Loading...
395 12TH ST - ENERGY SHEETS , '3c 3 1 Z'-`i` �- 8� U OFFICE co Ek) cE tS ICC EVALUATION SERVICE 1. Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-1655 Reissued April 2014 This report is subject to renewal April 1, 2016. www.icc-es.org I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council- DIVISION: 07 00 00—THERMAL AND MOISTURE roofs. The foam plastic insulation is a two-component. PROTECTION open-cell,one-to-one by volume spray foam system with a Section: 07 21 00—Thermal Insulation nominal density of 0.5 pcf (8 kg/m3). The insulation REPORT HOLDER: is produced in the field by combining a polymeric isocyanate (A component) with a polymeric resin blend BAYER MATERIALSCIENCE LLC (B component). The insulation components have a shelf 2400 SPRING STUBNER ROAD life of six months when stored at temperatures between SPRING,TEXAS 77389 65°F(18°C)and 85'F(29'C)before installation. (800)221-3626 3.2 Surface-burning Characteristics: www.spf.bayermaterialscience.com The insulation, at a maximum thickness of 4 inches (102 mm)and a nominal density of 0.5 pcf(8 kg/m3), has a EVALUATION SUBJECT: flame spread index of less than 25 and a smoke-developed BAYSEALTM OC SPRAY-APPLIED POLYURETHANE index of less than 450 when tested in accordance with INSULATION ASTM E84. Thicknesses up to 12 inches(305 mm)for wall cavities and 16 inches (406 mm) for ceiling cavities are 1.0 EVALUATION SCOPE recognized based on room corner fire testing in Compliance with the following codes: accordance with NFPA 286, when covered with minimum 1/2-inch-thick (13 mm) gypsum board or an equivalent • 2012 and 2009 International Building Code• (IBC) thermal barrier complying with and installed in accordance ■ 2012 and 2009 International Residential Code (IRC) with the applicable code. • 2012 and 2009 International Energy Conservation 3.3 Thermal Resistance(R-values): Code (IECC) The insulation has thermal resistance(R-value), at a mean • Other Codes(see Section 8.0) temperature of 75'F(24°C), as shown in Table 1. Properties evaluated: 3.4 BaysealiN IC Coating: • Surface-burning characteristics BaysealTM IC intumescent coating is manufactured by • Physical properties Bayer MaterialScience and is a water-based latex coating with a specific gravity of 1.31. BaysealT"' IC is supplied in ■ Thermal resistance 5-gallon (19 L) pails and 55-gallon (208 L) drums and has • Attic and crawl space applications a shelf life of 12 months when stored in a factory-sealed • Fire-resistance-rated construction container at temperatures between 50°F(10°C)and 100°F (38°C) ■ Exterior walls in Types I through IV construction 3.5 Paint to Protect" DC315 Fireproof Paint: • Air permeability Paint to Protect DC 315 Fireproof Paint is manufactured 2.0 USES by International Fireproof Technology. Inc., and is a water- The BaysealTM OC insulation is used as a nonstructural based coating supplied in 5-gallon (19 L) pails and thermal insulating material in Type I, II, III, IV and V 55-gallon (208 L) drums. The coating material has a shelf construction (IBC) and dwellings under the IRC. See life of 24 months when stored in factory-sealed containers Section 4.5 for use in Type I, II, Ill and IV construction. The at temperatures between 50°F(10°C)and 90°F(32°C). insulation is for use in wall cavities, floor assemblies, 3.6 TPR2Fireshell" BMS-TC Intumescent Coating: ceiling assemblies or attics and crawl spaces when TPR` Fireshell BMS-TC Intumescent Coating is a one- installed in accordance with Section 4.3 The insulation component, water-based polymer coating. The coating is may be used in wall assemblies in fire-resistive-rated- supplied in 5 5-gallon (19 L construction as described in Sections 3.8 and 4.4. 9 ) pails and 55 gallon (208 L) drums and has a shelf life of one year when stored in a 3.0 DESCRIPTION factory-sealed container at temperatures of 50°F (10°C)or 3.1 General: above. Bayseal TM OC is a spray-applied cellular polyurethane 3.7 TPR Z Fireshell`''BMS-IC Intumescent Coating: foam plastic insulation that is installed t k.., �- i .\ rr=- h S-IC Intumescent Coating is a one- assemblies, ceilings, floors, crawlspaces a x) .� .., e e sed polymer coating. The coating is l('('-ES Evaluation Repo,tc are not to be construe,)as win esentarc v i s ora ,fmt, �n t.n 9p/A{�7 Uicabt td,F -.ed.nor are rho to h'Conant�i as an endorsement of the subject r f the report or a recommenJat,o, ae l Pikinu v,lirkinn•fi`7 E,oh r rce.LLC.express or rmphed.,r. tw! to ant finding or other matter In this report,or as to ant pru,itre1 qv ve the,rporf. .,f Copyright 0 2014 Page 1 of 4 SR-1655 I Most Widely Accepted and Trusted Page 2 of 5 upplied in 5-gallon (19 L) pails and 55-gallon (208 L) 22 wet mils (0.56 mm) [14 dry mils (0.36 mm)], at a rate of drums and has a shelf life of one year when stored in a 1.37 gallons (5.2L) per 100 square feet (9.2 m2). The factory-sealed container at temperatures of 50°F (10°C)or coating must be applied over the BaysealTM OC insulation above. in accordance with the coating manufacturer's instructions 3.8 Fire-resistance-rated Construction: and this report. Surfaces to be coated must be dry, clean and free of dirt, loose debris and other substances that BaysealT'" OC spray-applied foam insulation is recognized could interfere with adhesion of the coating. The coating is for use in a limited load-bearing, one-hour, fire-resistance- applied in one coat by airless spray equipment at ambient rated wall assembly when installed as described in temperatures above 50°F (10°C) and relative humidity of Section 4.4. less than 70 percent. 3.9 Air Permeability: 4.2.2.2 Application with TPR2 Fireshell BMS-TC BaysealT"' OC spray-applied polyurethane insulation, at a Intumescent Coating: The prescriptive 15-minute thermal minimum thickness of 3.5 inches (89 mm), is considered barrier may be omitted when installation is in accordance air-impermeable insulation in accordance with Sections with this section. The insulation and coating may be used R806 and R202 of the IRC based on testing in accordance in lieu of the code-prescribed 15-minute thermal barner. with ASTM E283. The foam plastic insulation thickness must not exceed 4.0 INSTALLATION 7'/2 inches (191 mm) in walls and 91/2 inches (241 mm) in ceilings, and the insulation must be covered with 20 wet 4.1 General: mils (0.5 mm) [12 dry mils (0.30 mm)] of TPR2 Fireshell'' BaysealT"' OC insulation must be installed in accordance BMS TC intumescent coating applied in a single coat at2a with the manufacturers published installation instructions rate of 1.25 gallons (4.75L) per 100 square feet (9.2 m ). and this report. A copy of the instructions must be available Surfaces to be coated must be dry, clean and free of dirt, at all times on the jobsite during installation. loose debris and other substances that could interfere with adhesion of the coating. The coating is applied in one coat The substrates to which the insulation is applied must be by airless spray equipment, medium knap roller or brush at clean, dry and free of frost, ice, loose debris, or ambient temperatures above 62°F and 95°F (16°C and contaminates that will interfere with adhesion of the spray 35°C)and relative humidity of less than 70 percent. 111 foam insulation. 4.3 Attics and Crawl Spaces: The insulation must be protected from the weather during and after application. The insulation must not be applied in 4.3.1 Application with a Prescriptive Ignition Barrier: electrical boxes. When BaysealT"' OC insulation is installed within attics or crawl spaces where entry is made only for service of The insulation is applied in passes having a maximum utilities, an ignition barrier must be installed in accordance thickness of 6 inches (152 mm) per pass. Multiple passes with IBC Section 2603.4.1.6 and IRC Sections R316.5.3 are made to obtain the desired thickness, which is not to and R316.5.4, as applicable. The ignition barrier must be exceed 12 inches(305 mm)for wall cavities and 16 inches consistent with the requirements for the type of (406 mm) for ceiling cavities. The insulation must not be construction required by the applicable code, and must be used in areas that have a maximum service temperature installed in a manner so that the foam plastic insulation is greater than 180°F (82°C). The foam plastic insulation not exposed BaysealT'" OC insulation, as described in this must not be used in electrical outlet or junction boxes or in section, may be installed in unvented attics in accordance contact with rain, water or soil. The substrate must be free with IRC Section R806. The attic or crawl space area must of moisture,frost or ice, loose scales, rust,oil and grease. be separated from the interior of the building by an 4.2 Thermal Barrier: approved 15-minute thermal barrier as described in Section 4.2.1. 4.2.1 Application with a Prescriptive Thermal Barrier: The BaysealTM OC insulation, with a maximum nominal 4.3.2 Application without a Prescriptive Ignition thickness of 12 inches (305 mm) for wall cavities and Barrier: Where the spray-applied insulation is installed in 16 inches(406 mm)for ceiling cavities, must be separated accordance with Sections 4.3.2.1, 4.3.2.2 or 4.3.2.3 the from the interior of the building by an approved thermal following conditions apply: barrier of 1/2-inch-thick (12.7 mm) gypsum wallboard or a) Entry to the attic or crawl space is to service utilities, an equivalent 15-minute thermal barrier complying with and no storage is permitted. and installed in accordance with the applicable code. b) There are no interconnected attic or crawl space areas. Exception: within an attic or crawl space, installation must be in accordance with Section 4.3. c) Air in the attic or crawl space is not circulated to other parts of the building. 4.2.2 Application without a Prescriptive Thermal Barrier: d) Attic ventilation is provided when required by IBC Section 1203.2 or IRC Section R806, except when air- 4.2.2.1 Application with Paint to Protect- DC-315 impermeable insulation is permitted in unvented attics intumescent Coating: The prescriptive 15-minute thermal in accordance with the 2012 IRC Section R806.5(2009 barrier may be omitted when installation is in accordance IRC Section R806.4). Under-floor (crawl space) with this section. The insulation and coating may be spray- ventilation is provided when required by IBC Section applied to the interior facing of walls, the underside of roof 1203.3 or IRC Section R408.1, as applicable. sheathing or roof rafters, and in crawl spaces, and may be e) Combustion air is provided in accordance with left exposed as an interior finish without a prescribed 15-minute thermal barrier or prescribed ignition barrier International Mechanical Code` Section 701 The thickness of the foam plastic applied to the underside 4.3.2.1 Application with Bayseal IC Intumescent of the roof sheathing must not exceed 11'/2 inches Coating: In attics BaysealTM OC insulation may be spray- (292 mm). The thickness of the foam plastic applied to applied to the underside of roof sheathing or roof rafters; vertical wall surfaces must not exceed 10 inches(254 mm). and in crawl spaces. Bayseal T'" OC insulation may be The foam plastic must be covered on all surfaces with DC spray-applied to the underside of floors as described in this 315 Fireproof Paint at a minimum wet film thickness of section. The thickness of the foam plastic applied to the FSR-1655 I Most Widely Accepted and Trusted Page 3 of 5 underside of the top space must not exceed 13 inches compound in accordance with ASTM C840 or GA216.The (406 mm). The thickness of the foam plastic applied to interior cavity is filled with BaysealTM OC spray applied vertical surfaces must not exceed 11'/4 inches (286 mm). foam insulation. All foam plastic surfaces must be covered with 7.5 wet mils Opposite Face: One layer of 5/ inch-thick 15.9 mm (0.2 mm) [4 dry mils (0.10 mm)] of the BaysealTM IC TypepX gypsum wallboardymust be applied in(the same intumescent coating described in Section 3.4. The manner as for the initial face. The horizontal joints in the BaysealTM IC intumescent coating must be applied over the BaysealTM OC insulation in accordance with the gypsum wallboard on the opposite face must be staggered manufacturers instructions and this report Surfaces to be a minimum of 8 inches (203 mm)from the horizontal joints ) coated must be dry, clean, and free of dirt, loose debris in the wallboard on the initial face. If the intention is for use and any other substances that could interfere with as an exterior wall, code complying sheathing and a code complying exterior wall covering must be installed in accordance with the applicable code. 4.4.2 Axial Load Design: Axial loads applied to the wall assembly must be limited to the lesser of the following: 1. 2,756 pounds(122 642 N)per stud. 2. A maximum of 51 adhesion of the coating. The BaysealT IC coating is applied with a medium-size nap roller, soft brush or conventional airless spray equipment at a rate of 0.5 gallon (1.9L) per 100 square feet (9.2 m2). The coating must be applied when ambient and substrate temperatures are above 50'F (10-C)and requires a 24-hour curing time after application. BaysealTM OC insulation, as described in thispercent of the load calculated in accordance with Sections 3.6 and 3.7 of the ANSI/AFBPA NDS. 4.5 Exterior Walls in Types I, II, Ill and IV Construction: section, may be installed in unvented conditioned attics in accordance with the 2009 IRC Section R806.4 or the 2012 IRC Section R806.5. The attic or crawl space area must be separated from the interior of the building by an approved 15 minute thermal barrier as described in Section 4.2.1. When used on exterior walls of Type I, II, Ill and IV 4.3.2.2 Application with TPR2 Fireshell'' BMS-IC construction, must comply with Section 2603.5 of the IBC Intumescent Coating: In attics. BaysealTM OC insulation and this section (Section 4.5), and the insulation must be may be spray-applied to the underside of roof rafters: and installed at a maximum thickness of 35/e inches (92 mm) in crawl spaces. BaysealT"' OC insulation may be spray- See Table 2 for a description. The potential heat of the applied to the underside of floors as described in this BaysealT"" OC spray-applied polyurethane insulation is 488 section. The thickness of the foam plastic applied to the Btu/ft2(5.5 MJ/m2)per inch of thickness. underside of the top space must not exceed 91/2 inches 5.0 CONDITIONS OF USE (241 mm). The thickness of the foam plastic applied to The BaysealT"' OC insulation described in this report vertical surfaces must not exceed 7 inches (178 mm). All foam plastic surfaces must be covered with the TPR2 complies with, or is a suitable alternative to what is Fireshell' BMS IC intumescent coating described in specified in, those codes listed in Section 1.0 of this report. Section 3.7. The intumescent coating must be applied over subject to the following conditions. the BaysealTM OC insulation in accordance with the 5.1 This evaluation report and the manufacturer's manufacturer's instructions and this report. The foam published installation instructions, when required by plastic insulation must be covered with 7 wet mils(0.2 mm) the code official, must be submitted at the time of [4 dry mils (0.10 mm)] of TPR2 Fireshell BMS-IC permit application. intumescent coating applied in a single coat at a rate of 5.2 BayseatTM OC insulation and BaysealT"" IC 0.83 gallon(1.10 L)per 100 square feet(9.2 m2). Surfaces intumescent coating must be installed in accordance to be coated must be dry, clean and free of dirt, loose with the manufacturer's published installation debris and other substances that could interfere with instructions, this report and the applicable code. The adhesion of the coating. The coating is applied in one coat instructions within this report govern if there are any by airless spray equipment, medium knap roller or brush at conflicts between the manufacturer's published ambient temperatures above 70°F (21°C) and relative installation instructions and this report. humidity of less than 70 percent, and requires a 24-hour 5.3 BaysealT"•' OC insulation must be separated from the curing time. The attic or crawl space area must be interior of the building by an approved 15 minute separated from the interior of the building by an approved thermal barrier, as described in Section 4.2.1, except 15-minute thermal barrier as described in Section 4.2.1. as noted in Section 4.2.2. 4.3.2.3 Use on Attic Floors: BaysealT"•' OC insulation 5.4 Bayseal TM OC insulation must be protected from the may be installed at a maximum thickness of 111/4 inches weather during and after application. (286 mm)between joists in attic floors. The insulation must be covered on all exposed surfaces with BaysealTM IC 5.5 BaysealTM OC insulation must be applied by installers intumescent coating as described in Section 4.3.2.1. The certified by Bayer MaterialScience LLC. BaysealT"" OC insulation must be separated from the area 5.6 When use is on buildings of Types I, II, Ill and IV beneath the attic by an approved thermal barrier. An construction, installation must be as described in ignition barrier in accordance with IBC Section 2603.4.1.6 Section 4.5 and Table 2. and IRC Section R316.5.3 may be omitted. 5.7 Use of BayseatTM OC insulation in areas where the 4.4 One-hour Fire-resistance-rated Wall Assembly probability of termite infestation is -very heavy- must (Limited Load-bearing): be in accordance with IBC Section 2603.8 or IRC 4.4.1 Initial Face: One layer of 5/8-inch-thick (15.9 mm) Section R318.4, as applicable.. Type X gypsum wallboard must be applied parallel to the 5.8 Jobsite certification and labeling of the insulation must interior face of 2-by-6 wood studs spaced a maximum of comply with IRC Sections N1101.4 and N1101.4.1 16 inches (406 mm) on center. The gypsum boards must and IECC Sections 303.1.1 and 303.1.2, as be attached using Type S, 15/8-inch-long (41 mm) screws applicable. spaced 8 inches (203 mm) on center. All exposed 5.9 In exterior wall applications, a vapor retarder may be wallboard joints must be taped with joint tape, and required by the code official in accordance with IBC compound and screw heads must be covered with joint Section 1405.3 or IRC Section R601.3,as applicable. SSR-1655 I Most Widely Accepted and Trusted Page 4 of 5 • 5.10 BaysealTM" OC insulation is produced in Phoenix. • 2006 International Residential Codes(2006 IRC) Arizona and Spring, Texas, under a quality control • 2006 International Energy Conservation Code' (2006 program with inspections by ICC-ES. IECC) 6.0 EVIDENCE SUBMITTED The products comply with the above-mentioned codes as 6.1 Data in accordance with the ICC-ES Acceptance described in Sections 2.0 through 7.0 of this report, except Criteria for Spray-applied Foam Plastic Insulation as noted below: (AC377), dated June 2012, including reports of tests • Application with a Prescriptive Thermal Barrier: see in accordance with Appendix X of AC377. Section 4.2.1. except the approved thermal barrier must 6.2 Reports of room corner tests in accordance with be installed in accordance with Section R314.4 of the NFPA 286. 2006 IRC. 6.3 Report of air leakage testing in accordance with • Application without a Prescriptive Thermal Barrier: ASTM E283. See Section 4.2.2. 6.4 Report of testing in accordance with ASTM E119. • Application with a Prescriptive Ignition Barrier: See 6.5 Report of potential heat of foam plastic testing in Section 4.3.1 except attics must be vented in accordance with NFPA 259. accordance with Section 1203.2 of the IBC or Section R806 of the IRC, and crawl space ventilation must be in 6.6 Report of fire propagation characteristics testing in accordance with IBC Section 1203.3 or IRC Section accordance with NFPA 285. R408.as applicable. 7.0 IDENTIFICATION ■ Application without a Prescriptive Ignition Barrier: Components for Bayseal'M OC insulation are identified See Section 4.3.2, except attics must be vented in with the manufacturer's name (Bayer MaterialScience, accordance with Section 1203.2 of the IBC or Section LLC), address and telephone number: the product trade R806 of the IRC. and crawl space ventilation must be in name (BaysealTM" OC); product type (A or B component); accordance with IBC Section 1203.3 or IRC Section use instructions; the density; the flame-spread and smoke- R408, as applicable and combustion air is provided in developed indices;the evaluation report number(ESR 1655); accordance with 2006 International Mechanical Code' Sections 701 and 703 Intumescent coatings are identified with the ■ Protection Against Termites: See Section 5.7, except manufacturer's name and address, the product name and use of the insulation in areas where the probability of use instructions. termite infestation is "very heavy" must be in 8.0 OTHER CODES accordance with Section R320.5 of the 2006 IRC. In addition to the codes referenced in Section 1.0. the • Jobsite Certification and Labeling: See Section 5.8, products described in this report were evaluated for except jobsite certification and labeling must comply compliance with the requirements of the following codes: with Sections 102.1.1 and 102.1.1.q, as applicable, of the 2006 IECC. • 2006 International Building Code'(2006 IBC) TABLE 1-THERMAL RESISTANCE(R-VALUES) THICKNESS(inches) R-VALUE(°F.ft2.h/Btu) 1 3.7 2 7.4 3 11 3.5 13 4 15 5 18 5.5 20 6 22 7 25 7.75 27 8 28 9 32 10 35 11 39 12 42 13 46 14 50 15 53 16 56 For SI: 1 inch=25.4 mm:1°F.ft2.h/Btu=0.176 110 k.mzlW. 'Calculated R-values are based on tested K-values at 1-and 3.5-inch thicknesses. 1R-values greater than 10 are rounded to the nearest whole number. ESR-1655 I Most Widely Accepted and Trusted Page 5 of 5 TABLE 2—NFPA 285 COMPLYING EXTERIOR V.ALL ASSEMBLIES IN TYPES I,II,III AND IV CONSTRUCTION WALL COMPONENT MATERIALS 1 -Concrete wall 2-Concrete masonry wall 3-1 layer./;.inch-thick Type X gypsum wallboard complying with ASTM C36 or C1396 on interior. Base Wall System- installed over steel studs,minimum 3•/ inch deep.No 20 gage.C-shaped,spaced a maximum of Use either 1.2 or 3 24 inches on center Gypsum wallboard must be attached with No.6. 1'/:-inch-long self-tapping screws located 8 inches on center along the perimeter and in the field of wallboard. Gypsum wallboard joints must be taped and treated with joint compound in accordance with ASTM C840 or GA-216. Floorline Firestopping 4 pcf mineral wool(e g.Thermafiber)in each stud cavity at each floorline attached with Z-clips 1 -None Cavity Insulation- 2-Full cavity depth or less of Bayseal`"OC insulation applied using exterior sheathing as substrate Use either 1 or 2 or 3 and covering the width of the cavity and inside the stud flange 3-Fiberglass batt insulation(faced or unlaced) Exterior Sheathing-Only for Base • Wall System No 3 1 --I-inch-thick.exterior type gypsum sheathing Use either 1 or 2 2-`/E-inch-thick.exterior type gypsum sheathing 1 -Brick-standard nominal 4-inch-thick clay brick -Brick veneer anchors-standard types installed a maximum of 24 inches OC vertically on each stud Exterior Wall covering- -Maximum 2 inch air gap between exterior insulation and brick Use either 1 or 2 2-Stucco-minimum /4--inch-thick.exterior cement plaster and lath.A secondary water-resistive barrier may be installed between the exterior insulation and the lath The secondary water-resistive barrier must not be full-coverage asphalt or butyl-based self-adhered membranes For SI: 1 inch=25.5 mm; 1 pcf= 16.018 kg/m' OFFICE COPY FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: 395 12TH ST Builder Name: Marco Heating&Air Inc Street: 395 12TH STREET Permit Office: DUVAL CNTY City,State,Zip: ATLANTIC BEACH,FL,32233 Permit Number: Owner: MATHIEU BUILDERS Jurisdiction: 261300 Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types(3551.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3551.00 ft2 b.N/A R= ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft2 10.Ceiling Types (3432.0 sqft.) Insulation Area 5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 2024.00 ft2 6. Conditioned floor area above grade(ft2) 3549 b.Cathedral/Single Assembly(Unvented)R=0.1 1408.00 ft2 Conditioned floor area below grade(ft2) 0 c.N/A R= ft2 11.Ducts R ft2 7. Windows(514.6 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 8 276 a. U-Factor: Dbl,U=0.32 514.58 ft2 b.Sup: Attic,Ret:Attic,AH:GREAT RM 8 434 SHGC: SHGC=0.29 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 18.0 SEER:15.00 b.Central Unit 38.5 SEER:15.00 c. U-Factor: N/A ft' SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 18.0 HSPF:8.50 SHGC: b.Electric Heat Pump 38.5 HSPF:9.00 Area Weighted Average Overhang Depth: 2.000 ft. Area Weighted Average SHGC: 0.290 14.Hot water systems a.Propane Tankless Cap: 1 gallons 8. Floor Types (3549.0 sqft.) Insulation Area EF:0.800 a.Slab-On-Grade Edge Insulation R=0.0 3083.00 ft2 b. Conservation features b.Floor over Garage R=0.0 349.00 ft2 None c.other(see details) R= 117.00 ft2 15.Credits Pstat Total Proposed Modified Loads: 79.79 Glass/Floor Area: 0.145 PASS Total Baseline Loads: 85.06 il I hereby certify that the plans and specifications covered by Review of the plans and .,•.*.- CNE sTgl�.,,. this calculation are in compliance with the Florida Energy specifications covered by this ti•,;'. ..:0#,':AS: Code. ctl:CA tlDrr.C•SS.0U=v.mn�npaAA calculation indicates compliance r c %/„ t O•"YrmNWp•N.Nc'.E -. ��'. Dorothy Deane ,'�^�^ a�^^�^-° with the Florida Energy Code. :' ::r ";'' 3 O': PREPARED BY: °"`20t6O6t01B9 34 Before construction is completed i this building will be inspected for ?0'•; _0 :,�i DATE: compliance with Section 553.908 •`.. I hereby certify that this building,as designed, is in compliance Florida Statutes. ' �;C.. with the Florida Energy Code. • OD WEA.• OWNER/AGENT:_ 2 // co'- BUILDING OFFICIAL: //11- _ ' DATE: DATE: V 6* G l 6 - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 7 FORM R405-2014 PROJECT Title: 395 12TH ST Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 3549 Lot# Owner: MATHIEU BUILDERS Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Marco Heating&Air Inc Rotate Angle: 270 Street: 395 12TH STREET Permit Office: DUVAL CNTY Cross Ventilation: No County: Duval Jurisdiction: 261300 Whole House Fan: No City,State,Zip: ATLANTIC BEACH, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE V Design Location TMY SiteIECC Design Temp Int Design Temp Heating Design Daily Temp Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL JACKSONVILLE INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 2 TON 1379 11981 2 4 TON 2170 19923 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 MST BD&BATH 422 3798 No 2 1 1 Yes Yes Yes 2 MST WIC 219 1971 No 0 1 Yes Yes Yes 3 LAUNDRY 144 1296 No 0 1 No Yes Yes 4 BONUS 466 3728 No 0 1 Yes Yes Yes 5 STAIRS 92 828 No 0 1 Yes Yes Yes 6 POWDER 36 360 No 0 1 No Yes Yes 7 FRONT 393 3930 No 0 1 Yes Yes Yes 8 B3 226 2034 No 1 1 1 Yes Yes Yes 9 MST HALL 63 567 No 0 1 Yes Yes Yes 10 BTH 1 105 945 No 0 1 Yes Yes Yes 11 B1 180 1620 No 1 1 1 Yes Yes Yes 12 BTH 3/WIC 85 765 No 0 1 Yes Yes Yes 13 BTH2/WIC 85 765 No 0 1 Yes Yes Yes 14 B2 143 1287 No 1 1 1 Yes Yes Yes 15 KITCHEN 190 1710 Yes 0 1 Yes Yes Yes 16 HALL 263 2367 No 0 1 No Yes Yes 17 GREAT RM 437 3933 No 0 1 Yes Yes Yes 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 7 FORM R405-2014 FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge lnsulatio MST BD&BATH 70 ft 0 422 ft2 ___ 0.2 0.2 0.6 2 Slab-On-Grade Edge Insulatio MST WIC 15 ft 0 219 ft2 ____ 0.2 0.2 0.6 3 Slab-On-Grade Edge Insulatio LAUNDRY 1 ft 0 144 ft2 ____ 0.2 0.2 0.6 4 Floor over Garage BONUS ___ ___ 349 ft2 0 0.2 0.2 0.6 5 Slab-On-Grade Edge Insulatio STAIRS 13 ft 0 92 ft2 ____ 0.2 0.2 0.6 . 6 Slab-On-Grade Edge Insulatio POWDER 1 ft 0 36 ft2 ____ 0.2 0.2 0.6 7 Slab-On-Grade Edge Insulatio FRONT 41 ft 0 393 ft2 ____ 0.2 0.2 0.6 8 Slab-On-Grade Edge Insulatio B3 38 ft 0 226 ft2 ---- 0.2 0.2 0.6 9 Slab-On-Grade Edge Insulatio MST HALL 16 ft 0 63 ft2 ___ 0.2 0.2 0.6 10Slab-On-Grade Edge Insulatio BTH 1 29 ft 0 105 ft2 ____ 0.2 0.2 0.6 11Slab-On-Grade Edge Insulatio B1 14 ft 0 180 ft2 ____ 0.2 0.2 0.6 12SIab On-Grade Edge Insulatio BTH 3/WIC 11 ft 0 85 ft2 ___ 0.2 0.2 0.6 13Slab-On-Grade Edge lnsulatio BTH2/WIC 5 ft 0 85 ft2 ___ 0.2 0.2 0.6 14Slab-On-Grade Edge Insulatio B2 16 ft 0 143 ft2 ____ 0.2 0.2 0.6 15SIab-On-Grade Edge Insulatio KITCHEN 3 ft 0 190 ft2 ____ 0.2 0.2 0.6 16Slab-On-Grade Edge Insulatio HALL 1 ft 0 263 ft2 ___ 0.2 0.2 0.6 17SIab-On-Grade Edge Insulatio GREAT RM 23 ft 0 437 ft2 ___ 0.2 0.2 0.6 18FIoor Over Other Space BONUS ____ ____ 117 ft2 0 0.2 0.2 0.6 .ME. - - ice. ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 4126 ft2 0 ft2 Medium 0.9 No 0.9 No 20 33.7 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 3433 ft2 N N 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 7 ' FORM R405-2014 CEILING V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Cathedral/Single Assembly(UnVAASsi:IBD&BATH 0.1 Blown 422 ft2 0.1 Wood 2 Under Attic(Unvented) MST WIC 0.1 Blown 219 ft2 0.1 Wood 3 Under Attic(Unvented) LAUNDRY 0.1 Blown 48 ft2 0.1 Wood 4 Under Attic(Unvented) BONUS 0.1 Blown 445 ft2 0.1 Wood 5 Under Attic(Unvented) STAIRS 0.1 Blown 92 ft2 0.1 Wood 6 Under Attic(Unvented) POWDER 0.1 Blown 36 ft2 0.1 Wood 7 Under Attic(Unvented) FRONT 0.1 Blown 393 ft2 0.1 Wood 8 Cathedral/Single Assembly(Unvented B3 0.1 Blown 226 ft2 0.1 Wood 9 Under Attic(Unvented) MST HALL 0.1 Blown 63 ft2 0.1 Wood 10 Under Attic(Unvented) BTH 1 0.1 Blown 105 ft2 0.1 Wood 11 Cathedral/Single Assembly(Unvented B1 0.1 Blown 180 ft2 0.1 Wood 12 Under Attic(Unvented) BTH 3/WIC 0.1 Blown 85 ft2 0.1 Wood 13 Under Attic(Unvented) BTH2/WIC 0.1 Blown 85 ft2 0.1 Wood 14 Cathedral/Single Assembly(Unvented B2 0.1 Blown 143 ft2 0.1 Wood 15 Under Attic(Unvented) KITCHEN 0.1 Blown 190 ft2 0.1 Wood 16 Under Attic(Unvented) HALL 0.1 Blown 263 ft2 0.1 Wood 17 Cathedral/Single Assembly(UnventtaREAT RM 0.1 Blown 437 ft2 0.1 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below V# Omt To Wall Type Space R-Value Ft In Ft In Area R-Value Fraction Absor. Grade% 1 N=>W Exterior Frame-Wood MST BD&B 19 21 0 9 0 189.0 ft2 0 0.23 0.4 0 2 E=>N Exterior Frame-Wood MST BD&B 19 19 0 9 0 171.0 ft2 0 0.23 0.4 0 3 S=>E Exterior Frame-Wood MST BD&B 19 4 0 9 0 36.0 ft2 0 0.23 0.4 0 4 W=>S Exterior Frame-Wood MST BD&B 19 26 0 9 0 234.0 ft2 0 0.23 0.4 0 5 W=>S Exterior Frame-Wood MST WIC 19 15 0 9 0 135.0 ft2 0 0.23 0.4 0 6 N=>W Exterior Frame-Wood BONUS 19 30 0 8 0 240.0 ft2 0 0.23 0.4 0 7 E=>N Exterior Frame-Wood BONUS 19 24 0 8 0 192.0 ft2 0 0.23 0.4 0 8 S=>E Exterior Frame-Wood BONUS 19 30 0 8 0 240.0 ft2 0 0.23 0.4 0 9 W=>S Exterior Frame-Wood BONUS 19 24 0 8 0 192.0 ft2 0 0.23 0.4 0 10 N=>W Exterior Frame-Wood STAIRS 19 5 0 9 0 45.0 ft2 0 0.23 0.4 0 11 W=>S Exterior Frame-Wood STAIRS 19 8 0 9 0 72.0 ft2 0 0.23 0.4 0 12 E=>N Exterior Frame-Wood FRONT 19 6 0 10 0 60.0 ft2 0 0.23 0.4 0 13 S=>E Exterior Frame-Wood FRONT 19 32 0 10 0 320.0 ft2 0 0.23 0.4 0 14 W=>S Exterior Frame-Wood FRONT 19 3 0 10 0 30.0 ft2 0 0.23 0.4 0 15 E=>N Exterior Frame-Wood B3 19 14 0 9 0 126.0 ft2 0 0.23 0.4 0 16 S=>E Exterior Frame-Wood 83 19 15 0 9 0 135.0 ft2 0 0.23 0.4 0 17 W=>S Exterior Frame-Wood 83 19 9 0 9 0 81.0 ft2 0 0.23 0.4 0 18 N=>W Exterior Frame-Wood MST HALL 19 7 0 9 0 63.0 ft2 0 0.23 0.4 0 19 E=>N Exterior Frame-Wood MST HALL 19 9 0 9 0 81.0 ft2 0 0.23 0.4 0 20 N=>W Exterior Frame-Wood BTH 1 19 15 0 9 0 135.0 ft2 0 0.23 0.4 0 21 E=>N Exterior Frame-Wood BTH 1 19 7 0 9 0 63.0 ft2 0 0.23 0.4 0 22 W=>S Exterior Frame-Wood BTH 1 19 7 0 9 0 63.0 ft2 0 0.23 0.4 0 23 E=>N Exterior Frame-Wood B1 19 12 0 9 0 108.0 ft2 0 0.23 0.4 0 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 7 • FORM R405-2014 WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below # Omt To Wall Type Space R-Value Ft In Ft In Area R-Value Fraction Absor. Grade% _24 W=>S Exterior Frame-Wood B1 19 2 0 9 0 18.0 ft2 0 0.23 0.4 0 _25 E=>N Exterior Frame-Wood BTH 3/WIC 19 5 0 9 0 45.0 ft2 0 0.23 0.4 0 _26 S=>E Exterior Frame-Wood BTH 3/WIC 19 6 0 9 0 54.0 ft2 0 0.23 0.4 0 27 E=>N Exterior Frame-Wood BTH2/WIC 19 5 0 9 0 45.0 ft2 0 0.23 0.4 0 _28 N=>W Exterior Frame-Wood B2 19 5 0 9 0 45.0 ft2 0 0.23 0.4 0 29 E=>N Exterior Frame-Wood B2 19 11 0 9 0 99.0 ft2 0 0.23 0.4 0 30 N=>W Exterior Frame-Wood KITCHEN 19 3 0 9 0 27.0 ft2 0 0.23 0.4 0 31 N=>W Exterior Frame-Wood GREAT RM 19 23 0 9 0 207.0 ft2 0 0.23 0.4 0 DOORS # Omt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 W=>S Insulated BTH 1 None .35 2 8 8 21.3 ft2 WINDOWS Orientation shown is the entered orientation(=>)changed to As Built(rotated 270 degrees). Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N=>W 1 Vinyl Low-E Double Yes 0.32 0.29 10.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 2 E=>N 2 Vinyl Low-E Double Yes 0.32 0.29 12.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 3 E=>N 2 Vinyl Low-E Double Yes 0.32 0.29 16.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 4 E=>N 2 Vinyl Low-E Double Yes 0.32 0.29 16.5 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 5 W=>S 4 Vinyl Low-E Double Yes 0.32 0.29 33.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 6 S=>E 8 Metal Double(Clear) Yes 0.32 0.29 15.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 7 W=>S 9 Metal Double(Clear) Yes 0.32 0.29 18.3 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 8 W=>S 11 Vinyl Low-E Double Yes 0.32 0.29 16.5 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 9 S=>E 13 Vinyl Low-E Double Yes 0.32 0.29 12.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 10 S=>E 13 Vinyl Low-E Double Yes 0.32 0.29 33.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 11 S=>E 16 Vinyl Low-E Double Yes 0.32 0.29 33.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 12 E=>N 19 Vinyl Low-E Double Yes 0.32 0.29 20.7 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 13 E=>N 19 Vinyl Low-E Double Yes 0.32 0.29 11.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 14 N=>W 20 Vinyl Low-E Double Yes 0.32 0.29 10.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 15 E=>N 23 Vinyl Low-E Double Yes 0.32 0.29 16.5 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 16 E=>N 25 Vinyl Low-E Double Yes 0.32 0.29 10.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 17 E=>N 27 Vinyl Low-E Double Yes 0.32 0.29 10.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 18 N=>W 28 Vinyl Low-E Double Yes 0.32 0.29 16.5 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 19 E=>N 29 Vinyl Low-E Double Yes 0.32 0.29 16.5 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 20 N=>W 30 Vinyl Low-E Double Yes 0.32 0.29 13.8 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 21 N=>W 31 Vinyl Low-E Double Yes 0.32 0.29 33.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 22 N=>W 31 Vinyl Low-E Double Yes 0.32 0.29 96.0 ft2 2 ft 0 in 2 ft 0 in None Exterior 5 23 S=>E 13 Vinyl Low-E Double Yes 0.32 0.29 24.0 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds None 24 E=>N 2 Vinyl Low-E Double Yes 0.32 0.29 21.3 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds None 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 7 FORM R405-2014 GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 678 ft2 678 ft2 64 ft 9 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACI-I(50) .000286 2658.7 145.96 274.49 .2707 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump Split HSPF:8.5 18 kBtu/hr 1 sys#1 2 Electric Heat Pump Split HSPF:9 38.5 kBtu/hr 2 sys#2 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit Split SEER: 15 18 kBtu/hr 540 cfm 0.7 1 sys#1 2 Central Unit Split SEER: 15 38.5 kBtu/hr 1155 cfm 0.7 2 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Propane Tankless Exterior 0.8 1 gal 55.1 gal 120 deg None 2 Propane Tankless Exterior 0.8 1 gal 55.1 gal 120 deg None SOLAR HOT WATER SYSTEM VFSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS V —Supply-- —Return--- Air CFM 25 CFM25 HVAC# # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 8 276 ft2 Attic 69 ft2 Default Leakage Attic (Default) (Default) 1 1 2 Attic 8 434 ft2 Attic 109 ft2 Default Leakage GREAT RM (Default) (Default) 2 2 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 6 of 7 FORM R405-2014 TEMPERATURES Programable Thermostat:Y Ceiling Fans: CoolingJan ( Feb r Mar A r r[ Ma fX Jun r[Xj Jul r[X Au ((X]Se Oct r 1 Nov Dec HeatinX Jan X Feb EX Mar Apr l Ma [ Jun l J Jul l Aul i SeOct [X)Nov X Dec VentingJan [[ Feb X'lMar X Apr [ May [ Jun [ Jul [ Aug [ ]SepX Oct [X]Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 7 of 7 ' FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 94 The lower the EnergyPerformance Index, the more efficient the home. 395 12TH STREET, ATLANTIC BEACH, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area a.Frame-Wood,Exterior R=19.0 3551.00 ft2 2. Single family or multiple family Single-family b.N/A R= ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area a.Roof Deck(Unvented) R=20.0 2024.00 ft2 6. Conditioned floor area(ft2) 3549 b.Cathedral/Single Assembly(Unvented)R=0.1 1408.00 ft2 7. Windows" Description Area c.N/A R= ft2 a. U-Factor: Dbl,U=0.32 514.58 ft2 11•Ducts R ft2 a.Sup:Attic,Ret:Attic,AH:Attic 8 276 SHGC: SHGC=0.29 b.Sup: Attic,Ret:Attic,AH:GREAT RM 8 434 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 18.0 SEER:15.00 SHGC: b.Central Unit 38.5 SEER:15.00 d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 18.0 HSPF:8.50 Area Weighted Average Overhang Depth: 2.000 ft. b.Electric Heat Pump 38.5 HSPF:9.00 Area Weighted Average SHGC: 0.290 8. Floor Types Insulation Area 14.Hot water systems Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 3083.00 ft2 a.Propane EF:0.8 b.Floor over Garage R=0.0 349.00 ft2 c.other(see details) R= 117.00 ft2 b. Conservation features None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building ................. '•"R ;:Building ... srgr�..- Construction through the above energy saving features which will be installed (or exceeded) , I. ; -........04:;• in this home before final inspection. Otherwise, a new EPL Display Card will be completed =y ,, `' ,..,z• s+ based on installed Co mpliant features. ` _'„ •°,.3•,ro Builder Signature ,��Z,�-z•_ Date: ��a0l.� ' �_r,yam+a Address of New Home:3 ? 72t S,L City/FL Zip: W t/„/,, StcL\.4 •••v ;:• re_ 3zz3� *Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient mortgage (EEM)incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405 2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS. Permit Number. Jackso'rvi'.le,FL, MANDATORY�/ REQUIREMENTS See individual code sections for full details. /- 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law (Section 553.9085,Flonda Statues)requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall venly that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through 8402.4.4. R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the critena listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved thud party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written repos of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors.fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures: 3.Interior doors,if instated at the time of the test,shall be open: 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6.Supply and return registers,if installed al the time of the lest,shall be fully open. P R402.4.2 Fireplaces.New wood-burning fireplaces shall have tightfitting flue dampers and outdoor combustion air. j8402.4.3 Fenestration air leakage.Windows.skylights and sliding glass doors shall have an air infiltration rate of nomore than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square lool(2.6 Us/m2),when tested according to NFRC 400 or AAMA)W DMNCSA 101/I.S.2JA440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. N R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psi(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. Ar; R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls / that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. // R403.2.2 Sealing(Mandatory)All ducts.air handlers.and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.2.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct lightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99.Florida Statutes,or as authorized by Florida Statutes,to be'substantially leak free-by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential 01 0.1 inches w.g.(25Pa)across the system.including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test.If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage lest is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory ton buildings complying by Section R405 of this code. 7/2112015 11:t8 AM EnergyGauge4D USA-FlaRes2014 -Section R405.4.1 Com Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS- (Continued) R403.2.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design air flow rate when tested in accordance with ASHRAE 193. R403.2.3 Building Cavities(Mandatory).Building framing cavities shall not be used as ducts or plenums. /- R403.3 Mechanical system piping insulation(Mandatory). Mechanical system pipng capable of carrying fluids above 105'P(41'C) or below 55'F(13'0)shall be insulated to a minimum of R-3., 0 R403.3.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight,moisture,equipment maintenance-and wind.and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. yd R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heal traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 i%:inches(89 mm)in the hot water distribution tine and cold water line located as close as possible to the storage lank. R403.4.4 Water heater efficiencies(Mandatory). Water heater efficiencies R403.4.4.1 Storage water heater temperature controls • R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100"F to t 40'F(38'C to 60"C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Flonda Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water healing category. Solar water heaters shall met the criteria Section R403.4.4.2.1. ▪ R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy tactor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors. and SRCC Standard TM-1.Solar Domestic Hol Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an Orientation within 45 degrees of true south. / R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable.or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. 0" R403.5.1 Whole-house mechanical ventilation system fan efficacy. Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1. Exception:Where mechanical ventilation tans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. R403.5.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums nor residential buildings m ASHRAE 62,Ventilation for Acceptable Indoor Air Quality. shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioned system make air shall be provided to conditioned space from attics,crawlspaces,attached closed garages or outdoor spaces adjacent to swimming pools or spas. 3- If ventilation air is drawn from enclosed spaces(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19,space permitting,or R-10 otherwise. „( R403.6.HeatIng and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. �+ f°/ 8403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies. based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 7/21/2015 11:18 AM EnergyGauge®USA-FlaRes2014 .Section R405.4.1 Corn Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS- (Continued) • R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shad be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower ctm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gams if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its coding capacity is loss than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. Y 11403.6.1.2 Heating equipment capacity • R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. • 11403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. • 11403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmosphenc burners shall not be less than the design load calculated in accordance with Section 11403.6.1. 7 R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis.such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance dunng base load periods is utilized. • R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ 11403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems.supplied through energy service to the building,shall include automatic controls capable of shutt,ng oft the system when the pavement temperature is above 55'F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. • R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSIfAPSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O 11403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-oft switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters tired by natural gas or LP gas shall not have continuously burning pilot lights. ▪ R403.9.1.2 Heat pump pool heaters. Heal pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160.Table 2.Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. o R403.9.2 Time switches. Time switches or other control method that can automatically turn oft and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps.Heaters-pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • I. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3 Where pumps are powered exclusively from on-site renewable generation. o 11403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or solar energy source computed over an operating season. 1111404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be h.gh-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. X% 11404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights R405.2 erformance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. /R405.2.1 Performance ONLY. Ceilings shaH have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sutticent space,R-10 is allowed. 7/21/2015 11:18 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: 395 12TH ST Builder Name: Marco Heating&Air Inc Street: 395 12TH STREET Permit Office: DUVAL CNTY City.State,Zip: ATLANTIC BEACH ,FL,32233 Permit Number: Owner: MATHIEU BUILDERS Jurisdiction: 261300 Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 6/10/2016 3:43 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 • FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Envelope Leakage Test Report Prescriptive and Performance Method Project Name: 395 12TH ST Builder Name: Marco Heating&Air Inc Street: 395 12TH STREET Permit Office: DUVAL CNTY City,State,Zip: ATLANTIC BEACH,FL,32233 Permit Number: Design Location: FL,Jacksonville Jurisdiction: 261300 Cond.Floor Area:: 3549 sq.ft. Cond.Volume: 31904 cu ft. Envelope Leakage Test Results Leakage Characteristics Regression Data: C: n: R: CFM(50): Single or Multi Point Test Data HOUSE PRESSURE FLOW: ELA: EqLA: ACH: ACH(50): SLA: R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3. Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6.Supply and return registers,if installed at the time of the test,shall be fully open. I hereby certify that the above envelope leakage Where required by the code official, -cm STgj -•., performance results demonstrate compliance testing shall be conducted by an ; ;•:�,o with Florida Energy Code requirements in approved third party.A written " < i accordance with Section R402.4.1.2. report of the results of the test shall be signed by the third party c4 � � 11 conducting the test and provided to °.. C a SIGNATOR +� the code official. *r ' �. � ��,.. ."5 y PRINTED NAME: 45,/,„ �'dw BUILDING OFFICIAL: DATE: /,6/76 DATE: 6/10/2016 3:44 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 • Building Analysis Job: 395 12TH STREET . 4 wrightsoft Date: MAY 3,2016 9 Entire House By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating & Air Inc 720 MITI Creek Rd,Jacksonville,FL 32211 Phone:904-743-3350 Fax:904-743-4427 License:CAC1815711 Pro'ect Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET,ATLANTIC BEACH, FL 32233 Phone:904-268-2845 Desi•n Conditions Location: Indoor: Heating Cooling Jacksonville Intl AP, FL, US Indoor temperature(°F) 5 Elevation: 33 ft Design TD(°F) 38 18 Latitude: 30°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 11.0 51.2 Dry bulb(°F) 33 93 Infiltration: Daily range(°F) - 18 ( M ) Method Simplified Wetbulb(°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heatin• Component Btu h/ft2 Btuh %of load Walls 2.7 9264 17.7 v. °" Glazing 12.0 5633 10.8 Doors 14.6 975 1.9 Ceilings 2.1 7298 14.0 Floors 3.9 13235 25.3 Infiltration 1.7 6134 11.7 • Ducts 9744 18.6 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 52283 100.0 Coolin• Component Btuh/ft2 Btuh %of load Walls 1.4 4982 10.9 Was Internal Gates Glazing 21.8 10210 22.3 Doors 11.8 785 1.7 Ceilings 1.6 5390 11.8 Floors 0.0 106 0.2 Glanng - Infiltration 0.4 1551 3.4 Ducts 13478 29.4 Ventilation 0 0 Internal gains 9350 20.4 a Blower 0 0 Or Duds Adjustments 0 Ceilings Total 45852 100.0 Infieratan Latent Cooling Load=8933 Btuh Overall U-value=0.201 Btuh/ft2-°F Data entries checked. ft2016-Jun-10 14:59:46 wri htso Right-Suite®Universal 2017 17.0.01 RSU17889 Page 1 ..PS\RIGHTJ\MISC\MATHIEU BUILDERS1395 12TH ST.rup Calc=MJ8 Front Door faces: E t' wrightsoft Right-J® Worksheet Job: 395 12TH STREET Entire House Date: MAY 3,2016 By: MARCO HEATING AND AIR Marco Heating & Air Inc Plan : CUSTOM 720 Mil Creek Rd.Jacksonville,FL 32211 Phone.904-743-3350 Fax:904-743-4427 License:CAC1815711 1 Room name Entire House 1.5 TON 2 Exposed wall 406.0 ft 210.0 ft 3 Room height 9.0 ft 8.7 ft 4 Room dimensions 5 Room area 3549.0 f t' 1379.0 ft' I I I I I I Ty Construction U-value OriHTM Area (ft') Load Area (ft') Load number (Btuh/ft'-°F (Btuh/fI') I or perimeter (ft) I (Btuh) I or perimeter (ft) (Btuh) Heat I Cool I Gross I N/P/S I Heat Cool I Gross I NIP/S Heat I Cool 1 6 12E-Osw 0.068 n 2.55 1.43 825 736 1876 1056 633 565 1441 811 1Dc2om 0.320 n 12.00 10.51 19 0 222 194 19 0 222 194 4A4-2ov 0.320 n 12.00 10.51 50 0 594 520 50 0 594 520 D 1100 0.390 n 14.62 11.78 21 21 312 251 0 0 0 0 11 W 12E-Osw 0.068 e 2.55 1.43 967 788 2009 1130 490 480 1224 689 -G 4A4-2ov 0.320 e 12.00 30.13 20 0 240 603 10 0 120 301 -G 4A4-2ov 0.320 e 12.00 30.13 14 0 165 414 0 0 0 0 -G 4A4-2ov 0.320 e 12.00 30.13 50 0 594 1491 0 0 0 0 G 4A4-2ovd 0.320 e 12.00 30.13 96 0 1152 2893 0 0 0 0 12E-Osw 0.068 s 2.55 1.43 990 840 2141 1205 363 297 758 , 426 10D-v 0.320 s 12.00 7.36 21 21 248 152 0 0 0 0 4A4-2ov 0.320 s 12.00 10.51 20 20 240 210 0 0 0 0 4A4-2ov 0.320 s 12.00 10.51 12 12 144 126 12 12 144 126 4A4-2ov 0.320 s 12.00 10.51 16 16 192 168 16 16 192 168 4A4-2ov 0.320 s 12.00 10.51 11 11 132 116 0 0 0 0 4A4-2ov 0.320 s 12.00 10.51 50 50 594 520 17 17 198 173 • 11D0 0.390 s 14.62 11.78 21 21 312 251 21 21 312 251 12E-Osw 0.068 w 2.55 1.43 801 684 1744 981 292 277 706 397 1D-c2om 0.320 w 12.00 30.13 15 0 180 452 15 0 180 452 4A4-2ov 0.320 w 12.00 30.13 12 0 144 362 0 0 0 0 4A4-2ov 0.320 w 12.00 30.13 66 0 792 1989 0 0 0 0 D 11 DO 0.390 w 14.62 11.78 24 24 351 283 0 0 0 0 P 12C-Osw 0.091 - 3.41 1.39 438 438 1495 610 378 378 1290 526 C 16X19-0ad 0.408 - 2.12 1.57 3437 3437 7298 5390 1267 1267 2690 1987 F 19C-19cscp 0.049 - 0.64 0.30 354 354 225 106 354 354 225 106 F 22A-tpm 1.180 - 44.25 0.00 3083 294 13009 0 913 98 4336 0 6 I c)AED excursion I 0 0 If Envelope loss/gain 36405 21473 I I 14633 7130 12 a) Infiltration 6134 1551 3044 770 b) Room ventilation 0 0 0 0 13 Internal gains Occupants @ 230 5 1150 2 460 Appliances/other 8200 2600 Subtotal(lines 6 to 13) 42540 32374 17677 10959 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 42540 32374 17677 10959 15 Duct loads I 23% 42% 9744 13478 18% 41% 3209 4446 I I l I Total requireroomd load(cfm) I I l 522831 458521 1883 1883 1 I 208866001 154066001 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. ± vv_..._. 2016-Jun-10 14:59:46 .� Right-Suite®Universal 2017 17.0.01 RSU17889 Page 1 AC'C.1. _.PS\RIGHTJ\MISC\MATHIEU BUILDERS\395 12TH ST.rup Calc=MJ8 Front Door faces. E + wrightsoft Right-J® Worksheet Job: 395 12TH STREET • Entire House Date: MAY 3, By: MARCO HEATING AND AIR Marco Heating & Air Inc Plan: CUSTOM 720 MITI Creek Rd.Jacksonville,FL 32211 Phone.904-743-3350 Fax:904-743-4427 License:CAC1 815711 1 Room name 3.5 TON 2 Exposed wall 196.0 ft 3 Room height 9.2 ft 4 Room dimensions 5 Room area 2170.0 f t' 1 I I I i i Ty Construction U-value OrHTM Area (f t') Load Area Load number (Bt uh/ft'-°F II I(Btuh/f I') I tI or perimeter (ft) (Bluh) I or perimeter` Heat Cool Gross I N/P/S Heat I CooGross I N/PS I Heat I Cool 6 12E-Osw0.068 n 2.55 1.43192t 171 435t 245 10-c2om 0.320 n 12.00 10.51 0 0 0 0 Il-G 4A4-2ov 0.320 n 12.00 10.51 0 0 0 0 0 11130 0.390 n 14.62 11.78 21 21 312 251 11 W 12E-Osw 0.068 e 2.55 143 477 308 785 442 -G 4A4-2ov 0.320 e 12.00 30.13 10 0 120 301 .-G 4A4-2ov 0.320 e 12.00 30.13 14 0 165 414 ..--G 4A4-2ov 0.320 e 12.00 30.13 50 0 594 1491 -G 4A4-2ovd 0.320 e 12.00 30.13 96 0 1152 2893 12E-Osw 0.068 s 2.55 1.43 627 542 1383 778 100-v 0 320 s 12.00 7.36 21 21 248 152 4A4-2ov 0.320 s 12.00 10.51 20 20 240 210 4A4-2ov 0.320 s 12.00 10.51 0 0 0 0 4A4-2ov 0.320 s 12.00 10.51 0 0 0 0 4A4-2ov 0.320 s 12.00 10.51 11 11 132 116 4A4-2ov 0.320 s 12.00 10.51 33 33 396 347 1100 0.390 s 14.62 11.78 0 0 0 0 12E-Osw 0.068 w 2 55 1.43 509 407 1038 584 1D-c2om 0.320 w 12.00 30.13 0 0 0 0 4A4-2ov 0.320 w 12.00 30.13 12 0 144 362 11 4A4-2ov 0 320 w 12 00 30.13 66 0 792 1989 0 11 DO 0.390 w 14.62 11.78 24 24 351 283 P 12C-Osw 0.091 - 3.41 1.39 60 60 205 84 C 16X19-0ad 0 408 - 2.12 1 57 2170 2170 4608 3403 F 19C-19cscp 0.049 - 0.64 0 30 0 0 0 0 F 22A-tpm 1.180 - 44.25 0 00 2170 196 8673 0 I 61 c)AED excursion Envelope loss/gain I I 4 21772 0 14343 12 a) Infiltration 3090 781 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 3 690 Appliances/other 5600 1 Subtotal(lines 6 to 13) I 24862 21415 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 24862 21415 15 Duct loads 26% 42% 6535 9031 Total room load I I 313971 304461 I I Air required(cfm) l 128311 1283 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2016-Jun-1014:59:46 ,�� Right-Suite®U niv er sal 2017 17 RSU17889 Page 2 ...PS\RIGHTJ\MISC\MATHIEU BUILDERS1395 12TH ST.rup Calc=MJ8 Front Door faces E htsoft VNProject Summary Job: 39512TH STREET rI Date: MAY 3,2016 wrightsoft House By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating & Air Inc 720 Mill Creek Rd.Jacksonville,FL 32211 Phone:904-743-3350 Fax:904-743-4427 License:CAC1615711 Project Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET, ATLANTIC BEACH, FL 32233 Phone: 904-268-2845 Notes: ORIENTATION-EAST-FRONT DOOR 1.5 TON 5KW& 3.5 TON 8KW Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 Moisture difference 51 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 42540 Btuh Structure 32374 Btuh Ducts 9744 Btuh Ducts 13478 Btuh Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 52283 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 45852 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 5771 Btuh Ducts 3162 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft2) 3549 3549 Equipment latent load 8933 Btuh Volume (ft') 31904 31904 Air changes/hour 0.28 0.15 Equipment total load 54785 Btuh Equiv.AVF (cfm) 149 80 Req.total capacity at 0.70 SHR 5.5 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 °F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Jun-10 14:58:49 4 wrightsoft Right-Suite®Universal 2017 17.0.01 RSU17889 Page 1 'CC-k ..PS\RIGHTJ\MISC\MATHIEU BUILDERS\395 12TH ST.rup Calc=MJ8 Front Door faces: E ' . -44- Project Summary Job: 39512TH STREET W ri htsoft Date: MAY 3,2016 9 1.5 TON By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating & Air Inc 720 Mill Creek Rd,Jacksonville,FL 32211 Phone:904-743-3350 Fax:904-743-4427 License:CAC1815711 Pro'ect Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET,ATLANTIC BEACH, FL 32233 Phone:904-268-2845 Notes: ORIENTATION-EAST-FRONT DOOR 1.5 TON 5KW&3.5 TON 8KW Desi•n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F li Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 51 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 17677 Btuh Structure 10959 Btuh Ducts 3209 Btuh Ducts 4446 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 20886 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 15406 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1775 Btuh Ducts 1064 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft2) 1379 1379 Equipment latent load 2839 Btuh Volume(ft3) 11981 11981 Air changes/hour 0.37 0.20 Equipment total load 18244 Btuh Equiv.AVF(cfm) 74 40 Req.total capacity at 0.82 SHR 1.6 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN;JANITROL;AMANA DISTI... Trade GOODMAN;JANITROL;AMANA DISTI... Model GSZ140181 K Cond GSZ140181 K AHRI ref 8242613 Coil ASPT25B14A AHRI ref 8242613 Efficiency 8.2 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 14760 Btuh Heating output 17200 Btu h @ 47°F Latent cooling 3240 Btuh Temperature rise 26 °F Total cooling 18000 Btuh Actual air flow 600 cfm Actual air flow 600 cfm Air flow factor 0.029 cfm/Btuh Air flow factor 0.039 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.84 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 111 2016-Jun-10 14:58:49 „• S\ wrightsoft Right-Suite®Universal 2017 17.0.01 RSU17889 Page ...PRIGHTJ'MISCIMATHIEU BUILDERS\395 12TH ST.rup Calc=W8 Front Door faces: E • • Project Summary Job: 395 12TH STREET AIF wrightsoft Date: MAY 3,2016 9 3.5 TON By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating & Air Inc 720 Mill Creek Rd.Jacksonville,FL 32211 Phone:904-743-3350 Fax:904-743-4427 License:CAC1815711 Project Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET,ATLANTIC BEACH, FL 32233 Phone:904-268-2845 Notes: ORIENTATION-EAST-FRONT DOOR 1.5 TON 5KW&3.5 TON 8KW Desi•n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 51 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 24862 Btuh Structure 21415 Btuh Ducts 6535 Btuh Ducts 9031 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31397 Btuh Use manufacturers data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 30446 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3996 Btuh Ducts 2098 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft2) 2170 2170 Equipment latent load 6094 Btuh Volume(ft3) 19923 19923 Air changes/hour 0.23 0.12 Equipment total load 36540 Btuh Equiv.AVF(cfm) 75 40 Req.total capacity at 0.84 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN;JANITROL;AMANA DISTI... Trade GOODMAN;JANITROL;AMANA DISTI... Model GSZ140421 K Cond GSZ140421 K AHRI ref 8242633 Coil ASPT47D14A AHRI ref 8242633 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 32340 Btuh Heating output 38000 Btuh @ 47°F Latent cooling 6160 Btuh Temperature rise 27 °F Total cooling 38500 Btuh Actual air flow 1283 cfm Actual air flow 1283 cfm Air flow factor 0.041 cfm/Btuh Air flow factor 0.042 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.83 14 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Jun-10 14:58:49 -+- wrightsoft Right-Suite®Universal 2017 17.0.01 RSU17889 Page 3 ...PSIRIGHTJ\MISC\MATHIEU BUILDERS\395 12TH ST.rup Calc=MJ8 Front Door faces: E - Manual S Compliance Report Job: 39512TH STREET wrightsoft Date: MAY 3,2016 1.5 TON By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating &Air Inc 720 Mill Creek Rd.Jacksonville,FL 32211 Phone:904-743-3350 Fax:904-743-4427 License:CAC1815711 Project Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET,ATLANTIC BEACH, FL 32233 Phone:904-268-2845 Cooling Equipment Design Conditions Outdoor design DB: 92.7°F Sensible gain: 15406 Btuh Entering coil DB: 78.4°F Outdoor design WB: 77.1°F Latent gain: 2839 Btuh Entering coil WB: 64.2°F Indoor design DB: 75.0°F Total gain: 18244 Btuh Indoor RH: 50% Estimated airflow: 600 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Goodman Mfg. Model: GSZ140181K+ASPT25B14A Actual airflow: 600 cfm Sensible capacity: 17106 Btuh 111%of load Latent capacity: 3839 Btuh 135%of load Total capacity: 20945 Btuh 115%of load SHR: 82% Heating Equipment Design Conditions Outdoor design DB: 32.5°F Heat loss: 20886 Btuh Entering coil DB: 68.3°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Goodman Mfg. Model: GSZ140181K+ASPT25B14A Actual airflow: 600 cfm Output capacity: 18000 Btuh 86%of load Capacity balance: 38 °F Supplemental heat required: 2886 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 600 cfm Output capacity: 5.9 kW 96%of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Jun-10 14:58:49 wrightsoft Right-Suite®Universal 2017 17.0.01 RSU17889 Page 1 ...PSIRIGHTJ\MISCUMTHIEU BUILDERS1395 12TH ST.rup Calc=MJ8 Front Door faces: E +`+ Manual S Compliance Report Job: 395 12TH STREET wrightsoft Date: MAY 3,2016 3.5 TON By: MARCO HEATING AND AIR Plan: CUSTOM Marco Heating & Air Inc 720 Mill Creek Rd,Jacksonville.FL 32211 Phone.904-743-3350 Fax:904-743-4427 License:CACI 815711 Project Information For: 395 12TH STREET, MATHIEU BUILDERS 395 12TH STREET,ATLANTIC BEACH, FL 32233 Phone: 904-268-2845 Cooling Equipment Design Conditions Outdoor design DB: 92.7°F Sensible gain: 30446 Btuh Entering coil DB: 78.1°F Outdoor design WB: 77.1°F Latent gain: 6094 Btuh Entering coil WB: 64.1°F Indoor design DB: 75.0°F Total gain: 36540 Btuh Indoor RH: 50% Estimated airflow: 1283 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Goodman Mfg. Model: GSZ140421K+ASPT47D14A Actual airflow: 1283 cfm Sensible capacity: 31846 Btuh 105%of load Latent capacity: 6094 Btuh 100%of load Total capacity: 37940 Btuh 104%of load SHR: 84% Heating Equipment Design Conditions Outdoor design DB: 32.5°F Heat loss: 31397 Btuh Entering coil DB: 68.4°F Indoor design DB: 70.0"F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Goodman Mfg. Model: GSZ140421K+ASPT47D14A Actual airflow: 1283 cfm Output capacity: 38500 Btuh 123%of load Capacity balance: 29 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1283 cfm Output capacity: 8.4 kW 92%of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Jun-10 14:58:49 wrightsoft Right-Suite;JUniver sal 2017 17.0 01 RSU17889 Paget ACOA .PS\RIGHTJ\MISC\MATHIEU BUILDERS1395 12TH ST rup Calc=MJ8 Front Door faces E • MATHIEU BUILDERS PLAN: CUSTOM ADDRESS: 395 12TH STREET_ GOODMAN 3.5 TON HEAT PUMP SYSTEM SEER: _15_ HSPF: _9.0 _ GOODMAN 1.5 TON HEAT PUMP SYSTEM SEER: _15_ HSPF: _8.5 _ DESIGN COOL BTUH: 60000_ AVAILABLE STATIC PRESSURE: _1:1_ TOTAL CFM: 2800 TOTAL EFFECTIVE LENGTH: 428_ PERFORMANCE METHOD: DUCT MATERIAL: R6 VINYL FLEX SUPPLY BRANCH DETAIL TABLE ROOM NAME COOLING CFM BRANCH SIZE LINEAR FT DUCT MATERIAL OFFICE 165 CFM 7" 15' VINYL FLEX DINING 200 CFM 8" 15' VINYL FLEX GREAT ROOM (2) 165 CFM (2) 7" 20' VINYL FLEX FOYER 35 CFM 4" 15' VINYL FLEX KITCHEN (2) 165 CFM (2) 7" 18' VINYL FLEX LAUNDRY 35 CFM 4" 22' VINYL FLEX PANTRY 35 CFM 4" 25' VINYL FLEX BONUS ROOM (3) 165 CFM (3) 7" 45' VINYL FLEX STAIRS 100 CFM 6" 15' VINYL FLEX BR 1 165 CFM 7" 16' VINYL FLEX BR1 WIC 35 CFM 4" 20' VINYL FLEX BATH 1 35 CFM 4" 20' VINYL FLEX BR3 165CFM 7" 20' VINYL FLEX BATH 3 35 CFM 4" 20' VINYL FLEX BR 3 WIC 35 CFM 4" 15' VINYL FLEX BATH 2 35 CFM 4" 15' VINYL FLEX BR2 165 CFM 7" 15' VINYL FLEX BR2 WIC 35 CFM 4" 15' VINYL FLEX MBR (2) 100 CFM (2) 6" 20' VINYL FLEX MBA 100 CFM 6" 20' VINYL FLEX MBR WIC 35 CFM 4" 12' VINYL FLEX MBA TOILET 35 CFM 4" 30' VINYL FLEX TOTALS 2800 CFM 428 LN (FT) SUPPLY TRUNK DETAIL TABLE LOCATION DESIGN BTUH TRUNK SIZE DUCT MATERIAL FROM UNIT TO 1ST DISTR BOX 12202 10" VINYL FLEX FROM UNIT TO 1ST DISTR BOX 21054 14" VINYL FLEX 1 • I 5 1 . ®D' g • c.,t i A sry zb g I " i r i 13 D ^ mu Or M461D+> aS r , a. 93 CIS . 1):•-.. ,., 1.. k I . ..,•........;OIL -< ..", '4.' Ili Ildiga Ir.4=11AI 5.i 7..6MI6 C•• 1 1 1f'11 ' ii E..� �,', ra.r : . 53_ _ . . Ft r.{ 0. i I r - e:a :0:-(°—°-`"- '." -'74.-t, Q — s s••crs zsr. . ' N T. 7. V43; ------- - - ---------- ---- --- --- -Y al F �- itA ,i; Jt. i•ii; f� I — .11)----; , A I' a • J i � n • 1. w . to o i • 4° i 6 �q6 :•: li r, a h_ I ,i - _ A4 . I ra 1 IN ' i. . ..• 4* la —* •• h!.._.t: ,e, . ,J,_____, . As: P.;11 107 0., d.1101 i, ..' • , tli f rA 1• 4:: v i:01 ., w d. r. I ____ I 1 r i •'4 r r"r'' li ...,[. , I 1�l±rr j s..r •t417Jr ``� e 1 •ARKES.R \ 7v r RESIDENCE H ,LR„n, 395 12th STREET y [.... x I ATLANTIC BEACH. FLORIDA _J Rill tMw mi ____. 4 D 4 1q/ �� m D T-- 0 O O ., 13 - p 70 [ 1. z L y-E lir y 4,113/4. j,___ 11/2!____.. 4•-1 3/l• y d-E V2 D 263E DH 263E DH r - o Z b C!p b b 8 z O ,,,, 0 J J I 13 31 i t Z i I , �) 18 WIA2c D R