310 4TH ST - ENGINEER LETTERS AGC Alexander Grace Consulting, Inc. June 8, 2016 Bill Elledge Turnkey Construction 5991 Chester Avenue, Unit 105 Jacksonville, FL 32217 Re: Joist Assessment Letter Regante, Unit 310 4th Street, Atlantic Beach, FL Job Number 15-10-0110 Dear Bill, On May 4, 2016, AGC provided this solution for adding a 3" hole in the three ply 2x10 joists: Apply a 2x10x2'-0" scab to the face of the 3-ply beam with (2) rows of 10d nails at 3" o.c. The hole must be centered vertically and horizontally on the scab. This repair was overly sufficient for the 3" hole. It is acceptable that the hole be up to 4" in diameter. Nothing further is required. If you have further questions, please don't hesitate to call. Sinctlhhhhh1i •0 WAYNE. so', c iQ: O S ' ten • :9• T F • Iv rNAE FL 59• $1111111%"‘‘ 3016 South 3«d Street,Suite 201 • Jacksonville Beach,FL 32250 • 904-241-8010 FLOORS L L/3 R L/3 6_9/3 MAX.I I NO NOTCHES — D/6 MAX. I PERMITTED 141-(;/3 D/3 MAX. j � I I I I D/6 MAX. FOR MEMBERS I LESS THAN —�— 4 IN.NOMINAL FLOOR JOIST—CENTER CUTS DIMENSION I I I D/4 MAX.Z I t_D/4 MAX. I I FLOOR JOIST—END CUTS —� I I I I D/3 MAX. 4 1 ' PIPE OR CONDUIT 2 IN.MIN.FROM TOP 11111)o, I � AND BOTTOM OF JOIST 4D(ACTUAL DEPTH) I For SI: 1 inch=25.4 mm. I FIGURE R502.1.11 [IRC R502.8] CUTTING,NOTCHING AND DRILLING I R502.2 Design and construction. Floor framing of light- Table R502.3.1(1) Floor joist spans for common lum- I frame wood construction shall be designed and constructed in ber species.Reserved. 1 accordance with the provisions of Section R301.2.1.1 or in , Table R502.3.1(2) Floor joist spans for common lum- I accordance with the AF&PA NDS. Floor framing of light- ber species.Reserved 1 I frame wood construction shall also comply with Sections I R317,R318 and R502.1. R502.3.2 Other floor joists.Reserved 1 I Figure R502.2 Floor construction.Reserved. R502.3.3 Floor cantilevers.Reserved. 1 R502.2.1 Framing at braced wall lines.Reserved. Table R502.3.3(1) Cantilever spans for floor joists sup- I I R502.3 Allowable joist spans.Reserved. porting light-frame exterior bearing wall and roof I only.Reserved. I R502.3.1 Sleeping areas and attic joists.Reserved. I FLORIDA BUILDING CODE—RESIDENTIAL,5th EDITION(2014) 5.3 AGO Alexander Grace Consulting, Inc. June 6, 2016 Bill Elledge Turnkey Construction 5991 Chester Avenue, Unit 105 Jacksonville, FL 32217 Re: Joist Assessment Letter Regante, Unit 310 4th Street, Atlantic Beach, FL Job Number 15-10-0110 Dear Bill, During construction of the above referenced structure, the plumber required holes in existing joists. The holes were as shown on the attached document. I have performed a location analysis on each joist and confirm it is acceptable for the joists to have holes drilled as shown. If you have further questions, please don't hesitate to call. SirelywAyN,, to,� ,,� Q►4.•••' , ,i to • to , Amy v o :tv: ...< o . p. •�. . FL 593 : Hull 3016 South 3'!Street,Suite 201 • Jacksonville Beach,FL 32250 • 904-241-8010 AGC Alexander Grace Consulting, Inc. May 4, 2016 Bill Elledge Turnkey Construction 5991 Chester Avenue, Unit 105 Jacksonville, FL 32217 Re: Repair Letter Regante, Unit 310 4th Street, Atlantic Beach, FL Job Number 15-10-0110 Dear Bill, During construction of the above referenced structure, the following questions arose: 1. Need detail for extending existing floor joists. Add a 2x10x14'-0" scab to one side of the existing joists and fasten with (2) rows of SDW22300 screws,or equivalent,at 24" o.c. Use an LUS210-2 to fasten to beam filler. 2. Need to drill a 3" hole in the 3-ply beam for plumbing. Apply a 2x10x2'-0" scab to the face of the 3-ply beam with (2) rows of 10d nails at 3" o.c.The hole must be centered vertically and horizontally on the scab. If you have further questions, please don't hesitate to call. Sincerely, \`,�,IIIIIII1, ldAYNFI 11, 4(< �SIFIC O59 P8 'Zm = �c * - • O •4 Geoff Gartner, PE FL 59328 3016 South 3•d Street,Suite 201 • Jacksonville Beach,FL 32250 • 904-241-8010 AGO Alexander Grace Consulting, Inc. June 8, 2016 Bill Elledge Turnkey Construction 5991 Chester Avenue, Unit 105 Jacksonville, FL 32217 Re: Joist Assessment Letter Regante, Unit 310 4th Street, Atlantic Beach, FL Job Number 15-10-0110 Dear Bill, On May 4, 2016, AGC provided this solution for adding a 3" hole in the three ply 2x10 joists: Apply a 2x10x2'-0" scab to the face of the 3-ply beam with (2) rows of 10d nails at 3" o.c. The hole must be centered vertically and horizontally on the scab. This repair was overly sufficient for the 3" hole. It is acceptable that the hole be up to 4" in diameter. Nothing further is required. If you have further questions, please don't hesitate to call. Sin cc , WAYNE #, 401/4". ENS.Q...... ?lV;' 0 59 8 CC 1. S F .'4i• : • Geoff tet40 el Si •aA s,` FL 59328 3016 South 3'd Street,Suite 201 • Jacksonville Beach,FL 32250 • 904-241-8010 4