1637 ATLANTIC BEACH DR - DENSITY REPORT FORM BOARD ELEVATION CERTIFICATE
Date 4/,//i4, Permit Number: /Co eoP
Address: /4. / .#Trotu77c 8r,' ' PR./ i. .4 f/
All American Surveyors Work Order # ilar=egoo=Ezzi /468
Required Slab Elevation on City Approved Site Plan:
Actual Elevation of Form Board or Grade Stake:
fo. 4/
Survey Company:
ALL AMERICAN SURVEYORS OF FLORIDA INC.
3751 San Jose Place, Suite 15
Jacksonville FL 32257 Work Phone: 904-279-0088
Signature of Surveyor: (PartyChief)
UNIVERSAL UES Project No: 0910.1400187.0000
il pi
Workorder No: 169950-1
ENGINEERING SCIENCES Report Date: 4/11/2016
Consultants In:Geotechnical Engineering•Environmental Sciences
Geophysical Services•Construction Materials Testing•Threshold Inspection
Building Inspection•Plan Review•Building Code Administration
5561 Florida Mining Blvd So.,Jacksonville, 32257 • P: 904-296-0757 • F: 904-296-0748
In-Place Density Test Report
Client: UES Technician: Kori Osteen
160 Cape May Avenue
Ponte Vedra, FL 32081 Date Tested: 04/11/2016
Project: Atlantic Beach Country Club
Area Tested: 7 Type of Test!
Material: hill Field: ASTM D-6938 Nuclear Gauge Metho
Reference Datum: 0 = Top of Fill Laboratory: ASTM D1557 Modified Proctor
The tests below meet the minimum 95% relative soil compaction requirement of Laboratory Proctor maximum dry density.
Maximum optimum Field Dry Field Soil Fill
Depth Test Density Moisture Density Moisture Compaction p Pass
No. Location of Test Range (pcf) t%1 (pcf) %) %) (inch) or Fail
1 NE corner of pad 0 - 1 ft 103.3 14.3 98.6 9.7 95 N/A Pas:
2 NW corner of pad 0 - 1 ft 103.3 14.3 101.4 7.4 98 N/A Pas:
3 SE corner of pad 0 - 1 ft 103.3 14.3 99.1 7.3 96 N/A Pas:
4 SW corner of pad 0 - 1 ft 103.3 14.3 100.4 8.9 97 N/A Pas:
To establish a mutual protection to Universal's clients, the Public and ourselves,all reports are submitted as confidential property of our clients and authorization