Loading...
303 10TH ST - ENERGY SHEET , OFFICE COPY Residential System Sizing Calculation Summary Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Location for weather data: Jacksonville, FL -Defaults: Latitude(30.5) Altitude(30 ft.) Temp Range(M) Humidity data: Interior RH (50%) Outdoor wet bulb (77F) Humidity difference(49gr.) Winter design temperature(TMY3 99%) 29 F Summer design temperature(TMY3 99%) 95 F Winter setpoint 70 F Summer setpoint 75 F Winter temperature difference 41 F Summer temperature difference 20 F Total heating load calculation 41155 Btuh Total cooling load calculation 28452 Btuh Submitted heating capacity % of calc Btuh Submitted cooling capacity % of calc Btuh Total (Electric Heat Pump) 87.5 36000 Sensible(SHR = 0.75) 125.7 27000 Heat Pump + Auxiliary(0.0kW) 87.5 36000 Latent 129.0 9000 Total (Electric Heat Pump) 126.5 36000 WINTER CALCULATIONS Winter Heating Load (for 3073 sqft) Load component Load Window total 401 sqft 4932 Btuh ('A'alIsi22.6%)J Cdlmgs19.3%; Wall total 2942 sqft 9321 Btuh Door total 60 sqft 1132 Btuh Ceiling total 1952 sqft 3829 Btuh ( 4 nCOwsclz.rtii Floor total See detail report 10063 Btuh Infiltration 212 cfm 9557 Btuh Duct loss 2321 Btuh ( Guctsl5.6%i j Subtotal 41155 Btuh [Floors(.24.5%i Ventilation 0 cfm 0 Btuh TOTAL HEAT LOSS 41155 Btuh Coors 2'°roi ( InfiL123.2%; SUMMER CALCULATION Summer Cooling Load (for 3073 sqft) Load component Load Window total 401 sqft 7160 Btuh Wall total 2942 sqft 5031 Btuh Door total 60 sqft 856 Btuh CellingslSS°•b; Ceiling total 1952 sqft 2428 Btuh L windowsi252%) Floor total 0 Btuh Infiltration 159 cfm 3496 Btuh Infiltration 17.7%71 Internal gain 920 Btuh Duct gain 1585 Btuh Sens. Ventilation 0 cfm 0 Btuh Blower Load 0 Btuh Latentint(2.S%) Total sensible gain 21477 Btuh Doors(3.0°/oj g Int.Gain(3.2°h) Latent gain(ducts) 880 Btuh Latent gain(infiltration) 5295 Btuh Ducts(g 7%) Latent gain(ventilation) 0 Btuh —__�� Latent gain(internal/occupants/other) 800 Btuh ( Infil(30.9%; Total latent gain 6975 Btuh TOTAL HEAT GAIN 28452 Btuh EnergyGauge®Sysrbth D.Dew w brn yo. �, 8th Edition PREPARED BY: Y ON:rn•7knolyD.Gapwr,c+U$, �_ =T Gardner DATE: •m"y^ ��^ ..W.t.L'T. EnergyGauge®/USRCZB v4.0 Residential Window Diversity MidSummer Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Weather data for: Jacksonville - Defaults Summer design temperature 95 F Average window load for July 2502 Btuh Cooling setpoint 75 F Peak window load for July 3445 Btuh Summer temperature difference 20 F Excusion limit(130%0 of Ave.) 3252 Btuh Latitude 30.5 North Window excursion (July) 30 Btuh WINDOW Average and Peak Loads 1I,•Oa r 01M.ell0•MIND•MD•OM•MD•MO•0111.4■0•MI•1=0•MD•MO•MD•AIM•4 OM•SW••11;‘•all"IMO•MI•Obi 3.200 3.000 ` 2,800 .J `. 2.600 1 r 2.400 . ' % • 2.200 % ,. '• ..0 \0 00 , ` ,e 8 10 12 14 16 18 2 —•—• VindowLoad (Btuh) —•—• Llmltforexcursion 12 Hour Average Total July Window Load(Radiation and conduction) Warning: This application has glass areas that produce relatively large heat gains for part of the day. Variable air volume devices may be required to overcome spikes in solar gain for one or more rooms. A zoned system may be required or some rooms may require zone control. lU.rwi iv EnergyGauge®System Sizin for F-yloorida residees only PREPARED BY:T v• 0 �+ DATE: October 21, 2015 a EnergyGauge®/USRCZB v4.0 Residential Window Diversity October Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Weather data for: Jacksonville - Defaults Summer design temperature 95 F Average window load for October 2771 Btuh Cooling setpoint 75 F Peak window load for October 3806 Btuh Summer temperature difference 20 F Excusion limit(130% of Ave.) 3603 Btuh Latitude 30.5 North Window excursion (October) 117 Btuh WINDOW Average and Peak Loads ._._._._._._._._._._._._._._._._._I::: .AN"Mall._. 3.500 ■ '. • r, v' • J_ • V_ 2.500 • • 8 10 12 14 10 18 2� -•-• Window Load (6tr4— -•-• Limit for excursion 12 Hour Average • Total October Window Load(Radiation and conduction) Warning: This application has glass areas that produce relatively large heat gains for part of the day. Variable air volume devices may be required to overcome spikes in solar gain for one or more rooms. A zoned system may be required or some rooms may require zone control. rx EnergyGauge®System Sizing for Florida residence only PREPARED BY: Y� v• GAro r DATE: October 2015 EnergyGauge®/USRCZB v4.0 System Sizing Calculations - Winter Residential Load - Room by Room Component Details Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 Building Type: User 10/21/2015 Reference City: Jacksonville, FL (Defaults) Winter Temperature Difference: 41.0 F (TMY3 99%) Component Loads for Room#1: 1st Floor Window Panes/Type Frame U Orientation Area(sqft) X HTM= Load 1 2, NFRC 0.22 Vinyl 0.30 S 36.0 12.3 443 Btuh 2 2, NFRC 0.22 Vinyl 0.30 S 54.0 12.3 664 Btuh 3 2, NFRC 0.22 Vinyl 0.30 W 96.0 12.3 1181 Btuh 4 2, NFRC 0.22 Vinyl 0.30 W 36.0 12.3 443 Btuh 5 2, NFRC 0.22 Vinyl 0.30 N 24.0 12.3 295 Btuh 6 2, NFRC 0.22 Vinyl 0.30 E 8.0 12.3 98 Btuh 7 2, NFRC 0.22 Vinyl 0.30 E 12.0 12.3 148 Btuh 8 2, NFRC 0.22 Vinyl 0.30 E 24.0 12.3 295 Btuh Window Total 290.0(sqft) 3567 Btuh Walls Type Ornt. Ueff. R-Value Area X HTM= Load (Cav/Sh) 1 Frame-Wood -Adj (0.077) 19.0/0.0 331 3.17 1049 Btuh 2 Frame-Wood -Ext (0.077) 19.0/0.0 259 3.17 821 Btuh 3 Frame-Wood -Ext (0.077) 19.0/0.0 217 3.17 688 Btuh 4 Frame-Wood -Ext (0.077) 19.0/0.0 204 3.17 646 Btuh 5 Frame-Wood -Ext (0.077) 19.0/0.0 164 3.17 520 Btuh 6 Frame-Wood -Ext (0.077) 19.0/0.0 311 3.17 985 Btuh 7 Frame-Wood -Ext (0.077) 19.0/0.0 299 3.17 947 Btuh Wall Total 1785(sqft) 5655 Btuh Doors Type Storm Ueff. Area X HTM= Load 1 Insulated - Garage, n (0.460) 24 18.9 453 Btuh 2 Insulated - Exterior, n (0.460) 24 18.9 453 Btuh 3 Insulated - Exterior, n (0.460) 12 18.9 226 Btuh Door Total 60(sqft) 1132Btuh Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load 2 Unvent Attic/L/Shing (0.048) 1.0/19.0 831 2.0 1630 Btuh Ceiling Total 831(sqft) 1630Btuh Floors Type Ueff. R-Value Size X HTM= Load 1 Slab On Grade (1.180) 0.0 208.0 ft(perim.) 48.4 10063 Btuh Floor Total 1952 sqft 10063 Btuh Room Envelope Subtotal: 22047 Btuh Infiltration Type Wholehouse ACH Room Volume Wall Ratio CAM= Natural 0.45 19520 0.61 128.7 5798 Btuh Duct load Average sealed,Supply(R6.0-Cond.), Retum(R6.0-Cond.) (DLM of 0.000) 0 Btuh Room#1 Sensible Room Subtotal 27846 Btuh EnergyGauge®/USRCZB v4.0 Page 1 Manual J Winter Calculations Residential Load - Component Details (continued) Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 Building Type: User 10/21/2015 Component Loads for Room#2: 2nd Floor Window Panes/Type Frame U Orientation Area(sqft) X HTM= Load 9 2, NFRC 0.22 Vinyl 0.30 S 15.0 12.3 184 Btuh 10 2, NFRC 0.22 Vinyl 0.30 W 32.0 12.3 394 Btuh 11 2, NFRC 0.22 Vinyl 0.30 W 6.0 12.3 74 Btuh 12 2, NFRC 0.22 Vinyl 0.30 N 30.0 12.3 369 Btuh 13 2, NFRC 0.22 Vinyl 0.30 E 28.0 12.3 344 Btuh Window Total 111.0(sgft) 1365 Btuh Walls Type Ornt. Ueff. R-Value Area X HTM= Load (Cav/Sh) 8 Frame-Wood -Ext (0.077) 19.0/0.0 265 3.17 840 Btuh 9 Frame-Wood -Ext (0.077) 19.0/0.0 362 3.17 1147 Btuh 10 Frame-Wood - Ext (0.077) 19.0/0.0 158 3.17 501 Btuh 11 Frame-Wood - Ext (0.077) 19.0/0.0 372 3.17 1179 Btuh Wall Total 1157(sqft) 3666 Btuh Ceilings Type/Color/Surface Ueff. R-Value Area X HTM= Load 1 Unvent Attic/L/Shing (0.048) 1.0/19.0 1121 2.0 2199 Btuh Ceiling Total 1121(sqft) 2199Btuh Floors Type Ueff. R-Value Size X HTM= Load 2 Interior (1.180) 0.0 1121.0 sqft 0.0 0 Btuh Floor Total 1121 sqft 0 Btuh Room Envelope Subtotal: 7230 Btuh Infiltration Type Wholehouse ACH Room Volume Wall Ratio CFM= Natural 0.45 8968 0.39 83.4 3758 Btuh Duct load Average sealed,Supply(R6.0-Attic), Retum(R6.0-Attic) (DLM of 0.211) 2321 Btuh Room#2 Sensible Room Subtotal 13310 Btuh SYSTEM GROUPS (BLOCK LOADS) Heating Loads For System(s):1 , Block load 27846 Btuh Serving Rooms: 1 EnergyGauge®/USRCZB v4.0 Page 2 Manual J Winter Calculations Residential Load - Component Details (continued) Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 Building Type: User 10/21/2015 Heating Loads For System(s):2 Block load 13310 Btuh Serving Rooms: 2 kl/HOLE HOUSE TOTALS Subtotal Sensible Heat Loss 41155 Btuh Totals for Heating Ventilation Sensible Heat Loss 0 Btuh Total Heat Loss 41155 Btuh EQUIPMENT 1. Electric Heat Pump CARRIER#25HCD418/FV4CNF003 18000 Btuh 2. Electric Heat Pump CARRIER#25HCD418/FV4CNF003 18000 Btuh Key:Window types-NFRC(Requires U-Factor and Shading coefficient(SHGC)of glass as numerical values) or-Glass as'Clear'or'Tint'(Uses U-Factor and SHGC defaults) U-(Window U-Factor) ^^ HTM-(Manual] Heat Transfer Multiplier) Version 8 EnergyGauge®/USRCZB v4.0 Page 3 System Sizing Calculations - Summer Residential Load - Room by Room Component Details Bouy Family Project Title: 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Reference City: Jacksonville, FL Temperature Difference: 20.0F(TMY3 99%) Humidity difference: 49gr. Component Loads for Room#1: 1st Floor Type* Overhang Window Area(sqft) HTM Load Window Panes SHGC U InSh IS Ornt Len Hgt Gross Shaded Unshaded Shaded Unshaded 1 2 NFRC 0.22,0.30 No No S 1.3ft 5.0ft 36.0 17.6 18.4 11 13 417 Btuh 2 2 NFRC 0.22, 0.30 No No S 9.Oft 1.3ft 54.0 54.0 0.0 11 13 572 Btuh 3 2 NFRC 0.22, 0.30 No No W 10.0f 2.0ft 96.0 75.5 20.5 11 27 1357 Btuh 4 2 NFRC 0.22,0.30 No No W 1.3ft 3.Oft 36.0 0.0 36.0 11 27 978 Btuh 5 2 NFRC 0.22, 0.30 No No N 1.3ft 10.0f 24.0 0.0 24.0 11 11 254 Btuh 6 2 NFRC 0.22, 0.30 No No E 2.Oft 2.0ft 8.0 0.0 8.0 11 27 217 Btuh 7 2 NFRC 0.22, 0.30 No No E 2.0ft 2.Oft 12.0 0.0 12.0 11 27 326 Btuh 8 2 NFRC 0.22, 0.30 No No E 2.0ft 2.Oft 24.0 0.0 24.0 11 27 652 Btuh Window Total 290 (sqft) 4774 Btuh Walls Type U-Value R-Value Area(sqft) HTM Load Cav/Sheath 1 Frame-Wood-Adj 0.08 19.0/0.0 331.0 1.5 512 Btuh 2 Frame-Wood-Ext 0.08 19.0/0.0 259.0 1.7 448 Btuh 3 Frame-Wood-Ext 0.08 19.0/0.0 217.0 1.7 376 Btuh 4 Frame-Wood-Ext 0.08 19.0/0.0 204.0 1.7 353 Btuh 5 Frame-Wood-Ext 0.08 19.0/0.0 164.0 1.7 284 Btuh 6 Frame-Wood-Ext 0.08 19.0/0.0 311.0 1.7 538 Btuh 7 Frame-Wood-Ext 0.08 19.0/0.0 299.0 1.7 518 Btuh Wall Total 1785 (sqft) 3028 Btuh Doors Type Area (sqft) HTM Load 1 Insulated-Garage 24.0 14.3 342 Btuh 2 Insulated-Exterior 24.0 14.3 342 Btuh 3 Insulated-Exterior 12.0 14.3 171 Btuh Door Total 60 (sqft) 856 Btuh Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM Load 2 Unvented Attic/Light/Shingle 0.048 1.0/19.0 831.0 1.24 1034 Btuh Ceiling Total 831 (sqft) 1034 Btuh Floors Type R-Value Size HTM Load 1 Slab On Grade 0.0 1952(ft-perimeter) 0.0 0 Btuh Floor Total 1952.0 (sqft) 0 Btuh Zone Envelope Subtotal: 9692 Btuh Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Load Natural 0.34 19520 0.61 96.5 2121 Btuh Internal Occupants Btuh/occupant Appliance Load gain 2 X 230 + 0 460 Btuh Sensible Envelope Load: 12273 Btuh Duct load Average sealed,Supply(R6.0-Cond.),Retum(R6.0-Cond.) (DGM of 0.000) 0 Btuh Sensible Zone Load 12273 Btuh EnergyGauge®/USRCZB v4.0 Page 1 Manual J Summer Calculations Residential Load - Component Details (continued) Bouy Family Project Title: Climate:FL_JACKSONVILLE_INTL_ARPT 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Component Loads for Room#2: 2nd Floor Type* Overhang Window Area(sqft) HTM Load Window Panes SHGC U InSh IS Ornt Len Hgt Gross Shaded Unshaded Shaded Unshaded 9 2 NFRC 0.22, 0.30 No No S 1.3ft 2.0ft 15.0 14.9 0.1 11 13 159 Btuh 10 2 NFRC 0.22,0.30 No No W 1.3ft 2.0ft 32.0 0.0 32.0 11 27 869 Btuh 11 2 NFRC 0.22,0.30 No No W 1.3ft 2.0ft 6.0 0.0 6.0 11 27 163 Btuh 12 2 NFRC 0.22, 0.30 No No N 1.3ft 2.0ft 30.0 0.0 30.0 11 11 318 Btuh 13 2 NFRC 0.22, 0.30 No No E 1.3ft 2.0ft 28.0 0.0 28.0 11 27 760 Btuh Window Total 111 (sqft) 2270 Btuh _ Walls Type U-Value R-Value Area(sqft) HTM Load Cav/Sheath 8 Frame-Wood-Ext 0.08 19.0/0.0 265.0 1.7 459 Btuh 9 Frame-Wood-Ext 0.08 19.0/0.0 362.0 1.7 627 Btuh 10 Frame-Wood-Ext 0.08 19.0/0.0 158.0 1.7 273 Btuh 11 Frame-Wood-Ext 0.08 19.0/0.0 372.0 1.7 644 Btuh Wall Total 1157 (sqft) 2003 Btuh Ceilings Type/Color/Surface U-Value R-Value Area(sqft) HTM Load 1 Unvented Attic/Light/Shingle 0.048 1.0/19.0 1121.0 1.24 1395 Btuh Ceiling Total 1121 (sqft) 1395 Btuh _ Floors Type R-Value Size HTM Load 2 Interior 0.0 1121 (sqft) 0.0 0 Btuh Floor Total 1121.0 (sqft) 0 Btuh Zone Envelope Subtotal: 5667 Btuh Infiltration Type Wholehouse ACH Volume(cuft)Wall Ratio CFM= Load Natural 0.34 8968 0.39 62.6 1375 Btuh Internal Occupants Btuh/occupant Appliance Load gain 2 X 230 + 0 460 Btuh Sensible Envelope Load: 7502 Btuh Duct load Average sealed,Supply(R6.0-Attic),Retum(R6.0-Attic) (DGM of 0.211) 1585 Btuh Sensible Zone Load 9087 Btuh The following window Excursion will be assigned to the system loads. Windows i October excursion for System 1 117 Btuh July excursion for System 2 0 Btuh Excursion Subtotal: 117 Btuh EnergyGauge®/USRCZB v4.0 Page 2 Manual J Summer Calculations Residential Load - Component Details (continued) Bouy Family Project Title: Climate:FL_JACKSONVILLE_INTL_ARPT 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 Duct load 0 Btuh Sensible Excursion Load 117 Btuh EnergyGauge®/USRCZB v4 0 Page 3 • Manual J Summer Calculations Residential Load - Component Details (continued) Bouy Family Project Title: Climate:FL_JACKSONVILLE_INTL_ARPT 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 LSYSTEMROUPS (BLOCK LOADS) Sensible Envelope Load 12273 Btuh Window Excursion 117 Btuh Cooling Loads Sensible Duct Load (duct gain multiplier of 0.000) 0 Btuh (Includes 0 Btuh due to window excursion) Sensible ventilation 0 Btuh For System(s): Zone Sensible gain 12390 Btuh 1 Latent infiltration/ventilation gain 3213 Btuh Serving Zones: Latent duct gain 0 Btuh 1 Latent occupant gain 400 Btuh Latent other gain 0 Btuh Total block load 16003 Btuh Sensible Envelope Load 7502 Btuh Window Excursion 0 Btuh Cooling Loads Sensible Duct Load (duct gain multiplier of 0.211) 1585 Btuh Sensible ventilation 0 Btuh For System(s): Zone Sensible gain 9087 Btuh 2 Latent infiltration/ventilation gain 2083 Btuh Serving Zones: Latent duct gain 880 Btuh 2 Latent occupant gain 400 Btuh Latent other gain 0 Btuh Total block load 12449 Btuh EnergyGauge®/USRCZB v4.0 Page 4 Manual J Summer Calculations Residential Load - Component Details (continued) Bouy Family Project Title: Climate:FL_JACKSONVILLE_INTL_ARPT 303 10th Street The Bouy Residence Revised Atlantic Beach, FL 32233-0000 10/21/2015 WHOLE HOUSE TOTALS Sensible Envelope Load All Zones 19892 Btuh Sensible Duct Load 1585 Btuh Total Sensible Zone Loads 21477 Btuh Sensible ventilation 0 Btuh Blower 0 Btuh Whole House Total sensible gain 21477 Btuh Totals for Cooling Latent infiltration gain (for 49 gr. humidity difference) 5295 Btuh Latent ventilation gain 0 Btuh Latent duct gain 880 Btuh Latent occupant gain (4.0 people @ 200 Btuh per person) 800 Btuh Latent other gain 0 Btuh Latent total gain 6975 Btuh TOTAL GAIN 28452 Btuh EQUIPMENT 1. Central Unit CARRIER#25HCD418/FV4CNF003 18000 Btuh 2. Central Unit CARRIER#25HCD418/FV4CNF003 18000 Btuh *Key: Window types(Panes-Number and type of panes of glass) (SHGC-Shading coefficient of glass as SHGC numerical value) (U-Window U-Factor) (InSh-Interior shading device:none(No),Blinds(B),Draperies(D)or Roller Shades(R)) - For Blinds:Assume medium color, half closed ily For Draperies:Assume medium weave, half closed For Roller shades:Assume translucent, half closed (IS-Insect screen:none(N), Full(F)or Half('/)) (Ornt-compass orientation) 1_1 Version 8 EnergyGauge®/USRCZB v4.0 Page 5 ; - irorightsoft. Manual S Compliance Report Job: 1st Floor By: OFFICE COPY • Project Information For: Bouy Residence 303 10th St,Atlantic Beach, FL Cooling Equipment Desig Conditions Outdoor design DB: 92.7°F Sensible gain: 13471 Btuh Entering coil DB: 79.0°F Outdoor design WB: 77.1°F Latent gain: 3642 Btuh Entering coil WB: 64.5°F Indoor design DB: 75.0°F Total gain: 17113 Btuh Indoor RH: 50% Estimated airflow: 600 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCD418A*030+FV4CNF003 Actual airflow: 600 cfm Sensible capacity: 13920 Btuh 103%of load Latent capacity: 4080 Btuh 112% of load Total capacity: 18000 Btuh 105% of load SHR: 77% Heating Equipment Design Conditions Outdoor design DB: 32.5°F Heat loss: 13599 Btuh Entering coil DB: 66.2°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions • Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCD418A*030+FV4CNF003 Actual airflow: 600 cfm Output capacity: 18000 Btuh 132%of load Capacity balance: 28 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 600 cfm Output capacity: 3.8 kW 94%of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. • 2015-Dec-03 10:53:24 wrightsoft Right-Suite®Universal 2015 15.0.19 RSU17457 Page 1 Aailk ..,Bouy Residence,303 10th St,Atlantic Bch.rup Calc=MJ8 Front Door faces: S Job: Date: htsoft° Manual S Compliance Report at + " yirig 2nd Floor project information For: Bout'Residence 303 10th St, Atlantic Beach, FL Cooling Equipment Entering coil DB: 77.3°F Btuh Entering coil D B: 63.6°F Design Conditions Sensible gain: 14072 Btuh 92.7°F ain: 2571 Outdoor design DB: Latent gain: 16643 Btuh Indoor design design : 77.1°F Total gain: 600 ctu Indoor design DB: 75.0% Estimated airflow: Indoor RH: 50% Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP 600 Model: 25HCD418A*030+FV4CNF003 Manufacturer: Car cfm Actual airflow: 13920 Btuh 99%of load Sensible capacity: Btuh 159%of load Total 77% capacity: 4080 108%of load SHR: Latent s y' 18000 Btuh Totaal l capacity: Heating Equipment Design Conditions Heat loss: 8728 Btuh Entering coil DB: 67.0°F Outdoor design DB: 32.5°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Model: 25HCD418A*030+FV4CNF003 16 °I Carrier Capacity balance: Manufacturer: 600 cfm Actual airflow: Btuh 206% of load Capacity balance: -99 16 Output mentalth: 18000 0 Btuh Supplemental heat required: Backup equipment type: Elec strip Model: Manufacturer: 600 cfm Actual airflow: Output capacity: 1.9 kW 74%of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. wrightsoft' Right-Suite®universal 2015 RSU17457 1pf�pf�� ` 147 /K� ...,Bout'Residence,303 tom St,Atlantic Bcn.rup Cato=MJ8 Front Door faces: S A wri htsofta Project Summary Job: 9 1st Floor Date: By: Project Information For: Bouy Residence 303 10th St, Atlantic Beach, FL • Notes: Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 68 °F Inside db 75 °F Design TD 36 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 51 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 9879 Btuh Structure 8272 Btuh Ducts 3720 Btuh Ducts 5200 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 13599 Btuh Use manufacturer's data n Rate/swing multiplier 0.98 Infiltration Equipment sensible load 13162 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 1 (Average) Structure 2388 Btuh Ducts 1254 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft2) 1952 1952 Equipment latent load 3642 Btuh Volume (ft') 17568 17568 Air changes/hour 0.33 0.16 Equipment total load 16803 Btuh Equiv.AVF(cfm) 98 46 Req. total capacity at 0.75 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HCD418A*030 Cond 25HCD418A*030 AHRI ref Coil FV4CNF003 AHRI ref • Efficiency 8.2 HSPF Efficiency 12.0 EER, 14.5 SEER Heating input Sensible cooling 12600 Btuh Heating output 18000 Btuh @ 47°F Latent cooling 5400 Btuh Temperature rise 27 °F Total cooling 18000 Btuh Actual air flow 600 cfm Actual air flow 600 cfm Air flow factor 0.044 cfm/Btuh Air flow factor 0.045 cfm/Btuh, Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.79 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. •eZ,� WI'ilght�r+aft° Rig ht-Su ite®Universal201515.0.19 RSU17457 2015-Dec-0310:53:24 ik ..,Bouy Residence,303 10th St,Atlantic Bch.rup Calc=MJ8 Front Door faces: S Page 1 • '* wrightsoft K Job: .._ Project Summary 2nd Floor Byte: By: Project Information For: Bouy Residence 303 10th St, Atlantic Beach, FL Notes: Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db Outside db Inside db 68 °F Inside db 93 °F Design TD 36 °F 8 °F Design TD 1 18 °F Daily range M Relative humidity 50 % Moisture difference 51 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 5673 Btuh 10142 Btuh Ducts Structure Central vent(0 cfm) 3054 Btuh Ducts 3930 Btuh Humidification nt al vent(0 Central vent(0 cfm) 0 Btuh Piping 0 Btuh Blower 0 Btuh 0 Btuh Equipment load 8728 Btuh Use manufacturer's data n Rate/swing multiplier 0.98 Infiltration Equipment sensible load 13749 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 1 (Average) Structure 1712 Btuh Ducts 859 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft2) 1121 1121 Equipment latent load 2571 Btuh Volume (ft3) 11210 11210 Air changes/hour 0.30 0.14 Equipment total load Equiv.AVF (cfm) 56 26 Req. total capacity at 0.75 SHR 16 11.5 torah Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HCD418A*030 Cond 25HCD418A*030 AHRI ref Coil FV4CNF003 Efficiency AHRI ref Heating input 8.2 HSPF Efficiency 12.0 EER, 14.5 SEER Heating output 18000 Btuh @ 47°F Latent cooling 12600 Btuh temperature rise 27 °F Total cooling 5400 Btuh Actual air flow 600 cfm Actual air flow 18000 cfm Air flow factor 0.069 cfm/Btuh Air flow factor 600 cfm Static pressure 0 in H2O 0.043 in H2 cfm/Btuh Space thermostat Static pressure 0 in H2O Load sensible heat ratio 0.85 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. " WFlghtl:s0f`t Right-Suite®Universal 2015 15.0.19 RSU17457 2015-Dec-03 10:53:24 Page 2 .,Bouy Residence,303 10th Si,Atlantic Bch.rup Calc=MJ8 Front Door faces: S FORM R405-2014 TABLE 402.4.1.1 OFFICE COPY AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: The Bouy Residence Revised Builder Name: Lendry Homes LLC Street: 303 10th Street Permit Office: Atlantic Beach City, State,Zip: Atlantic Beach, FL,32233-0000 Permit Number Owner: Bouy Family Jurisdiction: 261100 Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. /r Rim joists Rim joists are insulated and include an air barrier. l/ Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. !/ Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping pping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. v ;, Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. G� Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. l/ Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or / air sealed boxes shall be installed. !/ HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. U Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors (/ 10/21/2015 11:06 AM EnergyGaugeCR®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 Florida Department of Business and Professional Regulations ' Residential Whole Building Performance and Prescriptive Methods ADDRESS: 303 10th Street Permit Number: Atlantic Beach, FL,32233-0000 MANDATORY REQUIREMENTS See individual code sections for full details. C 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) 0 display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law " [Section 553.9085, Florida Statues] requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components■""• installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the planC) and specifications submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix C. m C R402.4 Alr leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of 0 Sections R402.1 through R402.4.4. o R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The 13 , sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2, and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Where required by the code official,testing shall be conducted by an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures; 3. Interior doors, if installed at the time of the test, shall be open; 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Heating and cooling systems, if installed at the time of the test,shall be turned off;and 6. Supply and return registers, if installed at the time of the test, shall be fully open. O R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. o R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2), when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows, skylights and doors. O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. O R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. O R403.2.2 Sealing(Mandatory)All ducts, air handlers, and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99, Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa)across the entire system, including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25Pa)across the system, including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. rlJn lvi rv-r) v 14 MANDATORY REQUIREMENTS - (Continued) O R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. ❑ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105F(41`C) or below 55F(13'C)shall be insulated to a minimu m of R-3., o R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause degradation of the • material. Adhesive tape shall not be permitted. ❑ R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. ❑ R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 1/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. C R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies • R403.4.4.1 Storage water heater temperature controls _ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100T to 14 OF(38`C to 60C). . R403.4.4.1.2 Shut down. A separate switch or p c o a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. o R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. . R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential or Florida Building Code, Mechanical, as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. o R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1, Exception: Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. o R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics,crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise. ❑ R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. o R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors, provisions for future expansion or other factors which affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load, but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the cot inmant shall not he lace then the ramii atoll Intent Inert r'Jnivi n'iuD-cu 14 MANDATORY REQUIREMENTS - (Continued) 0 R403.6.1.1 Cooling equipment capacity. (continued) The published value for AHRI total capacity is a nominal, rating-test value and shall not be used for equipment sizing. Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment. This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. R403.6.1.2 Heating equipment capacity ▪ R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. . R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. - R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. o R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. • R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. • R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 55F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40`F. o R403.9 Swimming pools, inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through 8403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. o R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. ▪ R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions-Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. o R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters, pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. o R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or • at the water surface or a liquid cover or other means proven to reduce heat loss. • Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or • solar energy source computed over an operating season. G RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. C R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights ❑ R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. O R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19. Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space, R-10 is allowed. FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: The Bouy Residence Revised Builder Name: Lendry Homes LLC Street: 303 10th Street Permit Office: Atlantic Beach City, State,Zip: Atlantic Beach, FL, 32233-0000 Permit Number: Owner: Bouy Family Jurisdiction: 261100 Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(3403.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame Wood, Exterior R=19.0 3048.00 ft2 b. Frame-Wood, Adjacent R=19.0 355.00 ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (1952.0 sqft.) Insulation Area a. Roof Deck(Unvented) R=19.0 1952.00 ft2 6. Conditioned floor area above grade(ft2) 3073 b. N/A R= ft2 Conditioned floor area below grade(ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(401.0 sqft.) Description Area a. Sup: 1st Floor, Ret: 1st Floor,AH:Attic 6 614.6 a. U-Factor: Dbl, U=0.30 401.00 ft2 b. Sup: Attic, Ret:Attic, AH:Attic 6 307.3 SHGC: SHGC=0.22 b. U-Factor: N/A ft2 12. Cooling systems kBtu/hr Efficiency SHGC: a. Central Unit 18.0 SEER:14.50 c. U-Factor: N/A ft2 b. Central Unit 18.0 SEER:14.50 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Heat Pump 18.0 HSPF:8.20 SHGC: b. Electric Heat Pump 18.0 HSPF:8.20 Area Weighted Average Overhang Depth: 4.514 ft. Area Weighted Average SHGC: 0.220 14. Hot water systems a. Propane Tankless Cap: 1 gallons 8. Floor Types (3073.0 sqft.) Insulation Area EF:0.920 a.Slab-On-Grade Edge Insulation R=0.0 1952.00 ft2 b. Conservation features b. Floor Over Other Space R=0.0 1121.00 ft2 None c. N/A R= ft2 15.Credits Pstat Glass/Floor Area: 0.130 Total Proposed Modified Loads: 64.41 PASS SS Total Baseline Loads: 73.14 rf1 I hereby certify that the plans and specifications covered by Review of the plans and "�,.,THE ST...'' *; ,e• $04.•....... ...`91'' *y this calculation are in compliance with the Florida Energy specifications covered by this 1' \- ... c►;, . :gyp `c. Code. TlrpOtl I�/ D. Digitally 59�abyrmotnyo calculation indicates compliance �4v.•,.,��'��` 4 • `.s Gardner Dr1:�n=rmanyD Gardner, with the Florida Energy Code. i.,10/,,1 ';,.� �: mUS,o=USA HERS. .__ �:.. PREPARED BY: Before construction is completed �' , .,`Y.;,� Gardner p - •'� - emaiktim®usaher5.tom -•� ��..- DATE: Date.2015.102111:1509-0400' this building will be inspected for ¢.',i' ; .fy i compliance with Section 553.908 ,'.. I hereby certify that this building, as designed, is in compliance Florida Statutes. .. "e1;..•- r' ;•';S .` with the Florida Energ.ode. ., x,00..... -..;:a,...5.�,.�' OWNER/AGEN //�� ` - ---- / /!BUILDING OFFICIAL: ` DATE: i z e/ZG�5 DATE: /Z1i - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 10/21/2015 11:03 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 PROJECT Title: The Bouy Residence Revised Bedrooms: 3 Address Type: Street Address Building Type: User Conditioned Area: 3073 Lot# Owner: Bouy Family Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Lendry Homes LLC Rotate Angle: 0 Street: 303 10th Street Permit Office: Atlantic Beach Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233-0000 New/Existing: New(From Plans) Comment: CLIMATE / IECC Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Blockl 1952 19520 2 Block2 1121 8968 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Intl!ID Finished Cooled Heated 1 1st Floor 1952 19520 Yes 2 1 1 Yes Yes Yes 2 2nd Floor 1121 8968 No 2 2 1 Yes Yes Yes FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio 1st Floor 208 ft 0 1952 ft2 ____ 0.75 0 0.25 2 Floor Over Other Space 2nd Floor ____ ____ 1121 ft2 0 0 0.5 0.5 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Composition shingles 2183 ft2 488 ft2 Medium 0.85 No 0.9 No 19 26.6 V ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 1952 ft2 N N CEILING V # _Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Unvented) 2nd Floor 1 1121 ft2 0.11 Wood 2 Under Attic(Unvented) 1st Floor 1 831 ft2 0.11 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below # Ornt-.------To wall Type Space R-Value_- Ft In Ft-. In _-__Area-__...R-Value-Eraction___Absor__Grade%a_ 1 S Garage Frame-Wood 1st Floor 19 35 6 10 355.0 ft2 0.23 0.5 0 2 S Exterior Frame-Wood 1st Floor 19 29 6 10 295.0 ft2 0.23 0.75 0 3 S Exterior Frame-Wood 1st Floor 19 29 6 10 295.0 ft2 0.23 0.75 0 4 W Exterior Frame-Wood 1st Floor 19 30 10 300.0 ft2 0.23 0.75 0 5 • W Exterior Frame-Wood 1st Floor 19 20 10 200.0 ft2 0.23 0.75 0 6 N Exterior Frame-Wood 1st Floor 19 33 6 10 335.0 ft2 0.23 0.75 0 7 E Exterior Frame-Wood 1st Floor 19 35 6 10 355.0 ft2 0.23 0.75 0 8 S Exterior Frame-Wood 2nd Floor 19 35 8 280.0 ft2 0.23 0.75 0 - 9 W Exterior Frame-Wood 2nd Floor 19 50 8 400.0 ft2 0.23 0.75 0 10 N Exterior Frame-Wood 2nd Floor 19 23 6 8 188.0 ft2 0.23 0.75 0 11 E Exterior Frame-Wood 2nd Floor 19 50 8 400.0 ft2 0.23 0.75 0 DOORS V # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 S Insulated 1st Floor None .46 3 8 24 ft2 2 S Insulated 1st Floor None .46 3 8 24 ft2 3 E Insulated 1st Floor None .46 1 6 8 12 ft2 WINDOWS Orientation shown is the entered, Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 S 2 Vinyl Low-E Double Yes 0.3 0.22 36.0 ft2 1 ft 4 in 5 ft 0 in None None 2 S 3 Vinyl Low-E Double Yes 0.3 0.22 54.0 ft2 9 ft 0 in 1 ft 4 in None None 3 W 4 Vinyl Low-E Double Yes 0.3 0.22 96.0 ft2 10 ft 0 in 2 ft 0 in None None 4 W 5 Vinyl Low-E Double Yes 0.3 0.22 36.0 ft2 1 ft 4 in 3 ft 0 in None None 5 N 6 Vinyl Low-E Double Yes 0.3 0.22 24.0 ft2 1 ft 4 in 10 ft 0 in None None 6 E 7 Vinyl Low-E Double Yes 0.3 0.22 8.0 ft2 2 ft 0 in 2 ft 0 in None None 7 E 7 Vinyl Low-E Double Yes 0.3 0.22 12.0 ft2 2 ft 0 in 2 ft 0 in None None 8 E 7 Vinyl Low-E Double Yes 0.3 0.22 24.0 ft2 2 ft 0 in 2 ft 0 in None None 9 S 8 Vinyl Low-E Double Yes 0.3 0.22 15.0 ft2 1 ft 4 in 2 ft 0 in None None 10 W 9 Vinyl Low-E Double Yes 0.3 0.22 32.0 ft2 1 ft 4 in 2 ft 0 in None None 11 W 9 Vinyl Low-E Double Yes 0.3 0.22 6.0 ft2 1 ft 4 in 2 ft 0 in None None 12 N 10 Vinyl Low-E Double Yes 0.3 0.22 30.0 ft2 1 ft 4 in 2 ft 0 in None None 13 E 11 Vinyl Low-E Double Yes 0.3 0.22 28.0 ft2 1 ft 4 in 2 ft 0 in None None ...01.1111 1&TVV LSO I, GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 490 ft2 384 ft2 53.5 ft 9.5 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000295 2374 130.33 245.1 .2792 5 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts _ 1 Electric Heat Pump None HSPF:8.2 18 kBtu/hr 1 sys#1 2 Electric Heat Pump None HSPF:8.2 18 kBtu/hr 2 sys#2 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit Split SEER:14.5 18 kBtu/hr 540 cfm 0.75 1 sys#1 2 Central Unit Split SEER: 14.5 18 kBtu/hr 540 cfm 0.75 2 sys#2 HOT WATER SYSTEM ✓ # System Type SubType Location EF Cap Use SetPnt Conservation 1 Propane Tankless Exterior 0.92 1 gal 60 gal 120 deg None SOLAR HOT WATER SYSTEM V FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply---- ----Return--- Air CFM 25 CFM25 HVAC# V # Location R Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 1st Floor 6 614.6 ft 1st Floor 153.65 Default Leakage Attic (Default) (Default) 1 1 2 Attic 6 307.3 ft Attic 76.825 Default Leakage Attic (Default) (Default) 2 2 ■ TEMPERATURES Programable Thermostat:Y Ceiling Fans:At Venting Jan Feb F Mar lXJ Apr € May Jun Jul Aug Sep !XI Oct ix Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 rvnivi n'uo-eu I w ■ ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 88 The lower the EnergyPerformance Index, the more efficient the home. 1 , 303 10th Street, Atlantic Beach, FL, 32233-0000 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame Wood, Exterior R=19.0 3048.00 ft2 b. Frame-Wood, Adjacent R=19.0 355.00 ft2 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 3 d. N/A R= ft2 5. Is this a worst case? No 10. Ceiling Types Insulation Area a. Roof Deck(Unvented) R=19.0 1952.00 ft2 6. Conditioned floor area(ft2) 3073 b. N/A R= ft2 7. Windows" Description Area c. N/A R= ft2 a. U-Factor: Dbl, U=0.30 401.00 ft2 11. Ducts R ft2 a. Sup: 1st Floor, Ret: 1st Floor,AH:Attic 6 614.6 SHGC: SHGC=0.22 b. Sup: Attic, Ret:Attic,AH:Attic 6 307.3 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a. Central Unit 18.0 SEER:14.50 SHGC: b.Central Unit 18.0 SEER:14.50 d. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency a. Electric Heat Pump 18.0 HSPF:8.20 Area Weighted Average Overhang Depth: 4.514 ft. b. Electric Heat Pump 18.0 HSPF:8.20 Area Weighted Average SHGC: 0.220 8. Floor Types Insulation Area 14. Hot water systems Cap: 1 gallons a. Slab-On-Grade Edge Insulation R=0.0 1952.00 ft2 a. Propane EF:0.92 b. Floor Over Other Space R=0.0 1121.00 ft2 c. N/A R= ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) F:yoF ENE S 4...4 0.•* ,,,. in this home before final inspection. Otherwise, a new EPL Display Card will be completed :��3',,,, .� r '- ,t, r based on installed Code compliant features. ,,,,;,1-.. ..€ e/°;�="„�o _ .r,Pp" 74 : Builder Signature: Date:/z�/ / Address of New Horn e D - ? c ,° Q f .4-• .122.53 ...,.. v WE *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 10/21/2015 11:05 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1