Untitled (37) r 4 ENGLAND G TI-IIMS, INC \ CONSULTING AND DESIGN ENGINEERS 6136 ATLANTIC BLV(0. JACKSONVILLE. FL 32211 (904] 724-9436 April 15, 1983 y Mr. William M. Baldwin, P.E. ��7rg 6x T$ r� Cedars Executive Center - Suite 250-E llp,� ID 2639 North Monroe Street APR _ j_.-; Tallahassee, FL 32303 Reference: Atlantic Village Center CITY OF City of Atlantic Beach ATLANTIC BEACH E83-04-1 Dear Bill : Pursuant to your submittal of the final paving and drainage design for the referenced project we have completed the review and find the plans approved subject to the following modifications. 1. Provide physical slope on 24" RCP storm drainage along Royal Palm Drive. 2. All drainage structures shall be pre-cast or poured in place concrete. Concrete block endwalls are not acceptable. 3. Provide underdrain in the westerly retention basin. 4. Overflow from northerly retention basin must be piped. 5. Provide curb or regrade pavement in the N.W. area of the project to insure runoff does not sheet flow over the sides of the outfall ditch. 6. Show outfall ditch section on plans. 7. Increase westerly drainage easement to 50 ft. to allow for maintenance berm. 8. Resolve conflict between 24" storm sewer and 8" sanitary sewer at N.E. portion of the project. Please make these modifications and submit revised plans to be inserted into the approved building permit plans. Should you have any questions, please call . Sincerel , G/7- Douglas s . Miller, P.E. Vice President DCM/cwb' ✓cc: Bill Moss