Loading...
1679 ATLANTIC BEACH DR - ENERGY REPORTS 4. c ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report OFFICE COPY Reissued eissued August 2014 This report is subject to renewal August 2015. www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the Intemational Code Council=® DIVISION: 07 00 00—THERMAL AND MOISTURE pcf. The insulation's liquid components are supplied in PROTECTION nominally 55-gallon drums, labeled as "A" component or Section: 07 21 00—Thermal Insulation "B" component. The insulation components have a shelf life of six months when stored in unopened containers at REPORT HOLDER: temperatures between 70°F (21'C)and 90°F (32°C). SES FOAM 3.2 Surface-burning Characteristics: 4008 LOUETTA ROAD,#538 At a maximum thickness of 4 inches (102 mm) and a SPRING, TEXAS 77388-4405 nominal density of 0.5 pcf, the insulation has a flame- (713)239-0252 spread index of 25 or less and a smoke-developed index of www.sesfoam.com 450 or less when tested in accordance with ASTM E84. Thicknesses of up to 111/2 inches (292 mm) for wall EVALUATION SUBJECT: cavities and ceiling cavities are recognized based on room corner fire testing in accordance with NFPA 286, when SES FOAM 0.5 Ib SPRAY: SPRAY-APPLIED the insulation is covered with a minimum 1/2-inch-thick POLYURETHANE FOAM PLASTIC INSULATION (12.7 mm) gypsum board installed in accordance with the applicable code. 1.0 EVALUATION SCOPE 3.3 Thermal Resistance(R-values): Compliance with the following codes: The insulation has thermal resistance(R-values) at a mean ■ 2012 and 2009 Intemational Building Code(IBC) temperature of 75°F (24°C)as shown in Table 1. ■ 2012 and 2009 Intemational Residential Code(IRC) 3.4 Air Permeability: ■ 2012 and 2009 Intemational Energy Conservation The insulation, at a minimum thickness of 3 inches Code'(IECC) (76 mm), is considered air-impermeable in accordance ■ Other Codes(see Section 8.0) with IRC Section R202, based on testing in accordance with ASTM E283. Properties evaluated: 4.0 INSTALLATION ■ Surface-burning characteristics 4.1 General: ■ Physical properties SES Foam 0.5 Ib spray insulation must be installed in ■ Thermal resistance (R-values) accordance with the manufacturer's published installation ■ Attic and crawl space installation instructions and this report. A copy of the manufacturer's published installation instructions must be available at all ■ Air permeability times on the jobsite during installation. 2.0 USES 4.2 Application: SES Foam 0.5 Ib spray polyurethane foam plastic The insulation is spray-applied at the jobsite using a insulation is used as a nonstructural thermal insulating volumetric positive displacement pump as identified in the material in buildings of Type V-B (IBC) construction, and in SES Foam 0.5 Ib spray application manual. The insulation dwellings built under the IRC. The insulation is for use in components must be stored at temperatures between wall cavities and floor/ceiling assemblies, and in attics and 70°F (21'C) and 90°F (32°C) for several days before crawl spaces when installed as described in Section 4.4. application. The insulation must not be used in areas Under the IRC, the insulation may be used as air- that have maximum in-service temperatures greater than impermeable insulation when installed as described in 180°F (82°C). The insulation must not be used in Section 3.4. electrical outlet or junction boxes or in contact with water 3.0 DESCRIPTION (e.g., rain, condensation, ice, snow) or soil. The substrate 3.1 General: must be free of moisture, frost or ice, loose scales, rust, oil, grease or other surface contaminants. The insulation can SES Foam 0.5 Ib spray foam insulation is a two- be installed in one pass to the maximum thickness. The component, open cell, one-to-one-by-volume spray-applied spray-applied foam insulation must be protected from polyurethane foam system with a nominal density of 0.5 weather during and after installation. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICCEvaluation Service,LLC,express or implied,as to any finding or other matter in this report,or as to any product covered by the report. Copyright 0 2014 Page 1 of 3 ESR-3375 I Most Widely Accepted and Trusted Page 2 of 3 4.3 Thermal Barrier: 5.0 CONDITIONS OF USE SES Foam 0.5 Ib spray insulation must be separated from The SES Foam 0.5 Ib spray polyurethane foam plastic the interior of the building by an approved thermal barrier insulation described in this report complies with, or is a Of 1/2-inch-thick (12.7 mm) gypsum wallboard or an suitable alternative to what is specified in, those codes equivalent 15-minute thermal barrier complying with, and listed in Section 1.0 of this report, subject to the following installed in accordance with, IBC Section 2603.4 or IRC conditions: Section R316.4, as applicable. Within an attic or crawl 5.1 The insulation must be installed in accordance with space, installation must be in accordance with Section 4.4. the manufacturer's published installation instructions, 4.4 Attics and Crawl Spaces: this evaluation report and the applicable code. If there are any conflicts between the manufacturer's 4.4.1 Application with a Prescriptive Ignition Barrier: published installation instructions and this report, this When SES Foam 0.5 Ib spray is installed within attics and report governs. crawl spaces, where entry is made only for service of 5.2 The insulation must be separated from the interior of the utilities, an ignition barrier must be installed in accordance building by an approved 15-minute thermal barrier, as with IBC Section 2603.4.1.6 or IRC Section R316.5.3 or described in Section 4.3. Installation in an attic or R316.5.4, as applicable. The ignition barrier must be crawl space must be as described in Section 4.4. consistent with the requirements for the type of construction required by the applicable code, and must be 5.3 The insulation must not exceed the thicknesses noted installed in a manner so that the foam plastic insulation is in Sections 3.2 and 4.4. not exposed. SES Foam 0.5 Ib spray insulation at a 5.4 The insulation must be protected from exposure to the minimum thickness of 3 inches(76 mm) may be installed in weather during and after application. unvented attics in accordance with 2012 IRC Section R806.5 (2009 IRC Section R806.4), as applicable. 5.5 The insulation must be applied by contractors certified 4.4.2 Application without a Prescriptive Ignition by SES Foam. Barrier: Where the spray-applied insulation is installed in 5.6 Use of the insulation in areas where the probability of accordance with this section (Section 4.4.2) or Section termite infestation is "very heavy" must be in 4.4.3, the following conditions apply: accordance with 2012 IBC Section 2603.9 (2009 IBC Section 2603.8)or IRC Section R318.4, as applicable. a) Entry to the attic or crawl space is to service utilities, 5.7 Jobsite certification and labeling of the insulation must and no storage is permitted. comply with IRC Sections N1101.4 and N1101.4.1 b) There are no interconnected attic or crawl space and IECC Sections R303.1.1 and 303.1.1.1, as areas. applicable. c) Air in the attic or crawl space is not circulated to other 5.8 SES Foam 0.5 Ib spray polyurethane foam plastic parts of the building. insulation is produced in St. Louis, Missouri, under a quality control program with inspections by ICC-ES. d) Attic ventilation is provided when required by IBC 6.0 EVIDENCE SUBMITTED Section 1203.2 or IRC Section R806, except when air-impermeable insulation is permitted in unvented 6.1 Data in accordance with the ICC-ES Acceptance attics in accordance with 2012 IRC Section R806.5 or Criteria for Spray-applied Foam Plastic Insulation 2009 IRC Section R806.4. Under-floor (crawl space) (AC377), dated June 2012, including reports of tests ventilation is provided when required by IBC Section in accordance with Appendix X of AC377. 1203.3 or IRC Section R408.1, as applicable. 6.2 Report of room corner fire testing in accordance with e) Combustion air is provided in accordance with NFPA 286. International Mechanical Code°Section 701. 6.3 Report of air permeance testing in accordance with In attics, the insulation may be spray-applied to the ASTM E283. underside of roof sheathing or roof rafters, and/or vertical 7.0 IDENTIFICATION surfaces, and in crawl spaces the insulation may be spray- applied to the underside of floors and/or vertical surfaces Components of the SES Foam 0.5 Ib spray polyurethane foam plastic insulation are identified with the as described in this section. The thickness of the foam plastic applied to the underside of the top of the space manufacturer's name (SES Foam) and address; the date of manufacture or the lot number; the product trade name must not exceed 12 inches (305 mm). The thickness of the foam plastic applied to vertical surfaces must not exceed (SES Foam 0.5 Ib); the mixing instructions; the density;the 11'/2 inches (292 mm). The foam plastic may be installed flame-spread and smoke-developed indices; and the without a covering or coating. The insulation may be evaluation report number(ESR-3375). installed in unvented attics in accordance with 2012 IRC 8.0 OTHER CODES Section R806.5 (2009 IRC Section R806.4). The ignition In addition to the codes referenced in Section 1.0, the barrier in accordance with IBC Section 2603.4.1.6 or IRC products in the report were evaluated for compliance with Section R316.5.3 may be omitted. the requirements of the following codes: 4.4.3 Use on Attic Floors: SES Foam 0.5 Ib spray ■ 2006 International Building Code°(2006 IBC) insulation may be installed exposed at a maximum 2006 International Residential Code(2006 IBC) thickness of 11112 inches (292 mm) between joists in attic floors. The ignition barrier in accordance with IBC Section ■ 2006 and 2003 International Energy Conservation 2603.4.1.6 or IRC Section R316.5.3 may be omitted. The Code(2006 IECC) insulation must be separated from the interior of the building by an approved thermal barrier. ESR-3375 I Most Widely Accepted and Trusted Page 3 of 3 The products comply with the above-mentioned codes as provided in accordance with Sections 701 and 703 of described in Sections 2.0 through 7.0 of this report, with the 2006 IECC. revisions as noted below: ■ Protection against Termites: See Section 5.6, except ■ Application with a Prescriptive Thermal Barrier: See use of the insulation in areas where the probability of Section 4.3, except the approved thermal barrier must termite infestation if"very heavy" must be in accordance be installed in accordance with Section R314.4 of the with Section R320.5 of the 2006 IRC. 2006 IRC. ■ Jobsite Certification and Labeling: See Section 5.7, ■ Application with a Prescriptive Ignition Barrier: See except jobsite certification and labeling must comply Section 4.4.1, except an ignition barrier must be with Sections 102.1.1 and 102.1.1.1, as applicable, of installed in accordance with Section R314.5.3 or the 2006 IECC. R314.5.4 of the 2006 IRC. ■ Application without a Prescriptive Ignition Barrier: See Section 4.4.2, except that combustion air is TABLE 1—THERMAL RESISTANCE(R-VALUES'2) THICKNESS(inches) R-VALUE(°F•ft2•h/Btu) 1 4.0 2 7.6 3 11 3.5 13 4 15 5 19 6 22 7 26 8 30 9 33 10 37 11 41 12 44 For SI: 1 inch=25.4 mm, 1°F•ft2•h/Btu=0.176 110K•m2/W. 'R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. tICC EVALUATION lz�� SERVICE Most Wide[y Accepted . ICC-ES VAR Environmental Report VAR-1 030* Reissued July 2013 This report is subject to renewal September 1, 2015. www.icc-es.or-Wep 1 800-423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council° DIVISION: 07 00 00—THERMAL AND MOISTURE high-pressure, plural component SPF application PROTECTION equipment. The bio-based content is as set forth in Table 1 Section: 07 21 00—Thermal Insulation of this report. REPORT HOLDER: 4.0 CONDITIONS 4.1 Code Compliance: SES FOAM See ICC-ES report ESR-3375 for compliance of the SES 4008 LOUETTA ROAD, #538 Foam 0.5 Ib Foam S Polyurethane Foam Plastic Insulation SPRING, TEXAS 77388-4405 with code requirements. (713)239-0252 www.sesfoam.com 4.2 Green Codes, Standards and Rating Systems Eligibility: EVALUATION SUBJECT: The information presented in Tables 2 through 5 of this report provides a matrix of areas of evaluation and SES FOAM 0.5 Ib SPRAY POLYURETHANE FOAM corresponding limitations and/or additional project-specific PLASTIC INSULATION requirements, and offers benefits to individuals who are 1.0 EVALUATION SCOPE assessing eligibility for compliance. The final interpretation of the specific requirements of the Compliance with the following environmental criteria: code rests with the Authority Having Jurisdiction. ICC-ES Environmental Criteria for Determination of Compliance for items noted as "Verified Attribute" is Bio-based Material Content(EC102), dated March 1, 2012. subject to any conditions noted in the tables. Decisions on Compliance eligibility with the applicable sections of compliance for those items noted as "Eligible for Points" in the following codes and standards: Tables 2 through 5 rests with the user of this report, and those items are subject to the conditions noted. The user is ■ 2012 International Green Construction CodeTM (IgCC) advised of the project-specific provisions that may be (see Table 2 for details) contingent upon meeting specific conditions, and the ■ ASHRAE Standard 189.1 – 2009 (see Table 3 for verification of those conditions is outside the scope of this details) report. ■ National Green Building Standard (ICC 700-2008) (see Due to the variability of costs and volume, the bio-based Table 4 for details) content percentage listed in this report is based upon weight (mass). The use of cost or volume as the method ■ ANSI/GBI 01-2010, Green Building Assessment for calculation is outside the scope of this report. Protocol for Commercial Buildings (see Table 5 for 5.0 BASIS OF EVALUATION details) 2.0 USES The information in this report, including the "Verified Attributes," is based upon submission of documentation SES Foam 0.5 Ib Foam S Polyurethane Foam Plastic demonstrating compliance with the requirements set forth Insulation is used as nonstructural thermal insulating in ICC-ES EC102. (Evaluation applies to IgCC Section material in wall cavities, floor/ceiling assemblies, or in 505.2.4, item 3; ASHRAE 189.1 Section 9.4.1.3; ICC 700 attics and crawl spaces. See ICC-ES report ESR-3375 for Section 606.1;ANSI/GBI-01 Section 10.1.2.2.) more information on uses and applications. 6.0 IDENTIFICATION 3.0 DESCRIPTION Containers of SES Foam 0.5 Ib Foam S Polyurethane SES Foam 0.5 Ib spray-applied polyurethane foam plastic Foam Plastic Insulation are identified by a label bearing the insulation is a two-component, open-cell, water-blown, SES Foam name and address, product name, spray-applied polyurethane foam (SPF) with a nominal manufacturing date, manufacturing location and the VAR density of 0.5 Ib/ft3. The foam is sprayed in place using Environmental Report number(VAR-1030). 'Corrected May 2014 ICC-ES Verification of Attributes Reports are issued under the ICC-ES VAR Environmental Program."These reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied as to any finding or other matter in this report,or as to any product covered by the report. ram Copyright C 2014 Page 1 of 2 VAR-1030 1 Most Widely Accepted and Trusted Page 2 of 2 TABLE 1—BIO-BASED MATERIAL CONTENT SUMMARY PRODUCT NAME %MEAN BIO-BASED CONTENTMETHOD OF DETERMINATION SES Foam 0.5 Ib Spray Polyurethane Foam Plastic Insulation 17%(+/-3%)' ASTM D6866 Note: 'Based on precision and bias cited in ASTM D6866. TABLES 2 THROUGH 5 Section Possible Number Section Intent Points Conditions Of Use To Qualify For Points Finding TABLE 2—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2012 INTERNATIONAL GREEN CONSTRUCTION CODE Bio-based materials shall be those materials that comply with one or more of the following: 505.2.4 Bio-based content N/A 3.The requirements of USDA 7CFR Part 2902. • Note:USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 Ib Spray exceeds this minimum. TABLE 3—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2009 ASHRAE STANDARD 189.1 A minimum of 5%of building materials used,based on cost, shall be biobased products. Biobased products shall comply with the minimum biobased contents of the USDA's Designation of Biobased Items for Federal Procurement[7 CFR Part 2902],contain the 9.4.1.3 Biobased products N/A "USDA Certified Biobased Product"label,or be composed of solid wood,engineered wood,bamboo,wool,cotton,cork,agricultural fibers,or other biobased materials with at least 50%biobased content. Note: USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%). SES Foam 0.5 Ib Spray exceeds this minimum. TABLE 4—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2008 NATIONAL GREEN BUILDING STANDARD(ICC 700) The following biobased products are used: (h)products with the minimum biobased contents of the USDA 7 CFR Part 2902 606.1 Biobased products 3 (i)other biobased materials with a minimum of 50 percent biobased content(by weight 8 max or volume) Note: USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 Ib Spray exceeds this minimum. TABLE 5—SUMMARY OF AREA OF ELIGIBILITY WITH THE ANSI/GBI–01 (2010)STANDARD Bio-based products accounted for 1%or more of the materials used in the building. Percentage= 100 x A=6,where: A=Total cost or weight of bio-based products B=Total cost or weight of all building products 10.1.2.2 Materials content– 1 Cost or weight must be used consistently • Assemblies 7 max For USDA-designated products,products meeting or exceeding USDA's bio-based content,criteria or qualifying as USDA"BioPreferred"were used. Note: USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 Ib Spray exceeds this minimum. • =Verified attribute c EVALUATION N.-�8 c SERVICE Most • . Accepted .and Trusted ICC-ES Evaluation Report ESR-3375 Seal and Insulate with ENERGY STAR°Supplement Reissued August 2014 This report is subject to renewal August 2015. www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 21 00—Thermal Insulation REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING, TEXAS 77388-4405 (713)239-0252 www.sesfoam.com EVALUATION SUBJECT: SES FOAM 0.5 Ib SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION 1.0 EVALUATION SCOPE Conformance to the following: Seal and Insulate with ENERGY STAR® Program—Definitions and Testing Requirements for Residential Insulation, Version 1.0 Properties evaluated: ■ Thermal resistance ■ Surface-burning characteristics 2.0 PURPOSE OF THIS SUPPLEMENT This supplement is issued to certify that the insulation products described in Sections 2.0 through 8.0 of the master report ESR-3375 have been reviewed for compliance with the requirements of the Seal and Insulate with ENERGY STAR® Program, as set forth in the document Definitions and Testing Requirements for Residential Insulation, Version 1.0. The insulation product covered by this supplement is defined as"Spray or Pour Foam Insulation." The requirements for testing laboratory qualification and product sampling, as well as the specific material and test standards and editions used in this evaluation, are as set forth in the applicable documentation noted in Section 6.0 of the master evaluation report. 3.0 DEFINITIONS The following definitions are from Definitions and Testing Requirements for Residential Insulation, Version 1.0, and are applicable to the subject of this report. 3.1 General Definitions: Insulation: Any material mainly used to slow down heat flow. It may be mineral or organic, fibrous, cellular, or reflective (aluminum foil). It may be in rigid, semi-rigid,flexible, or loose-fill form. 3.2 Insulation Product Definitions: Spray or Pour Foam Insulation: A thermal insulating material that is sprayed or poured (as a gel or foamy liquid) into place, and expands or sets into a cellular foam and cures at the point of installation through a chemical reaction. Foamed materials include, but are not limited to polyurethane, polyisocyanurate, phenolic, and cementitious insulation. 3.3 Insulation Performance Definitions: R-value: The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area. For the purposes of the Seal and Insulate with ENERGY STAR®program, Imperial units will only be accepted[(h ft2•°F)/Btu]. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as to any finding or other matter in this report,or as to any product covered by the report. w�_ Copyright 0 2014 Page 1 of 6 ESR-3375 I Most Widely Accepted and Trusted Page 2 of 6 Smoke-Development Index: The characteristic of a material to emit smoke when exposed to flame or fire compared to red oak and inorganic cement. Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed to flame or fire compared to red oak and inorganic cement. 3.4 Thermal Resistance: The insulation has the thermal resistance R-values as noted in Table 1 of ESR-3375, based upon testing. 3.5 Installation: 3.5.1 General: The installation of the insulation must be in accordance with the requirements set forth in Sections 4.0 and 5.0 (as applicable) of ESR-3375. The insulation is manufactured on-site by spray polyurethane foam applicators meeting the qualification requirements of SES Foam. The following information on personal protective equipment and ventilation requirements is reprinted from the SES Foam published installation instructions: "F. SAFETY 3. PERSONAL PROTECTIVE EQUIPMENT(PPE): a. Skin: Wear gloves, coveralls, apron and boots as necessary to prevent contact of liquid components or partially-cured SPF with skin. When handling liquid components, gloves should be made of nitrile, neoprene, butyl or PVC. b. Eyes: Protect eyes while handling liquid components or spraying with safety goggles or safety goggles and a face shield. During spray application, eye protection may be provided by a full-face or hood respirator. c. Respiration: Firms engaged in the application of SES Foam systems must have a written respiratory protection program for employees engaged in handling or applying SES Foam materials. Depending on the situation, respiratory protection may include dust masks, air-purifying respirators (APR), powered air-purifying respirators (PAPR), or supplied- air respirators (SAR). 4. VENTILATION: Provide ventilation and other engineering controls to exhaust vapors from work areas and to protect building occupants and other trades." 3.5.2 Occupancy Time after Installation: The re-entry or re-occupancy time shall be in accordance with the manufacturer's installation instructions, which state the following: "E. RE-ENTRY SES Foam 0.5 Ib Spray reacts and cures within seconds of application. Re-entry times will vary depending on factors including ventilation. Typically, ventilation is continued for 24 hours following the conclusion of spray application and re-entry may occur at that time." 3.5.3 Figures: The figures shown represent general installations of the insulation in the following applications: above-grade wall, below-grade wall, vented and unvented crawl space, unvented cathedral ceiling, and vented and unvented attic. These figures are for illustration purposes and are not to be construed or used as construction documents. This supplement expires concurrently with the master report, reissued August 2014. ESR-3375 I Most Widely Accepted and Trusted Page 3 of 6 X °op0g00ogo0qoa0 gOgO0q0O0q0O00p00qqOqqp°OO gg00o°O0og00oq° q0o°°0oq°0oq°0oq°oq°0o°°00 0 0 o00go0o 0o0000000 000 q°° oq°po0gp ° oq°p Oo°°°q0 gOqOggo ° OOO (000 000 0p p00O WC; oo o°° gg000q0 0000 00 o0ogo 0 0 Interior Partition q00 qo 00000000 °000°00 Interior Finished Surface '0000000 (112-inch Sheetrock) gp000g4 00000000 000000 0 q0 q a00p000 SES Foam 0.51b Spray 00000000 00 0 qoq qo 00040°° Exterior Sheathing o0 000 00000 q qo SES FOAM 0.5 LB SPRAY ABOVE GRADE WALL INSULATION SES 05-1 071812 ESR-3375 I Most Widely Accepted and Trusted Page 4 of 6 000 0 Masonry Block 000 (Typical) 0 Interior Finish Surface 0 (1/2-inch Sheetrock) 0 C> 0 -�. * �- — 2"x 4"Studs 0 0 SES Foam 0.5 lb Spray o 0 SES FOAM 0.5 LB SPRAY BELOW GRADE WALL INSULATION(Insulation on Interior Side of Wall) SES 05-2 071812 Baffle to provide air space between Thermal insulation and roof Barrier* deck. (as required by local code) 0.00 °°°°°°°°°0000000... 000z'G -.600lo 000 °000°0°0°0°0°0°0°0°0°0°0.00 0 0 0000000 000000000 0 00 . 0 *0 o 00000 0 o o o�o 0 .2. . 00 oo'o'o'o 2 020°0°0 0°000°0 20go..Q �00°0020°0 0°02-°o � 200o000°0. o ..00. _2. 00000.00000 0000000 o '0-0'0g'.:'0 SES Foam 0.5 lb Spray 0.000000. oogozogo 200gogog 0000000 gogogogo Vented Soffit 01.-00-0'-0' gogogogo ogo;000goo' 0 o. .. �Ogogogo *Where attic entry is for the °°°°°°°°o oo SES Foam 0.5 lb Spray o . service of utilities only,thermal o-o 'g*oo oo o oo o. o and igniton barrier on the attic o o o o side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY VENTED ATTIC:FLOOR SOFFIT SES 05-3 1 071812 ESR-3375 I Most Widely Accepted and Trusted Page 5 of 6 a Subfloor SES Foam 0.5 Ib Spray >o�a�o�o�aoos00000aoo ° °g°° °gog° Header °°° o8g o % . °°°°a�8.°°°°mll °; ' Si ; Joist Floor Cross Section Thermal Barrier' Exterior Grade (as required by ; //-y //\ local code) \\/. 6" Min Footer` Vapor Barrier ^•, : M• 'Where crawlspace entry is for the " ': v =• /� service of utilities only,thermal ;' 2 :• / // // / and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY CRAWLSPACE:VENTED SES 05-4 071812 Subfloor Header Sill Joist Thermal Barrier' %oog (as required by Exterior Grade 00008 local code) SES Foam 0.5 Ib Spray Footer` 6"Min Vapor Barrier *Where crawlspace entry is for the service of utilities only,thermal and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY CRAWLSPACE:UNVENTED SES 05-5 071812 ESR-3375 I Most Widely Accepted and Trusted Page 6 of 6 Note:In cold climates.embed metal connector plates in spray foam to prevent winter-time condensation. 0 o o°o°o oo 0°0° °° 0o°0°00000 SES Foam 0.5 Ib Spray °°o°o°°° °°oo 00°0oo 00000 0 0 0 0° Roof Sheathing ° 00° 0 00 000 000o° ° Truss Top Cord/ 00 Rafter ° 00000 ° °°°°0° °o 00° n nn nnnnnn 0o nnnnnn nnnnnn Thermal Barrier' (as required by local code) Note:Local building code may require the use of a vapor retarder in cold climate zones. Ceiling/Thermal Barrier Where attic entry is for the as required by local building code. service of utilities only,thermal and ignition barrier on the attic side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY UNVENTED ATTIC/INSULATED ROOF DECK SES 05-6 071812 0 0 000 000 SES Foam 0.5 Ib Spray O O 0 O O D 0()0 to specified thickness- O O O O O O 0000 O Roof Sheathing O O 00000000 Thermal Barrier as Rafter O O O O required by code. 00 Note:The local building code may require the installation of a vapor barrier in cold climate zones. SES FOAM 0.5 LB SPRAY CATHEDRAL CEILING SES 05-7 071912 FORM R405-2014 OFFICE COPY RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the residential Simulated Performance method shall include ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a-ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst-case orientation, name and version of the compliance software tool, name of individual completing the compliance report(1 page) and an input summary checklist that can be used for field verification(usually 4 pages/may be greater). ❑ Energy Performance Level(EPL) Display Card(one page) ❑ Mandatory Requirements(three pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist(Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report(usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report(usually one page) EnergyGauge®-USRRPB v4.0 11/9/2015 12:05:11 PM Page 1 of 1 t FORM 8405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Brennan Residence Builder Name: Coastal Oaks Construction Street: 1679 Atlantic Beach Dr. Permit Office: Duval City, State,Zip: Atlantic Beach, FL,32233 Permit Number: Owner: Coastal Oaks Construction Jurisdiction: Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(3549.4 sgft.) Insulation Area 2. Single family or multiple family Single-family a. Frame-Wood, Exterior R=21.0 3549.40 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 4 d. N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (3137.6 sqft.) Insulation Area a.Roof Deck(Unvented) R=21.0 2756.00 ft2 6. Conditioned floor area above grade(ft2) 3771.35009765 b.Knee Wall(Unvented) R=0.0 381.60 ft2 Conditioned floor area below grade(ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(651.6 sqft.) Description Area a.Sup:System 1, Ret:System 1,AH:System 1 6 377.13 a. U-Factor: Dbl, U=0.27 555.60 ft2 b. Sup: System 2, Ret:System 2,AH:System 2 6 377.13 SHGC: SHGC=0.19 b. U-Factor: Dbl,U=0.55 96.00 ft2 12.Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.25 a.Central Unit 22.0 SEER:15.25 b.Central Unit 22.0 SEER:15.25 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Heat Pump 24.0 HSPF:8.70 SHGC: b. Electric Heat Pump 24.0 HSPF:8.70 Area Weighted Average Overhang Depth: 3.674 ft. Area Weighted Average SHGC: 0.199 14. Hot water systems 8. Floor Types (3772.0 sqft.) Insulation Area a. Natural Gas Tankless Cap:1 gallons EF:0.820 a.Slab-On-Grade Edge Insulation R=0.0 2756.00 ft2 b. Conservation features b. Floor Over Other Space R=0.0 1016.00 ft2 None c. N/A R= ft2 15.Credits Pstat Glass/Floor Area: 0.173 Total Proposed Modified Loads: 79.01 PASS Total Baseline Loads: 101.05 1 hereby certify that the plans and specifications covered by Review of the plans and THE ST4 j this calculation are in compliance with the Florida Energy specifications covered by this 0, Code. calculation indicates compliance with the Florida Energy Code. uf,,, =`: .':, „ PREPARED BY: -_ __ Before construction is completed DATE: _ Michael S. O'Donoughue this building will be inspected for compliance with Section 553.908 I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code. DD WfE C� OWNER/AGENT BUILDING- 1S DAT OFFICIAL: DATE: _ Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 11/9/2015 11:52 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2014 PROJECT Title: Brennan Residence Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 3771 Lot# Owner: Coastal Oaks Construction Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Coastal Oaks Construction Rotate Angle: 0 Street: 1679 Atlantic Beach Dr. Permit Office: Duval Cross Ventilation: County: Duval Jurisdiction: Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE / IECC Design Temp Int Design Temp Heating Design Daily Temp �/ Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL—JACKSONVILLE—INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Blockl 1946 28995.4 2 Blook2 1825.349 21904.2 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 System 1 1946 28995.4 Yes 4 1 1 Yes Yes Yes 2 System 2 1825.35 21904.2 No 1 3 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio System 1 155 ft 0 1946 ft2 ---- 0.3 0 0.7 2 Slab-On-Grade Edge Insulatio System 2 117 ft 0 810 ft2 ---- 0.3 0 0.7 3 Floor Over Other Space System 2 ---- ---- 1016 ft2 0 0.1 0 0.9 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Composition shingles 2985 ft2 574 ft2 Medium 0.85 No 0.9 No 21 22.6 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full cathedral ceilin Unvented 0 2756 ft2 N N 11/9/2015 11:52 AM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2014 CEILING # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Unvented) System 1 0 1740 ft2 0.11 Wood 2 Under Attic(Unvented) System 2 0 1016 ft2 0.11 Wood 3 Knee Wall(Unvented) System 2 0 381.6 ft2 0.11 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below # Omt To Wal!Type Space R-Value Et In Ft 1a - -Fraction Absor. Grade% 1 SW Exterior Frame-Wood System 1 21 7.5 0 11.8 0 88.5 ft2 0 0.23 0.6 0 2 SE Exterior Frame-Wood System 1 21 1.3 0 11.8 0 15.3 ft2 0 0.23 0.6 0 3 SW Exterior Frame-Wood System 1 21 14.1 0 11.8 0 166.4 ft2 0 0.23 0.6 0 4 NW Exterior Frame-Wood System 1 21 5.3 0 11.8 0 62.5 ft2 0 0.23 0.6 0 5 NE Exterior Frame-Wood System 1 21 22 0 11.8 0 259.6 ft2 0 0.23 0.6 0 6 SE Exterior Frame-Wood System 1 21 12 0 11.8 0 141.6 ft2 0 0.23 0.6 0 7 NE Exterior Frame-Wood System 1 21 15 0 11.8 0 177.0 ft2 0 0.23 0.6 0 8 NW Exterior Frame-Wood System 1 21 3.7 0 11.8 0 43.7 ft2 0 0.23 0.6 0 9 SW Exterior Frame-Wood System 1 21 9.8 0 10 0 98.0 ft2 0 0.23 0.6 0 _10 NW Exterior Frame-Wood System 1 21 5 0 10 0 50.0 ft2 0 0.23 0.6 0 11 SW Exterior Frame-Wood System 1 21 2 0 10 0 20.0 ft2 0 0.23 0.6 0 12 NE Exterior Frame-Wood System 1 21 12.5 0 10 0 125.0 ft2 0 0.23 0.6 0 13 NW Exterior Frame-Wood System 1 21 16.5 0 10 0 165.0 ft2 0 0.23 0.6 0 14 NW Exterior Frame-Wood System 1 21 10.6 0 10 0 106.0 ft2 0 0.23 0.6 0 15 NW Exterior Frame-Wood System 1 21 9.9 0 10 0 99.0 ft2 0 0.23 0.6 0 16 SW Exterior Frame-Wood System 1 21 6.7 0 10 0 67.0 ft2 0 0.23 0.6 0 17 NE Exterior Frame-Wood System 2 21 15 0 10 0 150.0 ft2 0 0.23 0.6 0 18 SE Exterior Frame-Wood System 2 21 18.5 0 10 0 185.0 ft2 0 0.23 0.6 0 19 NW Exterior Frame-Wood System 2 21 8.9 0 10 0 89.0 ft2 0 0.23 0.6 0 20 SE Exterior Frame-Wood System 2 21 13.5 0 10 0 135.0 ft2 0 0.23 0.6 0 21 SW Exterior Frame-Wood System 2 21 2 0 10 0 20.0 ft2 0 0.23 0.6 0 22 SE Exterior Frame-Wood System 2 21 8.3 0 10 0 83.0 ft2 0 0.23 0.6 0 23 SW Exterior Frame-Wood System 2 21 8.2 0 10 0 82.0 ft2 0 0.23 0.6 0 24 SE Exterior Frame-Wood System 2 21 6 0 10 0 60.0 ft2 0 0.23 0.6 0 _25 SW Exterior Frame-Wood System 2 21 4.1 0 10 0 41.0 ft2 0 0.23 0.6 0 26 SW Exterior Frame-Wood System 2 21 13.5 0 20.8 0 280.8 ft2 0 0.23 0.6 0 27 SE Exterior Frame-Wood System 2 21 1.3 0 11.8 0 15.3 ft2 0 0.23 0.6 0 28 SE Exterior Frame-Wood System 2 21 5.1 0 9 0 45.9 ft2 0 0.23 0.6 0 29 SW Exterior Frame-Wood System 2 21 12.2 0 9 0 109.8 ft2 0 0.23 0.6 0 _30 NW Exterior Frame-Wood System 2 21 5.1 0 9 0 45.9 ft2 0 0.23 0.6 0 31 SW Exterior Frame-Wood System 2 21 5.4 0 9 0 48.6 ft2 0 0.23 0.6 0 32 NE Exterior Frame-Wood System 2 21 14.6 0 9 0 131.4 ft2 0 0.23 0.6 0 _33 NW Exterior Frame-Wood System 2 21 6 0 9 0 54.0 ft2 0 0.23 0.6 0 34 NW Exterior Frame-Wood System 2 21 9.1 0 9 0 81.9 ft2 0 0.23 0.6 0 35 NE Exterior Frame-Wood System 2 21 16.9 0 9 0 152.1 ft2 0 0.23 0.6 0 36 NE Exterior Frame-Wood System 2 21 6 0 9 0 54.0 ft2 0 0.23 0.6 0 11/9/2015 11:52 AM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2014 DOORS # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 Wood System 1 None .2 .1 .1 .1 ft2 WINDOWS Orientation shown is the entered, Proposed orientation. / Wall Overhang �/ # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade_ Screening 1 SW 1 Vinyl Low-E Double Yes 0.27 0.19 24.0 ft2 4 ft 0 in 2.083 ft 0 None None 2 SW 1 Vinyl Low-E Double Yes 0.27 0.19 16.0 ft2 4 ft 0 in 2.083 ft 0 None None 3 SW 3 Vinyl Low-E Double Yes 0.27 0.19 18.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 4 NE 5 Vinyl Low-E Double Yes 0.55 0.25 96.0 ft2 12 It 0 in 1.5 ft 0 in None None 5 SE 6 Vinyl Low-E Double Yes 0.27 0.19 48.0 ft2 6.8 ft 0 in 1.5 It 0 in None None 6 NE 7 Vinyl Low-E Double Yes 0.27 0.19 30.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 7 NE 7 Vinyl Low-E Double Yes 0.27 0.19 9.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 8 SW 9 Vinyl Low-E Double Yes 0.27 0.19 21.6 ft2 4 ft 0 in 1.5 ft 0 in None None 9 NE 12 Vinyl Low-E Double Yes 0.27 0.19 18.0 11:2 1.5 ft 0 in 1.5 ft 0 in None None 10 NE 12 Vinyl Low-E Double Yes 0.27 0.19 24.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 11 NW 13 Vinyl Low-E Double Yes 0.27 0.19 25.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 12 NW 14 Vinyl Low-E Double Yes 0.27 0.19 8.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 13 NW 15 Vinyl Low-E Double Yes 0.27 0.19 8.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 14 NE 17 Vinyl Low-E Double Yes 0.27 0.19 24.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 15 NE 17 Vinyl Low-E Double Yes 0.27 0.19 30.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 16 SE 18 Vinyl Low-E Double Yes 0.27 0.19 25.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 17 NW 19 Vinyl Low-E Double Yes 0.27 0.19 24.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 18 SE 20 Vinyl Low-E Double Yes 0.27 0.19 8.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 19 SE 22 Vinyl Low-E Double Yes 0.27 0.19 25.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 20 SW 23 Vinyl Low-E Double Yes 0.27 0.19 12.5 11:2 1.5 It 0 in 1.5 ft 0 in None None 21 SE 24 Vinyl Low-E Double Yes 0.27 0.19 8.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 22 SW 26 Vinyl Low-E Double Yes 0.27 0.19 18.0 ft2 1.5 It 0 in 1.5 It 0 in None None 23 SW 26 Vinyl Low-E Double Yes 0.27 0.19 12.5 ft2 1.5 ft 0 in 1.5 ft 0 in None None 24 SW 29 Vinyl Low-E Double Yes 0.27 0.19 15.0 ft2 1.5 It 0 in 1.5 It 0 in None None 25 SW 29 Vinyl Low-E Double Yes 0.27 0.19 15.0 ft2 1.5 It 0 in 1.5 ft 0 in None None 26 NW 30 Vinyl Low-E Double Yes 0.27 0.19 18.0 ft2 1.5 ft 0 in 1.5 It 0 in None None 27 NE 32 Vinyl Low-E Double Yes 0.27 0.19 15.0 ft2 1.5 ft 0 in 1.5 ft 0 in None None 28 NE 35 Vinyl Low-E Double Yes 0.27 0.19 56.0 11:2 1.5 ft 0 in 1.5 ft 0 in None None INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000429 4241.6 232.86 437.93 .4065 5 11/9/2015 11:52 AM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5 FORM R405-2014 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.7 24 kBtu/hr 1 sys#2 2 Electric Heat Pump None HSPF:8.7 24 kBtu/hr 2 sys#1 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER:15.222.04 kBtu/hr 661 cfrn 0.75 1 sys#2 2 Central Unit None SEER:15.2!22.04 kBtu/hr 661 cfm 0.75 2 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas Tankless Exterior 0.82 1 gal 70 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply---- —Return-- Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool 1 System 1 6 377.13 System 1 94.283 Default Leakage System 1 (Default) (Default) 2 2 2 System 2 6 377.13 System 2 94283 Default Leakage System 2 (Default) (Default) 1 1 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Coolin Jan Feb Mar Apr Ma Jun [[X]]Jul Au X Se Oct NovDec Heating Jan lX}Feb Mar AApppr May Jun E )Jul JXJ AuSeP JA Oct JX� Nov tXDec Ventin Jan [ 11 Feb X Mar r Ma Jun ]]Jul Aug Se Oct Nov [ Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 11/912015 11:52 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 78 The lower the EnergyPerformance Index, the more efficient the home. 1679 Atlantic Beach Dr., Atlantic Beach, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame-Wood, Exterior R=21.0 3549.40 ft2 b. N/A R= ft2 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 4 d. N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area a. Roof Deck(Unvented) R=21.0 2756.00 ft2 6. Conditioned floor area(ft2) 3771 b. Knee Wall(Unvented) R=0.0 381.60 ft2 7. Windows" Description Area c. N/A R= ft2 a. U-Factor: Dbl, U=0.27 555.60 ft2 11. Ducts R ft2 a. Sup:System 1, Ret:System 1,AH:System 1 6 377.13 SHGC: SHGC=0.19 b. Sup: System 2, Ret:System 2,AH:System 2 6 377.13 b. U-Factor: Dbl, U=0.55 96.00 ft2 SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 22.0 SEER:15.25 SHGC: b.Central Unit 22.0 SEER:15.25 d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency SHGC: a. Electric Heat Pump 24.0 HSPF:8.70 Area Weighted Average Overhang Depth: 3.674 ft. b. Electric Heat Pump 24.0 HSPF:8.70 Area Weighted Average SHGC: 0.199 8. Floor Types Insulation Area 14. Hot water systems z a.Natural Gas Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 2756.00 ft EF:0.82 b.Floor Over Other Space R=0.0 1016.00 ft2 c. N/A R= ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building -VIE ST Construction through the above energy saving features which will be installed (or exceeded) o� _ gTFO in this home before final inspection. Otherwise, a new EPL Display Card will be completed '`4, based on installed Code co liant features. Builder Signature: Date: l I� Address of New Home: ` 62 77 7 4 r�,ay � p s City/FL Zip: I OpWE� 3a.z 3 3 *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 11/9/2015 11:52 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Brennan Residence Builder Name: Coastal Oaks Construction Street: 1679 Atlantic Beach Dr. Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233 Permit Number: Owner: Coastal Oaks Construction Jurisdiction: Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. VA Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity +� spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 11/9/2015 11:52 AM EnergyGauge®USA-FlaRes2014 Section 8405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 1679 Atlantic Beach Dr. Permit Number: Atlantic Beach,FL,32233 MANDATORY REQUIREMENTS See individual code sections for full details. 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law [Section 553.9085,Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. • R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed, but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3. Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems, if installed at the time of the test,shall be turned off,and 6.Supply and return registers,if installed at the time of the test, shall be fully open. o R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. O R402.4.3 Fenestration air IeakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. o R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed ` luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. l R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat(Mandatory).Heat pumps having supplementary electric-resistance heat shall have controls VP that,except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.2.2 Sealing(MandatoryAll ducts, air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99,Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system, including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system, including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 11/9/2015 11:52 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) 0 R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the ✓ design air flow rate when tested in accordance with ASHRAE 193. �❑ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3., 0 R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight,moisture,equipment maintenance, and wind,and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. Ve R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3%inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies 0 R403.4.4.1 Storage water heater temperature controls R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). R403.4.4.1.2 Shut down. A separate switch or a dearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water heating systems to be turned off. 0 R403.4.4.2 Water heating equipment Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that Gose when the ventilation system is not operating. 0 R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception:Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. 0 R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62,Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics, crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise. R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. 0 R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors, provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 11/9/2015 11:52 AM EnergyGauge D USA-FlaRes2014 -Section R405.4.1 Com Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) o R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. O R403.6.1.2 Heating equipment capacity R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. o R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building,shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. 0 R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters, pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. o R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or solar energy source computed over an operating season. RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. o R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space, R-10 is allowed. 11/9/2015 11:52 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3 Brennan Residence HVAC Load Calculations for Coastal Oaks Construction JACKSONVILLE I B IN ULD G SCIENCE Prepared By: Michael O'Donoughue Jacksonville Building Science, LLC 450 SR13 N#132 Jacksonville, FL., 32259 (904)807-3540 Monday, November 09, 2015 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. Rhvac-Residential&Light Commercial HVAC Loads Elite Softwom Development,Ina Jacksonville Building Science Brennan Residence St.Johns.FL 22259 _ Daae 2 ProOct Report --- -- - :General Project Information _ Project Title: Brennan Residence Designed By: Michael O'Donoughue Project Date: Monday, October 19, 2015 Client Name: Coastal Oaks Construction Company Name: Jacksonville Building Science, LLC Company Representative: Michael O'Donoughue Company Address: 450 SR13 N#132 Company City: Jacksonville, FL., 32259 Company Phone: (904) 807-3540 Company E-Mail Address: mod@JaxBuildingScience.com Company Website: www.JaxBuildingScience.com _Design-Data - - - --- Reference City: Jacksonville AP, Florida Building Orientation: Front door faces Southwest Daily Temperature Range: Medium Latitude: 30 Degrees Elevation: 26 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum RLdum D[y Bulb Difference Winter: 32 29.92 n/a n/a 72 n/a Summer: 93 77 49% 50% 75 50 Check Figures-- - - Total Building Supply CFM: 1,315 CFM Per Square ft.: 0.349 Square ft. of Room Area: 3,772 Square ft. Per Ton: 1,127 Volume(ft') of Cond. Space: 41,127 'building-Loads Total Heating Required Including Ventilation Air: 60,194 Btuh 60.194 MBH Total Sensible Gain: 30,360 Btuh 76 % Total Latent Gain: 9,809 Btuh 24 % Total Cooling Required Including Ventilation Air: 40,170 Btuh 3.35 Tons(Based On Sensible+ Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 Coastal Oaks Construction\Brennan\load calc\Brennan.rh9 Monday, November 09,2015, 10:51 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Buildinq Science AN Brennan Residence St.Johns,FL 32259 Total Building Summary Loads omponent Area Sen Lat Sen To scription Quart _ -_- Loss GainGain_ -- - - Marvin Integrity: Glazing-Wood Ultrex windows, u-value 534 5,763 0 8,616 8,616 0.27, SHGC 0.19 Aluminum Slider: Glazing-Aluminum sliding glass door, u- 96 2,112 0 2,561 2,561 value 0.55, SHGC 0.25 Marvin Integrity: Glazing-Wood Ultrex windows, in 21.6 175 0 117 117 partition wall, u-value 0.27, SHGC 0.19 12F1-Osw: Wall-Frame, R-21 open cell 1/2 Ib. spray foam 2821.4 7,337 0 3,355 3,355 insulation in 2 x 6 stud cavity, no board insulation, siding finish, wood studs 12F1-0sw: Part-Frame, R-21 open cell 1/2 Ib. spray foam 76.4 149 0 99 99 insulation in 2 x 6 stud cavity, no board insulation, siding finish,wood studs 1861-21o: Roof/Ceiling-Roof Joists Between Roof Deck 4134.2 7,774 0 4,665 4,665 and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-21 open cell 1/2 Ib. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist Foam kneewall-sd: Roof/Ceiling-Roof Joists Between 381.6 717 0 519 519 Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, Kneewall adjacent to foam attic, dark wood shake 22A-ph-t: Floor-Slab on grade, No edge insulation, no 272 14,773 0 0 0 insulation below floor, tile covering, passive, heavy moist soil Subtotals for structure: 38,800 0 19,932 19,932 People: 5 1,000 1,150 2,150 Equipment: 0 4,900 4,900 Lighting: 0 0 0 Ductwork: 9,281 4,907 2,094 7,001 Infiltration: Winter CFM: 196, Summer CFM: 36 8,597 1,201 702 1,903 _Ventilation:Winter CFM:_80 Summer CFM:80-__--_ 3,517 2,701 1,583 4,284 Total Building Load Totals: 60,194 9,809 30,360 40,170 wy - i Total Building Supply CFM: 1,315 CFM Per Square ft.: 0.349 Square ft. of Room Area: 3,772 Square ft. Per Ton: 1,127 Volume(ft')of Cond. Space: 41,127 Wilding Loads Total Heating Required Including Ventilation Air: 60,194 Btuh 60.194 MBH Total Sensible Gain: 30,360 Btuh 76 % Total Latent Gain: 9,809 Btuh 24 % Total Cooling Required Including Ventilation Air: 40,170 Btuh 3.35 Tons (Based On Sensible+ Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 Coastal Oaks ConstructionM3rennanUoad calc\Brennan.rh9 Monday, November 09,2015, 10:51 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Brennan Residence St.Johns,FL 32259 page 4_, Building Pie Chart Ventilation 6% Floor 25% Infiltration 14% Ductwork 15% Roof 14% `- Wall 12% Glass 13% Roof 13% Ventilation 11% Infiltration 5% Wall 9% Ductwork 17% Glass 28% Equipment 12% People 5% Y:\2.1 Coastal Oaks Construction\Brennan\load calc\Brennan.rh9 Monday, November 09, 2015, 10:51 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Brennan Residence St.Johns FL 32259- _Page 5- System 1 Room Load Summary _ -- -- Htg Min Run Run Clg Clg Min Act Room Area Sens Htg Duct Duct Sens Lat Clg Sys _No Name_ _ -- SF _-_--Btuh CFM Size Vel Btuh Btuh CFM CF ---Zone 1--- 1 Foyer 86 1,634 21 1-0 0 976 56 44 44 3 Gallery/Hall 125 0 0 1-0 0 0 0 0 0 4 Powder Room 39 0 0 1-0 0 0 0 0 0 5 Study 176 2,998 39 1-0 0 1,146 123 52 52 6 Gathering 411 5,298 69 1-0 0 3,714 540 169 169 7 Dining 180 5,771 75 1-0 0 2,773 395 126 126 8 Kitchen 281 370 5 1-0 0 3,058 200 139 139 9 Pantry_ 71 0 0 1-0 0_----___ _0-_ 0 0 0 Zone 1 subtotal 1,368 16,071 209 11,667 1,314 531 531 ---Zone 2--- 10 Hall/Day Foyer 157 2,782 36 1-0 0 1,246 90 57 57 11 Guest Bedroom 206 5,081 66 1-0 0 1,945 156 88 88 12 Guest WIC 75 238 3 1-0 0 130 0 6 6 13 Guest Bath 60 1,658 22 1-0 0 470 57 21 22 14 Laundry------------ _80 2,505 - _- _33 1-0 610 __.89 _--_-_28 33_ Zone 2 subtotal 578-- 12,265 _ 159 _- _4,401 __ 392 __200_ _200_ Ventilation 1,758 791 1,350 Duct Latent 618 Return Duct 644 0 1,370 System 1 total 1,946 30,739 368 15,863 5,044 686 686 Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the"Average Load Procedure + Excursion" method. 'Cooling System Summary -- - - - -- _ - -- - - - - - Cooling Sensible/Latent Sensible Latent TUWW Tons - - Split - - --Btuh -- - -Btuh Net Required: 1.74 76%/24% 15,863 5,044 20,907 Actual: 1.84 78%/22% 17,112 4,928 22,040 Equipment Data _ - -- - Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: 25HBC524A"030 25HBC524A'030 Indoor Model: FX4DNF025 Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.7 HSPF 15.25 SEER Sound: 0 0 Capacity: 24,000 Btuh 22,040 Btuh Sensible Capacity: n/a 17,112 Btuh Latent Capacity: n/a 4,928 Btuh AHRI Reference No.: n/a 7914088 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 93F, SOWB: 77F, WODB: 32F, SIDB: 75F, SIRH: 50%, WIDB: 72F, Sen. gain: 15,863 Btuh, Lat. gain: 5,044 Btuh, Sen. loss: 30,739 Btuh, Entering clg. coil DB: 76F, Entering clg. coil WB:63AF, Entering htg. coil DB: 66.2F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 686 CFM, Req. htg. airflow: 368 CFM Y:12.1 Coastal Oaks Construction\Brennan\load calc\Brennan.rh9 Monday, November 09, 2015, 10:51 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. it Jacksonville Building Science Brennan Residence St.Johns,FL 32259 - Page 6. l Svstem 2 Room Load Summary Htg Min Run Run Clg CIg Min ,4 Room Area Sens Htg Duct Duct Sens Lat Clg Sys No Name - - SF Btuh CFM_ Size - Vel Btuh Btuh CFM CafiAj ---Zone 1--- - - 15 Owner's 278 6,818 89 1-0 0 2,971 67 135 135 16 O. Foyer 85 276 4 1-0 0 154 0 7 7 17 O. Closet 115 2,293 30 1-0 0 621 25 28 30 18 O. Bath 155 2,819 37 1-0 0 1,261 26 57 57 19 O. WC 24 1,330 17 1-0 0 393 16 18 18 Zone 1 subtotal 656 13,537 176 5,400 134 246 246 ---Zone 2--- 2 Stairs 154 3,989 52 1-0 0 1,744 54 79 79 20 Landing 113 546 7 1-0 0 591 0 27 27 21 Bed 3 171 2,182 28 1-0 0 1,647 17 75 75 22 Bed 3 WIC 30 214 3 1-0 0 132 0 6 6 23 Bath 3 59 1,005 13 1-0 0 749 15 34 34 24 Bed2/3 Hall 84 273 4 1-0 0 152 0 7 7 25 Bed 2 175 1,850 24 1-0 0 1,096 29 50 50 26 Bed 2WIC 29 105 1 1-0 0 59 0 3 3 27 Bath 2 49 613 8 1-0 0 206 13 9 9 28 Retreat 304 2,893 38 1-0 0 2,691 233 122 122 Zone 2 subtotal -_ 1,169--_-13,670 178 9,066 361 412 412 Ventilation 1,758 791 1,350 Duct Latent 425 _ Return Duct 491 -128 2,495 System 2 total 1,825 29,456 354 14,497 4,765 629 629 Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the"Average Load Procedure +Excursion" method. mem Summary e Split Btuh Net Required: 1.61 75%/25% 14,497 4,765 19,263 Actual: 1.84 78%/22% 17,233 4,807 22,040 Equipment Data - - _ -- _ Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: 25HBC524A*030 25HBC524A*030 Indoor Model: FX4DNF025 Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.7 HSPF 15.25 SEER Sound: 0 0 Capacity: 24,000 Btuh 22,040 Btuh Sensible Capacity: n/a 17,233 Btuh Latent Capacity: n/a 4,807 Btuh AHRI Reference No.: n/a 7914088 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODS: 93F, SOWB: 77F, WODB: 32F, SIDB: 75F, SIRH: 50%, WIDB: 72F, Sen. gain: 14,497 Btuh, Lat. gain:4,765 Btuh, Sen. loss: 29,456 Btuh, Entering clg. coil DB: (Error), Entering clg. coil WB: (Error), Entering htg. coil DB: 66.4F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 629 CFM, Req. htg. airflow: 354 CFM Y:\2.1 Coastal Oaks Construction\BrennanUoad calc\Brennan.rh9 Monday, November 09, 2015, 10:51 AM Comfort 15 Heat Pump with Puron@ Refrigerant Carrier 1 —1/2 to 5 Nominal Tons turn to the .- Product Data INDUSTRY LEADING FEATURES/BENEFITS Efficiency • 15 SEER/12.5 EER/8.0-9.0 HSPF - • Microtube Technology'" refrigeration system • Indoor air quality accessories available Sound • Sound level as low as 69 dBA • Sound levels as low as 68 dBA with accessory sound blanket Comfort • System supports Edge®Thermidistat- or standard thermostat controls Reliability • Puron®refrigerant-environmentally sound,won't deplete the ozone layer and low lifetime service cost. • Scroll compressor • Internal pressure relief valve • Internal thermal overload - High pressure switch Nron- • Loss of charge switch me —d Wig— • Filter drier • Balanced refrigeration system for maximum reliability Carrier heat pumps with Puron®refrigerant provide a collection of Durability features unmatched by any other family of equipment.The 25HBC has been designed utilizing Carrier's Puron refrigerant. The WeatherArmor- protection package: environmentally sound refrigerant allows consumers to make a • Solid,durable sheet metal construction responsible decision in the protection of the earth's ozone layer. • Dense wire coil guard standard This product has been designed and manufactured to meet Energy • Baked-on powder paint Star©criteria for energy efficiency when matched with appropriate coil components. Refer to the combination ratings in the Product Applications Data for system combinations that meet Energy Star®guidelines. • Long-line-up to 250 feet(76.20 m)total equivalent length,up NOTE: Ratings contained in this document are subject to to 200 feet(60.96 m)condenser above evaporator,or up to 80 ft. change at any time. Always refer to the AHRI directory (24.38 m)evaporator above condenser(See Longline Guide for (www.ahiidhvctory.org) for the most up-to-date ratings more information) information. . Low ambient cooling(down to-20'F/-28.9°C)with accessory kit pppp P! ^N N_ N N N N^N N N N N p p N N N N P S m S N n n O O O m n n n � J .-� � � .-.- +7 17 :!7r++RRNNR N tv N N N N N N C4 N N N N N N I I I I I I I I I 1 1 I I I I 1 1 I I I I I I I I I I I I I I I I I I I I ONiiiiiiiiiiiii§d§§§ U§§ §§§§§§�������g W U U U U U U U U U U U U U U U U U U U U U I U U U U U U U_U U_U U U U U Lu Lu Lu t dR00 m NNR292R awe �mp�mpmw w Wmp QWp Wmm�mm Wmm �mmWmwpmwmwmpiWpmmmmmm mp mm WpWm�mpmm�mm mmQ�p�mp d — — m — -— m -- LL N N S S N N N S N N S N N N N S N S N N S S 10 10�b S N N N N N�IO S b S W N N m i0 w N m m �p U N W N W W W N W W W W N N W W N N N W W N N N N N W N W O N N N W W N N W m W N N S N W Q N N N p o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o d d o 0 0 0 0 o c d d d d d o d F c° vvi, co. oi, � gpt � t T `a,, eaa F N N N NN N IV N N N N N N N N W U mNN WNW mm ccpp Q mm mm mm m mtp m m pqp Qp�p 01N O�NNN WNOOONNGD W W W mN W NN Nui vi W Wvi role of oiv W r: NN t- •- ^ � ' ^ ^ •- •- ' ^ ^ ¢ « « M k M M i t Y Y Y M « « « « ' ' " a a<a a<<+ � a a' ' <a• i a J n n n n n n' _n n n n n n� p n p n n nn n p n' p n p n o n np_ p n NW {p pp p+p fp+o'p +o+O a OO N 71�+17+17+10 +l0 N W N tl]N f0 N l•+l t N O n N N O V O + 01 S Q N N N N�9 N l9 Q!N S N Lq N l9 N W N N N N OJ N lV O W (V (�l N O) W m !7 N Ol = M M t • Y Y « M Y i t Y • ♦ • t N R fV lV R R x M x S x x x x»>_= x x __=x x x x x x x x 3 a p,,as asaqas as as aaaaaaaaaaa W <2 Z Z Z Z W W Q a Z Z Z Z Z W Ul 4 z Z Z Z Z W W Z Z W o z Z W m Z U U UUUU((JJ UUUU U U U U U U U V U U U U U U U U U U U UUUU U N 0 0 0 �: " N a W O ^ W tp (� N CV N N N N N N N N CNV N N N N U � J W pa n m 2 N p C 0000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I I I I I I C4 C4 Oop pm pW OW _OO O O N101 O 101 D�S S I I app oy ao oa op pp Q S C; tC 1N Ol O) M n CC R N ^ W n N N O nO nnc�OO OOO l9 OfW Y7 4 $OOOOOO A. W 57 5? SZ Sc 52 'R' 'R�_ g �cir,��ci�o a ' ` add d d "ddgdd ioo g Y z8>>>>>>>>6e » > wwwwwwww pppUppUpUmpUppUpUW Um Ummm �WJ�m7 >UU Umx_mmm2m22�222m a N N N 8 n N a m W 1A O N N W W 1010 NW WN NN iff N �0�0SStff SS elf�O SOW�D W 1f110 _ NNRR °' NNRRRC04F1 Q �•$ ; w m m m Wo, m 060000060600000000 .=00000000 L� WY W (ZWI 7 Coo n W N O m O O Cl W m . nmi Pl NN S$N N N N$N N N W m N QOD W OIO N N W W O O W N 0 0 0 O 0 N NOl N m O N m f? R R m .n- N N N N OOO OO 00000000 OO OO OO OO OO CC COOOGCGOOC.-�COOG GGGG C f U _ lot N n N N m m m N. ly7 . R N N N N N N N N N N N N N N N Q • • • • • • • Y • • Y • t Y t t ♦ R • t e ♦ • i t GY Q�Q a « « ♦ « « Y i ♦ Y • s Y « QQaa«aaaaGGaa' as a<aQa¢¢as<aaaa'¢¢ =Jn_ n_+ +NN_nnnnnnncg cg------ ---- a _ -- - abW nnnnnnnN �� N N N N N C9 N N N N N N N N N N f9 N _ t Y • M Y Y i M M t ♦ M Y Y M Y f Y i Y Y « M Ao0 2n � � � � � IN. 00 1xxkkxx xxSAHxxxxxxx�xxx xx Y iM(L W a s a s a a a a aaa a a a a a a s a cZic0icZicZiicy.�0 c3tZitZ.�0cZitZicWit0icZ�c0800Uc80c75czi0cWi��Q°dU�cZi000CW� V Fyzl• e + 7 a W 3 + CO n N N N + n W N N + W O 'N U a I r� O I (ny N 10 N O N CO O O O N N O 4 vI N N N N N N N N N N N N N N N 5C > f� IL FI p pp m W m p �p �p ��pp {{pp a N � N N N p �oo00000o ----- -000 UfD W N O O O CO N C1 8 .+ W W W N N Cd N ci N N 11717 ���g��� � ��aa�� �maN N n N l7 m N f 9 W (h C'1m A C7 6 C 0 0 0 0 0 r 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C U N N N N N N N N N N N N N N N V O U Q N atin- N e Of N e' W V WN O) N W N W 'QN D LL N LL LL O 6 N -`- N; N n '-'N n 2 LL S S LW n m W W n m m W W LL LL LLLL LL LLLL LLLL g p ooze m ZZ a sp +pp+a a a °ooze W W W W WZm2000ZQizzNN W�9NN�9NN[0C9}MNNUUNY < SCO +Uxxp aT?N WW{q a{q IL aikkkk?yx yx Ypm Y— J +LL LLLL LL LL LL+ + LL LL+ LL LL LL Q <Q Z a2 Z Z a Z Z aZ C/J C/1 mLL LL<6 38 JACKSONVILLE Manual D - Duct Design & BUILLANG mAWARD 2015 SCIENCE® Schematic PARTNER OF THE YEAR Coastal Oaks Brennan Residence V15.10 CFM 783 mid speed range TESP 0.5 lConditioned area 1 3,772 Design Static air side devices = 0.03 0.03 0 lConditioned Volume 1 41,127 DPL= 0.06 ASP= 0.44 FR=PDx 100/TEL 0.10 TEL 434 Supply Network zone d4mper Lot Design Cal vel Size(ID) r/ Element Vel Specific CFM L Fitt Fitt EL TEL Duct Duct WxH TI 571 571 43 60 55 158 158 13.4 13.2 571 12 X 12 T I T2 212 212 15 60 55 130 130 9.3 8.1 377 9 X 9 Foyer Branch Ducts T2 Powder Room Element Lot Design L Fitt Fitt EL TEL Cal Vel Vel QTY Size Grill Size Study Specific CFM Duct Duct Gathering I Foyer 44 44 24 60 55 139 297 5.1 3.7 224 1 6 10x6 Dining 4 Powder Room 20 20 32 60 55 147 305 4.0 2.5 229 1 4 8x4 Kitchen 5 Stud 52 52 13 60 55 128 286 5.4 4.0 265 1 6 12x6 b Gathering 189 189 30 60 55 145 303 8.8 7.6 708 2 7 12X8 7 Dining 126 126 9 60 55 124 282 7.7 6.2 361 1 8 12X8 Hall/Day Foyer 8 Kitchen 140 140 11 60 55 126 284 7.9 6.5 401 1 8 12x8 Guest Bedroom 10 HalVDay Foyer. 57 57 18 60 55 133 263 5.6 4.2 290 1 6 10X6 Guest Bath I I Guest Bedroom 100 100 2 60 55 117 247 6.9 5.5 374 1 7 12x8 Laundry 13 Guest Bath 22 22 6 60 55 121 251 4.0 2.6 252 1 4 8x4 14 Laundry 33 33 11 60 55 126 256 4.0 3.2 378 1 4 8x4 11/7/2015 all calculations and designs in accordance with ACCA Manual D 2009 -2014 Rev pg 1 of 2 JACKSONVILLE Manual D - Duct Design & =,AWARD BUILDING 2015 SCIENCE® Schematic PARTNER OF THE YEAR Coastal Oaks Brennan Residence V15.10 System 2 CFM 688 mid speed range _ TESP 0.5 lConditioned area 1 3,772 Design Static air side devices = 0.03 0.03 0 lConditioned Volume 1 41,127 DPL= 0.06 ASP= 0.44 FR=PDx 100/TEL 0.09 TEL 466 Supply Network Element Lot Design L Fitt Fitt EL TEL Cal Vel Vel Size(ID) zone damper Specific CFM Duct Duct WxH rI 255 255 12 60 55 127 127 99 88 468 IO MBI 255 255 75 75 202 22X22X36 T2 433 434 8 60 55 123 123 12.1 11.s 553 12 Tl MB2 433 434 75 i 75 198 22X22X36 Owner's Branch Ducts T2 O.Closet Lot Design Cal Vel MB-1 O. Bath Element Specific CFM L Fitt Fitt EL TEL Duct Duct Vel QTY Size Grill Size 0. WC 15 Owner's 150 150 13 60 55 128 330 8.1 6.8 764 2 6 12X6 17 O.Closet 30 30 6 60 55 121 323 4.0 3.0 344 1 4 8x4 18 O.Bath 57 57 5 60 55 120 322 5.6 4.2 290 1 6 IM 19 0,WC 18 18 12 60 55 127 329 3.0 2.3 367 1 3 8X4 Stairs 2 Stairs 79 79 12 60 55 127 325 6.4 4.9 296 1 7 12X8 "rl Bed 3 21 Bed 3 75 75 7 60 ss 122 320 6.3 4.8 281 1 7 12x8 Bed 3 WIC 22 Bed 3 WIC 6 6 10 60 55 125 323 3.0 1.4 122 1 3 8x4 MB-2 Bath 3 23 Bath 3 34 34 16 60 55 131 329 4.0 3.2 390 1 4 8x4 Bed 2 25 Bed 2 54 54 12 60 55 127 325 5.5 4.1 275 1 6 12x6 Bed 2 WIC 26 Bed 2 WIC 3 3 6 1 60 55 121 319 3.0 1.0 61 1 3 8x4 Bath 2 27 Bath 2 16 17 9 60 55 124 322 3.0 2.3 346 1 3 8X4 Retreat 28 Retreat 166 166 14 1 60 55 129 327 1 8.5 7.1 621 2 7= 11/7/2015 all calculations and designs in accordance with ACCA Manual D 2009-2014 Rev pg 2 of 2 K t;.i 0 y�nr Z �� wt In tz P z @ ppg a j6 ap n I g .a SB d Am oz 0 [ � w g e8s < a n 8 T9G n w � � a U _ a o o jiu 1,C�I 6 HVAC NOTES m� a CD CD CD n SII. CD I i! � I n 0 I -- j CKSONVILLE o UIU.ING Coastal Oaks - Brenna Residence -First Floor Mechanical C7� - ITI o � - CD A [lit O O I � O a9 n (D O 9 .JAC KSONV i o UILVING Coastal Oaks - Brenna Residence - Ssecond Floor Mechanical N g