Loading...
350 3RD ST - ENERGY SHEETS OFFICE COPY EZ ICC EVALUATION Y. �• SERVICE ICC-ES Report ICC-ES I (800)423-6587 I (562) 699-0543 I www.icc-es.org This report is sub DIVISION:07 00 00—THERMAL AND MOISTURE PROTECTION SECTION:07 2100—THERMAL INSULATION REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING,TEXAS 77388-4405 EVALUATION SUBJECT: SUCRASEALTM 0.5 AND SES FOAM 0.5 LB SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION i:1)-- ICC ICC ICC T � . SMG LISTED Look for the trusted marks of Conformity! \V.\ ICC RIM "2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC)Award in Excellence" A Subsidiary of coot coanc« • SCC,�cr.tt.d ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not ��� cerrs specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service,LLC, express or implied, as nxii acccuro vn9•xn MPS to any finding or other matter in this report,or as to any product covered by the report. °^ '.,003 ° u ccn .b„ Copyright© 2015 ICC Evaluation Service,LLC.All rights reserved. EZ ICC EVALUATION • SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report7SR-3375 Reissued August 2014 Corrected November 2015 This report is subject to renewal August 2016. I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE 3.0 DESCRIPTION PROTECTION 3.1 General: Section: 07 21 00—Thermal Insulation SucrasealT" 0.5 spray foam insulation is a two- REPORT HOLDER: component, open cell, one-to-one-by-volume spray- applied polyurethane foam system with a nominal density SES FOAM of 0.5 pcf (8.0 kg/m3). The insulation's liquid components 4008 LOUETTA ROAD,#538 are supplied in nominally 55-gallon drums, labeled as "A" SPRING,TEXAS 77388-4405 component or "B" component. The insulation components (713)239-0252 have a shelf life of six months when stored in unopened containers at temperatures between 70°F (21°C)and 90°F (32°C). EVALUATION SUBJECT: 3.2 Surface-burning Characteristics: SUCRASEALTM 0.5 AND SES FOAM 0.5 LB SPRAY: At a maximum thickness of 4 inches (102 mm) and a SPRAY-APPLIED POLYURETHANE FOAM PLASTIC nominal density of 0.5 pcf, the insulation has a flame- INSULATION spread index of 25 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E84. 1.0 EVALUATION SCOPE Thicknesses for wall cavities and ceiling cavities are not limited when the insulation is covered with a minimum Compliance with the following codes: 1/2-inch-thick (12.7 mm) gypsum board installed in • 2012 and 2009 International Building Code®(IBC) accordance with the applicable code. 3.3 Thermal Resistance(R-values): • 2012 and 2009 International Residential Code®(IRC) The insulation has thermal resistance(R-values)at a mean • 2012 and 2009 International Energy Conservation temperature of 75°F(24°C)as shown in Table 1. Code®(IECC) 3.4 Air Permeability: • Other Codes(see Section 8.0) The insulation, at a minimum thickness of 3 inches Properties evaluated: (76 mm), is considered air-impermeable in accordance with IRC Section R202, based on testing in accordance • Surface-burning characteristics with ASTM E283. 3.5 DC 315 Fireproof Paint: • Physical properties • Thermal resistance(R values) DC 315 Fireproof Paint is manufactured by International Fireproof Technology, Inc., and is a water-based coating • Air permeability supplied in 5-gallon (19 L) pails and 55-gallon (208 L) drums and has a shelf life of six months when stored in a • Exterior walls in Types I-IV construction factory-sealed container at temperatures between 50°F 2.0 USES (10°C)and 90°F(32°C). 3.6 FireShell®F10E: SucrasealTM 0.5 spray polyurethane foam plastic insulation © 2 is used as a nonstructural thermal insulating material in FireShell F10E is manufactured by TPR , and is a water buildings of Type I, II, Ill, IV and V (IBC)construction, and based coating supplied in 5-gallon (19 L) pails and in dwellings built under the IRC. The insulation is for use in 55-gallon (208L) drums and has a shelf life of one year wall cavities and floor/ceiling assemblies, and in attics and when stored in a factory-sealed container at temperatures crawl spaces when installed as described in Section 4.4. above 45°F (7°C). Under the IRC, the insulation may be used as air- 4.0 INSTALLATION impermeable insulation when installed as described in 4.1 General: Section 3.4. SES Foam 0.5 lb Spray is identical to SucraseallM 0.5. Wherever SucraseallM 0.5 is mentioned, SucrasealiM 0.5 spray insulation must be installed in the same property applies to SES Foam 0.5 lb Spray. accordance with the manufacturer's published installation ICC-ES Evaluation Reports are not to be construed ac representing aesthetics or any other attributes not specifically addressed,nor are they to be construed 111 CI) as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service.LLC.express or implied,as to any finding or other matter in this report,or as to any product covered by the report. [9.= Copyright©2015 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 4 • ESR-3375 I Most Widely Accepted and Trusted Page 2 of 4 instructions and this report. A copy of the manufacturer's applied in one or more coats with brush, roller or airless published installation instructions must be available at all spray equipment. times on the jobsite during installation. 4.4 Attics and Crawl Spaces: 4.2 Application: 4.4.1 Application with a Prescriptive Ignition Barrier: The insulation is spray-applied at the jobsite using a When SucrasealTM 0.5 spray is installed within attics and volumetric positive displacement pump as identified in the crawl spaces, where entry is made only for service of SucrasealrM 0.5 spray application manual. The insulation utilities, an ignition barrier must be installed in accordance components must be stored at temperatures between with IBC Section 2603.4.1.6 or IRC Section R316.5.3 or 70°F (21°C) and 90°F (32°C) for several days before R316.5.4, as applicable, except when the installation is in application. The insulation must not be used in areas that accordance with Section 4.4.2 or Section 4.4.3. The have maximum in-service temperatures greater than 180°F ignition barrier must be consistent with the requirements (82°C). The insulation must not be used in electrical outlet for the type of construction required by the applicable or junction boxes or in contact with water (e.g., rain, code, and must be installed in a manner so that the foam condensation, ice, snow) or soil. The substrate must be plastic insulation is not exposed. SucrasealTM 0.5 spray free of moisture, frost or ice, loose scales, rust, oil, grease insulation at a minimum thickness of 3 inches (76 mm) or other surface contaminants. The insulation can be may be installed in unvented attics in accordance with installed in one pass to the maximum thickness. The 2012 IRC Section R806.5 (2009 IRC Section R806.4), as spray-applied foam insulation must be protected from applicable. weather during and after installation. 4.4.2 Application without a Prescriptive Ignition 4.3 Thermal Barrier: Barrier: Where the spray-applied insulation is installed in 4.3.1 Application with a Prescriptive Thermal Barrier: accordance with this section or Section 4.4.3, the following SucrasealTM 0.5 spray insulation must be separated from conditions apply: the interior of the building by an approved thermal barrier a) Entry to the attic or crawl space is to service utilities, of 1/2-inch-thick (12.7 mm) gypsum wallboard or an and no storage is permitted. equivalent 15-minute thermal barrier complying with, and installed in accordance with, IBC Section 2603.4 or IRC b) There are no interconnected attic or crawl space Section R316.4, as applicable, except when the installation areas. is in accordance with Section 4.3.2.Within an attic or crawl c) Air in the attic or crawl space is not circulated to other space, installation must be in accordance with Section 4.4. parts of the building. 4.3.2 Application without a Prescriptive Thermal d) Attic ventilation is provided when required by IBC Barrier: The prescriptive 15-minute thermal barrier may be Section 1203.2 or IRC Section R806, except when omitted when installation is in accordance with this section. air-impermeable insulation is permitted in unvented The insulation and coating may be spray-applied to the attics in accordance with 2012 IRC Section R806.5 or interior facing of walls and the underside of roof sheathing 2009 IRC Section R806.4. Under-floor (crawl space) or roof rafters, and in crawl spaces, and may be left ventilation is provided when required by IBC Section exposed as an interior finish without a prescribed 1203.3 or IRC Section R408.1,as applicable. 15-minute thermal barrier or prescribed ignition barrier when the installation is in accordance with either Sections e) Combustion air is provided in accordance with 4.3.2.1 or 4.3.2.2. International Mechanical Code°Section 701. 4.3.2.1 Application with DC 315 Fireproof Paint The In attics, the insulation may be spray-applied to the thickness of the foam plastic applied to the underside of underside of roof sheathing or roof rafters, and/or vertical roof sheathing and to vertical wall surfaces must not surfaces, and in crawl spaces the insulation may be spray- exceed 111/2 inches (292 mm). The foam plastic must be applied to the underside of floors and/or vertical surfaces covered on all surfaces with DC 315 Fireproof Paint at a as described in this section. The thickness of the foam minimum thickness of 18.0 mils (0.47 mm) wet film plastic applied to the underside of the top of the space thickness [12 mils (0.30 mm) dry film thickness] with a must not exceed 12 inches(305 mm). The thickness of the minimum application rate of 1.12 gal/100 ft2. The coating foam plastic applied to vertical surfaces must not exceed must be applied over the SucrasealTM 0.5 insulation in 111/2 inches (292 mm). The foam plastic may be installed accordance with the coating manufacturer's published without a covering or coating. The insulation may be instructions and this report. Surfaces to be coated must be installed in unvented attics in accordance with 2012 IRC dry, clean and free of dirt, loose debris and other Section R806.5 (2009 IRC Section R806.4). The ignition substances that could interfere with adhesion of the barrier in accordance with IBC Section 2603.4.1.6 or IRC coating. The coating is applied in one or more coats with Section R316.5.3 may be omitted. brush, roller or airless spray equipment. 4.4.3 Use on Attic Floors: SucrasealT" 0.5 spray 4.3.2.2 Application with FireShell®F10E: The thickness insulation may be installed exposed at a maximum of the foam plastic applied to the underside of roof thickness of 11 '/2 inches (292 mm) between joists in attic sheathing and to vertical wall surfaces must not exceed floors. The ignition barrier in accordance with IBC Section 111/2 inches (292 mm). The foam plastic must be covered 2603.4.1.6 or IRC Section R316.5.3 may be omitted. The on all surfaces with FireShelle F10E at a minimum insulation must be separated from the interior of the thickness of 20.0 mils (0.51 mm) wet film thickness building by an approved thermal barrier. [14 mils (0.36 mm) dry film thickness] with a minimum 4.5 Exterior Walls of Type I,II,Ill and IV Construction: application rate of 1.25 gal/100 ft2. The coating must be applied over the SucrasealTM 0.5 insulation in accordance 4.5.1 General:When used on walls of Type I, II, Ill and IV with the coating manufacturer's published instructions and exterior wall construction, the SucrasealTM 0.5 spray- this report. Surfaces to be coated must be dry, clean and applied foam insulation must comply with Section free of dirt, loose debris and other substances that could 2603.5 of the IBC and this section. The potential heat interfere with adhesion of the coating. The coating is of SucrasealTM 0.5 spray-applied foam insulation is ESR-3375 I Most Widely Accepted and Trusted Page 3 of 4 466 Btu/ft2(5.26 MJ/m2)per inch of thickness when tested 6.2 Reports of room corner fire-testing in accordance with in accordance with NFPA 259. NFPA 286. 4.5.2 Specific Wall Assemblies: Wall assemblies must 6.3 Report of air permeance testing in accordance with be as described in Table 2. ASTM E283. 5.0 CONDITIONS OF USE 6.4 Report of potential heat testing in accordance with The SucrasealTM 0.5 spray polyurethane foam plastic NFPA 259. insulation described in this report complies with, or is a 6.5 Report of fire propagation testing in accordance with suitable alternative to what is specified in, those codes NFPA 285. listed in Section 1.0 of this report, subject to the following 6.6 Engineering evaluation extending NFPA 285 testing conditions: to various exterior wall constructions. 5.1 The insulation must be installed in accordance with 7.0 IDENTIFICATION the manufacturer's published installation instructions, this evaluation report and the applicable code. If there Components of the SucrasealTM 0.5 spray polyurethane are any conflicts between the manufacturers foam plastic insulation are identified with the published installation instructions and this report, this manufacturers name (SES Foam) and address; the date report governs. of manufacture or the lot number; the product trade name (SucrasealTM 0.5 ); the mixing instructions; the density; the 5.2 The insulation must be separated from the interior of flame-spread and smoke-developed indices; and the the building by an approved 15-minute thermal evaluation report number(ESR 3375). barrier, as described in Section 4.3.1, except when the installation is in accordance with Section 4.3.2. 8.0 OTHER CODES Installation in an attic or crawl space must be as In addition to the codes referenced in Section 1.0, the described in Section 4.4. products in the report were evaluated for compliance with 5.3 The insulation must not exceed the thicknesses noted the requirements of the following codes: in Sections 3.2, 4.3,and 4.4. • 2006 International Building Code° 5.4 The insulation must be protected from exposure to the ■ 2006 International Residential Code° weather during and after application. 5.5 The insulation must be applied by contractors certified • 2006 International Energy Conservation Code by SES Foam. The products comply with the above mentioned codes as described in Sections 2.0 through 7.0 of this report, with 5.6 Use of the insulation in areas where the probability of revisions as noted below: termite infestation is "very heavy" must be in accordance with 2012 IBC Section 2603.9 (2009 IBC ■ Application with and without a Prescriptive Thermal Section 2603.8)or IRC Section R318.4,as applicable. Barrier: See Section 4.3, except the approved thermal barrier must be installed in accordance with Section 5.7 Jobsite certification and labeling of the insulation must R314.4 of the 2006 IRC. comply with IRC Sections N1101.4 and N1101.4.1 and IECC Sections R303.1.1 and 303.1.1.1, as • Application with a Prescriptive Ignition Barrier: See applicable. Section 4.4.1, except an ignition barrier must be installed in accordance with Section R314.5.3 or 5.8 When use is on exterior wall of buildings of Type I, II, R314.5.4 of the 2006 IRC. III or IV construction, construction must be as described in Section 4.5 and Table 2. ■ Application without a Prescriptive Ignition Barrier: See Section 4.4.2, except that combustion air is 5.9 A vapor retarder must be installed in accordance with provided in accordance with Sections 701 and 703 of the requirements of the applicable code. the 2006 IECC. 5.10 SucrasealT" 0.5 spray polyurethane foam plastic • Protection against Termites: See Section 5.6, except insulation is produced in St. Louis, Missouri, under a use of the insulation in areas where the probability of quality-control program with inspections by ICC-ES. termite infestation if"very heavy"must be in accordance 6.0 EVIDENCE SUBMITTED with Section R320.5 of the 2006 IRC. 6.1 Data in accordance with the ICC-ES Acceptance • Jobsite Certification and Labeling: See Section 5.7, Criteria for Spray-applied Foam Plastic Insulation except jobsite certification and labeling must comply (AC377), dated November 2012 (editorially corrected with Sections 102.1.1 and 102.1.1.1, as applicable, of April 2013), including reports of tests in accordance the 2006 IECC. with Appendix X of AC377. ESR-3375 I Most Widely Accepted and Trusted Page 4 of 4 TABLE 1—THERMAL RESISTANCE(R-VALUES'`) THICKNESS(inches) R-VALUE(°F.ft2•h/Btu) 1 4.0 2 7.6 3 11 3.5 13 4 15 5 19 6 22 7 26 8 30 9 33 10 37 11 41 12 44 For SI: 1 inch=25.4 mm,1°F•ft2'h/Btu=0.176 110K•m2/W. 'R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. TABLE 2—NFPA 285 COMPLYING EXTERIOR WALL ASSEMBLIES WALL COMPONENT MATERIALS 1 –Concrete wall 2–Concrete Masonry wall Base wall system–Use either 3–1 layer of 5/8-inch thick Type X gypsum wallboard installed on the interior side of minimum 3-5/8 inch 1,2,or 3 deep minimum 20 gauge thick steel studs spaced a maximum of 24-inch on center.Lateral bracing installed minimum every 4 ft.vertically or as required.Wall stud cavities shall be filled at each floor line with minimum 4 Ib/ft5 mineral-fiber insulation friction fit between steel wall studs. Resilient Channel–For use 1 –None with Base Wall System 3 above 2–Double leg"hat"shaped steel resilient channel installed perpendicular to the wall studs(interior side –Use either 1 or 2 only)and spaced a maximum of 24-inches on center between steel studs and Type X gypsum wallboard. Entire perimeter of window opening to be framed with resilient channel. Perimeter Fire Barrier System Perimeter fire barrier system complying with Section 715.4 of the 2012 IBC shall be installed to fill the void between the edge of the concrete floor slab and the interior surface of the exterior wall assembly. Full wall stud cavity depth or less of SucraSealTM 0.5 spray-applied foam plastic insulation applied using Wall Stud Cavity Insulation exterior gypsum sheathing as the substrate and covering the width of the cavity and the inside of the steel wall stud framing flange. Exterior sheathing–For Base 5/8-inch thick Type X exterior typegypsum sheathingcomplying with ASTM C1177. Wall System 3 above yp com P y g 1 –Any non-combustible exterior wall covering material Exterior Wall Covering–Use 2–Any non-combustible exterior wall covering system with a combustible WRB that has successfully been either 1,2,or 3 tested in accordance with NFPA 285. (see Note 1 below) 3–Metal Composite Material(MCM)Mitsubishi Plastic Composites America,Inc.,Alpoliclfr wall panels (see ICC-ES ESR-2653)or Alcoa Architectural Products Reynobond FR 6-mm panels(see ICC-ES ESR- 3435)where there is no exterior insulation in the cavity behind the panels. Flashing of window,door and As an option,flash around window,door and other exterior penetrations with limited amounts of maximum other exterior wall penetrations. 12-inch wide acrylic,asphalt or butyl-based flashing tape or liquid applied membrane material. For SI: 1 inch=25.4 mm:1 pcf=16.0 kg/m3. Note 3: Exterior wall coverings shall be installed in accordance with the manufacturer's installation requirements and must comply with the applicable provisions of IBC Chapter 14 and IRC Chapter 7. Ea, ICC EVALUATION �..,.• SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 FBC Supplement Issued February 2015 This report is subject to renewal August 2016. I (800) 423-6587 I (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section:07 21 00—Thermal Insulation REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING,TEXAS 77388-4405 (713)239-0252 EVALUATION SUBJECT: SUCRASEALTM 0.5 AND SES FOAM 0.5 LB SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that SucraSeal 0.5 spray polyurethane foam plastic insulation, recognized in ICC-ES master evaluation report ESR-3375, has also been evaluated for compliance with the codes noted below. Applicable code editions: • 2010 Florida Building Code—Building • 2010 Florida Building Code—Residential 2.0 CONCLUSIONS The SucraSeal 0.5 spray polyurethane foam plastic insulation (also known as SES Foam 0.5 lb Spray), described in Sections 2.0 through 7.0 of the master evaluation report ESR-3375, complies with the 2010 Florida Building Code—Building and the 2010 Florida Building Code—Residential, provided the design and installation are in accordance with the International Building Cod(?)provisions noted in the master report. Sucraseal 0.5/SES Foam 0.5 lb spray-applied polyurethane foam plastic insulation used in exterior walls of multi-story buildings located in the High-Velocity Hurricane Zones must comply with Section 2612.3.2.4 of the 2010 Florida Building Code—Building. For products falling under Florida Rule 9N-3, verification that the report holder's quality-assurance program is audited by a quality-assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official, when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master report, reissued August 2014 and corrected November 2015. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied as to any finding or other matter in this report,or as to any product covered by the report. .. Copyright 0 2015 ICC Evaluation Service.LLC. All rights reserved P3991 of 1 SICC EVALUATION • SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-3375 Seal and Insulate with ENERGY STAR®Supplement Issued August 2014 Revised February 2015 This report is subject to renewal August 2016. I (800)423-6587 I (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION Section: 07 21 00—Thermal Insulation REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING,TEXAS 77388-4405 (713)239-0252 EVALUATION SUBJECT: SUCRASEALTM 0.5 AND SES FOAM 0.5 LB SPRAY: SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION 1.0 EVALUATION SCOPE Conformance to the following: Seal and Insulate with ENERGY STAR® Program—Definitions end Testing Requirements for Residential Insulation, Version 1.0 Properties evaluated: • Thermal resistance • Surface-burning characteristics 2.0 PURPOSE OF THIS SUPPLEMENT This supplement is issued to certify that the insulation products described in Sections 2.0 through 8.0 of the master report ESR-3375 have been reviewed for compliance with the requirements of the Seal and Insulate with ENERGY STAR® Program, as set forth in the document Definitions and Testing Requirements for Residential Insulation, Version 1.0. The insulation product covered by this supplement is defined as"Spray or Pour Foam Insulation." The requirements for testing laboratory qualification and product sampling, as well as the specific material and test standards and editions used in this evaluation, are as set forth in the applicable documentation noted in Section 6.0 of the master evaluation report. 3.0 DEFINITIONS The following definitions are from Definitions and Testing Requirements for Residential Insulation, Version 1.0, and are applicable to the subject of this report. 3.1 General Definitions: Insulation: Any material mainly used to slow down heat flow. It may be mineral or organic, fibrous, cellular, or reflective (aluminum foil). It may be in rigid,semi-rigid,flexible. or loose-fill form. 3.2 Insulation Product Definitions: Spray or Pour Foam Insulation:A thermal insulating material that is sprayed or poured(as a gel or foamy liquid)into place, and expands or sets into a cellular foam and cures at the point of installation through a chemical reaction. Foamed materials include, but are not limited to polyurethane, polyisocyanurate, phenolic, and cementitious insulation. 3.3 Insulation Performance Definitions: R-value:The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area. For the purposes of the ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed lir— I as an endorsement of the subject of the report or a recommendation for its use.There is no warrant).by ICC Evaluation Service,fd.C,express or implied,as to any.finding or other matter in this report,or as to any product revered by the report. Copyright 0 2015 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 6 ESR-3375 Most Widely Accepted and Trusted - Page 2 of 6 Seal and Insulate with ENERGY STAR program. Imperial units will only be accepted[(h•ft2•°F)/Btu]. Smoke-Development Index: The characteristic of a material to emit smoke when exposed to flame or fire compared to red oak and inorganic cement. Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed to flame or fire compared to red oak and inorganic cement. 3.4 Thermal Resistance: The insulation has the thermal resistance R-values as noted in Table 1 of ESR-3375, based upon testing. 3.5 Installation: 3.5.1 General: The installation of the insulation must be in accordance with the requirements set forth in Sections 4.0 and 5.0(as applicable)of ESR-3375. The insulation is manufactured on-site by spray polyurethane foam applicators meeting the qualification requirements of SES Foam. The following information on personal protective equipment and ventilation requirements is reprinted from the SES Foam published installation instructions: "F. SAFETY 3. PERSONAL PROTECTIVE EQUIPMENT(PPE): a. Skin:Wear gloves,coveralls, apron and boots as necessary to prevent contact of liquid components or partially-cured SPF with skin.When handling liquid components, gloves should be made of nitrile, neoprene, butyl or PVC. b. Eyes: Protect eyes while handling liquid components or spraying with safety goggles or safety goggles and a face shield. During spray application,eye protection may be provided by a full-face or hood respirator. c. Respiration: Firms engaged in the application of SES Foam systems must have a written respiratory protection program for employees engaged in handling or applying SES Foam materials. Depending on the situation,respiratory protection may include dust masks, air-purifying respirators (APR), powered air-purifying respirators (PAPR), or supplied-air respirators(SAR). 4. VENTILATION: Provide ventilation and other engineering controls to exhaust vapors from work areas and to protect building occupants and other trades." 3.5.2 Occupancy Time after Installation: The re-entry or re-occupancy time shall be in accordance with the manufacturer's installation instructions, which state the following: "G. RE-ENTRY SucrasealTu 0.5 reacts and cures within seconds of application. Re-entry times will vary depending on factors including ventilation. Typically, ventilation is continued for 24 hours following the conclusion of spray application and re-entry may occur at that time." 3.5.3 Figures: The figures shown represent general installations of the insulation in the following applications: above-grade wall, below-grade wall, vented and unvented crawl space, unvented cathedral ceiling,and vented and unvented attic. These figures are for illustration purposes and are not to be construed or used as construction documents. This supplement expires concurrently with the master report, reissued August 2014 and corrected November 2015. ESR-3375 I Most Widely Accepted and Trusted Page 3 of 6 • i — Interior Partition • Interior Finished Surface (1,2-inch Sheetrock) SUCRASEALTM 0 5 or SES Foam 0.5 Ib Spray Exterior Sheathing *40 SOALOM0 5 ABOVE GRADE WALL INSULATION SES 05-1 (1629..:..: SESES FOAM 0 5 LB SPRAY ESR-3375 I Most Widely Accepted and Trusted Page 4 of 6 y'•. Masonry Block f/!y IIypoail ` .. .. .. . .. . t !manor Fm,sh Su Aaco •I.... .. . t1/2•inch Shea:rcck) • 7 s 4-Studs I -. .. _ SUCRASCALw 05 or •• b SFS Foam 05 Spray i:._. • I. 1:• . . SUCRASEAI'0 5 BELOW GRADE WALL INSULATION I SES 05-2 06291.: SES FOAM 0 5 LB SPRAY (Insulation on Interior Side of Wall Baffle to provide air space betweenThermal insulation and roof Barrier' deck. (as required by local code) i _ 1 / — j . SUCRASEALIM 0.5 or SES Foam 0.51b Spray Vented Soffit - -. ., 'Where attic entry is for the SES Foam 0.5 lb Spray service of utilities only.thermal and Igniton barrier on the attic . • side of the spray foam surface may be omitted. SALOM0 5 VENTED ATTIC.FLOOR t SOFFIT I SES 05-3 I 062914 SFSFS FOAM 05 LB SPRAY ESR-3375 Most Widely Accepted and Trusted Paae 5 of 6 Subfloor SUCRASEALTM 0.5 or SES Foam 0.5 lb Spray Header .- ---- .. - • _ • • • _ Sill - _NIIP Joist Floor Cross Section Thermal Barrier' ---- (as required by Exterior Grade local code) Footer Vapor Barrier ,•0, 'Where crawlspace entry is for the • •• service of utilities only.thermal and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SUCRASFAI 5 SES rOAt.t05 CRAWLSPACE:VENTED SES 05-4 062914 LB SPRAY Subfloor Header- lit ._: ; : _ �_. Sill—' —` 1 Joist Thermal Barrier' •.._ . --: re (as required by Exterior Grade_. . . . . local code) .- • .....-d— SUCRASEAL M 0.5 or i; SES Foam 0.5 lb Spray Footer 6 Min Vapor Barrier ....... .• 'Where crawlspace entry is for the service of utilities only.thermal and igniton barrier on the crawlspace side of the spray foam surface may be omitted. SUCRASE.•.''' i i ';ES FOAM , 13SPRAY I CRAWLSPACE-UNVENTED SES 05-5 062914 ESR-3375 ' Most Widely Accepted end Trusted Page 6 of 6 Note In cold climatesemlxtd metal connector plates.0 spray foam to prevent winter-time rordersation SUCRASEALIr,I 0.5 or • ;� SES Foam 0.5 lb Spray ....-0- - • Roof Sheathing -•t ,1 russ Top Cord: '• - Rafter ��'` f il Thermal Barrier- (as required by local code) Note Local budding code may require the use of a vapor retarder in cold climate zones 'Where attic entry is for the Ceiling'Thermal Barrier service of utilities only thermal AS required by local building code. and igndon barrier on the attic side of the spray foam surface may be ovntled SUCRASEALIMCI 5 UNVENTED ATTIC!INSULATED ROOF DECK SES 05-6 062914 SES FOAM 0 5 LB SPRAY • r1�_ u.I SUCRASEAL 0.5 or ' ' _ SES Foam 0 5 lb Spray _ _ _ - " _ _ to specified thickness. _ = ' _ _ • Roof Sheathing Thermal Barrier as Rafter • required by code. - Note:The local building code may require the installation of -- a vapor barrier in cold climate zones. SUCRASFA0M05 CATHEDRAL CEILING I SES 05-7 I ari (+'.1 _:F.S FOAM110 51.6 SPRAY aY E` ICC EVALUATION `.�• SERVICE ICC-ES Report ICC-ES 1 (800)423-6587 1 (562) 699-0543 I www.icc-es.org Reissued 09/203. This report is sub'ect to,r-r &f DIVISION:07 00 00—THERMAL AND MOISTURE PROTECTION SECTION:07 2100—THERMAL INSULATION REPORT HOLDER: SES FOAM 4008 LOUETTA ROAD,#538 SPRING,TEXAS 77388-4405 EVALUATION SUBJECT: SES FOAM 0.5 LB SPRAY POLYURETHANE FOAM PLASTIC INSULATION ICC ICCICC (44441/4- -t° EM PMG LISTED Look for the trusted marks of Conformity! ICC :ilk 11. "2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC)Award in Excellence" A Subsidiary of :.oc nj!." Ac<.een<e ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not � see ce-0� specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a MIs, ( recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as IMS'.R:crcd'tC JroMm OCPS to any finding or other matter in this report,or as to any product covered by the report. PRODUCT ER'KJ,00.4 au cc, Copyright© 2015 ICC Evaluation Service, LLC.All rights reserved. SICC EVALUATION • SERVICE Most Widely Accepted and Trusted ICC-ES VAR Environmental Report VAR-1030 Reissued September 2015 This report is subject to renewal September 2017. 1800-423-6587 I (562)699-0543 A Subsidiary of the International Code Council° DIVISION: 07 00 00—THERMAL AND MOISTURE high-pressure, plural component SPF application PROTECTION equipment. The bio-based content is as set forth in Table 1 Section:07 21 00—Thermal Insulation of this report. REPORT HOLDER: 4.0 CONDITIONS 4.1 Code Compliance: SES FOAM See ICC-ES report -SR.-7c for compliance of the SES 4008 LOUETTA ROAD,#538 Foam 0.5 lb Foam S Polyurethane Foam Plastic Insulation SPRING,TEXAS 77388-4405 with code requirements. (713)239-0252 4.2 Green Codes, Standards and Rating Systems Eligibility: EVALUATION SUBJECT: The information presented in Tables 2 through 5 of this report provides a matrix of areas of evaluation and SES FOAM 0.5 lb SPRAY POLYURETHANE FOAM corresponding limitations and/or additional project-specific PLASTIC INSULATION requirements, and offers benefits to individuals who are assessing eligibility for compliance. 1.0 EVALUATION SCOPE The final interpretation of the specific requirements of the Compliance with the following environmental criteria: code rests with the Authority Having Jurisdiction. ICC-ES Environmental Criteria for Determination of Compliance for items noted as "Verified Attribute" is Bio-based Material Content(EC102),dated March 1,2012. subject to any conditions noted in the tables. Decisions on Compliance eligibility with the applicable sections of compliance for those items noted as"Eligible for Points"in the following codes and standards: Tables 2 through 5 rests with the user of this report, and I • 2012 International Green Construction CodeTM CC those items are subject to the conditions noted. The user is (g ) advised of the project-specific provisions that may be (see Table 2 for details) contingent upon meeting specific conditions, and the • ASHRAE Standard 189.1 – 2009 (see Table 3 for verification of those conditions is outside the scope of this details) report. • National Green Building Standard (ICC 700-2008) (see Due to the variability of costs and volume, the bio-based Table 4 for details) content percentage listed in this report is based upon weight (mass). The use of cost or volume as the method • ANSI/GBI 01-2010, Green Building Assessment for calculation is outside the scope of this report. Protocol for Commercial Buildings (see Table 5 for details) 5.0 BASIS OF EVALUATION 2.0 USES The information in this report, including the "Verified Attributes," is based upon submission of documentation SES Foam 0.5 lb Foam S Polyurethane Foam Plastic demonstrating compliance with the requirements set forth Insulation is used as nonstructural thermal insulating in ICC-ES EC102. (Evaluation applies to IgCC Section material in wall cavities, floor/ceiling assemblies. or in 505.2.4, item 3; ASHRAE 189.1 Section 9.4.1.3; ICC 700 attics and crawl spaces. See ICC-ES report for Section 606.1;ANSI/GBI-01 Section 10.1.2.2.) more information on uses and applications. 6.0 IDENTIFICATION 3.0 DESCRIPTION Containers of SES Foam 0.5 lb Foam S Polyurethane SES Foam 0.5 lb spray-applied polyurethane foam plastic Foam Plastic Insulation are identified by a label bearing the insulation is a two-component, open-cell, water-blown, SES Foam name and address, product name, spray-applied polyurethane foam (SPF) with a nominal manufacturing date, manufacturing location and the VAR density of 0.5 lb/ft". The foam is sprayed in place using Environmental Report number(VAR-1030). ICC-ES Verification of Attributes Reports are issued under the ICC-ES VAR Environmental Program.These reports are not to be construed as represeming aesthetics or try other 11 attributes not specifically addressed,nor are they to be construed as an endorsement of the subject of the report or a recanmeradniatinn for its use.There is no warranty by ICC Evaluation Service,U.C,express or implied,as to aryfirdling or other natter in this report,or as to any product covered by the report. �i°Pai" Copyright 0 2015 ICC Evaluation Service,LLC. All rights reserved Page 1 of 2 VAR-1030 I Most Widely Accepted and Trusted Page 2 of 2 TABLE 1—BIO-BASED MATERIAL CONTENT SUMMARY PRODUCT NAME % MEAN 610-BASED CONTENT METHOD OF DETERMINATION SES Foam 0.5 lb Spray Polyurethane Foam Plastic Insulation 17%(+1-3%)' ASTM D6866 Note: 'Based on precision and bias cited in ASTM D6866. TABLES 2 THROUGH 5 Section Possible Number Section Intent Points Conditions Of Use To Qualify For Points Finding TABLE 2—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2012 INTERNATIONAL GREE LCO6LWifUCT1ON CODE Bio-based materials shall be those materiels trot cort amitthemtemrmmuae of the following: 505.2.4 Bio-based content N/A 3.The requirements of USDA 7CFR Part 2902. • Note:USDA 7 CFR Part 2902§2907.17 seas a mailman)Ibant of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum TABLE 3—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2009 ASHRAE STAIi1/NW1211:1 A minimum of 5%of building materials used,based on cost,sttalllbar It sbased products. Biobased products shall comply with the minimum)biobased apmttertts;effthe USDA's Designation of Biobased Items for Federal Procurement[7CFR f d 72302].contain the 9.4.1.3 Biobased products NIA "USDA Certified Biobased Product'label,or be composed ofsadltt . i ,engineered • wood,bamboo,wool,cotton,cork,agricultural fibers,or°their tbiabasaat materials with at least 50%biobased content. Note:USDA 7 CFR Part 2902§2907.17 sets a minimum c,-4as t,ar nCrarnt of 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds this minimum. TABLE 4—SUMMARY OF AREA OF ELIGIBILITY WITH THE 2008 NATIONAL GRIM BUILDNGs1TlItMtDARD(ICC 700) The following biobased products are used: (h)products with the minimum biobased contents of the 11S0147/ Part 2902 606.1 Biobased products 3 (i)other biobased materials with a minima=elf 50 percerrttttu olimmrrbent(by weight • 8 max or volume) Note:USDA 7 CFR Part 2902§2907.17 sets a minirsanmkh®ftraaut annitentof 7%(10% +/-3%).SES Foam 0.5 lb Spray exceeds liras minimum TABLE 5—SUMMARY OF AREA OF ELIGIBILITY WITH THE ANSUGB1–D1 j21:1`T0)'S ANDARD Bio-based products accounted for 1%or more of the materials used in the building. Percentage=100 x A-B,where: A=Total cost or weight of bio-based products B=Total cost or weight of all building prock,sclts 10.1.2.2 Materials content– 1 Cost or weight must be used consistently • Assemblies 7 max For USDA-designated products,products einerittingerr eriezentlirrigliERINft bo-based content,criteria or qualifying as USDA"B mbf'%nr£ursed. Note:USDA 7 CFR Part 2902§2907.17 seism rniirwnni m ibis-in ragba nrtteri of 7%(10% +1-3%).SES Foam 0.5 lb Spray exceedtshiisrni mimnamn. • =Verified attribute FORM R405-2014OFFICE COPY a " HOU RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the residential Simulated Performance method shall include ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, e-ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst-case orientation, name and version of the compliance software tool, name of individual completing the compliance report (1 page) and an input summary checklist that can be used for field verification (usually 4 pages/may be greater). ❑ Energy Performance Level(EPL) Display Card (one page) ❑ Mandatory Requirements(three pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report(usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) OCT 1 9 2016 EnergyGauge®-USRCSB v5.1 9/22/2016 10:05:21 AM Page 1 of 1 FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Schooling Residence Builder Name: Street: 350 Third St Permit Office: Atlantic Beach City.State,Zip: Atlantic Beach.FL, Permit Number: Owner: Jurisdiction: 261100 Design Location: FL,MAYPORT_NS County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types (3526.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3157.20 ft2 b.Frame-Wood,Adjacent R=19.0 368.80 ft2 3. Number of units.if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft2 10.Ceiling Types 24100A-sgft.) Insulation Area 5. Is this a worst case? No a.Roof Dec nvented R=22.0 2400.00 ft2 6. Conditioned floor area above grade(ft2) 3820 b.N/A R= ft2 Conditioned floor area below grade(fgt. 0 c.N/A R= ft2 11.Ducts R ft2 7. Windows(615.6 sqft.) Description Area a.Sup: 1st Floor,Ret: 1st Floor,AH: 1st Floor 6 252.72 a. U-Factor: Dbl. U=0.40 615.55 ft2 b.Sup: 2nd Floor,Ret:2nd Floor,AH:2nd Floor 6 234.88 SHGC: SHGC=0.25 b. U-Factor: N/A ' ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 24.0 SEER:17.00 b.Central Unit 24.0 SEER:17.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft' a.Electric Heat Pump 25.0 HSPF:9.00 SHGC: b.Electric Heat Pump 25.0 HSPF:9.00 Area Weighted Average Overhang Depth: 5.236 ft. Area Weighted Average SHGC: 0.250 14. Hot water systems 8. Floor Types (3820.0 sqft.) Insulation Area a. Propane Tankless Cap 1 gallons EF:0.750 a.Slab-On-Grade Edge Insulation R=0.0 1944.00 ft2 b. Conservation features b. Floor Over Other Space R=0.0 1748.00 ft2 None c.other(see details) R= 128.00 ft' 15. Credits None Total Proposed Modified Loads: 71.84 Glass/Floor Area: 0.161 PASS Total Baseline Loads: 96.99 I hereby certify that the plans and specifications covered by Review of the plans and ..�.�O�1NE ST,g��,,..tf this calculation are in compliance with the Florida Energy specifications covered by this .` ti, -` r:. a 0 Code. calculation indicates compliance : Co/o„op, '.,', •:�``: d. Ryan B. Ellis with the Florida Energy Code. r 1./'ii , �' ,d.0 PREPARED BY: Before construction is completed u� 110. `70 i, DATE: 9/22/16 this building will be inspected for .0cd 0''. ;_c. , /l compliance with Section 553.908 •' t ., I hereby certify that this building. as designed, is in compliance Florida Statutes. '= t,�; -' �� : with the Florida Energy Code. ''•.,COP ,,.• OWNER/AGENT: BUILDING OFFICIAL: ! ,! DATE: DATE: /L9• 43. - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 • ' FORM R405-2014 PROJECT Title: Schooling Residence Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 3820 Lot# Owner: Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Rotate Angle: 0 Street: 350 Third St Permit Office: Atlantic Beach Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, New/Existing: New(From Plans) Comment: CLIMATE IECC Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,MAYPORT_NS FL_MAYPORT_NS 2 39 90 70 75 1037 61 Medium BLOCKS Number Name Area Volume 1 Blockl 1944 19634.4 2 Block2 1876 20260.8 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 1st Floor 1944 19634.4 Yes 3 0 1 Yes Yes Yes 2 2nd Floor 1876 20260.8 No 4 4 1 Yes Yes Yes FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulation 1st Floor 202 ft 0 1944 ft2 __ 0 0 1 2 Raised Floor 2nd Floor ____ ____ 128 ft2 19 0 0 1 3 Floor Over Other Space 2nd Floor ____ _-__ 1748 ft2 0 0 0 1 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Composition shingles 2400 ft2 606 ft2 Medium 0.96 No 0.9 No 22 30.3 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 2072 ft2 N N 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 ' FORM R405-2014 CEILING V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic(Unvented) 1st Floor 0 Blown 227 ft' 0.11 Wood 2 Under Attic(Unvented) 2nd Floor 0 Blown 2173 ft' 0.11 Wood WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below # Ornt To Wall Type Space R-Value ___Ft _1n Ft In Area _.R-Value Fraction_ Absor. Grade% 1 N Exterior Frame-Wood 1st Floor 19 40 10.1 404.0 ft2 0.05 0.170000 0 2 W Exterior Frame-Wood 1st Floor 19 46 10.1 464.6 ft' 0.05 0.170000 0 _ 3 S Exterior Frame-Wood 1st Floor 19 40 10.1 404.0 ft2 0.05 0.170000 0 4 S Exterior Frame-Wood 1st Floor 19 15 9.1 136.5 ft' 0.05 0.170000 0 5 E Exterior Frame-Wood 1st Floor 19 7 9.1 63.7 ft' 0.05 0.170000 0 6 N Garage Frame-Wood 1st Floor 19 15 9.1 136.5 ft' 0.05 0.170000 0 7 E Garage Frame-Wood 1st Floor 19 23 10.1 232.3 ft' 0.05 0.170000 0 8 E Exterior Frame-Wood 1st Floor 19 16 10.1 161.6 ft' 0.05 0.170000 0 9 N Exterior Frame-Wood 2nd Floor 19 21 10.8 226.8 ft' 0.05 0.170000 0 10 W Exterior Frame-Wood 2nd Floor 19 46 10.8 496.8 ft' 0.05 0.170000 0 11 S Exterior Frame-Wood 2nd Floor 19 40 10.8 432.0 ft' 0.05 0.170000 0 12 E Exterior Frame-Wood 2nd Floor 19 34 10.8 367.2 ft' 0.05 0.170000 0 DOORS �% # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 N Wood 1st Floor None .46 3 6.7 20.1 ft2 WINDOWS Orientation shown is the entered. Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation_ Int Shade Screening 1 N 1 Vinyl Low-E Double Yes 0.4 0.25 67.0 ft2 8 ft 0 in 3.5 ft 0 in Drapes/blinds None 2 N 1 Vinyl Low-E Double Yes 0.4 0.25 20.0 ft' 8 ft 0 in 0.5 ft 0 in Drapes/blinds None 3 N 1 Vinyl Low-E Double Yes 0.4 0.25 40.2 ft' 8 ft 0 in 3.5 ft 0 in Drapes/blinds None 4 N 1 Vinyl Low-E Double Yes 0.4 0.25 12.0 ft' 8 ft 0 in 0.5 ft 0 in Drapes/blinds None 5 W 2 Vinyl Low-E Double Yes 0.4 0.25 25.0 ft' 1.3 ft 0 in 2.5 ft 0 in Drapes/blinds None 6 W 2 Vinyl Low-E Double Yes 0.4 0.25 15.0 ft' 1.299999 12.9 ft 0 i Drapes/blinds None 7 S 3 Vinyl Low-E Double Yes 0.4 0.25 128.0 ft' 12 ft 0 in 1.5 ft 0 in Drapes/blinds None 8 S 3 Vinyl Low-E Double Yes 0.4 0.25 11.3 ft' 12 ft 0 in 1.5 ft 0 in Drapes/blinds None 9 S 4 Vinyl Low-E Double Yes 0.4 0.25 20.1 ft' 1.299999 2 ft 0 in Drapes/blinds None 10 S 4 Vinyl Low-E Double Yes 0.4 0.25 24.0 ft' 1.299999 2 ft 0 in Drapes/blinds None 11 E 8 Vinyl Low-E Double Yes 0.4 0.25 10.0 ft' 1.299999 2 ft 0 in Drapes/blinds None 12 N 9 Vinyl Low-E Double Yes 0.4 0.25 24.0 ft' 1.299999 5 ft 0 in Drapes/blinds None 13 N 9 Vinyl Low-E Double Yes 0.4 0.25 27.0 ft' 1.299999 1.2 ft 0 in Drapes/blinds None 14 W 10 Vinyl Low-E Double Yes 0.4 0.25 10.0 ft' 1.299999 4 ft 0 in Drapes/blinds None 15 W 10 Vinyl Low-E Double Yes 0.4 0.25 37.5 ft' 1.299999 8.4 ft 0 in Drapes/blinds None 16 S 11 Vinyl Low-E Double Yes 0.4 0.25 50.0 ft' 1.299999 1.1 ft 0 in Drapes/blinds None 17 S 11 Vinyl Low-E Double Yes 0.4 0.25 72.0 ft' 1.299999 1.1 ft 0 in Drapes/blinds None 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 ' FORM R405-2014 WINDOWS Orientation shown is the entered,Proposed orientation. / Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC _ Area Depth Separation Int Shade Screening 18 E 12 Vinyl Low-E Double Yes 0.4 0.25 10.0 ft' 1.299999 4 ft 0 in Drapes/blinds None 19 E 12 Vinyl Low-E Double Yes 0.4 0.25 12.5 ft2 1.299999 8.5 ft 0 in Drapes/blinds None GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 346 ft2 346 ft2 37.9 ft 9.1 ft 0 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000332 3324.6 182.52 343.25 .3145 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:9 25 kBtu/hr 1 sys#1 2 Electric Heat Pump None HSPF:9 25 kBtu/hr 2 sys#2 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER: 17 24 kBtu/hr 720 cfm 0.75 1 sys#1 2 Central Unit None SEER: 17 24 kBtu/hr 720 cfm 0.75 2 sys#2 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Propane Tankless Exterior 0.75 1 gal 70 gal 120 deg None SOLAR HOT WATER SYSTEM VFSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS / --Supply-- —Return— Air CFM 25 CFM25 HVAC# �/ # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 1st Floor 6 252.72 f 1st Floor 97.2 ft2 Default Leakage 1st Floor (Default)c(Default)c 1 1 2 2nd Floor 6 234.88 f 2nd Floor 93.8 ft2 Default Leakage 2nd Floor (Default)c(Default)c 2 2 9/22/2016 10:05 AM EnergyGauge©USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 6 • ' FORM R405-2014 TEMPERATURES Programable Thermostat: None Ceiling Fans: Cooling Jan Feb Mar Apr Ma X Jun X Jul X Au X Se Oct Nov Dec Heating X Jan X Feb X Mar [ 1 APr Ma Jun Jul Aug Sep Oct 'xi Nov )C Dec VentingJan Feb X Mar [X Apr [ May [ Jun [ Jul [ Aug [ Sep X Oct X Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 �ain //QvS•-e- OFFICE COPY 3)1d FORM R405-2014 • ENERGY PERFORMANCE LEVEL (EPL) • DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 74 The lower the EnergyPerformance Index, the more efficient the home. 350 Third St, Atlantic Beach, FL, 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area • • 2. Single family or multiple family Single-family a.Frame Wood.Exterior R=19.0 3157.20 ft� b.Frame-Wood.Adjacent R=19.0 368.80 ft 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 4 d.N/A R= ft' 5. Is this a worst case? No 10.Ceiling Types Insulation Area a.Roof Deck(Unvented) R=22.0 2400.00 ft: 6. Conditioned floor area(ft2) 3820 b.N/A R= ft' 7. Windows" Description Area c.NIA R= ft'' a. U-Factor: Dbl.U=0.40 615.55 ft' 11.Ducts R ft a.Sup: 1st Floor,Ret:1st Floor.AH:1st Floor 6 252.72 SHGC: SHGC=0.25 b.Sup: 2nd Floor.Ret:2nd Floor.AH:2nd Floor 6 234.88 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 24.0 SEER:17.00 SHGC: b.Central Unit 24.0 SEER:17.00 d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 25.0 HSPF:9.00 Area Weighted Average Overhang Depth: 5.236 ft. b.Electric Heat Pump 25.0 HSPF:9.00 Area Weighted Average SHGC: 0.250 8. Floor Types Insulation Area 14.Hot water systems Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 1944.00 ft' a.Propane EF:0.75 b.Floor Over Other Space R=0.0 1748.00 ft' c.other(see details) R= 128.00 ft' b. Conservation features None 15.Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building „::.' ---�=--. Construction through the above energy saving features which will be installed (or exceeded) ,7-. , o\;, in this home before final inspection. Otherwise, a new EPL Display Card will be completed ' ��.. based on installed Code compliant features. `Q 'C‘, I ;� I�; Builder Signature: (i2-----": ::::. Dater '� //6 fr'-z.*0- .. /.' Address of New Home: 1' ' Cit /FL Zi :!�;r vs. i, *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. i 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 4pd.17t tff!M uad0 a£0g£-ONI1OOHOS8 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 350 Third St Permit Number: Atlantic Beach ,FL. MANDATORY REQUIREMENTS See individual code sections for full details. X 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law[Section 553.9085. Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. X R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. x R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1.as applicable to the method of construction. Where required by the code official.an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2.and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official.testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors.fireplace and stove doors shall be closed,but not sealed.beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust.intake.makeup air,backdraft and flue dampers shall be closed.but not sealed beyond intended infiltration control measures; 3.Interior doors.if installed at the time of the test,shall be open: 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems.if installed at the time of the test,shall be turned off;and 6.Supply and return registers.if installed at the time of the test,shall be fully open. X R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. X R402.4.3 Fenestration air leakageWindows.skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 L/s/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. X R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. X R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system. X R403.1.3 Heat pump supplementary heat(Mandatory)Heat pumps having supplementary electric-resistance heat shall have controls that, except during defrost.prevent supplemental heat operation when the heat pump compressor can meet the heating load. X R403.2.2 Sealing(MandatorAll ducts.air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99, Florida Statutes,or as authorized by Florida Statutes.to be`substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test.total leakage shall be less than or equal to 3 cfm(85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) X R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. x R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)or below 55°F(13°C)shall be insulated to a minimum of R-3., R403.3.1 Protection of piping insulation. ❑ R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. X R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'/2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.4.4 Water heater efficiencies(Mandatory). X R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140`F(38`C to 60°C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of combustion types of service water heating systems to be turned off. x R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation.Commercial Provisions.for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. ▪ R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors.and SRCC Standard TM-1.Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal:and 2. Be installed at an orientation within 45 degrees of true south. 0 R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code. Residential or Florida Building Code.Mechanical,as applicable.or with other approved means of ventilation.Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. X R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. X R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies.based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6.or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) X R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment).the blower cfm provided by the expanded performance data.the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units.the capacity of equipment may be sized in accordance with good design practice. X R403.6.1.2 Heating equipment capacity ' R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. ▪ R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. ' R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. X R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis.such as anticipated additional loads caused by major entertainment events.shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building.shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F.and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. ❑ R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160.Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps.Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: • 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy.such as a heat pump or solar ' energy source computed over an operating season. X RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights X R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. X R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space.R-10 is allowed. 9/22/2016 10:05 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Schooling Residence Builder Name: Street: 350 Third St Permit Office: Atlantic Beach City,State.Zip Atlantic Beach .FL, Permit Number: Owner: Jurisdiction: 261100 Design Location: FL,MAYPORT_NS COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. x Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. x Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. x Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and x Rim joists Rim joists are insulated and include an air barrier. X Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. X The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. x Exposed earth in unvented crawl spaces shall be covered with a Class I Shafts, penetrations Duct shafts. utility penetrations, and flue shaft openings to exterior or x unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity X spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. X Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be x air tight, IC rated. and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to X available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air x barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. x HVAC register boots HVAC register boots that penetrate building thermal envelope shall be x sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have x gasketed doors 9122!2016 10:05 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 ProjectSummaryJob. +�+ wrightsoft Date: 9/18/16 1st Floor By: M.Ellis Energy Design Systems, Inc. 11727 Brady Rd.Jacksonville. FL 32223 Phone 904-268-3670 Fax 904-268-3670 Email eds fax@gmail corn Pro'ect Information For: Schooling Residence 350 Third St,Atlantic Beach, FL Notes: Desi• n Information Weather: Mayport Ns, FL, US Winter Design Conditions Summer Design Conditions Outside db 38 °F Outside db 94 °F Inside db 68 °F Inside db 75 °F Design TD 30 °F Design TD 19 °F Daily range L Relative umidity 50 Moisture difference 50 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 20021 Btuh Structure 17888 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 20021 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load d?8 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 1 (Average) Structure 3537 Btuh Ducts 0 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 1944 1944 Equipment latent load Btuh Volume (ft3) 19634 19634 Air changes/hour 0.36 0.17 Equipment to load_ 2142 Btuh Equiv. AVF (cfm) 117 57 Req. total capacity at 0.74 SHR 0 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HCB624A"31 Gond 25HCB624A**31 AH RI ref 6936857 Coil FV4CNFOO2L AHRI ref 6936857 Efficiency 9 HSPF Efficiency 13.0 EER, 17 SEER Heating input Sensible cooling 16800 Btuh Heating output 25000 Btuh @ 47°F Latent cooling 7200 Btuh Temperature rise 28 °F Total cooling 24000 Btuh Actual air flow 800 cfm Actual air flow 800 cfm Air flow factor 0.040 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.83 Capacity balance point = 33 `F Backup: Input = 6 kW, Output = 20021 Btuh. 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft FItSOft 2016-Sep-22 10:05:51 9 Right-Suite®Universal 2017 17 0.04 RSU17457 Page 1 ACC: \Schooling Residence. 350 Third St.Atl Bch rup Calc=MJ8 Front Door faces N Project SummaryJob: ro +I+ wrightsoft � Date: 9/18/16 2nd Floor By: M.Ellis Energy Design Systems, Inc. 11727 Brady Rd,Jacksonville, FL 32223 Phone 904-268-3670 Fax 904-268-3670 Email eds jax@gmail corn Pro'ect Information For: Schooling Residence 350 Third St,Atlantic Beach, FL Notes: Desi. n Information Weather: Mayport Ns, FL, US Winter Design Conditions Summer Design Conditions Outside db 38 °F Outside db 94 °F Inside db 68 °F Inside db 75 °F Design TD 30 °F Design TD 19 °F Daily range L Relative humidity 50 Moisture difference 50 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 13296 Btuh Structure 18312 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 13296 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensibles ad '8 r tuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 1 (Average) Structure 3072 Btuh Ducts 0 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 1876 1876 Equipment latent load 307 Btuh Volume (ft3) 20261 20261 Air changes/hour 0.26 0.13 Equipment total load 21384�$tuh Equiv. AVF (cfm) 89 43 Req. totaTcapacity at 0.75 SHR --2.0 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HCB624A"31 Cond 25HCB624A**31 AH RI ref 6936857 Coil FV4CNFOO2L AH RI ref 6936857 Efficiency 9 HSPF Efficiency 13.0 EER, 17 SEER Heating input Sensible cooling 16800 Btuh Heating output 25000 Btuh @ 47°F Latent cooling 7200 Btuh Temperature rise 28 °F Total cooling 24000 Btuh Actual air flow 800 cfm Actual air flow 800 cfm Air flow factor 0.060 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.86 Capacity balance point = 22 °F Backup: Input = 4 kW, Output = 13296 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2016-Sep-22 10:05 51 Right-Suite®Universal 2017 17.0.04 RSU17457 Page 2 ACCP ,Schooling Residence.350 Third St.Atl Bch rup Calc=MJ8 Front Door faces N S Compliance liance Re ort Job: +�+ wrightsoft Manualp p Date: 9/18/16 1st Floor By: M.Ellis Energy Design Systems, Inc. 11727 Brady Rd.Jacksonville, FL 32223 Phone 904-268-3670 Fax 904-268-3670 Email eds.lax@gmaII com Project Information For: Schooling Residence 350 Third St,Atlantic Beach, FL Cooling Equipment Design Conditions Outdoor design DB: 94.4°F Sensible gain: 17888 Btuh Entering coil DB: 75.0°F Outdoor design WB: 77.4°F Latent gain:" 3537 Btuh Entering coil WB: 62.5°F Indoor design DB: 75.0°F Total gain: 21425 Btuh Indoor RH: 50% Estimated airflow: 800 cfm Manufacturer's Performance Data atActual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCB624A"31+FV4CNF002L Actual airflow: 800 cfm Sensible capacity: 17760 Btuh 99% of load Latent capacity: 6240 Btuh 176% of load Total capacity: 24000 Btuh 112% of load SHR: 74% Heating Equipment Design Conditions Outdoor design DB: 38.1°F Heat loss: 20021 Btuh Entering coil DB: 68.0°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCB624A**31+FV4CNF002L Actual airflow: 800 cfm Output capacity: 25000 Btuh 125% of load Capacity balance: 33 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 800 cfm Output capacity: 5.9 kW 100% of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Sep-22 10 23 37 41- wrightsoft Right-Suite®Universal 2017 17 0.04 RSU17457 Page 1 /CC _\Schooling Residence 350 Third St.Atl Bch rup Calc=MJ8 Front Door faces N Manual S Compliance Report Job: +I+ wrightsoft Date: 9118116 2nd Floor By: M.Ellis Energy Design Systems, Inc. 11727 Brady Rd.Jacksonville, FL 32223 Phone. 904-268-3670 Fax 904-268-3670 Email eds jax@gmailcorn Project Information For: Schooling Residence 350 Third St,Atlantic Beach, FL Cooling Equipment Design Conditions Outdoor design DB: 94.4°F Sensible gain: 18312 Btuh Entering coil DB: 75.0°F Outdoor design WB: 77.4°F Latent gain: 3072 Btuh Entering coil WB: 62.5°F Indoor design DB: 75.0°F Total gain: 21384 Btuh Indoor RH: 50% Estimated airflow: 800 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCB624A"31+FV4CNF002L Actual airflow: 800 cfm Sensible capacity: 17760 Btuh 97% of load Latent capacity: 6240 Btuh 203% of load Total capacity: 24000 Btuh 112% of load SHR: 74% Heating Equipment Design Conditions Outdoor design DB: 38.1°F Heat loss: 13296 Btuh Entering coil DB: 68.0°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HCB624A"31+FV4CNF002L Actual airflow: 800 cfm Output capacity: 25000 Btuh 188% of load Capacity balance: 22 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 800 cfm Output capacity: 3.9 kW 100% of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Sep-22 10-23 37 ,� wrightsoft Right-Suite®Universal 2017 17.0.04 RSU17457 Page 2 ACCA \Schooling Residence,350 Third St,Atl Bch rup Calc=MJ8 Front Door faces N N / N 1\ 1st Floor 14 ' MI 481 cfm 20 " alreicm cm''$:r- rwWUV 134 cfm 1 35 cfm 1 r..„66 cfm 83 1 cf if'cfm is : cfm 'Z' : c m 90 cfm LT 9 cfm c m _. Job #: Exclusively for the use of: Scale: 1 : 72 Performed for: Page 1 Schooling Residence Ocean Stale Ail Ccnd ticni rg Inc. Right-Suite®Universal 2017 350 Third St 17.C.C4 RSU 17457 Atlantic Beach,FL 2016-Sep-22 1C:C6:58 ...dence,350 Third St,A11 Bch.rup 2nd Floor 20 " 576.7.17 W.Wc m 8 ' 3 107 cfm 1 •2 cm `1 ' -s 1 MI 139 cfm 014 I 3 c m 12 " ' . cfm 6 ' /T • ' t 53 cfm 1 268 cfm tfm r'..."..ww47.11www"El 108 cfm cfm c m =_-��_�_________-'• Job #: Exclusively for the use of: Scale: 1 : 72 Performed for: Page 2 Schooling Residence Ocean Slate Air Ccndticning Inc. Right-Suite®Universal 2017 35C Third St 17.0.04 RSU 17457 Atlantic Beach,FL 2016-Sep-22 10:06:58 ...dence,350 Third St,All Bch.rup 4 wrightsoft Duct System Summary Date: 1st Floor By: Exclusively for the use of: Ocean State Air Conditioning, Inc Project Information For: Schooling Residence 350 Third St, Atlantic Beach, FL Heating Cooling External static pressure 0.10 in H2O 0.10 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.10 in H2O 0.10 in H2O Supply/ return available pressure 0.082 / 0.018 in H2O 0.082/ 0.018 in H2O Lowest friction rate 0.028 in/100ft 0.028 in/100ft Actual air flow 800 cfm 800 cfm Total effective length (TEL) 355 ft Supply Branch Detail Table Design Htg Clg IDesign I Diam I H x W I Duct Actual I Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk Butler c 1066 28 29 0.033 5.0 Ox 0 VIFx 37.0 210.0 st2 Den c 4948 133 134 0.066 9.0 Ox 0 VIFx 15.0 110.0 st2 Dining h 3334 90 88 0.035 8.0 Ox 0 VIFx 41.0 190.0 st2 FamilyRoom h 3990 107 107 0.068 8.0 Ox 0 VIFx 30.0 90.0 st2 FamilyRoom-A h 3990 107 107 0.080 8.0 Ox 0 VIFx 13.0 90.0 st2 Foyer h 2447 66 65 0.047 7.0 Ox 0 VIFx 25.0 150.0 st2 Kitchen h 2141 58 56 0.033 7.0 Ox 0 VIFx 56.0 190.0 st2 Kitchen-A h 2141 58 56 0.036 7.0 Ox 0 VIFx 40.0 190.0 st2 Mud Room c 4464 115 121 0.028 10.0 Ox 0 VIFx 71.0 220.0 st2 Pantry h 152 4 3 0.041 4.0 Ox 0 I VIFx 29.0 170.0 I st2 Powder c 1280 34 35 0.056 5.0 Ox 0 I VIFx 16.0 130.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct I Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 800 800 0.028 367 20.0 0 x 0 VinlFlx Bold/italic values have been manually overridden 2016-Sep-22 10 06 40 ,. wrightsoft Right-Suite®Universal 2017 17 0 04 RSU17457 Page 1 ACOA .1 Schooling Residence,350 Third St,All Bch rup Calc=MJ8 faces N Return Branch Detail Table Grill Htg Clg TEL IDesign 1 Veloc Diam H x W Stud/Joist Duct I Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Mats Trunk rb4 Ox 0 321 319 64.0 0.028 300 14.0 Ox 0 VIFx rb10 I Ox 0 I 479 481 35.0 0.052 450 14.0 Ox 0 VIFx 2016-Sep-22 10:06.40 WI'19�7tSOft Right-Sude®Universal 2017 17 0 04 RSU17457 page 2 Zak _\Schooling Residence.350 Third St.Atl Bch.rup Calc=MJ8 faces. N 4 wrightsoft Duct System Summarytabes 2nd Floor By: Exclusively for the use of: Ocean State Air Conditioning, Inc. Project Information For: Schooling Residence 350 Third St, Atlantic Beach, FL Heating Cooling External static pressure 0.10 in H2O 0.10 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.10 in H2O 0.10 in H2O Supply/ return available pressure 0.071 / 0.029 in H2O 0.071 / 0.029 in H2O Lowest friction rate 0.023 in/100ft 0.023 in/100ft Actual air flow 800 cfm 800 cfm Total effective length (TEL) 433 ft Supply Branch Detail Table Design Htg I Clg (Design Diam H x W Duct Actual I Ftg.Eqv I Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk Bath 2 h 2271 60 59 0.057 7.0 Ox 0 VIFx 35.0 90.0 st1 Bath 3 h 1990 53 52 0.035 6.0 Ox 0 VIFx 32.0 170.0 st1 Bed 1 c 3571 87 87 0.062 8.0 Ox 0 VIFx 25.0 90.0 st1 Bed 2-A h 4061 108 108 I 0.026 9.0 Ox 0 VIFx 42.0 230.0 st1 Bed 3-A h 4028 107 106 I 0.055 8.0 Ox 0 VIFx 18.0 110.0 st1 Laundry c 1444 38 38 0.029 5.0 Ox 0 VIFx 31.0 210.0 st1 Loft c 1646 38 40 0.037 6.0 Ox 0 VIFx 22.0 170.0 st1 Owner Bath c 3695 90 90 0.023 9.0 Ox 0 VIFx 57.0 250.0 stl Owner Closet h 2317 62 61 0.024 7.0 Ox 0 VIFx 44.0 250.0 st1 Owner Ste c 1863 43 46 0.029 6.01 Ox 0 VIFx 54.0 190.0 st1 Owner Ste.-A c 1863 43 46 0.037 6.01 Ox 0 VIFx 44.0 150.0 st1 Stairs h 2596 69 66 0.050 7.0 Ox 0 VIFx 12.0 130.0 st1 Supply Trunk Detail Table Trunk Htg 1 Clg Design Veloc I Diam H x W Duct I Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 Peak AVF 800 800 0.023 367 20.0 0 x 0 VinIFIx Bold/italic values have been manually overridden 2016-Sep-22 10:06:40 "f wrightsoft Right-Suites Universal 2017 17 0 04 RSU17457 Page 3 ACOA _\Schooling Residence,350 Third St,All Bch.rup Calc=MJ8 faces: N Return Branch Detail Table Grill Htg Cig TEL Design I Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb3 Ox 0 191 192 74.0 0.039 244 12.0 Ox 0 VIFx rt1 rb5 Ox 0 203 203 116.0 0.025 258 1 12.0 Ox 0 VIFx rt1 rb8 Ox 0 268 266 126.0 0.023 251 I 14.0 Ox 0 VIFx rt1 rb9 Ox 0 138 139 86.0 0.034 255 I 10.0 Ox 0 VIFx I rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc I Diam I H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt1 Peak AVF 800 800 0.023 367 20.0 0 x 0 VinIFIx 2016-Sep-22 10:06.40 wrightsoft Right-Suite®Universal 2017 17 0.04 RSU17457 Page 4 AZ—Ch _\Schooling Residence.350 Third St.Atl Bch.rup Calc=MJ8 faces. N FORM R405-2014 OFFICE COPY G ve s 1-7°') S -° RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2014 Florida Building Code, Energy Conservation via the residential Simulated Performance method shall include ❑ This checklist ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, e-ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst-case orientation, name and version of the compliance software tool, name of individual completing the compliance report (1 page) and an input summary checklist that can be used for field verification (usually 4 pages/may be greater). ❑ Energy Performance Level(EPL) Display Card(one page) ❑ Mandatory Requirements(three pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist(Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report(usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage". then a completed Form R405 Duct Leakage Test Report (usually one page) c � cav OCT 1 9 2016 EnergyGauge®-USRCSB v5.1 9/19/2016 4:28:21 PM Page 1 of 1 OFFICE COPY FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Schooling Guest House Builder Name: Street: 350 Third St Permit Office: Atlantic Beach City.State.Zip: Atlantic Beach,FL. Permit Number: Owner: Jurisdiction: 261100 Design Location: FL,MAYPORT_NS County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types (698.9 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame-Wood, Exterior R=19.0 571.48 ft' b. Frame-Wood.Adjacent R=19.0 127.40 ft2 3. Number of units.if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 0 d.N/A R= ft' 5. Is this a worst case'? No 10.Ceiling Types (397.0 sqft.) Insulation Area a. Roof Deck(Unvented) R=22.0 397.00 ft 6. Conditioned floor area above grade(ft') 343 b. N/A R= ft2 Conditioned floor area below grade(ft') 0 c.N/A R= ft2 11. Ducts R ft' 7. Windows(113.2 sqft.) Description Area a. U-Factor: Dbl,U=0.40 113.20 ft' SHGC: SHGC=0.25 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 8.1 SEER:15.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 10.9 HSPF:10.00 SHGC: Area Weighted Average Overhang Depth: 4.754 ft. Area Weighted Average SHGC: 0.250 14. Hot water systems a. Propane Tankless Cap: 1 gallons 8. Floor Types (343.0 sqft.) Insulation Area EF:0.750 a.Slab-On-Grade Edge Insulation R=0.0 343.00 ft' b. Conservation features b.N/A R= ft2 None c. N/A R= ft2 15. Credits None Total Proposed Modified Loads: 14.28 PASS Glass/Floor Area: 0.330 Total Baseline Loads: 17.25 I hereby certify that the plans and specifications covered by Review of the plans and .r.�O�ZNE STq? this calculation are in compliance with the Florida Energy specifications covered by this = ti. ' ,-' = s O�;':S Code. m calculation indicates compliance �' %o, 6• • °.• t3 • _,( ) .� Ryan B. Ellis with the Florida Energy Code. i' u) n« "'.; ::'::i�.,,;;,,,4,., 0 . PREPARED BY: Before construction is completed ,' ���,'c ... s DATE: 9/19/16 this building will be inspected for I _...;. ,_ I•`a i compliance with Section 553.908 N. . ,p - ,., . Florida Statutes. ' f -' = I hereby certify that this building, as designed, is in compliance `s, •�y with the Florida Energy Code. • COD wE' ,,.•' OWNER/AGENT: BUILDING OFFICIAL: •'.••. •.• �.•• DATE: DATE: Q e-/& - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 4 FORM R405-2014 PROJECT Title: Schooling Guest House Bedrooms: 0 Address Type: Street Address Building Type: User Conditioned Area: 343 Lot# Owner: Total Stories: 1 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Rotate Angle: 0 Street: 350 Third St Permit Office: Atlantic Beach Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, New/Existing: New(From Plans) Comment: CLIMATE JIECC Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,MAYPORT_NS FL MAYPORT NS 2 39 90 70 75 1037 61 Medium BLOCKS Number Name Area Volume 1 Block1 343 3121.3 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfiIID Finished Cooled Heated 1 Main 343 3121.3 No 2 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter R-Value Area Tile Wood Carpet 1 Slab-On-Grade Edge Insulation Main 76.8 ft 0 343 ft' —__ 0 0 1 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or shed Composition shingles 397 ft2 100 ft2 Medium 0.96 No 0 9 No 22 30.3 ATTIC ✓' # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 343 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type _^ 1 Under Attic(Unvented) rvlain 0 Blown 397 ft2 0.11 Wood 9/1912016 4:28 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 4 FORM R405-2014 WALLS / Airdjacent Cavity Width Height Sheathing Framing Solar Below V # Ornt--_ WaILT.ype Space R Value Ft In Ft In Area R Values_ .Fraction__.Ab5rf r c1P% 1 W Exterior Frame-Wood Main 19 24.4 9.1 222.0 ft2 0.05 0.170000 0 2 S Garage Frame-Wood Main 19 14 9.1 127.4 ft2 0.05 0.170000 0 3 E Exterior Frame-Wood Main 19 24.4 9.1 222.0 ft2 0.05 0.170000 0 4 N Exterior Frame-Wood Main 19 14 9.1 127.4 ft2 0.05 0.170000 0 WINDOWS Orientation shown is the entered.Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 W 1 Vinyl Low-E Double Yes 0.4 0.25 43.2 ft2 6 ft 0 in 1 ft 0 in Drapes/blinds None 2 W 1 Vinyl Low-E Double Yes 0.4 0.25 40.0 ft2 6 ft 0 in 1 ft 0 in Drapes/blinds None 3 N 4 Vinyl Low-E Double Yes 0.4 0.25 30.0 ft2 1.299999 1 ft 0 in Drapes/blinds None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 70 ft2 384 ft2 24 ft 9.1 ft 0 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000289 260.1 14.28 26.85 .2226 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:10 10.9 kBtu/hr 1 Ductless COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER: 15 8.1 kBtu/hr 243 cfm 0.75 1 Ductless HOT WATER SYSTEM V _ # System Type SubType Location EF Cap Use SetPnt Conservation _ 1 Propane Tankless Exterior 0.75 1 gal 60 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 9;19.2016 4:28 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 4 FORM R405-2014 TEMPERATURES Programable Thermostat: None Ceiling Fans: Coolin Jan Feb Mar A r Ma X Jun X Jul X Au X Se Oct [ Nov Dec Heatin 'X Jan X Feb XI Mar ' Apr l Mal Jun l Jul t Aul SethJ Oct [XI Nov l Dec VentingJan [ Feb X Mar X Apr [ May [ Jun [ Jul [ Aug [ Sep ( Oct X Nov [ Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 4 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 83 The lower the EnergyPerformance Index, the more efficient the home. 350 Third St, Atlantic Beach, FL, 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area a.Frame-Wood.Exterior R=19.0 571.48 ft' 2. Single family or multiple family Single-family b.Frame-Wood,Adjacent R=19.0 127.40 ft' 3. Number of units,if multiple family 1 c.N/A R= ft' 4. Number of Bedrooms 0 d.N/A R= ft' 10.Ceiling Types Insulation Area 5. Is this a worst case? No a.Roof Deck(Unvented) R=22.0 397.00 ft' 6. Conditioned floor area(ft') 343 b.N/A R= ft2 c.NiA R= ft2 7. Windows" Description Area 11.Ducts R ft' a. U-Factor: Dbl.U=0.40 113.20 ft2 SHGC: SHGC=0.25 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: NIA ft' a.Central Unit 8.1 SEER:15.00 SHGC: d. U-Factor: NIA ft2 13.Heating systems . kBtu/hr Efficiency SHGC: a.Electric Heat Pump 10.9 HSPF:10.00 Area Weighted Average Overhang Depth: 4.754 ft. Area Weighted Average SHGC: 0.250 8. Floor Types Insulation Area 14.Hot water systems Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 343.00 ft' a.Propane EF:0.75 b.NIA R= ft2 b. Conservation features c.N/A R= ft' None 15.Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building O`--}11 s�--,.:-, Construction through the above energy saving features which will be installed (or exceeded) .;(,, ri.... in this home before final inspection. Otherwise, a new EPL Display Card will be completed ,--,. -c. based on installed Cod ompliant features. =• s. ice,,.'.i. Builder Signature: Date: CJ -06 Address of New Home:',S5 ` d.5 f A-•13, City/FL Zip: D 01.23 3 ``: .1 c. „„•,,,,:// , tUU WI i\ *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 . FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 83 The lower the EnergyPerformance Index, the more efficient the home. 350 Third St, Atlantic Beach, FL, 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 571.48 ft= b.Frame-Wood.Adjacent R=19.0 127.40 ft= 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 0 d.N/A R= ft, 10.Ceiling Types Insulation Area 5. Is this a worst case? No a.Roof Deck(Unvented) R=22.0 397.00 ft' 6. Conditioned floor area(ft') 343 b.N/A R= ft' 7. Windows" Description Area c.NIA R= 112 a. U-Factor: Dbl.U=0.40 113.20 ft' 11.Ducts • R ft' SHGC: SHGC=0.25 b. U-Factor: NIA ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 8.1 SEER 15.00 SHGC: d. U-Factor: N!A ft' 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 10.9 HSPF:10.00 Area Weighted Average Overhang Depth: 4.754 ft. • Area Weighted Average SHGC: 0.250 • • 8. Floor Types Insulation Area 14.Hot water systems Ca 1 gallons ' a.Propane p a.Slab-On-Grade Edge Insulation R=0.0 343.00 ftane EF:0.75 b.N/A R= ft' c.N/A R= ft' b. Conservation features None 15.Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building =titin 5 ` ...--� Construction through the above energy saving features which will be installed (or exceeded) ' F•= in this home before final inspection. Otherwise, a new EPL Display Card will be completed �� , •f , .v based on installed Code c liant features. '''":.'i ale • al.. Builder Signature: ) Date: CFA 4� ~ r' Address of New Home: .City/FL Zip: -�: '� '_`-'�1 . '. '� -. 3� . ._. • *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 • FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 350 Third St Permit Number: Atlantic Beach .FL, MANDATORY REQUIREMENTS See individual code sections for full details. X 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law[Section 553.9085. Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. X R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. X R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2.and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake.makeup air.backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3. Interior doors.if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed: 5.Heating and cooling systems,if installed at the time of the test.shall be turned off;and 6.Supply and return registers,if installed at the time of the test.shall be fully open. X R402.4.2 Fireplaces.New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. X R402.4.3 Fenestration air leakageWindows.skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. X R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. X R403.1.1 Thermostat provision(Mandatory).At least one thermostat shall be provided for each separate heating and cooling system. X R403.1.3 Heat pump supplementary heat(Mandatory)Heat pumps having supplementary electric-resistance heat shall have controls that. except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. X R403.2.2 Sealing(Mandator011 ducts,air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99. Florida Statutes,or as authorized by Florida Statutes.to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 Umin)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa)across the entire system.including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test.If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm(85 Umin)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) X R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. 0 X R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)or below 55°F(13°C)shall be insulated to a minimum of R-3.. R403.3.1 Protection of piping insulation. R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. X R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3%inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. X R403.4.4 Water heater efficiencies(Mandatory). X R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). ▪ R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of combustion types of service water heating systems to be turned off. X R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code.Energy Conservation,Commercial Provisions.for the type of equipment installed.Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. ▪ R403.4.4.2.1 Solar water heating systems.Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806.Test Methods for Solar Collectors,and SRCC Standard TM-1.Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. 0 R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code. Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation.Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. X R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. X R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load.but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 2 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) X R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment).the blower cfm provided by the expanded performance data,the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer. in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. X R403.6.1.2 Heating equipment capacity - R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. • R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. ▪ R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. X R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis.such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building.shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F.and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. ❑ R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56.Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2.Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: - 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or solar ▪ energy source computed over an operating season. X RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights X R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. X R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space,R-10 is allowed. 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compli Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Schooling Guest House Builder Name: Street 350 Third St Permit Office: Atlantic Beach City,State,Zip: Atlantic Beach ,FL. Permit Number: Owner Jurisdiction: 261100 Design Location: FL,MAYPORT_NS COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. X Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. X Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. X Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and X Rim joists Rim joists are insulated and include an air barrier. X Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. X The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. X Exposed earth in unvented crawl spaces shall be covered with a Class I Shafts, penetrations Duct shafts. utility penetrations, and flue shaft openings to exterior or X unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit. or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity X spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. X Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be X air tight, IC rated. and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls. or insulation that on installation readily conforms to X available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air X barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or X air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be X sealed to the sub-floor or drywall. Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have X gasketed doors 9/19/2016 4:28 PM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 Job: +1+ wrightsoft Project Summary Date: 9/18/16 Entire House Energy Design Systems, Inc. 11727 Brady Rd.Jacksonville, FL 32223 Phone 904-268-3670 Fax 904-268-3670 Email eds jax@gmail corn Pro'ect Information For: Schooling Guest House 350 Third St,Atlantic Beach, FL Notes: Desi• n Information Weather: Mayport Ns, FL, US Winter Design Conditions Summer Design Conditions Outside db 38 °F Outside db 94 °F Inside db 68 °F Inside db 75 °F Design TD 30 °F Design TD 19 °F Daily range L Relative humidity 50 % Moisture difference 50 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 7071 Btuh Structure 6605 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 7071 Btuh Use manufacturer's data Y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 6605 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 1 (Average) Structure 969 Btuh Ducts 0 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 343 343 Equipment latent load 969 Btuh Volume (ft3) 3121 3121 Air changes/hour 0.99 0.32 Equipment total load 7574 Btuh Equiv. AVF (cfm) 52 17 Req. total capacity at 0.72 SHR 0.8 ton Heating Equipment Summary Cooling Equipment Summary Make Mitsubishi Electric Cooling & Heating Make Mitsubishi Electric Cooling & Heating Trade Mr. Slim Trade Mr. Slim Model SUZ-KAO9NA Cond SUZ-KAO9NA AH RI ref 3837466 Coil SEZ-KDO9NA AH RI ref 3837466 Efficiency 10 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 5670 Btuh Heating output 10900 Btuh @ 47°F Latent cooling 2430 Btuh Temperature rise 31 °F Total cooling 8100 Btuh Actual air flow 315 cfm Actual air flow 315 cfm Air flow factor 0.045 cfm/Btuh Air flow factor 0.048 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.87 Capacity balance point = 28 °F Backup: Input = 2 kW, Output = 7071 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2016-Sep-19 15 56'01 * wrightsoft Right-Suite®Universal 2017 17.0.04 RSU17457 Page 1 AC .chooling Guest House.350 Third St.Atl Bch.rup Calc=MJ8 Front Door faces W mManual S Compliance Report Job: -�+ wrightsoft p p Date: 9/18116 Entire House By: M.Ellis Energy Design Systems, Inc. 11727 Brady Rd.Jacksonville, FL 32223 Phone.904-268-3670 Fax 904-268-3670 Email:eds.jax@gmaa corn Project Information For: Schooling Guest House 350 Third St,Atlantic Beach, FL Cooling Equipment Design Conditions Outdoor design DB: 94.4°F Sensible gain: 6605 Btuh Entering coil DB: 75.0°F Outdoor design WB: 77.4°F Latent gain: 969 Btuh Entering coil WB: 62.5°F Indoor design DB: 75.0°F Total gain: 7574 Btuh Indoor RH: 50% Estimated airflow: 315 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Mitsubishi Electric Model: SUZ-KAO9NA+SEZ-KDO9NA Actual airflow: Cool 1§& Fdif3zating Sensible capacity: 5994 Btuh 91% of load Latent capacity: 2106 Btuh 217% of load Total capacity: 8100 Btuh 107% of load SHR: 74% Heating Equipment Design Conditions Outdoor design DB: 38.1°F Heat loss: 7071 Btuh Entering coil DB: 68.0°F Indoor design DB: 68.0`F Manufacturer's Performance Data atActual Design Conditions Equipment type: Split ASHP Manufacturer: Mitsubishi Electric Model: SUZ-KA09NA+SEZ-KDO9NA Actual airflow: 315 cfm Output capacity: 10900 Btuh 154% of load Capacity balance: 28 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 315 cfm Output capacity: 2.1 kW 100% of load Temp. rise: 50 °F The above equipment was selected in accordance with ACCA Manual S. 2016-Sep-19 15-56 01 WI'19f1tSOft Right-Suite®Universal 2017 17 0 04 RSu17457 Page 1 ACCA .chooling Guest House, 350 Third St,Atl Bch nip Calc=MJ8 Front Door faces W