28 SHERRY DR - FIRE COMMENTS t3At
aw Jacksonville Fire and Rescue Department A,,
'12 lr cal FIRE PREVENTION DIVISION
9rSCUE et
PROJECT NAME: 28 Sherry Hotel
ADDRESS: 28 Sherry Dr.
REVIEWED BY: RE
DATE: 12/30/2015
After initial review,the following exceptions were noted in your construction plans submitted to this
office as part of the building/mechanical permit process:
1. Please correct or provide the following to obtain plans approval. When resubmitting corrected sheets,
please provide a written narrative letter responding to our comments and directing the plans reviewer
to where the changes have taken place. Revised sheets should be clouded clearly showing areas were
changes or corrections have occurred. If this is an electronic submission please make sure that written
narrative is submitted under correspondence. Failure to provide response letter will result in a return
for corrections plans review submission.
2. Please include in your code summary reference of applicable Fire Codes to those currently adopted.
Florida is currently using the 5th Edition of the Florida Fire Prevention Code.
3. Provide light-frame truss-type construction identification signage per FAC 69A-60.0081 or written
verification from a licensed architect or engineer stating that such structure does not meet the
definition of 69A-60.0081.
d
4. Provide portable fire extinguisher protection per NFPA 10.