Loading...
362 PLAZA - ENERGY REPORTS �S ICC EVALUATION Most Widely Accepted and Trusted � SERVICE ICC-ES Report ESR-1826 ICC-ESI (800) 423-6587 I (562) 699-0543 I www.icc-es.org Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00—THERMAL INSULATION OFFICE COPY REPORT HOLDER: ICYNENE, INC. 6747 CAMPOBELLO ROAD MISSISSAUGA, ONTARIO L5N 2L7 CANADA EVALUATION SUBJECT: ICYNENE CLASSIC, CLASSIC MAX, CLASSIC ECO AND CLASSIC PLUS ICC ICC L_ESM PMG LISTED Look for the trusted marks of Conformity! :mak "2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC)Award in Excellence" A Subsidiary of CODE COUNCIL ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not 'A-A' specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a ANSI recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as AnAccredftedPngram to any finding or other matter in this report, or as to any product covered by the report. PRODUCT IuT10N .. .«.ro ccN Copyright° 2016 ICC Evaluation Service, LLC. All rights reserved. it-c ICC EVALUATION SERVICE Most Widely Accepted and Trusted ICC-ES Evaluation Report ESR-1826 Reissued February 2016 This report is subject to renewal February 2018. www.icc-es.org I (800)423-6587 I (562) 699-0543 A Subsidiary of the International Code Council® DIVISION: 07 00 00—THERMAL AND MOISTURE 2.0 USES PROTECTION Icynene Classic, Classic Max, Classic Eco and Classic Section: 07 21 00—Thermal Insulation Plus are used to provide thermal insulation in buildings and REPORT HOLDER: to seal areas such as plumbing and conduit penetrations against air infiltration. The insulations are for use in wall ICYNENE, INC. cavities and floor assemblies; and in attic and crawl space 6747 CAMPOBELLO ROAD installations as described in Section 4.4. MISSISSAUGA, ONTARIO L5N 2L7 The Classic, Classic Max and Classic Eco insulations are CANADA for use in Type V construction under the IBC and dwellings (905)363-4040 under the IRC; fire-resistance-rated construction when www.icynene.com installed in accordance with Section 4.5; and in Types I through IV construction when installed in accordance with EVALUATION SUBJECT: Section 4.6. ICYNENE CLASSIC, CLASSIC MAX, CLASSIC ECO AND The Classic Plus insulation are for use in Type V-B CLASSIC PLUS construction under the IBC and nonfire-resistance-rated construction under the IRC. 1.0 EVALUATION SCOPE The attributes of the insulations have been verified as 1.1 Compliance with the following codes: conforming to the provisions of ICC 700-2008 Section 703.2.1.1.1(c) as an air impermeable insulation. Note that • 2012 and 2009 International Building Code®(IBC) decisions on compliance for those areas rest with the user ® of this report. The user is advised of the project-specific • 2012 and 2009 International Residential Code®(IRC) provisions that may be contingent upon meeting specific • 2012 and 2009 International Energy Conservation conditions, and the verification of those conditions is Code®(IECC) outside the scope of this report. These codes or standards • 2013 Abu Dhabi International Building Code(ADIBC)t often provide supplemental information as guidance. 'The ADIBC is based on the 2009 IBC.2009 IBC code sections referenced 3.0 DESCRIPTION in this report are the same sections in the ADIBC. 3.1 General: • Other Codes(see Section 8.0) 3.1.1 Classic and Classic Max: Icynene Classic and Properties evaluated: Classic Max are low-density, open-cell, polyurethane foam plastic insulations and air barrier systems that are • Surface burning characteristics 100 percent water-blown with an installed nominal • Physical properties density of 0.5 pcf (8 kg/m3). The insulations are■ Thermal performance (R values) two- component, spray-applied products. The two components of the insulation are polymeric isocyanate (A-Component, • Attic and crawl space installation also known as Base Seal®) and proprietary resin • Fire resistance (B-Component, Classic or Classic Max Resin). When stored at temperatures between 50°F (10°C) and 100°F • Air permeability (38°C),the components have a shelf life of six months. • Noncombustible construction 3.1.2 Classic Eco: The Icynene Classic Eco foam plastic 1.2 Evaluation to the following green standard: insulation is two-component, low-density, open cell, spray- applied, foam plastic with a nominal density of • 2008 ICC 700 National Green Building StandardTM (ICC 0.5 pcf (8 kg/m3). The polyurethane foam is produced by 700-2008) combining a polymeric isocyanate (A component) and Attributes verified: proprietary resin, Classic Eco (B component). When stored at temperatures between 50°F (10°C) and 100°F (38°C), • See Section 2.0 the components have a shelf life of six months. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed II Ctio- as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LW,express or implied,as to any finding or other matter in this report,or as to any product covered by the report. IE 1003 Copyright 0 2016 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 8 ESR-1826 I Most Widely Accepted and Trusted Page 2 of 8 • 3.1.3 Classic Plus: The Icynene Classic Plus foam 3.5.2 DC 315: DC 315 intumescent coating is a water- plastic insulation is two-component, low density, open cell, based coating supplied in 5-gallon (19L) pails and spray-applied, foam plastic with a nominal density of 55-gallon (208L) drums. The coating material has a shelf 0.7 pcf(11 kg/m3). The polyurethane foam is produced by life of 24 months when stored in factory-sealed containers combining a polymeric isocyanate (A component) and at temperatures between 41°F(5°C)and 95°F (35°C). proprietary resin, Classic Plus (B component). When 4.0 INSTALLATION stored at temperatures between 50°F (10°C) and 100°F (38°C),the components have a shelf life of twelve months. 4.1 General: 3.2 Surface Burning Characteristics: The manufacturer's published installation instructions and 3.2.1 Classic and Classic Max: When tested in this report must be strictly adhered to and a copy of these accordance with ASTM E84/UL 723, at a thickness of instructions and this evaluation report must be available on 6 inches (152 mm) and a nominal density of 0.5 pcf the jobsite at all times during installation. (8 kg/m3), Icynene Classic and Classic Max have a flame 4.2 Application: spread index of 25 or less and a smoke developed index 4.2.1 General: Icynene Classic, Classic Max, Classic Eco of 450 or less.Thicknesses of up to 71/2 inches(190.5 mm) and Classic Plus foam plastic insulations must be applied for wall cavities and 111/2 inches (292 mm) for ceiling cavities are recognized based on room corner fire testing on the jobsite using two component, 1-to-1 ratio, spray in accordance with NFPA 286, when covered with equipment specified by Icynene, Inc. The foam plastic must not be sprayed onto a substrate that is wet, or minimum 1/2-inch-thick (13 mm) gypsum board or an covered with frost or ice, loose scales, rust, oil or grease. equivalent thermal barrier complying with the applicable The foam plastic insulation must not be used in electrical code. Greater thicknesses of insulation are recognized as outlet or junction boxes or in contact with rain or water, described in Section 4.4.1.2.1. and must be protected from the weather during and 3.2.2 Classic Eco: When tested in accordance with after application. Where the insulation is used as air- ASTM E84/UL 723, at a thickness of 6 inches (152 mm) impermeable insulation, such as in unvented attic spaces and a nominal density of 0.5 pcf(8 kg/m3), Icynene Classic regulated by IRC Section R806, the insulation must be Eco has a flame spread index of 25 or less and a smoke- installed at a minimum thicknesses noted in Section 3.4. developed index of 450 or less. Greater than 6-inch The insulation can be installed in one pass to the (152 mm) thicknesses of insulation are recognized, based maximum thickness. Where multiple passes are required, on the flame spread index of 25 or less, when the the cure time between passes is negligible. insulation is covered with minimum 1/2-inch-thick (13 mm) 4.2.2 Classic and Classic Max: The insulation must be gypsum wallboard or equivalent thermal barrier complying used in areas where the maximum service temperature is with the applicable code. no greater than 180°F (82°C). The insulation must be 3.2.3 Classic Plus: When tested in accordance with applied when the temperature is at or above 14°F (-10°C) ASTM E84/UL 723, at a thickness of 4 inches (152 mm) and be protected from the weather during and after and a nominal density of 0.7 pcf (11 kg/m3), Icynene application. Classic Plus has a flame spread index of 25 or less and a 4.2.3 Classic Eco: The insulation may be used in areas smoke developed index of 450 or less. Greater than where the maximum service temperature is no greater than 4-inch (102 mm) thicknesses of insulation are recognized, 180°F (82°C). The insulation must be applied when the based on the flame spread index of 25 or less, when the insulation is covered with minimum 1/2-inch-thick (13 mm) temperature is at or above 14°F (-10°C) and be protected gypsum wallboard or equivalent thermal barrier complying from the weather during and after application. with the applicable code. 4.2.4 Classic Plus: The insulation may be used in areas 3.3 Thermal Resistance: where the maximum service temperature is no greater than 180°F (82°C). The insulation must be applied when the Icynene Classic, Classic Max, Classic Eco and Classic temperature is at or above 14°F (-10°C) and be protected Plus have thermal resistance (R-values) at a mean from the weather during and after application. temperature of 75°F (24°C)as shown in Table 1. 4.3 Thermal Barrier: 3.4 Air Permeability: 4.3.1 Classic and Classic Max: Icynene spray-applied foam plastic insulations are 4.3.1.1 Application with a Prescriptive Thermal considered air impermeable insulation in accordance with Barrier: Icynene Classic and Classic Max foam plastic 2012 IRC Sections R202 and R806.5 and 2009 IRC insulations must be separated from the interior of the Sections R202 and R806.4, at the following thicknesses: building by an approved thermal barrier, such as '/2 inch • Classic and Classic Max: Minimum, 3 inches (76 mm) (12.7 mm) gypsum wallboard installed using mechanical based on testing in accordance with ASTM E2178. fasteners in accordance with the applicable code, or an • Classic Eco: Minimum, 51/2 inches (140 mm) based on equivalent 15 minute thermal barrier complying with the testing in accordance with ASTM E283. applicable code. When installation is within an attic or crawl space as described in Section 4.4, a thermal barrier • Classic Plus: Minimum, 2 inches (51 mm) based on is not required between the foam plastic and the attic or testing in accordance with ASTM E2178. crawl space, but is required between the foam plastic 3.5 Intumescent Coatings: insulation and the interior of the building. Thicknesses of up to 71/2 inches (190.5 mm) for wall cavities and 3.5.1 No Burn Plus XD: No Burn Plus XD intumescent 111/2 inches (292 mm) for ceiling cavities are recognized coating is a latex-based coating supplied in 1-gallon (4L) based on room corner fire testing in accordance with NFPA and 5-gallon (19L) pails and 55-gallon (208 L) drums. The 286, when covered with minimum 1/2-inch-thick (13 mm) coating material has a shelf life of 12 months when stored gypsum board or equivalent thermal barrier complying with in factory-sealed containers at temperatures between 40°F the applicable code. (4.4°C)and 90°F (32.2°C). ESR-1826 I Most Widely Accepted and Trusted Page 3 of 8 4.3.1.2 Application without a Prescriptive Thermal 2. There are no interconnected attic, crawl space or Barrier or Ignition Barrier: The prescriptive 15-minute basement areas. thermal barrier or ignition barrier may be omitted when 3. Air in the attic or crawl space is not circulated to other installation is in accordance with this section. The parts of the building. insulation and coating may be spray-applied to the interior facing of walls, the underside or roof sheathing of roof 4. Combustion air is provided in accordance with IMC rafters, and in crawl spaces, and may be left exposed as Section 701. an interior finish without a prescribed 15-minute thermal 5. Attic ventilation is provided when required by IBC barrier or ignition barrier. The thickness of the foam plastic Section 1203.2 or IRC Section R806, except when applied to the underside of the roof sheathing must not air-impermeable insulation is permitted in unvented exceed 14 inches (356 mm). The thickness of the spray attics in accordance with 2012 IRC Section R806.5 or foam insulation applied to vertical wall surfaces must not 2009 IRC Section R806.4, as applicable. exceed 6 inches (152 mm). The foam plastic must be covered on all surfaces with DC 315 coating at a minimum 6. Under-floor(crawl space) ventilation is provided when thickness of 20 wet mils[13 dry mils (0.33 mm)], applied at required by IBC Section 1203.3 or IRC Section a rate of 1.25 gallons (4.7 L) per 100 square feet (9.2 m2). R408.1, as applicable. The coating must be applied over the insulation in 4.4.1.2.1 Attics - Classic and Classic Max: In attics, accordance with the coating manufacturer's instructions Icynene Classic and Classic Max foam plastic insulations and this report. Surfaces to be coated must be dry, clean, may be spray-applied to the underside of the roof and free of dirt, loose debris and other substances that sheathing and/or rafters, as described in this section. The could interfere with adhesion of the coating. The coating is thickness of the foam plastic applied to the underside of applied in one coat with low-pressure airless spray the roof sheathing must not exceed 14 inches (356 mm). equipment. The thickness of the spray foam insulation applied 4.3.2 Classic Eco: to vertical wall surfaces must not exceed 5.5 inches 4.3.2.1 Application with a Prescriptive Thermal (140 mm). The insulation must be covered on all surfaces Barrier: Icynene Classic Eco polyurethane foam plastic with one of the coatings described in Section 3.5. The be separated the of thecoating must be applied over the insulation in accordance insulation mustinterior building by aapprovedthermalfrom barrier 1/2-inch-thickwith the coating manufacturer's instructions and this report. (13 mm) gypsum wallboard or an equivalent 15-minute Surfaces to be coated must be dry, clean, and free of dirt, thermal barrier complyingwith, and installed in accordance loose debris and other substances that could interfere with adhesion of the coating. The coating is applied in one coat with, IBC Section 2603.4 or IRC Section R316.4, as with low-pressure airless spray equipment. The coating applicable. must be applied to a thickness as follows: 4.3.3 Classic Plus: • No Burn Plus XD at a minimum thickness of 6 wet mils 4.3.3.1 Application with a Prescriptive Thermal (0.15 mm) [4 dry mils (0.1 mm) dry film thickness], Barrier: Icynene Classic Plus polyurethane foam plastic applied at a rate of 0.4 gallon (1.5 L) per 100 square insulation must be separated from the interior of the feet(9.2 m2). building by an approved thermal barrier of 1/2-inch-thick ■ DC 315 at a minimum thickness of 4 wet mils (0.1 mm) (13 mm) gypsum wallboard or an equivalent 15-minute [3 dry mils], applied at a rate of 0.3 gallon (1.1 L) per thermal barrier complying with, and installed in accordance 100 square feet(9.2 m2). with, IBC Section 2603.4 or IRC Section R316.4, as applicable. The coatings must be applied when ambient and 4.4 Attics and Crawl Spaces: substrate temperature is at least 60°F (16°C) and no more than 95°F (35°C). All other surfaces (including glass) must 4.4.1 Classic and Classic Max: be protected against damage from the coating. The 4.4.1.1 Application with a Prescriptive Ignition Barrier: insulation may be installed in unvented attics when the When Icynene Classic and Classic Max foam plastic foam plastic is applied at a minimum thickness of insulations are installed within attics where entry is made 3.5 inches (89 mm) as described in this section in only for service of utilities, an ignition barrier must be accordance with 2012 IRC Section R806.5 or 2009 IRC installed in accordance with IBC Section 2603.4.1.6 and Section R806.4, as applicable. IRC Sections R316.5.3 and R316.5.4, as applicable. The 4.4.1.2.2 Attics-Classic Max: When Classic Max is ignition barrier must be consistent with the requirements applied in unvented attics conforming to 2012 IRC Section for the type of construction required by the applicable code R806.5 or 2009 IRC Section R806.4,the insulation may be and must be installed in a manner so that the foam plastic applied to the underside of roof sheathing and/or rafters to insulation is not exposed. The Classic or Classic Max a minimum thickness of 31/2 inches (90 mm) and may be insulation may be installed in unvented attics when the applied to vertical wall surfaces to a minimum thickness of foam plastic is applied at a minimum thickness of 3 inches 3 /2 inches (90 mm). Maximum thickness on the underside (76 mm) in accordance with 2012 IRC Section R806.5 or of roof sheathing or on vertical wall surfaces is 20 inches 2009 IRC Section R806.4, as applicable. (508 mm). The insulation may be left exposed to the attic 4.4.1.2 Application without a Prescriptive Ignition without a prescriptive ignition barrier or an intumescent Barrier: Where Icynene Classic and Classic Max foam coating. plastic insulations are installed in an attic or crawl space The attic must have attic access complying with IRC without a prescriptive ignition barrier, in accordance with Section R807, horizontally placed in the floor, and opening Sections 4.4.1.2.1, 4.4.1.2.2, 4.4.1.2.3 and 4.4.1.2.4, the outward toward the living space. Items penetrating the roof following conditions apply: deck or walls, such as skylight wells and vents, must be 1. Entry to the attic or crawl space is only for service of covered with a minimum of 3'/2 inches (90 mm) of the utilities and no storage is permitted. Classic Max insulation. 4.4.1.2.3 Crawl Spaces: In crawl spaces, Icynene ESR-1826 I Most Widely Accepted and Trusted Page 4 of 8 Classic and Classic Max insulations may be spray-applied and this report. Surfaces to be coated must be dry, clean, to vertical walls and the underside of floors, as described in and free of dirt, loose debris and other substances that this section. The thickness of the foam plastic applied to could interfere with adhesion of the coating. The coating is the underside of the floors must not exceed 14 inches applied in one coat with low-pressure airless spray (356 mm). The thickness of the spray foam plastic equipment. The coating must be applied to a thickness as insulation applied to vertical wall surfaces must not exceed follows: 31/2 inches (88.9 mm). The foam plastic does not require • No Burn Plus XD at a minimum thickness of 10 wet mils an ignition barrier or a coating. (0.3 mm) [6 dry mils (0.2 mm)], applied at a rate of 4.4.1.2.4 Use on Attic Floors: When used on attic floors, 0.63 gallon (2.4 L) per 100 square feet(9.2 m2) Icynene Classic and Classic Max foam plastic insulations ■ DC 315 at a minimum thickness of 8 wet mils (0.2 mm) may be installed at a maximum thickness of 111/2 inches [6 dry mils (0.2 mm)], applied at a rate of 0.5 gallon (292 mm) between joists in attic floors. The insulation must (1.9 L) per 100 square feet(9.2 m2) be separated from the interior of the building by an approved thermal barrier.The coatings specified in Section The coating must be applied when ambient and 4.4.1.2.1 and the ignition barrier in accordance with IBC substrate temperature is at least 60°F (16°C) and no more Section 2603.4.1.6 and IRC Section R316.5.3, may be than 95°F (35°C). All other surfaces (including glass) must omitted. be protected against damage from the coating. 4.4.2 Classic Eco: Icynene Classic Eco insulation may be installed in 4.4.2.1 Application with a Prescriptive Ignition Barrier: unvented attics when the foam plastic is applied at a When Icynene Classic Eco is installed within attics or crawl minimum thickness of 5 /2 inches(140 mm)as described in spaces where entry is made only for service of utilities, an this section, in accordance with 2012 IRC Section R806.5 ignition barrier must be installed in accordance with IBC or 2009 IRC Section R806.4, as applicable. Section 2603.4.1.6 and IRC Sections R316.5.3 and 4.4.2.2.2 Crawl Spaces: In crawl spaces, Icynene R316.5.4, as applicable. The ignition barrier must be Classic Eco insulation may be spray-applied to vertical consistent with the requirements for the type of walls and the underside of floors, as described in this construction required by the applicable code and must be section. The thickness of the foam plastic applied to the installed in a manner so that the foam plastic insulation is underside of the floors must not exceed 14 inches not exposed. Icynene Classic Eco may be installed in (356 mm). The thickness of the spray foam plastic unvented attics when the foam plastic is applied at a insulation applied to vertical wall surfaces must not exceed minimum thickness of 5.5 inches (140 mm) in accordance 31/2 inches (88.9 mm). The foam plastic does not require with 2012 IRC Section R806.5 or 2009 IRC Section an ignition barrier or a coating. R806.4, as applicable. 4.4.2.2.3 Use on Attic Floors: Icynene Classic Eco 4.4.2.2 Application without a Prescriptive Ignition insulation may be installed at a maximum thickness of Barrier: Where Icynene Classic Eco insulation is installed 51/2 inches (152 mm) between joists in attic floors when in accordance with Sections 4.4.2.2.1, 4.4.2.2.2 and covered with one of the coatings applied as described in 4.4.2.2.3,the following conditions apply: Section 4.4.2.2.1. The insulation must be separated from 1. Entry to the attic or crawl space is to service utilities, the interior of the building by an approved thermal barrier. and no storage is permitted. 4.4.3 Classic Plus: 2. There are no interconnected attic or crawl space 4.4.3.1 Application with a Prescriptive Ignition Barrier: areas. When Icynene Classic Plus is installed up to a maximum 3. Air in the attic or crawl space is not circulated to other thickness of 4 inches (102 mm) within attics or crawl parts of the building. spaces where entry is made only for service of utilities, an ignition barrier must be installed in accordance with IBC 4. Combustion air is provided in accordance with IMC Section 2603.4.1.6 and IRC Sections R316.5.3 and Section 701. R316.5.4, as applicable. The ignition barrier must be 5. Attic ventilation is provided when required by IBC consistent with the requirements for the type of Section 1203.2 or IRC Section R806, except when construction required by the applicable code and must be air-impermeable insulation is permitted in unvented installed in a manner so that the foam plastic insulation is attics in accordance with 2012 IRC Section R806.5 or not exposed. Icynene Classic Plus may be installed in 2009 IRC Section R806.4, as applicable. unvented attics when the foam plastic is applied at a minimum thickness of 2 inches (51 mm) in accordance 6. Under-floor(crawl space) ventilation is provided when with 2012 IRC Section R806.5 or 2009 IRC Section required by IBC Section 1203.3 or IRC Section R806.4, as applicable. R408.1, as applicable. 4.4.3.2 Application without a Prescriptive Ignition 4.4.2.2.1 Attics and Crawl Spaces: In attics and crawl Barrier: Where Icynene Classic Plus insulation is installed spaces, Icynene Classic Eco insulation may be spray- in accordance with Sections 4.4.3.2.1, 4.4.3.2.2, and applied to the underside of the roof sheathing and/or 4.4.3.2.3, the following conditions apply: rafters, the underside of wood floors, and vertical surfaces, as described in this section. The thickness of the foam 1. Entry to the attic or crawl space is to service utilities, plastic applied to the underside of the top of the space and no storage is permitted. must not exceed 131/2 inches (343 mm). The thickness of 2. There are no interconnected attic or crawl space the spray foam plastic insulation applied to vertical wall areas. surfaces must not exceed 51/2 inches (140 mm). The foam plastic must be covered on all surfaces with one of the 3. Air in the attic or crawl space is not circulated to other coatings described in Section 3.5. The coating must be parts of the building. applied over the Icynene Classic Eco insulation in 4. Combustion air is provided in accordance with IMC accordance with the coating manufacturer's instructions Section 701. ESR-1826 I Most Widely Accepted and Trusted Page 5 of 8 '5. Attic ventilation is provided when required by IBC Max insulation nominally 2 inches (51 mm)thick. Section 1203.2 or IRC Section R806, except when Axial loads applied to the wall assembly must be limited air-impermeable insulation is permitted in unvented to the least of the following: attics in accordance with 2012 IRC Section R806.5 or 2009 IRC Section R806.4, as applicable. • 1,805 pounds(8029 N) per stud. 6. Under-floor(crawl space) ventilation is provided when ■ Design stress of 0.78 F'c. required by IBC Section 1203.3 or 1RC Section ■ Design stress of 0.78 F'c at a maximum le/d of 33. R408.1, as applicable. 4.5.1.2 Assembly 2 (Limited Load-bearing Wood Stud 4.4.3.2.1 Attics: In attics, Icynene Classic Plus insulation Wall): Minimum nominally 2-by-4 [02 by 31/2 inches may be spray-applied to the underside of the roof (38 mm by 89 mm)] southern pine (G = 0.55), No. 2 grade sheathing and/or rafters, the underside of wood floors, and studs spaced 16 inches (406 mm) on center with two vertical surfaces, as described in this section. The layers of 1/2-inch-thick (12.7 mm) Type X gypsum thickness of the foam plastic applied to the underside of wallboard installed vertically with joints staggered on each the top of the space must not exceed 14 inches (356 mm). face, attached with 8d box nails, 21/2 inches (64 mm) long The thickness of the spray foam plastic insulation applied and spaced 7 inches (178 mm) on center along the studs to vertical wall surfaces must not exceed 8 inches for the face layer and 6d cement coated box nails, 2 inches (203 mm). The foam plastic insulation must be covered on (51 mm) long and spaced 24 inches (610 mm) on center all exposed surfaces with DC315 intumescent coating at a along the studs. The stud cavity contains Icynene Classic minimum thickness of 4 wet mils (0.1 mm) [3 dry mils or Classic Max insulation nominally 2 inches(51 mm)thick. (0.08 mm)], applied at a rate of 0.25 gallon (0.95 L) per 100 square feet (9.2 m2). The coating must be applied Axial loads applied to the wall assembly must be limited over the Icynene Classic Plus insulation in accordance with to the least of the following: the coating manufacturer's instructions and this report. • 1,805 pounds(8029 N) per stud. Surfaces to be coated must be dry, clean, and free of dirt, loose debris and other substances that could interfere with • Design stress of 0.78 Pc. adhesion of the coating. The coating is applied in one coat • Design stress of 0.78 F'c at a maximum le/d of 33. with low-pressure airless spray equipment. The coating must be applied when ambient and 4.5.1.3 Assembly 3 (Floor/Ceiling): Minimum nominally substrate temperature is at least 60°F (16°C) and no more 2-by-10 [11/2 by 9 /4 inches (38 mm by 235 mm)] Douglas than 95°F (35°C). All other surfaces (including glass) must fir, No. 2 grade wood joists spaced 24 inches (610 mm) on be protected against damage from the coating. center, with minimum 1-by-3 [3/4 by 21/2 inches (19.1 by 64 mm)] spruce bridging at mid-span. Floor decking Icynene Classic Plus insulation may be installed in must be minimum 1/2-inch-thick (12.7 mm) exterior grade unvented attics when the foam plastic is applied at a plywood installed perpendicular to joists and fastened with minimum thickness of 2 inches (51 mm) as described in 2-inch-long (51 mm) ring shank nails 6 inches(152 mm) on this section, in accordance with 2012 IRC Section R806.5 center at the joints and 12 inches (305 mm) on center at or 2009 IRC Section R806.4, as applicable. the intermediate joists. Plywood joints must occur over 4.4.3.2.2 Crawl Spaces: In crawl spaces, Icynene joists. Icynene Classic or Classic Max insulation must be Classic Plus insulation may be spray-applied to vertical applied to the underside of the plywood deck between the walls and the underside of floors, as described in this joists to a depth of 5 inches (127 mm). Two layers of section. The thickness of the foam plastic applied to the minimum 5/8-inch-thick (15.9 mm), Type X gypsum underside of the floors must not exceed 14 inches wallboard must be attached perpendicular to the joists on (356 mm). The thickness of the spray foam plastic the ceiling side of the assembly. The first layer must be insulation applied to vertical wall surfaces must not exceed attached with 11/4-inch-long (32 mm), Type W drywall 8 inches (203 mm). The insulation must be covered with screws, spaced 24 inches (610 mm) on center. The DC-315 coating is described in Section 4.4.3.2.1. second layer must be applied perpendicular to the joists, 4.4.3.2.3 Use on Attic Floors: Icynene Classic Plus offset 24 inches(610 mm)from the base layer. The second layer must be attached with 2-inch-long (51 mm), Type S insulation may be installed at a maximum thickness of drywall screws spaced 12 inches (305 mm) on center. 13 inches (330 mm) between joists in attic floors. The Additional fasteners must be installed along the butt joints insulation must be separated from the interior of the of the second layer, securing the two layers together. building by an approved thermal barrier. The insulation These fasteners must be 11/2-inch-long (38 mm), Type G does not require an ignition barrier or a coating. drywall screws placed 2 inches (51 mm) back from each 4.5 One-hour Fire-resistance-rated Assemblies: end of the butt joint and spaced 12 inches (305 mm) on 4.5.1 Classic and Classic Max: center. The wallboard joints on the exposed side must be treated with paper tape embedded in joint compound and 4.5.1.1 Assembly 1 (Limited Load-bearing Wood Stud topped with an added coat of compound, and the fastener Wall): Minimum nominally 2-by-4 [11/2 by 31/2 inches heads must be coated with joint compound in accordance (38 mm by 89 mm)] southern pine (G = 0.55), No. 2 grade with ASTM C840 or GA-216. studs spaced 16 inches (406 mm) on center with a base 4.5.1.4 Assembly 4(Non-loadbearing Steel Stud Wall): layer of 1/2-inch-thick (12.7 mm) wood fiber sound board installed horizontally on each face with vertical joints Nominally 6-inch-deep (152.4 mm), No. 18 gage, located over the studs, attached with 6d box nails, 2 inches galvanized steel studs spaced 16 inches (406.4 mm) on center, are friction-fit into No. 18 gage galvanized steel (51 mm) long and spaced 24 inches (610 mm) on center floor and ceiling track with a layer of 5/8-inch-thick along the studs, and a second layer of 5/8-inch-thick (15.9 mm) Type X gypsum wallboard installed vertically on (15.9 mm),Type X gypsum board applied to the interior side with the long edge parallel to steel studs and secured each face, attached with 8d box nails, 21/2 inches (64 mm) using No. 6, 1'/4-inch-long (31.7 mm), self- drilling drywall long and spaced 7 inches (178 mm) on center along the screws spaced 8 inches (203 mm) on center around the studs. The stud cavity contains Icynene Classic or Classic ESR-1826 I Most Widely Accepted and Trusted Page 6 of 8 perimeter and 12 inches (305 mm) on center in the field. Optional: It is permitted to add code-complying EPS, ' The gypsum board joints must be treated with vinyl or XPS, foil-faced, rigid polyurethane board stock or casein, dry or premixed joint compound applied in two polyurethane spray foam on the exterior of the wall coats to cover all exposed screw heads and gypsum board (between the DensGlass sheathed wall and the brick), butt joints, and a minimum 2-inch-wide (51 mm) paper, while maintaining the 1-inch (25.4 mm) air space. The plastic, or fiberglass tape embedded in the first layer of length of the brick ties must be increased to account for the compound over butt joints of the gypsum board. The stud thickness of the insulation. cavity is filled with lcynene Classic or Classic Max 4.6 Exterior Walls in Type I, II, III and IV Construction: insulation up to 6 inches (152 mm) thick. DensGlass Exterior Sheathing, 1/2 inch (12.7 mm) thick, is installed 4.6.1 General: When used on exterior walls of Types I, II, parallel to steel studs with vertical joints offset a minimum III or IV construction, the assembly must comply with IBC of 16 inches (406 mm) from the vertical joints of the Section 2603.5 and this section, and the Classic, Classic gypsum board and the horizontal joints offset a minimum of Max and Classic Eco insulations must be installed at a 24 inches (610 mm) from the horizontal joints of the maximum thickness of 6 inches (152 mm). The potential gypsum board. The sheathing is attached using No. 6, heat of Icynene insulations tested in accordance with 1 /a-inch-long (31.7 mm), self-drilling drywall screws NFPA 259 is as follows: spaced 8 inches (203 mm) on center around the perimeter z and in the field. Hohmann & Barnard DW-10 brick ties, • Classic and Classic Max: 494 Btu/ft (5.6 MJ/m2) per 6 inches (152 mm) long by 11/2-inches (38 mm) wide, are inch of thickness spaced 16 inches (406.4 mm) on center vertically on each ■ Classic Eco: 168 Btu/ft2 (1.9 MJ/m2) per inch of steel stud, and secured, using two 15/8-inch-long (41.3 mm) thickness. self-drilling screws, through 4-inch (102 mm) red clay brick [31/2 inches (88.9 mm) by 21/4 inches (57.1 mm) by 4.6.2 Exterior Face: Nominally 6-inch-deep (152 mm), 73/4 inches (197 mm)] laid in a running bond pattern with No. 18 gage, galvanized steel studs spaced 16 inches Type S mortar, leaving a nominally 1-inch (25.4 mm) air (406 mm) on center, are fastened to No. 18 gage, gap between the brick and the exterior sheathing. galvanized steel floor and ceiling track using No. 8, Optional: It ispermitted to add code-complying, /a-inch-long (22.2 mm), self-tapping pan head framing p screws. GP DensGlass® Exterior Sheathing, /2 inch expanded polystyrene (EPS), extruded polystyrene (XPS), (12.7 mm) thick, is installed over the exterior side of steel foil-faced, rigid polyurethane board stock or polyurethane studs with the long end perpendicular to the steel studs, spray foa® on the exterior of the wall (between the using No. 6, Type S, 11/4-inch (31.7 mm) long, self-tapping DensGlass® sheathed wall and the brick), while bugle head screws spaced 8 inches (203 mm) on center maintaining the 1-inch (25.4 mm) air space. The length of around the perimeter and in the field. The stud cavity is the brick ties must be increased to account for the filled with Icynene Classic, Classic Max or Classic Eco thickness of the insulation. insulation to a nominal thickness of 6 inches(152 mm). 4.5.2 Classic Eco (Non-loadbearing Steel Stud Wall): 4.6.3 Interior Face: Type X gypsum board, 5/8 inches Nominally 6-inch-deep (152 mm) deep, No. 18 gage, (15.9 mm) thick, is installed with the long dimension galvanized steel studs spaced 16 inches (406 mm) on perpendicular to steel studs with No. 6, Type S, 11/4 inch- center, are friction-fit into No. 18 gage galvanized steel long (31.7 mm), self-tapping, bugle head screws spaced floor and ceiling track with a layer of 5/8-inch-thick 8 inches (203 mm) on center around the perimeter and in (15.9 mm), Type X gypsum board installed to the interior the field. The gypsum board joints must be treated with side with the long edge parallel to steel studs and secured vinyl or casein, dry or premixed joint compound applied in using No. 6, 11/4-inch-long (31.7 mm), self-drilling drywall two coats to cover all exposed screw heads and gypsum screws spaced 8 inches (203 mm) on center around the board butt joints, and a minimum 2-inch-wide (51 mm) perimeter and 12 inches (305 mm) on center in the field. paper, plastic, or fiberglass tape embedded in the first The gypsum board joints must be treated with vinyl or layer of compound over butt joints of the gypsum board. casein, dry or premixed joint compound applied in two coats to cover all exposed screw heads and gypsum board 4.6.4 Exterior Wall Covering: Details of the exterior wall butt joints, with a minimum 2-inch-wide (51 mm) paper, covering must be provided to the code official by the report plastic, or fiberglass tape embedded in the first layer of holder, designer or specifier, with an engineering analysis compound over butt joints of the gypsum board. The stud demonstrating that (1) the exterior wall covering conforms cavity is filled with lcynene Classic Eco insulation up to to ASTM E136 and (2) the addition of the wall covering to 6 inches (152 mm) thick. DensGlass ® Exterior Sheathing, the assembly described in this section does not negatively of the assembly conformance /2 inch (12.7 mm) thick, is installed parallel to steel studs affect with the requirements with vertical joints offset a minimum of 16 inches (406 mm) of IBC Section 2603.5. from the vertical joints of the gypsum board and the 5.0 CONDITIONS OF USE horizontal joints offset a minimum of 24 inches (610 mm) The Icynene Classic, Classic Max, Classic Eco and Classic from the horizontal joints of the gypsum board. The Plus spray-applied sheathing is attached using No. 6, 11/4-inch-long polyurethane foam plastic insulations (31.7 mm), self-drilling drywall screws spaced 8 inches described in this report comply with, or are suitable (203 mm) on center around the perimeter and in the field. alternatives to what is specified in, those codes listed in Hohmann & Barnard DW-10 brick ties, 6 inches (152 mm) Section 1.0 of this report, subject to the following long by 11/2 inches (38 mm) wide and spaced 16 inches conditions: (406 mm) on center vertically on each steel stud, are 5.1 This evaluation report and the manufacturer's secured, using two 15/8-inch-long (41.3 mm) self-drilling published installation instructions, when required by screws,through 4-inch (102 mm) red clay brick[31/2 inches the code official, must be submitted at the time of (88.9 mm) by 21/4 inches (57.1 mm) by 73/4 inches permit application. (197 mm)] laid in a running bond pattern with Type S 5.2 The insulation must be installed in accordance with mortar. A nominally 1-inch (25.4 mm) air gap is left the manufacturer's published installation instructions, between the brick and the exterior sheathing. this evaluation report and the applicable code. If there ESR-1826 I Most Widely Accepted and Trusted Page 7 of 8 is a conflict between the installation instructions and 6.7 Test report in accordance with NFPA 285, and related this report,this report governs. engineering analysis (Classic, Classic Max and 5.3 The insulation must be separated from the interior of Classic Eco). the building by an approved 15-minute thermal 6.8 Reports of tests in accordance with NFPA 259 barrier,except as noted in this report. (Classic, Classic Max and Classic Eco). 5.4 Since the performance of Classic Max, when installed 6.9 Reports of fire tests in accordance with ASTM E970 in unvented attics without a code-prescribed ignition (Classic, Classic Max and Classic Plus). barrier or an intumescent coating, is based on fire 6.10 For Classic Max, an engineering evaluation, including performance of an unvented attic, the installation full-scale fire testing, small-scale testing and fire must be approved by the code official as conforming with the provisions of Section 4.4.1.2.2 and modeling (Section 4.4.1.2.2). Conditions 1 to 5 of Section 4.4.1.2. 7.0 IDENTIFICATION 5.5 When Classic Max insulation is installed under All packages and containers of Classic, Classic Max, Section 4.4.1.2.2 of this report, a certificate must be Classic Eco and Classic Plus insulations must be labeled placed in the attic stating that the foam plastic with the Icynene, Inc., name and address; the product insulation has been installed in accordance with name; component designation (A or B); the flame spread Conditions 1 to 5 of Section 4.4.1.2 and the terms of index and the smoke-developed index; the shelf life Section 4.4.1.2.2 of ESR-1826; any alterations to the expiration date; the name of the inspection body (ICC-ES); attic or insulation must be consistent with those and the evaluation report number(ESR-1826). requirements. Intumescent coatings are identified with the 5.6 The insulation must not exceed the thicknesses and manufacturer's name and address, the product trade name densities noted in this report. and use instructions. 5.7 The insulation must be protected from the weather 8.0 OTHER CODES during and after application. 8.1 Scope: 5.8 The insulation must be applied by licensed dealers and installers certified by Icynene, Inc. In addition to the codes referenced in Section 1.0, the products recognized in this report were evaluated for 5.9 Use of the insulation in areas where the probability of compliance with the requirements of the following codes: termite infestation is "very heavy" must be in • 2006 International Building Code(2006 IBC) accordance with IRC Section R318.4 or IBC Section 2603.8, as applicable. • 2006 International Residential Codes(2006 IRC) 5.10 Jobsite certification and labeling of the insulation must • 2006 International Energy Conservation Code (2006 comply with IRC Sections N1101.4 and N1101.4.1 IECC) and IECC Sections 303.1.1 and 303.1.2, as applicable. 8.2 Uses: 5.11 A vapor retarder must be installed in accordance with The products comply with the above-mentioned codes as the applicable code. described in Sections 2.0 to 7.0 of this report, with the revisions noted below. 5.12 Icynene Classic, Classic Max, Classic Eco and • Application with a Prescriptive Ignition Barrier: See Classic Plus foam plastic insulations are Sections 4.4.1.1 (Classic and Classic Max) 4.4.2.1 manufactured in Mississauga, Ontario, Canada, under (Classic Eco) and 4.4.3.1 (Classic Plus), except attics a quality control program with inspections by ICC-ES. must be vented in accordance with 2006 IBC Section 6.0 EVIDENCE SUBMITTED 1203.2, and crawl space ventilation must be in 6.1 Data in accordance with the ICC-ES Acceptance accordance with 2006 IBC Section 1203.3, as Criteria for Spray-applied Foam Plastic Insulation applicable. Additionally, an ignition barrier must be (AC377), dated November 2012 (editorially corrected installed in accordance with 2006 IRC Section R314.5.3 April 2013). or R314.5.4, as applicable. • Application without a Prescriptive Ignition Barrier: 6.2 Reports of tests in accordance with AC377 Appendix See Sections 4.4.1.2 (Classic and Classic Max), 4.4.2.2 X [Classic and Classic Max (Section 4.4.1.2.1); (Classic Eco) and 4.4.3.2 (Classic Plus), except attics Classic Eco (Section 4.4.2.2.1) and Classic Plus must be vented in accordance with 2006 IBC Section (Sections 4.4.3.2.1 and 4.4.3.2.3)] and Appendix C 1203.2 or 2006 IRC Section R806, and crawl space [Classic and Classic Max (Section 4.4.1.2.3); and ventilation must be in accordance with 2006 IBC Section Classic Eco(Section 4.4.2.2.2)]. 1203.3 or 2006 IRC Section R408, as applicable. 6.3 Test reports on air leakage rate in accordance with • Jobsite Certification and Labeling: See Section 5.10, ASTM E283(Classic Eco). except jobsite certification and labeling must comply 6.4 Test report on air leakage rate in accordance with with 2006 IECC Sections 102.1.1 and 102.1.11, as ASTM E2178 (Classic, Classic Max and Classic applicable. Plus). • Protection Against Termites: See Section 5.9, except 6.5 Reports of room corner fire testing in accordance with use of the insulation in areas where the probability of NFPA 286 (Classic, Classic Max, Classic Eco, and termite infestation is "very heavy" must be in Classic Plus). accordance with 2006 IRC Section R320.5. 6.6 Test reports in accordance with ASTM E119 (Classic, Classic Max and Classic Eco). ESR-1826 I Most Widely Accepted and Trusted Page 8 of 8 • TABLE 1—THERMAL RESISTANCE(R-VALUES) R-VALUE(°F•ft2•h/Btu) THICKNESS Classic and Classic Max Classic Eco Classic Plus (inches) 1 3.7 3.7 4.0 2 7.4 7.4 8.0 3 11 11 12 3.5 13 13 14 4 14 14 16 5 18 18 20 5.5 20 20 22 6 22 22 24 7 25 25 28 7.5 27 27 30 8 29 29 32 9 32 32 36 9.5 34 34 38 10 36 36 40 11.5 41 41 42 13.5 — 49 54 14 50 50 56 For SI: 1 inch=25.4 mm, 1°F•ft2-h/Btu=0.176 110°K•m2/W. 1R-values are calculated based on tested K values at 1-and 3.5-inch thicknesses. 2R-values greater than 10 are rounded to the nearest whole number. OFFICE COPY FORM R405-2014 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: 4036 Merriam Builder Name: Cole Builders Street: 362 Plaza Rd. Permit Office: Atlantic Beach Bldg Dept City,State,Zip: Atlantic Beach, FL,32233 Permit Number: Owner: Merriam Residence Jurisdiction: 261100 Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types(4510.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame Wood,Exterior R=19.0 2690.00 ft2 b.Concrete Block-Int Insul, Exterior R=4.1 1300.00 ft2 3. Number of units,if multiple family 1 c. Frame-Wood,Adjacent R=19.0 370.00 ft2 4. Number of Bedrooms 4 d.other(see details) R= 150.00 ft2 5. Is this a worst case? No 10.Ceiling Types (2519.0 sqft.) Insulation Area a. Roof Deck(Unvented) R=20.0 2519.00 ft2 6. Conditioned floor area above grade(ft2) 4036 b. N/A R= ft2 Conditioned floor area below grade(ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(742.7 sqft.) Description Area a. Sup:Attic, Ret: 1st Floor,AH: 1st Floor 6 268.9 a. U-Factor: Dbl, U=0.28 742.67 ft2 b.Sup: Attic, Ret:2nd Floor,AH:2nd Floor 6 268.9 SHGC: SHGC=0.21 b. U-Factor N/A ft2 12. Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 42.0 SEER:15.00 b.Central Unit 42.0 SEER:15.00 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Heat Pump 43.0 HSPF:8.50 SHGC: b. Electric Heat Pump 43.0 HSPF:8.50 Area Weighted Average Overhang Depth: 8.851 ft. Area Weighted Average SHGC: 0.210 14. Hot water systems 8. Floor Types (4036.0 sqft.) Insulation Area a. Propane Tankless Cap: 1 gallons EF:0.590 a.Slab-On-Grade Edge Insulation R=0.0 1944.00 ft2 b. Conservation features b. Floor Over Other Space R=0.0 1517.00 ft2 None c.other(see details) R= 575.00 ft2 15.Credits Pstat Glass/Floor Area: 0.184 Total Proposed Modified Loads: 85.64 PASS Total Baseline Loads: 112.66 .......YYf..�,.. I hereby certify that the plans and specifications covered by Review of the plans and ...0.4... 11E STA-•-..•., this calculation are in compliance with the Florida Energy specifications covered by this ti;. = Oma,' Code. calculation indicates compliance ' >,, �+' with the Florida Energy Code. 'F. ,r 3�„�0 PREPARED BY: Before construction is completed .. 71 / ry .0? DATE: A, to f this building will be inspected for :_ o a• compliance with Section 553.908 , Florida Statutes. !' .may. C :'•a I hereby certify that thi building, as designed,is in compliance • with the Florida E ergy C e. • COD WEVtit• .'• OWNER/AGENT BUILDING OFFICIAL: illy DATE: /C/- /-r DATE: Ili -gi--/9 - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.2.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. - Compliance with a proposed duct leakage On requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with Section 803 of RESNET Standards, is not greater than 0.070 Can for whole house. 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2014 a ` PROJECT Title: 4036 Merriam Bedrooms: 4 Address Type: Street Address Building Type: User Conditioned Area: 4036 Lot# Owner: Merriam Residence Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Cole Builders Rotate Angle: 180 Street: 362 Plaza Rd. Permit Office: Atlantic Beach Bldg Dept Cross Ventilation: County: Duval Jurisdiction: 261100 Whole House Fan: City,State,Zip: Atlantic Beach, Family Type: Single-family FL, 32233 New/Existing: New(From Plans) Comment: CLIMATE V Design Location TMY SiteIECC Design Temp Int Design Temp Heating Design Daily Temp Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 2 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Block1 1944 19440 2 Block2 2092 20920 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 1st Floor 1944 19440 No 3 3 1 Yes Yes Yes 2 2nd Floor 2092 20920 Yes 2 1 1 Yes Yes Yes FLOORS ✓ # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio 1st Floor 234 ft 0 1944 ft2 ____ 0.4 0.4 0.2 2 Floor Over Other Space 2nd Floor ____ ____ 1517 ft2 0 0.5 0.4 0.1 3 Floor over Garage 2nd Floor ____ ____ 575 ft2 19 0.5 0.1 0.4 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Flat Gravel 2528 ft2 106 ft2 Medium 0.4 No 0.9 No 20 4.8 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 No attic Unvented 0 2519 ft2 N N 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2014 CEILING V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic(Unvented) 1st Floor 0 Blown 427 ft2 0.23 Wood 2 Under Attic(Unvented) 2nd Floor 0 Blown 2092 ft2 0.23 Wood WALLS / Adjacent Cavity Width Height Sheathing Framing Solar Below 1[_ # Ornt To __ Wall Type Space R-Value Ft In Ft in Area R-Value Fraction Absor_ Gradela 1 N=>S Exterior Frame-Wood 1st Floor 19 19 10 190.0 ft2 0.23 0.4 0 2 N=>S Exterior Concrete Block-Int Insul 1st Floor 4.1 18 10 180.0 ft2 0 0.4 0 3 E=>W Exterior Concrete Block-Int Insul 1st Floor 4.1 82 10 820.0 ft2 0 0.4 0 4 S=>N Exterior Concrete Block- Int Insul 1st Floor 4.1 17 10 170.0 ft2 0 0.4 0 5 W=>E Garage Concrete Block- Int Insul 1st Floor 4.1 15 10 150.0 ft2 0 0.01 0 6 S=>N Garage Frame-Wood 1st Floor 19 37 10 370.0 ft2 0.23 0.01 0 7 W=>E Exterior Concrete Block- Int Insul 1st Floor 4.1 13 10 130.0 ft2 0 0.4 0 8 W=>E Exterior Frame-Wood 1st Floor 19 43 10 430.0 ft2 0.23 0.4 0 9 N=>S Exterior Frame-Wood 2nd Floor 19 33 10 330.0 ft2 0.23 0.4 0 10 E=>W Exterior Frame-Wood 2nd Floor 19 70 10 700.0 ft2 0.23 0.4 0 11 S=>N Exterior Frame-Wood 2nd Floor 19 13 10 130.0 ft2 0.23 0.4 0 12 S=>N Exterior Frame-Wood 2nd Floor 19 30 10 300.0 ft2 0.23 0.4 0 13 W=>E Exterior Frame-Wood 2nd Floor 19 61 10 610.0 ft2 0.23 0.4 0 DOORS # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 S=>N Insulated 1st Floor None .46 3 8 24 ft2 WINDOWS Orientation shown is the entered orientation(=>)changed to As Built(rotated 180 degrees). Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N=>S 1 Vinyl Low-E Double Yes 0.28 0.21 48.0 ft2 16 ft 0 in 1 ft 0 in Drapes/blinds None 2 N=>S 2 Vinyl Low-E Double Yes 0.28 0.21 96.0 ft2 16 ft 0 in 1 ft 0 in Drapes/blinds None 3 E=>W 3 Vinyl Low-E Double Yes 0.28 0.21 10.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 4 E=>W 3 Vinyl Low-E Double Yes 0.28 0.21 8.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 5 E=>W 3 Vinyl Low-E Double Yes 0.28 0.21 26.7 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 6 E=>W 3 Vinyl Low-E Double Yes 0.28 0.21 24.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 7 E=>W 3 Vinyl Low-E Double Yes 0.28 0.21 18.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 8 S=>N 4 Vinyl Low-E Double Yes 0.28 0.21 18.0 ft2 5 ft 0 in 1 ft 0 in Drapes/blinds None 9 S=>N 4 Vinyl Low-E Double Yes 0.28 0.21 26.7 ft2 5 ft 0 in 1 ft 0 in Drapes/blinds None 10 W=>E 7 Vinyl Low-E Double Yes 0.28 0.21 8.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 11 W=>E 8 Vinyl Low-E Double Yes 0.28 0.21 26.7 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 12 W=>E 8 Vinyl Low-E Double Yes 0.28 0.21 8.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 13 N=>S 9 Vinyl Low-E Double Yes 0.28 0.21 72.0 ft2 16 ft 0 in 1 ft 0 in Drapes/blinds None 14 N=>S 9 Vinyl Low-E Double Yes 0.28 0.21 128.0 ft2 16 ft 0 in 1 ft 0 in Drapes/blinds None 15 E=>W 10 Vinyl Low-E Double Yes 0.28 0.21 66.7 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 16 E=>W 10 Vinyl Low-E Double Yes 0.28 0.21 18.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2014 ' WINDOWS Orientation shown is the entered orientation(=>)changed to As Built(rotated 180 degrees). Wall Overhang # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 17 S=>N 11 Vinyl Low-E Double Yes 0.28 0.21 36.0 ft2 4 ft 0 in 1 ft 0 in Drapes/blinds None 18 S=>N 12 Vinyl Low-E Double Yes 0.28 0.21 64.0 ft2 7 ft 0 in 1 ft 0 in Drapes/blinds None 19 W=>E 13 Vinyl Low-E Double Yes 0.28 0.21 10.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 20 W=>E 13 Vinyl Low-E Double Yes 0.28 0.21 12.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None 21 W=>E 13 Vinyl Low-E Double Yes 0.28 0.21 18.0 ft2 1 ft 0 in 1 ft 0 in Drapes/blinds None GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 575 ft2 384 ft2 43 ft 10 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000318 3363.3 184.64 347.25 .3012 5 HEATING SYSTEM V # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump Split HSPF:8.5 43 kBtu/hr 1 sys#1 2 Electric Heat Pump Split HSPF:8.5 43 kBtu/hr 2 sys#2 COOLING SYSTEM V # System Type - Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit Split SEER: 15 42 kBtu/hr 1260 cfm 0.75 1 sys#1 2 Central Unit Split SEER: 15 42 kBtu/hr 1260 cfm 0.75 2 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Propane Tankless 1st Floor 0.59 1 gal 60 gal 120 deg None SOLAR HOT WATER SYSTEM VFSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply--- Return Air CFM 25 CFM25 HVAC# V # Location R Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 268.9 ft 1st Floor 67.225 Proposed On 1st Floor ---cfm 136.1 cfm 0.07 0.50 1 1 2 Attic 6 268.9 ft 2nd Floor 67.225 Proposed On 2nd Floor ---cfm 146.4 cfm 0.07 0.50 2 2 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5 FORM R405-2014 TEMPERATURES Programable Thermostat:Y Ceiling Fans: CoolingJan Feb Mar A r r Ma [X:Jun Jul [X]Au (X Se Oct Nov Dec HeatinX Jan X]Feb X Mar Apr [ May [ Jun l Jul [ ]Aug [ SeOct X Nov l Dec VentingJan [ Feb X Mar XI Apr [[[ ]]]Ma [ Jun [ Jul [[[ 'Aug [ ]]]SepX Oct X Nov l Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 76 The lower the EnergyPerformance Index, the more efficient the home. 362 Plaza Rd., Atlantic Beach, FL, 32233 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame Wood, Exterior R=19.0 2690.00 ft2 b.Concrete Block-Int Insul, Exterior R=4.1 1300.00 ft2 3. Number of units,if multiple family 1 c. Frame-Wood,Adjacent R=19.0 370.00 ft2 4. Number of Bedrooms 4 d.other(see details) R= 150.00 ft2 10. Ceiling Types Insulation Area 5. Is this a worst case? No a. Roof Deck(Unvented) R=20.0 2519.00 ft2 6. Conditioned floor area(ft2) 4036 b. N/A R= ft2 7. Windows" Description Area c. N/A R= ft2 a. U-Factor: Dbl, U=0.28 742.67 ft2 11. Ducts R ft2 a. Sup:Attic, Ret: 1st Floor,AH: 1st Floor 6 268.9 SHGC: SHGC=0.21 b.Sup: Attic, Ret:2nd Floor,AH:2nd Floor 6 268.9 b. U-Factor: N/A ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 42.0 SEER:15.00 SHGC: b.Central Unit 42.0 SEER:15.00 d. U-Factor: N/A ft2 13. Heating systems kBtu/hr Efficiency SHGC: a. Electric Heat Pump 43.0 HSPF:8.50 Area Weighted Average Overhang Depth: 8.851 ft. b. Electric Heat Pump 43.0 HSPF:8.50 Area Weighted Average SHGC: 0.210 8. Floor Types Insulation Area 14. Hot water systems Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 1944.00 ft2 a. Propane EF:0.59 b. Floor Over Other Space R=0.0 1517.00 ft2 c.other(see details) R= 575.00 ft2 b. Conservation features None 15. Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building ,."""'"".,...„ Construction through the above energy saving features which will be installed (or exceeded) ••.,. pQ'�HE sTATF`'••, in this home before final inspection. Otherwise, a new EPL Display Card will be complet-d e3`;, .c, based on inst. o•- • pliant features. `rte `�•. Builder Signature Date: � (7 i i�* - two_e, a :� �/ i • r Address of New Home: �62 ?% le) City/FL Zip: ;�' \'4,c fig', o *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 Florida Department of Business and Professional Regulations Residential Whole Building Performance and Prescriptive Methods ADDRESS: 362 Plaza Rd. Permit Number: Atlantic Beach, FL,32233 MANDATORY REQUIREMENTS See individual code sections for full details. O 401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law [Section 553.9085, Florida Statues]requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate compliance for the building.A copy of the EPL display card can be found in Appendix C. O R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.1 through R402.4.4. O R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table 402.4.1.1,as applicable to the method of construction. Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 5 air changes per hour in Climate Zones 1 and 2,and 3 air changes per hour in Climate Zones 3 through 8.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals).Where required by the code official,testing shall be conducted by an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3. Interior doors,if installed at the time of the test,shall be open; 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Heating and cooling systems,if installed at the time of the test,shall be turned off;and 6. Supply and return registers,if installed at the time of the test,shall be fully open. O R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air. O R402.4.3 Fenestration air leakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 Us/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. O R402.4.4 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us)when tested in accordance with ASTM E 283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. • R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. • R403.2.2 Sealing(Mandatory)All ducts,air handlers,and filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts and plenum chambers,shall be constructed and sealed in accordance with Section C403.2.7.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria by post-construction or rough-in testing below. Duct tightness shall be verified by testing to Section 803 of the RESNET Standards by either an energy rater certified in accordance with Section 553.99, Florida Statutes,or as authorized by Florida Statutes,to be"substantially leak free"by either of the following: 1. Post-construction test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g. (25 Pa)across the entire system,including the manufacturer's air handler enclosure.All register boots shall be taped or otherwise sealed during the test. 2. Rough-in test:Total leakage shall be less than or equal to 4 cfm(113 L/min)per 100 square feet(9.29 m2)of conditioned floor area when tested at a pressure differential of 0.1 inches w.g.(25Pa)across the system,including the manufacturer's air handler enclosure.All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test,total leakage shall be less than or equal to 3 cfm (85 L/min)per 100 square feet(9.29 m2)of conditioned floor area. Exceptions: 1. The total leakage test is not required for ducts and air handlers located entirely within the building envelope. 2. Duct testing is not mandatory for buildings complying by Section R405 of this code. 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 1 of 3 FORM R405-2014 MANDATORY REQUIREMENTS - (Continued) ▪ R403.2.3 Building Cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. O R403.3 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3., R403.3.1 Protection of piping insulation. • R403.4.1 Circulating hot water systems(Mandatory). Circulating hot water systems shall be provided with an automatic or readily accessible manual switch that can turn off the hot-water circulating pump when the system is not in use. • R403.4.3 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 V2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. • R403.4.4 Water heater efficiencies(Mandatory). O R403.4.4.1 Storage water heater temperature controls ▪ R403.4.4.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). . R403.4.4.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water heating systems to be turned off. O R403.4.4.2 Water heating equipment. Water heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water heating category. Solar water heaters shall met the criteria Section R403.4.4.2.1. . R403.4.4.2.1 Solar water heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol,Collectors in installed solar water heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. p R403.5 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. p R403.6 Heating and cooling equipment(Mandatory). The following sections are mandatory for cooling and heating equipment. O R403.6.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This code does not allow designer safety factors,provisions for future expansion or other factors which affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. • R403.6.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load,but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.6,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Corn Page 2 of 3 FORM 8405-2014 MANDATORY REQUIREMENTS - (Continued) O R403.6.1.1 Cooling equipment capacity.(continued) The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing. Manufacture's expanded performance data shall be used to select cooling-only equipment.This selection shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower cfm provided by the expanded performance data, the design value for entering wet bulb temperature and the design value for entering dry bulb temperature. Design values for entering wet bulb and dry bulb temperature shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multi-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multi-family units,the capacity of equipment may be sized in accordance with good design practice. O R403.6.1.2 Heating equipment capacity ' R403.6.1.2.1 Heat pumps. Heat pumps sizing shall be based on the cooling requirements as calculated according to Section R403.6.1.1 and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load. ▪ R403.6.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.6.1. ' R403.6.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.6.1. O R403.6.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.7 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Commercial Provisions in lieu of Section R403. ❑ R403.8 Snow melt system controls(Mandatory). Snow and ice-melting systems,supplied through energy service to the building,shall include automatic controls capable of shutting off the system when the pavement temperature is above 55°F,and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F. ❑ R403.9 Swimming pools,inground spas and portable spas(Mandatory). The energy requirements for residential pools and inground spas shall be as specified in Sections R403.9.1 through R403.9.3 and in accordance with ANSI/APSP-15.The energy requirements for portable spas shall be in accordance with ANSI/APSP-14. O R403.9.1 Pool and spa heaters. All pool heaters shall be equipped with a readily accessible on-off switch that is mounted outside the heater to allow shutting off the heater without adjusting the thermostat setting. R403.9.1.1 Gas and oil-fired pool and spa heaters. All gas-and oil-fired pool and space heaters shall have a minimum ▪ thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013 when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural gas or LP gas shall not have continuously burning pilot lights. R403.9.1.2 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. O R403.9.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pumps according to a preset schedule shall be installed on all heaters and pumps. Heaters,pumps and motors that have built in timers shall be deemed in compliance with this equipment. Exceptions: ' 1. Where public health standards require 24-hour pump operations. 2. Where pumps are required to operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. O R403.9.3 Covers. Heated swimming pools and inground permanently installed spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Outdoor pools deriving over 70 percent of the energy for heating from site-recovered energy,such as a heat pump or ' solar energy source computed over an operating season. ❑ RR404.1 Lighting equipment(Mandatory). A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of permanently installed lighting fixtures shall contain only high efficacy lamps. Exception: Low-voltage lighting shall not be required to utilize high-efficacy lamps. O R404.1.1 Lighting equipment(Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights ❑ R405.2 Performance ONLY. All ducts not entirely inside the building thermal envelope shall be insulated to a minimum of R-6. O R405.2.1 Performance ONLY. Ceilings shall have minimum insulation of R-19.Where single assemby of the exposed deck and beam type or concrete deck roofs do not have sufficent space, R-10 is allowed. 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Com Page 3 of 3 FORM R405-2014 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: 4036 Merriam Builder Name: Cole Builders Street: 362 Plaza Rd. Permit Office: Atlantic Beach Bldg Dept City,State,Zip: Atlantic Beach, FL,32233 Permit Number: Owner: Merriam Residence Jurisdiction: 261100 Design Location: FL,Jacksonville COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air-permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Corners and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. 7/ Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. / Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. 7 Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or 7/ unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity / spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be / air tight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in / exterior walls,or insulation that on installation readily conforms to available space shall extend behind piping and wiring. / Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air / barrier installed separating them from the showers and tubs. 111 Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or / air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. / ,/Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have gasketed doors 6/26/2017 10:49 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 Manual S Com liance Re ort Job: 4036 Merriam P � Date: 6/26!17 1st System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Project Information For: Cole Builders Cooling Equipment Design Conditions Outdoor design DB: 92.7°F Sensible gain: 29781 Btuh Entering coil DB: 78.7°F Outdoor design WB: 77.1 °F Latent gain: 6739 Btuh Entering coil WB: 64.6°F Indoor design DB: 75.0°F Total gain: 36520 Btuh Indoor RH: 50% Estimated airflow: 1383 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC542A00300+FX4DNF043L Actual airflow: 1383 cfm Sensible capacity: 30060 Btuh 101% of load Latent capacity: 8840 Btuh 131% of load Total capacity: 38900 Btuh 107% of load SHR: 77% Heating Equipment Design Conditions Outdoor design DB: 32.5°F Heat loss: 33616 Btuh Entering coil DB: 67.4°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC542A00300+FX4DNF043L Actual airflow: 1383 cfm Output capacity: 42000 Btuh 125% of load Capacity balance: 28 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1383 cfm Output capacity: 6.6 kW 67% of load Temp. rise: 13 °F Meets are all requirements of ACCA Manual S. wri htsoft 2017-Jun-26 12:10:30 9 Right-Suite®Universal 2017 17.0.21 RSU10246 Page 1 �'Crk ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Air to Air Inc. Manual S Compliance Report Job: 4036 Merriam Date: 6/26/17 "Toia�.lir Coutitimir .Sblati.r"" 2 n nd System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Project Information For: Cole Builders Cooling Equipment Design Conditions Outdoor design DB: 92.7°F Sensible gain: 31519 Btuh Entering coil DB: 75.9°F Outdoor design WB: 77.1 °F Latent gain: 6593 Btuh Entering coil WB: 63.4°F Indoor design DB: 75.0°F Total gain: 38111 Btuh Indoor RH: 50% Estimated airflow: 1383 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC542A00300+FX4DNB043L Actual airflow: 1383 cfm Sensible capacity: 30060 Btuh 95% of load Latent capacity: 8840 Btuh 134% of load Total capacity: 38900 Btuh 102%of load SHR: 77% Heating Equipment Design Conditions Outdoor design DB: 32.5°F Heat loss: 45062 Btuh Entering coil DB: 68.1°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC542A00300+FX4DNB043L Actual airflow: 1383 cfm Output capacity: 42000 Btuh 93% of load Capacity balance: 35 °F Supplemental heat required: 3062 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1383 cfm Output capacity: 8.1 kW 61% of load Temp. rise: 25 °F Meets are all requirements of ACCA Manual S. Wr- 2017-Jun-2612:10:30 htsoft 1- 9 Right-Suite®Universal 2017 17.0.21 RSU10248 Page 2 ACCP. ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Pro ect Job: 4036 Merriam 1 Summary Date: 6/26/17 Entire House By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville, FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro'ect Information For: Cole Builders Notes: Merriam Residence 362 Plaza Rd. Atlantic Beach, FL. 32233 Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 Moisture difference 51 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 59383 Btuh Structure 42065 Btuh Ducts 13752 Btuh Ducts 16619 Btuh Central vent (135 cfm) 5543 Btuh Central vent (135 cfm) 2616 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 78678 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 61300 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 4506 Btuh Ducts 4151 Btuh Central vent (135 cfm) 4674 Btuh Heating Cooling Area(ft2) 4036 4036 Equipment latent load 8657 Btuh Volume (ft3) 40360 40360 Air changes/hour 0.28 0.15 Equipment total load 69957 Btuh Equiv.AVF (cfm) 188 101 Req. total capacity at 0.70 SHR 7.3 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 °F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. L wri9 htsoft 2017-Jun-26 12:10:30 �� Right-Suite®Universal 2017 17.0.21 RSU10246 Page 1 ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Cale=MJ8 Front Door faces: N Pro ect Summar Job: 4036 Merriam ' Air to Air Inca 1 y Date: 6/26/17 "Total Air Conditioning.Solutions" 1st System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro"ect Information For: Cole Builders Notes: Merriam Residence 362 Plaza Rd. Atlantic Beach, FL 32233 Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 % Moisture difference 51 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 23629 Btuh Structure 16265 Btuh Ducts 7315 Btuh Ducts 12255 Btuh Central vent (65 cfm) 2672 Btuh Central vent (65 cfm) 1261 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 33616 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipmenf sensible load 29781 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2287 Btuh Ducts 2199 Btuh Central vent (65 cfm) 2253 Btuh Heatin Cooling Outside air Area(ft2) 1944 1944 Equipment latent load 6739 Btuh Volume (ft3) 19440 19440 Air changes/hour 0.28 0.15 Equipment total load 36520 Btuh Equiv.AVF (cfm) 91 49 Req. total capacity at 0.70 SHR 3.5 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC542A00300 Gond 25HBC542A00300 AHRI ref 9155360 Coil FX4DNF043L AHRI ref 9155360 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 29050 Btuh Heating output 42000 Btuh @ 47°F Latent cooling 12450 Btuh Temperature rise 28 °F Total cooling 41500 Btuh Actual air flow 1383 cfm Actual air flow 1383 cfm Air flow factor 0.045 cfm/Btuh Air flow factor 0.048 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.82 Capacity balance point = 28 °F Backup: Input = 7 kW, Output = 22415 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2017-Jun-2612:10:30 9 Right-Suite®Universal 2017 17.0.21 RSU10246 Page 2 ACCk ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N • Project SummaryJob: 4036 Merriam Air to Air Inc. 1 Date: 6/26/17 "Twa/.tirc.liriaaixg.\bfntiexs" 2nd System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro'ect Information For: Cole Builders Notes: Merriam Residence 362 Plaza Rd. Atlantic Beach, FL 32233 Desi• n Information Weather: Jacksonville Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 33 °F Outside db 93 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 18 °F Daily range M Relative humidity 50 Moisture difference 51 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 35754 Btuh Structure 25800 Btuh Ducts 6436 Btuh Ducts 4364 Btuh Central vent (70 cfm) 2871 Btuh Central vent (70 cfm) 1355 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 45062 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 31519 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2219 Btuh Ducts 1953 Btuh Central vent (70 cfm) 2421 Btuh Heating Cool i ng Outside air Area(ft2) 2092 2092 Equipment latent load 6593 Btuh Volume (ft3) 20920 20920 Air changes/hour 0.28 0.15 Equipment total load 38111 Btuh Equiv.AVF (cfm) 98 52 Req. total capacity at 0.70 SHR 3.8 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC542A00300 Cond 25HBC542A00300 AHRI ref 9155360 Coil FX4DNB043L AHRI ref 9155360 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 29050 Btuh Heating output 42000 Btuh @ 47°F Latent cooling 12450 Btuh Temperature rise 28 °F Total cooling 41500 Btuh Actual air flow 1383 cfm Actual air flow 1383 cfm Air flow factor 0.033 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.83 Capacity balance point = 35 °F Backup: Input= 8 kW, Output= 27586 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. WI'1 hts frt 2017-Jun-26 12:10:30 ACC*, ...R Right-Suite®Universal 2017 17.0.21 RSU10246 Page 3 ..R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Air to Air Inc. Right-J® Worksheet Job: 4036 Merriam ' -T.alAir",. 4 "`.ms Entire House Date: 6/26/17 By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville, FL 32225 Phone:904-278-1722 Fax:904-262-0772 1 Room name Entire House 1st System 2 Exposed wall 442.0 ft 235.0 ft 3 Room height 10.0 ft 10.0 ft 4 Room dimensions 5 Room area 4036.0 ft2 1944.0 ft2 Ty Construction U-value Or HTM Area (tt2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuhift2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VI L- 12E-Osw 0.068 n 2.55 1.43 700 356 908 511 370 226 576 324 G 3A-2ov 0.280 n 10.50 18.62 344 0 3612 6406 144 0 1512 2681 W 12E-Osw 0.068 e 2.55 1.43 1520 1348 3437 1934 820 733 1869 1052 t--C 3A-2ov 0.280 e 10.50 35.10 172 0 1806 6037 87 0 914 3053 11 W 13A-flocs 0.143 s 5.36 2.72 600 455 2440 1236 170 125 670 340 L- G 3A-2ov 0.280 s 10.50 19.51 145 255 1523 2829 45 79 473 878 Vr13A-flocs 0.143 w 5.36 2.72 1170 1087 5829 2953 560 517 2772 1405 G 3A-2ov 0.280 w 10.50 35.10 83 0 872 2913 43 0 452 1509 112E-Osw 0.068 - 2.55 0.86 370 346 882 299 370 346 882 299 D 1100 0.390 ne 14.62 11.78 24 24 351 283 24 24 351 283 P 13A-4ocs 0.143 - 5.36 1.66 150 150 804 249 150 150 804 249 C 18B-10z1 0.076 ne 2.85 2.71 2519 2519 7179 6835 427 427 1217 1159 F 19A-Obscp 0.295 - 4.16 1.96 1517 1517 6304 2976 0 0 0 0 F 20P-19c 0.050 - 1.88 0.68 575 575 1078 394 0 0 0 0 F 22A-tpl 0.989 - 37.09 0.00 1944 394 14598 0 1944 200 7403 0 6 c)AED excursion 0 0 Envelope loss/gain 51623 35853 19895 13231 12 a) Infiltration 7760 1962 3734 944 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 5 1150 3 690 Appliances/other 3100 1400 Subtotal(lines 6 to 13) 59383 42065 23629 16265 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 59383 42065 23629 16265 15 Duct loads 23% 40% 13752 16619 31% 75% 7315 12255 Total room load 73135 58684 30944 28520 Air required(cfm) 2766 2766 1383 1383 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. w r ig h tsoft 2017-Jun-26 12:10:30 ACOA Right-Suite®Universal 2017 17.0.21 RSU10246 P 1 ...R\Public\Amy\Cole Builders`A036 Merriam Res.rup Calc=MJ8 Front Door faces: N Air to Air Inc. Right-J® Worksheet Job: 4036 Merriam "'Taint Air` tim'ogS'olu"°°'" Entire House Date: 6/26/17 By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville. FL 32225 Phone:904-278-1722 Fax:904-262-0772 1 Room name 2nd System 2 Exposed wall 207.0 ft 3 Room height 10.0 ft 4 Room dimensions 5 Room area 2092.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh'ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N'P,S Heat Cool Gross N`P S Heat Cool 6 W 12E-Osw 0.068 n 2.55 1.43 330 130 332 187 I G 3A-2ov 0.280 n 10.50 18.62 200 0 2100 3724 14/ 12E-Osw 0.068 e 2.55 1.43 700 615 1568 882 L-.G 3A-2ov 0.280 e 10.50 35.10 85 0 893 2983 11 W 13A-4ocs 0.143 s 5.36 2.72 430 330 1770 897 Imo; 3A-2ov 0.280 s 10.50 19.51 100 176 1050 1951 '4/ 13A-4ocs 0.143 w 5.36 2.72 610 570 3057 1549 G 3A-2ov 0.280 w 10.50 35.10 40 0 420 1404 12E-Osw 0.068 - 2.55 0.86 0 0 0 0 D 11 DO 0.390 ne 14.62 11.78 0 0 0 0 P 13A-4ocs 0.143 - 5.36 1.66 0 0 0 0 C 18B-10z1 0.076 ne 2.85 2.71 2092 2092 5962 5676 F 19A-Obscp 0.295 - 4.16 1.96 1517 1517 6304 2976 F 20P-19c 0.050 - 1.88 0.68 575 575 1078 394 F 22A-tpl 0.989 - 37.09 0.00 0 194 7195 0 6 c)AED excursion 0 Envelope loss/gain 31728 22622 12 a) Infiltration 4026 1018 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 2 460 Appliances/other 1700 Subtotal(lines 6 to 13) 35754 25800 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 35754 25800 15 Duct loads 18% 17% 6436 4364 Total room load 42190 30164 Air required(cfm) 1383 1383 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2017-Jun-26 12:10:30 RCCA Right-Suite®Universal 2017 17.0.21 RSU10246 Page 2 ...R\Public\Amy\Cole Builders'\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Air to Air Inc Right-J® Worksheet Job: 4036 Merriam 'lied Air Coorfeiocieerg VaM(1•10- 1st System Date: 6/26/17 By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville, FL 32225 Phone:904-278-1722 Fax:904-262-0772 1 Room name 1st System 1st Floor 2 Exposed wall 235.0 ft 235.0 ft 3 Room height 10.0 ft 10.0 ft heat/cool 4 Room dimensions 1944.0 x 1.0 ft 5 Room area 1944.0 ft2 1944.0 ft2 Ty Construction U-value Or HTM Area (tt2) Load Area (tt2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 14! 12E-Osw 0.068 n 2.55 1.43 370 226 576 324 370 226 576 324 G 3A-2ov 0.280 n 10.50 18.62 144 0 1512 2681 144 0 1512 2681 12E-Osw 0.068 e 2.55 1.43 820 733 1869 1052 820 733 1869 1052 3A-2ov 0.280 e 10.50 35.10 87 0 914 3053 87 0 914 3053 11 W 13A-4ocs 0.143 s 5.36 2.72 170 125 670 340 170 125 670 340 3A-2ov 0.280 s 10.50 19.51 45 79 473 878 45 40 473 878 V� 13A-4ocs 0.143 w 5.36 2.72 560 517 2772 1405 560 517 2772 1405 G 3A-2ov 0.280 w 10.50 35.10 43 0 452 1509 43 0 452 1509 F 12E-Osw 0.068 - 2.55 0.86 370 346 882 299 370 346 882 299 f D 11D0 0.390 ne 14.62 11.78 24 24 351 283 24 24 351 283 P 13A-4ocs 0.143 - 5.36 1.66 150 150 804 249 150 150 804 249 C 18B-10z1 0.076 ne 2.85 2.71 427 427 1217 1159 427 427 1217 1159 F 19A-Obscp 0.295 - 0.00 0.00 0 0 0 0 0 0 0 0 F 20P-19c 0.050 - 0.00 0.00 0 0 0 0 0 0 0 0 F 22A-tpl 0.989 - 37.09 0.00 1944 200 7403 0 1944 200 7403 0 6 c)AED excursion 0 0 Envelope loss/gain 19895 13231 19895 13231 12 a) Infiltration 3734 944 3734 944 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 3 690 3 690 Appliances/other 1400 1400 Subtotal(lines 6 to 13) 23629 16265 23629 16265 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 23629 16265 23629 16265 15 Duct loads 31% 75% 7315 12255 31% 75% 7315 12255 Total room load 30944 28520 30944 28520 Air required(cfm) 1383 1383 1383 1383 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft ,... 2017-Jun-26 Right-Suite®Universal 2017 17.0.21 RSU10246ACCA Page 3 ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Air di Air Inc. Right-J® Worksheet Job: 4036 Merriam r.04ir`_°.dit,.,.u8'au" 2nd System DBate.v JH6/17 Air to Air, Inc. 11578 Davis Creek Court.Jacksonville. FL 32225 Phone:904-278-1722 Fax:904-262-0772 1 Room name 2nd System 2nd Floor 2 Exposed wall 207.0 ft 207.0 ft 3 Room height 10.0 ft 10.0 ft heat/cool 4 Room dimensions 2092.0 x 1.0 ft 5 Room area 2092.0 ft2 2092.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (BtutVft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 41 12E-Osw 0.068 n 2.55 1.43 330 130 332 187 330 130 332 187 G 3A-2ov 0.280 n 10.50 18.62 200 0 2100 3724 200 0 2100 3724 W L- 12E-Osw 0.068 e 2.55 1.43 700 615 1568 882 700 615 1568 882 � 3A-2ov 0.280 e 10.50 35.10 85 0 893 2983 85 0 893 2983 11 w, 13A-4ocs 0.143 s 5.36 2.72 430 330 1770 897 430 330 1770 897 L-G 3A-2ov 0.280 s 10.50 19.51 100 176 1050 1951 100 88 1050 1951 V� 13A-4ocs 0.143 w 5.36 2.72 610 570 3057 1549 610 570 3057 1549 I G 3A-2ov 0.280 w 10.50 35.10 40 0 420 1404 40 0 420 1404 12E-Osw 0.068 - 0.00 0.00 0 0 0 0 0 0 0 0 D 11 DO 0.390 ne 0.00 0.00 0 0 0 0 0 0 0 0 P 13A-4ocs 0.143 - 0.00 0.00 0 0 0 0 0 0 0 0 C 18B-10zl 0.076 ne 2.85 2.71 2092 2092 5962 5676 2092 2092 5962 5676 F 19A-06scp 0.295 - 4.16 1.96 1517 1517 6304 2976 1517 1517 6304 2976 F 20P-19c 0.050 - 1.88 0.68 575 575 1078 394 575 575 1078 394 F 22A-tpl 0.989 - 37.09 0.00 0 194 7195 0 0 194 7195 0 6 c)AED excursion 0 0 Envelope loss/gain 31728 22622 31728 22622 12 a) Infiltration 4026 1018 4026 1018 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 2 460 Appliances/other 1700 1700 Subtotal(lines 6 to 13) 35754 25800 35754 25800 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 35754 25800 35754 25800 15 Duct loads 18% 17% 6436 4364 18% 17% 6436 4364 Total room load 42190 30164 42190 30164 Air required(cfm) 1383 1383 1383 1383 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. iOGP. -+- wrightsoft 2017-Jun-26 12:10:30 Right-Suite®Universal 2017 17.0.21 RSU10246 Page 4 ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N BuildingAnalysis Job: 4036 Merriam ' Air to Air Inc Y Date: 6/26/17 ,•Toldt lir Conditioninq.Sulutions" Entire House By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro'ect Information For: Cole Builders Desi• n Conditions Location: Indoor: Heating Cooling Jacksonville Intl AP, FL, US Indoor temperature(°F) 70 75 Elevation: 33 ft Design TD (°F) 38 18 Latitude: 30°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/lb) 11.0 51.2 Dry bulb(°F) 33 93 Infiltration: Daily range (°F) - 18 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heatin• Component Btuh/ft2 Btuh %of load Wails 3.8 14301 18.2 Ventilation Glazing 10.5 7812 9.9 walls Doors 14.6 351 0.4 DuctsCeilings 2.8 7179 9.1 azFloors 5.4 21980 27.9 Gig Infiltration 1.9 7760 9.9 aver Ducts 13752 17.5 Infiltration Piping 0 0 Ceilings Humidification 0 0 Ventilation 5543 7.0 Floors Adjustments 0 Total 78678 100.0 Coolin • Component Btuh/ft2 Btuh %of load Walls 1.9 7182 11.7 Walls Ventilation Glazing 24.4 18184 29.7 Internal Gains Doors 11.8 283 0.5 Ceilings 2.7 6835 11.1 Floors 0.8 3369 5.5 Infiltration 0.5 1962 3.2 Glazing___- Ducts Ducts 16619 27.1 Ventilation 2616 4.3 Internal gains 4250 6.9 Blower 0 0 Adjustments 0 Otngr.. Infiltration Total 61300 100.0 ceilings Floors Latent Cooling Load= 8657 Btuh Overall U-value= 0.150 Btuh/ft2-°F Data entries checked. .� wrightsoft 2017-Jun-2612:10:31 Right-Suite®Universal 2017 17.0.21 RSU10246 Page 1 AC ...R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N ` • Analysis Job: 4036 Merriam 'r to.Air Inc Building Y Date: 6/26/17 iirc »on,- 1st System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro'ect Information For: Cole Builders Desi• n Conditions Location: Indoor: Heating Cooling Jacksonville Intl AP, FL, US Indoor temperature (°F) 70 75 Elevation: 33 ft Design TD (°F) 38 18 Latitude: 30°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 11.0 51.2 Dry bulb (°F) 33 93 Infiltration: Daily range (°F) - 18 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heatin• Component Btuh/ft2 Btuh %of load Walls 3.6 7575 22.5 Ventilation Glazing 10.5 3350 10.0 Walls Doors 14.6 351 1.0al Ducts Ceilings 2.8 1217 3.6 Floors 3.8 7403 22.0 Infiltration 1.9 3734 11.1 Glazing- Ducts 7315 21.8 Piping 0 0 Other CeilingsInfiltration Humidification 0 0 Ventilation 2672 7.9 Floors Adjustments 0 Total 33616 100.0 Coolin • Component Btuh/ft2 Btuh % of load Walls 1.7 3668 12.3 Walls Ventilation Glazing 25.5 8122 27.3 Internal Gains Doors 11.8 283 0.9 Ceilings 2.7 1159 3.9 Floors 0 0 0 Infiltration 0.5 944 3.2 Glazing.__ Ducts 12255 41.1 Ventilation 1261 4.2 Internal gains 2090 7.0 Ducts Blower 0 0 Adjustments 0 8tr Total 29781 100.0 of Uration Latent Cooling Load = 6739 Btuh Overall U-value = 0.110 Btuh/ft2-°F Data entries checked. .t -+ wrightsoft 2017-Jun-2612:10:31 Right-Suite®Universal 2017 17.0.21 RSU10246ACCk p 2 ..R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N Job: 4036 Air to Air Inc. Building Analysis Date: 6/26/17Merriam ' "Total Iireundili iulinns.. 2nd System By: JH Air to Air, Inc. 11578 Davis Creek Court,Jacksonville,FL 32225 Phone:904-278-1722 Fax:904-262-0772 Pro'ect Information For: Cole Builders Desi• n Conditions Location: Indoor: Heating Cooling Jacksonville Intl AP, FL, US Indoor temperature (°F) 70 75 Elevation: 33 ft Design TD (°F) 38 18 Latitude: 30`N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference(grub) 11.0 51.2 Dry bulb(CF) 33 93 Infiltration: Daily range (°F) - 18 ( M ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heatin• Component Btuh/ft2 Btuh %of load Walls 4.1 6726 14.9 Walls ventilation Glazing 10.5 4163 9.9 Ducts Doors 0 0 0 Ceilings 2.8 5962 13.2 Glazing Floors 7.0 14577 32.3 Infiltration Infiltration 1.9 4026 8.9 Ducts 6436 14.3 Ceilings Piping 0 0 Humidification 0 0 Ventilation 2871 6.4 Floors Adjustments 0 Total 45062 100.0 Coolin • Component Btuh/ft2 Btuh %of load Walls 2.1 3514 11.1 Walls Ventilation Glazing 23.7 10062 31.9 Internal Gains Doors 0 0 0 Ceilings 2.7 5676 18.0 110 Ducts Floors 1.6 3369 10.7 Infiltration 0.5 1018 3.2 Ducts 4364 13.8 Glazing___ Infiltration Ventilation 1355 4.3 Internal gains 2160 6.9 Floors Blower 0 0 Adjustments 0 Total 31519 100.0 Ceilings Latent Cooling Load= 6593 Btuh Overall U-value= 0.180 Btuh/ft2-°F Data entries checked. wrightsoft 2017-Jun-26 12:10:31 A Right-Suite®Universal 2017 17.0.21 RSU10246 Page 3 ..R\Public\Amy\Cole Builders\4036 Merriam Res.rup Calc=MJ8 Front Door faces: N i MARK MACCO !....-1 ARCHITECTS NOVANI VE COMMERCIAL AND RE910EN7IAL DESIGN 501.11710748 Alb OSCEOLA AVENUE ' IALR.9ONV,LLE BEACH Ft 37280 E.I 4 T 245 RN NON x N4AR CN R1xN) 9 ppm MACCMRCNITECTS.rom 8>m Mk XV r•r r-r .• x • • ,.• r,f-1. r ,-T 11 7 In 60101.110.01104.1. r.r I , t 101 I 1 111 r rA�' © :t MARK MACCO,AIA O1 r. eNE.., II!PIII.,�s�1� � 1 NCARB --M IMM.TDMr9Aw, C.® ?'� RARIOARMOISiM1fOM SAMSON I — t:11( ) 0i so 2 r.rI _ ,. _ —1 r., No. Desaipt on Date ti' A.!!, 1 - - _ O• M .,e ,� t , Iwv M.. t. e;Ns9 n.mnoA..«o M tea, . I gays ► RT L il�.. _ ;O 01 .•. -T" ' -M r.r r.r PROVIDE ..\,-w . .?` 1v,,Iq`���/ „ C,MK ._ r \ ,tt. y�i r� I �a O 41 ' C� ... 1 .7., IIIIII ''"''tia.4b„, ..., , II*I - VP :y o . _ _ .:. 11)1 + MOM. 1. �) MAIM Moor ; O '6, Gry .�t ®' O, W•31/14.11- IMO. .4 OA i=:�1 • - . ..MOM -!".. i1. --••---------,--1 j ; , ®: °_ ` �� MERRIAM1IIII i` _- - . RESIDENCE Eli o ' - 97 !CPDuct Sized per ASHRAE Standards. 2ND FLOOR 1.1 __ ---___-- Friction Loss -./6 PLAN Static - fg Total CFA's -/ MNwu,« , mRa Num.,M, AlriMtll xM Duct Sizes shown in X Length. a,, ,garr os.ts.2on 04 O 9'�QNO FLOOR TEL - R C M 7804.0mmompoRp 0.4407.4744„ °"'^M €N. •I0 uctu W.,.•01 VI.ula. C-CFM's on Drawing OM.001911011 `"'.'M_ Checker ..«so.NNNroa. = .,.,., -,,, A 201 R i / ' — ..R.a. .�'Nn`L:a` 1l4.,.1.0" ❑MARK MACCO ARCHITECTS NE,OVAnVE CO.IMCACIAL AND SEENENTULL DESION SOLUTIONS QEO.CEO.AAVENUE LKKKONMI.LE OF-ACK A 32250 a f6MImMG....a..m 0 PK DX 2A►01101 one ..=JIAO W YyCMIK TS...m r.r ll Mal II. •-. 7.:r7r..1,. r-f !-f r-r 1.11. _ n•r a P.. I.I .ean.a KAKOTA ,I.II I {1.1.11.151 II IL MAIM . p O O O I 0 to Ill I I .��I+.ILT !UMW/IMAMA' �— I I' , o an 9 (-41.5,,,10 ceD Ai 0 MI —1* ..iAMiY EM WI, II -ry J I -O �r \O • . r a �';t� • MARK MACCO,AIA Iw.MNNN. „'■'® O�/L�� /N� — � • 1.n,.«..M�. .:►:� NCARB \ C • I �'Il,_r^140 ® J a rLaInA EEwrnAnoN.fANSaw A SIMI---1.1� , illi o o /I� ::• _ 'I N MI WO I No. Description Date r® o. cit _ . ' It I 1 �Q ■ Vi L o - li`IMTN ollr,l! o' Spyit,:, . `=M ■r "" E.....i� Ly:,. .�.:-` <_NMI. "' � A ® Duct Sized per ASH$AE Standards. © !-r !.f Friction Loss -, / * MERRIAM - — - M n. Static Z? -�--M-- Total CFM's - /2 - 6 RESIDENCE I I Duct Sizes shol,N7 in Area X Length. ,EN,N.. ak C 07,7"3°" FM's on DraL w ng FIRST FLOOR var PLAN WALL LEGEND PM.e N..... *MN ® mar A.rr MX .N.w..M».a ® "" .Nf S..M.A 0 a ..�is .... 0E19.zon A.. ...r.1O+`MYm.»... prim n mwnLn' fR : "" w.:lmD...q MWM : " E' O .nS. S.m KM!ma o Mr....... M•117.1.011.111011.1,04. char 4, MWM VISIlli ...�.f...MM . s � A 200 .1:M.m..MOI OFFICE COPY TRINITY ERD APPENDIX 1:ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE Table Deck Application Type Description Page 1A Wood New,Reroof(Tear-Off),Recover C-1 Mechanically Attached Insulation,Bonded Roof Cover 4 1B Wood New,Reroof(Tear-Off),Recover D-1 Insulated,Mechanically Attached Roof Cover 4 1C Wood New,Reroof(Tear-Off),Recover D-3 Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 4 10 Wood New,Reroof(Tear-Off),Recover E-1 Non-Insulated,Mechanically Attached Roof Cover 5 1E Wood New,Reroof(Tear-Off),Recover E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 5 1F Wood New Construction F Non-Insulated,Bonded Roof Cover 5 2A Steel or Structural Concrete New,Reroof(Tear-Off),Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 6-7 2B Steel or Structural Concrete New,Reroof(Tear-Off),Recover C-1 Mechanically Attached Insulation,Bonded Roof Cover 8-9 2B Steel New,Reroof(Tear-Off),Recover C-2 Mechanically Attached Insulation,Plate-Bonded Roof Cover 10 2D Steel or Structural Concrete New,Reroof(Tear-Off),Recover D-1 Insulated,Mechanically Attached Roof Cover 11-14 2E Steel or Structural Concrete New,Reroof(Tear-Off),Recover D-2 Insulated,Mechanically Attached Roof Cover(RUSS Strips) 15 3A Structural Concrete New,Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 16-17 3B Structural Concrete New,Reroof(Tear-Off),Recover C-2 Mechanically Attached Insulation,Plate-Bonded Roof Cover 17-18 3C Structural Concrete New,Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 18 4A LWIC New,Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 19 4A-1 LWIC over Steel New,Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 19 4A-2 LWC over Structural Concrete New,Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 20 5A Gypsum Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 21 6A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 22 6B Steel Recover C-2 Mechanically Attached Insulation,Plate-Bonded Roof Cover 23 6C Steel Recover D-1 Insulated,Mechanically Attached Roof Cover 24 6D Steel or Structural Concrete Recover E Non-Insulated,Mechanically Attached Roof Cover 25 6E Various Recover F-2 New LWC over Existing Roof,Bonded Roof Cover 26 The following notes apply to the systems outlined herein: 1, The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction, Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Unless otherwise noted,fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements: > Wood Deck: Mule-Hide Drill Point Fastener or Mule-Hide HDP Fastener with Mule-Hide 3 in.Insulation Plate. Minimum%-Inch steel penetration,engage the top flute of the steel deck > Steel Deck: Mule-Hide Drill Point Fastener or Mule-Hide HDP Fastener with Mule-Hide 3 in.Insulation Plate. Minimum%-inch steel penetration,engage the top flute of the steel deck. > Structural Concrete: Mule-Hide HOP Fastener or Mule-Hide Fluted Concrete Nail with Mule-Hide 3 in.Insulation Plate,Minimum 1-inch embedment. Fasteners installed with a pilot hole in accordance with the fastener manufacturer's published installation instructions. 3. Unless otherwise noted,insulation may be any one layer or combination of polyisocyanurate,polystyrene,fiberboard,perlite and/or gypsum-based Insulation board that meets the QA requirements of F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover. 4. Minimum 200 psi,minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type C-2(plate bonded roof cover)or Type D(mechanically attached membrane), whereby the membrane fasteners are installed through the LWIC to engage the structural steel or concrete deck, The structural deck shall be of equal or greater type,thickness and strength to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. Exterior Research and Design,LLC.d/b/a Trinity)ERD Evaluation Report M15060.06.09-R4 for FL12772-R4 Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION;Mule-Hide TPO-c Single Ply Roof Systems Revision 4:04/03/2017 Prepared by: Robert Nieminen,PE-59166 Mule-Hide Products Co.,Inc.;(608)365-3111 Appendix 1,Page 1 of 26 TRINITY ERD 5. Preliminary Insulation attachment for System Type D: Refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29(January 2016). 6. Unless otherwise noted,insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application;the ribbons/beads shall expand as noted in the manufacturer's published instructions: > Mule-Hide Helix'Low-Rise Adhesive(HELIX): Continuous%to 1-inch wide beads,12-inch o.c. ICP Adhesives CR-20: Continuous 2''/to 3%:-inch wide ribbons,12-inch o.c. OlyBond 500(OB-500): Continuous'''4 to 1-inch wide ribbons,12-inch o.c.using PaceCart or SpotShot application devices. > Note: When multiple layers(s)of insulation and/or coverboard are installed in ribbon-applied adhesive,adhesive ribbons shall be staggered from layer-to-layer a distance of one-half the ribbon spacing. > Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. 7. Unless otherwise noted,all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure(MOP)limitations. In no case shall these values be used to'increase'the MDP listings in the tables;rather if MDP listing below meets or exceeds that listed for a particular system in the tables,then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table: > ICP Adhesives CR-20: MDP -117.5 psf (Min.1.0-Inch thick) > OlyBond 500(0B500): MDP -315.5 psf (Min.0.5-inch thick Poly ISO 1,H-Shield or ENRGY 3) > OlyBond 500(0B500): MPD -487.5 psf (Min.0.5-inch thick Poly ISO 2 or ACFoam II) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD-1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 or Roofing Application Standard RAS 137. Assemblies marked with an asterisk" carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29(January 2016)for Zone 2/3 enhancements. 10. For assemblies with all components fully bonded in place,the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16,and no rational analysis is permitted. 11. For mechanically attached components over existing decks,fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12. For existing substrates in a bonded recover or re-roof installation,the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive,and the existing roof system(for recover)shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction,as documented through field uplift testing In accordance with ANSI/SPRI IA-1,ASTM E907,FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For System Type D,steel deck applications,the roof membrane shall be run with Its length perpendicular to the steel deck flutes. 14. For Recover Applications using System Type C-2(Plate Bonded Roof Cover)or Type D(Mechanically Attached Roof Cover),the insulation Is optional. Alternatively,min.0.5-inch HP Recovery Board,Poly ISO 1-HD,H- Shield HD or SecurShield HD or min.0.25-inch to 0.625-inch Dens Deck,Dens Deck Prime,SECUROCK Gypsum-Fiber Roof Board or SECUROCK Glass-Mat Roof Board or min.3/8-Inch Insulfoam R-Tech EPS or Fan-Fold may be used as a separator board,preliminarily attached prior to roof cover installation. The separator component shall be documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when installed with the roof cover in Recover applications. 15. Lightweight Insulating Concrete(LWC)shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced,refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced,the minimum design mix shall be 300 psi. In all cases,the minimum top-coat thickness is 2-inches. For LWC over structural concrete,reference Is made to FBC Section 1917.4.1,Point 1. Exterior Research and Design,LLC.d/b/a Trinity)ERD Evaluation Report M15060.06.09-R4 for FL12772-R4 Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION;Mule-Hide TPO-c Single Ply Roof Systems Revision 4:04/03/2017 Prepared by: Robert Nieminen,PE-59166 Mule-Hide Products Co.,inc.;(608)365-3111 Appendix 1,Page 2 of 26 TRINITY ERD 16. For adhered membrane systems,side laps shall be minimum 2-inch wide sealed with min.1.5-inch heat weld. Unless otherwise noted,membrane adhesive application rates are as follows: Membrane Adhesive Method Rate Mule-Hide TPO-c Mule-Hide TPO-c Bonding Adhesive(TPO-c BA) Contact(both sides) 60 ft2/gal Mule-Hide TPO-c Aqua Base 120 BA Contact(both sides) 120 ft2/gal Mule-Hide TPO-c Fleece Back Aqua Base 120 BA Wet lay(substrate) 120 ft'/gal Mule-Hide TPO-c Fleece Back Mule-Hide Helix°Low-Rise Adhesive(HELIX) Wet lay(substrate) FULL=continuous ribbons,maximum 4-inch o.c. 17. For membrane systems attached using TPO 10-inch Pressure-Sensitive RUSS,the underside of the membrane which comes in contact with the tape shall be primed with HP-250 Primer. The membrane shall be secured by placing the primed portion onto the tape portion of the TPO 10-inch Pressure-Sensitive RUSS and roll with a steel hand roller to ensure contact. 18. For bonded membrane systems,unless otherwise noted,reference to"Mule-Hide TPO-c"membrane below also includes"Mule-Hide TPO-c EXTRA". 19. Vapor barrier options for use over structural concrete deck followed by adhesive-applied insulation carry the following Maximum Design Pressure(MDP)limitations. The lesser of the MDP listings below vs.those In Table 3A applies. VAPOR BARRIER OPTIONS;STRUCTURAL CONCRETE DECK;FOLLOWED BY ADHESIVE-APPLIED INSULATION PER TABLE 3A: Vapor Barrier Option# Primer Insulation Adhesive MOP(psf) Type Application VB-1. Carlisle CAV-GRIP Primer F5'"Air&Vapor Barrier or Carlisle VapAir Seal 725TR Self-adhering HELIX(RIBBON,12-inch o.c.) -97.5 V8-2. ASTM D41 Carlisle SureMB 9OTG Base or SureMB 120 TG Poly Base Torch-applied HELIX(RIBBON,12-inch o.c.) -97.5 VB-3. ASTM D41 Carlisle SureMB 90 Base or SureMB 120 Poly Base Hot-asphalt HELIX(RIBBON,12-inch o.c.) -97.5 20. "MOP"=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design,LLC.d/b/a Trinity I ERD Evaluation Report M15060.06.09-R4 for FL12772-R4 Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION;Mule-Hide TPO-c Single Ply Roof Systems Revision 4:04/03/2017 Prepared by: Robert NIeminen,PE-59166 Mule-Hide Products Co.,Inc.;(608)365-3111 Appendix 1,Page 3 of 26 TRINITY ERD TABLE 1A: WOOD DECKS-NEW CONSTRUCTION,REROOF(Tear-Off)or RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION,BONDED ROOF COVER System Deck MDP Base Insulation Layer Top Insulation Layer Roof Cover(Note 16) No. (Note 1) Type Fasteners Attach (psf) W 1 Min.19/32"plywood or (Optional)One or more layers, Min.1.5-inch Poly ISO 1,H-Shield,ACFoam II, Note 2 1 per 2 ft' Mule-Hide TPO-c/TPO-c BA or Aqua 45.0' wood plank any combination,loose laid ( Poly ISO 2 or ENRGY 3 Base 120 BA TABLE 18: WOOD DECKS—NEW CONSTRUCTION,REROOF(Tear-Off)or RECOVER SYSTEM TYPE D-1: INSULATED,MECHANICALLY ATTACHED ROOF COVER System Insulation Layer(Note 14) Roof Cover MDP Roof Deck No. Type Attach Membrane Fasteners Spacing (psf) — Min.19/32-Inch plywood or wood plank at max.24"spans One or more Preliminarily Mule Hide 6-Inch o.c.within 5.5-inch wide laps spaced 90.5-inch Mule-Hide END W-2 attached using 8d ring shank nails spaced 6"o.c.in the field layers,any attached TPO-c Fasteners and 2.4 o.c. Outside of lap sealed with 1.5-inch heat-weld -52.5 and#10 ring shank nails spaced 4"o.c.at the perimeter combination Seam Plates Min.19/32-Inch plywood or wood plank at max.24"spans One or more Mule-Hide EHD Preliminarily Mule-Hide 6-Inch o.c.within 5.5-inch wide laps spaced 66.5-inch W-3 attached using 8d ring shank nails spaced 6"o.c.in the field layers,any Fasteners and 2.4 -67.5 and#10 ring shank nails spaced 4"o.c.at the perimeter combination attached TPO-c Seam Plates o.c. Outside of lap sealed with 1.5-inch heat-weld 6-inch o.c.within 5-inch wide laps spaced 67-Inch o.c. Min.23/32-Inch OSB at max.24-inch spans attached using One or more Mule-Hide EHD Outside of lap sealed with 1.5-inch heat-weld and 6- W-4 8d ring shank nails spaced 6"o.c,In the field and 8"o.c.at layers,any Preliminarily Mule-Hide Fasteners and 2.4 inch o.c.In one row centered between the laps. -67.5 intermediate supports combination attached TPO-c Seam Plates Center row covered with 6-inch wide cover strip sealed with 1.5-Inch heat weld at all edges TABLE 1C: WOOD DECKS-NEW CONSTRUCTION,REROOF(TEAR-OFF)OR RECOVER SYSTEM TYPE D-3: INSULATED,MECHANICALLY ATTACHED BASE SHEET,BONDED ROOF COVER System Insulation(Note 14) Base Sheet Roof Cover MDP Deck(Note 1) No. Type Attach Base Sheet Fasteners Attach Membrane Adhesive (Pall Min.19/32-inch plywood at One or more Atlas Summit Mule-Hide Drill Point 12-inch o.c.at the 4-inch laps and 12- Self- W-5 max.24-inch spans;#10 x 2- layers,any Loose-laid Synthetic Fastener and Mule-Hlde 2" inch o.c.at three,equally spaced Mule-Hide SA-TPO -120.0 inch wood screws,6-inch o.c. combination Underlayment Seam Plate rows in the center of the sheet. adhered Exterior Research and Design,LLC.d/b/a Trinity I ERD Evaluation Report M15060.06.09-R4 for FL12772-R4 Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION;Mule-Hide TPO-c Single Ply Roof Systems Revision 4:04/03/2017 Prepared by: Robert Nieminen,PE-59166 Mule-Hide Products Co.,Inc.;(608)365-3111 Appendix 1,Page 4 of 26 TRINITY ERD TABLE 1D: WOOD DECKS-NEW CONSTRUCTION,REROOF(Tear-Off)or RECOVER SYSTEM TYPE E-1: NON-INSULATED,MECHANICALLY ATTACHED ROOF COVER Thermal Barrier Roof Cover System MDP Roof Deck Fastener Lap Width Lap Spacing Seam Weld No. Type Attach Membrane Fasteners (Psi) Spacing(inch) (inch) (Inch) (inch) Min.19/32-inch thick Mule-Hide FR Deck Panel A or C or (Optional)Any Mule Hide EHD W 6 Barrier Technology Corp"Blazeguard A or C"at max.24-inch Mule-Hide approved Loose-laid Fasteners and 2.4 12 5 48 1.5 -30.0 spans attached using No.8 x 2Y,-inch long course thread TPO-c thermal barrier Seam Plates screws spaced 6"o.c. Min.19/32-inch thick Mule-Hide FR Deck Panel A or C or (Optional)Any Mule-Hide EHD W 7 Barrier Technology Corp"Blazeguard A or C"at max.24-inch Mule-Hide approved Loose-laid Fasteners and 2.4 6 5 72 1.5 -52.5 spans attached using No.8 x 2Y,-Inch long course thread TPO-c thermal barrier Seam Plates screws spaced 6"o.c. Min.19/32-inch thick Mule-Hide FR Deck Panel A or C or (Optional)Any Mule-Hide EHD W 8 Barrier Technology Corp"Blazeguard A or C"at max.24-inch Mule-Hide approved Loose-laid Fasteners and 2.4 6 5 48 1.5 -75.0 spans attached using No.8 x 24-Inch long course thread TPO-c thermal barrier Seam Plates screws spaced 6"o.c. (Optional)Any Mule-Hide EHD 48(over W 9 Mln.19/32-inch plywood at max.24-Inch spans attached Mule-Hide approved Loose-laid Fasteners and 2,4 6 5.5 structural 1.5 -75.0 using 8d ring shank nails spaced 6-Inch o.c. thermal barrier TPO-c Seam Plates members) TABLE 1E: WOOD DECKS-NEW CONSTRUCTION,REROOF(TEAR-OFF)OR RECOVER SYSTEM TYPE E-2: NON-INSULATED,MECHANICALLY ATTACHED BASE SHEET,BONDED ROOF COVER System j Thermal Barrier Base Sheet Roof Cover MDP Deck(Note 1) No. Type Attach Base Sheet Fasteners Attach Membrane Adhesive (psf) Min.19/32-inch plywood at (Optional)Any Atlas Summit Mule-Hide Drill Point 12-Inch o.c.at the 4-inch laps and 12-inch Mule Hide SA- Self- W-10 max.24-inch spans;#10 x 2- approved Loose-laid Synthetic Fastener and Mule-Hide o.c.at three,equally spaced rows in the -120.0 TPO adhered inch wood screws,6-inch o.c. thermal barrier Underlayment 2"Seam Plate center of the sheet. TABLE 1F:WOOD DECKS—NEW CONSTRUCTION SYSTEM TYPE F:NON-INSULATED,BONDED ROOF COVER System Roof Deck Roof Cover(Note 16) MOP No. Membrane Application (Psf) W-11 Min.15/32-Inch thick Mule-Hide FR Deck Panel A or C or Barrier Technology Corp"Blazeguard A or C"at Mule-Hide TPO-c Aqua Base 120 BA 45.0 max.24-inch spans attached using No.8 x 2/:-inch long course thread screws spaced 6"o.c. W 12 Min.19/32-inch thick Mule-Hide FR Deck Panel A or C or Barrier Technology Corp"Blazeguard A or C"at Mule-Hide TPO-c Aqua Base 120 BA -52.5 max.24-inch spans attached using No.8 x 2%-inch long course thread screws spaced 6"o.c. Exterior Research and Design,LLC.d/b/a Trinity)ERD Evaluation Report M15060.06.09-R4 for'L12772-R4 Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION;Mule-Hide TPO-c Single Ply Roof Systems Revision 4:04/03/2017 Prepared by: Robert Nieminen,PE-59166 Mule-Hide Products Co.,Inc.;(608)365-3111 Appendix 1,Page 5 of 26 I 1 PERIMETER HALF SHEETS MH 2.4" SEAM PLATES & HDP OR EHD FASTENERS To . • • • • • o-0-00000-3-0000o33000005-0do o b 0 NOTE: `° 0' • o • 0 0 0 00 0 0 0 00 0 0 0 $3Z�° to 0 to to to 0 o SEE TPO MEMBRANE FASTENING TECHNICAL o o o o 0 o 0 BULLETIN #TPO-MA01-2006 FOR APPROPRIATE a f o (o 1 0 I0 f o ° FASTENER SPACING FOR VARIOUS DECK TYPES l0 o I° I° I° 0 b 0 AND WIND UPLIFT REQUIREMENTS. ° b0 0 O 0 0 0 0 °o ° I: °0 l0 0 o 0 NOTE: 0 0— t 0— -0 0 0 I° to I I° I° �O ° SEE TECHNICAL BULLETIN #TPO-MA02-2006 O 0 ° ° ° — �° n FOR PERIMETER ENHANCEMENT (° I°- _ °— ° 0 REQUIREMENTS. to 0 6 ° ° 0 O 10 a °1 o O l°0 lO 0 (O 0 °' NOTE: �° 0 0 �° 1°0 a o �O to IO �O ° 0 THIS DETAIL IS NOT APPROVED OVER STEEL o l0 o o {0 ROOF DECKS. FOR STEEL ROOF DECKS, 0 ° 0 0 0 I0 01 REFER TO DETAILS MHT-FM-308A OR B, O �° I00 0 0 0 100 O 0o O0 0 0 0 0 0 0 01°0 0 0 0 01°0 0 0 0 0 0 Ia 0 a o00—Q_ 000000o_Qo . 000000000009_000 PARAPET WALL BASE FLASHING HEAT WELDED SEAMS FIELD MEMBRANE LAYOUT DETAIL NO.: MULE-HIDE PERIMETER HALF SHEET OPTION PRODUCTS CO., INC. SYSTEMS: MHT-MA-101A (3 **, MECHANICALLY ATTACHED REVISION DATE: 10/2013 1