Selva Preserve Replat App - Fire Dept Corretion Commentd 12-5-17Fire Plans Review Fire Prevention Division
214 N. Hogan Street, Room 281
Jacksonville, Florida 32202
CORRECTIONS
CONTRACTOR: Selva Preserve LLC
PROJECT ADDRESS: 111h Street & Link Side Place
PERMIT NUMBER: 17-SPPR-501
The plans submitted for review have been returned for corrections. Please correct or provide the proceeding
requested information to obtain plans approval. When resubmitting corrected sheets, please provide a
written narrative letter responding to our comments and directing the plans reviewer to the sheets the
changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER "WILL" RESULT IN A RETURNED FOR
CORRECTIONS PERMIT STATUS. Revised sheets should be clouded clearly showing areas were changes or
corrections have occurred and re-inserted with the original set of drawings with old sheets removed. Unbound
plans will not be reviewed. If this is an electronic submission please make sure that written narrative is
submitted under correspondence along with a "complete set" (not just the revised sheets) of electronic
documents.
Required Fire Flow: NFPA 118.4 and Table 18.4.5.1.2
Please Provide Fire Flow Calculations Performed Within The Last Year For the Nearest Fire Hydrant Located
Within 500' Of The Most Remote Point Of The Proposed Building In Accordance With NFPA 1, Chapter 18 "Fire
Flow Requirements For Buildings" (2012 5th Edition) NFPA 1, 18.4.1.1* The procedure determining fire flow
requirements for buildings hereafter constructed or moved shall be in accordance with Section 18.4.NFPA 1,
18.4.5.2 Buildings Other Than One- and Two -Family Dwellings. The minimum fire flow and flow duration for
buildings other than one- and two-family dwellings shall be as specified in Table 18.4.5.1.2. Publicly Owned
Fire Hydrant Flow Calculations may be provided by the water purveyor. Private Hydrant Calculations May Be
Obtained Through The Services Of A Fire Protection Contractor Witnessed By The Local AHJ.