Loading...
328 5TH ST - ENERGY SHEETS ' E ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 Reissued August 2014 This report is subject to renewal August 2016. www.icc-es.orq I (800)423-6587 I (562)699-0543 A Subsidiary of the International Code Council® DIVISION:07 00 00—THERMAL AND MOISTURE pcf. The insulation's liquid components are supplied in PROTECTION nominally 55-gallon drums, labeled as "A" component or Section:07 21 00—Thermal Insulation "B" component. The insulation components have a shelf life of six months when stored in unopened containers at REPORT HOLDER: temperatures between 70°F(21°C)and 90°F(32°C). SES FOAM OFFICE COPY 3.2 Surface-burning Characteristics: 4008 LOUETTA ROAD,#538 At a maximum thickness of 4 inches (102 mm) and a SPRING,TEXAS 77388-4405 nominal density of 0.5 pcf, the insulation has a flame- (713)239-0252 spread index of 25 or less and a smoke-developed index of www.sesfoam.com 450 or less when tested in accordance with ASTM E84. Thicknesses of up to 111/2 inches (292 mm) for wall EVALUATION SUBJECT: cavities and ceiling cavities are recognized based on room corner fire testing in accordance with NFPA 286, when SES FOAM 0.5 lb SPRAY: SPRAY-APPLIED the insulation is covered with a minimum 1/2-inch-thick POLYURETHANE FOAM PLASTIC INSULATION (12.7 mm) gypsum board installed in accordance with the applicable code. 1.0 EVALUATION SCOPE 3.3 Thermal Resistance(R-values): Compliance with the following codes: The insulation has thermal resistance(R-values)at a mean • 2012 and 2009 International Building Code®(IBC) temperature of 75°F(24°C)as shown in Table 1. ■ 2012 and 2009 International Residential Code®(IRC) 3.4 Air Permeability: • 2012 and 2009 International Energy Conservation The insulation, at a minimum thickness of 3 inches Code®(IECC) (76 mm), is considered air-impermeable in accordance • Other Codes(see Section 8.0) with IRC Section R202, based on testing in accordance with ASTM E283. Properties evaluated: 4.0 INSTALLATION • ■ Surface-burning characteristics 4.1 General: IN Physical properties SES Foam 0.5 lb spray insulation must be installed in ■ Thermal resistance(R-values) accordance with the manufacturer's published installation • Attic and crawl space installation instructions and this report. A copy of the manufacturer's • Air permeability published installation instructions must be available at all times on the jobsite during installation. 2.0 USES 4.2 Application: SES Foam 0.5 lb spray polyurethane foam plastic The insulation is spray-applied at the jobsite using a insulation is used as a nonstructural thermal insulating volumetric positive displacement pump as identified in the material in buildings of Type V-B(IBC)construction, and in SES Foam 0.5 lb spray application manual. The insulation dwellings built under the IRC. The insulation is for use in components must be stored at temperatures between wall cavities and floor/ceiling assemblies, and in attics and 70°F (21°C) and 90°F (32°C) for several days before crawl spaces when installed as described in Section 4.4. application. The insulation must not be used in areas Under the IRC, the insulation may be used as air- that have maximum in-service temperatures greater than impermeable insulation when installed as described in 180°F (82°C). The insulation must not be used in Section 3.4. electrical outlet or junction boxes or in contact with water 3.0 DESCRIPTION (e.g., rain, condensation, ice, snow) or soil. The substrate 3.1 General: must be free of moisture,frost or ice,loose scales,rust,oil, grease or other surface contaminants. The insulation can SES Foam 0.5 lb spray foam insulation is a two- be installed in one pass to the maximum thickness. The component,open cell,one-to-one-by-volume spray-applied spray-applied foam insulation must be protected from polyurethane foam system with a nominal density of 0.5 weather during and after installation. ` ICC-ES Evaluation Reports are not in he construed as representing aerdtetics or any other attributes not specifically addressed,r ,w.,.I rs r '_.``�j~ 1\ as on endorsement of the subject()like report or a recommendation for its use.Mere is no warranty by ICC Evaluation Service Tress or implied,as ias rot to any finding or other matter in this report,or as to any product covered by the report. .. JUN 102016 4.3 Thermal Barrier: 5.0 CONDITIONS OF USE SES Foam 0.5 lb spray insulation must be separated from The SES Foam 0.5 lb spray polyurethane foam plastic the interior of the building by an approved thermal barrier insulation described in this report complies with, or is a of 1/2-inch-thick (12.7 mm) gypsum wallboard or an suitable alternative to what is specified in, those codes equivalent 15-minute thermal barrier complying with, and listed in Section 1.0 of this report, subject to the following installed in accordance with, IBC Section 2603.4 or IRC conditions: Section R316.4, as applicable. Within an attic or crawl 5.1 The insulation must be installed in accordance with space,installation must be in accordance with Section 4.4. the manufacturer's published installation instructions, 4.4 Attics and Crawl Spaces: this evaluation report and the applicable code. If there are any conflicts between the manufacturer's 4.4.1 Application with a Prescriptive Ignition Barrier: published installation instructions and this report, this When SES Foam 0.5 lb spray is installed within attics and report governs. crawl spaces, where entry is made only for service of 5.2 The insulation must be separated from the interior of the utilities, an ignition barrier must be installed in accordance building by an approved 15-minute thermal barrier, as with IBC Section 2603.4.1.6 or IRC Section R316.5.3 or described in Section 4.3. Installation in an attic or R316.5.4, as applicable. The ignition barrier must be crawl space must be as described in Section 4.4. consistent with the requirements for the type of construction required by the applicable code, and must be 5.3 The insulation must not exceed the thicknesses noted installed in a manner so that the foam plastic insulation is in Sections 3.2 and 4.4. not exposed. SES Foam 0.5 lb spray insulation at a 5.4 The insulation must be protected from exposure to the minimum thickness of 3 inches(76 mm)may be installed in weather during and after application. unvented attics in accordance with 2012 IRC Section R806.5(2009 IRC Section R806.4),as applicable. 5.5 The insulation must be applied by contractors certified by SES Foam. 4.4.2 Application without a Prescriptive Ignition Barrier: Where the spray-applied insulation is installed in 5.6 Use of the insulation in areas where the probability of accordance with this section (Section 4.4.2) or Section termite infestation is "very heavy" must be in 4.4.3,the following conditions apply: accordance with 2012 IBC Section 2603.9 (2009 IBC Section 2603.8)or IRC Section R318.4,as applicable. a) Entry to the attic or crawl space is to service utilities, 5.7 Jobsite certification and labeling of the insulation must and no storage is permitted. comply with IRC Sections N1101.4 and N1101.4.1 b) There are no interconnected attic or crawl space and IECC Sections R303.1.1 and 303.1.1.1, as areas. applicable. c) Air in the attic or crawl space is not circulated to other 5.8 SES Foam 0.5 lb spray polyurethane foam plastic parts of the building. insulation is produced in St. Louis, Missouri, under a quality control program with inspections by ICC-ES. d) Attic ventilation is provided when required by IBC 6.0 EVIDENCE SUBMITTED Section 1203.2 or IRC Section R806, except when air-impermeable insulation is permitted in unvented 6.1 Data in accordance with the ICC-ES Acceptance attics in accordance with 2012 IRC Section R806.5 or Criteria for Spray-applied Foam Plastic Insulation 2009 IRC Section R806.4. Under-floor (crawl space) (AC377), dated June 2012, including reports of tests ventilation is provided when required by IBC Section in accordance with Appendix X of AC377. 1203.3 or IRC Section R408.1,as applicable. 6.2 Report of room corner fire testing in accordance with e) Combustion air is provided in accordance with NFPA 286. International Mechanical Code®Section 701. 6.3 Report of air permeance testing in accordance with In attics, the insulation may be spray-applied to the ASTM E283. underside of roof sheathing or roof rafters, and/or vertical 7.0 IDENTIFICATION surfaces,and in crawl spaces the insulation may be spray- Components of the SES Foam 0.5 lb spray polyurethane applied to the underside of floors and/or vertical surfaces foam plastic insulation are identified with the as described in this section. The thickness of the foam manufacturer's name (SES Foam) and address; the date plastic applied to the underside of the top of the space of manufacture or the lot number; the product trade name must not exceed 12 inches(305 mm).The thickness of the (SES Foam 0.5 lb);the mixing instructions;the density; the foam plastic applied to vertical surfaces must not exceed flame-spread and smoke developed indices; and the 111/2 inches (292 mm). The foam plastic may be installed evaluation report number(ESR-3375). without a covering or coating. The insulation may be installed in unvented attics in accordance with 2012 IRC 8.0 OTHER CODES Section R806.5 (2009 IRC Section R806.4). The ignition In addition to the codes referenced in Section 1.0, the barrier in accordance with IBC Section 2603.4.1.6 or IRC products in the report were evaluated for compliance with Section R316.5.3 may be omitted. the requirements of the following codes: 4.4.3 Use on Attic Floors: SES Foam 0.5 lb spray ■ 2006 International Building Code®(2006 IBC) insulation may be installed exposed at a maximum thickness of 111/2 inches (292 mm) between joists in attic • 2006 International Residential Code®(2006 IBC) floors. The ignition barrier in accordance with IBC Section ■ 2006 and 2003 International Energy Conservation 2603.4.1.6 or IRC Section R316.5.3 may be omitted. The Code®(2006 IECC) insulation must be separated from the interior of the building by an approved thermal barrier. The products comply with the above-mentioned codes as provided in accordance with Sections 701 and 703 of described in Sections 2.0 through 7.0 of this report, with the 2006 IECC. revisions as noted below: • Protection against Termites: See Section 5.6, except • Application with a Prescriptive Thermal Barrier: See use of the insulation in areas where the probability of Section 4.3, except the approved thermal barrier must termite infestation if"very heavy"must be in accordance be installed in accordance with Section R314.4 of the with Section R320.5 of the 2006 IRC. 2006 IRC. ■ Jobsite Certification and Labeling: See Section 5.7, • Application with a Prescriptive Ignition Barrier: See except jobsite certification and labeling must comply Section 4.4.1, except an ignition barrier must be with Sections 102.1.1 and 102.1.1.1, as applicable, of installed in accordance with Section R314.5.3 or the 2006 IECC. R314.5.4 of the 2006 IRC. • Application without a Prescriptive Ignition Barrier: See Section 4.4.2, except that combustion air is TABLE 1—THERMAL RESISTANCE(R-VALUES11) THICKNESS(Inches) R-VALUE(°F•ft2•h/Btu) 1 4.0 2 7.6 3 11 3.5 13 4 15 5 19 6 22 7 26 6 30 9 33 10 37 11 41 12 44 For SI:1 inch=25.4 mm,1°F•ft2•h/Btu=0.176 110K•m2/W. 'R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES VAR Environmental Report . VAR-1030* Reissued July 2013 This report is subject to renewal September 1, 2015. www.icc-es.org/ep 1800-423-6587 I (562)699-0543 A Subsidiary of the International Code Council® DIVISION:07 00 00—THERMAL AND MOISTURE high-pressure, plural component SPF application PROTECTION equipment.The bio-based content is as set forth in Table 1 Section:07 21 00—Thermal Insulation of this report. REPORT HOLDER: 4.0 CONDITIONS 4.1 Code Compliance: SES FOAM See ICC-ES report ESR-3375 for compliance of the SES 4008 LOUETTA ROAD,#538 Foam 0,5 lb Foam S Polyurethane Foam Plastic Insulation SPRING,TEXAS 773884405 y (713)239-0252 with code requirements. www.sesfoam.com 4.2 Green Codes, Standards and Rating Systems Eligibility: EVALUATION SUBJECT: The information presented in Tables 2 through 5 of this FOAM 0.5 lb SPRAY POLYURETHANE FOAM report provides a matrix of areas of evaluation and SES PLASTIC INSULATION corresponding limitations and/or additional project-specific requirements, and offers benefits to individuals who are 1.0 EVALUATION SCOPE assessing eligibility for compliance. The final interpretation of the specific requirements of the Compliance with the following environmental criteria: code rests with the Authority Having Jurisdiction. ICC-ES Environmental Criteria for Determination of Compliance for items noted as "Verified Attribute" is Bio-based Material Content(EC102),dated March 1,2012. subject to any conditions noted in the tables. Decisions on Compliance eligibility with the applicable sections of compliance for those items noted as"Eligible for Points"in the following codes and standards: Tables 2 through 5 rests with the user of this report, and ■ 2012 International Green Construction Code TM (IgCC) those items are subject to the conditions noted.The user is advised of the project-specific provisions that may be (see Table 2 for details) contingent upon meeting specific conditions, and the • ASHRAE Standard 189.1 - 2009 (see Table 3 for verification of those conditions is outside the scope of this details) report. • National Green Building Standard (ICC 700-2008) (see Due to the variability of costs and volume,the bio-based Table 4 for details) content percentage listed in this report is based upon • ANSI/GBI 01-2010, Green Building Assessment weight (mass). The use of cost or volume as the method for calculation is outside the scope of this report. Protocol for Commercial Buildings (see Table 5 for details) 5.0 BASIS OF EVALUATION 2.0 USES The information in this report, including the "Verified Attributes," is based upon submission of documentation SES Foam 0.5 lb Foam S Polyurethane Foam Plastic demonstrating compliance with the requirements set forth Insulation is used as nonstructural thermal insulating in ICC-ES EC102. (Evaluation applies to IgCC Section material in wall cavities, floor/ceiling assemblies, or in 505.2.4, item 3; ASHRAE 189.1 Section 9.4.1.3; ICC 700 attics and crawl spaces. See ICC-ES report ESR-3375 for Section 606.1;ANSI/GBI-01 Section 10.1.2.2.) more information on uses and applications. 6.0 IDENTIFICATION 3.0 DESCRIPTION Containers of SES Foam 0.5 lb Foam S Polyurethane SES Foam 0.5 lb spray-applied polyurethane foam plastic Foam Plastic Insulation are identified by a label bearing the insulation is a two-component, open-cell, water-blown, SES Foam name and address, product name, spray-applied polyurethane foam (SPF) with a nominal manufacturing date, manufacturing location and the VAR density of 0.5 Ib/ft . The foam is sprayed in place using Environmental Report number(VAR-1030). "Corrected May 2014 ICC-ES Verification of Attributes Reports are issued under the ICC-ES VAR Environmental Program.?hese reports are not to be vomit-tied as representing aesthetics or any other attributes not specinatlly addressed nor are they to be consumed as an endorsement of the subject of the report or a recommendation far its use.There is no warranty by ICC ;"' Evaluation Service,LLC,express or implied as to atryfinding or otter matter in this report,or as to any product covered by the report. ti'�`; nxa`w TABLE 1—BIO-BASED MATERIAL CONTENT SUMMARY PRODUCT NAME %MEAN BIO-BASED CONTENT METHOD OF DETERMINATION SES Foam 0.5 lb Spray Polyurethane Foam Plastic Insulation 17%(+/-3%)1 ASTM D6866 Note: 'Based on precision and bias cited in ASTM D6866. TABLES 2 THROUGH 5 Section Possible Number Section Intent Points Conditions Of Use To Qualify For Points Finding TABLE 2—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2012 INTERNATIONAL GREEN CONSTRUCTION CODE Bio-based materials shall be those materials that comply with one or more of the following: 505.2.4 Bio-based content N/A 3.The requirements of USDA 7CFR Part 2902. • Note:USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum. TABLE 3—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2009 ASHRAE STANDARD 189.1 A minimum of 5%of building materials used,based on cost,shall be biobased products. Biobased products shall comply with the minimum biobased contents of the USDA's Designation of Biobased Items for Federal Procurement[7 CFR Part 29021 contain the 9.4.1.3 Biobased products N/A "USDA Certified Biobased Product"label,or be composed of solid wood,engineered wood,bamboo,wool,cotton,cork,agricultural fibers,or other biobased materials with at • least 50%blobased content. Note:USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum. TABLE 4—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2008 NATIONAL GREEN BUILDING STANDARD(ICC 700) The following biobased products are used: (h)products with the minimum biobased contents of the USDA 7 CFR Part 2902 606.1 Biobased products 3 (i)other blobased materials with a minimum of 50 percent biobased content(by weight 8 max or volume) • Note:USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum. TABLE 5—SUMMARY OF AREA OF ELIGIBILITY WITH THE ANSI/GBI–01(2010)STANDARD Bio-based products accounted for 1%or more of the materials used in the building. Percentage=100 x A=6,where: A=Total cost or weight of bio-based products B=Total cost or weight of all building products 10.1.2.2 Materials content– 1 Cost or weight must be used consistently • Assemblies 7 max For USDA-designated products,products meeting or exceeding USDA's bio-based content,criteria or qualifying as USDA"BioPreferred"were used. Note:USDA 7 CFR Part 2902§2907.17 sets a minimum bio-based content of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum. • =Verified attribute •i • • • • EZ. ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 Seal and Insulate with ENERGY STAR®Supplement Reissued August 2014 This report is subject to renewal August 2016. www.icc-es.org I (800)423-6587 I (562)699-0543 A Subsidiary of the International Code Council° DIVISION:07 00 00—THERMAL AND MOISTURE PROTECTION Section:07 21 00—Thermal Insulation REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING,TEXAS 77388-4405 (713)239-0252 www.sesfoam.com EVALUATION SUBJECT: SES FOAM 0.5 lb SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION 1.0 EVALUATION SCOPE Conformance to the following: Seal and Insulate with ENERGY STAR°Program—Definitions and Testing Requirements for Residential Insulation, Version 1.0 Properties evaluated: a Thermal resistance ■ Surface-burning characteristics 2.0 PURPOSE OF THIS SUPPLEMENT This supplement is issued to certify that the insulation products described in Sections 2.0 through 8.0 of the master report ESR-3375 have been reviewed for compliance with the requirements of the Seal and Insulate with ENERGY STAR° Program, as set forth in the document Definitions and Testing Requirements for Residential Insulation, Version 1.0. The insulation product covered by this supplement is defined as"Spray or Pour Foam Insulation." The requirements for testing laboratory qualification and product sampling, as well as the specific material and test standards and editions used in this evaluation, are as set forth in the applicable documentation noted in Section 6.0 of the master evaluation report. 3.0 DEFINITIONS The following definitions are from Definitions and Testing Requirements for Residential Insulation, Version 1.0, and are applicable to the subject of this report. 3.1 General Definitions: Insulation: Any material mainly used to slow down heat flow. It may be mineral or organic, fibrous, cellular, or reflective (aluminum foil). It may be in rigid,semi-rigid,flexible,or loose-fill form. 3.2 Insulation Product Definitions: Spray or Pour Foam Insulation:A thermal insulating material that is sprayed or poured(as a gel or foamy liquid)into place, and expands or sets into a cellular foam and cures at the point of installation through a chemical reaction. Foamed materials include,but are not limited to polyurethane,polyisocyanurate, phenolic, and cementitious insulation. 3.3 Insulation Performance Definitions: R-value:The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area. For the purposes of the Seal and Insulate with ENERGY STAR*program, Imperial units will only be accepted[(h•ft2•°F)/Btuj. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other antibuics not specifically addressed,nor arc they to be construed as an endorsement of the subject of the report or a recommendation for its use.Mere is no warranty by ICC f•valuation Service,LLC,express or implied,as VMS! to any finding or other mater In this report,or as to any product covered by the report. aa"'i Smoke-Development Index:The characteristic of a material to emit smoke when exposed to flame or fire compared to red oak and inorganic cement. Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed to flame or fire compared to red oak and inorganic cement. 3.4 Thermal Resistance: The insulation has the thermal resistance R-values as noted in Table 1 of ESR-3375,based upon testing. 3.5 Installation: 3.5.1 General: The installation of the insulation must be in accordance with the requirements set forth in Sections 4.0 and 5.0(as applicable)of ESR-3375.The insulation is manufactured on-site by spray polyurethane foam applicators meeting the qualification requirements of SES Foam. The following information on personal protective equipment and ventilation requirements is reprinted from the SES Foam published installation instructions: "F. SAFETY 3. PERSONAL PROTECTIVE EQUIPMENT(PPE): a. Skin: Wear gloves, coveralls, apron and boots as necessary to prevent contact of liquid components or partially-cured SPF with skin.When handling liquid components,gloves should be made of nitrite, neoprene, butyl or PVC. b. Eyes: Protect eyes while handling liquid components or spraying with safety goggles or safety goggles and a face shield.During spray application,eye protection may be provided by a full-face or hood respirator. c. Respiration: Firms engaged in the application of SES Foam systems must have a written respiratory protection program for employees engaged in handling or applying SES Foam materials. Depending on the situation, respiratory protection may include dust masks, air-purifying respirators (APR), powered air-purifying respirators(PAPR), or supplied- air respirators(SAR). 4. VENTILATION: Provide ventilation and other engineering controls to exhaust vapors from work areas and to protect building occupants and other trades." 3.5.2 Occupancy Time after Installation: The re-entry or re-occupancy time shall be in accordance with the manufacturer's installation instructions,which state the following: "E. RE-ENTRY SES Foam 0.5 lb Spray reacts and cures within seconds of application. Re-entry times will vary depending on factors including ventilation. Typically, ventilation is continued for 24 hours following the conclusion of spray application and re-entry may occur at that time." 3.5.3 Figures:The figures shown represent general installations of the insulation in the following applications:above-grade wall, below-grade wall,vented and unvented crawl space, unvented cathedral ceiling, and vented and unvented attic.These figures are for illustration purposes and are not to be construed or used as construction documents. This supplement expires concurrently with the master report,reissued August 2014. • • ')papa00p ;,%wo0 :*0 :00000000000 0 00:0-0:o 000000::000 Opo 000 Opo o Opo pp0 Op0:0-0 Op p0n000 0000000000000000�p00000°OOa06aa00c AL �00p0° O , pp0. �OOpO0 �OO�nO c..°0* °a O�OpnOti .:.00:00„c p 000:00:8- o 0po°6pO Interior Partition > po pe p0appo 0pC O p0 p pO0p0pa 000p0o a� � Interior Finished Surface • 00000000 (112-inch Sheelrock) 60:0 0,9°OC op060o op o °:o0 Q � SES Foam 0.5 lb Spray >p pop pc i,O00Qop 1 Exterior Sheathing 0000 0600 SES FOAM 0.5 LB SPRAY ASOVE GRADE WALL INSULATION SES 05-1 071912 UDts:O>•cc0- Masonry Block O��•r:• ;:.1 (Typical)---- ,/ ° ...;.:...z.:,;...:.::.::: '..•,�: Interior Finish Surface ♦ , .. (1/2-inch Sheetrock) `—�o ,•••••1'r•• .t 2"x 4"Studs 1I SES Foam 0.5 lb Spray 0,,, SES FOAM 0.5 LB SPRAY 1 BELOlaton GADlnterlordeASlINS aTION I SES 05-2 I 071812 Baffle to provide air space between may.. insulation and roof = Therm e al deck. �f- (as required ,,-,-=:- by local code) /,�// . 00• 0 0 000' i // �0000ao°oo°QO0000000a000 °oxooaoaoo /j 00000000..00000000000. 0000000000000000000000, .401 00000;0; 00000000 0000000 0 O O0 0 ::::: SES Foam 0,5 lb Spray 0000 0000°000 000.0000 00 000000000 0 00:0°000°0 000000000 00:00000 0°0000000 0 0;0;0; Vented Soffit :$000$: 0 1:g: gggg 0 0 0 0 ogogog0g gog°gog° `Where attic entry is for the ° ° ° SES Foam 0.5 lb Spray oggggggg service of utilities only,thermal g°go og° and igniton barrier on the attic 0 0 0 -:°gp° ° side of the spray foam surface V may be omitted. SES FOAM 0.5 LB SPRAY VENTED ATTIC:FLOOR/SOFFIT SES 05-3 071812 I ,:g.; 1 ;:ge, Subfloor ili °°Q° SES Foam 0.5 lb Spray If =i °°og°e° °o°°O°o°°0°O0o°o°0o°OOo°°O� °°° °° °°e°e°O°g°e°°e°°°o°e°$ovovo ,0,,ov_o°�o�° °°°°°°°°o°°000°000°°°o°o°°°o°o°o°o°°°oo. o° '°°0oO°OOO°OOOOOOOOOOO iii' Header �oaogege°°a°g ... '1 r, gg°e Sq>�°>°egg^�° Sill- Witt ii°i.' •88 8 og :' Joist Floor Cross Section O•••O• ° •_ ... • Thermal Barrier" Exterior Grade ..... (as required by / •`•ve• local code) X �\\\\88 8, ••••••.�. 6"Min •• •• Footer ��������� ��� �� !`Vapor Barrier `' •'r•''•• /\//\//\//r 'Where crawlspace entry Is for the ,' r` ' '•' i\ ' \ \\\ service of utilities only,thermal ,. ; :`•`f ; • /,,\\///\//cand igniton barrier on the crawtspace side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY CRAWLSPACE:VENTED SES 05-4 071812 A J sero gig° Subfloor viii Header fWier:, °°° — Sill- ►����� o°lJoist * •••WI• ►•���•4 a g Thermal Barrier' I'.�.�. A'mg! (as required by Exterior Grade ;4;i:4;35'0i local code) � \`/\ /\///„ �•:�= o': � SES Foam 0.5 lb Spray ► w'�. KS: , 6"Min Footer-„,.... ►•��•�•� • Vapor B.rrier • . .•`:,-1.•'.•:•••••,.. �/\\\ `1 'Where crawlspace entry is for the service of utilities only,thermal and igniton barrier on the crawlspace side of the spray foam surface may be omitted. • SES FOAM 0.5 LB SPRAY l CRAWLSPACE:UNVENTED I SES 05-5 1 071812 1 • Note:In cold climates,embed metal connector plates in spray foam to prevent winter-Ume condensation. o" • SES Foam 0.5 lb Spray E;y �°?000000. o°o j ,.°o° ' o° � Ooo „v Roof Sheathing _., o 000O Truss Top Cord/ °° Rafter _.,..,..°00. °°°' ,,---';' LAIIIIIIIIIIIIIII 1111111111111MIEMI gldIIIIIIII1 Thermal Barrier* (as required by local code) ill1 Note:Local building code may require the use of a vapor retarder n cold climate zones. Ceiling/Thermal Barrier 'Where attic entry is for the as required by local building code. service of utilities only,thermal and Igniton barrier on the attic side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY UNVENTED ATTIC/INSULATED ROOF DECK SES 05.6 071812 r i 0'''-'-=.,---... ,SES Foam 0.5 lb Spray . 0000.000 1to specified thickness. 0 O O O:•OO 0• -• 0 • 0OOID.Roof Sheathing ,: ---,ID ----0 00 0. 0 0 0 0 0' ' Thermal Barrier as Rafter �� fi•O O O ' required by code. .O �%� .=/ Note:The local building code / I may require the installation of s„'"'''-' a vapor barrier in cold climate `� zones. 1 SES FOAM 0.5 LB SPRAY I CATHEDRAL CEILING I SES 05-7 [ 071912 . • • f FILE COPY FORM R405-2014 - - FLORIDA, ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Faulk Apartment Builder Name: Street: 328 5th Street Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233 Permit Number: Owner: Bee Tree Homes Jurisdiction: Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(1293.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame Wood,Exterior R=13.3 1013.80 ft2 b.Frame-Wood,Adjacent R=13.3 279.20 ft2 3. Number of units,if multiple family 1 c.N/A2 R= t f 4. Number of Bedrooms 1 d.N/A R= ft2 10.Ceiling Ty Insulation Area 5. Is this a worst case? No a.Roof e: :4aos .)(Uvented) l R=21.0 840.00 ft2 6. Conditioned floor area above grade(ft2) 840 b.N/A R= ft2 Conditioned floor area below grade(ft2) 0 c.N/A R= ft2 11.Ducts R ft2 7. Windows(111.5 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6 168 a. U-Factor: Dbl,U=0.29 111.50 ft2 SHGC: SHGC=0.24 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 16.6 SEER:14.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 17.6 HSPF:8.20 SHGC: Area Weighted Average Overhang Depth: 1.087 ft. Area Weighted Average SHGC: 0.240 14.Hot water systems 8. Floor Types (840.0 sqft.) Insulation Area a.Natural Gas Tankless Cap:1 gallons EF:0.820 a.Floor over Garage R=19.0 790.00 ft2 b. Conservation features b.Slab-On-Grade Edge Insulation R=0.0 50.00 ft2 None c.N/A R= ft2 15.Credits Pstat Glass/Floor Area: 0.133 Total Proposed Modified Loads: 33.46 PASS Total Baseline Loads: 33.39 I hereby certify that the plans and specifications covered by Review of the plans and :'' F LKE.ST,gT' this calculation are in compliance with the Florida Energy specifications covered by this ../. ...;.-ti .-i-' `;FO Code. calculation indicates compliance • 4 �,,��6'•.� it+ with the Florida Energy Code. ...... `.'.',,e�„..O i i.!row PREPARED BY: Before construction is completed ' 1 Pte` t a ;,-1.1, .; ' m DATE: May 24,2016 Michael S. O'Donoughue this building will be inspected for ? " . ¢r;!`� •--.raa compliance with Section 553.908 t,`. ' . I herebycertifythat this building,as designed,is in compliance Florida Statutes. �' ''. with the Florida Energy Cod . g -OD 14 ••• OWNER/AGENT: . BUILDING OFFICIAL: IN DATE: � J�'I t' V DATE: S= 3/'/ 6 I - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2014 PROJECT Title: Faulk Apartment Bedrooms: 1 Address Type: Street Address Building Type: User Conditioned Area: 840 Lot# Owner: Bee Tree Homes Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Rotate Angle: 0 Street: 328 5th Street Permit Office: Duval Cross Ventilation: County: Duval Jurisdiction: Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE V Design Location TMY SiteIECC Design Temp Int Design Temp Heating Design Daily Temp Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block1 840 8300 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Intl!ID Finished Cooled Heated 1 System 1 790 7900 Yes 2 1 1 Yes Yes Yes 2 1st Floor 50 400 No 0 0 1 Yes Yes Yes FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio 1st Floor 28 ft 0 50 ft2 ---- 0 0 1 2 Floor over Garage System 1 ____ ____ 790 ft2 19 0 0 1 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Metal 939 ft2 210 ft2 Light 0.85 No 0.9 No 21 26.6 V ATTIC # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full cathedral ceilin Unvented 0 840 ft2 N N 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2014 CEILING V # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Unvented) System 1 0 790 ft2 0.11 Wood 2 Under Attic(Unvented) 1st Floor 0 50 ft2 0.11 Wood WALLS VAdjacent Space Cavity Width Height Sheathing Framing Solar Below # Ornt To Wall Type R-Value Ft In Ft In Area R-Value Fraction Absor. Grade/o 1 W Exterior Frame-Wood System 1 13.3 9.5 0 12.8 0 121.6 ft2 0 0.23 0.6 0 2 N Exterior Frame-Wood System 1 13.3 6.8 0 12.8 0 87.0 ft2 0 0.23 0.6 0 3 N Garage Frame-Wood 1st Floor 13.3 12 0 12.8 0 153.6 ft2 0 0.23 0.6 0 4 W Exterior Frame-Wood System 1 13.3 9.667 0 8 0 77.4 ft2 0 0.23 0.6 0 5 W Garage Frame-Wood 1st Floor 13.3 15.7 0 8 0 125.6 ft2 0 0.23 0.6 0 6 W Exterior Frame-Wood System 1 13.3 21 0 8 0 168.0 ft2 0 0.23 0.6 0 7 S Exterior Frame-Wood System 1 13.3 12.75 0 8 0 102.0 ft2 0 0.23 0.6 0 8 E Exterior Frame-Wood System 1 13.3 21 0 8 0 168.0 ft2 0 0.23 0.6 0 9 S Exterior Frame-Wood System 1 13.3 12.83 0 8 0 102.6 ft2 0 0.23 0.6 0 10 N Exterior Frame-Wood System 1 13.3 2 0 8 0 16.0 ft2 0 0.23 0.6 0 11 E Exterior Frame-Wood System 1 13.3 13.9 0 8 0 111.2 ft2 0 0.23 0.6 0 12 N Exterior Frame-Wood System 1 13.3 7.5 0 8 0 60.0 ft2 0 0.23 0.6 0 DOORS V # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 N Insulated System 1 None .4 3 3.5 10.5 ft2 2 W Insulated 1st Floor None .4 3 6.7 20.1 ft2 WINDOWS Orientation shown is the entered,Proposed orientation. / Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 W 1 Wood Low-E Double Yes 0.29 0.24 18.0 ft2 1.1 ft 0 in 11 ft 0 in None None 2 N 2 Wood Low-E Double Yes 0.29 0.24 10.5 ft2 1.1 ft 0 in 11 ft 0 in None None 3 W 6 Wood Low-E Double Yes 0.29 0.24 33.5 ft2 1.1 ft 0 in 1 ft 0 in None None 4 S 7 Wood Low-E Double Yes 0.29 0.24 15.0 ft2 1 ft 0 in 4.1 ft 0 in None None 5 S 9 Wood Low-E Double Yes 0.29 0.24 15.0 ft2 1.1 ft 0 in 4.1 ft 0 in None None 6 E 11 Wood Low-E Double Yes 0.29 0.24 7.5 ft2 1.1 ft 0 in 1 ft 0 in None None 7 N 12 Wood Low-E Double Yes 0.29 0.24 12.0 ft2 1.1 ft 0 in 4.1 ft 0 in None None GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 810ft2 384ft2 103 ft 10 ft 1 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2014 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000314 691.7 37.97 71.41 .2976 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.2 17.6 kBtu/hr 1 sys#1 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER:14 16.64 kBtu/hr 499 cfm 0.75 1 sys#1 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas Tankless Exterior 0.82 1 gal 40 gal 120 deg None SOLAR HOT WATER SYSTEM VFSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply---- Return Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 168 ft2 Attic 42 ft2 Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programable[ Jan fX1 Thermostat: lY IXIM:rr Ceiling Fans: en Vt ng fX1 Feb 1)(1 Apr May lXl Jun iunn lXi Jul lX�Aug lXiSep 2:13 IX]Oct X]Nov Dec Jev St Venting [ ]Jan [ ]Feb x Mar 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5 l FORM R405-2014 Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 ' FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 100 The lower the EnergyPerformance Index,the more efficient the home. 328 5th Street, Atlantic Beach, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=13.3 1013.80 ft2 b.Frame-Wood,Adjacent R=13.3 279.20 ft2 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Ty..-: Insulation Area a.Roof D: k(Unvented) R=21.0 840.00 ft2 6. Conditioned floor area(ft2) 840 b.N/A R= ft2 7. Windows" Description Area c.N/A R= ft2 a. U-Factor: Dbl,U=0.29 111.50 11. Ducts R ft2 ft2 a.Sup:Attic,Ret:Attic,AH:Attic 6 168 SHGC: SHGC=0.24 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 16.6 SEER:14.00 SHGC: d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 17.6 HSPF:8.20 Area Weighted Average Overhang Depth: 1.087 ft. Area Weighted Average SHGC: 0.240 8. Floor Types Insulation Area 14.Hot water systems Cap:1 gallons a.Floor over Garage R=19.0 790.00 ft2 a.Natural Gas EF:0.82 b.Slab-On-Grade Edge Insulation R=0.0 50.00 ft2 c. N/A R= ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building =" EKE ST •.. Construction through the above energy saving features which will be installed (or exceeded) ,'yOF.... ......... 4,o in this home before final ins ection. Otherwise,a new EPL Display Card will be completed : �c�•,, ,;� based on installed Codec iant features. :a ,:-..%''>::,-t- 0 a' •__�.1'�.w:4 Builder Signature: Date: C I Li I Le :.0'; ( a Address of New Home: cit ckk City/FL Zip: 1\1,�,,,k4,t-72.,,,....C1k t •.,!.t c D. ��g .. *Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation,contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 • FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 328 5th Street Permit Number: Atlantic Beach,FL,32233 MANDATORY REQUIREMENTS See individual code sections for full details. i401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law [Section 553.9085,Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. o R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3.Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6.Supply and return registers,if installed at the time of the test,shall be fully open. O R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. O R402.4.3 Fenestration air leakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 L/s)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed S luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. �j�J/ R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system. 1 R403.1.3 Heat pump supplementary heat(Mandatory).Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.2.2 Sealing(MandatoryAll ducts,air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99,Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 1 of 3 • • FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) O R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. lir R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3., O R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight,moisture,equipment maintenance,and wind,and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. 1e R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. ile R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies O R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water heating systems to be turned off. O R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. ▪ R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. leR403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. O R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception:Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. O R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62,Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics,crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise. R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. se O R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) O R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. • R403.6.1.2 Heating equipment capacity • R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1 1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. ▪ R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. • R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. o R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. 71 R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building.shall include automatic controls capable of shutting off the system when the pavement temperature is above 55`F.and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40`F. 1 R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2.Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. o R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or • solar energy source computed over an operating season. RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. 0 R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. O R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space. R-10 is allowed. 5/24/2016 9:53 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name. Paulk Apartment Builder Name: Street: 328 5th Street Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233 Permit Number: Owner: Bee Tree Homes Jurisdiction: Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations,and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated,and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 5/24/2016 9:54 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 Paulk Casita HVAC Load Calculations for Bee Tree Homes v JACKSONVILLE` BUILDING SCIENCE® Prepared By: Michael O'Donoughue Jacksonville Building Science, LLC 450 SR13 N#132 Jacksonville, FL.,32259 (904)807-3540 Tuesday, May 24,2016 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D. ' �dJ v ,:�:�5 �` v ��'1� J I-`ns�'k'r� ��"j�� •^� k Y`'s 7 3r�" �kr7 ^�',�,,+a,r .n'N',::s �'��';a-.�-•�rt `"� ' i • 4 r �L -}� "S`�'-- _ 1 "�im ,�r��'��'�`}'�£.,z.���;.sa� fs x c'„-Y. +is�,i:,yb"sx -v E� ��'k �y,'ttiF�lr„�•��~a-- � . • 't4„.3(k d tt a tXeN Al XQkaa ' £� 474 - t` a t��., 'X L• • d�-J ,Project Report Project Title: Faulk Casita Designed By: Michael O'Donoughue Project Date: Monday, May 09,2016 Client Name: Bee Tree Homes Company Name: Jacksonville Building Science, LLC Company Representative: Michael O'Donoughue Company Address: 450 SR13 N#132 Company City: Jacksonville, FL., 32259 Company Phone: (904)807-3540 Company E-Mail Address: mod@JaxBuildingScience.com Company Website: www.JaxBuildingScience.com Lesign Data -- Reference City: Jacksonville Mayport Naval, Florida Building Orientation: Front door faces North Daily Temperature Range: Medium Latitude: 30 Degrees Elevation: 16 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb ReLHum Edam Dry Bulb Difference Winter: 39 36.58 n/a n/a 72 n/a Summer: 92 78 54% 50% 75 58 Check Figures — —— -- —.=- — ---- —--- — Total Building Supply CFM: 458 CFM Per Square ft.: 0.545 Square ft.of Room Area: 840 Square ft. Per Ton: 746 Volume(ft3)of Cond. Space: 6,962 Building Loads — ------____----------------- Total Heating Required Including Ventilation Air: 14,751 Btuh 14.751 MBH Total Sensible Gain: 10,815 Btuh 80 % Total Latent Gain: 2,709 Btuh 20 % Total Cooling Required Including Ventilation Air: 13,523 Btuh 1.13 Tons(Based On Sensible+ Latent) I Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 BeeTree Homes\Paulk\load calc apartment\Paulk Casita.rh9 Tuesday, May 24,2016,9:39 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Paulk Casita St Johns FL 32259 _____- Page 3 Total Building SurnmarLLoads AIIIMIIIIIMIIIIMIIIIIIIIIIIIIIIIIIIIIIIIIIIIMIIMIIII Pella low-e: Glazing-vinyl double pane low-e., u-value 111.5 1,068 0 2,206 2,206 0.29, SHGC 0.24 11J: Door-Metal-Fiberglass Core 30.6 570 0 417 417 12C1-0sw:Wall-Frame, R-13.3 open cell 1/2 lb. spray 891.8 2,649 0 1,886 1,886 foam insulation in 2 x 4 stud cavity, no board 1 insulation,siding finish,wood studs 12C1-0sw: Part-Frame, R-13.3 open cell 1/2 lb. spray 259.1 700 0 466 466 foam insulation in 2 x 4 stud cavity, no board insulation,siding finish,wood studs 1861-210-ml: Roof/Ceiling-Roof Joists Between Roof 1182.3 1,833 0 1,278 1,278 Deck and Ceiling or Foam Encapsulated Roof Joists, R-21 open cell 1/2 lb. spray foam, 5.5 inches in 2 x 6 joist cavity, 1 inch on joist, light metal 22A-ph-t: Floor-Slab on grade, No edge insulation, no 28 1,255 0 0 0 insulation below floor,tile covering, passive, heavy moist soil 20P1-19op-t: Floor-Over open crawl space or garage, 790.2 1,330 0 484 484 Passive, spray foam insulation, R-19 open cell 1/2 lb. spray foam insulation, 5 inches in 2 x 10 joist cavity, tile covering Subtotals for structure: 9,405 0 6,737 6,737 People: 2 400 460 860 Equipment: 0 1,950 1,950 Lighting: 0 0 0 Ductwork: 1,778 738 489 1,227 Infiltration:Winter CFM: 58, Summer CFM:0 2,117 0 0 0 Ventilation:Winter CFM:40, Summer CFM:40 1,451 1,571 748 2,318 AED Excursion: 0 0 431 431 Total Building Load Totals: 14,751 2,709 10,815 13,523 Check Figures Total Building Supply CFM: 458 CFM Per Square ft.: 0.545 Square ft.of Room Area: 840 Square ft. Per Ton: 746 Volume(ft3)of Cond. Space: 6,962 Building Loads --- - --- -_ --- T Total Heating Required Including Ventilation Air: 14,751 Btuh 14.751 MBH Total Sensible Gain: 10,815 Btuh 80 Total Latent Gain: 2,709 Btuh 20 % Total Cooling Required Including Ventilation Air: 13,523 Btuh 1.13 Tons(Based On Sensible+ Latent) Notes _ Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 BeeTree Homes\Paulk\load calc apartment\Paulk Casita.rh9 Tuesday, May 24,2016,9:39 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Faulk Casita St.Johns,FL 32259 {{{ Page_.__.._._.__ e 4 BuildinQPie Chart Ventilation 10% Floor 18% Infiltration 14% Roof 12% Ductwork 120/o Door 4% Wall 23% Glass 7% Floor 4% AED Excursion 3% Roof 9% Ventilation 17% Wall 17% Ductwork 9% Glass 16% Equipment 14% Door 3% People 6% Y:12.1 BeeTree Homes\Paulk\load calc apartment\Paulk Casita.rh9 Tuesday, May 24, 2016, 9:39 AM • ,Rhvm* '--'------- � — Jacksonville Building Science St.Johns FL 32259 Sk3/e/D 1 Zone 5 Summary (Average for --__—_ Rooms) LCom- Pella low-e: Glazing-vinyl double pane low-e., u-value 111.5 1,068 0 2,206 2,206 0.29, SHGC 0.24 11J: Door-Metal-Fiberglass Core 30.6 570 0 417 417 12C1'Omw:VVaU'Fnemo. R-13.3 open cell 1/2 lb. spray 891.8 2,649 0 1,886 1,886 foam insulation in 2 x 4 stud cavity, no boar insulation, siding finish,wood studs 12C1'Omw: Part-Fmma. R'18.3open cell 1/2lb.spray 259.1 700 0 466 466 foam insulation in 2 x 4 stud cavity, no board insulation,siding finish,wood studs 18B1-210-ml: Roof/Ceiling-Roof Joists Between Roof 1182.3 1,833 0 1,278 1,278 Deck and Ceiling or Foam Encapsulated Roof Joists, R-21 open cell 1/2 lb.spray foam,5.5 inches in 2 x 6 joist cavity, 1 inch on joist, light metal 22A-ph-t: Floor-Slab on grade, No edge insulation, no 28 1,255 0 0 0 insulation below floor,tile covering,passive, heavy moist soil 20P1-l9op-t: Floor-Over open crawl space or garage, 790.2 1,330 0 484 484 Passive,spray foam insulation, R-19 open cell 1/2 lb. spray foam insulation,5 inches in 2 x 10 joist cavity, tile covering Subtotals for structure: 9.405 0 6,737 6,737 People: 2 400 460 860 Equipment: 0 1,950 1,950 Lighting: 0 0 0 Ductwork: 1,622 0 489 489 Infiltration:Winter CFM:58, Summer CFM:0 2,117 0 0 0 System 1.Zone 5Load Totals: 13,144 400 10.067 10,467 | -- ------- Check Figures Supply CFM: 458 CFM Per Square ft.: 0.545 Square ft.of Room Area: 840 Square ft.Per Ton: 963 Volume (ft3)of Cond.Space: 6,962 � 9173 2onoLoaof?" `="/..r 7~--=`� Total Heating Required: 13,144 Btuh 13.144 MBH Total Sensible Gain: 10.067 Btuh 96 % Total Latent Gain: 400 Btuh 4 % Total Cooling Required: 10,467 Btuh 0.87 Tons(Based OnSensible+La�nV |�-' ------------- ---------- - --' -----�� �--���-- -- � —' -- - - ----'--� ^Noh» Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. - y — — — — Paulk asitaJ Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development Inc. Jacksonville Building Science St Johns FL. 32259 System I Room Load Summary Htg Min Run Run Clg Clg Min A Room Area Sens Htg Duct Duct Sens Lat Clg � No Name SF Btuh CFM Size Vel Btuh Btuh CFM C., ---Zone 5--- 1 Bath 6 50 3,704 48 1-0 0 1,561 0 71 71 2 Kitchen 160 2,098 27 1-0 0 2,613 200 119 119 3 Living Room 300 3,151 41 1-0 0 3,269 200 149 149 4 Suite 5 230 2,681 35 1-0 0 1,660 0 75 75 5 B5 100 1,510 20 1-0 0 965 0 44 44 Ventilation 1,451 748 1,571 Duct Latent 339 Return Duct 156 0 398 System 1 total 840 14,751 171 10,815 2,709 458 458 Cooling System Summary Cooling Sensible/Latent Sensible Latent To ll Tons Split Btuh Btuh B Net Required: 1.13 80%/20% 10,815 2,709 13,523 Actual: 1.39 79%/21% 13,129 3,508 16,637 Equpment Data , ...,,i,,,, , ._. Heating System Cooling System Type: Air Source Heat Pump Air Source Heat Pump Model: CH14NB018****A CH14NB018****A Indoor Model: FB4CNP018L Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING Description: Air Source Heat Pump Air Source Heat Pump Efficiency: 8.2 HSPF 14 SEER Sound: 0 0 Capacity: 17,600 Btuh 16,637 Btuh Sensible Capacity: n/a 13,129 Btuh Latent Capacity: n/a 3,508 Btuh AHRI Reference No.: n/a 7845770 Y:\2.1 BeeTree Homes\Paulk\load calc apartment\Paulk Casita.rh9 Tuesday, May 24,2016,9:39 AM CH14NB Single—Stage Heat Pump with Puron® Refrigerant Carrie) 1 -1/2 To 5 Tons turn to the expert__ ...,F.1 Product Data INDUSTRY LEADING _ FEATURES/BENEFITS Efficiency 1 Jy • 14 SEER/11.5- 11.7 EER/8.2 HSPF • Microtube Technology'" refrigeration system - • Indoor air quality accessories available fil -71,r I�� �� (ii Sound LL{uHMICQ I j+!I:;' • Sound level as low as 69 dBA 111 I 1 .11 l'!' • Sound levels as low as 68 dBA with accessory sound blanket 1'tt �1}� II NMI ;1.'' Comfort -''111111�tl l0 • System supports Coll ,Edge®or standard thermostat controls c I !! `tllllll 111010)111 Reliability � `�I� IR 1011111 ( Il • Puron®refrigerant-environmentally sound,won't deplete the '1 Milli - ozone layer and low lifetime service cost. 4111111Ii�lllA ; I11: • Scroll compressor 411111 �[ Hii I, • Internal pressure relief valve Ilk I • Internal thermal overload il ; IIIIIlf111NIg11 • High pressure switch �� !' • Loss of charge switch -__. • Filter drier • Balanced refrigeration system for maximum reliability Durability NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory WeathcrArmor" protection package: (www.ahridirectory.org) for the most up-to-date ratings • Solid,durable sheet metal construction information. • Dense wire coil guard Applications • Long-line-up to 250 feet(76.20 m)total equivalent length,up to 20U feet(60.96 in)condenser above evaporator,or up to 80 ft. (24.38 m)evaporator above condenser(See Longline Guide for more information.) • Low ambient(down to-20"F/-28.9"C)with accessory kit Monday, March 16, 2015 Currier Case Summary Report Turn to the Experts Job: 2/18/2016 Case 1 Outdoor: CH14NA0180000A Indoor:FB4CNF018 Type: Dom SpIitHP,208/230, 10 SODB(°F) SIDB(°F) SIRH SIWB(°F) WJDB(°F) WDB(°F) Elev(ft) Suction line loss(ft) AVF(cfm) 93.5 75.0 51.7 63.0 35.9 70.0 0 1.4 600 Unit Net Cool Net Cool Net Cool Cool Net Heat Heat AVF Sensible Latent Capacity SEER kW Capacity HSPF kW (cfm) (Btuh) (Btuh) (Btuh) (Btuh) AHRI Rated: 600 0 0 17800 13.50 0.00 17600 8.00 0.00 Adjusted: 600 12330 4307 16637 1.49 14702 1.30 2016-Feb-23 10 30:08 4 wrightsoft Performance Calculator 1.0.22 Page 1 CurrierCase Details Report Turn to the Exports. Job: 2/18/2016 Case 1 Equipment Cooling Data Table Outdoor:CHI4NA0180000A Indoor:FB4CNF018 ODB 75 85 95 105 115 125 (°F) Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr AVF EWB (Btuh) (kW) (Btuh) (kW) ()Ruh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (cfm) (°F) 525 57 16970 16970 1.19 16300 16300 1.3515580 15580 1.52 14810 14810 1.73 13980 13980 1.9513080 13080 2.20 62 17640 15030 1.19 16780 14640 1.3515880 14220 1.53 14930 13760 1.73 14000 14000 1.9513100 13100 220 67 19440 12770 1.19 18480 12390 1.3617470 11990 153 16400 11580 1.73 15260 11150 1.9614060 10690 2.21 72 21430 10440 1.20 20380 10060 1.36 19270 9660 1.54 18100 9260 1.74 16860 8830 1.97 15560 8390 2.22 600 57 17730 17730 1.20 17010 17010 1.3616240 16240 1.54 15410 15410 1.74 14520 14520 1.97 13570 13570 2.22 62 18080 16130 1.20 17200 15710 1.36 16270 16270 1.54 15430 15430 1.74 14540 14540 1.97 13590 13590 2.22 67 19860 13610 1.20 18860 13220 1.37 17800 12820 1.55 16690 12390 1.75 15510 11950 1.97 14270 11480 2.22 72 21880 10960 121 20770 10580 1.38 19620 10180 1.5618400 9760 1.7617120 9330 1.9815770 8880 2.23 675 57 18360 18360 1.21 17600 17600 1.38 16780 16780 156 15910 15910 1.75 14970 14970 1.9813970 13970 2.23 ODB: Outdoor dry bulb Total: Total capacity EWB: Indoor wet bulb Sens: Sensible capacity AVF: Air volumetric flow Pwr: kW input 2016-Feb-23 10:30:08 41- wrightsoft Performance Calculator 1.0.22 Page 1 Currier Case Details Report Turn to the Exports Job: 2/1812016 Case 1 Equipment Heating Data Table Outdoor:CH14NA0180000A Indoor:FB4CNF018 ODB -3 7 17 27 37 47 57 67 (°F) Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr EDB AVF (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (°F) (cfm) 65 525 5260 1.03 7450 1.09 9800 1.14 12540 1.21 15070 1.27 17870 1.35 21000 1.44 24190 1.53 600 5360 1.04 7570 1.09 9960 1.13 12700 1.19 15260 1.24 18130 1.31 21350 1.40 24320 1.47 675 5440 1.04 7660 1.09 10090 1.13 12830 1.18 15430 1.23 18330 1.29 21540 1.37 24320 1.43 70 525 4980 1.08 7150 1.14 9490 1.20 12280 1.27 14780 1.33 17540 1.41 20610 1.51 23840 1.61 600 5080 1.08 7270 1.14 9640 1.19 12450 1.25 14980 1.31 17800 1.38 20950 1.47 24010 1.55 675 5160 1.09 7380 1.14 9770 1.18 12580 1.24 15140 1.29 18010 1.36 21210 1.44 24050 1.50 75 525 4650 1.13 6830 1.19 9150 1.25 11980 1.33 14490 1.40 17210 1.48 20220 1.58 23470 1.69 600 4740 1.13 6950 1.19 9310 1.24 12160 1.31 14690 1.37 17460 1.45 20550 1.54 23680 1.62 675 4840 1.14 7050 1.19 9440 1.24 12300 1.30 14860 1.36 17670 1.42 20820 1.51 23750 1.58 600 4740 1.13 6950 1.19 9310 1.24 12160 1.31 14690 1.37 17460 1.45 20550 1.54 23680 1.62 675 4840 1.14 7050 1.19 9440 1.24 12300 1.30 14860 1.36 17670 1.42 20820 1.51 23750 1.58 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ODB: Outdoor dry bulb Totl: Total capacity AVF: Air volumetric flow Pwr: kW input EDB: Indoor dry bulb 2016-Feb-23 1030:08 wrightsoft Performance Calculator 1.022 Page 2 JACKSONVILLE Manual D - Duct Design & r�ENERGYSTAR BUILDING - `" AWARD 2015 SCIENCE® Schematic PARTNER OF THE YEAR Beetree Homes - Paulk Apartment CFM 600 mid speed range TESP 0.5 Conditioned area 840 Design Static air side devices = 0.03 0.03 0 Conditioned Volume 0 DPL= 0.06 ASP= 0.44 FR=PDx100/TEL 0.13 TEL 329 , ,() �. Supply Network Element Lot Design L Iain Fin EL TEL Cal vel Vel Size(ID) Specific CFM Duct Duct WxH T1 419 419 5 35 15 55 55 12.0 11.3 419 12 X 12 Branch Ducts Element Lot Design L Fitt Fitt EL TEL Cal Vel Vel QTY ' Size Grill Size Specific CFM Duct Duct I Bath 6 69 69 19 60 55 134 189 6.14.6 258 I 7 _ 10x6 2 Kitchen 116 116 8 60 55 123 178 7.4 • 6.0 332 1 8 12x8 3 Living room 139 139 II 60 55 126 , 181 7.9 6.5 398 I 8 12x8 4 Suite 5 55 55 12 60 55 127 182 5.6 4.1 280 _ 1 6 10x6 5 Bath 5 40 40 5 60 55 120 175 4.9 ' 3.5 294 1 5 10x6 5/23/2016 all calculations and designs in accordance with ACCA Manual D 2009-2014 Rev pg 1 of 1 ' • •MEW.LLx.L L NO 031NI2ld 41.1=.8/1.SI 3WVOS 9NIMV210• •SONIMVLIO 3S3H13WVOS ION 00.1 ' suoi11 OUIOads ®3DN3IJS O Tuau lndd °NIalm a aauapisax lined sauUGH aaUUaag DVAH y3111ANOSNDW s� ,lj,4'?� s(<4.1 '-'1P ti . a S0° N fl.. n U _ S 1L at o m 0 .i j �3g Y L• f,-.1 v V .7 N Z .• 5 m8 4 a U i�<' off rzoz` v f-A a 3 2 •_• • .. Y p p% r y 3 6 i P E F P t 8 d. ; Y+7 §.4';011 Ts; _ 2 - m $ o f t i A gg 5 S < _ gg 9 430 ,0 E 7 1 _ tl a i 2 3 e P 7 g I E - F y �( z .. 7 3 a `Y " 3t 1 J L L ! 3 E E il .2 . s a i - A Y § $ f. ; . ' „fit - g c � z11 3 p E. `n ` m a c _ . .1 .7° , '; `' , •0, 0 •1 E s < .. r L a d£ Y <gg $g, 8 E � � I 3 � L' Ems` Z a` � � � 2 6 j qi 5 5 47 . 1� 6 1, 2 v t`` @ z 1 .�s ,1 j s a L R = ' " i ` 3 C L'- .Z _ o : U G riE . E .8 x e C .iii ; SS _ 5 $ °C l �'i N 1 :122 : ' - .5. .' _ pp x o. pf c o m e •y 2.5 fi 6 _ s 5y _. 7 �- S a S t n 2• k' ' 3 q s E g E v C - < < °'2 •-.. z 7 n s , $- 3 �. Z 1P-t1� 2 2 g €qq = i F r a i _ _ . 2 liA14 W Ill' N g g a 3 p % ;F - E - - 6 < C Fz- 3 < Y Y u. O 117- E�', ,Cg9 S A i S E ' i r € g t I IfiiimPE?••% •ONDee .Z . S$£t` 370yy S 0 t c rE / I i Q 'Alin O i `g E V C 1 v ' It u f J= V I\ 2 N m a e .1 3, - 2 c s j C lo g ; dh E _ Z E y y t tl y 9 s aAnS 3 : r 4 C E E E 5 I 2 3 g. P: h r s17: g •' 14:75-1 ,0 cVI z 5 7 i 5 I. 7.. §-A .12 7.7i a no: E a 83 8 2 �9� g�• @ tli"Y E n L 8, i s T. `• ` at < 2 a E a c - 3 � gg 5 Y u 1 E _zsIl YIr . i i 3 1 E, _G A G r€ E Y 4 Y s i o 1 S s x ..'z •81 2 .8- g 5 s g gW Y l i 0 iIflI: b 1j $ 8 E.cGG g." Y= y 0-4 9 s . 2 a 0 f II!J .It 54<4<= 6<S E GAA - g 14 .E r, L K >E y. ®3JN31D I y e ,-_I U !d Ieaiuegaaysi aouapisa)J lined -saWOH aaa�aa8 DNKFII t 311IANOS>IDVf c^ I A dop a0'. --1. . _ ______,k.........._.___,___-1 3, (,-.1.,e r1 il, .... ,. ... ., � ce-I rV� N '.I. o • 1 le , Li_1. /3 = f .5 ,. ,,,, _ . . _ , ., _e I '] ' . , Y. `-1I. -- I - .. 'kT- i ! ` I I Iri 1 „ „ c a C S ; V E1 c cis U o o w 4, V4 L_ g 3• 1 in . L----i* . es • • 71 . Ell3JN3ID 1 mid iraTUEgaayv aauapisag Xinud-sOWoH aa9NI1lin . .. /R 1 3 I1II NOs?1Dvr a9' s 2u 111 -- P.b 31. - ,-- \ 0 N as 111/4111k._ 0 vs I?, GPo ` � . � waE._ - m N • l n .£ -_—- •� a ..,. !i U r U 0 RS .4 U N 4. O O w b c O v O tu I, -� i ae i as 1 S h 9 4 Rhvac-Residential&Light Commercial HVAC L d Elite Software Development,lnc �I Jacksonville Building Science,„ ' Paulk Casita I St.Johns.FL 32259 Page tj Manual S Performance Data - System 1 - System 1 ] Outdoor Dry Bulb: 92 Sensible Gain: 10,815 Outdoor Wet Bulb: 78 Latent Gain: 2,709 Indoor Dry Bulb: 75 Total Gain: 13,523 Indoor RH: 50 Load SHR: 0.80 Elevation: 16 Supply Airflow: 458 Latitude: 30 Entering Dry Bulb: 76.4 Altitude Factor: 1 Entering Wet Bulb: 64 E•ui•ment Performance Data at S stem Desi•n Conditio't, Air Source Heat Pump Model: CH14NB018****A+FB4CNP018L, Nominal Capacity: 16,637 Entered In er•olation D. .. EDB 1 EWB Air Flow ODB Total Power 75°F °F CFM °F Capacity Input Sensible Btuh kW S/T Capacity j Btuh 62 85 16780 1.35 0.725 12159 458 95 15880 4.53 0.722 11469 67 85; 18480 1.36 0.811 14984 95i 17470 1.53 0.811 14174 Interpolation Results: Percent Load of Load Sensible Capacity: 12,117 10,815 112% Latent Capacity: 4,219 2,709 156% Total Capacity: 16,336 13,523 121% Power Input: 3.54 Y:\2.1 BeeTree Homes\Paulk\load calc apartment\Paulk Casita.rh9 Tuesday, May 31,2016, 12:04 PM FILE COPY ..,, „ r:.'',rry.. ;..err FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Paulk Residence Builder Name: Bee Tree Homes Street: 328 Fifth Street Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233 Permit Number: Owner: Bee Tree Homes Jurisdiction: Design Location: FL,Jacksonville 1. New construction or existing New(From Plans) 9. Wall Types(3349.7 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame Wood,Exterior R=13.3 3349.70 ft2 b.N/A R= ft2 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (3752.0 sqft.) Insulation Area a.Roof Deck(Unvented) R=21.0 3232.00 ft2 6. Conditioned floor area above grade(ft2) 4135 b.Knee Wall(Unvented) R=0.0 520.00 ft2 Conditioned floor area below grade(1t2) 0 c.N/A R= ft2 11. Ducts R ft2 7. Windows(620.3 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6 646 a. U-Factor: Dbl,U=0.30 444.00 ft2 SHGC: SHGC=0.20 b. U-Factor: Dbl,U=0.27 108.00 ft2 12.Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.22 a.Central Unit 38.6 SEER:14.00 c. U-Factor: Dbl,U=0.27 35.25 ft2 SHGC: SHGC=0.21 13.Heating systems kBtu/hr Efficiency d. U-Factor: other(see details) 33.00 ft2 a. Electric Heat Pump 41.0 HSPF:8.20 SHGC: other(see details) Area Weighted Average Overhang Depth: 6.636 ft. Area Weighted Average SHGC: 0.204 14.Hot water systems 8. Floor Types (4135.0 sqft.) Insulation Area a.Natural Gas Tankless Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 3142.00 ft2 EF:0.820 b. Conservation features b.Floor Over Other Space R=0.0 903.00 ft2 None c.other(see details) R= 90.00 ft2 15.Credits Pstat Total Proposed Modified Loads: 87.41 Glass/Floor Area: 0.150 PASS Total Baseline Loads: 104.88 I hereby certify that the plans and specifications covered by Review of the plans and ' �xE ST,4'.., this calculation are in compliance with the Florida Energy specifications covered by this A��' , , •..:0�.\. Code. calculation indicates compliance vj`t!/IN,' . •i.2....:•.��-.:,�'`• with the Florida Energy Code. /, nn,, ,;'O`•; PREPARED BY: Before construction is completedy' -- DATE: May24,2016 this buildingwill be inspected for a f 1; �-- v Michael S. O'Donoughue p 1 0 l.� compliance with Section 553.908 I herebycertifybuilding,as designed, compliance that this is in Florida Statutes. �' ." :' with the Florida Energy 2pd . •%.vODWE'C�J OWNER/AGENT: BUILDING OFFICIAL: M ...... DATE: \1711t(../ DATE: S'7/.1 6 - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. - Compliance with a proposed duct leakage On requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with Section 803 of RESNET Standards, is not greater than 0.000 On for whole house. 5/24/2016 8:46 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 • FORM 8405-2014 PROJECT Title: Faulk Residence Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 4135 Lot# Owner: Bee Tree Homes Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Bee Tree Homes Rotate Angle: 0 Street: 328 Fifth Street Permit Office: Duval Cross Ventilation: County: Duval Jurisdiction: Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE V Design Location TMY SiteIECC Design Temp Int Design Temp Heating Design Daily Temp Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Blockl 4135 56482 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 System 1 3142 45559 Yes 5 2 1 Yes Yes Yes 2 2nd Floor 993 10923 No 0 2 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio System 1 290 ft 0 3142 ft2 ____ 0 0 1 2 Raised Floor System 1 ____ ____ 90 ft2 19 0 0 1 3 Floor Over Other Space 2nd Floor ____ ____ 903 ft2 0 0 0 1 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) _ 1 Gable or shed Metal 3885 ft2 1078 ft2 Light 0.85 No 0.9 No 21 33.7 V ATTIC # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full cathedral ceilin Unvented 0 3232 ft2 N N 5/24/2016 8:46 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2014 CEILING V # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Unvented) 2nd Floor 0 993 ft2 0.11 Wood 2 Under Attic(Unvented) System 1 0 2239 ft2 0.11 Wood 3 Knee Wall(Unvented) 2nd Floor 0 520 ft2 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below # Ornt To Wall Type R-Value Ft In Ft In Area R-Value Fraction Absor. Grade% _ 1 N Exterior Frame-Wood System 1 13.3 7.083 0 10 0 70.8 ft2 0 0.23 0.6 0 2 N Exterior Frame-Wood System 1 13.3 11.83 0 10 0 118.3 ft2 0 0.23 0.6 0 3 N Exterior Frame-Wood System 1 13.3 12.66 0 10 0 126.7 ft2 0 0.23 0.6 0 4 E Exterior Frame-Wood System 1 13.3 15.83 0 10 0 158.3 ft2 0 0.23 0.6 0 5 N Exterior Frame-Wood System 1 13.3 17.33 0 10 0 173.3 ft2 0 0.23 0.6 0 6 E Exterior Frame-Wood System 1 13.3 6.333 0 10 0 63.3 ft2 0 0.23 0.6 0 7 E Exterior Frame-Wood System 1 13.3 10.75 0 10 0 107.5 ft2 0 0.23 0.6 0 8 S Exterior Frame-Wood System 1 13.3 7.1 0 10 0 71.0 ft2 0 0.23 0.6 0 9 S Exterior Frame-Wood System 1 13.3 25.08 0 10 0 250.8 ft2 0 0.23 0.6 0 10 S Exterior Frame-Wood System 1 13.3 18.41 0 15.3 0 281.8 ft2 0 0.23 0.6 0 11 W Exterior Frame-Wood System 1 13.3 14.83 0 14.25 0 211.3 ft2 0 0.23 0.6 0 12 S Exterior Frame-Wood System 1 13.3 18.16 0 13 0 236.2 ft2 0 0.23 0.6 0 13 W Exterior Frame-Wood System 1 13.3 9 0 10 0 90.0 ft2 0 0.23 0.6 0 14 W Exterior Frame-Wood System 1 13.3 12.41 0 10 0 124.2 ft2 0 0.23 0.6 0 15 W Exterior Frame-Wood System 1 13.3 5.083 0 10 0 50.8 ft2 0 0.23 0.6 0 16 N Exterior Frame-Wood System 1 13.3 9.75 0 10 0 97.5 ft2 0 0.23 0.6 0 17 N Exterior Frame-Wood System 1 13.3 15.25 0 10 0 152.5 ft2 0 0.23 0.6 0 18 E Exterior Frame-Wood System 1 13.3 12.41 0 10 0 124.2 ft2 0 0.23 0.6 0 19 S Exterior Frame-Wood 2nd Floor 13.3 5.167 0 10 0 51.7 ft2 0 0.23 0.6 0 20 N Exterior Frame-Wood 2nd Floor 13.3 26 0 9 0 234.0 ft2 0 0.23 0.6 0 21 E Exterior Frame-Wood 2nd Floor 13.3 18 0 9 0 162.0 ft2 0 0.23 0.6 0 22 N Exterior Frame-Wood 2nd Floor 13.3 1 0 9 0 9.0 ft2 0 0.23 0.6 0 23 S Exterior Frame-Wood 2nd Floor 13.3 13.33 0 9 0 120.0 ft2 0 0.23 0.6 0 24 S Exterior Frame-Wood 2nd Floor 13.3 2.667 0 9 0 24.0 ft2 0 0.23 0.6 0 25 S Exterior Frame-Wood 2nd Floor 13.3 6.583 0 9 0 59.2 ft2 0 0.23 0.6 0 26 S Exterior Frame-Wood 2nd Floor 13.3 15.81 0 9 0 142.3 ft2 0 0.23 0.6 0 27 W Exterior Frame-Wood 2nd Floor 13.3 4.333 0 9 0 39.0 ft2 0 0.23 0.6 0 DOORS `✓ # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 E Wood System 1 None .46 3 4 12 ft2 2 N Wood 2nd Floor None .46 3 6.7 20.1 ft2 5/24/2016 8:46 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2014 WINDOWS Orientation shown is the entered,Proposed orientation. Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N 1 Wood Low-E Double Yes 0.3 0.2 57.0 ft2 7.5 ft 0 in 1.5 ft 0 in None None 2 N 2 Wood Low-E Double Yes 0.3 0.2 24.0 ft2 7.5 ft 0 in 1.5 ft 0 in None None 3 N 3 Wood Low-E Double Yes 0.3 0.2 24.0 ft2 7.5 ft 0 in 1.5 ft 0 in None None 4 N 5 Wood Low-E Double Yes 0.3 0.2 24.0 ft2 7.5 ft 0 in 1.5 ft 0 in None None 5 E 4 Wood Low-E Double Yes 0.27 0.21 18.8 ft2 1.1 ft 0 in 1.5 ft 0 in None None 6 E 6 Wood Low-E Double Yes 0.3 0.2 12.0 ft2 1.1 ft 0 in 15 ft 0 in None None 7 S 9 Wood Low-E Double Yes 0.28 0.19 33.0 ft2 12 ft 0 in 1 ft 0 in None None 8 S 9 Wood Low-E Double Yes 0.27 0.21 16.5 ft2 12 ft 0 in 1 ft 0 in None None 9 S 10 Wood Low-E Double Yes 0.3 0.2 96.0 ft2 12 ft 0 in 1 ft 0 in None None 10 S 10 Wood Low-E Double Yes 0.3 0.2 24.0 ft2 1.1 ft 0 in 4 ft 0 in None None 11 S 12 Wood Low-E Double Yes 0.3 0.2 48.0 ft2 12 ft 0 in 1 ft 0 in None None 12 S 12 Wood Low-E Double Yes 0.3 0.2 27.0 ft2 12 ft 0 in 2.5 ft 0 in None None 13 W 14 Wood Low-E Double Yes 0.3 0.2 8.0 ft2 1.1 ft 0 in 11 ft 0 in None None 14 N 16 Wood Low-E Double Yes 0.3 0.2 8.0 ft2 7.5 ft 0 in 1 ft 0 in None None 15 N 17 Wood Low-E Double Yes 0.3 0.2 24.0 ft2 7.5 ft 0 in 1.5 ft 0 in None None 16 E 18 Wood Low-E Double Yes 0.27 0.22 21.0 ft2 1.1 ft 0 in 13 ft 0 in None None 17 E 18 Wood Low-E Double Yes 0.27 0.22 18.0 ft2 1.1 ft 0 in 13 ft 0 in None None 18 E 18 Wood Low-E Double Yes 0.27 0.22 24.0 ft2 1.1 ft 0 in 13 ft 0 in None None 19 E 18 Wood Low-E Double Yes 0.27 0.22 45.0 ft2 1.1 ft 0 in 5 ft 0 in None None 20 E 21 Wood Low-E Double Yes 0.3 0.2 30.0 ft2 1.1 ft 0 in 1.5 ft 0 in None None 21 S 25 Wood Low-E Double Yes 0.3 0.2 8.0 ft2 1.1 ft 0 in 2 ft 0 in None None 22 S 26 Wood Low-E Double Yes 0.3 0.2 30.0 ft2 1.1 ft 0 in 4 ft 0 in None None INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000434 4706.8 258.4 485.96 .4114 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.2 41 kBtu/hr 1 sys#1 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER:14 38.58 kBtu/hr 1157 cfm 0.75 1 sys#1 5/24/2016 8:46 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5 • FORM R405-2014 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas Tankless Exterior 0.82 1 gal 70 gal 120 deg None SOLAR HOT WATER SYSTEM V FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply---- Return -- Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 646 ft2 Attic 162 ft2 Proposed Qn Attic ---cfm 0.0 cfm 0.00 0.60 1 1 TEMPERATURES Programable( T1hermostat:lV EXi Ceiling Fans: Venting fXl Jan IXJ Feb Mar iXJApr May lXJ Jun lXi Jul lXl Aug lXl Sep !X]Oct �XJ Nov lx.}Dec Venting [ J Jan [ J Feb XMar Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 5/24/2016 8:46 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 83 The lower the EnergyPerformance Index,the more efficient the home. 328 Fifth Street, Atlantic Beach, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame Wood,Exterior R=13.3 3349.70 ft2 b.N/A IR= ft 3. Number of units,if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area a.Roof Deck(Unvented) R=21.0 3232.00 ft2 6. Conditioned floor area(ft2) 4135 b.Knee Wall(Unvented) R=0.0 520.00 ft2 7. Windows" Description Area c.N/A R= ft2z a. U-Factor: Dbl,U=0.30 444.00 ft2 11.Ducts R ft a.Sup:Attic, Ret:Attic,AH:Attic 6 646 SHGC: SHGC=0.20 b. U-Factor: Dbl,U=0.27 108.00 ft2 SHGC: SHGC=0.22 12.Cooling systems kBtu/hr Efficiency c. U-Factor: Dbl,U=0.27 35.25 ft2 a.Central Unit 38.6 SEER:14.00 SHGC: SHGC=0.21 d. U-Factor: other(see details) 33.00 ft2 13.Heating systems kBtu/hr Efficiency SHGC: other(see details) a.Electric Heat Pump 41.0 HSPF:8.20 Area Weighted Average Overhang Depth: 6.636 ft. Area Weighted Average SHGC: 0.204 8. Floor Types Insulation Area 14.Hot water systems Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 3142.00 ft2 a.Natural Gas EF:0.82 b.Floor Over Other Space R=0.0 903.00 ft2 c.other(see details) R= 90.00 ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building ;•••01..... j;•••. Construction through the above energy saving features which will be installed(or exceeded) -: tib-- .. 0 in this home before final inspection. Otherwise, a new EPL Display Card will be completed i yc.'y,, % based on installed Code • nt features. 11,,„ ......-..:..4'...' .,- ,' . - O: Builder Signature: Date: a a ��Z.Ity . `' '.. Address of New Home: 1).-2:46 ckk V�vt-� City/FL Zip: ii ,t_c 1,� c-\ o ..4 `y... ..-\fp4. *Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 5/24/2016 8:27 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Paulk Residence Builder Name: Bee Tree Homes Street: 328 Fifth Street Permit Office: Duval City,State,Zip: Atlantic Beach,FL,32233 Permit Number: Owner: Bee Tree Homes Jurisdiction: Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings,drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawispace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations,and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 5/24/2016 8:30 AM EnergyGauge®USA-FlaRes2014 Section R405 4.1 Compliant Software Page 1 of 1 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 328 Fifth Street Permit Number: Atlantic Beach ,FL.32233 M�►NDATORY REQUIREMENTS See individual code sections for full details. �' 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law [Section 553.9085.Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. c R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors.fireplace and stove doors shall be closed,but not sealed.beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air.backdraft and flue dampers shall be closed. but not sealed beyond intended infiltration control measures; 3.Interior doors,if installed at the time of the test.shall be open: 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems. if installed at the time of the test,shall be turned off;and 6.Supply and return registers.if installed at the time of the test.shall be fully open. o R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. o R402.4.3 Fenestration air IeakageWindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 L/s/m2).and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. C R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 L/s)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed ;>) luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. V'] R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat(Mandatory).Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost.prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.2.2 Sealing(Mandatory)111 ducts.air handlers.and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99.Florida Statutes.or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system. including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test.total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 5/24/2016 9:12 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105'F(41'C) or below 55°F(13°C)shall be insulated to a minimum of R-3., C R403.3.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight.moisture,equipment maintenance,and wind,and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. 1 R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. 1 R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies (I) R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38`C to 60'C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation.Commercial Provisions.for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. ▪ R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806.Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar water heating systems should meet the following criteria. 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal:and 2. Be installed at an orientation within 45 degrees of true south. R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code.Residential or Florida Building Code.Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. o R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception:Where mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. C R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62,Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics.crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise. le R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. C R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies. based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 5/24/2016 9:12 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) C R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal, rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. O R403.6.1.2 Heating equipment capacity • R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. ▪ R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. ' R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. C R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. • R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. • R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems, supplied through energy service to the building.shall include automatic controls capable of shutting off the system when the pavement temperature is above 55`F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. C R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum • thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2.Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. G R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or ' solar energy source computed over an operating season. RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. C R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space. R-10 is allowed. 5/24/2016 9:12 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 3 of 3 Paulk Residence HVAC Load Calculations for Bee Tree Homes JACKSONVILLE BUILUNG SCIENCE® Prepared By: Michael O'Donoughue Jacksonville Building Science, LLC 450 SR13 N#132 Jacksonville. FL., 32259 (904)807-3540 Tuesday, May 24, 2016 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2, and ACCA Manual D. Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Paulk Residence St Johns.FL 32259 Pace 2 Project Report — -- - General Project Informa/•lir•`' Project Title: Paulk Residence Designed By: Michael O'Donoughue Project Date: Monday, May 09,2016 Client Name: Bee Tree Homes Company Name: Jacksonville Building Science, LLC Company Representative: Michael O'Donoughue Company Address: 450 SR13 N#132 Company City: Jacksonville, FL., 32259 Company Phone: (904)807-3540 Company E-Mail Address: mod©JaxBuildingScience.com Company Website: www.JaxBuildingScience.com I Design Data Reference City: Jacksonville Mayport Naval, Florida Building Orientation: Front door faces North Daily Temperature Range: Medium Latitude: 30 Degrees Elevation: 16 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 39 36.58 n/a n/a 72 n/a Summer: 92 78 54% 50% 75 58 Check Figures__— ---- Total Building Supply CFM: 1,274 CFM Per Square ft.: 0.308 Square ft. of Room Area: 4,135 Square ft. Per Ton: 1,301 Volume(ft3)of Cond. Space: 45,507 tEs uilding Loads _ ____ _ — __ -__ Total Heating Required Including Ventilation Air: 50,221 Btuh 50.221 MBH Total Sensible Gain: 28,145 Btuh 74 % Total Latent Gain: 9,989 Btuh 26 % Total Cooling Required Including Ventilation Air: 38,134 Btuh 3.18 Tons(Based On Sensible+Latent) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday, May 24,2016,8:57 AM .; Rhvac-Residential&Light Commercial HVAC Loads 4 Elite Software Development,Inci Jacksonville Building Science Paulk Residence I St.Johns,FL 32259- - _ - . -- __ ?age 3 Total Building Summary Loads _ _ _ 'Component _ Area Sen Lat Sen Totat'i Description _ _ _ _._ Quan Loss _ Gain ___ Gain Gain _ Gain] Pella low-e wood: Glazing-Proline Series Enduraclad 444 4,400 0 4,901 4,901 wood double pane low-e with argon., u-value 0.3, SHGC 0.2 Pella low-e wood: Glazing-Proline Series Enduraclad 143.2 1,278 0 3,388 3,388 wood double pane low-e with argon.,u-value 0.27, SHGC 0.22 Pella low-e wood: Glazing-Proline Series Enduraclad 33 304 0 288 288 wood double pane low-e with argon., u-value 0.28, SHGC 0.19 11G: Door-Wood-Panel 12 214 0 181 181 11A: Door-Wood-Hollow Core 20.1 47 0 47 47 12C1-0sw:Wall-Frame, R-13.3 open cell 1/2 lb. spray 2483.6 7,377 0 5,252 5,252 foam insulation in 2 x 4 stud cavity, no board insulation,siding finish,wood studs 12A-Osw: Part-Frame, no insulation in stud cavity, no 520.5 625 0 625 625 board insulation,siding finish,wood studs 12C1-0sw: Part-Frame, R-13.3 open cell 1/2 lb. spray 231.9 104 0 104 104 foam insulation in 2 x 4 stud cavity,no board insulation,siding finish,wood studs 1861-210-ml: Roof/Ceiling-Roof Joists Between Roof 4876.3 7,565 0 5,270 5,270 Deck and Ceiling or Foam Encapsulated Roof Joists, R-21 open cell 1/2 lb. spray foam,5.5 inches in 2 x 6 joist cavity, 1 inch on joist, light metal 22A-ph-t: Floor-Slab on grade, No edge insulation, no 290 12,997 0 0 0 insulation below floor,tile covering, passive, heavy moist soil 20P1-19op-c: Floor-Over open crawl space or garage, 90 151 0 55 55 Passive,spray foam insulation, R-19 open cell 1/2 lb. spray foam insulation,5 inches in 2 x 10 joist cavity, carpet covering Subtotals for structure: 35,062 0 20,111 20,111 People: 5 1,000 1,150 2,150 Equipment: 125 3,450 3,575 Lighting: 0 0 0 Ductwork: 6,980 3,755 1,003 4,758 Infiltration:Winter CFM: 185, Summer CFM:90 6,728 3,538 1,684 5,222 Ventilation:Winter CFM:40, Summer CFM:40 1,451 1,571 748 2,318 Total Building Load Totals: 50,221 9,989 28,145 38,134 ------- ------ (.Check Figures ______ ____-.._ Total Building Supply CFM: 1,274 CFM Per Square ft.: 0.308 Square ft.of Room Area: 4,135 Square ft. Per Ton: 1,301 Volume(ft3) of Cond. Space: 45,507 FBuilding Loads Total Heating Required Including Ventilation Air: 50,221 Btuh 50.221 MBH Total Sensible Gain: 28,145 Btuh 74 Total Latent Gain: 9,989 Btuh 26 Total Cooling Required Including Ventilation Air: 38,134 Btuh 3.18 Tons(Based On Sensible+Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition,Version 2,and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. Y:\2.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday,May 24,2016,8:57 AM Rhvac-Residential 8 Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science Paulk Residence St Johns FL 32259 —__.-- -- -._.-Page 4 Building Pie Chart Ventilation 3% Infiltration 13% Floor 26% Ductwork 14% • , x ° Door 1% Roof 15% '` .= 4 Glass 12% Wall 16% Floor 0% Ventilation 6% Roof 14% Infiltration 14% Wall 16% Ductwork 12% Equipment 9% Glass 22% People 6% Door 1% Y:\2.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday, May 24. 2016, 8:57 AM • Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc. Jacksonville Building Science 16> Paulk Residence _St_Johns,FL 32259Page 5 System I Room Load Summary WoHtgHtg Min Run Run Clg Clg Min Act Area Sens Duct Duct Sens Lat Clg Sys SF hoa tip Btuh CFM Size Vel Btuh Btuh CFM CFM ---Zone 1--- 1 Foyer 130 1,530 20 1-0 0 956 64 43 43 2 Study 204 2,009 26 1-0 0 1,420 308 65 65 3 Study WIC 27 64 1 1-0 0 41 0 2 2 4 Bath 2 80 1,760 23 1-0 0 714 115 32 32 5 B3 43 57 1 1-0 0 37 0 2 2 6 Laundry Room 68 181 2 1-0 0 116 0 5 5 (aka B4- Downstairs) 7 Suite 2 275 4,524 59 1-0 0 1,864 302 85 85 9 Mud Room 50 948 12 1-0 0 508 58 23 23 10 Pantry 80 1,882 24 1-0 0 479 162 22 24 11 Kitchen 428 2,977 39 1-0 0 4,081 428 186 186 12 Dining Room 238 0 0 1-0 0 243 200 11 11 13 Great Room 440 6,675 87 1-0 0 4,329 794 197 197 25 Suite 2 Hall 51 0 0 1-0 0 0 0 0 0 Zone 1 subtotal 2,115 22,608 294 14,788 2,431 673 673 --Zone 2--- 14 Owner's Suite 285 6,922 90 1-0 0 3,212 756 146 146 15 Owner's Hall 95 252 3 1-0 0 162 0 7 7 16 Owner's WIC 116 1,253 16 1-0 0 440 82 20 20 17 Owner's Bath 147 1,719 22 1-0 0 869 113 40 40 18 Owner's WC 47 1,759 23 1-0 0 559 135 25 25 19 Owner's Sitting 185 2,275 30 1-0 0 960 139 44 44 Zone 2 subtotal 874 14,180 184 6,202 1,225 282 282 ---Zone 3--- 8 Stairs 152 4,036 52 1-0 0 4,611 272 210 210 20 Loft 359 1,594 21 1-0 0 1,133 229 52 52 21 Suite 4 251 2,790 36 1-0 0 2,282 287 104 104 22 B4 WC 40 495 6 1-0 0 289 54 13 13 23 B4 87 192 2 1-0 0 124 0 6 6 24 Suite 3 256 1,896 25 1-0 0 1,184 165 54 54 Zone 3 subtotal 1,145 11,004 143 9,623 1,007 438 438 Ventilation 1,451 748 1.571 Duct Latent 541 Return Duct 978 -610 3.214 System 1 total 4,135 50,221 621 28,145 9,989 1,274 1,274 Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the"Average Load Procedure +Excursion"method. Cooling System Summary Cooling Sensible/Latent Sensible Latent Total 10000.., ons Split Btuh- Btuh - Btuh Net Required: Actual: 3.18 74%/26% 28,145 9,989 38,134 3.21 74%/26% 28,586 9,989 38,575 Data Type: -. Heating System Cooling System Air Source Heat Pump Air Source Heat Pump Model: OH14NB042****A CH14NB042****A Indoor Model: FB4CNP042L Brand: CARRIER AIR CONDITIONING CARRIER AIR CONDITIONING i Description: Air Source Heat Pump Air Source Heat Pump Y:',2.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday,May 24, 2016,8:57 AM Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.1 Jacksonville Building Science Paulk Residence! St.Johns,FL 32259 - — PaaeLJ System 1 Room Load Summary (cont'd) Data_ -‘111,- I Efficiency: 8.2 HSPF 14 SEER Sound: 0 0 Capacity: 41,000 Btuh 38,575 Btuh Sensible Capacity: n/a 28,586 Btuh Latent Capacity: n/a 9,989 Btuh AHRI Reference No.: n/a 7835544 Y:12.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday,May 24,2016,8:57 AM Carrier, Case Details Report Turn to the Expert Job: 2/18/2016 Case 1 Equipment Cooling Data Table Outdoor:CH14NA0420000A Indoor:FB4CNP042 ODB 75 85 95 105 115 125 (°Fl Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr Total Sens Pwr AVF EWB (Btuh) (kW) (Btuh) (kVV) (Bluh) (kVl/) (Btuh) (kVV) (Btuh) (kw) (Btuh) (kw) (cfml (°A 1225 57 39590 39590 2.85 37990 37990 3.18 36300 36300 3.53 34500 34500 3.92 32560 32560 4.35 30450 30450 4.83 62 41130 34950 2.83 39090 34020 3.18 36990 33030 3.54 34800 31960 3.92 32600 32600 4.35 30490 30490 4.83 67 45060 29550 2.78 42760 28640 3.15 40380 27710 3.53 37860 26740 3.93 35240 25740 4.37 32440 24680 4.86 72 49420 24000 2.69 46660 23080 3.09 44190 22130 3.50 41400 21160 3.93 38490 20160 4.38 35400 19110 4.88 1400 57 41190 41190 2.87 39470 39470 3.21 37640 37640 3.58 35710 35710 3.97 33620 33620 4.40 31370 31370 4.89 62 42030 37400 286 39940 36370 3.21 37750 37650 3.58 35750 35750 3.97 33660 33660 4.41 31410 31410 4.89 67 45920 31410 2.80 43510 30480 3.18 41000 29520 3.57 38390 28530 3.97 35660 27490 4.42 32790 26400 4.90 72 50340 25140 2.70 47640 24200 3.12 44850 23230 3.53 41950 22240 3.96 38920 21230 4.42 35740 20170 4.92 1575 57 42530 42530 2.89 40680 40680 3.25 38740 38740 3.61 36690 36690 4.01 34480 34480 4.45 32110 32110 4.94 ODB: Outdoor dry bulb Total: Total capacity EWB: Indoor wet bulb Sens: Sensible capacity AVF: Air volumetric flow Pwr: kW input W rI htsoft' 2016-Feb-23 12.10 37 9 Performance Calculator 0 22 Page 1 �.�.«r Case Details Report Turn to the Experti Job: 211812016 Case 1 Equipment Heating Data Table Outdoor:CH14NA0420000A Indoor:FB4CNP042 ODB -3 7 17 27 37 47 57 67 (°F) Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr Total Pwr EDB AVF (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kVV) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (Btuh) (kW) (°F) (dm) 65 1225 13640 2.13 18060 2.28 22720 2.45 27780 2.63 33740 2.82 39100 2.97 45430 3.11 52750 3.20 1400 13910 2.14 18380 2.29 23100 2.45 28280 2.62 34140 2.79 39630 2.93 46120 3.05 53260 3.11 1575 14160 2.15 18660 2.30 23420 2.46 29370 2.64 34510 2.78 40070 2.91 46660 3.01 53490 3.05 70 1225 12890 2.26 17360 2.41 22030 2.57 27040 2.74 33190 2.94 38480 3.09 44690 3.24 52010 3.36 1400 13150 2.27 17690 2.41 22410 2.57 27490 2.73 33620 2.91 39000 3.06 45380 3.18 52590 3.26 1575 13410 2.29 17970 2.42 22730 2.57 27870 2.73 33960 2.90 39430 3.03 45930 3.15 52890 3.20 75 1225 12130 2.40 16630 2.53 21300 2.69 26290 2.86 32580 3.06 37860 3.23 43980 3.38 51220 3.51 1400 12390 2.41 16930 2.54 21680 2.69 26740 2.85 33040 3.04 38370 3.19 44640 3.32 51880 3.42 1575 12630 2.43 17210 2.55 22000 2.69 27110 2.85 33410 3.03 38790 3.16 45180 3.29 52230 3.36 1400 12390 2.41 16930 2.54 21680 2.69 26740 2.85 33040 3.04 38370 3.19 44640 3.32 51880 3.42 1575 12630 2.43 17210 2.55 22000 2.69 27110 2.85 33410 3.03 38790 3.16 45180 3.29 52230 3.36 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ODB: Outdoor dry bulb Totl: Total capacity AVF: Air volumetric flow Pwr: kW input EDB: Indoor dry bulb - 0 37 2016-Feb-23 12 wrightsoft Performance Calculator 1.0.22 Page 2 rm.,ENERGY STAR JACKSONVILLE BUILDING Manual D - Duct Design & - AWARD 2015 SCIENCE® Schematic PARTNER OF THE YEAR Beetree Homes - Paulk Main House CFM 1,400 mid speed range TESP 0.5 Conditioned area 4,135 Design Static air side devices = 0.03 0.03 0 Conditioned Volume 56412 DPL= 0.06 ASP= 0.44 FR=PDx 100/TEL 0.10 TEL 440 '' 1 Supply Network Lot Design Cal VeI Size(ID) Element Specific CFM L Fitt Fin EL TEL Vet Duct Duct WxH T1 666 666 5 35 15 55 55 14.2 14.3 477 16 T2 666 666 5 15 15 35 90 14.2 14.3 581 15 X 1 1 T3 563 563 37 15 15 67 157 13.3 13.1 540 15 X 10 T4 260 260 35 35 15 85 85 99 8.9 477 10 MBI 260 260 75 75 160 22X22X36 T5 430 430 18 21 15 54 54 ®® 402 14 MB2 430 430 75 75 129 22x22x36 Branch Ducts Element Lot Design L Fitt Fitt EL TEL Cal Vel Vel QTY Size Grill Size Specific CFM Duct Duct I Foyer 42 42 21 60 55 136 293 5.0 3.6 308 1 5 10x6 2 Study 61 61 II 60 55 126 283 5.7 4.3 311 I 6 10x6 3 Study WIC 10 10 2 60 55 117 274 3.0 1.7 204 I 3 8x4 4 Bath2 30 30 5 60 55 120 277 4.0 3.0 344 I 4 8x4 5 Bath3 10 10 2 60 55 117 274 3.0 1.7 204 I 3 8x4 6 Laundry 10 10 3 60 55 118 275 3.0 1.7 204 1 3 8x4 8 Suite 2 82 82 7 60 55 122 279 6.4 5.0 307 1 7 12x8 9 Mud room 24 24 12 60 55 127 284 4.0 2.7 275 1 4 8x4 JO Pantry 27 27 12 60 55 127 284 4.0 2.9 310 1 4 8x4 I I Kitchen/Dining 186 186 6 60 55 121 278 8.8 7.5 696 2 7 12x8 13 Great Room 184 184 13 60 55 128 285 8.7 7.5 938 3 6 10x6 14 Owners 142 142 9 60 55 124 284 8.0 6.6 724 2 6 12x6 16 0 WIC 18 18 4 60 55 119 279 3.0 2.3 367 1 3 8x4 17 0 Bath 36 36 8 60 55 123 283 4.7 3.3 264 I 5 10x6 I8 0 WC 25 25 14 60 55 129 289 4.0 2.8 287 1 4 8x4 19 Sitting 39 39 12 60 55 127 287 4.9 3.5 286 I 5 10x6 20 Stairs 203 203 18 60 55 133 262 9.1 7.9 760 2 7 12x8 21 Loft 65 65 12 60 55 127 256 5.9 4.5 331 1 6 10x6 22 Suite 4 95 95 8 60 55 123 252 6.8 5.4 356 1 7 12x8 5/23/2016 all calculations and designs in accordance with ACCA Manual D 2009-2014 Rev pg 1 of 2 • • 1, ENERGY JACKSONVILLE Manual D - Duct Design & r' AWARD 20STAR BUILDING SCIENCE® Schematic PARTNER OF THE YEAR Beetree Homes - Paulk Main House 23 Bath4 WC 10 10 11 60 55 126 255 3.0 1.7 204 I 3 8x4 24 Bath 4 10 10 6 60 55 121 250 3 0 1.7 204 1 3 8x4 25 Suite 3 47 47 14 60 55 129 258 5.3 3.8 239 I 6 I2x6 1 1 0 0 I I I 5/23/2016 all calculations and designs in accordance with ACCA Manual D 2009-2014 Rev pg 2 of 2 ' •VI03W.LLX.LL NO 031NI8d A,L=.B/L SI 3MVOS ONIMVMO• •SDNIMV210 3S3H131VOS ION 00• suoiMioadS ®3JN31JS C) asnoH u►ew Tommi aauapisa)Kilned saUIoH aaUaau DVAH 43llinNOSNDV1 , Vr s� 0 a sO d !n i N .. rn $ S 2 o p.,, s z r:: oo _ Q I .... 0 V tF,—w`n^t.roM ;KK 7;O-- u ip Q v� r NN LT: U Z - w /W[- U y g a N 2 m 0 2 en $ t t mi ,_. a aasia Z C Z' . hNyNin yp S U c e 4+ a i O u 1 W = ,V U uy 1"111gp 44 8e i l V E Q 3 ; Z pp t Z u i —EEWs $ 5 -• ,.noa I3 E Sff @ Yy fi - r. Y c 1 G• L . Z F § c .1 “,11i Q ay 9• .:, v u f I . e 2 C 01-1; F F r 5 3 E _ 1 4 .4 E n v % 1". a i G 2 EX �, `c N i Z g I i 5 N E i - b — r :E 3 .5 z 'Q X €gi g < p .z a 5 s .1 .. ` s i _ - 2 & ;: illi g e _ £ E 5 3 a z @ 5 1 s $ If g i6e d $ R21141I I: • i; g s S 50 t - ' s a E 2 .1 t $ < < cZ u ac �S P,, ' 6 ,190 s j 's `^ . N 1 W _ i s u u @ d Y r j LL 2 5 :, e E s s Y : x q_ ;I at Z 1 2 ) ..F3.. 3 < l z 1 ▪ zi `• G EY 1 r a E 9 E c S a E 1 _. :, i 0 1 116,130ME!®.% eloc)geo li _ ^7 x a K r 3 �E G I 6 1 $ `- `S n Y t s n 3 P . p Z i i C E E C p. -.g2 = sI 4 in 4 A 75 1c g E En V] z 11.10 TC„ g p � sg' z �g . t' 2 g= S s 5a ¢ i r c .4 € f pI b l Z a B ,ig.g9 “.o 0 f .0 . < G g g e E i W'2S$$ 003. g e 8 : E ,4E` e� 2 :`4 F g g :-it s Q 1 — < 3 E 1 4 ' Y c S c'. Y e E 5 $ 5 Y D J l G_ . s 410 s E ;ill" 3EYE Ii g E ` 1 Itgt a_¢4 I E; 1 st et s l4 Y F 2 Y s $ I ct r cn 2,,, ;pg./ 7,31,..-r � t ' E 2 E ° _ 2e = g s?1� E `@t 1Y P Z 9 15 ' 9 8 c 9 Z I 111"7m I/;4 °.5 G i i ! Y= c 5 i c 1 F!-! +i r a Milli] 54 aaz' a l 9 J i € si 11 r E lis 83 A5 J Juu !E.v 5_n ..5 S_1..b — — — "X' — c ' 4 uS :AAA Z - • • ®37N3DV t 1 r 3 .--I U Id t 0P W43 I 03uapisaJ lined-satuoH aaa;aag 9NKflIA I I 311IANOSNDI !(baa , , i, r _ f — e-I I r �' II . . , I J= --moi E - c _ I F O p 1 I i '' I 1 ' ri , ,______ , , c , r_.,i i_,. . a I U �_y I. v1 Cl* , ' . . , [. U 0 0 Li. y t. w as O.- ; - - I I • 103JN317 1, 1 , < N urld lnoluey�ayv 03uapisag lined-sauuoH aar�aag DN�.1s NDV � 1 I w laa C 2,...8 'Y g L —. I o I I N Io —.marlcn G s y I e Y 5 C_ • .vim~ 4. I1 8 , .1 i s h— 9 • _• I---r, � n r-r- n- T L -i3'--I I I - iI' - r _a. U g U N v O O 4. C O U N w N 1_ U } 71 N ce a 1 •i c ►I w .------ ------------------.- ----- -_-. Rhvac-Residential&Light Commercial HVAC Loads Elite Software Dilkevelopment,Inc. Jacksonville Building Science • Paulk Residence St.Johns,FL 32259 - Pane 5 Manual S Performance Data - System 1 - System 1 ii=Cooling Loads and Design Conditions Outdoor Dry Bulb: 92 Sensible Gain: 28,145 Outdoor Wet Bulb: 78 Latent Gain: 9,989 Indoor Dry Bulb: 75 Total Gain: 38,134 Indoor RH: 50 Load SHR: 0.74 Elevation: 16 Supply Airflow: 1,274 Elevation: 16 Supply Airflow: 1,274 Elevation: 16 Supply Airflow: 1,274 "Equipment Performance Data at System Design Conditions Air Source Heat Pump Model: CH14NB042""'A+FB4CNP042L, Nominal Capacity: 38,575 Entered Inter•olation Data:__ EDB B Air Flow ODB Total Power 75°F °F CFM °F Capacity Input Btuh kW S/T =Capacity I '' Btuh 85 39940 3.21 0.75 29951 62 95 37750 3.58 0.735 27761 i 1274 85 43510 3.18 0.77 33521 67 95 41000 3.57 0.756 31011 Interpolation Results: Percent Load of Load Sensible Capacity: 28,749 28,145 102% Latent Capacity: 9,989 9,989 100% Total Capacity: 38,738 38,134 102% Power Input: 3.52 Y:\2.1 BeeTree Homes\Paulk\load calc main house\Paulk Residence.rh9 Tuesday, May 31,2016, 11:11 AM