter Summer Infiltration Specified: 0.250 AC/hr 0.250 AC/hr 59 CFM 59 CFM Infiltration Actual: 0.250 AC/hr 0.250 AC/hr Above Grade Volume: X 14.156 Cu.ft. X 14.156 Cu.ft. 3,539 Cu.ft./hr 3,539 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 59 CFM 59 CFM Total Building Ventilation: 0 CFM 0 CFM ---System 1-- Infiltration &Ventilation Sensible Gain Multiplier: 21.98 = (1.10 X 0.999 X 20.00 Summer Temp. Difference) Infiltration &Ventilation Latent Gain Multiplier: 31.54 = (0.68 X 0.999 X 46.43 Grains Difference) Infiltration &Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 AC/hr(30 CFM) Summer Infiltration Specified: 0.250 AC/hr(30 CFM) ---System 2--- Infiltration &Ventilation Sensible Gain Multiplier: 21.98 = (1.10 X 0.999 X 20.00 Summer Temp. Difference) Infiltration &Ventilation Latent Gain Multiplier: 31.54 = (0.68 X 0.999 X 46.43 Grains Difference) Infiltration &Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference) Winter Infiltration Specified: 0.250 AC/hr(29 CFM) Summer Infiltration Specified: 0.250 AC/hr(29 CFM) Duct Load Factor Scenarios for System 1 Attic Duct Duct Surface From No. Type Description Location Ceiling Leakage Insulation Area [T]MDD 1 Supply Main Attic 16B 0.09 6 239 No 1 Return Main Attic 16B 0.15 6 44 No Duct Load Factor Scenarios for System 2 Attic Duct Duct Surface From No. Type Description Location Ceiling Leakage Insulation Area [T]MDD 1 Supply Main Attic 16B 0.09 6 239 No 1 Return Main Attic 16B 0.15 6 44 No C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services I Regante 312 4th St Jacksonville. FL 32218 i Page 4 Load Preview Report Net ft.' Sen Lat Net Sen Sy C s Sys Duct Scope Ton /Ton Area Gain Gain Gain Loss CFM CFM CFM Size Building 2.39 742 1,770 25,097 3,527 28,624 22,425 453 1,142 1,142 System 1 1.34 661 885 13,901 2,164 16,065 13,369 270 632 632 14 Duct Latent 432 432 Zone 1 885 13,901 1,732 15,633 13,369 270 632 632 14 1-Foyer 140 1,092 203 1,295 2,968 60 50 50 1-4 2-Bath 1 72 0 0 0 0 0 0 0 0-0 3-Bedroom 1 175 3,216 121 3,337 2,012 41 146 146 2-5 4-Living 306 5,342 938 6,280 4,778 97 243 243 2-7 5-Kitchen 192 4,251 470 4,721 3,610 73 193 193 2-6 System 2 1.05 845 885 11,196 1,363 12,559 9,057 183 509 509 14 Duct Latent 433 433 Zone 1 885 11,196 930 12,126 9,057 183 509 509 14 6-2nd Floor Landing 144 337 0 337 256 5 15 15 1-4 7-Bath 3 50 117 0 117 89 2 5 5 1-4 8-Bedroom4 154 2,253 108 2,361 1287 26 102 102 1-6 9-Br 4 WIC 30 71 0 71 53 1 3 3 1-4 10-Br 3 WIC 30 946 59 1,005 625 13 43 43 1-4 11-Bedroom 3 132 1,843 217 2.060 1,903 38 84 84 1-5 12-M WIC 40 266 49 315 368 7 12 12 1-4 13-Master Bedroom 196 2,999 276 3,275 2,371 48 136 136 2-5 14-Master Bath 109 2,365 221 2,586 2,106 43 108 108 1-6 C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services ' Regante 312 4th St Jacksonville.FL 32218 _ Page 5 Duct Size Preview Room or Source Minimum Maximum Rough. Design SP Duct Duct Htg Clg Act. Duct Duct Name Velocity Velocity Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 Supply Runouts Zone 1 1-Foyer Built-In 450 750 0.01 0.1 569.6 60®50 50 1-4 2-Bath 1 Built-In 450 750 0.01 0.1 0 0 1111,0 0 0-0 3-Bedroom 1 Built-In 450 750 0.01 0.1 536.5 41 X146 146 2-5 4-Living Built-In 450 750 0.01 0.1 454.7 97 243 243 2-7 5-Kitchen Built-In 450 750 0.01 0.1 492.5 73 193 193 2-6 Other Ducts in System 1 Supply Main Trunk Built-In 550 600 0.01 0.1 591.6 270 632 632 14 System 2 Supply Runouts Zone 1 6-2nd Floor Landing Built-In 450 750 0.01 0.1 175.5 5 15 15 1-4 7-Bath 3 Built-In 450 750 0.01 0.1 61 2 5 5 1-4 8-Bedroom 4 Built-In 450 750 0.01 0.1 522 26 102 102 1-6 1 9-Br 4 WIC Built-In 450 750 0.01 0.1 36.8 1 1114. 3 3 1-4 10-Br 3 WIC Built-In 450 750 0.01 0.1 493.3 13 R43 43 1-4 11-Bedroom 3 Built-In 450 750 0.01 0.1 614.9 38 1.84 84 1-5 12-M WIC Built-In 450 750 0.01 0.1 138.7 71E12 12 1-4 13-Master Bedroom Built-In 450 750 0.01 0.1 500.4 48 I.36 136 2-5 14-Master Bath Built-In 450 750 0.01 0.1 547.9 43 X108 108 1-6 Other Ducts in System 2 Supply Main Trunk Built-In 550 600 0.01 0.1 476.5 183 509 509 14 ---------------- --- Summary ............. System 1 Heating Flow: 270 Cooling Flow. 632 System 2 Heating Flaw: 183 Cooling Flow. 509 C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads --. Elite Software Development,Inc. Home Energy Services Regante 312 4th St Jacksonville.FL 32218 , Page 6 Total Building Summary Loads 1 Component Area Sen Lat Sen Total Description Quan Loss Gain Gain Gain 4A-6-o: Glazing-Double pane low-e (e =0.20 or less), 247.4 3,295 0 6,524 6,524 high performance, operable window, e=0.05 on surface 2, any frame, u-value 0.35, SHGC 0.3 11J: Door-Metal- Fiberglass Core 20.1 458 0 374 374 12C-Osw: Wall-Frame, R-13 insulation in 2 x 4 stud 1260.5 4,358 0 3,041 3,041 cavity, no board insulation, siding finish, wood studs 16B-30: Roof/Ceiling-Under Attic with Insulation on Attic 884.5 1,075 0 1,556 1,556 Floor(also use for Knee Walls and Partition Ceilings), Vented Attic, No Radiant Barrier, Dark Asphalt Shingles or Dark Metal, Tar and Gravel or Membrane, R-30 insulation 22A-ph: Floor-Slab on grade, No edge insulation, no 97 5,006 0 0 0 ■ insulation below floor, any floor cover, passive, heavy moist soil Subtotals for structure: 14,192 0 11,495 11,495 People: 4 800 920 1,720 Equipment: 0 5,800 5,800 Lighting: 0 0 0 Ductwork: 5,770 865 5,587 6,452 Infiltration: Winter CFM: 59, Summer CFM: 59 2,463 1,862 1,295 3,157 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 Total Building Load Totals: 22,425 3,527 25,097 28,624 Check Figures iiiiiiiiikeL Total Building Supply CFM: 1,142 CFM Per Square ft.: 0,645 Square ft. of Room Area: 1,770 Square ft. Per Ton: 742 Volume (ft3)of Cond. Space: 14,156 Building Loa•s':, Total Heating Required Including Ventilation Air: 22,425 Btuh 22.425 MBH Total Sensible Gain: 25,097 Btuh 88 % Total Latent Gain: 3,527 Btuh 12 % Total Cooling Required Including Ventilation Air: 28,624 Btuh 2.39 Tons(Based On Sensible + Latent) Notes Migir .. Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. I C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Regante 312 4th St Jacksonville.FL 32218 i Page 7 Building Pie Chart Infiltration 11% Floor 22% Building Roof 5% Ductwork 26% Loss 22,425 Btuh Wall 19% Door 2% Glass 15% Roof 5 0 o Infiltration 11% Wall 11% Ductwork 23% Building Gain 28,624 Glass 23% Btuh Door 1% People 6% Equipment 20% C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development, Inc. Home Energy Services Regante 312 4th St Jacksonville. FL 32218 '�1 Page 8 System 1 Room Load Summary Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sy No Name SF Btuh CFM Size Vel Btuh Btuh CFM ---Zone 1--- 1 Foyer 140 2,968 60 1-4 570 1,092 203 50 50 2 Bath 1 72 0 0 0-0 0 0 0 0 0 3 Bedroom 1 175 2,012 41 2-5 537 3,216 121 146 146 4 Living 306 4,778 97 2-7 455 5,342 938 243 243 5 Kitchen 192 3,610 73 2-6 492 4,251 470 193 193 Duct Latent 432 System 1 total 885 13,369 270 13,901 2,164 632 632 System 1 Main Trunk Size: 14 in. Velocity: 592 ft./min Loss per 100 ft.: 0.071 in.wg Cooling System Summary Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 1.34 87% / 13% 13,901 2,164 16,065 Actual: 1.48 75%/25% 13,350 4,450 17,800 Equipment Data Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: 25HCD418A*030 25HCD418A*030 Indoor Model: FB4CNP018L Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.2 HSPF 14 SEER Sound: 0 0 Capacity: 17,600 Btuh 17,800 Btuh Sensible Capacity: n/a 13,350 Btuh Latent Capacity: n/a 4,450 Btuh AHRI Reference No.: n/a 7978287 C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Home Energy Services Regante 312 4th St Jacksonville.FL 32218 Page 9 System 2 Room Load Summary Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM ---Zone 1--- 6 2nd Floor Landing 144 256 5 1-4 176 337 0 15 15 7 Bath 3 50 89 2 1-4 61 117 0 5 5 8 Bedroom 4 154 1,287 26 1-6 522 2,253 108 102 102 9 Br 4 WIC 30 53 1 1-4 37 71 0 3 3 10 Br 3 WIC 30 625 13 1-4 493 946 59 43 43 11 Bedroom 3 132 1,903 38 1-5 615 1,843 217 84 84 12 M WIC 40 368 7 1-4 139 266 49 12 12 13 Master Bedroom 196 2,371 48 2-5 500 2,999 276 136 136 14 Master Bath 109 2,106 43 1-6 548 2,365 221 108 108 Duct Latent 433 System 2 total 885 9,057 183 11,196 1,363 509 509 System 2 Main Trunk Size: 14 in. Velocity: 477 ft./min Loss per 100 ft.: 0.046 in.wg Cooling System Summary IIIIIIr Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 1.05 89%/ 11% 11,196 1.363 12,559 Actual: 1.48 75%/25% 13,350 4,450 17,800 Equipment Data Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: 25HCD418A*030 25HCD418A*030 Indoor Model: FB4CNP018L Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.2 HSPF 14 SEER Sound: 0 0 Capacity: 17,600 Btuh 17,800 Btuh Sensible Capacity: n/a 13,350 Btuh Latent Capacity: n/a 4,450 Btuh AHRI Reference No.: n/a 7978287 C:\...\Regante 312 4th St.rh9 Tuesday, June 16, 2015, 12:56 PM FORM 405-10 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Regante 310 4th St Builder Name: Bosco Custom Homes Street: 310 4th Street Permit Office: Atlantic Beach City,State,Zip: Atlantic Beach,FL,32250- Permit Number: Owner: Jurisdiction: 261100 Design Location: FL,Jacksonville 1. New construction or existing Existing(Projecte 9. Wall Types(2028.0 sqft.) Insulation Area 2. Single family or multiple family Multi-family a.Frame Wood,Exterior R=13.0 1480.00 ft2 b.Frame-Wood,Common R=11.0 368.00 ft2 3. Number of units,if multiple family 1 c.Frame-Wood,Adjacent R=13.0 180.00 ft2 4. Number of Bedrooms 6 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (885.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 885.00 ft2 6. Conditioned floor area above grade(ft2) 1769.5 b.N/A R= ft2 c.N/A R= ft2 Conditioned floor area below grade(ft2) 0 11 Ducts R ft2 7. Wndows(262.2 sqft.) Description Area a.Sup:Attic,Ret:Main,AH:Main 6 176.95 a. U-Factor Dbl,U=0.33 262.20 ft2 b.Sup: Attic,Ret:2nd Floor,AH:2nd Floor 6 176.95 SHGC: SHGC=0.30 b. U-Factor N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 17.8 SEER:14.00 b.Central Unit 17.8 SEER:14.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 17.8 HSPF:8.20 SHGC: b.Electric Heat Pump 17.8 HSPF:8.20 Area Weighted Average Overhang Depth: 2.487 ft. Area Weighted Average SHGC: 0.300 14.Hot water systems 8. Floor Types (1770.0 sqft.) Insulation Area a.Electric Cap:40 gallons 0.940 0 a.Slab-On-Grade Edge Insulation R=0.0 885.00 ft2 b. Conservation features b.Floor Over Other Space R=0.0 885.00 ft2 None c.N/A R= ft2 15.Credits CF,Pstat Glass/Floor Area: 0.148 Total Proposed Modified Loads: 35.94 PASS Total Standard Reference Loads: 45.35 I hereby certify that the plans and specifications covered by Review of the plans and ::•''1THE stn...., this this calculation are in compliance with the Florida Energy specifications covered by this . , - 04,%. Code. calculation indicates compliance �c, y/o,. if. 11' e '.A9"r+ic`" with the Florida Energy Code. 'E. moll. ∎.%.0•: 4�a 'tr-- PREPARED BY: //�� '.' �. Before construction is completed ' 1 4 DATE: 6/16/2015 this building will be inspected for ?0 ...._n.-`•._ a compliance with Section 553.908 ':• *` I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code. • D WE 1'4•.• OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist - Compliance requires a roof absorptance test and a roof emittance test in accordance with 405.6.2 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 6 PROJECT Title: Regante 310 4th St Bedrooms: 6 Address Type: Street Address Building Type: User Conditioned Area: 1770 Lot# Owner: Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Bosco Custom Homes Rotate Angle: 0 Street: 310 4th Street Permit Office: Atlantic Beach Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Multi-family FL, 32250- New/Existing: Existing(Projected) Comment: CLIMATE / IECC Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block/ 885 7080 2 Block2 884.5 7076 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfiIID Finished Cooled Heated 1 Main 885 7080 Yes 3 1 1 Yes Yes Yes 2 2nd Floor 884.5 7076 No 0 5 1 Yes Yes Yes FLOORS # Floor Type _ Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio Main 118 ft 0 885 ft2 ____ 0.6 0 0.4 2 Floor Over Other Space 2nd Floor ____ ____ 885 ft2 0 0.3 0 0.7 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Flat Compositionshingles 888 ft2 38 ft2 Light 0.85 Yes 0.9 Yes 0 4.8 ATTIC # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 No attic Vented 300 885 ft2 N N 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 6 CEILING V # Ceiling Type _ Space R-Value Area Framing Frac Truss Type 1 Under Attic(Vented) 2nd Floor 30 885 ft2 0.11 Wood WALLS # n V / Adjacent wa Cavity Width Height Sheathing Framing Solar Below � Space R-Value Ft In Et In Area R-Value Fraction Absor_ Grade-°% 1 N Exterior Frame-Wood Main 13 5 0 8 0 40.0 ft2 0 0.23 0.8 0 2 E Exterior Frame-Wood Main 13 9.5 0 8 0 76.0 ft2 0 0.23 0.8 0 3 E Exterior Frame-Wood Main 13 9 0 8 0 72.0 ft2 0 0.23 0.8 0 4 E Exterior Frame-Wood Main 13 13 0 8 0 104.0 ft2 0 0.23 0.8 0 5 S Exterior Frame-Wood Main 13 14 0 8 0 112.0 ft2 0 0.23 0.8 0 6 S Exterior Frame-Wood Main 13 14 0 8 0 112.0 ft2 0 0.23 0.8 0 7 W Exterior Frame-Wood Main 13 19 0 8 0 152.0 ft2 0 0.23 0.8 0 8 W Exterior Frame-Wood Main 13 11 0 8 0 88.0 ft2 0 0.23 0.8 0 9 N Garage Frame-Wood Main 13 10 0 8 0 80.0 ft2 0 0.23 0.8 0 10 N Garage Frame-Wood Main 13 6 0 8 0 48.0 ft2 0 0.23 0.8 0 11 N Garage Frame-Wood Main 13 6.5 0 8 0 52.0 ft2 0 0.23 0.8 0 12 W Exterior Frame-Wood 2nd Floor 13 7 0 8 0 56.0 ft2 0 0.23 0.8 0 13 W Exterior Frame-Wood 2nd Floor 13 11 0 8 0 88.0 ft2 0 0.23 0.8 0 14 N Exterior Frame-Wood 2nd Floor 13 9 0 8 0 72.0 ft2 0 0.23 0.8 0 15 N Exterior Frame-Wood 2nd Floor 13 18 0 8 0 144.0 ft2 0 0.23 0.8 0 16 E Exterior Frame-Wood 2nd Floor 13 13.5 0 8 0 108.0 ft2 0 0.23 0.8 0 17 E Exterior Frame-Wood 2nd Floor 13 4 0 8 0 32.0 ft2 0 0.23 0.8 0 18 E Exterior Frame-Wood 2nd Floor 13 11.5 0 8 0 92.0 ft2 0 0.23 0.8 0 19 S Exterior Frame-Wood 2nd Floor 13 5 0 8 0 40.0 ft2 0 0.23 0.8 0 20 W Exterior Frame-Wood 2nd Floor 13 11.5 0 8 0 92.0 ft2 0 0.23 0.8 0 21 S Neighbor Frame-Wood Main 11 23 0 8 0 184.0 ft2 0 0.23 0.8 0 22 S Neighbor Frame-Wood 2nd Floor 11 23 0 8 0 184.0 ft2 0 0.23 0.8 0 DOORS / ,V # Ornt Door Type Space Storms U-Value Ft Width In Ft Heighln Area 1 N Insulated Main Metal .28 3 6.7 20.1 ft2 2 S Insulated Main Metal .28 3 6.7 20.1 ft2 WINDOWS Orientation shown is the entered,Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 E 2 Vinyl Low-E Double Yes 0.33 0.3 30.0 ft2 10 ft 0 in 1 ft 0 in None None 2 E 4 Vinyl Low-E Double Yes 0.33 0.3 40.0 ft2 1 ft 0 in 10 ft 0 in None None 3 W 8 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft2 7 ft 0 in 10 ft 0 in None None 4 W 12 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft2 1 ft 0 in 1 ft 0 in None None 5 N 14 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft2 1 ft 0 in 1 ft 0 in None None 6 N 15 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft2 1 ft 0 in 1 ft 0 in None None 7 N 15 Vinyl Low-E Double Yes 0.33 0.3 40.2 ft2 1 ft 0 in 1 ft 0 in None None 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 6 WINDOWS Orientation shown is the entered,Proposed orientation. Wall Overhang # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 8 E 16 Vinyl Low-E Double Yes 0.33 0.3 16.0 ft' 1 ft 0 in 1 ft 0 in None None 9 E 18 Vinyl Low-E Double Yes 0.33 0.3 16.0 ft' 1 ft 0 in 1 ft 0 in None None 10 S 19 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft' 1 ft 0 in 1 ft 0 in None None 11 W 20 Vinyl Low-E Double Yes 0.33 0.3 20.0 ft' 1 ft 0 in 1 ft 0 in None None GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 308 ft' 308 ft' 42 ft 8 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Best Guess .0003 1392.4 76.44 143.76 .2844 5.9018 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.2 17.8 kBtu/hr 1 sys#1 2 Electric Heat Pump None HSPF:8.2 17.8 kBtu/hr 2 sys#2 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER:14 17.8 kBtu/hr 534 cfm 0.75 1 sys#1 2 Central Unit None SEER: 14 17.8 kBtu/hr 534 cfm 0.75 2 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Main 0.94 40 gal 90 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft' DUCTS / ----Supply---- Return---- Air CFM 25 CFM25 HVAC# �/ # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 176.95 f Main 44.2375 Default Leakage Main (Default) (Default) 1 1 2 Attic 6 176.95 f 2nd Floor 44.2375 Default Leakage 2nd Floor (Default) (Default) 2 2 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 6 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Coolin [[ 1Jan [ ]1 Feb [[ ]]Mar r f Ma X]l Jun X]]Jul X]Au [[X]]Se [ ]Oct [ ]Nov [ Dec Heating [XJ Jan [X]Feb [X]Mar Apr r I May 4 1 Lunn ]Jul t l Aug [ )Sep [ ]Oct [X]Nov [X Dec Venting [ 11 Jan [ ]Feb [[X]]Mar X Apr [ May [[ ]Jun [ 'Jul ( ]Au [[ ]]Sep [X]Oct [X]Nov [ Dec ThermostatSchedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 6 FORM 405-10 Florida Code Compliance Checklist Florida Department of Business and Professional Regulations Residential Whole Building Performance Method ADDRESS: 310 4th Street PERMIT#: Atlantic Beach, FL, 32250- MANDATORY REQUIREMENTS SUMMARY-See individual code sections for full details. COMPONENT SECTION SUMMARY OF REQUIREMENT(S) ' CHECK Air leakage 402.4 To be caulked, gasketed, weatherstripped or otherwise sealed. Recessed lighting IC-rated as meeting ASTM E 283. Windows and doors = 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces: gasketed doors & outdoor combustion air. Must complete envelope leakage report or visually verify Table 402.4.2. Thermostat & 403.1 At least one thermostat shall be provided for each separate heating controls and cooling system. Where forced-air furnace is primary system, programmable thermostat is required. Heat pumps with supplemental electric heat must prevent supplemental heat when compressor can meet the load. Ducts 403.2.2 All ducts, air handlers, filter boxes and building cavities which form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section 503.2.7.2 of this code. 403.3.3 Building framing cavities shall not be used as supply ducts. Water heaters 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly marked circuit breaker (electric) or shutoff(gas). Circulating system pipes insulated to = R-2 + accessible manual OFF switch. Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level. No make-up air from attics, crawlspaces, garages or outdoors adjacent to pools or spas. Swimming Pools 403.9 Pool pumps and pool pump motors with a total horsepower(HP)of= 1 &Spas HP shall have the capability of operating at two or more speeds. Spas and heated pools must have vapor-retardant covers or a liquid cover or other means proven to reduce heat loss except if 70% of heat from site-recovered energy. Off/timer switch required. Gas heaters minimum thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters minimum COP=4.0. Cooling/heating 403.6 Sizing calculation performed & attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification required. Special equipment occasion cooling or heating capacity requires separate system or variable capacity system. Electric heat >10kW must be divided into two or more stages. Ceilings/knee walls 405.2.1 R-19 space permitting. 6/16/2015 2:23 PM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 6 of 6 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 79 The lower the EnergyPerformance Index, the more efficient the home. 310 4th Street, Atlantic Beach, FL, 32250- 1. New construction or existing Existing(Projecte 9. Wall Types Insulation Area 2. Single family or multiple family Multi-family a.Frame-Wood,Exterior R=13.0 1480.00 ft2 b.Frame-Wood,Common R=11.0 368.00 ft2 3. Number of units,if multiple family 1 c.Frame-Wood,Adjacent R=13.0 180.00 ft2 4. Number of Bedrooms 6 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area a.Under Attic(Vented) R=30.0 885.00 ft 2 6. Conditioned floor area(ft2) 1770 b.N/A R= ft2 7. Windows** Description Area c.N/A R= ft2 2 a. U-Factor: Dbl,U=0.33 262.20 ft2 11.Ducts R ft a.Sup:Attic,Ret:Main,AH:Main 6 176.95 SHGC: SHGC=0.30 b.Sup: Attic,Ret:2nd Floor,AH:2nd Floor 6 176.95 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 17.8 SEER:14.00 SHGC: b.Central Unit 17.8 SEER:14.00 d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 17.8 HSPF:8.20 Area Weighted Average Overhang Depth: 2.487 ft. b.Electric Heat Pump 17.8 HSPF:8.20 Area Weighted Average SHGC: 0.300 8. Floor Types Insulation Area 14.Hot water systems ft2 a.Electric Cap:40 gallons a.Slab-On-Grade Edge Insulation R=0.0 885.00 ft EF:0.94 b.Floor Over Other Space R=0.0 885.00 ft2 c.N/A R= ft2 b. Conservation features None 15.Credits CF,Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building ;:•� .... .... Construction through the above energy saving features which will be installed (or exceeded) �•0. in this home before final inspection. Otherwise, a new EPL Display Card will be completed :4�3";;;''� .'-` , '°r+ based on installed Code compliant features. :I mo. '`,,;"-„..`0 Builder Signature: Date: '•. a Address of New Home: City/FL Zip: .0 ` 4C D . *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. EnergyGaugee USA-FlaRes2010 Section 405.4.1 Compliant Software TABLE 402.4.2 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Regante 310 4th St Builder Name: Bosco Custom Homes Street: 310 4th Street Permit Office: Atlantic Beach City,State,Zip: Atlantic Beach,FL.32250- Permit Number: Owner: Jurisdiction: 261100 Design Location: FL.Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier Exterior thermal envelope insulation for framed walls is installed in substantial contact and continuous alignment with building envelope air barrier. Breaks or joints in the air barrier are filled or repaired. Air-permeable insulation is not used as a sealing material. Air-permeable insulation is inside of an air barrier. Ceiling/attic Air barrier in any dropped ceiling/soffit is substantially aligned with insulation and any gaps are sealed. Attic access (except unvented attic), knee wall door, or drop down stair is sealed. Walls Corners and headers are insulated. Junction of foundation and sill plate is sealed. Windows and doors Space between window/door jambs and framing is sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including Insulation is installed to maintain permanent contact with underside above-garage and of subfloor decking. cantilevered floors) Air barrier is installed at any exposed edge of insulation. Crawl space walls Insulation is permanently attached to walls. Exposed earth in unvented crawl spaces is covered with Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations. knee walls and flue shafts opening to exterior or unconditioned space are sealed. Narrow cavities Batts in narrow cavities are cut to fit, or narrow cavities are filled by sprayed/blown insulation. Garage separation Air sealing is provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures are air tight, IC rated, and sealed to drywall. Exception—fixtures in conditioned space. Plumbing and wiring Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing, or sprayed/blown insulation extends behind piping and wiring. Shower/tub on exterior wall Showers and tubs on exterior walls have insulation and an air barrier separating them from the exterior wall. Electrical/phone box on Air barrier extends behind boxes or air sealed-type boxes are installed. Common wall Air barrier is installed in common wall between dwelling units. HVAC register boots HVAC register boots that penetrate building envelope are sealed to subfloor or drywall. Fireplace _ Fireplace walls include an air barrier. EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software