1545 MAIN ST - ANTENNA TO EXISTING TOWER ri,,,J r�r,
:�s ' CITY OF ATLANTIC BEACH
�`a r 800 SEMINOLE ROAD
,V -=',
ATLANTIC BEACH, FL 32233
it
4Olt v INSPECTION PHONE LINE 247-5814
COMMERCIAL - ALTERATION COMMERCIAL
MUST CALL BY 4PM FOR NEXT DAY INSPECTION: 247-5814
PERMIT INFORMATION:
PERMIT NO: COMM17-0026
Description: add antenna to existing support tower&concrete pad
Estimated Value: 35000
Issue Date: 12/14/2017
Expiration Date: 6/12/2018
PROPERTY ADDRESS:
Address: 1545 MAIN ST
RE Number: 172325 0010
PROPERTY OWNER:
Name: PAR PRO LTD
Address: PO BOX 330177
ATLANTIC BEACH, FL 32233-0177
GENERAL CONTRACTOR INFORMATION:
Name:
Address:
Phone:
Name: CROWN CASTLE USA, INC
Address: 4511 NORTH RIMES AVE SUITE 210
TAMPA, FL 33614
Phone:
PERMIT INFORMATION:
Please see attached conditions of approval.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOU PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF
COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB
SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY
BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
* A notice of Commencement is only required for work exceeding an estimated value of
$2,500. For HVAC work, a Notice of Commencement is only required when HVAC work
exceeds and estimated value of$7,500.
i!.Ait-- 4 , City of Atlantic Beach APPLICATION NUMBER
r4 it r f�\ Building Department (To be assigned by the Building Department.)
800 Seminole Road C f M II
-00)k'
j- , Atlantic Beach, Florida 32233-5445 W M (•C�
Phone(904)247-5826 • Fax(904)247-5845
J�3 �'r E-mail: building-dept@coab.us Date routed: I 1 / 1/
City web-site: http://www.coab.us `
APPLICATION REVIEW AND TRACKING FORM
Property Address: IS' tS Mlkt(1 5+ _ De
_ •artment review required Yes No
A Buildin.
Applicant: C(Oi�,n toc�� A A) 311C. Planning &Zoning
Tree Administrator
Project: ; (1 Si-t i) an.ttAna On L' 1'S-f u1,-- ---./01 s
IbtAi. / � COAL(
,Public Utilities
�( et4A W AL(C kd Public Safety
Fire Services
Review fee $ _ Dept Signature _
Other Agency Review or Permit Required Review or Receipt Date
of f Pe rmit Verified By _
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St. Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: Approved. ['Denied. ❑Not applicable
(Circle one.) Comments:
BUILDING -. r
PLANNING &ZONING
Reviewed by: t� % c% \l`l Date:
TREE ADMIN. Second Review: ['Approved as revised.
❑ pp ['Denied. ['Not applicable
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ['Approved as revised. ❑Denied. ❑Not applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
1 vtrie, City of Atlantic Beach APPLICATION NUMBER
r: Building Department (To be assigned by the Building Department.)
r _ ,� ` 800 Seminole Road a p, n A j 1- _/ '
Atlantic Beach, Florida 32233-5445 1.-lJl' Ivl 1 V dCJ
/ Phone(904)247 5826 Fax(904)247 5845 , i �,
I i
art 9' i' E-mail: building-dept@coab.us Date routed:
City web-site: http://www.coab.us
APPLICATION REVIEW AND TRACKING FORM
Property Address: 1S'-tS lk& r 5-1' _ Department review required Yes No
A `'4. t c,� Building
Applicant: C 1Ov )R 6 .E- U JA-i , Planning &Zoning
Tree Administrator
Project: I (1 SA-4 II anttn,j a DA i...‘4511 ublic Work
Public Utilitie
.tpvJa (4 ' 4 Unu(1t4. •p&dSafety •
Fire Services
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: ,pproved. I 'Denied. ❑Not applicable
(Circle one.) Comments:
BUILDING (1—
PLANNING &ZONING
Reviewed by. �� Date:
7
TREE ADMIN. 4
Second Review: ['Approved as revised. ['Denied. ❑Not applicable
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied. fNot applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
1..Lvf�, City of Atlantic Beach APPLICATION NUMBER
L1�r Building Department (To be assigned by the Building Department.)
- W
800 Seminole Road /1�f1 pt M ' 't --0a
0
JNj rr Atlantic Beach, Florida 32233-5445 7 I
W Phone(904)247-5826 • Fax(904) 247-58 OV 3 201 , i
If/ -4--
0;119/ Email: building-dept@coab.us Date routed:
City web-site: http://www.coab.us �'
APPLICATION REVIEW AND TRACKING FORM
Property Address: ISLAS" MA-A 5+- _ De•artment review required Yes No
Buildin•
Applicant: C(OvJ(1. CAsiii_ vk-, anc. „ &Zoning.
a Tree Administrator
Project: ; (1 Silt ►) anttfl,na OA Q,\ti S1)/1JG `:ublic Wo
�i /�'l Public Utilitie
-
"'J� c Gld e.V ncl�� V kd Public Safety
Fire Services
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
►�.
Reviewing Department First Review: Approved. ❑Denied. •t applicable
(Circle one.) Comments:
BUILDING
PLANNING & ZONIN •G r .te: 7(-0—/1
Reviewed b ,. ////,
/_
TREE ADMIN. Second Review: Approved as revised. ❑Denied. ❑Not applicable
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied. I INot applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
ro...tv�;:,, City of Atlantic Beach APPLICATION NUMBER
�S n� Building Department (To be assigned by the Building Department.)
800 Seminole Road si /1 f1 pt „A ( •'4 �,11 'B,
,� ",, Atlantic Beach, Florida 32233-5445 2017 d 1 lam►KJ
Phone(904)247 5826 Fax(904)247 584�UV 3 /
amts'' E-mail: building-dept@coab.us Date routed: 1 I I '1
City web-site: http://www.coab.us -- -
APPLICATION REVIEW AND TRACKING FORM
Property Address: t S LAS- M[A.t!1 54 _ Department review required Yes No
A Buildin _
Applicant: C(OvJ(1 Wilt- �. ttS11-eit_... Planning &Zoning")
ree Administrator
Project: (0 Sill I) ajik-t1 xxa On bti s >� public Works
�) /„�''ll Public Utilities
ii)vJa � AA W n(J &el Public Safety
Fire Services
Review fee $ fi/ .---- Dept Signature ) .1%*,
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: ❑Approved. Denied. Not applicable
(Circle one.) Comments:
BUILDING
PLANNING & ZONING
Reviewed by: ate: VII 17
TREE ADMIN. Second Review: Approved as revised. ❑Denied. Not applicable
P aI9WORK Comments:
'UBLIC UTILIT S
/1—/t/— /7
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: Approved as revised. ❑Denied. ❑Not applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
812565/JA52XC035 - — - __
>f�"l BuildingPermit Application { �- u `�
t�
,s 1i d pp 1�1 f
t.) .1/1"
;� City of Atlantic Beach in NOV I,
I
800 Seminole Road,Atlantic Beach, FL 32233 t f L 8 2017 r,�
is Phone: (904) 247-5826 Fax: (904)247-5845 Lt i
c�MAA i1 —ole a .
Job Address: 1545 MAIN ST Atlantic Beach FL 32233 Permit Number: I
Legal Description 17-2S-29E 5.71 PT GOVT LOT 4 RECD O/R 11544-628 BEING PARCEL 3 RE# 172325-0000
Valuation of Work (Replacement Cost)$35,000 Heated/Cooled SF Non-Heated/Cooled
• Class of Work(Circle one): New Addition Alteration Repair Move Demo Pool Window/Door
• Use of existing/proposed structure(s)(Circle one): ommerci3D Residential
• If an existing structure,is a fire sprinkler system installed?(Circle one): Yes No (N/A)
• Submit a Tree Removal Permit Application if any trees are to be removed or Affidavit of No Tree Removal
Describe in detail the type of work to be performed:
Propose KMW antenna ETCT654L12H6, 4 radios, 1 filter, 1 Hybrid per sector, 1 fiber.
Florida Product Approval# for multiple products use product approval form
Property Owner Information
Name: Crown Castle for Sprint Address: 4511 N.Himes Ave.,Ste.210
City Tampa State FL Zip 33614 Phone 813-342-3852
E-Mail donna.carroll@crowncastle.com
Owner or Agent(If Agent, Power of Attorney or Agency Letter Required)
Contractor Information
Name of Company: crown Castle USA Inc Qualifying Agent: Richard Lee Cullum
Address 4511 N Himes Ave,Ste 210 City Tampa State FL Zip 33614
Office Phone 813-342-3852 Job Site/Contact Number 813-342-3852
State Certification/Registration# CGC062125 E-Mail c/o donna.carroll@crowncastle.com
Architect Name&Phone#
Engineer's Name&Phone#
Workers Compensation Trcwckrs Pfpvi y cap u.•t,3y L4-1-id _
Exempt/Insurer/Lease Employees/Expiration Date
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all the laws regulationg
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING,SIGNS,
WELLS, POOLS, FURNACES, BOILERS, HEATERS,TANKS,and AIR CONDITIONERS,etc.
OWNER'S AFFIDAVIT:I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT.
/X.,
£CoLP
(Signature of Ow or Agent including Contractor) (Signature of Contractor)
Signed and sworn to(or affirmed)before me this / day of Signed and sworn to(or affirmed)before me this i day of
YIOV , tot-, , by eVirl petiole- (10V , Z-011, by Poring C�tDl '
, /
(Signature of Notary) (Signature of Notary) .
=o A (-`'''lTERRI ANELLO
:-o`' °J• TERRI ANELLO MY COMMISSION #FF188523
MY COMMISSION#FF186523 ''..:N ,.P° EXPIRES January 11,2019
['Personally Known OR ,� '�� [, ]'Personally Known OR '••.,Fora.°.:
y' `i
[ I Produced Identification•''.:.FOF..ti°P` EXPIRES January 11, 2019 [ ]Produced Identification (40/)338-0153 FioridallotaryService.com
........
Type of Identification: 007)398 0153 FloridallotaryServire corn J Type of Identification:
Account Detail Page 1 of 2
_ rtiy _ ._.
-. . ..-....... .. ,, s MP .. .._
iffi
tl
dtr 1_ tura
_ r ziati l T' e._
Log,is for County Staff Only
Property Tax Search Account Detail Login
Welcome Account Detail
Property Tax Search
Search Results
Tangible Tax Search
Local Business Tax Search Important Notice
Collection Cart The Information contained herein does not constitute a title search and should not be relied on as such.There may be additional
balances that do NOT display on this weblike:unpaid(lens,Installment accounts or deleted accounts.
Tax Collector Home
To better serve property owners,homestead and other exemption-related liens filed by the Property Appraiser's Office have been added to the
Tax Collector's software.These exemption-releated liens are now viewable and payable online.These lien types may be researched at the
Clerk of courts website www.duvalclerk.com.
21
Property Tax Account Details Pay Current Taxes
Account I Property Type I Last Update
No Current Taxes.
172325-0000 REAL ESTATE 2/25/2017 11:20:07 PM
Mailing Address: SITUS:
PAR PRO LTD 1545 MAIN ST 32233 Pay Delinquent Taxes
PO BOX 330177
ATLANTIC BEACH,FL No delinquent payment due for
32233-0177 this account.
Millage Code Escrow Code
USD3
Legal Description I Cart:$0.00
17-2S-29E 5.71 PT GOVT LOT 4 RECD O/R 11544-628 BEING PARCEL 3
Nuisance and Demolition Liens
Nuisance and Demolition Liens are NOT included in the Property Tax bill.These liens
must be paid separately.Please call(904)255-7000 for information regarding these
specific lien types.
No Nuisance or Demolition Liens Found
Property Tax Bills
Tax Year I Folio I Owner Name I Amount Due I I
( 2013 1333981.0000 PAR PRO LTD $0.00
2012 1333723.0000 PAR PRO LTD $0.00
( 2011 ) 1333236.0000 PAR PRO LTD $0.00
( 2010 j 1333082.0000 PAR PRO LTD $0.00
( 2009 ) 1332723.0000 PAR PRO LTD $0.00
2008 ) 1332051.0000 PAR PRO LTD $0.00
2007 ) 1331267.0000 PAR PRO LTD $0.00
Total) $0.00 J
http://fl-duval-taxcollector.publicaccessnow.com/propertytaxsearch/accountdetail.aspx?p=... 2/28/2017
•
.August 11,2009
Mrs.Delia Rodriguez
Par-Pro,LTD
15«5 Main Street
Atlantic Beach,FL 32233-1938
RE: Business Unit#812565
Site Name: Mayport
Dear Mrs.Rodriguez
This Letter of intent("LOP')sets forth the terms of the agreement that is to be memorialized between Crown Castle
South LLC ("Lessee") and Par-Pro, LTD (Lessor). Lessor and Lessee intend to modify, among other things, the
length of the term of the lease agreement as may be amended ("Lease") for property located at 1545 Main St.,
Atlantic Beach,Duval County,Florida.
For and in consideration of One Hundred Dollars($100.00)paid by Lessee to Lessor.the parties agree as follows:
• 1. Lessor and Lessee will enter into an amendment to the Lease("Lease Amendment")wherein the term
of the Lease will be modified and the rent due under the Lease will be increased. The Lease currc try provides
that there is one(I)current remaining five(5)year term with a current lease expiration of February 2r2016. That
Lease section will be amended to provide that the remaining term of the Lease will be two(2)additional renewable
terms of 5 years each added on to the current final lease expiration date of February 28,2016. The new final Lease
expiration date will be February 28,2026.
in addition to the modification described above, the Lease Amendment will further modify the Lease to
provide that:
•
a. Lessor will receive a$250.00 monthly rent increase on September 1,2009.
b. Lessor's Rent will be reconciled by Lessee and adjusted and reimbursed If needed.
c. Lessor will receive the regularly scheduled five year monthly term rent increase of 115%
on March 1,2011,March 1,2016 and March 1,2021.
2. Lessor shall cooperate in all ways, including but not limited to providing information, signing
documents and seeking execution by third parties of documents that will remove, subordinate or satisfy any
mortgages.deeds of trusts,liens or other encumbrances affecting the Property.
3. Upon receipt of this LO1 evidencing Lessor's acceptance of the terms herein.Lessee shall submit this
LOY to its property committee. if the LO1 is approved by the property committee, Lessee shall prepare the draft
Lease Amendment and transmit it to Lessor, which agrees to review and respond to the some without any
unreasonable delay.
4. Regardless of whether the transaction contemplated by this LO1 is consummated. Lessor and Lessee
each will pay Its own out-of-pocket expenses.
5. Notwithstanding anything to the contrary contained heroin,Lessee shall have the right to terminate this
LO1 and/or decline to enter into the Lease Amendment for any or no reason at any time prior to MC execution of the
Lease Amendment, without damages to Lessor.
®tYX1 .cDate j&3t �Tpe
GUN: $(,D Slab Lease/Lic <�,(Q
UJI J. ...I UP V,•V., JV1L-1VJv� .-• 'v. V-, V../
•
•
•
6. Lessor represents and warrants that Lessor is duly authorized and has the full power, right and
authority to enter into this L01 and to perform all of its obligations under this LOI and to execute and deliver all
documents,including but not limited to the Lease Amendment, contemplated by this L01.. From the date of this LOl
thr•)ugh the date that Lessor executes the Lease Amendment, Lessor shall use its best effort' to ensure that the
forgoing representations and wananties shall remain true and correct end Lessor shall promptly notify Lessee if
any representation or warranty is or possibly may not be true or correct. Lessor's representations, warranties and
covenants shall survive following the Hill execution of the Lease Amendment
if u is LOl accurately sets forth our understanding regarding the foregoing, please so indicate by signing and
returning to the undersigned the enclosed copy of this letter.
Thanks and please sign and fax this back to my attention at 713-570-3110.
Michael Cianciola
Crown Castle Corporate Real Estate
712-57G-3060
Lessor:
Pau--Pro.LTDI
Cd-2--1.414445
Name: {i( ' N I A.b Q.l: l,!
Title: r/•"
Date: V/gAle-107
•
Lessee:
Crown Castle South LLC
By:
Name:
len Duran
Aid Acquisitk u int
Title: Crown CactleUSA
Late: 91201C')�
JAX\1366381 2 -2-
CINGULAR WIRELESS LEGAL REVIEW FACT SHEET
(Complete a Separate Fact Sheet for each Landlord and/or Legal Document)
BASIC INFORMATION
Date Created: 1/19/10 Region I Market: STA
Site Name: Mayport Site Number: 812565-Crown Castle
Consulting Entity submitting this Fact Sheet: Crown Castle South 10020470-Cingular
Consulting Entity Reviewer Name: Theresa Little Contact Number: 713-570-3052
E-Mail: theresa.little@crowncastle.corn
Site Acq. Coordinator/Consultant
(representing Consulting Entity ): Contact Number:
E-Mail Address:
If previously reviewed by Legal, name of reviewer:
Date of previous review:
Business Terms Approved By: Property Committee—9/23/2009
Cingular Wireless (REM)Approver's Signature(unless approval by e-mail, if so please attach)
Date of Approval
SITE INFORMATION
Type of Document/Project:
Lease Type: NEW BUILD ❑ UMTS ❑ DECOMMISSION ❑
Other, Indicate/Explain:
Amendment Type: TDMA/2G ❑ GSM/2.5G ❑ E911 ❑ 3G ❑ UMTS ❑
Other, Indicate/Explain: Lease Extension
Agreement Type: Land ❑ Land w/Option ❑ Structure ❑ Structure w/Option ❑
Additional Equipment Space Lease ❑
Other, Indicate/Explain:
Is this Lease associated with another(i.e. separate lease, easements, right of way etc.)? No ® Yes❑
If yes, explain:
Square footage of proposed lease premises:
Rent amount: $1008.33
Escalation: Fixed
Tax Lot Block: N/A
Site Address: 1545 Main Street, Atlantic Beach, FL 32233
County (where site is located), please attach vesting deed: Duval
Type of Site (check all that apply):
Collocation ❑ Relocation ❑ Tower® Rooftop ❑ Rooftop w/Ground ❑ Raw Land ❑
Apartment/Co-op/Condo ❑ Cell On Wheels ❑ Utility Tower❑
Other, Please indicate/explain(include all utility pole applications) ❑
Type of Equipment(check all that apply):
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company instructions
Page 1 of 6
TDMA Micro ❑ Macro ❑ GSM Micro ❑ Macro ❑ UMTS Micro❑ Macro ❑
Other❑ Please indicate type and explain (include all utility pole applications):
LANDLORD INFORMATION
Landlord Name: Par-Pro, Ltd.
Landlord Type (LLC, corp., indiv., partnership.) partnership
DOCUMENT INFORMATION—ALL APPLICABLE DOCUMENTS MUST BE ATTACHED
Cingular Wireless Form ❑ Landlord Form ❑ Site Lease (SLA) to MLA ❑
Lease Exhibit ❑
Is this a sublease? Yes ❑ No ❑ (if yes, attach copy of fully executed underlying prime lease)
Other® -- If other specify: Third Amendment to Option and Lease Agreement
IF SUE W1I TING Alu'LENDi EN7 PLEASE SE PROCEED i4 PAGE
I LEASE& OPTION AGREEMENTS
LANDLORD FORM
When submitting landlord form for review:
1) For each section of the lease, please identify any differences between landlord's language
and Cingular Wireless'standard language.
2) Please identify any additional language found in landlord's form that is not present in the
standard Cingular Wireless form.
3) Please identify the omission of any Cingular Wireless standard language that is not
included in landlord's form.
CINGULAR WIRELESS FORM DOCUMENTS
Indicate whether standard language is used, if menu language will be used, or if other language
will be used by marking the appropriate box below for each section of the lease. In the event
"Other" is check please provide reason for such deviation and if Landlord has suggested
language please insert after "LL's Suggested Language, if applicable". (Please Note: It's Cingular
Legal's preference to draft the language and present it to the Landlord.) For options, please
check the appropriate box in the "Option to Lease" section. For leases, please check the
appropriate box under the "Lease of Premises" section.
OPTION TO LEASE:
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company instru Oions
Page 2 of 6
No changes to standard language ❑ Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide sugguested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
LEASE OF PREMISES:
No changes to standard language El Menu Language El Other El
If other is checked, please describe reason for change and provide suggested language, if any.
3) LL's reason for change:
4) LL's suggested language, if applicable:
FOR BOTH OPTIONS AND LEASES, PLEASE CHECK THE APPROPRIATE BOX UNDER EACH SECTION BELOW.
PERMITTED USE:
No changes to standard language El Menu Language❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
TERM:
No changes to standard language ❑ Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
RENT:
No changes to standard language ❑ Menu Language El Other ❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
3) Change in the escalation percentage? No El Yes ❑ If yes, please explain:
APPROVALS:
No changes to standard language❑ Menu Language El Other El
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
TERMINATION:
No changes to standard language❑ Menu Language❑ Other❑ Termination Fee❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
3) • Change in the termination fee? No ❑ Yes ❑ If yes, please explain:
INSURANCE:
No changes to standard language El Menu Language El Other❑
If other is checked,please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
INTERFERENCE:
No changes to standard language ❑ Menu Language El Other El
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company instructions
Page 3 of 6
INDEMNIFICATION:
No changes to standard language El Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
WARRANTIES:
No changes to standard language El Menu Language ❑ Other ❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
ENVIRONMENTAL:
No changes to standard language ❑ Menu Language❑ Other 0
If other is checked,please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
ACCESS:
No changes to standard language ❑ Menu Language ❑ Other El
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
3) 24/7 access at no additional charge?Yes❑ No El If no, please explain:
REMOVAL/RESTORATION:
No changes to standard language 0 Menu Language El Other El
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
MAINTENANCE/UTILITIES:
No changes to standard language❑ Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
DEFAULT AND RIGHT TO CURE:
No changes to standard language El Menu Language 0 Other❑
if other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
ASSIGNMENT/SUBLEASE:
No changes to standard language❑ Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
NOTICES:
No changes to standard language❑ Menu Language 0 Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
SEVERABILITY:
No changes to standard language ❑ Menu Language❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company instructions
Page 4 of 6
1) LL's reason for change:
2) LL's suggested language, if applicable:
CONDEMNATION:
No changes to standard language❑ Menu Language El Other ❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
CASUALTY:
No changes to standard language El Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
WAIVER OF LANDLORD'S LIENS:
No changes to standard language❑ Menu Language ❑ Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
TAXES:
No changes to standard language❑ Menu Language El Other 0
If other is checked, please describe reason for change and provide suggested language, if any.
3) LL's reason for change:
4) LL's suggested language, if applicable:
SALE OF PROPERTY:
No changes to standard language❑ Menu Language 0 Other❑
If other is checked, please describe reason for change and provide suggested language, if any.
5) LL's reason for change:
6) LL's suggested language, if applicable:
MISCELLANEOUS:
No changes to standard language 0 Menu Language❑ Other 0
If other is checked, please describe reason for change and provide suggested language, if any.
1) LL's reason for change:
2) LL's suggested language, if applicable:
Yl,1S POffi7ON P1 UST QE COft1PLErED FOR AXEN MENFS
OTHER:
Relocation❑ if not standard menu language, please explain the deviation:
Power Upgrades El If not standard menu language, please explain the deviation:
Collocation Fee ❑ If not standard menu language, please explain the deviation:
Attorney Fees El If not standard menu language, please explain the deviation:
Capital Contribution❑ If not standard menu language, please explain the deviation:
Have you read the entire underlying lease you are seeking to amend to ensure Cingular's standard
requirements are met?Yes ® No❑ NIA El
List terms being amended: Note: Use the following format for antenna change outs, pole
replacements, change in square footage of Premises, changes in landscaping, etc., so your
changes are easily visible.
WHAT IS THERE WHAT IS BEING WHAT WILL CINGULAR
CURRENTLY? CHANGED? END UP WITH?
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company iistruwons
Page 5 of 6
Amount of Rental Increase!if any ❑ $ N/A❑ total amount$ NIA❑
Effective Date of Rental Increase:
List All Terms Being Amended/Added and Clearly Explain the Reason for each provision:
10 year lease extension.
Additional Comments:
•
THIS SECTION MUST BE COMPLETED FOR ALL DOCUMENTS.
BEFORE SUBMITTING THIS FACT SHEET, DID YOU REMEMBER TO ATTACH THE FOLLOWING?
1. ALL applicable back up documentation, including the following:
a)All documents referred to in your amendment Yes® No 0 N/A❑
b)All prior amendments(fully executed) Yes ® No❑ N/A 0
c)Copy of fully executed underlying prime lease Yes® No 0 N/A 0
d)Copy of fully executed Master lease Yes(El No 0 N/A 0
e)Deed Yes® No❑ N/A❑
f)Exhibits to Document submitted for review,if any and if available Yes® No D N/A 0
2. Cingular market authority's business approval (if e-mail) Yes❑ No❑ N/A El
3. Amendment to MOL(if Premises or Term is being amended) Yes® No 0 N/A❑
4. Copy of prior recorded MOL,if any Yes® No 0 N/A❑
5. SNDA Yes 0 No 0 N/A El
6. Is leasing entity is different than deed owner Yes 0 No❑ N/A El
if so provide info.which explains the different entity
(i.e. Homestead Affidavit,Corporate Resolution,Certificate of L.P.,etc.):
CINGULAR WIRELESS PROPRIETARY
Use pursuant to Company instructions
Page 6 of 6
—a . - -- - --—----T==,,To
'A !It t!Mili Itttt$I
g �� Ill L. __
I' -------- --- - - - --- -
Ai — ---- --i.
1.
"'900000090000009-990000. l'
/ t2
p•
to 3.3_iIi killabliAi eJJ.IE
iiF "--- -- ----------- -•-- -
i 2g11 7' _75a_,_, X7.71-7-2_2-2•--',..3.\'
4 [ a55555��$i Solo55f5°§
C. ! 11
li i ilfili hiT F[F
d K K K a N M I F F F F F F F F F F F F
a 1'r?ilrlig1iiiaafr[335a /
0 ccc_crtt:tr_[ttertcctrrt
co
I'1 L a s --._�... ..._.._..•,.._......-
j iicducsscuTtasa,auctaaaa1
v
fib
s Ass ASSESA -
al — - '{{ 1 $i1TF fi#1 flhiiius5
06 l i i' f l 1 T H flT H °,
I
11 c_t_c t_c_t t t a a__t_t_t t c t_
iiiii
ill
as3axa ,ir:a.i iii
tei te b :I b L Ili t 4 I I I I I l I I I I I I I I LLLLLLLL
CClsitesTM : Real Estate Information Manager Nage 1 of 3
cc11es ccL?° F
• � manager
home site information application tracking project information operations Information real estate forecasting my work
search list detail
MAYPORT-812565 (
prev
(1 of i) next
Financial Summary
Final Lease Expiration: 02/29/2016 Base Rent(Monthly): 608.33
Priority: Priority 1 Base Rent(Annual): 7,299.96
Tower Revenue(Annual): 67,477.80 Non Rent Exp(Annual): 4,706.97
Exp Incl Rent(Annual): 16,806.93 Revenue Share(Annual): 4,800.00
TMRR(Annual): 50,670.87 Margin: High Margin
Notes Processes Contacts Detail License Info Lease Info Deal List Deal Detail
[Save
Deal Overview - Site ID:812565 > Site Name: MAYPORT
Load Transaction Model
Deal ID: 33970 Status:* Active
Deal Name:* 10 year LE
Deal Type:* Extension Bonus Deal End Date:
Created: Feb 19 2009 Created By: Michael Cianciola
Customer Waiting? 0 Yes 4)No Mandatory Close By Date:
*Indicates a required field.
Milestones
Dep. Sent/Ord'd/ Rec/ Last Mod
tf Milestone ~ !t Due Complete n/a By/Date Comments
1 Deal Negotiation Begun Sep 01 2009 Sep 03 2009 Michael
Clanciola
Sep 21
2009
2 LOI Sent to Landlord 1 Sep 07 2009 Sep 10 2009 Michael
Cianciola
Sep 21
2009
3 101 Signed by Landlord 2 Sep 14 2009 Sep 17 2009 Michael
Clanciola
Sep 21
2009
4 Submit for PC Approval 3 Sep 21 2009 BEN
DURAN
Sep 21
2009
5 Deal Approved 4 Sep 24 2009 Hal
Frazer
Sep 24
2009
6 Submit for Reapproval 5
7 Reapproval 7 6
8 Deal Assigned 5 Sep 25 2009 �9 Q Sherri
Sacks
Sep 25
2009
9 Initial Deal Documents Sep 28 2009 Eli oct 02 2009 SUSAN
MOTr
Oct 02
http://www.ccisites.com/eng/Irm/detail.do 1/19/2010
PAULJ. FORD fiR
PJF & COMPANY
1965-2015
Date: August 28, 2017
Angela Harris BUILDING DEPARTMEMaul J Ford and Company
Crown Castle 0 E. Broad Street Suite 600
12725 Morris Road Extension Suite 400 APPROVED Columbus, OH 43215
Alpharetta, GA 30004 614.221.6679
Subject: Structural Analysis Report
Carrier Designation: Clearwire Corp Co-Locate
Carrier Site Number: JA52XC035
Carrier Site Name: NA
Crown Castle Designation: Crown Castle BU Number: 812565
Crown Castle Site Name: MAYPORT
Crown Castle JDE Job Number: 454367
Crown Castle Work Order Number: 1446144
Crown Castle Application Number: 402364 Rev. 2
Engineering Firm Designation: Paul J Ford and Company Project Number: 37517-3033.001.8700
Site Data: 1545 Main Street, Atlantic Beach, Duval County, FL
Latitude 30°20'13", Longitude-81°25'12"
190 Foot-Self Support Tower
Dear Angela Harris,
Paul J Ford and Company is pleased to submit this "Structural Analysis Report" to determine the structural
integrity of the above mentioned tower. This analysis has been performed in accordance with the Crown Castle
Structural 'Statement of Work' and the terms of Crown Castle Purchase Order Number 1074303, in accordance
with application 402364, revision 2.
Theur p ose of the analysis is to determine acceptability of the tower stres . ased on our analysis we
P P
have determined the tower stress level for the structure and foundation, un ollowing load case, to be:
LC7: Existing + Reserved + Proposed Equipment c'/ Sufficient Capacity
Note:See Table I and Table II for the proposed and existing/reserved loadi ,y, �Tively.
This analysis has been performed in accordance with the 201 orida Building Code, 5th Edition, based upon
an ultimate 3-second gust wind speed of 129 mph converted to a nominal 3-second gust wind speed of 100 mph
per section 1609.3.1 as required for use in the TIA-222-G Standard per Exception#5 of Section 1609.1.1.
Exposure Category C with a topographic category 1 and crest height of 0 feet, and Risk Category II were used
in this analysis. .
,a`',`,�S i i i i i li/l,;.
We at Paul J Ford and Company appreciate the opportunity of providing our continl.ti(►g.�(�e�a9��s to
you and Crown Castle. If you have any questions or need further assistance on tgZs�oliypil8�ais .•F�i��
please give us a call. 7'
27 is No. 79560 ---
Respectfully submitted by: _
yer4.4.... 60.44.„," — : * : —
` II . iX
STATE OF �
Jared Smith, E.I.
Structural Designer ///S ,t
,, t v.,\\•
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 2
TABLE OF CONTENTS
1) INTRODUCTION
2)ANALYSIS CRITERIA
Table 1 - Proposed Antenna and Cable Information
Table 2- Existing and Reserved Antenna and Cable Information
3)ANALYSIS PROCEDURE
Table 3- Documents Provided
3.1)Analysis Method
3.2)Assumptions
4)ANALYSIS RESULTS
Table 4-Section Capacity(Summary)
Table 5—Tower Components vs. Capacity
Table 6- Microwave Dish Tilt(Sway) Results for 60 mph Rev G Service Wind
5)APPENDIX A
tnxTower Output
6)APPENDIX B
Base Level Drawing
7)APPENDIX C
Additional Calculations
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 3
1) INTRODUCTION
This tower is a 190 ft Self Support tower designed by Rohn in November of 1990.The tower was originally
designed for a wind speed of 100 mph per EIA-222-D. The tower was reinforced by modifications designed by
PJF in July of 2011.
2)ANALYSIS CRITERIA
This analysis has been performed in accordance with the 2014 Florida Building Code, 5th Edition, based upon
an ultimate 3-second gust wind speed of 129 mph converted to a nominal 3-second gust wind speed of 100 mph
per section 1609.3.1 as required for use in the TIA-222-G Standard per Exception#5 of Section 1609.1.1.
Exposure Category C with a topographic category 1 and crest height of 0 feet, and Risk Category II were used
in this analysis.
Table 1 -Proposed Antenna and Cable Information
Center Number Number Feed
Mounting Lineof Antenna Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size(in)
(ft)
3 tower mounts Connect-it PVFM-12-3-4-
96
r 3 ericsson 1 RRUS 31 1325
RRUS 82 W/SOLAR
178.0 178.0 3 ericsson 1 ; 7/8
SHIELD
6 j ericsson RRUS-11800MHz 3 1-3/16
3
kmw ETCR-654L12H6 w/
communications Mount Pipe
3 nokia RADAR FILTER
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 4
Table 2- Existing and Reserved Antenna and Cable Information
Center Number Number Feed
Mounting Line Antenna
of Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size(in)
(ft)
3 andrew DBXNH-6565B-R2M w/
Mount Pipe
6 I andrew ! E15S09P78
6 andrew i SBNHH-1 D65B w/Mount
Pipe
3 commscope SBJAH4-1 D65B-DL w/
Mount Pipe
2 I commscope WCS-IMFQ-AMT-43 3 5/16
187.0 190.0 I 3 ericsson RRUS 12 3 3/8 1
3 ericsson I RRUS 32 B2 5 3/4
3 ericsson RRUS 32 B30 12 I 1-5/8
3 ericsson I RRUS 32 B66
r 3 ericsson RRUS-11
6 raycap DC2-48-60-0-9E
r 1 1 raycap DC6-48-60-18-8C
2 raycap DC6-48-60-18-8F
187.0 1 tower mounts Sector Mount[SM 502-3]
184.0 j 1 I andrew # VHLP2-11
183.0 I 2 andrew VHLP2-18 3 1/2 1
I 3 dragonwave Horizon DUO
• samsung
3 E nRRHv2
178.0 telecommunications
178.0 3 argus technologies LLPX310R-V4 w/Mount 3 { 5/16 3
Pipe 3 9077
1 terrawave i JUNCTION BOX
1 tower mounts Sector Mount[SM 401-3]
I 3 I andrew I ETW200VS12UB I
6 andrew TMBXX-6517-R2M w/
Mount Pipe 3 1-1/4
3 nokia FRIG 3 i 1-3/5 1
130.0 130.0 -- — ---
3 nokia FXFB 1 7 1-5/8
3 raycap RNSDC-7771-PF-48
1tower mounts Sector Mount[SM 104-3]
1 3 I nokia FASB w/Mount Pipe l - - I 2
Notes:
1) Existing Equipment
2) Reserved Equipment
3) Equipment To Be Removed
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 5
3)ANALYSIS PROCEDURE
Table 3- Documents Provided
Document Remarks Reference Source
GEOTECHNICAL REPORTS j ATEC,,#72-01065, 12/3/1990 I 111139 I CCISITES
r TOWER FOUNDATION 1 I
- 816089 CCISITES
DRAWINGS/DESIGN/SPECS
TOWER MANUFACTURER I I
DRAWINGS Rohn, #25703JC, 11/30/1990 225932 I CCISITES
POST-MODIFICATION TEP,#113297, 1/12/2012 3062154 j CCISITES
INSPECTION
TOWER REINFORCEMENT I
DESIGN/DRAWINGS/DATA PJF, #37511-1230, 7/5/2011 3009343 1 CCISITES
3.1) Analysis Method
tnxTower(version 7.0.5.1), a commercially available analysis software package,was used to create a
three-dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.
3.2) Assumptions
1) Tower and structures were built in accordance with the manufacturer's specifications.
2) The tower and structures have been maintained in accordance with the manufacturer's
specification.
3) The configuration of antennas,transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings.
This analysis may be affected if any assumptions are not valid or have been made in error. Paul J
Ford and Company should be notified to determine the effect on the structural integrity of the tower.
4)ANALYSIS RESULTS
Table 4-Section Capacity(Summary)
Section Elevation(ft) Component Type Size Critical P(K) SF*P allow % Pass/Fail
No. Element (K) Capacity
T1 190-180 i Leg Pipe 2.875"S).276 (2.5 f 2 -5.70 74.51 7.6 I Pass
T2 180-160 I Leg I Pipe 3.5"x 0.300"(3 XS) i 29 I -36.44 94.46 38.6 Pass
Ii
T3 160-140 Leg 1 Pipe 4.5"x 0.337"(4 XS) ; 68 I -71.25 159.90 44.6 E Pass
IPipe 5.563"x 0.375"(5 I i
T4 140-120 Leg XS) 107 ( -103.39 i 239.38 43.2 I Pass
Pipe 6.625"x 0.340"(6 }
T5 I 120-100 Leg EHS 146 I -133.70 244.02 54.8 I Pass
r ______...__ -I-
T6 { 100-80 Leg Pipe 6.62XS 0.432"(6 I 173 I. -166.20 303.62 54.7 Pass
I { ; Pipe 6.625"x 0.432"(6
T7 80-60 Leg XS 200 I -195.60 303.58 64.4 Pass
Pipe 8.625")s7.375"(8
T8 60-40 Leg � EH227 1 -224.12 386.31 58.0 Pass
1Pipe 8.625"x 0.375"(8
T9 40-20 Leg € EHS) 254 -252.85 386.31 65.5 Pass
T10 t 20-0 Leg l Pipe 8.625"X 0.500"(8 281 -267.20 505.43 52.9 Pass
i
T1 190-180 Diagonal I Pipe 2.375"x 0.154"(2 J 9 i -4.67 24.15 19.4 Pass
tnxTower Report-version 7.0.5.1
.
.
August 28, 2017
190 Ft Self Support ToweStructural Analysis CC/8UNoD12565
Project Number 3751FJ033.00/.8700, Application 40z354. Revision z Page 6
Section Critical sp^p_)allow %
Elevation(ft) Component Type Size p(w> Pass/pao
No. Element (� canac/tv
'' - - ------ '--- - - - ---- STD) l
To 180'160 DiagonalDiagonal �a>p�o�o7�xo
- -- 0.218"(2 33 'o.mr 23.14 41.3 Pass__-
(2
113 160 140 Diagonal ' ~---'- --' ° 71 | -7.58 15.33 49.4 Pass
4opi u»7e^ �mr(o 1
T4 � '�uu Diagonal `-- -- 1� -10.27 m.n ruo Pass
r- -- ----
Ta �oo_�oo Diagonal | p/P»o�o7�»o�oo (2.5 � 153 _�o�� 16.50 74.8 | Pass
|
STD)
_ |
T6 100'80 Diagonal u.5"xum6"(3 STD) ' 180 -11J3 28.50 41.2 Pass
17 ao'sm Diagonal 1Pipe x.5^xuu1sr(3STD) 207 -11.66 24.78 47.0 Pass
T8 60'40 Diagonal 'Pipe n.5"xum6"(3STD)I 234 -12.75 22.07 57.8 Pass
T9 | *n'om Diagonal Pipe o.5"xn.21or(3STD)/ 261 -13.21 | 19.40 68.1 Pass
T10 20-0 Diagonal w/ .300" 294 -19.5033.7057.9PassH�o�� _
Pipe '- ---- `' - 10 -3.24 22.58 14.3 PassT1 __ 180 Horizontal STD)
pipo1/rxu1w5"Ua 31 -5.14 ous 22.8 Pass-
STD)
--��_''
p�*�arxn�m��.o | 70 -4.71 19.14 24.6 Pass T3 STD)
T4 Pipe 2.375 -- (2 I 112 -7.07 | 27.21 26.0 Pass
"'"/ ' -__ __ |
. ,_--- --- (2 1m | -7.39'~ STD) 22.64 32.6 Pass
Pimo�r�no�a��T6 100-80 Horizontal 178 ' �
Pipe -7.64 16.86 45.3 Pass
u�o7�xoono (2.5 | -8.11
.. 60 Horizontal205 STD)
| / 28.6428.3 Pass
Pipe%�or�xo�uo» (2.518 60-40 Horizontal232 i eo1 22.38 41.6 Pass
_
Pipe 2.n7s xo.2o�� 259�s | | '1001 1782 oez Pass
'" STD)
� |
'n Horizontal �pvo�urs «»� m��e
' 67.1 Pass
--^---�--- GTn} �-� _
�
T1 190'180 | Top Girt �pn1�*^»»��mr(1�a s ! -0.91 22.63 *o � Pass
STD) �
lno oo_u nw«u»uH»�1 Pipe 1er^u1w��� 292 -4.64 12.8e 36.0 Pass
Bracing STD)
T10 ou_o n»uunm Diag 1 Pipe 2.375 :u15r(2 289 -4.24 9.00 *71 Pass
Bracing STD)
�
� m�uunumn� Pipe
r10 uo_o Ua
297 -0.05 11.86 0.4 Pass
| | _ Bracing STD)
__ |
nnuuno Hip
T1n uo'o
Pipe «»2»» (2.5ueu -0.06 10.56 0.5 Pass--"-- � STD) |
Bracing
T1 1�'1� Inner Bracing L2x2x1/8 25 -0.02 6.56 0.2 Pass
Tu ' 180'160 Inner Bracing L2x2x1/8 sa I *01 6.48 0.1 Pass
To 160'*40 Inner Bracing L2x2x1/8 81 1. -0.01 *.79 0.1 Pass
T4 140'120 Inner Bracing L2x2x1/8 120 | -0.01 3.28 0.3 | Pass
T* 120'100 Inner Bracing L2x2x1/8 15e 1 -0.01 2.48 0.3 Pass
-
Ta 100'80- Inner Bracing u21x2x21mx3/16 -- 186 | *.01 5.23 0.2 Pass
Tr ! oo'no Inner Bracing u3x3x3/16 | 212 -0.01 6.83 0.2 Pass |
T8 oo'*o
--- nn,an« L31mxn1mx1w----- uwo -`--.01 11.13 0.2 Pass
- m -
To 40'20 Inner u31 o1mx 267 01 8.92 0.2 Pass
--7lno 20'o Inner Bracing Pipe 2.375xu15r(2 310 -0.01 / e.5e 0.2 Pass
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 7
Section Elevation(ft) Component Type Size Critical P(K) SF'P_allow % Pass/Fail
No. Element (K) Capacity
i STD)
Summary I
Leg(T9) 65.5 I Pass
Diagonal i 78.0 1 Pass
T4
----- t€ Horizontal
i (T10) 67.1 Pass
f j
i-
Top Girt 4.0 Pass
Redund
1 ? Horz 1 36.0 Pass
Bracing
(T10)
I Redund
I j Diag 1 47.1 Pass
Bracing
(T10)
Redund Hip
1 Bracing 0.4 I Pass
I (T10)
A
Redund Hip
Diagonal 1 0.5 Pass
Bracing
6°C11° (T10)
6 \(
Inner
Bracing 0.3 I Pass
j t 1 E . (T5)
I :Bolt Checks 52.8 Pass
I i Rating= 78.0 —1 Pass
Table 5-Tower Component Stresses vs. Capacity—LC77
Notes Component Elevation (ft) %Capacity Pass/Fail
1 Anchor Rods 0 1 52.3 Pass
1 Base Foundation 0 30.0 I Pass
Structural !
1 Base Foundation 0 42.0 Pass
Soil Interaction
Structure Rating (max from all components)= 78.0%
-
Notes:
1) See additional documentation in"Appendix C—Additional Calculations"for calculations supporting the%capacity
consumed.
Table 6- Microwave Dish Tilt(Sway) Results for 60 mph Rev G Service
Dish Dish Analysis Results Tilt Analysis Results
Elevation Dish Diameter Dish Frequency at Service Wind Twist(Sway) at
ft ft GHz deg Service Wind
deg
184.0 VHLP2-11 j 2.175 - 0.1481 0.0279
•
•
183.0 VHLP2-18 j 2.175 I - 0.1479 j 0.0278
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Seff Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 8
APPENDIX A
TNXTOWER OUTPUT
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 9
Tower Input Data
The main tower is a 3x free standing tower with an overall height of 190.00 ft above the ground line.
The base of the tower is set at an elevation of 0.00 ft above the ground line.
The face width of the tower is 8.50 ft at the top and 27.68 ft at the base.
This tower is designed using the TIA-222-G standard.
The following design criteria apply:
1) Tower is located in Duval County, Florida.
2) ASCE 7-10 Wind Data is used (wind speeds converted to nominal values).
3) Basic wind speed of 100 mph.
4) Structure Class II.
5) Exposure Category C.
6) Topographic Category 1.
7) Crest Height 0.00 ft.
8) Deflections calculated using a wind speed of 60 mph.
9) A non-linear(P-delta)analysis was used.
10) Pressures are calculated at each section.
11) Stress ratio used in tower member design is 1.
12) Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are
not considered.
Options
Consider Moments-Legs Distribute Leg Loads As Uniform Use ASCE 10 X-Brace Ly Rules
Consider Moments-Horizontals Assume Legs Pinned 4 Calculate Redundant Bracing Forces
Consider Moments-Diagonals Assume Rigid Index Plate Ignore Redundant Members in FEA
Use Moment Magnification 4 Use Clear Spans For Wind Area SR Leg Bolts Resist Compression
4 Use Code Stress Ratios -4 Use Clear Spans For KUr All Leg Panels Have Same Allowable
4 Use Code Safety Factors-Guys Retension Guys To Initial Tension Offset Girt At Foundation
Escalate Ice Bypass Mast Stability Checks 4 Consider Feed Line Torque
Always Use Max Kz 4 Use Azimuth Dish Coefficients ' Include Angle Block Shear Check
Use Special Wind Profile 4 Project Wind Area of Appurt. Use TIA-222-G Bracing Resist.
Exemption
Include Bolts In Member Capacity Autocalc Torque Arm Areas Use TIA-222-G Tension Splice
Exemption
Leg Bolts Are At Top Of Section Add IBC.6D+W Combination Poles
4 Secondary Horizontal Braces Leg 4 Sort Capacity Reports By Component Include Shear-Torsion Interaction
Use Diamond Inner Bracing(4 Sided) Triangulate Diamond Inner Bracing Always Use Sub-Critical Flow
SR Members Have Cut Ends Treat Feed Line Bundles As Cylinder Use Top Mounted Sockets
SR Members Are Concentric
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 10
Wind 180
'Jr
legA
Wind 90
0.
d
Leg C Leg B
Face C
Wind Normal
Triangular Tower
Tower Section Geometry
Tower Tower Assembly Description Section Number Section
Section Elevation Database Width of Length
Sections
•• ft ft ft
T1 190.00-180.00 8.50 1 10.00
T2 180.00-160.00 8.54 1 20.00
T3 160.00-140.00 8.63 1 20.00
T4 140.00-120.00 10.71 1 20.00
T5 120.00-100.00 12.79 1 20.00
T6 100.00-80.00 15.04 1 20.00
T7 80.00-60.00 17.54 1 20.00
T8 60.00-40.00 20.18 1 20.00
T9 40.00-20.00 22.68 1 20.00
T10 20.00-0.00 25.18 1 20.00
Tower Section Geometry (cont'd)
Tower Tower Diagonal Bracing Has Has Top Girt Bottom Girt
Section Elevation Spacing Type K Brace Horizontals Offset Offset
End
ft ft Panels in in
T1 190.00-180.00 5.00 K Brace Down No Yes 0.0000 0.0000
T2 180.00-160.00 6.67 K Brace Down No Yes 0.0000 0.0000
T3 160.00-140.00 6.67 K Brace Down No Yes 0.0000 0.0000
T4 140.00-120.00 6.67 K Brace Down No Yes 0.0000 0.0000
T5 120.00-100.00 10.00 K Brace Down No Yes 0.0000 0.0000
T6 100.00-80.00 10.00 K Brace Down No Yes 0.0000 0.0000
T7 80.00-60.00 10.00 K Brace Down No Yes 0.0000 0.0000
T8 60.00-40.00 10.00 K Brace Down No Yes 0.0000 0.0000
T9 40.00-20.00 10.00 K Brace Down No Yes 0.0000 0.0000
T10 20.00-0.00 20.00 K1 Down No Yes 0.0000 0.0000
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 11
Tower Section Geometry (cont'd)
Tower Leg Leg Leg Diagonal Diagonal Diagonal
Elevation Type Size Grade Type Size Grade
ft
T1 190.00- Pipe Pipe 2.875"x 0.276"(2.5 A618-50 Pipe Pipe 2.375"x 0.154"(2 A618-50
180.00 XS) (50 ksi) STD) (50 ksi)
T2 180.00- Pipe Pipe 3.5"x 0.300"(3 XS) A618-50 Pipe Pipe 2.375"x 0.218"(2 XS) A618-50
160.00 (50 ksi) (50 ksi)
T3 160.00- Pipe Pipe 4.5"x 0.337"(4 XS) A618-50 Pipe Pipe 2.375"x 0.154"(2 A618-50
140.00 (50 ksi) STD) (50 ksi)
T4 140.00- Pipe Pipe 5.563"x 0.375"(5 XS) A618-50 Pipe Pipe 2.375"x 0.154"(2 A618-50
120.00 (50 ksi) STD) (50 ksi)
T5 120.00- Pipe Pipe 6.625"x 0.340"(6 A618-50 Pipe Pipe 2.875"x 0.203"(2.5 A618-50
100.00 EHS) (50 ksi) STD) (50 ksi)
T6 100.00- Pipe Pipe 6.625"x 0.432"(6 XS) A618-50 Pipe Pipe 3.5"x 0.216"(3 STD) A618-50
80.00 (50 ksi) (50 ksi)
T7 80.00-60.00 Pipe Pipe 6.625"x 0.432"(6 XS) A618-50 Pipe Pipe 3.5"x 0.216"(3 STD) A618-50
(50 ksi) (50 ksi)
T8 60.00-40.00 Pipe Pipe 8.625"x 0.375"(8 A618-50 Pipe Pipe 3.5"x 0.216"(3 STD) A618-50
EHS) (50 ksi) (50 ksi)
T9 40.00-20.00 Pipe Pipe 8.625"x 0.375"(8 A618-50 Pipe Pipe 3.5"x 0.216"(3 STD) A618-50
EHS) (50 ksi) (50 ksi)
T10 20.00-0.00 Pipe Pipe 8.625"x 0.500"(8 XS) A618-50 Arbitrary (37515-2715)2.875"x.276" A500-46
(50 ksi) Shape Pipe w/3.5"x.300"Half (46 ksi)
Sleeve
Tower Section Geometry (cont'd)
Tower No. Mid Girt Mid Girt Mid Girt Horizontal Horizontal Horizontal
Elevation of Type Size Grade Type Size Grade
Mid.
ft Girts
T1 190.00- None Flat Bar A36 Pipe Pipe 1.9"x 0.145" A618-50
180.00 (36 ksi) (1.5 STD) (50 ksi)
T2 180.00- None Flat Bar A36 Pipe Pipe 1.9"x 0.145" A618-50
160.00 (36 ksi) (1.5 STD) (50 ksi)
T3 160.00- None Flat Bar A36 Pipe Pipe 1.9"x 0.145" A618-50
140.00 (36 ksi) (1.5 STD) (50 ksi)
T4 140.00- None Flat Bar A36 Pipe Pipe 2.375"x 0.154" A618-50
120.00 (36 ksi) (2 STD) (50 ksi)
T5 120.00- None Flat Bar A36 Pipe Pipe 2.375"x 0.154" A618-50
100.00 (36 ksi) (2 STD) (50 ksi)
T6 100.00- None Flat Bar A36 Pipe Pipe 2.375"x 0.154" A618-50
80.00 (36 ksi) (2 STD) (50 ksi)
T7 80.00-60.00 None Flat Bar A36 Pipe Pipe 2.875"x 0.203" A618-50
(36 ksi) (2.5 STD) (50 ksi)
T8 60.0040.00 None Flat Bar A36 Pipe Pipe 2.875"x 0.203" A618-50
(36 ksi) (2.5 STD) (50 ksi)
T9 40.00-20.00 None Flat Bar A36 Pipe Pipe 2.875"x 0.203" A618-50
(36 ksi) (2.5 STD) (50 ksi)
T10 20.00-0.00 None Flat Bar A36 Pipe Pipe 2.875"x 0.203" A618-50
(36 ksi) (2.5 STD) (50 ksi)
Tower Section Geometry (cont'd)
Tower Secondary Secondary Horizontal Secondary Inner Bracing Inner Bracing Size Inner Bracing
Elevation Horizontal Type Size Horizontal Type Grade
Grade
ft
T1 190.00- Solid Round A572-50 Equal Angle L2x2x1/8 A36
180.00 (50 ksi) (36 ksi)
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CC/BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 12
Tower Secondary Secondary Horizontal Secondary Inner Bracing Inner Bracing Size Inner Bracing
Elevation Horizontal Type Size Horizontal Type Grade
.. Grade
ft
T2 180.00- Solid Round A572-50 Equal Angle L2x2x1/8 A36
160.00 (50 ksi) (36 ksi)
T3 160.00- Solid Round A572-50 Equal Angle L2x2x1/8 A36
140.00 (50 ksi) (36 ksi)
T4 140.00- Solid Round A572-50 Equal Angle L2x2x1/8 A36
120.00 (50 ksi) (36 ksi)
T5 120.00- Solid Round A572-50 Equal Angle L2x2x1/8 A36
100.00 (50 ksi) (36 ksi)
T6 100.00- Solid Round A572-50 Equal Angle L2 1/2x2 1/2x3/16 A36
80.00 (50 ksi) (36 ksi)
17 80.00-60.00 Solid Round A572-50 Equal Angle L3x3x3/16 A572-50
(50 ksi) (50 ksi)
T8 60.00-40.00 Solid Round A572-50 Equal Angle L3 1/2x3 1/2x1/4 A572-50
(50 ksi) (50 ksi)
T9 40.00-20.00 Solid Round A572-50 Equal Angle L3 1/2x3 1/2x1/4 A572-50
(50 ksi) (50 ksi)
T10 20.00-0.00 Solid Round A572-50 Pipe Pipe 2.375"x 0.154"(2 A618-50
(50 ksi) STD) (50 ksi)
Tower Section Geometry (cont'd)
Tower Redundant Redundant Redundant K Factor
Elevation Bracing Type Size
Grade
ft
T10 20.00- A53-B-35 Horizontal(1) Pipe Pipe 1.9"x 0.145"(1.5 1
0.00 (35 ksi) Diagonal(1) Pipe STD) 1
Hip(1) Pipe Pipe 2.375"x 0.154"(2 1
Hip Diagonal Pipe STD) 1
(1) Pipe 1.9"x0.145"(1.5
STD)
Pipe 2.875"x 0.203"(2.5
STD)
Tower Section Geometry (cont'd)
Tower Gusset Gusset Gusset GradeAdjust.Factor Adjust. Weight Mult. Double Angle Double Angle Double Angle
Elevation Area Thickness A, Factor Stitch Bolt Stitch Bolt Stitch Bolt
(per face) A Spacing Spacing Spacing
Diagonals Horizontals Redundants
ft ft2 in in in in
T1 190.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
180.00 (36 ksi)
T2 180.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
160.00 (36 ksi)
T3 160.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
140.00 (36 ksi)
T4 140.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
120.00 (36 ksi)
T5 120.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
100.00 (36 ksi)
T6 100.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
80.00 (36 ksi)
T7 80.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
60.00 (36 ksi)
T8 60.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
40.00 (36 ksi)
T9 40.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
20.00 (36 ksi)
T10 20.00- 0.00 0.3750 A36 1 1 1.1 0.0000 0.0000 36.0000
0.00 (36 ksi)
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 13
Tower Section Geometry (cont'd)
K Factors'
Tower Calc Calc Legs X K Single Girls Horiz. Sec. Inner
Elevation K K Brace Brace Diags Horiz. Brace
Single Solid Diags Diags
Angles Rounds X X X X X X X
ft Y Y Y Y Y Y Y
T1 190.00- Yes No 1 1 1 1 1 1 1 1
180.00 1 1 1 1 1 1 1
T2 180.00- Yes No 1 1 1 1 1 1 1 1
160.00 1 1 1 1 1 1 1
T3160.00- Yes No 1 1 1 1 1 1 1 1
140.00 1 1 1 1 1 1 1
T4 140.00- Yes No 1 1 1 1 1 1 1 1
120.00 1 1 1 1 1 1 1
T5 120.00- Yes No 1 1 1 1 1 1 1 1
100.00 1 1 1 1 1 1 1
T6 100.00- Yes No 1 1 1 1 1 1 1 1
80.00 1 1 1 1 1 1 1
T7 80.00- Yes No 1 1 1 1 1 1 1 1
60.00 1 1 1 1 1 1 1
T8 60.00- Yes No 1 1 1 1 1 1 1 1
40.00 1 1 1 1 1 1 1
T9 40.00- Yes No 1 1 1 1 1 1 1 1
20.00 1 1 1 1 1 1 1
T10 20.00- Yes No 1 1 1 1 1 1 1 1
0.00 1 1 1 1 1 1 1
'Note:K factors are applied to member segment lengths.K-braces without inner supporting members will have the K factor in the out-of-
plane direction applied to the overall length.
Tower Section Geometry fcont'd)
Tower . Leg Diagonal Top Girt Bottom Girt i Mid Girt i Long Horizontal 1 Short Horizontal
Elevation
ft i I
Net Width U Net U Net Width U Net U Net U Net U Net U
Deduct Width Deduct Width Width I Width Width
in Deduct in Deduct Deduct Deduct Deduct
in in in in in
T1 190.00- 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
180.00 I
T2 180.00- 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
160.00
T3 160.00- 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
140.00
T4 140.00- j 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
120.00
T5 120.00- 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 1 0.0000 0.75
100.00
T6 100.00- 0.0000 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
80.00
T7 80.00- 0.0000 1 0.0000 0.75 0.0000 0.75 ; 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
60.00
T8 60.00- 0.0000 1 0.0000 0.75 0.0000 0.75 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
40.00
T9 40.00- 0.0000 1 0.0000 0.75 0.0000 0.75 1 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
20.00
T10 20.00- 0.0000 1 0.0000 0.75 0.0000 0.75 � 0.0000 0.75 0.0000 0.75 0.0000 0.75 0.0000 0.75
0.00
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 14
Tower Section Geometry (cont'd)
Tower Leg Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short
Elevation Connection Horizontal
ft Type
Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No. Bolt Size No.
in in in in in in in
T1 190.00- Flange 0.8750 4 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
180.00 A325N A325N A325N A325N A325N A325N A325N
T2 180.00- Flange 0.8750 4 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
160.00 A325N A325N A325N A325N A325N A325N A325N
T3 160.00- Flange 1.0000 4 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
140.00 A325N A325N A325N A325N A325N A325N A325N
T4 140.00- Flange 1.0000 6 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
120.00 A325N A325N A325N A325N A325N A325N A325N
T5 120.00- Flange 1.0000 6 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
100.00 A325N A325N A325N A325N A325N A325N A325N
T6 100.00- Flange 1.0000 6 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
80.00 A325N A325N A325N A325N A325N A325N A325N
T7 80.00- Flange 1.0000 8 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
60.00 A325N A325N A325N A325N A325N A325N A325N
T8 60.00- Flange 1.0000 8 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
40.00 A325N A325N A325N A325N A325N A325N A325N
T9 40.00- Flange 1.0000 8 0.6250 3 0.0000 0 0.0000 0 0.6250 0 0.6250 2 0.6250 0
20.00 A325N A325N A325N A325N A325N A325N A325N
T10 20.00- Flange 1.0000 10 0.7500 3 0.0000 0 0.0000 0 0.6250 0 0.7500 2 0.6250 0
0.00 A354-BC A325N A325N A325N A325N A325N A325N
Feed Line/Linear Appurtenances - Entered As Round Or Flat
Description Face Allow Component Placement Face Lateral # # Clear Width or Perimete Weight
or Shield Type Offset Offset Per Spacing Diameter r
Leg ft in (Frac FW) Row in in plf
in
**Face C**
LDF4- C No Ar(CaAa) 178.00-0.00 -2.0000 -0.47 3 2 0.5200 0.6300 0.15
50A(1/2") 0.5000
TSZ 999 C No Ar(CaAa) 178.00-0.00 -2.0000 -0.46 3 .3 1.1900 1.1900 1.07
067/xxxM-
8AWG(1-
3/16)
FIBER ONLY C No Ar(CaAa) 178.00-0.00 -2.0000 -0.45 1 1 0.8670 0.8670 0.25
CABLE
48(7/8)
2.5"Conduit C No Ar(CaAa) 178.00-0.00 -2.0000 -0.48 1 1 2.8730 2.8730 5.53
1.5"flat C No Af(CaAa) 178.00-0.00 -2.0000 -0.45 2 2 12.0000 1.5000 1.80
Cable Ladder 1.5000
Rail
**Face A**
LDF7-50A(1- A No Ar(CaAa) 130.00-0.00 0.0000 0.4 10 7 0.5200 1.9800 0.82
5/8") 0.5000
ASU9325TY A No Ar(CaAa) 130.00-0.00 0.0000 0.4 3 3 1.5840 1.5840 1.61
P01(1-3/5")
1.5"flat A No Af(CaAa) 130.00-0.00 0.0000 0.4 2 2 12.0000 1.5000 1.80
Cable Ladder 1.5000
Rail
**Face B**
HJ7-50A(1- B No Ar(CaAa) 187.00-0.00 -2.0000 0.4 12 12 0.5200 1.9800 1.04
5/8") 0.5000
ATCB- B No Ar(CaAa) 187.00-0.00 -2.0000 0.4 3 3 2.1900 0.3150 0.07
B01(5/16) 0.5000
WR- B No Ar(CaAa) 187.00-0.00 -2.0000 0.4 5 5 0.7740 0.7740 0.59
VG86ST-
BRD(3/4)
LDF2-50 B No Ar(CaAa) 187.00-0.00 -2.0000 0.4 3 3 0.4400 0.4400 0.08
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 15
Description Face Allow Component Placement Face Lateral # # Clear Width or Perimete Weight
or Shield Type Offset Offset Per Spacing Diameter r
Leg ft in (Frac FW) Row in in plf
in
(3/8"foam)
1.5"flat B No Af(CaAa) 187.00-0.00 -2.0000 0.4 2 2 12.0000 1.5000 1.80
Cable Ladder 1.5000
Rail -
Safety Line C No Ar(CaAa) 190.00-0.00 0.0000 -0.5 1 1 0.3750 0.3750 0.22
3/8
Feed Line/Linear Appurtenances - Entered As Area
Description Face Allow Component Placement Total CAAA Weight
or Shield Type Number
Leg ft ft2/ft plf
Feed Line/Linear Appurtenances Section Areas
Tower Tower Face AR AF CAAA CAAA Weight
Sectio Elevation In Face Out Face
n ft ft2 ft2 ft2 ft2 K
T1 190.00-180.00 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 24.427 0.000 0.14
C 0.000 0.000 0.375 0.000 0.00
T2 180.00-160.00 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 26.310 0.000 0.24
T3 160.00-140.00 A 0.000 0.000 0.000 0.000 0.00
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T4 140.00-120.00 A 0.000 0.000 29.552 0.000 0.17
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T5 120.00-100.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T6 100.00-80.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T7 80.00-60.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T8 60.00-40.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T9 40.00-20.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
T10 20.00-0.00 A 0.000 0.000 59.104 0.000 0.33
B 0.000 0.000 69.790 0.000 0.39
C 0.000 0.000 29.150 0.000 0.27
Feed Line Center of Pressure
Section Elevation CPX CPZ CPX CPz
Ice Ice
ft in in in in
T1 190.00-180.00 6.7096 3.4099 7.3403 3.7285
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 16
Section Elevation CPX CPz CPX CPz
Ice Ice
.. ft in in in in
T2 180.00-160.00 8.4988 4.4601 9.6236 5.0702
T3 160.00-140.00 9.3253 4.8799 10.5851 5.5658
T4 140.00-120.00 8.5320 1.4999 9.6950 1.8039
T5 120.00-100.00 8.1685 -1.3483 9.2908 -1.3624
T6 100.00-80.00 9.3716 -1.5323 10.6561 -1.5461
T7 80.00-60.00 10.6741 -1.7322 12.1343 -1.7457
T8 60.00-40.00 11.5764 -1.8679 13.1577 -1.8807
T9 40.00-20.00 12.7994 -2.0562 14.5458 -2.0689
T10 20.00-0.00 14.0383 -2.2472 15.9520 -2.2598
Discrete Tower Loads
Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight
or Type Horz Adjustmen Front Side
Leg Lateral t
Vert
ft ft ft2 ft2 K
ft °
ft
Flash Beacon Lighting C None 0.0000 190.00 No Ice 2.70 2.70 0.05
DBXNH-6565B-R2M w/ A From Leg 4.00 0.0000 187.00 No Ice 8.51 7.16 0.08
Mount Pipe 0.00
3.00
(2)E15S09P78 A From Leg 4.00 0.0000 187.00 No Ice 0.75 0.34 0.02
0.00
3.00
(2)SBNHH-1D65B w/ A From Leg 4.00 0.0000 187.00 No Ice 8.42 7.42 0.08
Mount Pipe 0.00
3.00
SBJAH4-1 D65B-DL w/ A From Leg 4.00 0.0000 187.00 No Ice 9.47 7.74 0.08
Mount Pipe 0.00
3.00
WCS-IMFQ-AMT-43 A From Leg 4.00 0.0000 187.00 No Ice 0.55 0.39 0.02
0.00
3.00
RRUS 12 A From Leg 4.00 0.0000 187.00 No Ice 3.15 1.29 0.06
0.00
3.00
RRUS 32 B2 A From Leg 4.00 0.0000 187.00 No Ice 2.73 1.67 0.05
0.00
3.00
RRUS 32 B30 A From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS 32 B66 A From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS-11 A From Leg 4.00 0.0000 187.00 No Ice 2.79 1.19 0.05
0.00
3.00
(2)DC2-48-60-0-9E A From Leg 4.00 0.0000 187.00 No Ice 0.93 0.56 0.02
0.00
3.00
DC6-48-60-18-8F A From Leg 4.00 0.0000 187.00 No Ice 0.92 0.92 0.02
0.00
3.00
DBXNH-6565B-R2M w/ B From Leg 4.00 0.0000 187.00 No Ice 8.51 7.16 0.08
Mount Pipe 0.00
3.00
(2)E15S09P78 B From Leg 4.00 0.0000 187.00 No Ice 0.75 0.34 0.02
0.00
3.00
(2)SBNHH-1D65B w/ B From Leg 4.00 0.0000 187.00 No Ice 8.42 7.42 0.08
Mount Pipe 0.00
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 17
Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight
or Type Horz Adjustmen Front Side
Leg Lateral t
Vert
ft ft ft2 ft2 K
ft °
ft
3.00
SBJAH4-1 D65B-DL w/ B From Leg 4.00 0.0000 187.00 No Ice 9.47 7.74 0.08
Mount Pipe 0.00
3.00
WCS-IMFQ-AMT-43 B From Leg 4.00 0.0000 187.00 No Ice 0.55 0.39 0.02
0.00
3.00
RRUS 12 B From Leg 4.00 0.0000 187.00 No Ice 3.15 1.29 0.06
0.00
3.00
RRUS 32 B2 B From Leg 4.00 0.0000 187.00 No Ice 2.73 1.67 0.05
0.00
3.00
RRUS 32 B30 B From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS 32 B66 B From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS-11 B From Leg 4.00 0.0000 187.00 No Ice 2.79 1.19 0.05
0.00
3.00
(2)DC2-48-60-0-9E B From Leg 4.00 0.0000 187.00 No Ice 0.93 0.56 0.02
0.00
3.00
DC6-48-60-18-8C B From Leg 4.00 0.0000 187.00 No Ice 2.74 2.74 0.03
0.00
3.00
DBXNH-6565B-R2M w/ C From Leg 4.00 0.0000 187.00 No Ice 8.51 7.16 0.08
Mount Pipe 0.00
3.00
(2)E15S09P78 C From Leg 4.00 0.0000 187.00 No Ice 0.75 0.34 0.02
0.00
3.00
(2)SBNHH-1D65B w/ C From Leg 4.00 0.0000 187.00 No Ice 8.42 7.42 0.08
Mount Pipe 0.00
3.00
SBJAH4-1 D65B-DL w/ C From Leg 4.00 0.0000 187.00 No Ice 9.47 7.74 0.08
Mount Pipe 0.00
3.00
RRUS 12 C From Leg 4.00 0.0000 187.00 No Ice 3.15 1.29 0.06
0.00
3.00
RRUS 32 B2 C From Leg 4.00 0.0000 187.00 No Ice 2.73 1.67 0.05
0.00
3.00
RRUS 32 B30 C From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS 32 B66 C From Leg 4.00 0.0000 187.00 No Ice 2.74 1.67 0.05
0.00
3.00
RRUS-11 C From Leg 4.00 0.0000 187.00 No Ice 2.79 1.19 0.05
0.00
3.00
(2)DC2-48-60-0-9E C From Leg 4.00 0.0000 187.00 No Ice 0.93 0.56 0.02
0.00
3.00
DC6-48-60-18-8F C From Leg 4.00 0.0000 187.00 No Ice 0.92 0.92 0.02
0.00
3.00
Sector Mount[SM 502-3] C None 0.0000 187.00 No Ice 33.02 33.02 1.67
Horizon DUO A From Leg 4.00 0.0000 178.00 No Ice 0.47 0.29 0.01
0.00
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 18
Description Face Offset Offsets: Azimuth Placement CAA, CAAA Weight
or Type Horz Adjustmen Front Side
Leg Lateral
Vert
ft ft ft2 ft2 K
ft
ft
0.00
RRUS 31 B25 A From Leg 4.00 0.0000 178.00 No Ice 1.62 1.28 0.06
0.00
0.00
RRUS 82 W/SOLAR A From Leg 4.00 0.0000 178.00 No Ice 2.98 1.43 0.06
SHIELD 0.00
0.00
(2)RRUS-11 800MHz A From Leg 4.00 0.0000 178.00 No Ice 2.52 1.30 0.05
0.00
0.00
ETCR-654L12H6 w/Mount A From Leg 4.00 0.0000 178.00 No Ice 13.27 6.54 0.10
Pipe 0.00
0.00
RADAR FILTER A From Leg 4.00 0.0000 178.00 No Ice 1.07 0.27 0.02
0.00
0.00
Horizon DUO B From Leg 4.00 0.0000 178.00 No Ice 0.47 0.29 0.01
0.00
0.00
RRUS 31 B25 B From Leg 4.00 0.0000 178.00 No Ice 1.62 1.28 0.06
0.00
0.00
RRUS 82 W/SOLAR B From Leg 4.00 0.0000 178.00 No Ice 2.98 1.43 0.06
SHIELD 0.00
0.00
(2)RRUS-11 800MHz B From Leg 4.00 0.0000 178.00 No Ice 2.52 1.30 0.05
0.00
0.00
ETCR-654L12H6 w/Mount B From Leg 4.00 0.0000 178.00 No Ice 13.27 6.54 0.10
Pipe 0.00
0.00
RADAR FILTER B From Leg 4.00 0.0000 178.00 No Ice 1.07 0.27 0.02
0.00
0.00
Horizon DUO C From Leg 4.00 0.0000 178.00 No Ice 0.47 0.29 0.01
0.00
0.00
RRUS 31 B25 C From Leg 4.00 0.0000 178.00 No Ice 1.62 1.28 0.06
0.00
0.00
RRUS 82 W/SOLAR C From Leg 4.00 0.0000 178.00 No Ice 2.98 1.43 0.06
SHIELD 0.00
0.00
(2)RRUS-11 800MHz C From Leg 4.00 0.0000 178.00 No Ice 2.52 1.30 0.05
0.00
0.00
ETCR-654L12H6 w/Mount C From Leg 4.00 0.0000 178.00 No Ice 13.27 6.54 0.10
Pipe 0.00
0.00
RADAR FILTER C From Leg 4.00 0.0000 178.00 No Ice 1.07 0.27 0.02
0.00
0.00
Connect-it PVFM-12-3-4- C None 0.0000 178.00 No Ice 33.02 33.02 1.67
96
ETW200VS12UB A From Leg 4.00 0.0000 130.00 No Ice 0.40 0.16 0.01
0.00
0.00
(2)TMBXX-6517-R2M w/ A From Leg 4.00 0.0000 130.00 No Ice 8.77 6.96 0.07
Mount Pipe 0.00
0.00
FRIG A From Leg 4.00 0.0000 130.00 No Ice 2.39 0.97 0.06
0.00
0.00
FXFB A From Leg 4.00 0.0000 130.00 No Ice 3.54 1.02 0.06
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 19
Description Face Offset Offsets: Azimuth Placement CAAA CAAA Weight
or Type Horz Adjustmen Front Side
Leg Lateral t
Vert
ft ft ft2 ft2 K
ft °
ft
0.00
0.00
RNSDC-7771-PF-48 A From Leg 4.00 0.0000 130.00 No Ice 3.18 1.20 0.02
0.00
0.00
FASB w/Mount Pipe A From Leg 4.00 0.0000 130.00 No Ice 13.90 14.69 0.24
0.00
0.00
ETW200VS12UB B From Leg 4.00 0.0000 130.00 No Ice 0.40 0.16 0.01
0.00
0.00
(2)TMBXX-6517-R2M w/ B From Leg 4.00 0.0000 130.00 No Ice 8.77 6.96 0.07
Mount Pipe 0.00
0.00
FRIG B From Leg 4.00 0.0000 130.00 No Ice 2.39 0.97 0.06
0.00
0.00
FXFB B From Leg 4.00 0.0000 130.00 No Ice 3.54 1.02 0.06
0.00
0.00
RNSDC-7771-PF-48 B From Leg 4.00 0.0000 130.00 No Ice 3.18 1.20 0.02
0.00
0.00
FASB w/Mount Pipe B From Leg 4.00 0.0000 130.00 No Ice 13.90 14.69 0.24
0.00
0.00
ETW200VS12UB C From Leg 4.00 0.0000 130.00 No Ice 0.40 0.16 0.01
0.00
0.00
(2)TMBXX-6517-R2M w/ C From Leg 4.00 0.0000 130.00 No Ice 8.77 6.96 0.07
Mount Pipe 0.00
0.00
FRIG C From Leg 4.00 0.0000 130.00 No Ice 2.39 0.97 0.06
0.00
0.00
FXFB C From Leg 4.00 0.0000 130.00 No Ice 3.54 1.02 0.06
0.00
0.00
RNSDC-7771-PF-48 C From Leg 4.00 0.0000 130.00 No Ice 3.18 1.20 0.02
0.00
0.00
FASB w/Mount Pipe C From Leg 4.00 0.0000 130.00 No Ice 13.90 14.69 0.24
0.00
0.00
6'x 2"Mount Pipe A From Leg 4.00 0.0000 130.00 No Ice 1.43 1.43 0.02
0.00
0.00
6'x 2"Mount Pipe B From Leg 4.00 0.0000 130.00 No Ice 1.43 1.43 0.02
0.00
0.00
6'x 2"Mount Pipe C From Leg 4.00 0.0000 130.00 No Ice 1.43 1.43 0.02
0.00
0.00
Sector Mount ISM 104-3) C None 0.0000 130.00 No Ice 30.02 30.02 0.95
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 20
Dishes
Description Face Dish Offset Offsets: Azimuth 3 dB Elevation Outside Aperture Weight
or Type Type Horz Adjustment Beam Diameter Area
Leg Lateral Width
Vert
ft ft ft ft2 K
VHLP2-18 A Paraboloid From 4.00 60.0000 178.00 2.17 No Ice 3.72 0.03
w/Shroud(HP) Leg 1.00
5.00
VHLP2-11 B Paraboloid From 4.00 90.0000 178.00 2.17 No Ice 3.72 0.03
w/Shroud(HP) Leg 1.00
6.00
VHLP2-18 C Paraboloid From 4.00 15.0000 178.00 2.17 No Ice 3.72 0.03
w/Shroud(HP) Leg 1.00
5.00
Maximum Tower Deflections - Service Wind
Section Elevation Horz. Gov. Tilt Twist
No. Deflection Load
ft in Comb. _ ° _
T1 190-180 3.115 29 0.1484 0.0282
T2 180-160 2.799 29 0.1474 0.0275
T3 160-140 2.181 29 0.1345 0.0242
T4 140-120 1.640 29 0.1143 0.0180
T5 120-100 1.173 29 0.0963 0.0127
T6 100-80 0.797 29 0.0769 0.0090
T7 80-60 0.500 29 0.0599 0.0064
T8 60-40 0.280 29 0.0423 0.0046
T9 40-20 0.122 29 0.0271 0.0029
T10 20-0 0.027 35 0.0118 0.0013
Critical Deflections and Radius of Curvature - Service Wind
Elevation Appurtenance Gov. Deflection Tilt Twist Radius of
Load Curvature
ft Comb. in ° ft
190.00 Flash Beacon Lighting 29 3.115 0.1484 0.0282 Inf
187.00 DBXNH-6565B-R2M w/Mount 29 3.020 0.1483 0.0280 Inf
Pipe
184.00 VHLP2-11 29 2.925 0.1481 0.0279 Int
183.00 VHLP2-18 29 2.893 0.1479 0.0278 Inf.
178.00 Horizon DUO 29 2.735 0.1467 0.0274 497135
130.00 ETW200VS12UB 29 1.396 0.1052 0.0151 58746
Maximum Tower Deflections - Design Wind
Section Elevation Horz. Gov. Tilt Twist
No. Deflection Load
ft in Comb. °
T1 190-180 13.539 8 0.6409 0.1256
T2 180-160 12.172 8 0.6367 0.1228
T3 160-140 9.500 8 0.5815 0.1078
T4 140-120 7.150 8 0.4950 0.0803
T5 120-100 5.123 8 0.4173 0.0567
T6 100-80 3.483 8 0.3334 0.0400
T7 80-60 2.192 8 0.2600 0.0288
T8 60-40 1.231 8 0.1837 0.0206
T9 40-20 0.540 4 0.1177 0.0129
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 21
Section Elevation Horz. Gov. Tilt Twist
No. Deflection Load
ft in Comb. 0
T10 20-0 0.116 20 0.0510 0.0055
Critical Deflections and Radius of Curvature - Design Wind
Elevation Appurtenance Gov. Deflection Tilt Twist Radius of
Load Curvature
ft Comb. in ft
190.00 Flash Beacon Lighting 8 13.539 0.6409 0.1256 565836
187.00 DBXNH-6565B-R2M w/Mount 8 13.129 0.6406 0.1249 565836
Pipe
184.00 VHLP2-11 8 12.719 0.6397 0.1241 478627
183.00 VHLP2-18 8 12.582 0.6392 0.1238 449905
178.00 Horizon DUO 8 11.898 0.6340 0.1219 136589
130.00 ETW200VS12UB 8 6.092 0.4558 0.0675 13636
Bolt Design Data
Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria
No. Type Grade Of Load per Load Load Ratio
ft in Bolts Bolt K Allowable
K
T1 190 Leg A325N 0.8750 4 0.64 40.59 0.016 V 1 Bolt Tension
Diagonal A325N 0.6250 3 1.56 12.43
0.125 6/ 1 Bolt Shear
Horizontal A325N 0.6250 2 1.67 12.43 0134 y/ 1 Bolt Shear
T2 180 •• Leg A325N 0.8750 4 7.50 40.59
0.185 �'// 1 Bolt Tension
Diagonal A325N 0.6250 3 3.19 12.43
0.257 V 1 Bolt Shear
Horizontal A325N 0.6250 2 2.58 12.43
0.208 V 1 Bolt Shear
T3 160 Leg A325N 1.0000 4 15.76 53.01
0.297 V 1 Bolt Tension
Diagonal A325N 0.6250 3 2.53 12.43
0.204 VV 1 Bolt Shear
Horizontal A325N 0.6250 2 2.36 12.43
0.190 1 Bolt Shear
T4 140 Leg A325N 1.0000 6 15.20 53.01
0.287 V 1 Bolt Tension
Diagonal A325N 0.6250 3 3.42 12.43
0.276 V 1 Bolt Shear
Horizontal A325N 0.6250 2 3.53 12.43
0.284 V 1 Bolt Shear
T5 120 Leg A325N 1.0000 6 19.88 53.01 0.375 V 1 Bolt Tension
Diagonal A325N 0.6250 3 4.11 12.43 0.331 V 1 Bolt Shear
Horizontal A325N 0.6250 2 3.69 12.43
0.297 1 Bolt Shear
T6 100 Leg A325N 1.0000 6 24.79 53.01 0.468 V 1 Bolt Tension
Diagonal A325N 0.6250 3 3.91 12.43 0.315 V 1 Bolt Shear
Horizontal A325N 0.6250 2 3.82 12.43 0.307 V 1 Bolt Shear
T7 80 Leg A325N 1.0000 8 21.83 53.01 0.412 V 1 Bolt Tension
Diagonal A325N 0.6250 3 3.89 12.43 0.313 V 1 Bolt Shear
Horizontal A325N 0.6250 2 4.06 12.43 b.327 V 1 Bolt Shear
T8 60 Leg A325N 1.0000 8 24.91 53.01 0.470 V 1 Bolt Tension
Diagonal A325N 0.6250 3 4.25 12.43
0.342 y/ 1 Bolt Shear
Horizontal A325N 0.6250 2 4.68 12.43
0.377 V 1 Bolt Shear
T9 40 Leg A325N 1.0000 8 27.97 53.01
0.528 V 1 Bolt Tension
Diagonal A325N 0.6250 3 4.40 12.43
0.354 V 1 Bolt Shear
Horizontal A325N 0.6250 2 5.08 12.43 0.409 V 1 Bolt Shear
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 22
Section Elevation Component Bolt Bolt Size Number Maximum Allowable Ratio Allowable Criteria
No. Type Grade Of Load per Load Load Ratio
ft in Bolts Bolt K Allowable
K
T10 20 Leg A354-BC 1.0000 10 23.32 55.22
0.422 V 1 Bolt Tension
Diagonal A325N 0.7500 3 6.50 17.89 0.363 I, 1 Bolt Shear
Horizontal A325N 0.7500 2 5.39 17.89 0.301 V 1 Bolt Shear
Compression Checks
Leg Design Data (Compression)
Section Elevation Size L L„ Kl/r A P„ OP„ Ratio
No. P„
ft ft ft int K K Oa
T1 190-180 Pipe 2.875"x 0.276"(2.5 10.00 5.00 64.9 2.2535 -5.70 74.51 0.076'
XS) K=1.00 V
T2 180-160 Pipe 3.5"x 0.300"(3 XS) 20.00 6.67 70.4 3.0159 -36.44 94.46 0.386'
K=1.00 V
T3 160-140 Pipe 4.5"x 0.337"(4 XS) 20.04 6.68 54.3 4.4074 -71.25 159.90 0.446 1
K=1.00 V
T4 140-120 Pipe 5.563"x 0.375"(5 20.04 6.68 43.6 6.1120 -103.39 239.38 0.432'
XS) K=1.00 V
T5 120-100 Pipe 6.625"x 0.340"(6 20.04 10.02 54.0 6.7133 -133.70 244.02 0.548 1
EHS) K=1.00 V
T6 100-80 Pipe 6.625"x 0.432"(6 20.05 10.03 54.8 8.4049 -166.20 303.62 0.547 1
• XS) K=1.00 V
T7 80-60 Pipe 6.625"x 0.432"(6 20.06 10.03 54.8 8.4049 -195.60 303.58 0.644 1
XS) K=1.00 VI'
T8 60-40 Pipe 8.625"x 0.375"(8 20.05 10.03 41.2 9.7193 -224.12 386.31 0.580 1
EHS) K=1.00 V
T9 40-20 Pipe 8.625"x 0.375"(8 20.05 10.03 41.2 9.7193 -252.85 386.31 0.655'
EHS) K=1.00 V
T10 20-0 Pipe 8.625"x 0.500"(8 20.05 10.03 41.8 12.762 -267.20 505.43 0.529'
XS) K=1.00 7
V
1 P„ 14P„contr0ls
Diagonal Design Data (Compression)
Section Elevation Size L L. Kl/r A P„ OP" Ratio
No. P„
ft ft ft inz K K @p”
T1 190-180 Pipe 2.375"x 0.154"(2 6.58 6.39 97.4 1.0745 -4.67 24.15 0.194'
STD) K=1.00 V
T2 180-160 Pipe 2.375"x 0.218"(2 7.94 7.67 120.1 1.4773 -9.57 23.14 0.413'
XS) K=1.00 V
T3 160-140 Pipe 2.375"x 0.154"(2 8.55 8.25 125.8 1.0745 -7.58 15.33 0.494'
STD) K=1.00
V
T4 140-120 Pipe 2.375"x 0.154"(2 9.24 8.91 135.8 1.0745 -10.27 13.17 0.780 1
STD) K=1.00 V
T5 120-100 Pipe 2.875"x 0.203"(2.5 12.52 12.06 152.7 1.7040 -12.34 16.50 0.748'
STD) K=1.00
V
T6 100-80 Pipe 3.5"x 0.216"(3 13.31 12.89 132.9 2.2285 -11.73 28.50 0.412'
tnxTower Report-version 7.0.5.1
August 28,2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 23
Section Elevation Size L L„ KI/r A P„ 4P„ Ratio
No. Pu
, ft ft ft in2 K K Op„
STD) K=1.00 V
T7 80-60 Pipe 3.5"x 0.216"(3 14.21 13.82 142.5 2.2285 -11.66 24.78 0.470
STD) K=1.00 V
T8 60-40 Pipe 3.5"x 0.216"(3 15.12 14.64 151.0 2.2285 -12.75 22.07 0.5781
STD) K=1.00 V
T9 40-20 Pipe 3.5"x 0.216"(3 16.08 15.62 161.1 2.2285 -13.21 19.40 0.681
STD) K=1.00 V
T10 20-0 (37515-2715)2.875"x 24.33 12.17 158.8 3.7615 -19.50 33.70 0.579'
.276"Pipe w/3.5"x.300" K=1.00 V
Half Sleeve
1 P„ I fig:).controls
Horizontal Design Data (Compression)
Section Elevation Size L L„ KI/r A P" 4)P„ Ratio
No. P„
ft ft ft int K K OP"
T1 190-180 Pipe 1.9"x 0.145"(1.5 8.52 4.14 79.8 0.7995 -3.24 22.58 0.143'
STD) K=1.00 V
T2 180-160 Pipe 1.9"x 0.145"(1.5 8.60 4.15 80.0 0.7995 -5.14 22.52 0.228 1
STD) K=1.00 V
T3 160-140 Pipe 1.9"x 0.145"(1.5 10.01 4.82 92.9 0.7995 -4.71 19.14 0.2461
STD) K=1.00 V
T4 140-120 Pipe 2.375"x 0.154"(2 12.10 5.82 88.7 1.0745 -7.07 27.21 0.260
STD) K=1.00 V
T5 120-100.. Pipe 2.375"x 0.154"(2 13.92 6.68 101.9 1.0745 -7.39 22.64 0.326 1
STD) K=1.00 V
T6 100-80 Pipe 2.375"x 0.154"(2 16.29 7.87 120.0 1.0745 -7.64 16.86 0.4531
STD) K=1.00 V
T7 80-60 Pipe 2.875"x 0.203"(2.5 18.86 9.15 115.9 1.7040 -8.11 28.64 0.2831
STD) K=1.00 V
T8 60-40 Pipe 2.875"x 0.203"(2.5 21.43 10.35 131.1 1.7040 -9.31 22.38 0.4161
STD) K=1.00 V
T9 40-20 Pipe 2.875"x 0.203"(2.5 23.93 11.60 147.0 1.7040 -10.01 17.82 0.562 1
STD) K=1.00 V
T10 20-0 Pipe 2.875"x 0.203"(2.5 25.18 12.23 154.9 1.7040 -10.77 16.05 0.671
STD) K=1.00 V
1 P„ /OP„controls
Top Girt Design Data (Compression)
Section Elevation Size L L„ KI/r A P„ 4P„ Ratio
No. Po
ft ft ft in2 K K O p„
T1 190-180 Pipe 1.9"x 0.145"(1.5 8.50 4.13 79.6 0.7995 -0.91 22.63 0.040 1
STD) K=1.00 V
1 P„ /OP„controls
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 24
Redundant Horizontal (1) Design Data (Compression)
• Section Elevation Size L L„ KI/r A P„ OP" Ratio
No. P„
ft ft ft in2 K K 4)P"
T10 20-0 Pipe 1.9"x 0.145"(1.5 6.29 5.93 114.4 0.7995 -4.64 12.89 0.360'
STD) K=1.00 V
1 P„ /¢P"controls
Redundant Diagonal (1) Design Data (Compression)
Section Elevation Size L L" KI/r A P„ von Ratio
No. P"
ft ft ft in2 K K
T10 20-0 Pipe 2.375"x 0.154"(2 11.50 10.77 164.2 1.0745 -4.24 9.00 0.471 '-
STD) K=1.00 V
1 P„ /4P"controls
Redundant Hip (1) Design Data (Compression)
Section Elevation Size L L„ KI/r A P„ 4P" Ratio
No. P„
ft ft ft in2 K K e"
T10 20-0 Pipe 1.9"x 0.145"(1.5 6.29 6.29 121.3 0.7995 -0.05 11.86 0.004'
STD) K=1.00 V
1 P„ /op„controls
Redundant Hip Diagonal (1) Design Data (Compression)
Section Elevation Size L L. Kl/r A P„ OP, Ratio
No. P„
ft ft ft in2 K K CPP
T10 20-0 Pipe 2.875"x 0.203"(2.5 15.07 15.07 190.9 1.7040 -0.06 10.56 0.005'
STD) K=1.00 ✓
1 P„ /e"controls
Inner Bracing Design Data (Compression)
Section Elevation Size L L„ Kl/r A P„ en Ratio
No. P„
ft ft ft in2 K K tOP"
T1 190-180 L2x2x1/8 4.25 4.25 128.3 0.4844 -0.02 6.56 0.002-'
K=1.00 V
T2 180-160 L2x2x1/8 4.28 4.28 129.3 0.4844 -0.01 6.48 0.001 '
K=1.00 V
T3 160-140 L2x2x1/8 5.01 5.01 151.1 0.4844 -0.01 4.79 0.001 '
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCl BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 25
Section Elevation Size L L„ KI/r A P„ 4P„ Ratio
No. P„
.. ft ft ft in2 K K OR,
K=1.00 V
T4 140-120 L2x2x1/8 6.05 6.05 182.6 0.4844 -0.01 3.28 0.003'
K=1.00 (/
T5 120-100 L2x2x1/8 6.96 6.96 210.0 0.4844 -0.01 2.48 0.003 1
K=1.00 ✓
T6 100-80 L2 1/2x2 1/2x3/16 8.15 8.15 197.5 0.9020 -0.01 5.23 0.002 1
K=1.00 V
T7 80-60 L3x3x3/16 9.43 9.43 189.9 1.0900 -0.01 6.83 0.002 1
K=1.00 V
T8 60-40 L3 1/2x3 1/2x1/4 10.71 10.71 185.2 1.6900 -0.01 11.13 0.001 1
K=1.00 V
T9 40-20 L3 1/2x3 1/2x1/4 11.96 11.96 206.9 1.6900 -0.01 8.92 0.001 '
K=1.00 V
T10 20-0 Pipe 2.375"x 0.154"(2 12.59 12.59 191.9 1.0745 -0.01 6.59 0.002'
STD) K=1.00 V
1 P„ /oP„controls
Tension Checks
Leg Design Data (Tension)
Section Elevation Size L Lu KI/r A P„ 4Pn Ratio
No. P„
ft ft ft in2 K K OP„
T1 190-180 Pipe 2.875"x 0.276"(2.5 10.00 5.00 64.9 2.2535 2.58 101.41 0.025'
XS) V
T2 180-160 Pipe 3.5"x 0.300"(3 XS) 20.00 6.67 70.4 3.0159 29.99 135.72 0.221 '
V
T3 160-140 Pipe 4.5"x 0.337"(4 XS) 20.04 6.68 54.3 4.4074 63.04 198.34 0.318'
V
T4 140-120 Pipe 5.563"x 0.375"(5 20.04 6.68 43.6 6.1120 91.21 275.04 0.332'
XS) V
T5 120-100 Pipe 6.625"x 0.340"(6 20.04 10.02 54.0 6.7133 119.29 302.10 0.395'
EHS) y/
T6 100-80 Pipe 6.625"x 0.432"(6 20.05 10.03 54.8 8.4049 148.76 378.22 0.393 1
XS) V
T7 80-60 Pipe 6.625"x 0.432"(6 20.06 10.03 54.8 8.4049 174.66 378.22 0.462'
XS) V
T8 60-40 Pipe 8.625"x 0.375"(8 20.05 10.03 41.2 9.7193 199.25 437.37 0.456'
EHS) V
T9 40-20 Pipe 8.625"x 0.375"(8 20.05 10.03 41.2 9.7193 223.78 437.37 0.512'
EHS) V
T10 20-0 Pipe 8.625"x 0.500"(8 20.05 10.03 41.8 12.762 233.61 574.32 0.407'
XS) 7 V
1 P„ I oP„controls
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 26
Diagonal Design Data (Tension)
• Section Elevation Size L L„ KI/r A P,, OPS Ratio
No. P„
ft ft ft in2 K K OP„
T1 190-180 Pipe 2.375"x 0.154"(2 6.58 6.39 97.4 1.0745 4.59 48.35 0.095'
STD) V
T2 180-160 Pipe 2.375"x 0.218"(2 7.94 7.67 120.1 1.4773 9.46 66.48 0.142'
XS) V
T3 160-140 Pipe 2.375"x 0.154"(2 8.14 7.84 119.5 1.0745 7.51 48.35 0.155'
STD) V
T4 140-120 Pipe 2.375"x 0.154"(2 9.24 8.91 135.8 1.0745 10.14 48.35 0.210'
STD) V
T5 120-100 Pipe 2.875"x 0.203"(2.5 12.19 11.73 148.5 1.7040 12.15 76.68 0.158'
STD)
+
T6 100-80 Pipe 3.5"x 0.216"(3 13.31 12.89 132.9 2.2285 11.44 100.28 0.114'
STD) V
17 80-60 Pipe 3.5"x 0.216"(3 14.21 13.82 142.5 2.2285 11.27 100.28 0.112'
STD) V
T8 60-40 Pipe 3.5"x 0.216"(3 15.12 14.64 151.0 2.2285 12.27 100.28 0.122 1
STD) V
T9 40-20 Pipe 3.5"x 0.216"(3 16.08 15.62 161.1 2.2285 12.66 100.28 0.126'
STD) ✓
T10 20-0 (37515-2715)2.875"x 24.33 12.17 158.8 3.7615 18.96 155.73 0.122 1
.276"Pipe w/3.5"x.300" V
Half Sleeve
1 P„ /OP"controls
Horizontal Design Data (Tension)
Section Elevation Size L L„ KI/r A P„ OR, Ratio
No. P„
ft ft ft in2 K K ePP"
T1 190-180 Pipe 1.9"x 0.145"(1.5 8.52 4.14 79.8 0.7995 3.33 35.98 0.093'
STD) V
T2 180-160 Pipe 1.9"x 0.145"(1.5 8.60 4.15 80.0 0.7995 5.17 35.98 0.144 1
STD) ✓
T3 160-140 Pipe 1.9"x 0.145"(1.5 10.01 4.82 92.9 0.7995 4.68 35.98 0.130'
STD)
V
T4 140-120 Pipe 2.375"x 0.154"(2 12.10 5.82 88.7 1.0745 7.03 48.35 0.145 1
STD) V
T5 120-100 Pipe 2.375"x 0.154"(2 13.92 6.68 101.9 1.0745 7.27 48.35 0.150'
STD) V
T6 100-80 Pipe 2.375"x 0.154"(2 16.29 7.87 120.0 1.0745 7.57 48.35 0.156'
STD) V
T7 80-60 Pipe 2.875"x 0.203"(2.5 18.86 9.15 115.9 1.7040 8.08 76.68 0.105 1
STD) ✓
T8 60-40 Pipe 2.875"x 0.203"(2.5 21.43 10.35 131.1 1.7040 9.36 76.68 0.122'
STD) V
T9 40-20 Pipe 2.875"x 0.203"(2.5 23.93 11.60 147.0 1.7040 10.16 76.68 0.133 1
STD) V
T10 20-0 Pipe 2.875"x 0.203"(2.5 25.18 12.23 154.9 1.7040 10.32 76.68 0.135'
STD)
V
1 P„ / P.controls
tnxTower Report-version 7.0.5.1
• August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 27
Top Girt Design Data (Tension)
Section Elevation Size L L„ KI/r A Pu OP„ Ratio
No. Po
ft ft ft in2 K K 4)P„
T1 190-180 Pipe 1.9"x 0.145"(1.5 8.50 4.13 79.6 0.7995 0.92 35.98 0.026'
STD) V
1 P o /OP,,controls
Redundant Horizontal (1) Design Data (Tension)
Section Elevation Size L Lo KI/r A Po (1)P„ Ratio
No. Po
ft ft ft in2 K K (1)P"
T10 20-0 Pipe 1.9"x 0.145"(1.5 6.29 5.93 114.4 0.7995 4.64 25.18 0.184'
STD) V
1 P„ /4P„controls
Redundant Diagonal (1) Design Data (Tension)
Section Elevation Size L L„ Kl/r A P„ OP" Ratio
No. Po
ft ft ft in2 K K (OP,.
T10 20-0 Pipe 2.375"x 0.154"(2 11.50 10.77 164.2 1.0745 4.24 33.85 0.125'
STD) V
1 P„ /dP„controls
Redundant Hip Diagonal (1) Design Data (Tension)
Section Elevation Size L L„ KI/r A P„ dP„ Ratio
No. Po
ft ft ft in2 K K OP"
T10 20-0 Pipe 2.875"x 0.203"(2.5 15.07 15.07 190.9 1.7040 0.08 53.68 0.001 '
STD) V
1 P„ /OP„controls
Inner Bracing Design Data (Tension)
Section Elevation Size L L„ KI/r A P„ COP" Ratio
No. Po
ft ft ft in2 K K OP.
T1 190-180 L2x2x1/8 4.25 4.25 81.4 0.4844 0.02 15.69 0.001 1
V
T2 180-160 L2x2x1/8 4.30 4.30 82.4 0.4844 0.01 15.69 0.000 1
V
T3 160-140 L2x2x1/8 4.31 4.31 82.6 0.4844 0.00 15.69 0.000 1
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 28
Section Elevation Size L L„ KI/r A P„ OPS Ratio
No. P„
.. ft ft ft in2 K K OR,
V
T4 140-120 L2x2x1/8 6.05 6.05 115.9 0.4844 0.01 15.69 0.0001
V
T5 120-100 L2x2x1/8 6.40 6.40 122.6 0.4844 0.00 15.69 0.000 1
Vi"
T6 100-80 L2 1/2x2 1/2x3/16 7.52 7.52 116.0 0.9020 0.00 29.22 0.000
I,
T7 80-60 L3x3x3/16 8.77 8.77 112.1 1.0900 0.00 49.05 0.00/01
Y
T10 20-0 Pipe 2.375"x 0.154"(2 12.59 12.59 191.9 1.0745 0.00 48.35 0.000 1
STD) 1,r+'
1 P„ /4P„controls
Section Capacity Table
Section Elevation Component Size Critical P eP„,p„. % Pass
No. ft Type Element K K Capacity Fail
-
T1 190-180 Leg Pipe 2.875"x 0.276"(2.5 XS) 2 -5.70 74.51 7.6 Pass
T2 180-160 Leg Pipe 3.5"x 0.300"(3 XS) 29 -36.44 94.46 38.6 Pass
T3 160-140 Leg Pipe 4.5"x 0.337"(4 XS) 68 -71.25 159.90 44.6 Pass
T4 140-120 Leg Pipe 5.563"x 0.375"(5 XS) 107 -103.39 239.38 43.2 Pass
15 120-100 Leg Pipe 6.625"x 0.340"(6 EHS) 146 -133.70 244.02 54.8 Pass
T6 100-80 Leg Pipe 6.625"x 0.432"(6 XS) 173 -166.20 303.62 54.7 Pass
T7 80-60 Leg Pipe 6.625"x 0.432"(6 XS) 200 -195.60 303.58 64.4 Pass
T8 60-40 Leg Pipe 8.625"x 0.375"(8 EHS) 227 -224.12 386.31 58.0 Pass
T9 40-20 Leg Pipe 8.625"x 0.375"(8 EHS) 254 -252.85 386.31 65.5 Pass
T10 20-0 • Leg Pipe 8.625"x 0.500"(8 XS) 281 -267.20 505.43 52.9 Pass
T1 190-180 Diagonal Pipe 2.375"x 0.154"(2 STD) 9 -4.67 24.15 19.4 Pass
T2 180-160 Diagonal Pipe 2.375"x 0.218"(2 XS) 33 -9.57 23.14 41.3 Pass
T3 160-140 Diagonal Pipe 2.375"x 0.154"(2 STD) 71 -7.58 15.33 49.4 Pass
T4 140-120 Diagonal Pipe 2.375"x 0.154"(2 STD) 114 -10.27 13.17 78.0 Pass
T5 120-100 Diagonal Pipe 2.875"x 0.203"(2.5 153 -12.34 16.50 74.8 Pass
STD)
T6 100-80 Diagonal Pipe 3.5"x 0.216"(3 STD) 180 -11.73 28.50 41.2 Pass
T7 80-60 Diagonal Pipe 3.5"x 0.216"(3 STD) 207 -11.66 24.78 47.0 Pass
T8 60-40 Diagonal Pipe 3.5"x 0.216"(3 STD) 234 -12.75 22.07 57.8 Pass
T9 40-20 Diagonal Pipe 3.5"x 0.216"(3 STD) 261 -13.21 19.40 68.1 Pass
T10 20-0 Diagonal (37515-2715)2.875"x.276" 294 -19.50 33.70 57.9 Pass
Pipe w/3.5"x.300"Half
Sleeve
T1 190-180 Horizontal Pipe 1.9"x 0.145"(1.5 STD) 10 -3.24 22.58 14.3 Pass
T2 180-160 Horizontal Pipe 1.9"x 0.145"(1.5 STD) 31 -5.14 22.52 22.8 Pass
T3 160-140 Horizontal Pipe 1.9"x 0.145"(1.5 STD) 70 -4.71 19.14 24.6 Pass
T4 140-120 Horizontal Pipe 2.375"x 0.154"(2 STD) 112 -7.07 27.21 26.0 Pass
T5 120-100 Horizontal Pipe 2.375"x 0.154"(2 STD) 151 -7.39 22.64 32.6 Pass
T6 100-80 Horizontal Pipe 2.375"x 0.154"(2 STD) 178 -7.64 16.86 45.3 Pass
T7 80-60 Horizontal Pipe 2.875"x 0.203"(2.5 205 -8.11 28.64 28.3 Pass
STD)
18 60-40 Horizontal Pipe 2.875"x 0.203"(2.5 232 -9.31 22.38 41.6 Pass
STD)
T9 40-20 Horizontal Pipe 2.875"x 0.203"(2.5 259 -10.01 17.82 56.2 Pass
STD)
T10 20-0 Horizontal Pipe 2.875"x 0.203"(2.5 290 -10.77 16.05 67.1 Pass
STD)
T1 190-180 Top Girt Pipe 1.9"x 0.145"(1.5 STD) 5 -0.91 22.63 4.0 Pass
T10 20-0 Redund Horz 1 Pipe 1.9"x 0.145"(1.5 STD) 292 -4.64 12.89 36.0 Pass
Bracing
T10 20-0 Redund Diag 1 Pipe 2.375"x 0.154"(2 STD) 289 -4.24 9.00 47.1 Pass
Bracing
T10 20-0 Redund Hip 1 Pipe 1.9"x 0.145"(1.5 STD) 297 -0.05 11.86 0.4 Pass
Bracing
tnxTower Report-version 7.0.5.1
• August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364, Revision 2 Page 29
Section Elevation Component Size Critical P ePa„ow % Pass
No. ft Type Element K K Capacity Fail
•' T10 20-0 Redund Hip Pipe 2.875"x 0.203"(2.5 298 -0.06 10.56 0.5 Pass
Diagonal 1 Bracing STD)
T1 190-180 Inner Bracing L2x2x1/8 25 -0.02 6.56 0.2 Pass
T2 180-160 Inner Bracing L2x2x1/8 54 -0.01 6.48 0.1 Pass
T3 160-140 Inner Bracing L2x2x1/8 81 -0.01 4.79 0.1 Pass
T4 140-120 Inner Bracing L2x2x1/8 120 -0.01 3.28 0.3 Pass
T5 120-100 Inner Bracing L2x2x1/8 159 -0.01 2.48 0.3 Pass
T6 100-80 Inner Bracing L2 1/2x2 1/2x3/16 186 -0.01 5.23 0.2 Pass
T7 80-60 Inner Bracing L3x3x3/16 212 -0.01 6.83 0.2 Pass
T8 60-40 Inner Bracing L3 1/2x3 1/2x1/4 240 -0.01 11.13 0.2 Pass
T9 40-20 Inner Bracing L3 1/2x3 1/2x1/4 267 -0.01 8.92 0.2 Pass
T10 20-0 Inner Bracing Pipe 2.375"x 0.154"(2 STD) 310 -0.01 6.59 0.2 Pass
Summary
Leg(T9) 65.5 Pass
Diagonal 78.0 Pass
(T4)
Horizontal 67.1 Pass
(T10)
Top Girt 4.0 Pass
(T1)
Redund 36.0 Pass
Horz 1
Bracing
(T10)
Redund 47.1 Pass
Diag 1
Bracing
(T10)
Redund 0.4 Pass
Hip 1
Bracing
(T10)
Redund 0.5 Pass
Hip
Diagonal 1
Bracing
(T10)
Inner 0.3 Pass
Bracing
(T5)
Bolt 52.8 Pass
Checks
RATING= 78.0 Pass
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 30
APPENDIX B
BASE LEVEL DRAWING
LEC A
('510 10 130 n LIM ••
16
(7)1-]/]-10.30 n LMl ••
••
(1614110)
% P7 a/1e'10 111111 RR
V
(37 lir 10 11 11 LEK(
(])]/'10 011n LIM
f.D -]/e-10 161 n LML
•.•e. VVelrO�CLAM
LEG 11
/ (wo/5 10 1 Ct..)
n)7/e-10.len 1161
(3)1480-01 CWCun-W K 110/0/40)
(]7 S/.e'10.M n 1161
07 0077 To
110 n 11711
( )
(3)3)I/VVI-10 1K n LML
LIG C
tnxTower Report-version 7.0.5.1
August 28, 2017
190 Ft Self Support Tower Structural Analysis CCI BU No 812565
Project Number 37517-3033.001.8700,Application 402364,Revision 2 Page 31
APPENDIX C
ADDITIONAL CALCULATIONS
tnxTower Report-version 7.0.5.1
II
Qa 190.0 rt ii , !l 1 I •
< W - ® e
1M I SYMBOL LIST
_ _ 180.0 rt
I
- MARK SIZE i MARK SIZE
X 1A Pipe 2.875 x 0.275(2.5 XS) F Pipe 2.375 x 0218'(2 XS)
se I II , B Pipe 5.563'x 0.375'(5 XS) G Pipe 2.875'x 0.203'(2.5 STD)
S yr C Pipe 6.625'x 0.340'(6 EHS) H (37515-2715)2.875"x.275 Pipe w/3.5 x.300'
0 o - ut 0 Pipe 8.625 x 0.500'(8 XS) Half Sleeve
;
a E Pipe 2.375'x o.154'(2 STD) I Pipe 1.9'x 0.145'(1.5 STD)
a _ - 1600rt MATERIAL STRENGTH
,zrGRADE Fy Fu ; GRADE Fy I Fu -
F N 8, d A618-50 50 ksi 70 ksi I A500-46 46 ksi 162 kal
IS a
V os TOWER DESIGN NOTES
.e
• H e CO 1. Tower is located in Duval County,Florida.
< = 2. Tower designed for Exposure C to the TIA-222-G Standard.
a h 3. Tower designed for a 100 mph basic wind in accordance with the TIA-222-G Standard.
- o _ -er - 140.006" 4. Deflections are based upon a 60 mph wind.
6 5. Tower Structure Class II.
.? 6. Topographic Category 1 with Crest Height of 0.00 ft
g I I I AI I 7. TOWER RATING:78%
„,.._ 120.0 ft
N IV
h_
P U o o n
E In
eu n < < S
V Z 2 Z
< g
E. _ - _ 100_0 rt
S o
Di
b N Q
e z n
X
F.
n
-ox - _F _ 80.0 ft
N N
w
g m
E. 5 o
N
m
- c.;,460Art
O g
LI -
N
a
F a
_ 05 3
W N
E. r
_o - 40,0 rt ALL REACTIONS
x ARE FACTORED
m N n i4 MAX.CORNER REACTIONS AT BASE:
a 8 DOWN: 293 K
Ca a. -
SHEAR: 36 K
UPLIFT: -257 K
_ 20.0 rt SHEAR: 33 K
r.
AL
N � , A 6IK
E o I Q - w - w0
1 SHEAR MOMENT •
60 K 6615 kip-ft
oort
TORQUE 34 kip-ft
N REACTIONS-100 mph WIND
e _
9 O el C s
e >n e
g o o c f7 b ' 9 g t
o f m� a'g a a d g . t
in 6 5 H � z° s° C s LL x
Job:
p.JF
Paul JFord and Company 190-ft Self Support Tower Atlantic Beach,FL
250 E. Broad Street Suite 600 Project PJF#37517-3033(BU#812565)
Coilumbus,OH 43215 Client:Crown Castle Drawn by:Jared Smith Appd:
Phone:614.221.6679 Code.TIA-222-G Date:08/28/17 Scale:NTS
FAX:614.448.4105 Path`p„ Dwg No.E-1
Anchor Rod Check for Self Supporting Towers f\gs C�A�! LE
TIA-222-G, Section 4.9.9 Rev. 6.1 tk
Site Data Reactions
BU#: 812565 Eta Factor, tl 0.55 Detail Type
Site Name: Uplift, Pu: 257 kips
App#: Shear,Vu: 33 kips
Anchor Rod Data lir: in
Qty: 10 Mu=0.65*1af*Vu ft-kips
Diam: 1 in
Rod Material: A354 Gr. BC(1/4 to 2-1/2 incl.)
Strength (Fu): 125 ksi Anchor Rod Results:
Yield(Fy): 109 ksi Max Rod(Cu+Vu/rj): 31.7 Kips
Design Axial,c*Fu*Anet: 60.6 Kips
*Rod Circle: in Anchor Rod Stress Ratio: 52.3%
*e: in
*#of Rods 1 or 2
If Applicable;
Mu= Pu x e: ft-kips Anchor Rod Results with Bending Considered:
*Only enter rod circle,offset(e)and number When the clear distance from the top of concrete to the bottom
of anchor rods at the extreme fiber to of level nut excceeds 1.0 times the diameter of the anchor rod,
consider if eccentric load due to leg the following interaction equation shall also be satisfied(see
reinforcement exist. Figure 4-4 of Rev. G):
(VAR.)2+i(Pu/4Rnt)+(MARnm))2<=1
0 0 o a: oRnv 4*0.45*Fub*Ay= kips
oC'a+
A !1 B Qom;_ 8 $Rnt=0*Fu*Anel= kips
4Rnm 4*Fy*Z= ft-kips
caraxs-‘ uorce Y--.
1' —I
SECTION A-A SECTION s-3
Detail Type(a) Detail Type(b)
?zeo.90 70
C
JGar snrr+
Gros :.a+melrl
mac- :._T]
SECTION C-C SECTION D-D
Detail Type(c) Detail Type(d) Maximum Acceptable Ratio: 105 %
7j-O•Ss (5.v Not.1 b )
S4 Governing Stress Ratio: 52.3% Pass
Figure 4-4 of TIA-222-G
37517-3033.001.8700 SST Anchor Rod Check For Rev G-Rev 6.1 091912.xls
PJF job no. 37517-3033.001 Project name BU 812565 293 kips page 1
Combined Footing Foundation
Concrete strength F'c= 3 (ksi)
Rebar Strength Fy= 60 (ksi)
Soil Density= 100 (pcf) 'III=III 'I I I-1 I I'
Depth to Water Table= 4.5 (ft)
minimum cover over vert rebar= 3 inches
Overturning Moment=6615 ft-k Nc
d/2 d/2=27.656 in
I
Total Horizontal Load =60 k CT) ► 4 o. l4
1.2D=>Tower i
'Wt=62k ii
I- r -O
l' / j
.."-- -if 5o
s.
�O d O' 0
;IIlI
'III=111 ' 'I 11=111
103.312 in
...........2. ...1
---, " . 10
Ftg Overturning Resistance= 17498.9 ft-kips
36' Total Overturning Moment=7190.7 ft-kips
Required Overturning Safety Factor= 1
11 Overturning Safety Factor=2.43
36.5 ft Ratio=0.41 OK
Maximum Net Soil Bearing = 1.577 ksf
257 kips 293 kips Ultimate Net Soil Bearing = 3.75 ksf
36 kip
1 1Soil Bearing Stress Ratio=0.42 OK
in
o Ult Punching Shear Capacity=219 psi
4 ft square conc pier9 I I=1 II III-1Ii' 11 11=III Ult Punching Shear Force= 14 psi
with ( 16 )#9 vert#4 ties v Punching Shear Stress Ratio=0.06 OK
= U,
5 ft thk conc footing with `D C° Pad Bending Moment Capacity= 17295 ft-k
(72)#9 bars by 36 ft Ig Pad Bending Moment= 1533 ft-k
1.0
each way top&bottom--► Bending Moment Stress Ratio=0.09 OK
A A A A A ♦ ♦
AA A ♦ AA r
Pier Rebar Capacity=-864 kips
i Pier Rebar Required =-257 kips
i Net Soil Bearing = Pier Rebar Stress Ratio=0.3 OK
5.673 ft 1247 psf
Total concrete=249.4 cubic yards �♦ Pad Bending Shear Capacity= 1990 ft-k
P= 1278.46 k Pad Bending Shear= 0 ft-k
I'
Bending Shear Stress Ratio=0 OK
v1.7, Effective 11/02/16