Loading...
1776 MARITIME OAK DR - ENERGY SHEETS ES ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 Reissued August 2014 This report is subject to renewal August 2016. www.icc-es.orcl I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council° DIVISION:07 00 00—THERMAL AND MOISTURE pcf. The insulation's liquid components are supplied in PROTECTION nominally 55-gallon drums, labeled as "A" component or Section:07 21 00—Thermal Insulation "B" component. The insulation components have a shelf life of six months when stored in unopened containers at REPORT HOLDER: temperatures between 70°F(21°C)and 90°F(32°C). SES FOAM 3.2 Surface-burning Characteristics: 4008 LOUETTA ROAD,#538 At a maximum thickness of 4 inches (102 mm) and a SPRING,TEXAS 77388-4405 nominal density of 0.5 pcf, the insulation has a flame- (713)239-0252 spread index of 25 or less and a smoke-developed index of www.sesfoam.com 450 or less when tested in accordance with ASTM E84. Thicknesses of up to 111/2 inches (292 mm) for wall EVALUATION SUBJECT: cavities and ceiling cavities are recognized based on room corner fire testing in accordance with NFPA 286, when SES FOAM 0.5 lb SPRAY: SPRAY-APPLIED the insulation is covered with a minimum 1/2-inch-thick POLYURETHANE FOAM PLASTIC INSULATION (12.7 mm) gypsum board installed in accordance with the applicable code. 1.0 EVALUATION SCOPE 3.3 Thermal Resistance(R-values): Compliance with the following codes: The insulation has thermal resistance(R-values)at a mean • 2012 and 2009 International Building Code®(IBC) temperature of 75°F(24°C)as shown in Table 1. • 2012 and 2009 International Residential Code®(IRC) 3.4 Air Permeability: • 2012 and 2009 International Energy Conservation The insulation, at a minimum thickness of 3 inches Code®(IECC) (76 mm), is considered air-impermeable in accordance • Other Codes(see Section 8.0) with IRC Section R202, based on testing in accordance with ASTM E283. Properties evaluated: 4.0 INSTALLATION • Surface-burning characteristics 4.1 General: • Physical properties SES Foam 0.5 lb spray insulation must be installed in • Thermal resistance(R-values) accordance with the manufacturer's published installation • Attic and crawl space installation instructions and this report. A copy of the manufacturer's published installation instructions must be available at all • Air permeability times on the jobsite during installation. 2.0 USES 4.2 Application: SES Foam 0.5 lb spray polyurethane foam plastic The insulation is spray-applied at the jobsite using a insulation is used as a nonstructural thermal insulating volumetric positive displacement pump as identified in the material in buildings of Type V-B (IBC)construction, and in SES Foam 0.5 lb spray application manual. The insulation dwellings built under the IRC. The insulation is for use in components must be stored at temperatures between wall cavities and floor/ceiling assemblies, and in attics and 70°F (21°C) and 90°F (32°C) for several days before crawl spaces when installed as described in Section 4.4. application. The insulation must not be used in areas Under the IRC, the insulation may be used as air- that have maximum in-service temperatures greater than impermeable insulation when installed as described in 180°F (82°C). The insulation must not be used in Section 3.4. electrical outlet or junction boxes or in contact with water 3.0 DESCRIPTION (e.g., rain, condensation, ice, snow) or soil. The substrate 3.1 General: must be free of moisture, frost or ice, loose scales, rust,oil, grease or other surface contaminants. The insulation can SES Foam 0.5 lb spray foam insulation is a two- be installed in one pass to the maximum thickness. The component, open cell, one-to-one-by-volume spray-applied spray-applied foam insulation must be protected from polyurethane foam system with a nominal density of 0.5 weather during and after installation. ICC-ES Evaluation Reports are not to he construed as representing aesthetics or any other attributes not specifically addressed,nor are they to he construed i iu ANSI as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as to any finding or other matter in this report,or as to any product covered by the report. " Copyright CO 2014 Page 1 of 3 cSR-3375 I Most Widely Accepted and Trusted Page 3 of 3 The products comply with the above-mentioned codes as provided in accordance with Sections 701 and 703 of described in Sections 2.0 through 7.0 of this report, with the 2006 IECC. revisions as noted below: • Protection against Termites: See Section 5.6, except • Application with a Prescriptive Thermal Barrier: See use of the insulation in areas where the probability of Section 4.3, except the approved thermal barrier must termite infestation if"very heavy" must be in accordance be installed in accordance with Section R314.4 of the with Section R320.5 of the 2006 IRC. 2006 IRC. • Jobsite Certification and Labeling: See Section 5.7, • Application with a Prescriptive Ignition Barrier: See except jobsite certification and labeling must comply Section 4.4.1, except an ignition barrier must be with Sections 102.1.1 and 102.1.1.1, as applicable, of installed in accordance with Section R314.5.3 or the 2006 IECC. R314.5.4 of the 2006 IRC. • Application without a Prescriptive Ignition Barrier: See Section 4.4.2, except that combustion air is TABLE 1—THERMAL RESISTANCE(R-VALUES'.2) THICKNESS(inches) R-VALUE(°F1t2•h/Btu) 1 4.0 2 7.6 3 11 3.5 13 4 15 5 19 6 22 7 26 8 30 9 33 10 37 11 41 12 44 For SI: 1 inch=25.4 mm,1°F•ft2•h/Btu=0.176 110K•m2/W. 'R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. e ir. 4 \ - , E--z. ICC EVALUATION � SERVICE Most Widely Accepted and Trusted ICC-ES VAR Environmental Report VAR-1030* Reissued July 2013 This report is subject to renewal September 1, 2015. www.icc-es.orglep 1800-423-6587 I (562)699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE high-pressure, plural component SPF application PROTECTION equipment.The bio-based content is as set forth in Table 1 Section: 07 21 00—Thermal Insulation of this report. 4.0 CONDITIONS REPORT HOLDER: 4.1 Code Compliance: SES FOAM See ICC-ES report ESR-3375 for compliance of the SES 4008 LOUETTA ROAD,#538 Foam 0.5 lb Foam S Polyurethane Foam Plastic Insulation SPRING,TEXAS 77388-4405 with code requirements. (713)239-0252 4.2 Green Codes, Standards and Rating Systems www.sesfoam.com Eligibility: g' ty: EVALUATION SUBJECT: The information presented in Tables 2 through 5 of this report provides a matrix of areas of evaluation and SES FOAM 0.5 lb SPRAY POLYURETHANE FOAM corresponding limitations and/or additional project-specific PLASTIC INSULATION requirements, and offers benefits to individuals who are assessing eligibility for compliance. 1.0 EVALUATION SCOPE The final interpretation of the specific requirements of the Compliance with the following environmental criteria: code rests with the Authority Having Jurisdiction. ICC-ES Environmental Criteria for Determination of Compliance for items noted as "Verified Attribute" is Bio-based Material Content(EC102), dated March 1, 2012. subject to any conditions noted in the tables. Decisions on Compliance eligibility with the applicable sections of compliance for those items noted as "Eligible for Points" in the following codes and standards: Tables 2 through 5 rests with the user of this report, and those items are subject to the conditions noted.The user is • 2012 International Green Construction Code1M (IgCC) advised of the project-specific provisions that may be (see Table 2 for details) contingent upon meeting specific conditions, and the • ASHRAE Standard 189.1 – 2009 (see Table 3 for verification of those conditions is outside the scope of this details) report. • National Green Building Standard (ICC 700-2008) (see Due to the variability of costs and volume, the bio-based Table 4 for details) content percentage listed in this report is based upon weight (mass). The use of cost or volume as the method • ANSI/GBI 01-2010, Green Building Assessment for calculation is outside the scope of this report. Protocol for Commercial Buildings (see Table 5 for 5.0 BASIS OF EVALUATION details) The information in this report, including the "Verified 2.0 USES Attributes," is based upon submission of documentation SES Foam 0.5 lb Foam S Polyurethane Foam Plastic demonstrating compliance with the requirements set forth Insulation is used as nonstructural thermal insulating in ICC-ES EC102. (Evaluation applies to IgCC Section material in wall cavities, floor/ceiling assemblies, or in 505.2.4, item 3; ASHRAE 189.1 Section 9.4.1.3; ICC 700 attics and crawl spaces. See ICC-ES report ESR-3375 for Section 606.1;ANSI/GBI-01 Section 10.1.2.2.) more information on uses and applications. 6.0 IDENTIFICATION 3.0 DESCRIPTION Containers of SES Foam 0.5 lb Foam S Polyurethane SES Foam 0.5 lb spray-applied polyurethane foam plastic Foam Plastic Insulation are identified by a label bearing the insulation is a two-component, open-cell, water-blown, SES Foam name and address, product name, spray-applied polyurethane foam (SPF) with a nominal manufacturing date, manufacturing location and the VAR density of 0.5 lb/ft3. The foam is sprayed in place using Environmental Report number(VAR-1030). `Corrected May 2014 ICC-ES Verification of Attributes Reports are issued under the ICC-ES VAR Environmental program.These reports are not to he construed as representing aesthetics or any other rzc attributes not specifically addressed,nor are they to he construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC t',s., Evaluation Service.LLC,express or implied.as to any finding or other matter in this report,or as to any product covered by the report. WI WWI Page 1 of 2 Copyright®2014 F 4 EZ ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 Seal and Insulate with ENERGY STAR®Supplement Reissued August 2014 This report is subject to renewal August 2016. www.icc-es.org I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council' DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 21 00—Thermal Insulation REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING, TEXAS 77388-4405 (713)239-0252 www.sesfoam.com EVALUATION SUBJECT: SES FOAM 0.5 lb SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION 1.0 EVALUATION SCOPE Conformance to the following: Seal and Insulate with ENERGY STAR® Program—Definitions and Testing Requirements for Residential Insulation, Version 1.0 Properties evaluated: • Thermal resistance • Surface-burning characteristics 2.0 PURPOSE OF THIS SUPPLEMENT This supplement is issued to certify that the insulation products described in Sections 2.0 through 8.0 of the master report ESR-3375 have been reviewed for compliance with the requirements of the Seal and Insulate with ENERGY STAR Program, as set forth in the document Definitions and Testing Requirements for Residential Insulation, Version 7.0. The insulation product covered by this supplement is defined as"Spray or Pour Foam Insulation." The requirements for testing laboratory qualification and product sampling, as well as the specific material and test standards and editions used in this evaluation, are as set forth in the applicable documentation noted in Section 6.0 of the master evaluation report. 3.0 DEFINITIONS The following definitions are from Definitions and Testing Requirements for Residential Insulation, Version 1.0, and are applicable to the subject of this report. 3.1 General Definitions: Insulation: Any material mainly used to slow down heat flow. It may be mineral or organic, fibrous, cellular, or reflective (aluminum foil). It may he in rigid, semi-rigid,flexible, or loose-fill form. 3.2 Insulation Product Definitions: Spray or Pour Foam Insulation: A thermal insulating material that is sprayed or poured (as a gel or foamy liquid) into place, and expands or sets into a cellular foam and cures at the point of installation through a chemical reaction. Foamed materials include, but are not limited to polyurethane, polyisocyanurate, phenolic, and cementitious insulation. 3.3 Insulation Performance Definitions: R-value: The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area. For the purposes of the Seal and Insulate with ENERGY STAR®program, Imperial units will only be accepted [(h•ft2•°F)/Btu]. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service.LLC.express or implied.as Eighlt to any finding or other matter in this report.oras to any product covered by the report. Copyright c 2014 Page 1 of 6 ESR-3375 I Most Widely Accepted and Trusted Page 2 of 6 Smoke-Development Index: The characteristic of a material to emit smoke when exposed to flame or fire compared to red oak and inorganic cement. Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed to flame or fire compared to red oak and inorganic cement. 3.4 Thermal Resistance: The insulation has the thermal resistance R-values as noted in Table 1 of ESR-3375, based upon testing. 3.5 Installation: 3.5.1 General: The installation of the insulation must be in accordance with the requirements set forth in Sections 4.0 and 5.0(as applicable)of ESR-3375.The insulation is manufactured on-site by spray polyurethane foam applicators meeting the qualification requirements of SES Foam. The following information on personal protective equipment and ventilation requirements is reprinted from the SES Foam published installation instructions: "F. SAFETY 3. PERSONAL PROTECTIVE EQUIPMENT(PPE): a. Skin:Wear gloves, coveralls, apron and boots as necessary to prevent contact of liquid components or partially-cured SPF with skin.When handling liquid components, gloves should be made of nitrile, neoprene, butyl or PVC. b. Eyes: Protect eyes while handling liquid components or spraying with safety goggles or safety goggles and a face shield. During spray application,eye protection may be provided by a full-face or hood respirator. c. Respiration: Firms engaged in the application of SES Foam systems must have a written respiratory protection program for employees engaged in handling or applying SES Foam materials. Depending on the situation, respiratory protection may include dust masks, air-purifying respirators (APR), powered air-purifying respirators (PAPR), or supplied- air respirators(SAR). 4. VENTILATION: Provide ventilation and other engineering controls to exhaust vapors from work areas and to protect building occupants and other trades." 3.5.2 Occupancy Time after Installation: The re-entry or re-occupancy time shall be in accordance with the manufacturer's installation instructions,which state the following: "E. RE-ENTRY SES Foam 0.5 lb Spray reacts and cures within seconds of application. Re-entry times will vary depending on factors including ventilation. Typically, ventilation is continued for 24 hours following the conclusion of spray application and re-entry may occur at that time." 3.5.3 Figures:The figures shown represent general installations of the insulation in the following applications: above-grade wall, below-grade wall, vented and unvented crawl space, unvented cathedral ceiling, and vented and unvented attic. These figures are for illustration purposes and are not to be construed or used as construction documents. This supplement expires concurrently with the master report, reissued August 2014. I 4 • ESR-3375 I Most Widely Accepted and Trusted Page 3 of 6 °°Qo°°00°°00°0 %0°°oo°°00°°00°oo°°oo°°ao° 09°°0a°°o0pOo0° 0°°00°ao°o9°pOoO10°°-0°O% 0 0°0 0 0°00°°0°00 0° 0000 o Qn O a�00°;:o 0'000000° (300 °°0 a 000 Oa °�o°° �°°000° °°o0°°oc no° °° o° n0° °„O0°�,❑ �op0ap00 -'� 0 O:00o 0c 00° o°° 00°0°0 0°0a Interior Partition )000o000C op 0000 09 o° 0° 1000000oc '---Interior Finished Surface 000,0o% (1/2-inch Sheetrock) >0°000°0c 00 .00°00°a9 °00°0000, 000a0 "�� 000 ,°900 0 co SES Foam 0.5 lb Spray >0 000 0C 0°noO0n0 >.< apo°QaC 00000 0° Exterior Sheathing OL0 000 0 SES FOAM 0.5 LB SPRAY ABOVE GRADE WALL INSULATION SES 05-1 071812 wESR-3375 I Most Widely Accepted and Trusted Page 4 of 6 O „..._<>_401:07'..::.1 Masonry Block 000 j / (Typical) INT ‹ ;• Z ,/ o Interior Finish Surface � o. �_ (112-inch Sheetrock) / g ` .'` - 2"x 4"Studs , ` . . SES Foam 0.5 lb Spray 111, SES FOAM 0.5 LB SPRAY I BELOW GRADE WALL INSULATION I SES 05-2 I 071812 (Insulation on Interior Side of Wall) i /-- Baffle to provide air space between j Thermal insulation and roof Barrier` deck. ///j (as required by local code) �� .00000.. i -.-•i -. i T i i i i . i /// 000000°00000000000°00°00°•00°00°00°00°0000°0000°00°000°0°00: / 000000000000000000000 •0000000000000000000000 000$000$ 11 .000000000 000000 0000000 SES Foam 0.5 lb Spray o°o°o° ° iiiiiiiiiiiiiiiiiiiiiiiiiiiii. °0°O°°°° og°$° ° o°°°°°°° ° o ° ° 00000°0° °° ° ° o 00000°°o° 0°000000 00000000 00000000 ° 000 Vented Soffit g0go°°o:0 °000°°°° 0000000°0°00 00 ° , 'Where attic entry is for the SES Foam 0.5 lb Spray 00000000 service of utilities only,thermal o°Oo°°°° ,0°0,0p°o and igniton barrier on the attic 0o side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY VENTED ATTIC:FLOOR!SOFFIT SES 05-3 071812 ESR-3375 I Most Widely Accepted and Trusted Page 5 of 6 gad Subfloor SES Foam 0.5 lb Spray °°°° ° ° °e °e°ee,e''eee ': °°,:° II y°.o°+.es°e�ers°ir°w° °° • •Ilse°°°ee°e°,°,°, ° ° s.°. °9. .° . ° Header 1e :• , °°°°°°° ° °° °°°° -�:e°eve Sill 1- - •-•-•iiie2o Joist Floor Cross Section •• °e ♦•• ••• ►•�•�•�•�� Thermal Barrier* (as required by Exterior Grade 1•••i•S%44 local code) .i\\\i/\\\\/�\\\e....•••44 ►.'�moi ►•�•�•�•�• 4 6"Min • • Footer ►��������4 Vapor Barrier • .:•� %\�///\�///\\//, "Where crawlspace entry is for the • 4 .,. --> \ \ \ service of utilities only,thermal / and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY CRAWLSPACE:VENTED SES 05-4 071812 I °e°e Subfloor I se°°e° es Header I oiiiiiiiiiiirevN. 1° ee°°°° °i*E °°° ° o Sill I;.;.;.;. °sees Joist ►•.o❖IWI I •.oeee •••••••4 asses Thermal Barrier' •••'°°°°° (as required by Exterior Grade j•�•-•-•;4iivie local code) /,�\/// � // /i••�••�4 sees° �� ►••••4°° SES Foam 0.5 lb Spray ••••••2,nt. •••• ►iiii4° Footer---...„....... ►••❖. 6"Min Vapor B-rrier Where crawlspace entry is for the service of utilities only,thermal and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY CRAWLSPACE:UNVENTED SES 05-5 071812 ESR-3375 I Most Widely Accepted and Trusted Page 6 of 6 Note:In cold climates,embed metal connector plates in spray foam to prevent winter-time condensation. I .o°o °o o°o°°°•• O °o SES Foam 0.5 lb Spray ;000°/ 1.1.! �'Oo$ o- /o .°0000.. ooh/ ••°000; }i� 'o°• Roof Sheathing i•° o°°• 4,34 t°.i' /o/ Truss Top Cord/ •0000° Rafter ooO00000°oo. • o o� nnnnnn / fr�__ nnnnnn 1111.1111111111 Thermal Barrier' (as required by local code) . Note:Local building code may V require the use of a vapor retarder 'n cold climate zones. Ceiling/Thermal Barrier 'Where attic entry is for the as required by local building code. service of utilities only,thermal and igniton barrier on the attic side of the spray foam surface may be omitted. SES FOAM 0.5 LB SPRAY UNVENTED ATTIC/INSULATED ROOF DECK SES 05-6 071812 ��Tc).---, _ i •00' 1000 SES Foam 0.5 lb Spray 'O• a 0•10 0 0 0 II to specified thickness. /• O 0 O• 4�/ "\4,4.4<C) • 00000* • / Roof Sheathing -- 0(30°0°• . 00000 / Thermal Barrier as Rafter :XO 0 O required by code. •O/ --1.411 ; Note:The local building code may requireethe installation of 1117141 a vapor barrier in cold climate zones. 11 SES FOAM 0.5 LB SPRAY CATHEDRAL CEILING SES 05-7 071912 FILE COPY FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: RIVER3608-Main House Builder Name: Riverside Homes Street: Ili 6 PILO i-i r4 O*AL O f-i y,L Permit Office: City of Atlantic Beach City,State,Zip: Atlantic Beach,FL, 31.233 Permit Number: Owner: Brankston Residence Jurisdiction: 261300 Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types(3695.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3438.50 ft2 b. Frame-Wood,Adjacent R=19.0 162.00 ft2 3. Number of units,if multiple family 1 c.Frame-Wood,Adjacent R=13.0 94.50 ft2 4. Number of Bedrooms 4 d. N/A • R= ft2 5. Is this a worst case? No 10.Ceiling Types 2235.0 sqft.) Insulation Area a. Roof Dec t ' R=22.0 2144.00 ft2 6. Conditioned floor area above grade(ft2) 3608 b. Knee Wall(Vented) R=0.0 91.00 ft2 Conditioned floor area below grade(ft2) 0 c. N/A R= ft2 11.Ducts R ft2 7. Windows(553.9 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:2nd Floor 6 360.8 a. U-Factor: Dbl,U=0.35 553.92 ft2 b.Sup: Attic,Ret:Attic,AH:2nd Floor 6 360.8 SHGC: SHGC=0.22 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 36.0 SEER:14.00 b.Central Unit 30.0 SEER:14.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 36.0 HSPF:8.20 SHGC: b.Electric Heat Pump 30.0 HSPF:8.20 Area Weighted Average Overhang Depth: 5.983 ft. Area Weighted Average SHGC: 0.220 14.Hot water systems 8. Floor Types (3608.0 sqft.) Insulation Area a.Propane Tankless Cap: 1 gallons EF:0.860 a.Slab-On-Grade Edge Insulation R=0.0 2144.00 ft2 b. Conservation features b.Floor Over Other Space R=0.0 1464.00 ft2 None c.N/A R= ft2 15.Credits Pstat Glass/Floor Area: 0.154 Total Proposed Modified Loads: 78.44 PASS Total Baseline Loads: 89.72 I hereby certify that the plans and specifications covered by Review of the plans and .•.* ST9p' •, this calculation are in compliance with the Florida Energy specifications covered by this � � 04.;:, Code. Digitally signed by Douglas R. calculation indicates compliance :°�4,4,.- ''. �`, ,... Douglas R. Stickles with the Florida Energy Code. 3 L `,,,,, ;;;.` ;�0� ON:cn=Douglas R.Stickles, : •^ PREPARED BY: Before construction is completed I cd -�-7 � } =US,0-A/C Masten HVAC,Inc. p(,? r� d j DATE: Sti[!�1eS _ nate•20,..osn213:12:2s-n4.00. this building will be inspected for t ;A compliance with Section 553.908 Florida Statutes. ***-...4r,--. � �S I hereby certify that this building, as designed, is in compliance �g with the Florida Energy Code. D /_ - •••• OD W>E ,.• OWNER/AGENT: 1/4thL- - -1D_►Sf -- BUILDING OFFICIAL: /PP DATE: 6-"w' DATE. 5'4/9-16 - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 4/21/2016 2:27 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2014 PROJECT Title: RIVER3608-Main House Bedrooms: 4 Address Type: Lot Information Building Type: User Conditioned Area: 1500 Lot# 106 Owner: Brankston Residence Total Stories: 2 Block/SubDivision: Atlantic Bch CC #of Units: 1 Worst Case: No PlatBook: Builder Name: Riverside Homes Rotate Angle: 315 Street: Permit Office: City of Atlantic Beach Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, New/Existing: New(From Plans) Comment: CLIMATE V Design Location TMY SiteIECC Design Temp Int Design Temp Heating Design Daily Temp Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL JACKSONVILLE INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block/ 2144 21440 2 Block2 1464 13176 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 1st Floor 2144 21440 Yes 2 1 1 Yes Yes Yes 2 2nd Floor 1464 13176 No 3 3 1 Yes Yes Yes FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge lnsulatio 1st Floor 211.3 ft 0 2144 ft2 ___ 0.7 0 0.3 2 Floor Over Other Space 2nd Floor ____ ____ 1464 ft2 0 0.45 0 0.55 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 2483 ft2 0 ft2 Light 0.6 No 0.4 No 22 30.3 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 2144 ft2 N N 4/21/2016 2:27 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2014 CEILING V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic(Unvented) 1st Floor 0 Blown 680 ft2 0.11 Wood 2 Knee Wall(Unvented) 1st Floor 0 Blown 29 ft2 0.11 Wood 3 Under Attic(Unvented) 2nd Floor 0 Blown 1464 ft2 0.11 Wood 4 Knee Wall(Unvented) 2nd Floor 0 Blown 62 ft2 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Belo w V_# Omt.--- To Wall.Type R-Value Ft In Ft In -ArPa R-Value-Fraction -Absor. Grade%- _ 1 N=>NW Exterior Frame-Wood 1st Floor 19 3 3 10 32.5 ft2 0.23 0.75 0 2 W=>SW Exterior Frame-Wood 1st Floor 19 1 6 10 15.0 ft2 0.23 0.75 0 _ 3 N=>NW Exterior Frame-Wood 1st Floor 19 10 3 10 102.5 ft2 0.23 0.75 0 4 E=>NE Exterior Frame-Wood 1st Floor 19 1 6 10 15.0 ft2 0.23 0.75 0 5 N=>NW Exterior Frame-Wood 1st Floor 19 2 9 10 27.5 ft2 0.23 0.75 0 _ 6 N=>NW Exterior Frame-Wood 1st Floor 19 20 9 10 207.5 ft2 0.23 0.75 0 7 W=>SW Exterior Frame-Wood 1st Floor 19 2 10 20.0 ft2 0.23 0.75 0 _ 8 N=>NW Exterior Frame-Wood 1st Floor 19 12 6 10 125.0 ft2 0.23 0.75 0 _ 9 E=>NE Exterior Frame-Wood 1st Floor 19 32 10 320.0 ft2 0.23 0.75 0 _10 S=>SE Exterior Frame-Wood 1st Floor 19 10 3 10 102.5 ft2 0.23 0.75 0 11 E=>NE Exterior Frame-Wood 1st Floor 19 6 10 60.0 ft2 0.23 0.75 0 12 S=>SE Exterior Frame-Wood 1st Floor 19 10 6 10 105.0 ft2 0.23 0.75 0 13 E=>NE Exterior Frame-Wood 1st Floor 19 2 10 20.0 ft2 0.23 0.75 0 14 S=>SE Exterior Frame-Wood 1st Floor 19 7 6 10 75.0 ft2 0.23 0.75 0 _15 E=>NE Exterior Frame-Wood 1st Floor 19 9 3 10 92.5 ft2 0.23 0.75 0 16 S=>SE Garage Frame-Wood 1st Floor 13 10 6 9 94.5 ft2 0.23 0.01 0 17 S=>SE Garage Frame-Wood 1st Floor 19 18 9 162.0 ft2 0.23 0.01 0 _18 W=>SW Exterior Frame-Wood 1st Floor 19 26 3 10 262.5 ft2 0.23 0.75 0 _19 N=>NW Exterior Frame-Wood 1st Floor 19 5 10 50.0 ft2 0.23 0.75 0 20 W=>SW Exterior Frame-Wood 1st Floor 19 19 6 10 195.0 ft2 0.23 0.75 0 21 N=>NW Exterior Frame-Wood 2nd Floor 19 29 9 261.0 ft2 0.23 0.75 0 22 E=>NE Exterior Frame-Wood 2nd Floor 19 21 9 189.0 ft2 0.23 0.75 0 23 N=>NW Exterior Frame-Wood 2nd Floor 19 10 6 9 94.5 ft2 0.23 0.75 0 24 E=>NE Exterior Frame-Wood 2nd Floor 19 15 9 135.0 ft2 0.23 0.75 0 _25 S=>SE Exterior Frame-Wood 2nd Floor 19 10 6 9 94.5 ft2 0.23 0.75 0 26 E=>NE Exterior Frame-Wood 2nd Floor 19 2 9 18.0 ft2 0.23 0.75 0 _27 S=>SE Exterior Frame-Wood 2nd Floor 19 7 6 9 67.5 ft2 0.23 0.75 0 28 E=>NE Exterior Frame-Wood 2nd Floor 19 7 6 9 67.5 ft2 0.23 0.75 0 29 S=>SE Exterior Frame-Wood 2nd Floor 19 21 6 9 193.5 ft2 0.23 0.75 0 30 W=>SW Exterior Frame-Wood 2nd Floor 19 3 9 9 33.8 ft2 0.23 0.75 0 _31 S=>SE Exterior Frame-Wood 2nd Floor 19 5 9 45.0 ft2 0.23 0.75 0 32 W=>SW Exterior Frame-Wood 2nd Floor 19 22 6 9 202.5 ft2 0.23 0.75 0 33 N=>NW Exterior Frame-Wood 2nd Floor 19 5 9 45.0 ft2 0.23 0.75 0 34 W=>SW Exterior Frame-Wood 2nd Floor 19 18 3 9 164.3 ft2 0.23 0.75 0 4/21/2016 2:27 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2014 DOORS V # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 S=>SE Insulated 1st Floor None .46 3 8 24 ft' 2 S=>SE Insulated 1st Floor None .46 2 8 8 21.3 ft' WINDOWS Orientation shown is the entered orientation(=>)changed to As Built(rotated 135 degrees). Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC _ Area Depth Separation Int Shade Screening 1 N=>NW 3 Vinyl Double(Clear) Yes 0.35 0.22 37.5 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 2 N=>NW 3 Vinyl Double(Clear) Yes 0.35 0.22 7.5 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 3 N=>NW 6 Vinyl Double(Clear) Yes 0.35 0.22 128.0 ft' 11 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 4 N=>NW 8 Vinyl Double(Clear) Yes 0.35 0.22 48.0 ft' 9 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 5 S=>SE 10 Vinyl Double(Clear) Yes 0.35 0.22 24.0 ft2 7 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 6 E=>NE 11 Vinyl Double(Clear) Yes 0.35 0.22 15.0 ft' 12 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5 7 E=>NE 11 Vinyl Double(Clear) Yes 0.35 0.22 3.0 ft2 12 ft 0 in 1 ft 0 in Drapes/blinds Exterior 5 8 S=>SE 12 Vinyl Double(Clear) Yes 0.35 0.22 30.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 9 S=>SE 12 Vinyl Double(Clear) Yes 0.35 0.22 6.0 ft' 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 10 S=>SE 14 Vinyl Double(Clear) Yes 0.35 0.22 10.7 ft2 34 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 11 E=>NE 15 Vinyl Double(Clear) Yes 0.35 0.22 6.0 ft' 9 ft 2 in 1 ft 0 in Drapes/blinds Exterior 5 12 W=>SW 18 Vinyl Double(Clear) Yes 0.35 0.22 18.8 ft' 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 13 W=>SW 20 Vinyl Double(Clear) Yes 0.35 0.22 33.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 14 N=>NW 21 Vinyl Double(Clear) Yes 0.35 0.22 6.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 15 N=>NW 21 Vinyl Double(Clear) Yes 0.35 0.22 30.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 16 E=>NE 22 Vinyl Double(Clear) Yes 0.35 0.22 12.5 ft' 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 17 E=>NE 24 Vinyl Double(Clear) Yes 0.35 0.22 12.5 ft' 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 18 S=>SE 25 Vinyl Double(Clear) Yes 0.35 0.22 30.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 19 S=>SE 27 Vinyl Double(Clear) Yes 0.35 0.22 20.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 20 S=>SE 29 Vinyl Double(Clear) Yes 0.35 0.22 8.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 21 S=>SE 31 Vinyl Double(Clear) Yes 0.35 0.22 15.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 22 W=>SW 32 Vinyl Double(Clear) Yes 0.35 0.22 30.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 23 N=>NW 33 Vinyl Double(Clear) Yes 0.35 0.22 7.5 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 24 W=>SW 34 Vinyl Double(Clear) Yes 0.35 0.22 15.0 ft2 1 ft 8 in 1 ft 0 in Drapes/blinds Exterior 5 GARAGE V # Floor Area Ceiling Area _ Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 654.9984 ft2 384 ft2 75.9 ft 9 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000305 2884.7 158.36 297.83 .289 5 4/21/2016 2:27 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5 FORM R405-2014 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:8.2 36 kBtu/hr 1 sys#1 2 Electric Heat Pump None HSPF:8.2 30 kBtu/hr 2 sys#2 COOLING SYSTEM V # System Type Subtype _ Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit split SEER: 14 36 kBtu/hr 1080 cfm 0.75 1 sys#1 2 Central Unit split SEER: 14 30 kBtu/hr 900 cfm 0.75 2 sys#2 HOT WATER SYSTEM V # System Type SubType Location EF Cap_ Use _ SetPnt Conservation 1 Propane Tankless Exterior 0.86 1 gal 70 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS V ----Supply---- Return---- Air CFM 25 CFM25 HVAC# # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 360.8 ft Attic 90.2 ft2 Default Leakage 2nd Floor (Default) (Default) 1 1 2 Attic 6 360.8 ft Attic 90.2 ft2 Default Leakage 2nd Floor (Default) (Default) 2 2 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Coolin [[ ]]Jan [[ ]]Feb [[ ]]Mar [ Apr Ma X Jun X Jul X Au X Se Oct ]Nov 13:cc Heating [X]Jan [X]Feb [X]Mar 1,�App May Jun Jul Aug Sep 1X1 Oct [1 Nov X Dec Venting [ ]Jan [[ ]]Feb [[X]]Mar Ix1JJJ Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 4/21/2016 2:27 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 87 The lower the EnergyPerformance Index, the more efficient the home. , Atlantic Beach, FL, 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area a.Frame-Wood,Exterior R=19.0 3438.50 ft2 2. Single family or multiple family Single-family b.Frame-Wood,Adjacent R=19.0 162.00 ft2 3. Number of units,if multiple family 1 c. Frame-Wood,Adjacent R=13.0 94.50 ft2 4. Number of Bedrooms 4 d.N/A R= ft2 10.Ceiling Types Insulation Area 5. Is this a worst case? No a.Roof Deck(Vented) R=22.0 2144.00 ft2 6. Conditioned floor area(ft2) 1500 b. Knee Wall(Vented) R=0.0 91.00 ft2 c. NIA R= ft2 7. Windows** Description Area 11.Ducts R ft2 a. U-Factor: Dbl,U=0.35 553.92 ft2 a.Sup:Attic,Ret:Attic,AH:2nd Floor 6 360.8 SHGC: SHGC=0.22 b.Sup: Attic,Ret:Attic,AH:2nd Floor 6 360.8 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor N/A ft2 a.Central Unit 36.0 SEER:14.00 SHGC: b.Central Unit 30.0 SEER:14.00 d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 36.0 HSPF:8.20 Area Weighted Average Overhang Depth: 5.983 ft. b.Electric Heat Pump 30.0 HSPF:8.20 Area Weighted Average SHGC: 0.220 8. Floor Types Insulation Area 14.Hot water systems Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 2144.00 ftZ a.Propane EF:0.86 b.Floor Over Other Space R=0.0 1464.00 ft2 b. Conservation features c. N/A R= ft2 None 7 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building •'ectiE sT4•' Construction through the above energysavingfeatures which will be installed (or exceeded) o4.................`T� in this home before final inspection. Otherwise, a new EPL Display Card will be completed • . '' ..` '0 based on installed Code compliant features. ;no, ..... , ';' off': sc4 ' -IC7i Builder Signature: 74,'e2.-- Date: 5. Ip• I c.) I a � ' Address of New Home: V11(P Q 'xis Cit /FL Zip: fd P►•.� .. ���.4;-....-. _ 1CO�. . 39-9-33 • *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 4/21/2016 2:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: nip mtt.rk 1 00-rd(i J Permit Number: Atlantic Beach, FL, 3yy'fj MANDATORY REQUIREMENTS See individual code sections for full details. o 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law (Section 553.9085,Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. ❑ R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. O R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3.Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6.Supply and return registers,if installed at the time of the test,shall be fully open. O R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. O R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. • R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. o R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.2.2 Sealing(Mandatory)All ducts,air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99,Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 4/21/2016 2:28 PM EnergyGauge5 USA-FlaRes2014 -Section R405.4.1 Corn Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) ❑ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3., R403.3.1 Protection of piping insulation. ❑ R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. ❑ R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 1 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. ❑ R403.4.4 Water heater efficiencies(Mandatory). O R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. O R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. . R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. O R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 4/21/2016 2:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) O R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. O R403.6.1.2 Heating equipment capacity • R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. ▪ R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. • R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. O R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building,shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. ❑ R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. ▪ R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps.Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or • solar energy source computed over an operating season. ❑ RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights ❑ R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. O R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space, R-10 is allowed. 4/21/2016 2:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 3 of 3 • FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: RIVER3608-Main House Builder Name: Riverside Homes Street: ('�'a1(O,at 1?� t ar'' Permit Office: City of Atlantic Beach City,State,Zip: Atlantic Beach,FL, '2?33 Permit Number: Owner: Brankston Residence Jurisdiction: 261.300 Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. ✓ Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. r1 Exposed earth in unvented crawl spaces shall be covered with a Class I rJltk vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. ✓ Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. •/� Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 4/21/2016 2:30 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 • Job: RIveR3608Manual S Compliance Report wrightsoft° Date: 04/22/16 1st System By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksornille,FL 32256 Phone:904-722-8995 Fax:904-722-8944 Project Information For: Riverside Homes 12276 San Jose Boulevard, Suite#120, Jacksonville, FL 32223 Phone: 904-503-7055 Cooling Equipment Design Conditions Outdoor design DB: 93.0°F Sensible gain: 26071 Btuh Entering coil DB: 77.5°F Outdoor design WB:77.0°F Latent gain: 5166 Btuh Entering coil WB: 63.7°F Indoor design DB: 75.0°F Total gain: 31237 Btuh Indoor RH: 50% Estimated airflow: 1100 cfm Manufacturer's Performance Data atActual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NB036****B+FB4CNP036L Actual airflow: 1100 cfm Sensible capacity: 24260 Btuh 93% of load Latent capacity: 6380 Btuh 123% of load Total capacity: 30640 Btuh 98% of load SHR: 79% Heating Equipment Design Conditions Outdoor design DB: 32.0°F Heat loss: 29905 Btuh Entering coil DB: 68.8°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NB036****B+FB4CNP036L Actual airflow: 1100 cfm Output capacity: 33000 Btuh 110% of load Capacity balance: 30 °F Supplemental heat required: 0 Btuh Economic balance:-99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1100 cfm Output capacity: 10.5 kW 120% of load Temp. rise: 68 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Apr-22 09:25:39 wrightsoft Right-Suite®Universal 2017 17.0.01 RSU13256 Page 1 K ...Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE Manual S Compliance liance Report ort Job: RIveR3608 - - wrightsoftA Date: 04122;16 2nd System By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,F1.32256 Phone:904-722-8995 Fax:904-722-8944 Project Information For: Riverside Homes 12276 San Jose Boulevard, Suite #120, Jacksonville, FL 32223 Phone: 904-503-7055 Cooling Equipment Design Conditions Outdoor design DB: 93.0°F Sensible gain: 21769 Btuh Entering coil DB: 76.9°F Outdoor design WB:77.0°F Latent gain: 4066 Btuh Entering coil WB: 63.4°F Indoor design DB: 75.0°F Total gain: 25835 Btuh Indoor RH: 50% Estimated airflow: 953 cfm Manufacturer's Performance Data atActual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NB030****A+FB4CNP030L Actual airflow: 953 cfm Sensible capacity: 21000 Btuh 96% of load Latent capacity: 5470 Btuh 135% of load Total capacity: 26470 Btuh 102% of load SHR: 79% Heating Equipment Design Conditions Outdoor design DB: 32.0°F Heat loss: 23225 Btuh Entering coil DB: 69.0°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NB030****A+FB4CNP030L Actual airflow: 953 cfm Output capacity: 28600 Btuh 123% of load Capacity balance: 28 °F Supplemental heat required: 0 Btuh Economic balance:-99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 953 cfm Output capacity: 7.2 kW 106% of load Temp. rise: 76 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Apr-22 09:25:39 wrightsoft Right-Suite®Universal 2017 17.0.01 RSU13256 Page 2 AC K ...HOmes\ATLANTIC BEACH CCIABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE SummaryJob: RIVER3608 4 Wrl htsoft° Project Date: 04/22/16 9 Entire House By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksoneille,FL 32256 Phone:904-722-8995 Fax 904-722-8944 Pro'ect Information For: Riverside Homes 12276 San Jose Boulevard, Suite #120, Jacksonville, FL 32223 Phone: 904-503-7055 Notes: Lot 106,Atlantic Beach C. C. Brankston Residence - Main House Desi• n Information Weather: Jacksonville, Intl Airport, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 50 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 40112 Btuh Structure 32060 Btuh Ducts 13019 Btuh Ducts 14905 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 53131 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 46965 Btuh Method Detailed Latent Cooling Equipment Load Sizing Shielding 3 (partial) Stories 1 Structure 5275 Btuh Ducts 3957 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 3608 3608 Equipment latent load 9232 Btuh Volume (ft3) 34616 34616 Air changes/hour 0 0 Equipment total load 56197 Btuh Equiv.AVF (cfm) 0 0 Req. total capacity at 0.70 SHR 5.6 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 °F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-22 09:25:39 A- wrightsott' Right-Suite®Universal 2017 17.0.01 RSU13256 Page 1 ..Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE Job: RIVER3608 4 wrightsoft Project Summary Date: 04/22/16 9 1st System By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax:904-722-8944 Project Information For: Riverside Homes 12276 San Jose Boulevard, Suite#120, Jacksonville, FL 32223 Phone: 904-503-7055 Notes: Lot 106,Atlantic Beach C. C. Brankston Residence- Main House Desi• n Information Weather: Jacksonville, Intl Airport, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 50 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 22472 Btuh Structure 17290 Btuh Ducts 7433 Btuh Ducts 8781 Btuh Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 29905 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 26071 Btuh Method Detailed Latent Cooling Equipment Load Sizing Shielding 3 (partial) Stories 1 Structure 2900 Btuh Ducts 2266 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 2144 2144 Equipment latent load 5166 Btuh Volume (ft3) 21440 21440 Air changes/hour 0 0 Equipment total load 31237 Btuh Equiv.AVF (cfm) 0 0 Req. total capacity at 0.70 SHR 3.1 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model CH14NB036****B Cond CH14NB036****B AHRI ref 8068612 Coil FB4CNP036L AHRI ref 8068612 Efficiency 8.2 HSPF Efficiency 11.7 EER, 14 SEER Heating input Sensible cooling 23100 Btuh Heating output 33800 Btuh @ 47°F Latent cooling 9900 Btuh Temperature rise 28 °F Total cooling 33000 Btuh Actual air flow 1100 cfm Actual air flow 1100 cfm Air flow factor 0.037 cfm/Btuh Air flow factor 0.042 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.83 l!' Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-22 09:25:39 ^- WI'19�1t5Oft� Right-Suite®Universal 2017 17.0.01 RSU13256 Page 2 ir6ZPK...Homes'ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE • - Pro ect Summar Job: R/22/1608 wrightsoft Y ate: 2nd System By: DRS H6 A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax:904-722-8944 Pro'ect Information For: Riverside Homes 12276 San Jose Boulevard, Suite #120, Jacksonville, FL 32223 Phone: 904-503-7055 Notes: Lot 106,Atlantic Beach C. C. Brankston Residence - Main House Desi• n Information Weather: Jacksonville, Intl Airport, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 50 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 17639 Btuh Structure 15367 Btuh Ducts 5586 Btuh Ducts 6402 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23225 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 21769 Btuh Method Detailed Latent Cooling Equipment Load Sizing Shielding 3 (partial) Stories 1 Structure 2375 Btuh Ducts 1691 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 1464 1464 Equipment latent load 4066 Btuh Volume (ft3) 13176 13176 Air changes/hour 0 0 Equipment total load 25835 Btuh Equiv.AVF (cfm) 0 0 Req. total capacity at 0.70 SHR 2.6 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model CH14NB030****A Gond CH14NB030****A AHRI ref 7835429 Coil FB4CNP030L AHRI ref 7835429 Efficiency 8.2 HSPF Efficiency 11.7 EER, 14 SEER Heating input Sensible cooling 20020 Btuh Heating output 28600 Btuh @ 47°F Latent cooling 8580 Btuh Temperature rise 27 °F Total cooling 28600 Btuh Actual air flow 953 cfm Actual air flow 953 cfm Air flow factor 0.041 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.84 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Apr-22 09:25:39 -iii- wrightsoft' Right-Suite®Universal 2017 17.0.01 RSU13256 Page 3 ACCP. ...HomesVATLANTIC BEACH CCVABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE • 4 wrightsoft Rig ht-J®Worksheet Job: RIVER3608 Entire House Byte: 04!22/16 By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax 904-722-8944 1 Room name Entire House 1st System 2 Exposed wall 391.3 ft 211.3 ft 3 Room height 9.6 ft 10.0 ft 4 Room dimensions 5 Room area 3608.0 ft' 2144.0 ft2 Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12E-Osw 0.068 ne 2.58 1.46 918 869 2245 1270 508 484 1251 708 3A-2ov 0.350 ne 13.30 22.99 24 0 319 552 24 0 319 552 3A-2ov 0.350 ne 13.30 30.99 25 0 333 775 0 0 0 0 ,., 12E-Osw 0.068 se 2.58 1.46 684 516 1333 754 283 188 486 275 11 3A-2ov 0.350 se 13.30 24.00 71 0 944 1704 71 0 944 1704 3A-2ov 0.350 se 13.30 32.00 73 5 971 2336 0 5 0 0 D 11J0 0.600 se 22.80 18.36 24 24 547 441 24 24 547 441 16 12E-Osw 0.068 sw 2.58 1.46 894 797 2059 1165 493 441 1140 645 3A-2ov 0.350 sw 13.30 24.00 52 0 692 1248 52 0 692 1248 3A-2ov 0.350 sw 13.30 32.00 45 14 599 1440 0 14 0 0 bp12E-Osw 0.068 nw 2.58 1.46 946 681 1760 996 545 324 837 474 3A-2ov 0.350 nw 13.30 22.99 221 0 2939 5081 221 0 2939 5081 3A-2ov 0.350 nw 13.30 30.99 44 0 585 1364 0 0 0 0 I12B-0sw 0.097 - 3.69 1.73 257 236 870 407 257 236 870 407 D 11 JO 0.600 se 22.80 18.36 21 21 479 386 21 21 479 386 P 166-15ad 0.061 - 2.32 3.30 91 91 211 300 29 29 67 96 C 16A-21ad 0.044 n 1.67 3.26 2144 2144 3585 6990 680 680 1137 2217 F 19A-19bscp 0.049 - 0.00 0.00 0 0 0 0 0 0 0 0 F 20P-19t 0.050 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A-tph 1.358 n 51.60 0.00 2144 381 19640 0 2144 209 10765 0 6 c)AED excursion 0 597 Envelope loss/gain 40112 27210 22472 14830 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 5 1150 2 460 Appliances/other 3700 2000 Subtotal(lines 6 to 13) 40112 32060 22472 17290 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 40112 32060 22472 17290 15 Duct loads 32% 47% 13019 14905 33% 51% 7433 8781 Total room bad 53131 46965 29905 26071 Air required(cfm) 2053 2053 1100 1100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Wf 1 ht30ft' 2016-Apr-22 09:25:39 . '. 9 Right-Suite®Universal 2017 17.0.01 RSU13256 Page 1 ..Homes1ATLANTIC BEACH CCIABCC106(Brankston).rup Cato=MJ8 Front Door faces:SE wrightsoft Right-J®J®Worksheet Job: RIVER3608 4 Date: 04/22/16 Entire House By: DRS A/C Masters HVAC, Inc. 445 Tresca Road.Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax 904-722-8944 1 Room name 2nd System 2 Exposed wall 180.0 ft 3 Room height 9.0 ft 4 Room dimensions 5 Room area 1464.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area Load number (Btuh/ft'-°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1qJ 12E-Osw 0.068 ne 2.58 1.46 410 385 995 563 L�_GG 3A-2ov 0.350 ne 13.30 22.99 0 0 0 0 3A-2ov 0.350 ne 13.30 30.99 25 0 333 775 UUU��flll12E-0sw 0.068 se 2.58 1.46 401 328 848 480 11 3A-20 v 0.350 se 13.30 24.00 0 0 0 0 3A-2ov 0.350 se 13.30 32.00 73 0 971 2336 D 11J0 0.600 se 22.80 18.36 0 0 0 0 Val 12E-Osw 0.068 sw 2.58 1.46 401 356 920 520 ll-GG 3A-2ov 0.350 sw 13.30 24.00 0 0 0 0 3A-2ov 0.350 sw 13.30 32.00 45 0 599 1440 1Q1 12E-Osw 0.068 nw 2.58 1.46 401 357 922 522 ;I C, 3A-2ov 0.350 nw 13.30 22.99 0 0 0 0 G 3A-2ov 0.350 nw 13.30 30.99 44 0 585 1364 R 128-0aw 0.097 - 3.69 1.73 0 0 0 0 I D 11 J0 0.600 se 22.80 18.36 0 0 0 0 P 16B-15ad 0.061 - 2.32 3.30 62 62 144 205 C 16A-21ad 0.044 n 1.67 3.26 1464 1464 2448 4773 F 19A-19bscp 0.049 - 0.00 0.00 0 0 0 0 F 20P-19t 0.050 - 0.00 0.00 0 0 0 0 F 22A-tph 1.358 n 51.60 0.00 0 172 8876 0 , 6 c)AED excursion 0 Envelope loss/gain 17639 12977 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 3 690 Appliances/other 1700 Subtotal(lines 6 to 13) 17639 15367 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 17639 15367 15 Duct loads 32% 42% 5586 6402 Total room load 23225 21769 Air required(cfm) 953 953 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wri htsoft• Ri 9 2016-Apr-22 09:25:39 9 ht-Suite®Universal 2017 17.0.01 RSU13256 Page 2 ..Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE 4 wrightsoft Rig ht-J®Worksheet Job: RIVER3608 1st System Byte: 116 By: DRS A/C Masters HVAC, Inc. 1 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax:904-722-8944 1 Room name 1st System 1st Floor 2 Exposed wall 211.3 ft 211.3 ft 3 Room height 10.0 ft 10.0 ft heat/cool 4 Room dimensions 2144.0 x 1.0 ft 5 Room area 2144.0 ft' 2144.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft'-°F) (Btuh/ftl or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12E-Osw 0.068 ne 2.58 1.46 508 484 1251 708 508 484 1251 708 3A-2ov 0.350 ne 13.30 22.99 24 0 319 552 24 0 319 552 3A-2ov 0.350 ne 0.00 0.00 0 0 0 0 0 0 0 0 12E-Osw 0.068 se 2.58 1.46 283 188 486 275 283 188 486 275 11 3A-2ov 0.350 se 13.30 24.00 71 0 944 1704 71 0 944 1704 11-Gp 3A-2ov 0.350 se 0.00 0.00 0 5 0 0 0 3 0 0 1 11 JO 0.600 se 22.80 18.36 24 24 547 441 24 24 547 441 k612E-Osw 0.068 sw 2.58 1.46 493 441 1140 645 493 441 1140 645 3A-2ov 0.350 sw 13.30 24.00 52 0 692 1248 52 0 692 1248 3A-2ov 0.350 sw 0.00 0.00 0 14 0 0 0 7 0 0 b12E-Osw 0.068 nw 2.58 1.46 545 324 837 474 545 324 837 474 3A-2ov 0.350 nw 13.30 22.99 221 0 2939 5081 221 0 2939 5081 3A-2ov 0.350 nw 0.00 0.00 0 0 0 0 0 0 0 0 q 12B-0sw 0.097 3.69 1.73 257 236 870 407 257 236 870 407 l-D 11 JO 0.600 se 22.80 18.36 21 21 479 386 21 21 479 386 P 16B-15ad 0.061 - 2.32 3.30 29 29 67 96 29 29 67 96 C 16A-21 ad 0.044 n 1.67 3.26 680 680 1137 2217 680 680 1137 2217 F 19A-19bscp 0.049 - 0.00 0.00 0 0 0 0 0 0 0 0 F 20P-19t 0.050 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A-tph 1.358 n 51.60 0.00 2144 209 10765 0 2144 209 10765 0 6 c)AED excursion 597 597 Envelope loss/gain 22472 14830 22472 14830 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 2 460 Appliances/other 2000 2000 Subtotal(lines 6 to 13) 22472 17290 22472 17290 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 22472 17290 22472 17290 15 Duct loads 33% 51% 7433 8781 33% 51% 7433 8781 Total room load 29905 26071 29905 26071 Air required(cfm) 1100 1100 1100 1100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. WPI htsoft' 2016-Apr-22 09:25:39 9 Right-Suite®Universal 2017 17.0.01 RSU13256 Page 3 ..Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE 4 wrightsoft Right-J®Worksheet Job: RIVER3608 Date: 04/22/16 2nd System By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax 904-722-8944 1 Room name 2nd System 2nd Floor 2 Exposed wall 180.0 ft 180.0 ft 3 Room height 9.0 ft 9.0 ft heat/cool 4 Room dimensions 1464.0 x 1.0 ft 5 Room area 1464.0 W 1464.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/ft2°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 6 12E-Osw 0.068 ne 2.58 1.46 410 385 995 563 410 385 995 563 3A-2ov 0.350 ne 0.00 0.00 0 0 0 0 0 0 0 0 3A-2ov 0.350 ne 13.30 30.99 25 0 333 775 25 0 333 775 12E-Osw 0.068 se 2.58 1.46 401 328 848 480 401 328 848 480 11D 3A-2ov 0.350 se 0.00 0.00 0 0 0 0 0 0 0 0 3A-2ov 0.350 se 13.30 32.00 73 0 971 2336 73 0 971 2336 11,10 0.600 se 0.00 0.00 0 0 0 0 0 0 0 0 W 12E-Osw 0.068 sw 2.58 1.46 401 356 920 520 401 356 920 520 -G 3A-2ov 0.350 sw 0.00 0.00 0 0 0 0 0 0 0 0 --G 3A-2ov 0.350 sw 13.30 32.00 45 0 599 1440 45 0 599 1440 b12E-Osw 0.068 nw 2.58 1.46 401 357 922 522 401 357 922 522 3A-2ov 0.350 nw 0.00 0.00 0 0 0 0 0 0 0 0 3A-2ov 0.350 nw 13.30 30.99 44 0 585 1364 44 0 585 1364 11--D 12B-0sw 0.097 - 0.00 0.00 0 0 0 0 0 0 0 0 L-D 11 JO 0.600 se 0.00 0.00 0 0 0 0 0 0 0 0 P 16B-15ad 0.061 - 2.32 3.30 62 62 144 205 62 62 144 205 C 16A-21 ad 0.044 n 1.67 3.26 1464 1464 2448 4773 1464 1464 2448 4773 F 19A-19bscp 0.049 - 0.00 0.00 0 0 0 0 0 0 0 0 F 20P-19t 0.050 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A-tph 1.358 n 51.60 0.00 0 172 8876 0 0 172 8876 0 6 c)AED excursion 0 0 Envelope loss/gain 17639 12977 17639 12977 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 3 690 3 690 Appliances/other 1700 1700 Subtotal(lines 6 to 13) 17639 15367 17639 15367 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 17639 15367 17639 15367 15 Duct loads 32% 42% 5586 6402 32% 42% 5586 6402 Total room load 23225 21769 23225 21769 Air required(cfm) 953 953 953 953 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Wri htscef - 2016-Apr-22 09:25:39 •4e--6116` Right-Suitee®Universal 2017 17.0.01 RSU13256 Page 4 ..Homes 1ATLANTIC BEACH CC 1ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE Building Analysis Job: RIveR3608 4 wrightsoft° Date: DRS/16 B Entire House Y A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville,FL 32256 Phone:904-722-8995 Fax 904-722-8944 Pro'ect Information For: Riverside Homes 12276 San Jose Boulevard, Suite #120, Jacksonville, FL 32223 Phone: 904-503-7055 Design Conditions Location: Indoor: Heating Cooling Jacksonville, Intl Airport, FL, US Indoor temperature (°F) 70 75 Elevation: 30 ft Design TD (°F) 38 18 Latitude: 31°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 11.5 50.0 Dry bulb (°F) 32 93 Infiltration: Daily range (°F) - 18 ( M ) Method Detailed Wet bulb (°F) - 77 Shielding 3 (partial) Wind speed (mph) 15.0 7.5 Stories 1 Heatin• Component Btuh/ft2 Btuh % of load Walls 2.7 8479 16.0 "" a Glazing 13.3 7382 13.9 1 Doors 22.8 1026 1.9 Ceilings 1.7 3585 6.7 Floors 9.2 19640 37.0 Infiltration 0 0 0 Ducts 13019 24.5 c.,..Piping 0 0 Humidification 0 0 C l 5. Ventilation 0 0 F.— Adjustments 0 Total 53131 100.0 Coolin • Component Btuh/ft2 Btuh % of load Walls 1.5 4893 10.4 ,.`mai „ Glazing 26.1 14500 30.9 Doors 18.4 826 1.8 Ceilings 3.3 6990 14.9 Floors 0 0 0 Infiltration 0 0 0 __E Ducts 14905 31.7 Ventilation 0 0 Internal gains 4850 10.3 Blower 0 0 Adjustments 0 Total 46965 100.0 Other Goings Latent Cooling Load = 9232 Btuh Overall U-value = 0.131 Btuh/ft2-°F Data entries checked. Wrl htsOft' 2016-Apr-22 09:age 1 �.�„ � 9 Right-Suite®Universal 2017 17.0.01 RSU13256 Page 1 ACCP. ...Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE Job: RIVER3608 4 wrightsoft Building Analysis Date: DRS 04/22/16 1st System Y A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville, FL 32256 Phone:904-722-8995 Fax 904-722-8944 Pro'ect Information For: Riverside Homes 12276 San Jose Boulevard, Suite#120, Jacksonville, FL 32223 Phone: 904-503-7055 Desi• n Conditions Location: Indoor: Heating Cooling Jacksonville, Intl Airport, FL, US Indoor temperature (°F) 70 75 Elevation: 30 ft Design TD (°F) 38 18 Latitude: 31 °N Relative humidity (%) 30 50 Moisture difference (gr/lb)Heating Cooling 11.5 50.0 Dry bulb (°F) 32 93 Infiltration: Daily range (°F) - 18 ( M ) Method Detailed Wet bulb (°F) - 77 Shielding 3 (partial) Wind speed (mph) 15.0 7.5 Stories 1 Heatin • Component Btuh/ft2 Btuh % of load Walls 2.7 4650 15.6 w' Glazing 13.3 4894 16.4 Doors 22.8 1026 3.4 Ceilings 1.7 1137 3.8 Floors 5.0 10765 36.0 11 Infiltration 0 0 0 Ducts 7433 24.9 Piping 0 0 Humidification 0 0 Celery, Ventilation 0 0 Floors Adjustments 0 Total 29905 100.0 Coolin• Component Btuh/ft2 Btuh % of load Ga Walls 1.5 2604 10.0 WWMme. . Glazing 25.0 9182 35.2 Doors 18.4 826 3.2 Ceilings 3.3 2217 8.5 Floors 0 0 0 Infiltration 0 0 0 Ducts 8781 33.7 Glazes _Ducts Ventilation 0 0 Internal gains 2460 9.4 Blower 0 0 Adjustments 0 Total 26071 100.0 G,,,; CAIN, Latent Cooling Load = 5166 Btuh Overall U-value = 0.120 Btuh/ft2-°F Data entries checked. At Wrl htsoft' 2016-Apr-22 09:25:41 ` 9 Right-Suite®Universal 2017 17.0.01 RSU13256 Page 2 ...HomestATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE Building Analysis Job: RIveR3608 41- wri htsoft° Date: 04/22/16 9 2nd System By: DRS A/C Masters HVAC, Inc. 445 Tresca Road,Suite#204,Jacksonville.FL 32256 Phone:904-722-8995 Fax:904-722-8944 Pro'ect Information For: Riverside Homes 12276 San Jose Boulevard, Suite #120, Jacksonville, FL 32223 Phone: 904-503-7055 Design Conditions Location: Indoor: Heating Cooling Jacksonville, Intl Airport, FL, US Indoor temperature (°F) 70 75 n TD (°F) 38 18 Desi Elevation: 30 ft 9 Latitude: 31°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 11.5 50.0 Dry bulb (°F) 32 93 Infiltration: Daily range (°F) - 18 ( M ) Method Detailed Wet bulb (°F) - 77 Shielding 3 (partial) Wind speed (mph) 15.0 7.5 Stories 1 Heatin• Component Btuh/ft2 Btuh % of load Walls 2.6 3829 16.50,c, Glazing 13.3 2487 10.7 Doors 0 0 0 Ceilings 1.7 2448 10.5 Floors 0 8876 38.2 Infiltration 0 0 0 Ducts 5586 24.1 Piping 0 0 Ceings Humidification 0 0 Ventilation 0 0 Floor Adjustments 0 Total 23225 100.0 Coolin• Component Btuh/ftz Btuh % of load Walls 1.5 2289 10.5 Glazing 31.6 5915 27.2 Doors 0 0 0 Ceilings 3.3 4773 21.9 Floors 0 0 0 Infiltration 0 0 0 Gam,°, -- Ducts 6402 29.4 iiii110—_cua. Ventilation 0 0 Internal gains 2390 11.0 Blower 0 0 Adjustments 0 Total 21769 100.0 c.,, Latent Cooling Load = 4066 Btuh Overall U-value = 0.148 Btuh/ft2-°F Data entries checked. - rightsoft- 9 2016-Apr-22 09:a ! 41 .�, - wRi ht-Suite®Universal 2017 17.0.01 RSU13256 Page 3 AI.C.P.....Homes\ATLANTIC BEACH CC\ABCC106(Brankston).rup Calc=MJ8 Front Door faces:SE N , , €}i -tP �W ss;r.rg a v o ON A� . 14 g 3^ 1 fti s W '414 3 0 o 8dotii . g I it COen p Or oC I 14 iii9 i lli i 1 If ae r s: • ---,ter >tis ==� t ,�j k ii, # Aigg ^ i a tp ii G N N Z d Ii P S tl b §Iiiiii :$' ;I ail 11 II $f mom` .,,..., uu��M N 6b < li !Ili li � RFI■1. � e� 1 ucv :�_ Ti o....0.6µ. IT!: n �gb� Y Illl�� p3c .6 r U NO r ii 11i 111M11 t CI- @a R E <ez . /(1)-- il iLi .ha..R , Q :I„ ws ,,, n 74--4'.” 1 --- , , - _ Lie R $ • � IC 11116111111 I a ° i$ ' ftp: <`"":r, :a I. ri F. SII rf 1 E • it 1 „ ---- IIR 22 _ :: 1 I�IIIIIId��_ o �R R LI�Q I. ,< �; n _�i o l vt �.� to �— a a+ s ,. t..r- t e k 1 '" a )c'l li, - , e $ {:x e� 1i it x: ,, ! • -. ILI • , ii >--m -ki k{z € g E. o Y.` _- SOC oz iia L b R w 111it ji t, i: µ66.c If a y ".a : 1 � b.a ' Q3I! } i r o. ae -.a .c 1 `1 au — ., .a a • 4 I \ 1 ! Oa s I-1-1 Cr) z 8 rn $ l P e CwIa R � 1 ° _ gl 1 s t= g it 2f II li'll 1 i., f — =1 ; q .`,1, ! _, F I avna.. t i it Nil f .(kOr hail 3t,t ria.ar.i .73 o �1 w+o.row 4i j l�p�li 1=k . iii ini 0 ill! o I ,. tl g . i ' g 'ow !g{ a !Y • B ' d i : .4 Plipoc‘ ii_ LL A"I. 7--- MI Al FA MIA tn... I r ......, . .-. .0.- 1..17*.r • �a 3 •I .l , Z (D_ iv , .. 04 IPA �l - rt"-,,,,74., N . mil sii_rommil „,____ ,,w ..... K µ n.. ,—p av ret r4. .. w ewe as -•. S:. 4?, _ir al. 1 ' 8 ,E �.� :alto .�. o gado'vi 1,rili do� 1'i1C�ar,6e - ° Z oz 1 ` 417' 4 2 -� 1_"__�_ —,1 . .--.. ..� IN. ae—.2 I N 4 Ilb I IA da 1 1 u� e r � 9 �� a !Y:„x.08 1:11 ().” - ' A It fti11111 ili 1 1f .,i.. w ea .. .. of a ♦ry