290 BEACH AVE - ENERGY SHEETS DISAPPROVED !�� CITY OF ATLANTIC BEACH
�J '' ,es,� 800 Seminole Road
J Atlantic Beach,Florida 32233
-,�' ;�;� .. Telephone(904)247-5800
-2) 1 6 _6 4 8 �^ 6 a 6_ 6 6 ,
r FAX(904) 247 5845
N CJ
tJi31 `rr,
REVISION REQUEST SHEET
Date: 13)1.k.s> Received by: Resubmitted:
Permit ber: ( G - M c L� - �-6 4—
Original Plans Examiner: O,,. A4,,, ,,,, Project Name: 1 k\ r
Project Address: 2I0 �s.i,-, Ave,_ .
Contractor: 14
Atr,wv+.,o A is Contact Name Name( , .,;,
Contact Phone : (joy-3c1V-(o,+s Contact e-mail:hAr r., p;(-co,.4,t, „r o
��.1.ems'-, •
Revision/Plan Check/Permit Fee (s) Due: $
Description of Proposed Revision to Existin Permit:
s.), Q,S PI1wa1 Z au,ai b h> tic 1l-,Stt,ll .. z,, . eztin- k" A∎A
*I uStAi dl)0- suer,.
7Re V Pyle c b DQn
Additional Increase in Building Value: $ r Additional S.F.
Site Plan Revised: Public W/U Approval:
By signing below. I(print name) p..1.,4 !yy y r'o,.O affirm that the above revision
is inclusive of the proposed changes.
'"5/3/1(a.
Signature of Contractor Agent(Contractor must sign if increase in valuation) Date
f r' r V
Office Use Only
Nr-- � C Date: Approved: Rejected: Notified by:
??is
Plan Review Comments: —.....____________j U
Department review required Yes No
uilding
&Zoning
Tree Administrator Plans Examiner
Public Works
Public Utilities -5 l d1 ci b
Public Safety
Fire Services Date Created 8/20/15 Rev 2
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
(904)247-5800
II
BUILDING DEPARTMENT REVIEW COMMENTS
Date: 3/07/16
Permit: 16-MECH-465 Applicant: Hammond
Review: 2 Address:
Site Address: 290 Beach Phone: 398-6488
RE#: Email: hammondairconditioning @gmail.com
Correction Comments:
Application is disapproved for the following issues: (Revision)
1. Please submit two (2) copies of original energy sheet printouts. The copy submitted contains
modified numbers and cannot be accepted.
-All details of as-built construction must match approved plans and documents.
2. Page 1 must be signed by owner/agent. EPL must be completed and signed. Air barrier and
insulation check list must be checked off to acknowledge requirements, per FBC-EC, Section
R103.1.1.2.
3. Bryant units are indicated in documents, but Carrier unit is installed. Please clarify.
4. Manufacturer's expanded data sheet, submitted, indicates more than one option. Please
submit new page(s)with only specific options to be used indicated. Page(s) must be from correct
brand.
5. Manual S figures indicate that the AC units are smaller than required. Please review.
On-site inspection reveals:
1. Duct sizes smaller than required.
2. Flex ducts pinched in some locations, restricting air flow.
3. Ducts installed tight against roof deck. No insulation below roof deck. The 1-1/2" space
required to protect duct work from roofing nails/screws was not provided.
Please remove duct work in third-floor roof/ceiling assembly, install proper insulation
(minimum R-10), provide 1-1/2" protection from nails/screws under roof deck, and provide
ample space for duct work. Provide ample space for all duct work.
ALL WORK MUST BE INSPECTED BEFORE COVERING.
Dan Arlington, CBO
f•-vyr 1.`i- •
•
FORM R405-2014
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Pitler 290 Beach Ave Builder Name:
Street: 290 Beach Ave Permit Office: 261100
City,State,Zip: Atlantic Beach , FL,32233 Permit Number:
Owner: Jurisdiction: Atlantic Beach
Design Location: FL,Jacksonville
1. New construction or existing New(From Plans) 9. Wall Types(3380.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3380.00 ft2
b. N/A R= ft2
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 3 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types (1319.0 sqft.) Insulation Area
a.Roof Deck(Unvented) _ R=21.0 1319.00 ft2
6. Conditioned floor area above grade(ft2) 3326 b.N/A R= ft2
Conditioned floor area below grade(ft2) 0 c.N/A R= ft2
11. Ducts R ft2
7. Windows(671.0 sqft.) Description Area a.Sup:System 1,Ret:System 1,AH:System 1 6 332.6
a. U-Factor: Dbl,U=0.32 671.00 ft2 b.Sup: System 2, Ret:System 2,AH:System 2 6 332.6
SHGC: SHGC=0.30
b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 22.2 SEER:14.00
b.Central Unit 28.6 SEER:14.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a. Electric Heat Pump 22.2 HSPF:8.20
SHGC: b. Electric Heat Pump 28.6 HSPF:8.20
Area Weighted Average Overhang Depth: 2.896 ft.
Area Weighted Average SHGC: 0.300 14. Hot water systems
8. Floor Types (1319.0 sqft.) Insulation Area a. Electric Tankless Cap: 1 gallons
EF:0.950
a.Slab-On-Grade Edge Insulation R=0.0 1319.00 ft2 b. Conservation features
b.N/A R= ft2 None
c.N/A R= ft2 15.Credits CF, Pstat
Total Proposed Modified Loads: 78.58
Glass/Floor Area: 0.202 PASS
Total Baseline Loads: 78.19
I hereby certify that the plans and specifications covered by Review of the plans and .- Sp
this calculation are in compliance with the Florida Energy specifications covered by thisO� _ ;FOB•••
4+ v
calculation indicates compliance � E1
Code. Nortite Epgrg5erjrices P v1 iii ?,_,,.r`p C
)Ale a)< g,en f with the Florida Energy Code. • I +n,,, - w. :;: .,?..• , D
PREPARED BY: ______
,,,4/,. .,
-,1'( � -- _ Before construction is completed `' '� �+° `:
. ' O
DATE: _�- ' 3/-1/2016 " this building will be inspected for : ty y
•
compliance with Section 553.908 '. *l H- .4 4 tr ;-`
I hereby certify that this building as'desi9ned, is in compliance Florida Statutes. /,�,
with the Florida Energy Code. %.. COD x'1'4.
OWNER/AGENT: Y` "" _--
" „, i- '..-;* `- BUILDING OFFICIAL:
DATE: __ _- I. DATE:
. or,r) \
- Compliance requires certification by the$ir handler unit manufacturer that the air handler --:-_ _ - .ualifies as
certified factory-sealed in accordance with R403.2.2.1. rk, f ( (�
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance wit - . . en f= -- •
test report in accordance with R402.4.1.2. I
- Compliance requires a roof absorptance test and a roof emittance test in accordance wit ' , .7.2 i
IMAR 3 2016
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software
J
FORM R405-2014
PROJECT
Title: Pitler 290 Beach Ave Bedrooms: 3 Address Type: Street Address
Building Type: User Conditioned Area: 3326 Lot#
Owner: Total Stories: 3 Block/SubDivision:
#of Units: 1 Worst Case: No — PlatBook:
Builder Name: Rotate Angle: 0 Street: 290 Beach Ave
Permit Office: 261100 Cross Ventilation: County: Duval
Jurisdiction: Atlantic Beach Whole House Fan: City,State,Zip: Atlantic Beach ,
Family Type: Single-family FL, 32233
New/Existing: New(From Plans)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium
BLOCKS
Number Name Area Volume
1 Block1 1319 10552
2 Block2 2007 16056
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 System 1 1319 10552 Yes 4 0 1 Yes Yes Yes
2 System 2 2007 16056 No 0 3 1 Yes Yes Yes
FLOORS
V # Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio System 1 148 ft 0 1319 ft2 ---- 0.4 0 0.6
ROOF
V/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Gable or shed Metal 1475 ft2 330 ft2 Medium 0.75 Yes 0.9 Yes 2149.- 26.6
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full cathedral ceilin Unvented 0 1319 ft2 N N
■
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
FORM R405-2014
CEILING
V # Ceiling Type Space R-Value Area Framing Frac Truss Type _
1 Under Attic(Unvented) System 1 0.1 1319 ft2 0.11 Wood
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
# Ornt Tn---- Wall Type Space R-Value- -Ft -1n_ Ft In Area R-VaiuP-Fiartion Absor GradP%
1 E Exterior Frame-Wood System 1 19 18 0 8 0 144.0 ft2 0 0.23 0.8 0
2 S Exterior Frame-Wood System 1 19 15.5 0 8 0 124.0 ft2 0 0.23 0.8 0
3 S Exterior Frame-Wood System 1 19 8 0 8 0 64.0 ft2 0 0.23 0.8 0
4 S Exterior Frame-Wood System 1 19 17 0 8 0 136.0 ft2 0 0.23 0.8 0
5 W Exterior Frame-Wood System 1 19 20 0 8 0 160.0 ft2 0 0.23 0.8 0
6 N Exterior Frame-Wood System 1 19 2 0 8 0 16.0 ft2 0 0.23 0.8 0
7 N Exterior Frame-Wood System 1 19 15.5 0 8 0 124.0 ft2 0 0.23 0.8 0
8 W Exterior Frame-Wood System 1 19 15 0 8 0 120.0 ft2 0 0.23 0.8 0
9 N Exterior Frame-Wood System 1 19 18.5 0 8 0 148.0 ft2 0 0.23 0.8 0
10 E Exterior Frame-Wood System 1 19 17.5 0 8 0 140.0 ft2 0 0.23 0.8 0
11 E Exterior Frame-Wood System 2 19 18 0 8 0 144.0 ft2 0 0.23 0.8 0
12 S Exterior Frame-Wood System 2 19 11.5 0 8 0 92.0 ft2 0 0.23 0.8 0
13 N Exterior Frame-Wood System 2 19 3 0 8 0 24.0 ft2 0 0.23 0.8 0
14 S Exterior Frame-Wood System 2 19 8 0 16 0 128.0 ft2 0 0.23 0.8 0
15 S Exterior Frame-Wood System 2 19 6.5 0 8 0 52.0 ft2 0 0.23 0.8 0
_16 W Exterior Frame-Wood System 2 19 1 0 8 0 8.0 ft2 0 0.23 0.8 0
17 S Exterior Frame-Wood System 2 19 13.5 0 8 0 108.0 ft2 0 0.23 0.8 0
18 W Exterior Frame-Wood System 2 19 20 0 8 0 160.0 ft2 0 0.23 0.8 0
19 N Exterior Frame-Wood System 2 19 2 0 8 0 16.0 ft2 0 0.23 0.8 0
_20 W Exterior Frame-Wood System 2 19 8 0 8 0 64.0 ft2 0 0.23 0.8 0
_21 N Exterior Frame-Wood System 2 19 5 0 8 0 40.0 ft2 0 0.23 0.8 0
_22 W Exterior Frame-Wood System 2 19 6.5 0 8 0 52.0 ft2 0 0.23 0.8 0
_23 N Exterior Frame-Wood System 2 19 4 0 8 0 32.0 ft2 0 0.23 0.8 0
_24 N Exterior Frame-Wood System 2 19 8 0 8 0 64.0 ft2 0 0.23 0.8 0
_25 N Exterior Frame-Wood System 2 19 17 0 8 0 136.0 ft2 0 0.23 0.8 0
_26 E Exterior Frame-Wood System 2 19 17 0 8 0 136.0 ft2 0 0.23 0.8 0
_27 E Exterior Frame-Wood System 2 19 33 0 8 0 264.0 ft2 0 0.23 0.8 0
_28 S Exterior Frame-Wood System 2 19 28.5 0 8 0 228.0 ft2 0 0.23 0.8 0
_29 W Exterior Frame-Wood System 2 19 35 0 8 0 280.0 ft2 0 0.23 0.8 0
_30 N Exterior Frame-Wood System 2 19 22 0 8 0 176.0 ft2 0 0.23 0.8 0
DOORS
V # Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 E Insulated System 1 None .6 3 8 24 ft2
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2014
WINDOWS
Orientation shown is the entered,Proposed orientation.
VWall Overhang
# Ornt ID Frame Panes NFR U-Factor SHGC Area Depth Separation Int Shade Screening
2 S 2 Vinyl Low-E Double Ye 0.32 0.3 21.0 ft2 1 ft 0 in 1 ft 0 in None None
3 S 2 Vinyl Low-E Double Yes 0. S. 4.0 ft2 1 ft 0 in 1 ft 0 in None None
4 S 3 Vinyl Low-E Double Yes 0.32 0.3 24.0 ft2 1 ft 0 in 1 ft 0 in None Exterior 5
5 S 4 Vinyl Low-E Double Yes 0.32 0.3 24.0 ft2 1 ft 0 in 1 ft 0 in None None
6 W 5 Vinyl Low-E Double Yes 0.32 0.3 32.0 ft2 1 ft 0 in 1 ft 0 in None None
7 W 5 Vinyl Low-E Double Yes 0.32 0.3 24.0 ft2 0 ft 0 in 0 ft 0 in None Exterior 5
8 N 7 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 15 ft 0 in None None
9 W 8 Vinyl Low-E Double Yes 0.32 0.3 32.0 ft2 28 ft 0 in 0 ft 0 in None Exterior 5
10 N 9 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 12 ft 0 in None None
11 E 10 Vinyl Low-E Double Yes 0.32 0.3 48.0 ft2 10 ft 0 in 0 ft 0 in None None
12 E 11 Vinyl Low-E Double Yes 0.32 0.3 62.5 ft2 1 ft 0 in 1 ft 0 in None None
13 S 12 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 1 ft 0 in None None
14 N 13 Vinyl Low-E Double Yes 0.32 0.3 10.0 ft2 1 ft 0 in 1 ft 0 in None None
15 S 14 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 1 ft 0 in None None
16 S 15 Vinyl Low-E Double Yes 0.32 0.3 8.0 ft2 1 ft 0 in 1 ft 0 in None None
17 S 17 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 1 ft 0 in None None
18 W 18 Vinyl Low-E Double Yes 0.32 0.3 45.0 ft2 1 ft 0 in 1 ft 0 in None None
19 W 20 Vinyl Low-E Double Yes 0.32 0.3 14.0 ft2 1 ft 0 in 1 ft 0 in None None
20 N 21 Vinyl Low-E Double Yes 0.32 0.3 8.0 ft2 1 ft 0 in 8 ft 0 in None None
21 W 22 Vinyl Low-E Double Yes 0.32 0.3 8.0 ft2 1 ft 0 in 1 ft 0 in None None
22 N 24 Vinyl Low-E Double Yes 0.32 0.3 4.0 ft2 1 ft 0 in 1 ft 0 in None None
23 N 25 Vinyl Low-E Double Yes 0.32 0.3 30.0 ft2 1 ft 0 in 3 ft 0 in None None
24 N 25 Vinyl Low-E Double Yes 0.32 0.3 15.0 ft2 1 ft 0 in 8 ft 0 in None None
25 E 26 Vinyl Low-E Double Yes 0.32 0.3 45.0 ft2 1 ft 0 in 1 ft 0 in None None
26 E 27 Vinyl Low-E Double Yes 0.32 0.3 40.0 ft2 1 ft 0 in 1 ft 0 in None None
27 S 28 Vinyl Low-E Double Yes 0.32 0.3 22.5 ft2 1 ft 0 in 1 ft 0 in None None
INFILTRATION
# Scope Method SLA CFM 50 ELA EqLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000254 2217.3 121.73 228.93 .2721 5
HEATING SYSTEM
/ # System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump Split HSPF:8.2 22.2 kBtu/hr 1 sys#1
2 Electric Heat Pump Split HSPF:8.2 28.6 kBtu/hr 2 sys#2
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
FORM 8405-2014
COOLING SYSTEM
V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 14 22.2 kBtu/hr 666 cfm 0.75 1 sys#1
2 Central Unit Split ' SEER: 14 28.6 kBtu/hr 858 cfm 0.75 2 sys#2
HOT WATER SYSTEM
V # System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric Tankless Exterior 0.95 1 gal 60 gal 120 deg None
SOLAR HOT WATER SYSTEM
V FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
V/ --Supply-- —Return-- Air CFM 25 CFM25 HVAC#
# Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 System 1 6 332.6 ft System 1 83.15 ft Default Leakage System 1 (Default) (Default) 1 1
2 System 2 6 332.6 ft System 2 83.15 ft Default Leakage System 2 (Default) (Default) 2 2
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
Coolin - Jan ,x: Feb 1 Mar - A r Ma X Jun X Jul X Au X Se Oct Nov Dec
Heating X Jan Feb X'Mar Ar f 1 May f Jun f Jul 4 Aug 4 Sep ' Oct �Nov X1 Dec
Venting Jan Feb 'X Mar X Apr [ May [ Jun [ Jul [ 'Aug [ Se X Oct Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
FORM R405-2014
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 100
The lower the EnergyPerformance Index, the more efficient the home.
290 Beach Ave, Atlantic Beach, FL, 32233
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Frame Wood,Exterior R=19.0 3380.00 ftZ
b.N/A R= ft
3. Number of units,if multiple family 1 c. N/A R= ft2
4. Number of Bedrooms 3 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types Insulation Area
a.Roof Deck(Unvented) R=21.0 1319.00 ft2
6. Conditioned floor area(ft2) 3326 b.N/A R= ft2
7. Windows** Description Area c.N/A R= ft2
2
a. U-Factor: Dbl,U=0.32 671.00 ft2 11•Ducts R ft
a.Sup:System 1,Ret:System 1,AH:System 1 6 332.6
SHGC: SHGC=0.30 b.Sup: System 2,Ret:System 2,AH:System 2 6 332.6
b. U-Factor: N/A ft2
SHGC: 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 22.2 SEER:14.00
SHGC: b.Central Unit 28.6 SEER:14.00
d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency
SHGC: a. Electric Heat Pump 22.2 HSPF:8.20
Area Weighted Average Overhang Depth: 2.896 ft. b. Electric Heat Pump 28.6 HSPF:8.20
Area Weighted Average SHGC: 0.300
8. Floor Types Insulation Area 14.Hot water systems
Cap:1 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1319.00 ft2 a. Electric p EF:0.95
b.N/A R= ft2
c.N/A R= ft2 b. Conservation features
None
15.Credits CF, Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building ...gkiE ST
Construction through the above energy saving features which will be installed (or exceeded)
Ark ''•-
in this home before final inspection. Otherwise, a new EPL Display Card will be completed co `= �'0 '
__� �
P P Y p � '�� .;ter a,,,
based on installed Code compliant features. i r um.�- }^. ,Fn
Builder Signature: Date: :0 ' i; r :
,. w � _4.a e il
Address of New Home: City/FL Zip: �. :
COD w.il. ;
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
3/1/2016 3:50 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
FORM R405-2014
Florida Department of Business and Professional Regulations
Residential Whole Building Performance and Prescriptive Methods
ADDRESS: 290 Beach Ave Permit Number:
Atlantic Beach,FL,32233
MANDATORY REQUIREMENTS See individual code sections for full details.
? 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law
[Section 553.9085,Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C.
? R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.1 through R402.4.4.
9 R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The
sealing methods between dissimilar materials shall allow for differential expansion and contraction.
• R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in
accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction.
Where required by the code official,an approved third party shall inspect all components and verify compliance.
• R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air
changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with
a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or
other infiltration control measures;
2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended
infiltration control measures;
3.Interior doors,if installed at the time of the test,shall be open;
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and
6.Supply and return registers,if installed at the time of the test,shall be fully open.
? R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air.
? R402.4.3 Fenestration air IeakageYVindows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or
AAMANVDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
? R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm(0.944 L/s)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
? R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system.
? R403.1.3 Heat pump supplementary heat(Mandatory).Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
? R403.2.2 Sealing(Mandatory)eall ducts,air handlers,and filter boxes and building cavities that form the primary air containment
passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance
with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction
or rough-in testing below.
Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section
553.99,Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following:
1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area
when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All
register boots shall be taped or otherwise sealed during the test.
2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested
at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be
taped or otherwise sealed during the test.If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm
(85 Umin)per 100 square feet(9.29 m2)of conditioned floor area.
Exceptions:
1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope.
2. Duct testing is not mandatory for buildings complying by Section R405 of this code.
3/1/2016 3:51 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Conn Page 1 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturers designation for an air leakage of no more than 2 percent of the
design air flow rate when tested in accordance with ASHRAE 193.
R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)
or below 55°F(13°C)shall be insulated to a minimum of R-3.,
? R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused
by sunlight,moisture,equipment maintenance,and wind,and shall provide shielding from solar radiation that can cause degradation of the
material.Adhesive tape shall not be permitted.
R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily
accessible manual switch that can turn off the hot-water circulating pump when the system is not in use.
? R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
? R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies
7 R403.4.4.1 Storage water heater temperature controls
. R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls
capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum
temperature setting range shall be from 100°F to 140°F(38°C to 60°C).
. R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied
to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main bumer(s)
of combustion types of service water heating systems to be turned off.
9 R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of
• Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water
heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1.
. R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water
heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and
2. Be installed at an orientation within 45 degrees of true south.
7 R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation.
Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
? R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the
efficacy requirements of Table R403.5.1.
Exception:Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an
electronically commutated motor.
9 R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical
• ventilation shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62,Ventilation for Acceptable Indoor Air Quality,
shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics,crawlspaces,attached closed
garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a
minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise.
? R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment.
? R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and
indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors
which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation
such as standard kitchen and bathroom exhaust systems.
• R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the
calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
3/1/2016 3:51 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 2 of 3
FORM R405-2014
MANDATORY REQUIREMENTS - (Continued)
? R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal, rating-test value and
shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This
selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the
load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data,
the design value for entering wet bulb temperature and the design value for entering dry bulb temperature.
Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the retum duct(s)is installed in an unconditioned space.
Exceptions:
1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of
equipment may be sized in accordance with good design practice.
? R403.6.1.2 Heating equipment capacity
▪ R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section
R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load.
. R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.6.1.
' R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.6.1.
? R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Commercial Provisions in lieu of Section R403.
R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building,shall
include automatic controls capable of shutting off the system when the pavement temperature is above 55°F,and no precipitation is falling
and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F.
R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and
inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy
requirements for portable spas shall be in accordance with ANSI/APSP-14.
? R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted
outside the heater to allow shutting off the heater without adjusting the thermostat setting.
R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum
•
thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56.
Pool heaters fired by natural gas or LP gas shall not have continuously buming pilot lights.
▪ R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is
required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
? R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a
preset schedule shall be installed on all heaters and pumps.Heaters, pumps and motors that have built in timers shall be deemed in
compliance with this equipment.
Exceptions:
• 1. Where public health standards require 24-hour pump operations.
2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
? R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or
at the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or
▪ solar energy source computed over an operating season.
RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps.
Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps.
R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights
R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6.
? R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or
concrete deck roofs do not have sufficent space, R-10 is allowed.
3/1/2016 3:51 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 3 of 3
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Pitler 290 Beach Ave Builder Name:
Street: 290 Beach Ave Permit Office: 261100
City,State,Zip: Atlantic Beach,FL,32233 Permit Number:
Owner: Jurisdiction: Atlantic Beach
Design Location: FL,Jacksonville
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings,drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/door jambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated,and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls, or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
3/1/2016 3:51 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
Pitler 290 Beach Ave
HVAC Load Calculations
for
Bosco Builders
914.71Ini
II
RSs�o�x�L
HA
HVAC Los
1Ec: EIINi'C
'AAR 3 2016
Prepared By:
Tonya McDuffie
Home Energy Services,
2060,Davis Rd..
Jacksonviffe, FL 32218
904757-3569
Thursday,-March 3 2016
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
- g
E
�€g F
Project Report — - - --
Project Title: Pitler 290 Beach Ave
Designed By: Tonya McDuffie
Project Date: Thursday,July 30, 2015
Client Name: Bosco Builders
Company Name: Home Energy Services
Company Representative: Tonya McDuffie
Company Address: 2060 Davis Rd.
Company City: Jacksonville, FL 32218
Company Phone: 904 757-3569
Company E-Mail Address: ecalcs @hesjax.com
Company Website: www.hesjax.com
Company Comment:
Reference City: Jacksonville, Florida
Building Orientation: Front door faces East
Daily Temperature Range: Medium
Latitude: 30 Degrees
Elevation: 26 ft.
Altitude Factor: 0.999
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter: 32 29.92 n/a n/a 70 n/a
Summer: 94 77 47% 50% 75 48
Total Building Supply CFM: 1,622 CFM Per Square ft.: 0.488
Square ft.of Room Area: 3,325 Square ft. Per Ton: 964
Volume(ft3)of Cond. Space: 33,246
, �.s �,
Total Heating Required Including Ventilation Air: 37,617 Btuh 37.617 MBH
Total Sensible Gain: 35,644 Btuh 86 %
Total Latent Gain: 5,724 Btuh 14
Total Cooling Required Including Ventilation Air: 41,368 Btuh 3.45 Tons(Based On Sensible+ Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
r
•
•
•
•
-z
h `{.
C:\...\Pitler290BeachAve.rh9 Thursday, March 3,2016, 1:02 PM
13r ' _
M Miscellaneous Report
Winter: 32 29.92 80% n/a 70 n/a
Summer: 94 77 47% 50% 75 48.06
v_:..>�.;aa°b „_,_,,,,_,.•..,w/' ,.,.x ai & w;;,�,,,._�,aszsss.-:•.• ,w,
Winter: 32 29.92 80% n/a 70 n/a •
Summer: 94 77 47% 50% 75 48.06
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.01000 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 550 ft./min 450 ft./min
Maximum Velocity: 600 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in. 0 in.
, i.. .p �,�`�._-' F r .t`/° 2=a" /
_<�,... ; ...,. ��..._..,;... ,,,,,.. H,. �✓n ice..„., _.._,.,F.»�,.... �. ,....,._., ..,..<.�.�.<��..�.,�.,,._:... .,,..,�.�i„z.,,u,.,:>�t�.naN .,ti:;,,.,� �✓<._.,'v��'
Winter Summer
Infiltration Specified: 0.250 AC/hr 0.250 AC/hr
139 CFM 139 CFM
Infiltration Actual: 0.250 AC/hr 0.250 AC/hr
Above Grade Volume: X 33.246 Cu.ft. X 33,246 Cu.ft.
8,311 Cu.ft./hr 8,311 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 139 CFM 139 CFM
Total Building Ventilation: 0 CFM 0 CFM
--System 1---
Infiltration&Ventilation Sensible Gain Multiplier: 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference)
Infiltration&Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference)
Infiltration&Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.250 AC/hr(55 CFM)
Summer Infiltration Specified: 0.250 AC/hr(55 CFM)
---System 2--
Infiltration&Ventilation Sensible Gain Multiplier: 20.88 = (1.10 X 0.999 X 19.00 Summer Temp. Difference)
Infiltration&Ventilation Latent Gain Multiplier: 32.65 = (0.68 X 0.999 X 48.06 Grains Difference)
Infiltration &Ventilation Sensible Loss Multiplier: 41.76 = (1.10 X 0.999 X 38.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.250 AC/hr(84 CFM)
Summer Infiltration Specified: 0.250 AC/hr(84 CFM)
C:\...\Pitler290BeachAve.rh9 Thursday, March 3,2016, 1:02 PM
.. ...__..._...... .
'Rhvac-Residential&Light Commercial HVAC Leads --
ElkatioftwaroC lac.
Home Energy Services ,'",-Pit*,,,,,,- 280 Ave
Bead► . I
Jacksonville,FL 32218
Load Preview Report
IScope
Net ft.' Sen; Lati Net Sen H' 3 Sys Sys Duct
1 Ton Ron Area Gain Gain! Gain Loss 9I FM Size
_ _ CFMlI CFM CFM,
Bulking - - 1-----_...__. ,.� i
-_ - --- - 3.45 964 3,325 35,644 5,724 41,368 37,617 761 1,622 1,622
System 1 153 865 1,319 15,311 2,995 18,306 17,335 351 697 697 14
Zone 1
1.319 15,311 2,995 18,306 17,335 351 697 697 It
1-Foyer
279 2,194 409 2,603 4,097 83 100 100 1
2-Pantry I
64 611 98 709 1,070 22 28 28 0-0'
3-Bath
4�lohen 54 525 0 525 0 0 24 24 4 `
320 5,530 676 6206 4.472 90 252 252 7
5-Dining
233 1,613 372 1.985 3.603 73 73 73 7 I
6-Living 370 4,839 1,440 6,279 4,093 83 220 220 6,6 I
System 2 192 1,044 2,006 20,333 2,729 23,062 20,282 410,,.......925 925 14
Zone 1-Cl9.:71%,Htg.:65% 1,334 15,345 1,555 16,900 13.253 268 ,698 698
7-Bedroom/Study 234 3,534 322 3,856 4,186 85 181` 161 8
8-Hall And Stair Area 120 864 158 1,022 820 17 39 39 5
9-Bath 2nd Story 105 362 74 436 527 11 16 16 4
10-Bedroom 1 280 4,476 352 4,828 2,932 59 204 204 8
11-Master Bath 114 1,825 129 1,954 1,066 22 83 83 5
12-Master Toilette 39 691 104 795 569 12 31 31 4 1
13-Walk In Closet 1 56 150 0 150 0 0 7 7 4
14-Walk In Closet 2 63 244 79 323 425 9 ,. 11; 11 4 il
15-Master Bedroom And Hall 323 3,199 337 3536 2,728 55 1146 146 8 i
Zone 2-Cig.:29%,Htg_35% 672 6,416 1,174 7,590 7,029 142`' 292' 292 il
16-3rd Floor 672 6,416 1,174 7,590 7,029 142 r,. 292 292 7,7,5
Stan of room airflows may be greater than system airflow because i
System has multi pie zones. I
I
I
I
I
I
I
1
I
I
I ,
C:1...\Pitler290BeachAve.rh9 Thursday,March 3,2016, 1:02 PM
•
Rhvac:Residential&Light Commercial HVAC Loads Elite Sotlware DewiopnlNR,Inc.!i
Home Energy Services Piller 290 Beads Ave i';
JaCksonvee,FL 32218 le P890 41
Duct Size Preview
Roan or Source Minimum Maximum' Rough. Design( SP) Duct Dual Htg E Cig Act. i Duct
Duct Name Velocity: Velocity; Factor L/100, Loss Velocity; Length.] Flow Flow; Flow Size
System 1 _..._.._...._.___.._
i
Supply Runouts
Zone 1
1-Foyer Built-In 450 750 0.01 0.1 0 83 ei 100 1
2-Pantry Bu @-in 450 750 0.01 0.1 0 22 vim 28 0-0
3-Bath(SR-140) TMDD 0 0 0.01 0.08 0.00347 275 4 0
4-Kitchen(SR-130) TMDD 0 0 0.01 0.08 0.05405 942.9 12 90 fir' ,` 252 7
5-Dining(SR-120) TMDD 0 0 0.01 0.08 0.00392 273.2 10 73 ,,i., 73 7
6-Living(SR-100.SR-110) TMDD 0 0 0.01 0.08 0.01192 560.2 6 83 6
0 0 0.01 0.08 0.01192 560.2 6 ° 220 6
Other Duds in System 1
Supply Main Trunk(ST-100) TMDD 0 0 0.0003 0.08 0.00384 532.3 12 245 569 14
RT-100 TMDD 0 0 0.01 0.08 0.00084 608.3 1 697 ' • ??4' 697 11x15
RR-100 TMDD 0 0 0.01 0.08 0.00085 652 1 697 - 697 14
System 2
Supply Runouts
Zone 1
7-BedroondStudy(SR-150) TMDD 0 0 0.01 0.08 0.00639 461.2 7 85 ;, 161 8
8-Hall And Star Area(SR-210) TMDD 0 0 0.01 0.08 0.00273 286 4 17 ' `'; 39 5
9-Batty 2nd Story(SR-230) TMDD 0 0 0.01 0.08 0.00473 183.4 12 11 16 4
10-Bedroom 1(SR-220) TMDD 0 0 0.01 0.08 0.01164 584.4 8 59 9,e'g : 204 8
11-Master Bath(SR-190) TMDD 0 0 0.01 0.08 0.01207 608.7 4 22 . 83 5
12-Master Toilette(SR-200) TMDD 0 0 0.01 0.08 0.01429 355.2 10 12 <.°i.l 31 4
13-Walk In Closet 1 (SR-170) TMDD 0 0 0.01 0.08 000033 80.2 4 0 Ito, , 7 4
14-Walk In Cioset2(SR-180) TMDD 0 0 0.01 008 0.00182 126.1 9.5 9 " ' 11 4
15-Master Bedroom And Hall ',TMDD 0 0 0.01 0.08 0.00075 418.3 1 55 ' 146 8
ow
(SR-160)
Zone 2
163rd Floor(SR-25Q SR-260, 0 0 0.01 008 000068 363 1 ' 7
SR-270) TMDD 0 0 0.01 0.08 000068 363 1 142 - . 292 7
0 0 0.01 0.08 0.00411 711.4 1 5
-
Other Ducts in System 2
Supply Main Trunk(ST-110) TMDD 0 0 0.01 0.08 002682 865.3 18 411 Inn 925 14
ST-120 TMDD 0 0 0.01 0.08 0.00719 533.5 8 141 y 291 10 i
RT-110 TMDD 0 0 0.01 0.08 000074 662.5 1 925 INI 925 16
RR-110 TMDO 0 0 0.01 008 000074 662.5 1 925 MEI 925 16 i
Summary
System 1
Heating Flaw: 351 Design Friction Rate: 0229 TEL Return: 2
Cooing Flow 697 Total Ctmulative SP Loss: 0.06 TEL Supply: 24
Fan ESP: 0.06 Device SP Loss: 0 TEL Total: 26 tie Fan SP Available: 0.06 Ream Loss Added to Supply: 0.002
System 2
Heating Fltaty: 410 Design Friction Rate: 0.142 TEL Return: 2
Cooling Flow: 925 Total Ctmulative SP Loss: 0.043 TEL Supply: 28
Fan ESP: 0.043 Device SP Loss: 0 TEL Total: 30
Fan SP Available: 0.043 Return Loss Added to Supply: 0.001
614
. Z 00 „,11
--
C:1...\Pitler290BeachAve.rh9 Thu .
,1�1 �3, ', ?"�0�'PM
N. d''' r
� t
V
•.*9
RI�� t �erc t#�fAC 1
411HySer
04 vi e,I I . ,.
Tabular Manual D Ductsize Grid - System 9
Ducts Room Feeds Flow Diam Vel •
Zones •
L 'System 1-System 1
Supply
'B- ST 100 1 569 •14 532
4,SR-100 Living 1 110 '6 560 '.
S,SR-110 Living 1 110 6 560
,SR-120 Dining :1 73 7 273
•
SR-130;Kitchen'1 252 7 943
SR-140 Bath 1 24 4 275 •
iD Return
B %RT-100 697 14 608
RR-100 697 14 652
•
•
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
v4l l at&"LUgt roont tirdai HVAC Loads ak
;I _ - @ G
CksonvWe,FL 32218 $
Tabular Manual D Ductsize Grid - System 2
Ducts Room Feeds Flow Diam Vel
Zones
F) System 2-System 2
8 Supply
B 5/ST-110 1,2 925 14 865
4.SR-150 Bed room/Study 1 161 8 461
SR-160 Master Bedroom And Hal 1 146 8 418
1,SR-170 Walk In Closet 1 1 7 4 80
4,SR-180 Walk In Closet 2 1 11 4,.. 126
,SR-190 Master Bath 1 83 5 609
*SR-200 Master Toilette 1 31 4 355
SR-210 Hall And Stair Ares 1 39 5 286
*SR-220 Bed room 1 1 204 8 584
4,SR-230 Bath 2nd Story 1 16 4... 183
ID ST-120 2 291 10 534
*SR-250 3rd Floor 2 97 7 363
,SR-260 3rd Floor 2 97 7 363
*SR-270 3rd Floor 2 97 5 711
® Ili Return
9 RT-11C 925 16 662
RR-110 925 16 662
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
� � C � .� 8 Y g ' ( .' Bfv-
i yy
Jacksonville,FL 32248 Y �
Tabular Manual D Ductsize Data - Duct System 1 - Supply
°"'§e ms / „ar-97:777,_ r ., A 40/1 /, a,%"c �,.� y�*Y 7yy('
� � i
---Duct Name: ST-100, Effective Length: 12.0
Trunk 0.0003 14 532 0.004
Up: Fan 60 10.8 0.032 0.000
Rnd 12.0 15.3 0.0 0.004
Presize 569 44 0.054 0.006
--Duct Name: SR-100,Supplies: Living, Effective Length: 6.0
Runout 0.01 6 560 0.012
Up: ST-100 60 4.7 0.199 0.000
Rnd 6.0 6.6 0.0 0.012
Presize 110 9.4 0.042 0.017
---Duct Name: SR-110,Supplies: Living, Effective Length: 6.0
Runout 0.01 6 560 0.012
Up: ST-100 60 4.7 0.199 0.000 !.
Rnd 6.0 6.6 0.0 0.012
Presize 110 9.4 0.042 0.017
---Duct Name: SR-120,Supplies: Dining, Effective Length: 10.0
Runout 0.01 7 273 0.004
Up: ST-100 60 5.4 0.039 0.000
Rnd 10.0 7.7 0.0 0.004
Presize 73 18.3 0.050 0.009
--Duct Name: SR-130,Supplies: Kitchen, Effective Length: 12.07 943 0.054
Runout 0.01
Up: ST-100 60 5.4 0.450 0.000
Rnd 12.0 7.7 0.0 0.054
Presize 252 22 0.000 0.060
---Duct Name: SR-140, Supplies: Bath, Effective Length:4.0
4 275 0.003
Runout 0.01
Up: ST-100 60 3.1 0.087 0.000
Rnd 4.0 4.4 0.0 0.003
Presize 24 4.2 0.051 0.009
Report Units: Pressure: in.wg, Duct lengths:feet, Duct sizes: inch, Airflow: CFM, Velocity:ft./min, Temperature: F
Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit.
The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream
with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk
include any device pressure losses entered, and the cumulative may also include the total static pressure
,.,.. loss ohe re urn
side. « AT F d5 a04 ,i P,a - a ,,
Number of active trunks: 1
Number of active runouts: 5
Total runout outlet airflow: 569
Main trunk airflow: 569
Largest trunk diameter: 14 ST-100
Largest runout diameter: 7 SR-120
Smallest trunk diameter: 14 ST-100
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
Ritirpc aJ& tg#tcon i a,a1#ivAC L b, 6
i 1l
i-Jactooniee,FL 3218
Tabular Manual D Ductsize Data - Duct System 1 - Supply (cont'd)
Smallest runout diameter: 4 SR-140
Supply fan external static pressure: 0.060
Supply fan device pressure losses: 0.000
Supply fan static pressure available: 0.060
Runout maximum cumulative static pressure loss: 0.060 SR-130
Return loss added to supply: 0.002
Total effective length of return (ft.): 2.0 RR-100
Total effective length of supply(ft.): 24.0 SR-130
Overall total effective length (ft.): 26.0 RR-100 to SR-130
Design overall friction rate per 100 ft.: 0.229 (Available SP x 100/TEL)
System duct surface area (Scenario 1): 107.3 Main (Not linked to duct load)
Total system duct surface area: 107.3
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
Rhvac Resideneart Light Commercial HV r • ,
'FeEty ` ��
J �e,FL. 8. ,,,__
Tabular Manual D Ductsize Data - Duct System 2 - Supply
t o € "4 .' € �` �� i
r � �
---Duct Name: ST-110, Supplies Zones: 1,2(6%Diversity), Effective Length: 18.0
Trunk 0.01 14 865 0.027
Up: Fan 60 10.8 0.149 0.000
Rnd 18.0 15.3 0.0 0.027
Presize 925 66 0.014 0.028
--Duct Name: SR-150,Supplies: Bedroom/Study(in Zone 1), Effective Length: 7.0
Runout 0.01 8 461 0.006
Up: ST-110 60 6.2 0.091 0.000
Rnd 7.0 8.7 0.0 0.006
Presize 161 14.7 0.008 0.035
--Duct Name: SR-160, Supplies: Master Bedroom And Hall (in Zone 1), Effective Length: 1.0
Runout 0.01 8 418 0.001
Up: ST-110 60 6.2 0.075 0.000
Rnd 1.0 8.7 0.0 0.001
Presize 146 2.1 0.014 0.029
---Duct Name: SR-170,Supplies:Walk In Closet 1 (in Zone 1), Effective Length:4.0
Runout 0.01 4 80 0.000
Up: ST-110 60 3.1 0.008 0.000 !.
Rnd 4.0 4.4 0.0 0.000
Presize 7 4.2 0.014 0.029
---Duct Name: SR-180,Supplies:Walk In Closet 2(in Zone 1), Effective Length:9.5
Runout 0.01 4 126 0.002
Up: ST-110 60 3.1 0.019 0.000
Rnd 9.5 4.4 0.0 0.002
Presize 11 9.9 0.012 0.030
---Duct Name: SR-190, Supplies: Master Bath (in Zone 1), Effective Length:4.0
Runout 0.01 5 609 0.012
Up: ST-110 60 3.9 0.302 0.000
Rnd 4.0 5.5 0.0 0.012
Presize 83 5.2 0.002 0.040
---Duct Name: SR-200,Supplies: Master Toilette(in Zone 1), Effective Length: 10.0
Runout 0.01 4 355 0.014
Up: ST-110 60 3.1 0.143 0.000
Rnd 10.0 4.4 0.0 0.014
Presize 31 10.5 0.000 0.043
--Duct Name: SR-210,Supplies: Hall And Stair Area(in Zone 1), Effective Length: 4.0
Runout 0.01 5 286 0.003
Up: ST-110 60 3.9 0.068 0.000
Rnd 4.0 5.5 0.0 0.003
Presize 39 5.2 0.012 0.031
--Duct Name: SR-220,Supplies: Bedroom 1 (in Zone 1), Effective Length: 8.0
Runout 0.01 8 584 0.012
Up: ST-110 60 6.2 0.146 0.000
Rnd 8.0 8.7 0.0 0.012
Presize 204 16.8 0.003 0.040
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
,-RliviteAtesitkontkil-41 tight Contin AC �y
� x a
.FL 32218 - "` �, i
Tabular Manual D Ductsigze Data - Duct System 2 - Supply (cont'd)
�''' 1, 7 '1 4�k �`,: - mil' y - ,may -f ff
: �� s° x qt a r?
. . :-'1 - a
� \ S
..,__,.,r> s .,,,„=,.�,�,> �-,,. ., ,, nw, /. r,E4. fin ......s.. A e .,.,>tee, .,Y) .. ,.... ,.,, ';',741: 7-'14'j„:::,,/;1"740:;
---Duct Name: SR-230, Supplies: Bath 2nd Story(in Zone 1), Effective Length: 12.0
Runout 0.01 4 183 0.005
Up: ST-110 60 3.1 0.039 0.000
Rnd 12.0 4.4 0.0 0.005
Presize 16 12.6 0.010 0.033
--Duct Name: ST-120,Supplies Zone: 2, Effective Length: 8.0
Trunk 0.01 10 534 0.007
Up: ST-110 60 7.8 0.090 0.000
Rnd 8.0 10.9 0.0 0.007
Presize 291 20.9 0.007 0.035
---Duct Name: SR-250, Supplies: 3rd Floor(in Zone 2), Effective Length: 1.0
Runout 0.01 7 363 0.001
Up: ST-120 60 5.4 0.068 0.000
Rnd 1.0 7.7 0.0 0.001
Presize 97 1.8 0.006 0.036
--Duct Name: SR-260,Supplies: 3rd Floor(in Zone 2), Effective Length: 1.0
Runout 0.01 7 363 0.001
Up: ST-120 60 5.4 0.068 0.000
Rnd 1.0 7.7 0.0 0.001
Presize 97 1.8 0.006 0.036
--Duct Name: SR-270,Supplies: 3rd Floor(in Zone 2), Effective Length: 1.0
Runout 0.01 5 711 0.004
Up: ST-120 60 3.9 0.411 0.000
Rnd 1.0 5.5 0.0 0.004
Presize 97 1.3 0.003 0.040
Report Units: Pressure: in.wg, Duct lengths:feet, Duct sizes: inch,Airflow: CFM,Velocity:ft./min, Temperature: F
Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply,they are at the exit.
The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream
with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk
include any device pressure losses entered,and the cumulative may also include the total static pressure loss of the return
side.
" .^ P F,t i Ste... 4,4t , ,',a. x ,;;M 'f f,.g s' *. :. ..
Number of active trunks: 2
Number of active runouts: 12
Total runout outlet airflow: 989
Main trunk airflow: 925
Largest trunk diameter: 14 ST-110
Largest runout diameter: 8 SR-150
Smallest trunk diameter: 10 ST-120
Smallest runout diameter: 4 SR-170
Supply fan external static pressure: 0.043
Supply fan device pressure losses: 0.000
Supply fan static pressure available: 0.043
Runout maximum cumulative static pressure loss: 0.043 SR-200
C:\ ...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
eDyvy�&U Co eroa HVA C Odds
:Herne Energy „Tabular Manual D Ductsize Data Duct System 2 - Supply (cont'd)
Return loss added to supply: 0.001
Total effective length of return (ft.): 2.0 RR-110
Total effective length of supply(ft.): 28.0 SR-200
Overall total effective length (ft.): 30.0 RR-110 to SR-200
Design overall friction rate per 100 ft.: 0.142 (Available SP x 100/TEL)
System duct surface area(Scenario 1): 173 Main (Not linked to duct load)
Total system duct surface area: 173
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
Rhvas-Residendtd44,4ght CommerstattIVAC Loads -is
SornettitlYS*440.68- 1300-M-0
Jacksorivifre,FL 32218
Tabular Manual D Ductsize Data - Duct System '1 - Return
---Duct Name: RT-100, Effective Length: 1.0
Trunk 0.01 14 608 0.001
Up: Fan 60 11 0.084 0.000
Rect 1.0 15 0.0 0.001
Nearest Inch 697 4.3 -0.001 0.002 !.
--Duct Name: RR-100, Effective Length: 1.0
Runout 0.01 14 652 0.001
Up: RT-100 60 10.8 0.085 0.000
Rnd 1.0 15.3 0.0 0.001
Nearest Inch 697 3.7 0.000 0.001
Report Units: Pressure: in.wg, Duct lengths:feet, Duct sizes: inch,Airflow: CFM,Velocity:ft./min,Temperature: F
Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply,they are at the exit.
The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream
with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk
include any device pressure losses entered, and the cumulative may also include the total static pressure loss of the return
side.
,may
. _ E tit � . , .� � ,I
Number of active trunks: 1
Number of active runouts: 1
Total runout outlet airflow: 697
Main trunk airflow: 697
Largest trunk diameter: 14 RT-100
Largest runout diameter: 14 RR-100
Smallest trunk diameter: 14 RT-100
Smallest runout diameter: 14 RR-100
Runout maximum cumulative static pressure loss: 0.001 RR-100
Return loss added to supply: 0.002
Total effective length of return (ft.): 2.0 RR-100
System duct surface area(Scenario 1): 8 Main (Not linked to duct load)
Total system duct surface area: 8
C:\ ...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
_ _ivtigm ,r4foreej4s, _ . , . ,..,- 1l
Jk? 11e Fi- W�'" ., -r yi - o i
A §
Tabular Manual D Ductsize Data - Duct S stem 2 - Return
i
�� �,.,ka h >>Me /' A..: td...�i�.� :.., ...." � ��6, ;.,...• �,,;�: /iby/s�n/
---Duct Name: RT-110, Effective Length: 1.0
Trunk 0.01 16 663 0.001
Up: Fan 60 12.4 0.074 0.000
Rnd 1.0 17.5 0.0 0.001
Nearest Inch 925 4.2 -0.001 0.001
---Duct Name: RR-110, Effective Length: 1.0
Runout 0.01 16 663 0.001 !:
Up: RT-110 60 12.4 0.074 0.000
Rnd 1.0 17.5 0.0 0.001
Nearest Inch 925 4.2 0.000 0.001
Report Units: Pressure: in.wg, Duct lengths:feet, Duct sizes: inch, Airflow: CFM, Velocity:ft./min, Temperature: F
Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit.
The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream
with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk
include any device pressure losses entered,and the cumulative may also include the total static pressure loss of the return
side.
Number of active trunks: 1
Number of active runouts: 1
Total runout outlet airflow: 925
Main trunk airflow: 925
16 RT-110
Largest trunk diameter:
Largest runout diameter: 16 RR-110
Smallest trunk diameter: 16 RT-110
Smallest runout diameter: 16 RR-110
0.001 RR-110
Runout maximum cumulative static pressure loss:
Return loss added to supply: 0.001
Total effective length of return (ft.): 2.0 RR-110
System duct surface area(Scenario 1): 8.4 Main (Not linked to duct load)
Total system duct surface area: 8.4
'Rhvac is an ACCA approved Manual J and�Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Pitler290BeachAve.rh9 Thursday, March 3,2016, 1:02 PM
', F �1 � __ .._.
Tabular Manual D Ductsize - Pressure Changes Graph - System 1
Pressure Changes Through Route with Highest Static Pressure Loss
0.08
-
0.07
0.06
E •
0.05
• 0.04
a• 0.03-
a. -
0.02 •_ •"
0.01
A
0.00 _-_ —.._ -- -- - - - -
- G F
■B
-0.01
• Static Pressure Available
• Velocity Pressure
Total Pressure Available
Notes: Return side point values are at entrance of duct,while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure available at
the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan Exit] is drawn
to show the static pressure available at the exit of the fan. Any device pressure losses entered for the supply main trunk
are accounted for between the fan entry and exit points.
A RR-100 0.000 0.027
B RT-100 -0.001 0.023
C [Fan Entrance] -0.002 0.022
D [Fan Exit] 0.058 0.076
E ST-100 0.054 0.072
F SR-130 0.000 0.056
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
row=-aosidetcortmorciamActoat*,
Sehirdit- �y r
Jadcsorivile;Fes.'32410
W ......
Tabular Manual D Ductsize - Pressure Changes Graph - System 2
Pressure Changes Through Route with Highest Static Pressure Loss
0.09
0.08
0.07
0.06
3 0.05
•
5 D
m 0.04
•
•
a 0.031
0.02
0.01
•
IA
0.00 •
-0.01
• Static Pressure Available
• Velocity Pressure
Total Pressure Available
Notes: Return side point values are at entrance of duct,while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure available at
the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan Exit]is drawn
to show the static pressure available at the exit of the fan. Any device pressure losses entered for the supply main trunk
are accounted for between the fan entry and exit points.
..ag 'idLmwa,+ia
A RR-110 0.000 0.028
B RT-110 -0.001 0.027
C [Fan Entrance] -0.001 0.026
D [Fan Exit] 0.041 0.089
E ST-110 0.014 0.062
F SR-200 0.000 0.008
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
i Rpyac R. CornmentatilW44 e 4, ; s "ist ms
J 3
,ls:] ► ,FLT . H.__ _._..
Total Building Summary Loads
I � NI 'Z.# e '' 4i "" i "' .
''�
J�'des.. � �Yz°- _ <: ��a -� 2 " : ;,, '' _ ' ,
4A-6-o: Glazing-Double pane low-e(e=0.20 or less), 585 7,106 0 13,108 13,108
high performance,operable window, a=0.05 on
surface 2, any frame, u-value 0.32, SHGC 0.3
4A-2a-d: Glazing-Double pane low-e(e=0.20 or less), 80 1,430 0 2,301 2,301
sliding glass door, a=0.20 on surface 3,wood with
metal clad frame, outdoor insect screen with 50%
coverage, u-value 0.47, SHGC 0.52
10D-f: Glazing-French door,double pane low-e glass(e= 48 766 0 702 702
0.10), insulated fiberglass frame, u-value 0.42,
SHGC 0.32
11J: Door-Metal-Fiberglass Core 24 547 0 432 432
12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 2643 6,831 0 3,846 3,846
cavity, no board insulation, siding finish, wood studs
18A1-21o: Roof/Ceiling-Roof Joists Between Roof Deck 1554 2,776 0 2,192 2,192
and Ceiling or Foam Encapsulated Roof Joists,
Spray Foam Insulation, Dark or Bold-Color Asphalt
Shingle, Dark Metal, Dark Membrane, Dark Tar and
Gravel, R-21 open cell 1/2 lb. spray foam, 5.5 inches
in 2 x 6 joist cavity, 1 inch on joist
22A-ph: Floor-Slab on grade, No edge insulation, no 181 9,342 0 0 0
insulation below floor, any floor cover, passive, heavy
moist soil
20P-19-c: Floor-Over open crawl space or garage, 1595.5 3,033 0 1,117 1,117
Passive, R-19 blanket insulation, carpet covering
Subtotals for structure: 31,831 0 23,698 23,698
People: 6 1,200 1,380 2,580
Equipment: 0 6,950 6,950
Lighting: 0 0 0
Ductwork: 0 0 0 0
Infiltration:Winter CFM: 139, Summer CFM: 139 5,786 4,524 2,890 7,414
Ventilation:Winter CFM: 0, Summer CFM: 0 0 0 0 0
AED Excursion: 0 0 726 726
Total Building Load Totals: 37,617 5,724 35,644 41,368
as Win. -R:=`;' ,� .<, :_ ,,, : .3, �; .��,,4,. .. ,. .:.�,„� ; ..u.,,.,„:, a;r�,�2,h.:i,. ,
Total Building Supply CFM: 1,622 CFM Per Square ft.: 0.488
Square ft. of Room Area: 3,325 Square ft. Per Ton: 964
Volume(ft3)of Cond. Space: 33,246
Total Heating Required Including Ventilation Air: 37,617 Btuh 37.617 MBH
Total Sensible Gain: 35,644 Btuh 86
Total Latent Gain: 5,724 Btuh 14 %
Total Cooling Required Including Ventilation Air: 41,368 Btuh 3.45 Tons(Based On Sensible+Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
iktiot sornmercrid •
Jaók8onvllle FL 3218
,
Building Pie Chart
Infiltration 15%
Floor 33% Door 1%
Building
Loss
37,617
Btuh
Glass 25%
Roof 7%
Wall 18%
r
Roof F51%°° AED Excursion 2%
Wall 9% Infiltration 18%
\
Building
Gain
41,368
Btuh Equipment 17%
Glass 39%
People 6%
Door 1%
C:\ ...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
exgr Sri# re ' d
Jacksanvile FL:3 11
Equipment Data - System 1 - System 1
Cooling
System Type: Air Source Heat Pump
Outdoor Model: 214DNCO24****A
Indoor Model: FB4CNP025L
Tradename: BRYANT HEATING AND COOLING SYSTEMS
Outdoor Manufacturer: BRYANT HEATING AND COOLING SYSTEMS
Description: Air Source Heat Pump
AHRI Reference No.: 8254821
Nominal Capacity: 22200
Adjusted Capacity: 18087
Adjusted Sensible Capacity: 16110
Adjusted Latent Capacity: 1977
Efficiency: 14 SEER
Heating
System Type: Air Source Heat Pump
Model: 214DNCO24****A
Tradename: BRYANT HEATING AND COOLING SYSTEMS
Manufacturer: BRYANT HEATING AND COOLING SYSTEMS
Description: Air Source Heat Pump
Capacity: 22000
Efficiency: 8.2 HSPF
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 94F, SOWB: 77F, WODB: 32F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.gain:
15,311 Btuh, Lat. gain: 2,995 Btuh, Sen. loss: 17,335 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg.coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD:45F, Req. clg. airflow: 697 CFM, Req. htg.airflow: 351 CFM
C:\...\Pitler290BeachAve.rh9 Thursday, March 3,2016, 1:02 PM
I� n &Ug Confli ct I fi i $
Jacksbrivffie,FL'2=$
Equipment Data System 2 - System 2
Cooling
System Type: Air Source Heat Pump
Outdoor Model: 214DNA030****A
Indoor Model: FB4CNF030L+TXV
Tradename: BRYANT HEATING AND COOLING SYSTEMS
Outdoor Manufacturer: BRYANT HEATING AND COOLING SYSTEMS
Description: Air Source Heat Pump
AHRI Reference No.: 8295898
Nominal Capacity: 28600
Adjusted Capacity: 22166
Adjusted Sensible Capacity: 18028
Adjusted Latent Capacity: 4138
Efficiency: 14 SEER
Heating
System Type: Air Source Heat Pump
Model: 214DNA030****A
Tradename: BRYANT HEATING AND COOLING SYSTEMS
Manufacturer: BRYANT HEATING AND COOLING SYSTEMS
Description: Air Source Heat Pump
Capacity: 28600
Efficiency: 8.2 HSPF
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 94F, SOWB: 77F,WODB: 32F, SIDB: 75F, SIRH: 50%,WIDB: 70F, Sen.gain:
20,333 Btuh, Lat.gain: 2,729 Btuh, Sen. loss:20,282 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg.coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD:45F, Req. clg.airflow: 925 CFM, Req. htg. airflow:410 CFM
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
F
�� ..:: S/y x .ate dy 6 .P E 1 � �' -„�" k
Manual S Performance ce Data - System I - System 1
aaita. m a a m _ _
Outdoor Dry Bulb: 94 Sensible Gain: 15,311
Outdoor Wet Bulb: 77 Latent Gain: 2,995
Indoor Dry Bulb: 75 Total Gain: 18,306
Indoor RH: 50 Load SHR: 0.84
Elevation: 26 Supply Airflow: 697
Latitude: 30 Entering Dry Bulb: 75
Altitude Factor: 1 Entering Wet Bulb: 62.5
`"m aka a,a;_aa i",�aaaa 'a _ o dwP s "_a€ "tix . a.
Air Source Heat Pump Model: 214DNCO24****A+FB4CNP025L, Nominal Capacity: 22,200
Entered Interpolation Data:
yr.1
v�ar
vat
21.45 1.73 0.992 21.27
20.5 1.94 1 20.5
i �� t°; i
11 j 2208 1.75 1 22.08
4 21.14 1.95 1 21.14
21.7 1.73 0.766 16.62
20.6 1.94 0.784 16.15
2202 175 0.799 17.59
20.88 1.96 0.819 17.1
Other Adjustments:
Elevation Derating: 1, Miscellaneous: 1, Direct Capacity Adjustment: -2.953
Interpolation Results:
Percent
Load of Load
Sensible Capacity: 16,110 15,311 105%
Latent Capacity: 1,977 2,995 66%
Total Capacity: 18,087 18,306 99%
Power Input: 1.93
This system's equipment was selected in accordance with ACCA Manual S.
C:\ ...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
i ti �ct *Vight��>k1>�AC ; b
PL 32210 _
Manual S Performance Data - System 2 - System 2
W,s w, Q '•fe :.",Q .sa:e¢ `...LS f,3e__h f,h✓n/: i, _,;, •nom .. _ ,., _ ....._ a5 •'^y'� �� ... .. .s !..
Outdoor Dry Bulb: 94 Sensible Gain: 20,333
Outdoor Wet Bulb: 77 Latent Gain: 2,729
Indoor Dry Bulb: 75 Total Gain: 23,062
Indoor RH: 50 Load SHR: 0.88
Elevation: 26 Supply Airflow: 925
Latitude: 30 Entering Dry Bulb: 75
Altitude Factor: 1 Entering Wet Bulb: 62.5
Air Source Heat Pump Model: 214DNA030****A+FB4CNF030L+TXV, Nominal Capacity:28,600
Entered Inter.olation Data:
-4 g,,4;i44:44,44.7.
85,1
e 26.74 2.17 0.918 24.55
it 25.44 2.41 0.939 23.9
27.62 2.21 0.991 27.37
26.36 2.45 0.886 23.36
27.22 2.17 0.731 19.89
,e 25.86 2.41 0.746 19.29
27.91 2.21 0.775 21.62
26.47 2.45 0.793 21
Other Adjustments:
Elevation Derating: 1, Miscellaneous: 1, Direct Capacity Adjustment: -4.362
Interpolation Results:
Percent
Load of Load
Sensible Capacity: 18,028 20,333 89%
Latent Capacity: 4,138 2,729 152%
Total Capacity: 22,166 23,062 96%
Power Input: 2.42
This system's equipment was selected in accordance with ACCA Manual S.
C:1...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
'# comm Rf}y,NN i s 3 «1 ,
a ' 41 9 '.
A K'4
System 1 Room Load Summary
s te8 z. `� ¢ . 4 ,„ -', �to � - , ff
� q -
<.._.,a ._<_.._.r., fir �v
---Zone 1---
1 Foyer 279 4,097 83 0-0 0 2,194 409 100 100
2 Pantry 64 1,070 22 0-0 0 611 98 28 28
3 Bath 54 0 0 4 - 525 0 24 24
4 Kitchen 320 4,472 90 7 - 5,530 676 252 252
5 Dining 233 3,603 73 7 - 1,613 372 73 73
6 Living 370 4,093 83 6,6 - 4,839 1,440 220 220
System 1 total 1,319 17,335 351 15,311 2,995 697 697
System 1 Main Trunk Size: 14 in.
Velocity: 532 ft./min
Loss per 100 ft.: 0.032 in.wg
Duct size results above are from Manual D Ductsize.
Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room.
See the Manual D Ductsize report for duct velocities and
othe r data�,,.
a '%,, �r /e�- 7 1'�� z? „ !s ee 8 .� . 3 _ , , q /'/ ,4,,V; r/ ',.,� 8 8 3 1 a s a a # 8'` ; , ' 2,99 5_ s� 18,306 1.53 84%/ 16% 15,311 Net Required:
Actual: 1.85 75%/25% 16,650 5,550 22,200
�. : 1 gr a srF.7 v z �u ' _ - *1 a�C hr'..';
Heating System Cooling System
Type: Air Source Heat Pump Air Source Heat Pump
Model: 214DNCO24****A 214DNCO24****A
Indoor Model: FB4CNP025L
Brand: BRYANT HEATING AND COOLING BRYANT HEATING AND COOLING
SYSTEMS SYSTEMS
Description: Air Source Heat Pump Air Source Heat Pump
Efficiency: 8.2 HSPF 14 SEER
Sound: 0 0
Capacity: 22,000 Btuh 22,200 Btuh
Adjusted Capacity: n/a 18,087 Btuh
Sensible Capacity: n/a 16,650 Btuh
Adjusted Sensible Capacity: n/a 16,110 Btuh
Latent Capacity: n/a 5,550 Btuh
Adjusted Latent Capacity: n/a 1,977 Btuh
AHRI Reference No.: n/a 8254821
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB:94F, SOWB: 77F, WODB: 32F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.gain:
15,311 Btuh, Lat. gain: 2,995 Btuh, Sen. loss: 17,335 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg.coil TD: 20F, Htg.coil TD:45F, Req. clg. airflow: 697 CFM, Req. htg.airflow: 351 CFM
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
'Rhv i�al&'� .HVAC Leads : k' 6 t b 2 3
Home .° �t"c s , A
: ...., `. ..., �•
_ -�!. iii.,,
System 2 Room Load Summary
s : y r Sy a ; 5-4717.4,.1„ ,0 s a
---Zone 1---
7 Bedroom/Study 234 4,186 85 8 - 3,534 322 161 161
8 Hall And Stair Area 120 820 17 5 - 864 158 39 39
9 Bath 2nd Story 105 527 11 4 - 362 74 16 16
10 Bedroom 1 280 2,932 59 8 - 4,476 352 204 204
11 Master Bath 114 1,066 22 5 - 1,825 129 83 83
12 Master Toilette 39 569 12 4 - 691 104 31 31
13 Walk In Closet 1 56 0 0 4 - 150 0 7 7
14 Walk In Closet 2 63 425 9 4 - 244 79 11 11
15 Master Bedroom 323 2,728 55 8 - 3,199 337 146 146
And Hall
Zone 1 subtotal 1,334 13,253 268 15,345 1,555 698 698
---Zone 2--
16 3rd Floor 672 7,029 142 7,7,5 - 6,416 1,174 292 292
Zone 2 subtotal 672 7,029 142 6,416 1,174 292 292
System 2 total 2,006 20,282 410 20,333 2,729 925 925
System 2 Main Trunk Size: 14 in.
Velocity: 865 ft./min
Loss per 100 ft.: 0.149 in.wg
Duct size results above are from Manual D Ductsize.
Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room.
See the Manual D Ductsize report for duct velocities and other data.
Note: Since the system is multizone,the Peak Fenestration Gain Procedure was used to determine glass sensible gains
at the room and zone levels,so the sums of the zone sensible gains and airflows for cooling shown above are not intended
to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which
the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the"Average Load
Procedure+ Excursion"method. •
... «a . : .
� 4 it�4� ,," , ._ "� ate F la �,..i, � ,
Net Required: 1.92 88%/ 12% 20,333 2,729 23,062
Actual: 2.38 75%/25% 21,450 7,150 28,600
Heating System Cooling System
Type: Air Source Heat Pump Air Source Heat Pump
Model: 214DNA030****A 214DNA030****A
Indoor Model: FB4CNF030L+TXV
Brand: BRYANT HEATING AND COOLING BRYANT HEATING AND COOLING
SYSTEMS SYSTEMS
Description: Air Source Heat Pump Air Source Heat Pump
Efficiency: 8.2 HSPF 14 SEER
Sound: 0 0
Capacity: 28,600 Btuh 28,600 Btuh
Adjusted Capacity: n/a 22,166 Btuh
Sensible Capacity: n/a 21,450 Btuh
Adjusted Sensible Capacity: n/a 18,028 Btuh
Latent Capacity: n/a 7,150 Btuh
Adjusted Latent Capacity: n/a 4,138 Btuh
AHRI Reference No.: n/a 8295898
C:\ ..\Pitler290BeachAve.rh9 Thursday, March 3,2016, 1:02 PM
Rhvac tt @PCfaI}MAC Loads », M
Liacksonvae r x 7
System 2 Room Load Summary (cont'd)
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 94F, SOWB: 77F,WODB: 32F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.gain:
20,333 Btuh, Lat.gain: 2,729 Btuh, Sen. loss:20,282 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg.coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD:45F, Req. clg. airflow: 925 CFM, Req. htg. airflow:410 CFM
C:\...\Pitler290BeachAve.rh9 Thursday, March 3, 2016, 1:02 PM
vi
w d
_ V p i V V
• N Q g T N N T
D N 8
O / L
O
O
• l7 D (7 O D O
D lr
p O
O co co a co V N O O J N O O V O e O `1 J O N r A J N O V N N W N V O V j W r NN N'.N V O r O J N V• T• O• W V ON i O V N J N;+N N W W V N N N m O T 9
-4 a tv,
<• O.. *_C -+IV CD v*A v n W 2-
O
N N N W W N N N W W N N N W 0 N N N N N N N N N N N N N N N -{ O
O f0 f0 co co co co A V co V O O 0 O 0 N N 4 A J N N N A co N p A or co 0 Q 0•
O W NCOO ON fNJ1 o CND-,N N1p`�O V m 8 or 'co V N 1OOIWJI O N V(NJ V-•N N 8J V 1 s 2
O Z
N N N N NNN N+NNNN-+ 0 O▪ N
N - - - N N CO
co D 5°co co Vw O-`N 2 C N • Oo•A 99 O C N S N
I•+'D O0 N W N A O+OO N S A N)C pp O N C ON W V o p I+ S
OOOA JO +V OO CO N N S .co 4 v v M
N N N N N N N N N N "A C %G 1 u
O O O G G O C CD G C O O O O O ut N.' N N N O N ut ut ill to N N N
W co W N N+ +O V V J J V •3 s V J J CA N U•N N N A W W W W d s d-
N N N W W N N N W W N N N o W
V CO CO O W V V V O W O O V 0 N O 0 N N h N W N N+N N N N O N N N N
O.4 (
1111111111111 .
WN WOr -. NCO N N m h m N O m N N A O O N CO N CO co W N CO fJ1 A N J
i . I
N N N N+N N N N+N N+N+ N O 1 N N „"+++N ++++ co m �'
V co N W m V V-.N J Opp A t0 O or pd C 1�pO N N. co P O V co O t0 co p�O4 co 2 C -p.
00 O N A J tW0 O V N 1O O OJ N f0 N N �} S A N m 10L m-•0 io v N A A N m O A co O ' S A _
to m
N N N N N N N N N N N N N N N
Al N N N N N N N N N •w w V V• V V •J J J V•V V V•V •J■J
W W W W W O V J J J /O.d N N a N P W W W W N N N N 3 Pi
i 3 m
J
O o I
N N N N W N N N N W N N N N co O
1 V j N N N N N N N+ N N N A
O O 92 O O 0 W 0(�0 p 0p��+N y Ny O NO co J O� C) � N A 0 0 0p�N p Ap 0 is-.0 +Ap� Ow ()O W(0 N m cco O V O V-•A O O V g 3 8 A •• 1A0 1J.1 V 0 0 0 A O tNJ N W d L.9.-,
N ; Z N ; Z 11111131111 it
N O
N N N N+N N 43 N+N N+N n 10 0 2.
010, N V AO V N�0(000,= 0 * N m N - O+W m - m O COD-,A m W am V o�O cNo co O. « S N y �' in OV s t'H FT1 ..__ s m s N N N N N N N p Np N p Np N N N p Np y Ny, .a 1 a;-+ {.p m tS1 0 m I p ggm OO N 0Ai 01 dA A A:00 Z ya _ n N .' N A A A A t8J NN N N 2`2 Z *d c 1 Z 2 d s w 3 > ° 3 D ° 3
x _ I I = a
N N N N N N N N N N N N N N N�O 5 .4 IJI N N-' Iro N + +N N -. N N - .•l m 0 ■_ 3
co co co V 10 N N A O O CO A A O f0 O (7 O O tC W co O 0 O f0 Co.E°.CO CO O N 0_ O n ;N N N O CO 01 co co co,co A A 94 O O O 0q d
N N++t0 O w ttpp V O G W W+0 g d Q N��..JO of A O 19, O. O 0 g d O O O O p�A A p CO A )O+A O E T
N co N A O O N A N m co J CO CO N 9 3 m N A R O W W V t W V t O+N N O 8 m-.W O+W+W A f0 O+W O O 0 'g m
0 0 21 1n O 1 w O 9
N ( `1). N N N N N N N N N N N = m •
7I O O m t0 0 a C r,O O V W 10 50 N O N m m A N N 7 y N N N W O N N+N A W++ J , y
0, O m�I O N N
N N O O+O+W W O O+O O N d S $ N A in' A"Si N 0 W W W O V s 42 N M S O 0 W H O N A A <0 O+O O M. it T N N W J W fO N A N O O J•
O A T T
v
3 "a
co 7c 41) x.31
WW▪ .fVJ W W V�IJLIJ JOJl�V J 3d OO1C CO V V V V 000O0N A 3g OVi0VJNAJA A AU10W CD CD W A :3g
W N JW W W N J NN AJ A A N g C 10 O Q C O-•CO CO CO(O,-4 V V V>-• s C A AA 01 V A A A N J WA A N M S
AA pp A N0OV N p JO O p A N N O 0 0 OCW O m 9 V p -•N A p p CO
co- N Vi to V<c.O-A 10 m 8 f0 co O A O cn J d /
A d O
N NN ry+N N+N+NN+++ N O• N
NO N . + W N
A O N ' O ONN N O Nj C '' A AN N�A A++�( A O : 0
- +W W A V J W O O A O O O O • S W O V G C m a 8 WG+3 8 8 N S * W S p O N A 8 8 W O p'8 N W S p
W N O N A A J +V V O N J 14 A
'JS�N 7CN.4 +++N %O or
0 0 0 0 0 0 0 0 0 0 1O O O 1D N *i A J+ P y Ny P P P Np F p Np A P A P A c �p Otp
co co co CA CD CD CO CD CO CD N IV CV N W W W W W+++N N V V J CO N R N CO.' P N A A A A W W N N N N+ :111 CO O m WO f0 O V V V V OO CT C.N O co ;§_
N N ro N N N N IV N CO CV j CV Al N + + + N + + ++ N
N 4p 3� CJ 0 Al N CO N N N O 0 . . . coo . . 0 0 0 O Omm O V 0 w o co W LJ pAp N W W fJ A N W W N A N s A
Co(J co-•Co ONi m N J-•v o N o CNO - 8• m V J m m i 0 0 W N W v m V COO 01 A N J 100 CO v J Co 0 COO A T g
O O O
.T 4 ?
ro
N N+N+N N+++N +++ O CO▪ N O O O CO CO
N
N NO O N N OO N-'4)J O A 7 � J J IJ W N J J A N -O O 9A> > C P W N N W W O 7'ipW 9 O.0 N 7 E
O W'88 Cf N 83 A Jo NON S S O m V m 0 88 8 WNO N+ ' S 21 V SFo'NN J Fo'Nm 0 O O 880
a S -
co N co co
CWD co W W co W CWO W OWl OWO N N N N N co R d A OJi tJT A A N A A W fJJ W N N 3 m is.,is,CND W OI N N-.N W O O D-.N 1/s
0 �- JJ