BUILDING DEPARTMENT PERMIT NOTES
Date: 4/20/16
Permit: 15-RADD-2400 Applicant: City of Atlantic Beach
Review: 2 Address: 1200 Sandpiper Lane
Site Address: 850 Seminole Road Phone: 247-5834
RE#: Email: rcarper@coab.us
Plan Notes:
1. Please provide signed/sealed plans for new retaining wall,before construction begins.
2. Truss engineering was not provided at Plan Review. Please submit truss engineering, signed-off by
EOR as meeting his design,before truss installation. Proceed at Contractors own risk.
3. The engineering report,requested in Plan Review Comment 4 (12/28/15)was not provided.
Provide before slab inspection. Any existing structural deficiencies discovered during demolition or
construction must be corrected.
4. Please submit a complete Energy package,per FBC-EC, Section C103,before mechanical work
begins. The Energy package can be submitted with the Mechanical Permit Application.
5. Please submit completed Florida Product Approval Forms, as requested in Comment 10(12/28/15)
before slab inspection.
6. This plan review applies to plans dated 01/15/2016,with Addendum 2,dated 02/29/2016.
7. Wire/conductor type and conduit type were not specified in Electrical pages. Conductor ampacity
and conduit fill must be verified at rough electrical inspection.
8. Please submit specific details for spray foam insulation and required thermal and ignition barriers.
Notes:
1. Please provide the signed/sealed Pile Installation hispection Report before slab inspection.
2. Detectable warnings are no longer required by the FAC. FDOT still requires them in FDOT ROWs.
Dan Arlington, CBO
904-247-5813
darlin¢ton(a)coab.us
f City of Atlantic Beach APPLICATION NUMBER
Building Department
A (To be assigned by the Bui ding Department.)
i 800 Seminole Road
Atlantic Beach,Flodda 32233-5445 V
Phone(904)247-5826 Fax(904)247-5845
E-mail: building-dept@wab.us Date routed: 9
City web-site: http:/(wwwcoah.Ua
APPLICATION REVIEW AND TRACKING FORM
Property Address: Afi A d Department review re uired Yes No
ll�r� T� e
Applicant: I 8 Zonin
1 Tree Administrator
Project: /�a✓Q. /}�� J'Yj Public W
Public Utill I
ublic Safety
ire Servlc
Review fee $ Dept Signature
Other Agency Review or Permit Required ReMRof P
Florida Dept.of Environmental Protection
Florida Dept.of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: ❑Approved. enied.
(Circle one.) Comments: /gL
/ 1►A r�.l T rj
BUILDING
PLANNING&ZONING Reviewed b ^I'
Y Date:z '
TREE ADMIN. Second Review: pproved as revised. ❑Denied.
PUBLICWORKS Comments: -4PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: � Date:
FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied.
\ Comments:
Reviewed by: Date:
BUILDING PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Road,Atlantic Beach,FL 32233
Office(904)247-5826 Fax(904)247-5845
Jab Address: 850 Seminole Road Atlantic Beach FL Pe Y/JTo )� Al" l S— HADD— a voo
Legal Description M1516-2 E 12.900 SALTAIR EC 2 Parcel# 170389-0000
nor ea o q. t
Valuation afWork SProposed Work heated/ceoled 6.721 pop-0eated/eoWed_
Class of Work(cirek one): New Additi Alterarim Repair Move Demolition poeLlepa window/door
Useofexkting/prouosr�stmclure(s)(drck one): Commercid R fuI
Ifan existing struehre,is a foe spre, rr system ins + e one): Cj.�> No N/A
Florida Product Appppmvel# please see form
For multiple pradam use produd approvalof rm
Describe in detail the type of work m be performed:Renovation(5,550 at)and Addition(6,721 t)W F-Asaing Atlantic
Beach Public Safety Buildine with site work
Property Owner Information:
Name: Ctv fAd ti Beach• UDL( S L4Y 1Xddress: 50 Seminole Road
City Afan[ic Beach ZiP 32233 Phme _r]'1 l- S R 23
E-Mail or Fax#(Oo— h4Dn t1i celau I1$
1
Coptraemrinformation•
Cmupmy Name:Add&WhimC sftmytore LLC Qualifying Agent T-1h S. d
Address:4169 SoumooivtPwkv Sm 101 City Jacksonville Stoml7.
Office Phone 9042962555 Job SWCwhcl Number TBD I.#904-29669 l`
State Cer ificatioMtegish d..# CGC-057409 11
Arcltit Nmne&Phone# lemons Rutherford&A es/85 38 I
Engineer's Name&Phone#Baker Klein Eoakmin /904-35 -8
I.Simple Title holder Name and Address
Bonding Company Name and Address it to,
Mortgage Lender Nmre and Addreaa
Applin(ervluheredymnhroob(alnaai(rodr Me wofi mMir va(bams as indicoted Irengy(hen rro wale lnaa( Au mmmemedptosro(M1e
Y.rvml[e ul/npermirmdawol( 1 fth.(bepe M(omcer(heswmide ofIXllawe regWatirrg caatrvttiomm(hbry,id' ]Iw
mrd void jwork ie mV mmmarmAwaAor.su(6 #m,orfro.,rtmamm orwork rs ya�e� dmdanvd7r adofsa mmY nme
T RecbAPG wmv;tl� sepurme aia mart be sennmlr PAaaVm(Ck flemaNe.4v6m.JAR huh Bolba,R'
WARNING TO OWNER:YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS
TO YOUR PROPERTY.IF YOU INTEND TO OBTAIN FINANCING CONSULT WITH
YOUR LENDER OR AN ATTORNEY BEFORE Y037R NOTICE OF
( n//y(Mr]Ame redmdemmnined(his Aw(irm mMAnow(he.rmnembelrvemMrorrw. A((pm vs a/lwsmdoNlrwwva goremm (hie
9Pa. wwrf
-al be
ro tiled w mai herew or rroe. ]hs%mwlms Ina a dna rvw vrevme ro Slv%auAun(Y ro.iolme or the
p.n.,nmm fmrahvfed( �rer;um(ygowmmimr n,aepeK.manaM[av(rumon ��p.Q
Sigoelure of Owner `- Si�mure of Comm _
Prim _
N.. O✓4G "!5. Lq TGv.1 , Do Prim Name 7rn A h
Swom to dsu eforyry me Swom((pp an'subsaibedbefore nne
oris�u/'/ Day of b 2 �5 this RL, yof ex-fDYJP2 .2012
//V/t7 7L1 f'{a
Me Q MJLL I .�
My Public NMa® ulr rEl c
Revised 01.26.10
'Ati$•+i>"r�� OONWIL APA]IE
MV COMMISSION 4 FF 018393
EXGIflES:May 14,201] svaonuy
�fl6•.. BontlN IDry Poon Pul6;Wtlewaen patiyav r�oy
a:??:• °��, MELANIE 14ILL
a•r 4,.= Notary Public-Florlda
•'oc My Commission#FF 203432
`rWyo11,f, 3> Expires:Fe
"n 2018
1612.5 Flood hazard documentation.
The following documentation shall be prepared and sealed by a registered
design professional and submitted to the building official'.
1. For construction in flood hazard areas other than coastal high hazard areas:
1.1. The elevation of the lowest floor, including basement, as required by the
foundation inspection and the final inspection in Section 110.3.
1.2. For fully enclosed areas below the design flood elevation where provisions to
allow for the automatic entry and exit of floodwaters do not meet the minimum
requirements in Section 2.6.2.1 of ASCE 24, construction documents shall
include a statement that the design will provide for equalization of hydrostatic
flood forces in accordance with Section 2.6.2.2 of ASCE 24.
1.3. For dry floodproofed nonresidential buildings, construction documents shall
include a statement that the dry floodproofing is designed in accordance with
ASCE 24.
m . ch
_ G G ! %
/ ( } !M0 ( � _
i@mK _
> 5 § ;- § ? (\\ k0k � m
§ ® ! ' )■ �
! \ \ ' c
I k
3
. cn
rr ! 0aKf* i ƒ
\ J ! k } \ } El
5j.
' e .
2 > § 2 « � ■ � � # E .
� ( ! | ` | : m § , :
( § � & 7 ( \ .
iKr � #
3
] § / /
= K !
k \
i;F10 Auldt-whae do-n-structors,-LLC
COAB - Police Station Addition
SCOPE CHANGES FROM DESIGN DEVELOPMENT PLANS
1 Segmented Block Retaining Wall-FEMA-Driven Changes
.DESCRIPTION CITY UNIT @
NOTESGrad728,700 Segentedbls/Adstmenin 1 LS 4,00000Segmented block wall retaining wall 1 LS 22,700.00Dewatering 1 LS 2,50000Turbitlity bonier/Addaionai Erosion control 1 LS 1,500.00TOTAL Segmented Block Retaining Wall-FEMA-Ddven Changes
2 North Parking Lot/Utilities added
DESCRIPTION OTY UNIT @ NO I ES
0
Parking Lot demo 300 BY 10.00 3,000
New asphalt/stuping/signage,etc 300 SY 50.00 15 00D
Concrete 1 LS 3,500.00 3,500
New Potable Water/Fire Lines 1 LS 17,000.00 00 17,000 Exisitin lines were su osed to be ade .ate to to into
Drainage increases 1 LS 30.00 3000
0
TOTAL North Parking Lot/Utilities added 41,500
3 Dumpster Enclosure
DESCRIPTION QTY SUNIT @
0
Dumpster enclosure added 1 LS 6, 00001 6,000 Exidii condition does not meet code
0
TOTAL Dumpster Enclasurel 6,000
4 Sidewalk size change
DESCRIPTION QTY UNIT @ NOTES
0
Sitlewalks cM1angetl from 5width to e' 1 LS 3,000.00 3,000 Part of street orange scope
0
TOTAL Sidewalk size hangel 3,000
5 Attic Insulation Change(Batt to Spray-foam)
DESCRIPTION QTY UN=1.50
NOTES
Changed insulation in the attic spaces from Batt insulation to 12,800 SS dnklerin the attic drives this change
Sprey-Foam w/smoke bonier retartlant TOTAL All lneulaUon Change
. )vv| /{ 2
: ( \k
-
-
| ||8
° - m § 2
- | *
} §
\ § | �
CIIAPTERCA-COMMERCIAL ENERGY EFFICIENCY
Form 0402-201{ALTERATIONS,RNOVILTNDUR.DING anV DUILOWG SYSTEMS
CI(mele Zone:
ddresa:. lonlian Remvalad BUM"vO Ouildinq System
Cif. Z.. DuihSn PearW Na'
Uuild r. mulb'n Uf :
Owner,
BUILDING ENVELOPE WFORMATION om chengedl ERkbn
R nlremenl
Eneebpe Component C OesIXlpUon Laea0oh UnN Required InaWbtl
Tbk G402.1.2 Reoftype 5�dy�JN a Tabb C4a 2 IRamfuew R-30 -
mflxlenravEmrgexa TaHo fd071..f:1 Saw regeaoxo, .I lh
roo/a R xrnanna omi0anaa A/
We01 shove rade sWx1IXw
Wee,.babes grads TaGN'CA02.7.2 wTabb C402.2 R-value R-i5
-S
Flan
UJxlar 0.4 0
Verliral lmmalragona
VH Prif
�.rPl;nr.W sNGG
. rows c402,3 u.IxIIX
$Ayfphh />( sIiGC h
OUILOWG SYSTEMS INFORMAl10N[lar, -AC;Simi.hb"Wror pool heeling,1106Gg aYaloma,sod repinramwi TeneatreVon(C1pf A.TN
Ra ulremenl E
SyaMm TYW ltleavlhaeYabml '11
LonWn UnR uh InaYlbd
Tcwntldiardng ayaMm. TamMC40729(730A,16//) EERwWRIEER E 3
Heating ryabm ,I Tabfea C40123124if IfSPFnGOPAFV&ErwE. 1.0
Venblegonlarhen m' "fi Tebbe C4M2.10.f f-
ou
- ran- aw
Ourts oash'on: Table C40T.27.1 ♦'aloe -G
R� Iddsp9nq—&-'MMX TgMo C403.20 Inches
Hof wales r T bk C404.. F.Et COP I•p
. ea:; TebNC/01AS2. 1w2 ' h' waF
FeueamQnAs Flrlar lnbmie .In OWLOIRGEtMLOPE INFORMAWNh0adlgve.
OIhaC
COMPLNNCEIS NYANSOASHRAEAESNAg0.10
(Submitabanam/orb as enddoivnwnb aandadwl viawap/anaandapaclfiaegIXw mveradbY Mu
IhembYaergfy Nal the Alana endapuci(®Bona wvbmdhytlre cnkvlalbn aro in mmpb'anae bulolionWiOWc p&...1h Mo Florida
Flbr aDo4dfngG a Comer�'aliw Ca .Eeargy Conaorvalioa.Befwornukwu.a
PREPARFDON re ( �^5 bd,fhir fimMng wAhebalrocicdM
PATE; td/R7I� Fnnw
I hemby mrply lhef lhis MWdmg isbeanpgnncre vah Hr¢Flmido Du2ding Code,Gergy aaeordanae vahSMrcm 553.905;F.S.
CmaemAan: UILDING
OWNER/AGENT OFFICIAL'
DATE. DATE:
�o
A�
i
COHAFFERG3--COMMERCIAL ENERGY EFRCJ NCY
Form Ca0L201lALTERATIONS,RENOVATEOOULLDING and BUILDING SYSTEMS [Iinele Zone:
'uc(Name: Olemon
maa:
lemlion Reno+aletl 8uddag Building System
Gd-,2i «Win permit No.'
BulLlor. annilb'n�r¢e:
Owner.
BUILDING ENVELOPE INFORMATION tWinomunmn9ed) Ellkkn
no a remvnl
Envebpe Compdnem DOemlplbe Locefbn Unit Requimtl InQahlbtl
T"MzfRaaffype �.3v s. Va')f�* Tsbh GI02. 2 sR.velue« R-36 „-
Rao/rodvdeocmEmMenon Tpble0002.2.f:/ sdermlbahnco, Nh
gow rwfs R Thormel omilbn.
LYnNI above rude aUAaaforor
Wag bhhw9rado T.WG102.1.2ar)T,No C102.2 R-value R-1
R-5
FlpOf '' 11 11 U+xI« 0,4 o
Vwlicollenaslia0ons YII PriflinYa�YVA SHGC
Tabfe Gdo2.9 .,U. w
Skylrghh N SHGC h
BUILDING SYSTEMS INFORMA I luN)hr HYAG,anvlw bolwhbror oolNeedn0,lighdngeybuems,and replammentnoo, WOn C10IA711
R ulmmanl
SYnam Type ldow1bo".-I Lacadoa UnN R uhed Insallad
Ymntl0iorw19 sytldm Tabhs C4W.23(13,fi$10-11)SEER orEEl{'I I
H.-um Yd.. .1 I..Cd03.23(S6) NSPFar -AFUE,Eror6 1.0
VeaNdioaldr,baodkr 's' { TablasuOlzio.1 f-2 a0n” 2OCO
Doo& Looabon: TeMe"03.2.T.1 -vaWe -fa 'Ir•
pig Widdaygb irpm 6m fampl low:..2s'
Hal wa/ar n - Tahb WC2 F.Ec COP I A
ei�a d TdNe"C40 b.z 1ort
FenesOalltldr.Enlor M mnmOvctmaUILgNG'ETLVECOPE INFORSNTNIN hoxdbove.
011ier:
COM"NCE IS BYANSOASNRAEAESNA 90.10
(SWahifa/bmel6lam wa andtl«vmm�b aandedad) oWox•yPhnsendspecihce0ava crnaredbY Mu
I LembY..0rylhnllheplans.dapdcd-miooscd+mdby Bm mkvlaLvn eroM mmMianae Isuluh'm iMicafns commNiance:1h llm Flaide
wdh fhe mldim
Florida Bdding Code,.Enagy Conmrva0on Bdvmc_risbucb'an u
PREPARED BY' e r_._-a_( �S pWlad,Oris OudGn9wiybemepeclod for
GATE: can�plianca
Ihdmby avNly Mallhis 6a0daq iswcompfanea vMrlha Fluido 0mbmg Codd,Energy ae�vtdanco xitl!saslirm F.S.
Canaorvdion: BUILDING
OWNER)AGENT: OFFICIAL:
DATE. DATE:
VA
fCRAPTER C4—COMMERCIAL ENERGY EFFICIENC
Y_
Fmm C402-2014ALTERATIONS,RENOVATED BUILOINGaotl BU.IDfNG SYSTEMS Name: cAddreas mn0 Bu0d'ag5 slam,.2. BmM
Bo0dar. Pemrdnn Ofize:
Owner.
OUILDING ENVELOPE INF0NMAlION sechennetll R nNemenl
CY
Enaebpe Component Oasaiptloa LoceUon Vhlt ILWintl MaWbd
TebiCO2f.2 ar zUJeIo
JM Jw„V^ Dbfn C44R.W.02.2 U .
mff l..Ennft. Table C4021.t SWarmAeole/wa. ,N
Mws ifs R Tho... f1w.
Wahl ,aWve rade Wactorar n-IS -
WBe.bgyryeratle TaWa G402.1.2 wTobb(:402.T Rvalua M1
-S
Fow BA o.
WIND.Vor6mlhmodslmnons 1La Arr�aPl;nY+LdW SNGC
. Tabk C402.8 11.helnr
Skyfi0hh h SHGC h
BIIiLDING SYSTEMS INFO RMAT10N.. VA...... hotwemror oolhasUn0,l-IphUn0ayeta,s.and mpkmmmtfoneabe0a leniBi L7n
Re ulremnnl
Syamm Typa(dooar.ay:mnl L.U.. Unh Rs uInd Inatallod
contlihanNB sys(dm Tables'C(03.T (13,64.NIL SEER or EER'/EER
Hee0rg system Tables C403.25(T-6J SPFmCOPAFUE,Fier& IA
VmNa6an/airhandyn ' 't TeMaa G02210.1 f-2 M pfin' 2aea
Ducti � aaenm: Te Me Cn03.T.Tf -value -fe.
" e Fluid design operating fame;T.L CV03.2B mhos A
11d wabr 4m3rr a. TabEo.G00.2 EFF,F;COP 1 A
s' db:+i Tdbl�'G0552. I w2 'hfin
FeeeaUeUotm:Enmr Infonnm.7ARUILLNN0ENVEL0PE INFORMATION boa ibove.
011ie
COMPLIANCE IS BYANSVASNRAEIIESNA MID
ISubmlTalhmok blm ore ddaiumvnk osndaded wiewalAlanaalld spesifi¢efbns aovemd Lythe
I hambyiernfylhef lha plansandapuullmafiwa mwmdby Mo ookvlalian ora io.mmpliarce Isu/ob'm indiwfes mmpnmrswlTh Me Honda
Ficowa Bonding Codd yCmseryalian, Coda,Enmyy Cons .Ibn.Bamocoilsln¢C'on u
PREPARED BY SkFi 4 L I(u6 IplefuC,V.bvdSinB wN be i ve -d lo'
DATE:
Ihereb,,xfiTy Orel Drishulidn0uin complmnm uaM Olo Flafda OuaKmg Coda,Cnergya�orI.wNb,Sadon 551.90S.F.s.
Cnna alm BUILDING
OWNERIAGEN7: OFFICIAL
DATE. DATE:
LORIDA BUILDING CODE,MERGYCONS
VON
FCNAPTEN CA---COMMERCIAL NERGYEFFI�ENCY
Falm CQZ 2014 ALTERATIONS,RNOVATED BUILDING end BUILUDIG SYSTEMS
Clinem Zone:
'etl Namo: Gmpen
dorsa: lemlian RanwaMd BuMvy Bu9dvg System
IA.% 3wki Pevmil NOJ
Builder. PemiHer dime'
Owner.
BUILDING ENVELOPE INFORMATION hoteabm ed) EIYELsn
R nbemmt
EnaeloPa Component C1 1BpaadpUon LoraUon Udtt Reaulnd MaYBod
Nml type JM�yY...MYVe')f^ Table GOLP.2w SURJeclord R-3
RW.fl danae,Emdlanae Ta,61e G021.1;1 Sularlvieclenm, Nh IC
(kwn. �ry A :Tdwmelamilenm
W.01 .aWve aU-1b ww
Wei,bekwgrade T.WC402.1.2 wTable CI022 xR-value R-15
R-5
I/ '' 11 11 su-lades 0,4 0
vwiwnana.,lratiwla udl'X,'Ar.W W s SHGC
table G02,9 SHGCr
Sb)'Tr9M1k � SIiGC h
BUILDING by STENS INFORMATION[lar -AC...... al wemror ool M1eNn011ihUne eydems,and repkaemmtlonestraUa�n�p01 A.TN
Ra ulremenl
Syaum TYW(desc9te ayeleml ' Loaatbn UnN betl WteOod
'cmddiwdng byslam Tebka'0403.23 113,&i,1& 1)SEER WEER NEER
ahand"n" m' 't TTebblka GG0033.22i10f2,1-bt)-2 NmPFw GOtPinAFMFawEe 1.0
NeeumsWem
Zero
Dudv owb'on: TONeG0327.1 R-yelae -lr.
R" Idd1p,a�1gYnpperampfemP:
raw 1211 kalres
Mef"larII.W w TvMoG. 04.2 EF,Ei COP 10
. ..oar. . WkC/0Sd21w2 "M1b'n wet .R .O
FadaeUelloas:Enmr lnlatmaUm in BUILDING LOPE INFORMATION bm Above.
Omar:
COMPLIANCE 15 BYANSVASIIRAEAESNA 90.10
(Submit aldaaek ltivir are enddaiumonlaosneededf eviewdplanamdapxMmeema moored by mia
Illwaby iera7y mel lbeplansmdapo Tmeiona mvemdbymo mkuloLkn em kavmpb'mm lndafim intlim(os cwn�ence ih me Flmida
WIM ma
Fldida Bdildng Cotld yCm aim Cade,EneW Canaaw fbi .Ral.mdaWcimu
PREPARED BY' 4 L �eS lad tW tiudain9 WI be kapaclad les
ATE. I ymaf mw 6uddmO lskcwnp0onea wih me Fkdds OUNing Coda,Energy aweNnmwim Serlian 5iT.90Q F.S
OWNERIAGENT:
UILIIING
DATE. AGOFFICIAL:
DATE: DATE:
CHAFTM BU/LOING CODE,TALE NERGY EMCIENION
CHAPIERC4--COMMERCIAL ENERGY EFFICIENCY
Fann C40Z-2014 ALTERMIONS,RENOVATED BUILDING and BUILUING 5V5TEM5
[IineM Zone:
'vM Nemo: OccvP
Address: IPraliPn Renvvaletl BUIMx,g Dvldrg System
Z. Om Mi P .uffi
Ougdx PemiilGnq Olfrce'
Owne,
BUILDING ENVELOPE INFORMATION 11-mch4mg0a)
Roqulmmml FBklanCY
E.Vial. eComponent �1 Desmlptlon LPceUon UnN Rm"IMd M.Ix%d
Rwrim. �sdP „ reblvG0222w =R-u a R-3® -
RPMmflealvmaaEm4Mnm rode C40ZS.f.Y =SMPrmdealarwe, .I lh
roma Th
a armel mA/
nfllen.
14x01 P..b rade U-Ixlmm n
Hutl,.bba gmdP tea's G02.1.2 P.YauP 04021 zR-�okm R-IS
R-S
'' '1 11 U-WI.
Vodicsl4maabaEPno �iir�l�n4+WJ SHGC
Table 0402:3 U-factor
gbh AN SHGC h
BUILDING SYSTEMS INFORMATION tvrHVAC,aervlce hof tnmrpr pool kee0np,Igh0np nyslems,end repkcemmt fenesvaUon[101 A.7tl
Re ulmmenl ERMkn
5yeum TypejdncRr e)radem) Laralbn UnN peauhetl InsmBad
i,.dlbmdn2 ay-NO Tebles'GW23(iJ,4B,1411 wEER,3EER £
Heeblrg ayalem Tab Ma Cd0313(R0) 11SPFarC -AFUE,G-- 1.0
VonNaliONeirbandM a to f Tai c4o3210.l 1- a/m' Z°cO
Doily Mon. TOW, ,03.2.7.1 -veMe -Ta -,
Row nmeeoigh Wem0tlg femP;Tede.C10126 mc-1w.NM"Jar Ir e. TebM Gap4.2 EF.E, COP I a
'bol -Teb(o G03.521a2 irden O
Fenee4vUobs:EnlPr MMmieUvn in HNIDING' ELOPE INFORMATION has tlho4e.
GMa
[OMPLDINCEIS BYANSOASNRAEAES'NA 90.f o
Submit�hohvbi/oim ora enddxvmanfa asndeded PWewalplanaaiM apacfiwtivna rnverotl Ly Mu
lAambycerdly lhellheda^s endapPdfiwfwra a»+amE 6ylhP mkulalwn emM mmPliarve lcu/vh'm intliwMs PmnpSanw wiVi tlm Flmidn
wdh the Ming
Floilda Rvydhg Cvtld nc yCwme alien CodeIekd, 'Gonmrvalion.B mqv odbiwlbnu
PREPARED BY Y (i Wo,tlrisbu ng wy/6e inrywdvdlu'
DATE: I.VR cvmpkenae
IMby.finny tliellhis 6uiMarB hat emnpfmnm vAllr Me FMddP Bu4ding Cade,Energy MeveONanca wjm Secloxn 551.gW;FS
OWNERIAG BUILDING
OHTIEWAGENT OFFIGAL:
DATE DATE
Hubsch, Jeremy
From: Arlington, Daniel
Sent: Monday, December 14, 2015 1:24 PM
To: Hubsch, Jeremy
Subject: FW: COAB PSB fill analysis
From: George Hadow fmailto:GHarlow@bakerklein.mml
Sent: Monday, December 14, 2015 12:12 PM
To: Arlington, Daniel
Cc: Blakeley Bruce; Layton, Douglas
Subject: COAB PSB fill analysis
Dan,
We ran an analysis to determine how much volume we are taking out of the creek by adding fill. We are adding
approximately 876 cubic feet of fill,which will decrease the volume of the creek by approximately 0.88%. 1 analyzed the
creek between Plaza and Seminole only...the creek is part of a much larger system so that percent decrease is negligible
when you consider the entire creek. I then looked at a portion of the floodplain at elevation 7 to determine the increase
in the creek height for the 100 year flood.The height increase is approximately 0.06 inches.This height increase is also
negligible if I were to analyze the entire floodplain.
In summary,the impact on the storage capacity of the creek is very minimal when we add fill to the site.
If you have any questions, please feel free to call me.
Best Regards,
George D.Harlow,E.I.
Baker
Klein
Certified 8(a), EDWOSS, JSEB, MBE
1334 Walnut Street
Jacksonville, FL 32206
Work: 904-559-2653
Mobile: 904-838-7854
Office: 904-356-8520
Fax: 904-356-8524
www.bakerklein.com
1
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
J ;" ATLANTIC BEACH,FL 32233
(904)247-5800
BUILDING DEPARTMENT REVIEW COMMENTS
Date: 12/28/15
Permit: 15-RADD-2400 Applicant: City of Atlantic Beach
Review: 2 Address: 1200 Sandpiper Lane
Site Address: 850 Seminole Road Phone: 247-5834
RE#: Email: dlayton@coab.us
Correction Comments:
Application is disapproved for the following issues:
1.Addition extends into the AE-7 Flood Zone. Hold Building Permit for approved CLOMR-F.
2. Please provide signed/sealed engineering for proposed retaining wall connected with CLOMR-F.
3. Plans state this building is Risk Category IB; Table 1604.5 lists police stations as Category IV.
Please clarify risk category and verify building design meets all requirements for Category IV.
4. Please provide truss engineering,signed off by EOR as meeting his design.
5. This project falls under the Florida Building Code-Existing Building(FBC-EB). Please provide the
alteration method(s),per FBC-EB, Section 101.5, and provide information and details required by the
specified section(s). If using Alteration Level 3, please review and provide engineering report.
6. Baker Klein general notes state NGVD datum;Page C0010 states NAVD. Please clarify the datum
for the existing FFE.
7. Elevation benchmark on Baker Klein engineering gives north flange bolt of existing fire hydrant.
Fire hydrant has two identical flanges. Please clarify upper or lower flange.
8. Energy Form C402-2014 is not approved for additions, per FBC-EC, C101.5.1.1. Please provide
complete energy package, including expanded manufacturer's data for equipment. Review R-value
for spray foam insulation on bottom of roof deck.
9. Spray foam insulation requires a thermal barrier. "JM Spider Insulation"only qualifies as an
ignition barrier,not a thermal barrier. Please provide all spray foam information, including the ESR
for foam and other products.
10. Florida Product Approval Numbers must have decimal places. Multiple products are listed under
whole numbers; specific products are listed under decimal places. R-numbers are still whole numbers.
This is a high wind area(140 mph,Wind Exposure C,Risk Category IV). Some products do not
qualify for this location. List all products required by FAC 9B-72,verify that they comply with the
wind pressures found on Page S 0.1,and provide specific Number with decimal places.
(Examples: cedar siding does not meet wind loads,some storefronts do not qualify. Check roofing)
Opening protection is required,per FBC-B, Chapter 16.
11. Please specify service conductors and conduit sizes on electrical riser diagram.
General Notes: Your re-submittal should include two complete sets of plans. Please
insert the revised pages into the plan sets, and pages removed from the stamped
"Job copy" set, should be marked as "old set" and should be included in the re-
submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan
review fee charged due to the amount of time necessary to review entire drawing
again.
ALL ITEMS changed or revised on plans and documents shall be identified by
circling, clouding or identified by some other legible method. ADDITIONAL ITEMS
MAY BE REQUIRED - DEPENDING ON NEW INFORMATION AND CLARITY OF FINAL PLANS
SUBMITTED FOR REVIEW.
Notes:
1. Please provide the signed/scaled Pile Installation Inspection Report before slab inspection.
2. Detectable warnings are no longer required by the FAC. FDOT still requires them in FDOT ROWS.
Dan Arlington,CBO
904-247-5813
darlingtonQcoab.us
` J
PRODUCT APPROVAL INFORMATION SHEET FOR THE CITY OF ATLANTIC BEACH,FLORIDA
Project Name: City of Atlantic Beach Public Safety Building Permit #-
850 Seminole Building Atlantic Beach, FL
Project Address:
As required by Florida Statute 553.842 and Florida Administrative Code Rule 913-72,please provide the information and product approval number(s)
for the building components listed below as applicable to the building construction project for the permit number listed above. You should contact
your product supplier if you do not know the product approval number for any of the applicable listed products. Information regarding statewide
productapproval maybe obtained at:wwwJloridabuildin .org.
Category/Subcategory Manufacturer Product Description Limitation of Use State# Local#
A.EXTERIOR DOORS
1. Swinging Premier Doors Hollow Metal Doo s/Frames FL6378.1
2. Sliding
3. Sectional
4. Roll up overhead Door C rporation 610, 620, 625 Rolling steel roor FL15960 1
5.Automatic
6. Other
B.WINDOWS
1.Single hung
2.Horizontal slider
3.Casement
4.Double hung
5.Fixed
6.Awning
7. Pass-through - -
8.Projected
9.Mullion
10. Windbreaker _
11. Dual action
_ _ C � n
� w A w N — O `O Go V a ti A w N — � � p �O oa v O� to A w N — y� ry' ry�
o � a n r z g g z z �! 3 m z z c > o O � n 3 n � n � m o � z o 0
� 'N O 3 t O � d 0 0 � a t � O d a � S = e rn `�" v } O t] '� � [+1 J Y
� o fl, � c. .a > > � =i c � v Z rv� T 6 v o 5' � � c
-a � w oc s a a s 2 w � C] o w o c �
a m a 'o a. �< N c 3 < £ �
v 6 a J O � Q O C � � 's b ry n � �` �i �
a
a y e o. N w c; � � w � m '% m p � o
T O U
N_ '�
N
x x 3
z w m
v m
n '° " m
Y b o n
m �
m a �
n m
� �
w
o q n � 1
N C p i
n 3 �
m
v �
m
3 � �
n �' �
� rt
O N a
M m � O
O H � 'J
� O �
n
a b [!
� 3
W N �
W
a o
0
"� C
a f0
v
m
a
m m
� r
['
o �
x
x
o
r �
y
r
F
20
FOL
�
/ � )
/
k
�
,
. 7
!
(
_ \ ) ( � � ` � ( } \ , � , § / }
! , _ ) E % ) = o
/° � » \ ` 2 / % 2
( ( 7 � { � / � � � � � � `
f « � \ \ } ${ \ k \
/ 7 § & \ {{ § ® ,
\ \ { ` k � � �
- ) ( \} {
E ^ ] + E ■
\ { \ E {
\ � � �
\ } ` ( ( �
\ 3 ` /
r p ƒ E\ 2
\ \ \ � ® %
/ �
\ \ � - \
/ \ \
! \ ® !
� ƒ ) / !
_ ` %] (
f . \ • ( E
� \ ( }
� � \ ! 2 !
�� } �\
� ) / ( k
({
ƒ \ 2
4
® ƒ
a2f ( f ; ) � ( //
> a
# 0
a@j e3 « , a ■
@J § \ § !
7
\ L7
\ 2 2 � ( /
( \ § §
` tv ƒ B\ )
'
„ \
} :L , 8
to
® ` ;
' ƒ /{
(
00
° f
d f7 A
v, C)
c oa o ry oc a = ? a s O O
SF: 'o c m
tNSD vmi mU, N 0=G m O O C
j — 3 O V° Q A F = r
N
C!' O .�
ry S UC �
T C �
d ^�
n
F 7 3
F F _
q m
� ro rt d
m a c
n �
n
w
N C C
n 3 C
t0 r n
m �
3 w O
o M a o
n n �
� o
a ^ w r
3
w m v
Q 'o'
g G
7 rt
w
rt
N
a
� y
rsJ C tl
C _ �
� m �
O O �
L �
r
A
ik
I'lj ¢ y , �
, , sy2B ) 3z
{ ; » ' ] , �_ , ■ \ § � '
J
)
. k
�
, {
On
% y
[ ƒ / _ ■
E �
§ \ § I )
( \ !
\ \ }
. �
T \
} > a
z * f { § » ` ! _/ / ■
( ® ƒ / ` : ® ® ! �f) r �
@J � l , = ,
.10
° ( /
0 ■ ! ! & > r [ !
{ i $ ) ]
\
( § ƒ .
§ ƒ E \ / §
ƒ fo |
{ { 1 §
t / (
E ( \ .
0 : £ & ® ) \ ( � _ , ® : ; ` t , ; ` , - - 32
) r !
w _
— � W N — O •O W J r\ to A W N — O � J 01 t/i A W N .x R �1
F •e o T � o -� g 3 n n a m = � � z o m � n � co a c o 0
w o m n
n. '� c
s
c
w
e
e
m
n
1 �
b
0
e
n
O
n
n
9
O
�.n
3
w
0
c
0
r
n
d
u
P"
0
n
i =
x
I
{ } % 0 0
on
} ( an
) + r »
* { > ! E
£ } 2 27 7
[ [ \ ■
\ y . _ ! ! ■
/ \ } } \\ �
\ \ \ {
( }
fE
\ ( ( k
\ (\
-
G \ )
� � � � � ` ( ® ( { � ! ; , » o � \ f! } 7 ■
} % $ m2
{ iE 7
! ¥ ,
� i \
) {} \ !
! ! E *
(
; § ] �
� ( ƒ
` ( ƒ
c �
o A n r a z a N 3 m z a c > o n 3 n m v, aZZV 'Jo0 0
m w a_ P 9 c as c+ ..• G7 C. O o+ t o
T G �
m
N
� K p
Y N
m p �
H q
'M1
O
w
m � a
� 3 c
N
w r'
� v
H N H
� rt
H
ren m a c
n
a ^ a r
� 3
a
P O
m
a m
w
m
a
m
r
u
a x
x
r
u
/ ) \ [ \ ; ! } w ; » a / w » 2 § / % k % / ` J ` � ®
� E ( ! ( a / f3 / ® { RlfaE ° ¢ � § ei
\ § � ® � ( E / m } { / ƒ { ( / / ( � !_ / | \ § / ,
, � q
` f \ ® ƒ \ , � 4
J
k
�
(
k
2
� � � £
� \
\ (
; { \ ) ! E ■
) \ ( [
t Q ) ( E
f \ ,
\ ( \
) :
( � /
% !I
� (}
�
} \ ) 9. § 2 \
� � � ! { k m ] � ` * 1 , : , # § � § ! _® ƒ ■
§ !0
! ! \ § rt (
® ( ! ( } ( !
\ k{k / � � (
0
0 & > @ [
2
2 ( § ` 7
\ \ \ \\� §
( | \ �
t ( (
2 »
'S to A W N �• O ° CO V 01 D A W N — F �. C b W J °� N A W t>tr
-r,o o '�o oB
N
x � 3
� x o
v � c
v 3 E n
m �
m a �
n m
w
m r a
n
� n
c m O
3 v °
n o io
n
a ^ w r
3
v
a
v c
0
3 �
a �
N
N
a
EP
m w
m r v
r
m
a
v
A
A
s
x
n :� � m _ t
�-' � W N � O �D 00 J D\ Vi A !�+ N � O y J D\ to A W N ... x � J
rn K p v, � �o H � n f1 m —] � � x1 Q m A (] �, W 9 ° O
,� � s s m � m m o o � m 2 o e" s c o 0 0 � 8 � `� 's
i�. O � y m � 6 � _ l�� jJ 7 � � Fn G;
Vl M O G. = Cyy � o�
c `�
� � n
S
O yi
m
O
m
ff
R
b
a
a
��y
� n
S
O
p
r
3
8
0
e
-°n
C
m
i �
m
u
t'
�i
u
\ | \
( } ( ! \ { 0 { 0 0
tv
) ( \& ƒ
E z § § E !
\ } \ {
$
r \ � ) k
# & ƒ !
\ \ }{ §
\ / (
4Z !
` k )
! Er
} (\
Atlantic Beach Public Safety Building Plans review,Comments for Fire.
Please correct or provide the following to obtain plana approval.When resubmitting connected sheets,please provide a written
narrative letter responding to our comments and directing the plans reviewer to where the changes have taken place. Revised
sheets should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set of
drawings with old sheets removed.
If Mis is an electronic submission please make sure that written narrative Is submitted under correspondence along with a
"complete ser(not lust the revised sheets)of electronic documents.Failure to provide response letter will result in a return for
corrections plans review submission.
1.) Provide kler s"tem clesian criteriaFlorida Administrative Code 61(115J2.010,4(A-01 Engineering Desion
criteria ' ed to be submitted with the construction documents 1 to tl 663.79(61 F.S.
hUplAt/Depanments/Planning-a.d-DlopmenUDocs/Building-insoe ion
DI I 1 n/fl kl [ tl it 010706 61,315-32.01 document should be in a questionformat
with all Information locel on one pace.
Submitted plans are missing current fire flow data.
2.) Provide Fire Alam,and Detection System design criteria per Florida Administrative Code 61 G1632.008(A-O).
Engineering documents shall be sealed by the designated engineer of record.(Please copy and paste below link for
requirements.)httpsl/www.Hwles.or / h terHome.as 7 h - 1 1 32
3.) Provide IHe safelyplan 0 include arrangement of means of egress 0 include all the following Aapplicable:
"Dead antl oorridors measurements
'Common path of travel measurements
Total travel distance to exits
'Markings of means of egress to include tactile exit signage.
'Emergency lighting
'Fire extinguisher placement
'All rated walls
'Identify all area or roans"uses and provide occupant load which will be determined by floor use areas divided by the applicable
occupant load factor per table 7.3.1.2 of NFPA 101.
4.) Provide lightweight truss signage per FAC 69A-60.0081 "IF APPLICAPLE-or provide wrMen verification from a licensed
engineer or licensed architect that proposed or existing building does not meet Me requirements of FAC 69A-60.01181.
"Light-frame tmss-typa construction"means a type of construction whose primary structural elements are formed by a
system of repetitive wood or light gauge steel framing members. Please see below for clarification to requirement.
htto9/ tai rn igPla d-D b VD dB 'Id' -I ecC -D' Nb lWi -f-01.094'oht-
weight-Muss-rule.asox
5.) Provide secondary means of egress from the fire stations crews quarters par NFPA 101 7.4.1
6.) Provide access control egress doom details(card!readers).Access Control must meet requirements of NFPA 101
7.2.1.6.2
i
J