1756 ATLANTIC BEACH DR -DENSITY TEST 4 , UNIVERSAL UES Project No: 0910.1400187.0000 . Workorder No: 185460-1 ENGINEERING SCIENCES Report Date: 3/29/2017 Consultants In:Geotechnical Engineering•Environmental Sciences Geophysical Services•Construction Materials Testing•Threshold Inspection Building Inspection•Plan Review•Building Code Administration 5561 Florida Mining Blvd So.,Jacksonville, 32257 • P: 904-296-0757 • F: 904-296-0748 In-Place Density Test Report Client: UES Technician: Michael Zimmerman 160 Cape May Avenue Ponte Vedra, FL 32081 Date Tested: 03/29/2017 Project: 1756 Atlantic beach Dr, Atlantic Beach Country Club Area Tested: lot 72 Type of Test: Material: Fill Field: ASTM D-6938 Nuclear Gauge Metho Reference Datum: 0 = Top of Fill Laboratory: ASTM D1557 Modified Proctor The tests below meet the minimum 95% relative soil compaction requirement of Laboratory Proctor maximum dry density. Vlaximum Optimum Field Dry Field Soil Fill TestDepth Density Moisture Density Moisture Compaction (inch) Pass No. Location of Test Range (pcf) (%) (pcf) (%1 (%1 (inch) or Fail 1 4' N X 4' E FROM SWC 0 - 1 ft 102.3 14.6 96.8 7.9 95 N/A Pas: 2 4' S X 4' E FROM NWC 0 - 1 ft 102.3 14.6 101.2 12.6 99 N/A Pas: 3 4' S X 4' W FROM NEC 0 - 1 ft 102.3 14.6 101.5 13.7 99 N/A Pas: 4 4' N X 4' W FROM SEC 0 - 1 ft 102.3 14.6 98.3 9.3 96 N/A Pas: Tn n..fnhli..h ,,,,.f,.nl nmfn nf;nn f.I/n;..n r..n/',.nl...n4.. Ihn O..I.I;..nnrl n..rrnl..nn n/l rn nn.in nm r,.hm;lfnr!n..nn.Crinnf;nl nrnnnrh,. n...nlinnfn enrf o..fhnri+efinn FORM BOARD ELEVATION CERTIFICATE Date Permit Number: /G-s, "i2 - 7-oB/ Address: /7.3-G /la.e/, ,!' / All American Surveyors Work Order # Requir 'J Slab Elevation on City Approved Site Plan: Actual Elevation of Form Board or Grade Stake: / Z. Z Survey Company: ALL AMER:CAN SURVEYORS OF FLORIDA INC. 3751 San Jose Pace, Suite 15 Jacksonville FL 32257 Work Phone: 904-279-0088 Signature of Surveyor: (PartyChief) 5 c /0 FORM BOARD ELEVATION CERTIFICATE Date Permit Number: « -c c • 3t-i� /7/6 �T ) iG Address: All American Surveyors Work Order # is'Q17S i Required Slab Elevation on City Approved Site Plan: /3, Actual Elevation of Form Board or Grade Stake: /-3. to Survey Company: ALL AMERICAN SURVEYORS OF FLORIDA INC. 3751 San Jose Place, Suite 15 Jacksonville FL 32257 Work Phone: 904-279-0088 Signature of Surveyor: (PartyChief) Pr %�_ UNIVERSAL UES Project No: 0910.1400187.0000 4 pi Workorder No: 185386-1 ENGINEERING SCIENCES Report Date: 3/28/2017 Consultants In:Geotechnical Engineering•Environmental Sciences Geophysical Services•Construction Materials Testing•Threshold Inspection /� Building Inspection•Plan Review•Building Code Administration 5.> c a r✓�,eo dr e_ 5561 Florida Mining Blvd So.,Jacksonville, 32257 • P:904-296-0757 • F: 904-296-0748 / In-Place Density Test Report Client: UES Technician: Kevin Gagnon 160 Cape May Avenue Ponte Vedrar 081 Date Tested: 03/28/2017 Project: 1716 Maritime Oak Dr, Atlantic Beach Country Club Area Tested: house pad Type of Test: Material: Fill Field: ASTM D-2937 Drive Cylinder Method Reference Datum: 0 = Top of Fill Laboratory: ASTM D1557 Modified Proctor The tests below meet the minimum 95% relative soil compaction requirement of Laboratory Proctor maximum dry density. Maximum optimum Field Dry Field Soil Fill Test Densi Depth Pass tY Moisture Density Moisture Compaction No. Location of Test Range (pc{) tool (pcf) (%) (%) (inch) or Fail 1 17'W 7' N of SE corner 0-1 ft 102.3 14.6 97.4 10.7 95 N/A Pas: 2 23' E 11' N of SW corner 0-1 ft 102.3 14.6 98.5 3.9 96 N/A Pas: 3 10'S 10' E of NW corner 0-1 ft 102.3 14.6 97.6 4.1 95 N/A Pas: 4 6' S 38' E' E of NW corner 0-1 ft 102.3 14.6 97.7 3.7 96 N/A Pas: To establish a mutual protection to Universal's clients, the Public and ourselves,all reports are submitted as confidential property of our clients and authorization