1600 PARK TER W - REVISION 2/1/18 •
j�i.A.1`l .
E f"-----./r. ,
I0 CITY OF ATLANTIC BEACH
�� 800 SEMINOLE ROAD
J :.r
OFFICE ATLANTIC BEACH, FL 32233
C (904) 247-5800
., piil9r
BUILDING REVIEW COMMENTS
Date: 2/1/2018
Permit#: 17-SFR-3329-01 Site Address: 1600 W PARK TER
Review Status: DENIED RE#: 171966 0000
Applicant: Dream Finders Property Owner: STREIT,JILL&THOMAS J
Email: cindy.collins@dreamfinders.com Email:jjstreit@hotmail.com
Phone: Phone:
THIS REVIEW IS ONE OF MULTIPLE DEPARTMENT REVIEWS.
Revisions may not be submitted until ALL departments have completed their respective reviews.
Revisions submitted MUST respond to EACH department review. Submittals that respond to only one or a
few correction items will not be accepted.
Correction Comments:
1. Revisions submitted for the changes to the energy calculations is not approved still do to the Manual S not being c pliant
accordink Florida Energy Conservation Code—R403.7.1.2.1, exceeding the maximum allowable equipment cooling
capacity ab• - the design cooling load.
Building
Mike Jones
Building Inspector/Plans Examiner
City of Atlantic Beach
800 Seminole Road
Atlantic Beach, FL 32233
904.247.5844
Email:mjones@coab.us / 1
Cmot ided IQt ew Cornw•en11 2- / - I tI',,o/
Resubmittal Notes:
All revisions and changes shall clearly stand out from the rest of the drawing on the sheet as a revision by way of
completely encircling the change with "clouding".The revision shall also be identified as to the sequence of revision by
indicating a triangle with the revision sequence number within it and located adjacent to the cloud.The revision date
and revision sequence number shall also be indicated in a conspicuous location in the title block for each sheet on which
a revision for that sequence occurs. For projects still in the initial review stage and permit pending, all sheets with
revisions shall be inserted into each set of drawings.The original sheets must be clearly marked "VOID" but are to be left
within the set of drawings. Complete new sets of drawings will not be accepted. ADDITIONAL ITEMS MAY BE REQUIRED
DEPENDING UPON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
OFFICE COPY CITY OF ATLANTIC BEACH
" 1 '',` - 800 Seminole Road
Atlantic Beach, Florida 32233
'kk: -. ) Telephone(904)247-5800
FAX(904)247-5845
fif319
r REVISION REQUEST SHEET OR
CORRECTIONS TO REVIEW COMMENT
Date: la-21,-17 Received by: Resubmitted:
Permit Number:11-Seg.-3329
Original Plans Examiner: Project Name: 1%,00--- -TI,..
Project Address:►t.00-41c11-N Ce. coc.e. k
Contractor( V& Cs0n,GS_l.l,c. m
Contact Nae: ,cc , m€,,A.0._
Contact Phone :`IOt1►-lAcic-( 5t1 Contact ail:
Revision/Plan Check/Permit Fee(s) Due: $ es a
Description of Proposed Revision to Existing Permit:
1M.�u c)Ln. " .,►\-,A.4-if R eiloNv.n iNCiti dvNA—
Additional Increase in Building Value: $ Lo o„r>,ha Additional S.F.';%p
Site Plan Revised: Public W/U Approval:
By signing belo. . (print name) nam_yS ce,c ,2. affirm that the above revision
is inclusive . . , • proposed changes.
14, lel
Signa if Contractor/Agent(Contractor must sign if increase in valuation) Date
office Use Only
Date: Approved: Refected: AV Notified by: __
Plan Review Comments:
/ha Meal 3 c 0 0-pi iasci P- rar+r , exc." ,F,/ Lo_e; /.►•,^,lir
UtC �., 2017 ?
De artment review required Yes ' No f�
uildi
annin 8 Zo
• flans Examiner
Tree A ministrator
Public Works
Public Utilities y^ O/
Public Safety
Date crested Oil bl6 Rev i
Fire Services
OFFICE COPY ,---=-------------- Vn (
.( CITY OF ATLANTIC BEACH
"Y JAN 2 3 riU'i
800 Seminole Road
Atlantic Beach,Florida 32233
REVISION REQUEST/CORRECTIONS TO PLAN REVIEW COMMENTS
\—L3-/$
Date Revision to Issued Permit 1( Corrections to Comments Permit# 17— Sf f 33 Zcj
—of
Project Address i(0 00 NIK 4' rat e w 66 r
Contractor/Contact Name 1- ivt f vet .XS
Phone Email C,l ri • Col I t A S P Dfeuwtt ei S .Coy
Description of Proposed Revision/Corrections: Permit Fee Due $
C--L atAie) R U ►tA--5 4-00 Com cte -F-Ofs r°°
P ivi
Additional Increase in Building Value $ Or Additional S.F.
By signing below,I affirm the Revision is inclusive of the proposed changes.
(printed name)
Signature of Contractor/Agent(Contractor must sign if increase in valuation) Date
(Office Use Only)
Approved Denied Not Applicable to Department
Revision/Plan Review Comments1
emirigewom
De artment Review Required: /
Building
arming & Zoning r90-.
Reviewed By
Tree Administrator
Public Worksi1•�O�
Public Utilities et
Public Safety Date
Fire Services
OFFICE COP Y
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes,LLC
Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval
City,State.Zip: Jacksonville ,FL, Permit Number:
1 Owner: Dream Finders Homes,LLC Jurisdiction: 261300
Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(4721.0 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=23.0 4474.30 ft2
b.Frame-Wood,Adjacent R=23.0 246.67 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 5
d.N/A R= ft2
10.Ceiling Types (3858.0 sqft.) Insulation Area
5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 3858.00 ft2
6. Conditioned floor area above grade(ft2) 3858 b.N/A R= ft2
c. N/A R= ft2
Conditioned floor area below grade(ft2) 0 11.Ducts R ft2
7. Windows(697.0 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Main 6 707
•
a. U-Factor: Dbl,U=0.36 600.97 ft2 b.Sup: Attic,Ret:Attic,AH:Attic 6 303
SHGC: SHGC=0.23
b. U-Factor: Dbl,U=0.62 96.00 ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 36.0 SEER:16.00
b.Central Unit 24.0 SEER:16.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a.Electric Heat Pump 36.0 HSPF:9.00
SHGC: b.Electric Heat Pump 24.0 HSPF:9.00
Area Weighted Average Overhang Depth: 5.916 ft.
Area Weighted Average SHGC: 0.233 14.Hot water systems
a.Natural Gas Tankless Cap: 1 gallons
• 8. Floor Types (3858.0 sqft.) Insulation Area EF:0.800
• a.Slab-On-Grade Edge Insulation R=0.0 2318.00 ft2 b. Conservation features '
b.Floor Over Other Space R=0.0 865,00 ft2 None
c.other(see details) R= 675.00 ft2 15.Credits Pstat
Total Proposed Modified Loads: 83.48PASS
Glass/Floor Area: 0.181 Total Baseline Loads: 113.57 .
I hereby certify that the plans and specifications covered by Review of the plans and f�4,1'
10E Sx,1? ,.
this calculation are in compliance with the Florida Energy specifications covered by this ti.- <'-a= ; 0°k
Code. calculation indicates compliance u„ _ °'' 6'
/ with the Florida Energy Code. +t.rrnq '',, - '::� •„`.0 i"t "
PREPARED BY: M 97 t.<7v. Before construction is completed ,,,,,, �°.-"•'
DATE: 01 /11.4/ `d this building will be inspected for 0 '� l_o � '
compliance with Section 553.908 * `Y x
Florida Statutes. '�1 '
I hereby certify that this building,as designed is' o fiance % C •• ••'s••,'''‘,.(C,. ..t,..
with the Florida Energy Code. ''` iQD ��4..+
OWNER/AGENT: tif BUILDING OFFICIAL: fri
U,7,/ p�
DATE: i ) I b I i$ DATE: 3-�/^ �/0
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2).
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 1 of 5
FORM R405-2017
PROJECT
Title: Streit Residence 3858 Left S Bedrooms: 5 Address Type: Street Address
Building Type: User Conditioned Area: 3858 Lot#
Owner Name: Dream Finders Homes,LLC Total Stories: 2 Block/Subdivision:
#of Units: i Worst Case: No PlatBook:
Builder Name: Dream Finders Homes,LLC Rotate Angle: 0 Street:. Lot 2&23,Block 6 Cou i
Permit Office: Duval Cross Ventilation: No County: Duval
Jurisdiction: 261300 Whole House Fan: No City, State,Zip: Jacksonville ,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
/ Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Jacksonville FL_JACKSONVILLE_INT 32 93 70 75 1281 49 Medium
BLOCKS
Number Name Area Volume
1 Blockl 2318 23180
2 Block2 1540 13860
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 Main 2318 23180 Yes 3 2 1 Yes Yes Yes
2 2nd Floor 865 7785 No 2 2 1 Yes Yes Yes
3 Bonus Room 675 6075 No 1 1 1 Yes Yes Yes
FLOORS
V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 264 ft 0 2318 ft2 ____ 0 0 1
2 Floor Over Other Space 2nd Floor ___ - 865 ft2 0 0 0 1
3 Floor over Garage Bonus Room ____ ____ 675 ft2 19 0 0 1
ROOF
/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Gable or Shed Metal 3598 ft2 998 ft2 Medium 0.6 N 0.9 No 20 33.7
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Unvented 0 2993 ft2 N N
i
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5
1
FORM R405-2017
CEILING
V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Unvented) Main 20 Blown 2318 ft2 0.11 Wood
2 Under Attic(Unvented) 2nd Floor 20 Blown 865 ft2 0.11 Wood
3 Under Attic(Unvented) Bonus Room 20 Blown 675 ft2 0.11 Wood
WALLS
/ Adjacent Space Cavity Width Height Sheathing Framing Solar Below
V # Ornt To WaiLType R-VaiuP Ft In Ft In ArPa R-vai"e Frartinn Ahsnr rradP°f
1 S Exterior Frame-Wood Main 23 61 0 10 0 610.0 ft2 0 0.23 0.6 0
2 S Garage Frame-Wood Main 23 24 8 10 0 246.7 ft2 0 0.23 0.01 0
_ 3 E Exterior Frame-Wood Main 23 59 8 10 0 596.7 ft2 0 0.23 0.6 0
_4 N Exterior Frame-Wood Main 23 61 0 10 0 610.0 ft2 0 0.23 0.6 0
_ 5 W Exterior Frame-Wood Main 23 59 8 10 0 596.7 ft2 0 0.23 0.6 0
_ 6 S Exterior Frame-Wood 2nd Floor 23 39 2 9 0 352.5 ft2 0 0.23 0.6 0
_ 7 E Exterior Frame-Wood 2nd Floor 23 23 4 9 0 210.0 ft2 0 0.23 0.6 0
_ 8 N Exterior Frame-Wood 2nd Floor 23 39 2 9 0 352.5 ft2 0 0.23 0.6 0
_ 9 W Exterior Frame-Wood 2nd Floor 23 23 4 9 0 210.0 ft 0 0.23 0.6 0
10 S Exterior Frame-Wood Bonus Room 23 24 0 9 0 216.0 ft2 0 0.23 0.6 0
11 E Exterior Frame-Wood Bonus Room 23 28 0 9 0 252.0 ft2 0 0.23 0.6 0 i
I'
_12 N Exterior Frame-Wood Bonus Room 23 24 0 9 0 216.0 ft2 0 0.23 0.6 0
13 W Exterior Frame-Wood Bonus Room 23 28 0 9 0 252.0 ft2 0 0.23 0.6 0
DOORS
# Ornt Door Type Space Storms U-ValueFt Width In FHeight Area
1 W Wood Main None .4 3 8 24 ft2 •
2 S Wood Main None .4 2 8 8 21.3 ft2 �L
WINDOWS
Orientation shown is the entered,Proposed orientation. -
•
Wall Overhang
# Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 64.0 ft2 8 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
2 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 48.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
3 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 48.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
4 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 30.0 ft2 12 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
5 E 3 Vinyl Low-E Double Yes 0.62 0.25 N 96.0 ft2 12 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
6 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 18.7 ft2 10 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
7 N 12 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
8 W 13 Vinyl Low-E Double Yes 0.36 0.23 N 8.8 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
9 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 18.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
10 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 16.0 ft2 30 ft 8 in 1 ft 0 in Drapes/blinds Interior 5
11 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 5.0 ft2 30 ft 8 in 1 ft 0 in Drapes/blinds Interior 5
12 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
13 S 10 Vinyl Low-E Double Yes 0.36 0.23 N 15.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
14 S 6 Vinyl Low-E Double Yes 0.36 0.23 N 80.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2017
WINDOWS 1
Orientation shown is the entered, Proposed orientation.
/ Wall Overhang
V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
15 N 8 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
16 N 8 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
17 W 9 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
18 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 14.2 ft2 8 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
19 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 3.6 ft2 1-ft 4 in 1 ft 0 in Drapes/blinds Interior 5
20 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 14.2 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
21 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 21.3 ft2 23 ft 8 in 1 ft 0 in Drapes/blinds Interior 5
22 S 10 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 ,
23 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 ,
24 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 12.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
25 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 18.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
26 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 7.1 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
27 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 7.1 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5
GARAGE
V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 684 ft2 684 ft2 92 ft 10 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EqLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000305 3086.7 169.45 318.68 .2892 5
L.
HEATING SYSTEM •
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split HSPF:9 36 kBtu/hr 1 sys#1
2 Electric Heat Pump/ None HSPF:9 24 kBtu/hr 2 sys#2
COOLING SYSTEM
V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split SEER:16 36 kBtu/hr 1080 cfm 0.7 1 sys#1
2 Central Unit/ None SEER: 16 24 kBtu/hr 720 cfm 0.7 2 sys#2
HOT WATER SYSTEM
V # System Type SubType Location EF Cap Use SetPnt Conservation
1 Natural Gas Tankless Exterior 0.8 1 gal 60.9 gal 120 deg None
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5
' FORM R405-2017
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
/ --Supply— —Return-- Air CFM 25 CFM25 HVAC#
�/ # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 707 ft2 Attic 240 ft2 Default Leakage Main (Default) (Default) 1 1
2 Attic 6 303 ft2 Attic 89 ft2 Default Leakage Attic (Default) (Default) 2 2
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
Cooling Jan Feb Mar Apr Ma X Jun Jul Au Se Oct Nov Dec
Venting lX]Jan ' Feb X Mar [X Apr May Jun Jul Aug Sep €X Oct [X Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling'(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 BO 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 -78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
II
I
1/16/2018 12:50 PM EnergyGaugeO USA-FlaRes2017 Section R405.4.1 Compliant Software Page 5 of 5
FORM R405-2017
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
.
ESTIMATED ENERGY PERFORMANCE INDEX* = 74
The lower the EnergyPerformance Index,the more efficient the home.
Lot 2& 23, Block 6 Country Club Lane, Jacksonville , FL,
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a.Frame Wood,Exterior R=23.0 4474.30 ft2
b.Frame-Wood,Adjacent R=23.0 246.67 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 5 d.N/A R= ft2
10.Ceiling Types Insulation Area
5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 3858.00 ft2
6. Conditioned floor area(ft2) . 3858 b.N/A R= ft2
c.N/A R= ft2
7. Windows' Description Area ft2
a. U-Factor: Dbl,U=0.36 600.97 ft2 11.Ducts R
a.Sup:Attic,Ret:Attic,AH:Main 6 707
SHGC: SHGC=0.23 b.Sup: Attic,Ret:Attic,AH:Attic 6 303
b. U-Factor: Dbl,U=0.62 96.00 ft2
SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft2 a.Central Unit 36.0 SEER:16.00
SHGC: b.Central Unit 24.0 SEER:16.00
d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency
SHGC: a.Electric Heat Pump 36.0 HSPF:9.00
Area Weighted Average Overhang Depth: 5.916 ft. b.Electric Heat Pump 24.0 HSPF:9.00
Area Weighted Average SHGC: 0.233
8. Floor Types Insulation Area 14.Hot water systems Cap: 1 gallons
a.Slab-On-Grade Edge Insulation R=0.0 2318.00 ft2 a.Natural Gas EF:0.8
b.Floor Over Other Space R=0.0 865.00 ft2
c.other(see details) R= 675.00 ft2 b. Conservation features
None
15.Credits Pstat
I •
I certify that
his home has comlied with the
e for
uilding
Construction tthr ugh the above penergy saving Florida
features which will be installed ll (orBexcce exceeded)
°```p EKE s-rg A.,,,
�,��,:
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: Lot 2&23, Block 6 Country Club Lane Permit Number:
Jacksonville ,FL,
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law
(Section 553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing
methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1,as applicable to the method of construction.Where required
by the code official,an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either
individuals as defined in Section 553.993(5)or(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i)or
an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing
•
buildings in which the new construction is less than 85 percent of the building thermal envelope.
•
During testing:
1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended
weatherstripping or other infiltration control measures.
2. Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond
intended infiltration control measures.
3. Interior doors,if installed at the time of the test,shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems,if installed at the time of the test,shall be turned off.
6. Supply and return registers,if installed at the time of the test,shall be fully open.
R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where
using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the
fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air IeakageWindows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot(1.5 L/s/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NERC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
•
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to
open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room,isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm(0.944 L/s).when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1:3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or
(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing(Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system,including the
manufacturer's air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the
entire system,including the manufacturer's air handler enclosure.Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)
or below 55°F(13°C)shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that
caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause
degradation of the material.Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory). Heated water circulation systems shall be in
accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump.The system return
pipe shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or Ul 515.Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
1/16/2018 12:50 PM EnergyGaugee USA-FlaRes2017 -FBC 6th Edition(2017)Complian Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3%2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies(Mandatory).
R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature
setting range shall be from 100°F to 140°F(38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of
combustion types of service water-heating systems to be turned off.
R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar
water-heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code,Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation
including:Natural,Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole-house mechanical ventilation system fan efficacy. When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable
Indoor Air Quality,shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces.attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10
otherwise.
R403.7 Heating and cooling equipment(Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and
indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that
affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMUIV
(CFM) (CFM/WATT) (CFM)
Range hoods Any 2.8 cfm/watt Any
In-line fan Any 2.8 cfm/watt Any II
Bathroom, utility room 10 1.4 cfm/watt <90 f�
Bathroom,utility room 90 2.8 cfm/watt Any
For SI: 1 cfm=28.3 L/min. a. When tested in accordance with HVI Standard 916
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's
expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded
performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.
Exceptions:
1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7:1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls(Mandatory) Snow-and ice-melting systems,supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F(10°C),and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F(4.8°C).
R403.10 Pools and permanent spa energy consumption(Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation
of such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the
power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors.Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating,computed over an operation season, is from site-recovered
energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required.
R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56.Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is
required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas(Mandatoryfhe energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14. •
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Exception:Low-voltage lighting. •
R404.1.1 Lighting equipment(Mandatory).Fuel gas lighting systems shall not have continuously burning pilot lights.
•
1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Compile Page 5 of 5
2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes, LLC
Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval
City,State,Zip: Jacksonville , FL: Permit Number:
Owner: Dream Finders Homes,LLC Jurisdiction: 261300
Design Location: FL,Jacksonville
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and anygaps in the air barrier shall be sealed.
g p shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with
sealed. a material having a thermal resistance of R-3 per inch
Knee walls shall be sealed. minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/door jambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls.
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
cavities shall be filled by insulation that on
Narrow cavities installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spacas.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be air tight and IC rated,
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind mein()and wiring
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover elates and walls or ceilinas
a. In addition,inspection of log walls shall be in accordance with the provisions of ICC-400.
1/16/2018 12:51 PM EnergyGauge®USA-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
FORM R405-2017 Envelope Leakage Test Report Performance
FLORIDA ENERGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Envelope Leakage Test Report
Performance Method
Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes,LLC
Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval
City,State,Zip: Jacksonville , FL, Permit Number:
Design Location: FL,Jacksonville Jurisdiction: 261300
Cond.Floor Area:: 3858 sq.ft. Cond.Volume: 37040 cu ft.
Envelope Leakage Test Results Leakage Characteristics
Regression Data:
C: n: R:
Single or Multi Point Test Data Required ACH(50)from
HOUSE PRESSURE FLOW: FORM R405-2017 :
-1 Pa cfm
2 Pa cfm Tested ACH(50) *:
3 Pa cfm
*Tested leakage must be less than or equal to the
4 Pa cfm required ACH(50)shown on Form R405-2017 for
5 Pa cfm this building. If the tested ACH(50) is less than 3
the building must have a mechanical ventilation
6 Pa cfm system.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour
in Climate Zones 1 and 2...Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Testing shall be conducted by
either individuals as defined in Section 553.993(5)or(7),Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f),(g),or(i)or an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing
shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing: -
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other
infiltration control measures;
2. Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration
control measures;
3. Interior doors,if installed at the time of the test,shall be open;
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5. Heating and cooling systems,if installed at the time of the test,shall be tumed off;and
6.Supply and return registers,if installed at the time of the test,shall be fully open.
I hereby certify that the above envelope leakage Testing shall be conducted by either ;.- 4,cgg STAT-+�
individuals as defined in Section
; ;..0 *�,
performance results demonstrate compliance �* t.•• ••••%,�z :_ .�
with Florida Energy Code requirements in 553.993(5)or(7), Florida Statutes or �t„ '` r •
accordance with Section R402.4.1.2. individuals licensed as set forth in x :
c•
Section 489.105(3)(f), (g),or(i)or an a2 a
approved third party.A written report of = •
1~ "
the results of the test shall be signed '•.; r'
SIGNATURE: by the third party conducting the test � ..,r.. r�•
and provided to the code official. o 06 ""
PRINTED NAME:
BUILDING OFFICIAL:
DATE: DATE:
•
1/16/2018 12:51 PM EnergyGauge®USA-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1
Project Summary Date:
264/1644 (Rest of House) By: Renee Brown/SPG
McGowan's Heating & Air Conditioning, Inc.
4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.com
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Notes: STREIT RESIDENCE
Desi• n Information
Weather: Jacksonville NAS, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 32 °F Outside db 99 °F
Inside db 70 °F Inside db 75 °F
Design TD 38 °F Design TD 24 °F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 28167 Btuh Structure 21577 Btuh
Ducts 3439 Btuh Ducts 4384 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 31607 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load flittuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 2591 Btuh
Ducts 772 Btuh
Central vent(0 cfm) 0 Btuh
Heating Cooling (none)
Area(ft2) 2318 2318 Equipment latent load :6 :tuh
Volume (ft3) 23180 23180
Air changes/hour 0.23 0.12 Egiggrnent Total Load Sen+Lat) tuh
Equiv.AVF (cfm) 90 48 Req. total capaci a . 2.8 ton
Heating Equipment Summary Cooling Equipment Summary
Make Trane Make Trane
Trade TRANE Trade TRANE
Model 4TWR7036B1 Cond 4TWR7036B1
AHRI ref 7599443 Coil TEM6A0C36H31++TDR
AHRI ref 7599443
Efficiency 9.6 HSPF Efficiency 12.5 EER, 17 SEER
Heating input Sensible cooling 25200 Btuh
Heating output 32000 Btuh @ 47°F Latent cooling 10800 Btuh
Temperature rise 24 °F Total cooling 36000 Btuh
Actual air flow 1200 cfm Actual air flow 1200 cfm
Air flow factor 0.038 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.89
Capacity balance point=32°F
Backup:
Input=9 kW, Output=31918 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wriptitsoft 2018-Jan-16 12:49:01
• - • Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1
...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
Project Summary Date:
M a 2nd Floor By: Renee Brown/SPG
McGowan's Heating & Air Conditioning, Inc.
4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web:www.mcgowansac corn
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Notes: STREIT RESIDENCE
Desi• n Information
Weather: Jacksonville NAS, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 32 °F Outside db 99 °F
Inside db 70 °F Inside db 75 °F
Design TD 38 °F Design TD 24 °F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 13432 Btuh Structure 10552 Btuh
Ducts 1886 Btuh Ducts 2473 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 15318 Btuh Use manufacturer's data y
uteamwin multiplier 1.
Infiltration tuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 2385 Btuh
Ducts 427 Btuh
Central vent(0 cfm) 0 Btuh
Heating Cooling (none)
Area(ftp 1540 1540 Equipment latent load- tuh
Volume (ft') 13716 13716
Air changes/hour 0.31 0.17 Equipment Total Load(Se.a+Lat) (.4 tuh
Equiv.AVF(cfm) 72 38 Req.total capacity at 0.70 SHR 1.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Trane Make Trane
Trade TRANE Trade TRANE
Model 4TWR7024A1 Cond 4TWR7024A1
AHRI ref 7793615 Coil TEM6A0B24H21++TDR
AHRI ref 7793615
Efficiency 8.5 HSPF Efficiency 12.5 EER, 17 SEER
Heating input Sensible cooling 17500 Btuh
Heating output 24000 Btuh @ 47°F Latent cooling 7500 Btuh
Temperature rise 26 °F Total cooling 25000 Btuh
Actual air flow 833 cfm Actual air flow 833 cfm
Air flow factor 0.054 cfm/Btuh Air flow factor 0.064 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.82
Capacity balance point=21 °F
Backup:
Input=4 kW, Output= 15306 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrighisoti 2016-Jan-1612:49:01
Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2
Aftk ..eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
N
A1r\
First Floor
6x12
tlldsrgWBf atOC �4 z 6 0
owner-...),:t, access 4" Q
owners
8:10
8' 6
r_L
16x 16
12" 7- Rte..
4"Fan 1 1
" 4x6 - :. 0
nest .% ,414" •• 6. • 4'Fan .�
9 86 4074.1 `I 1 4.4 z6 • ;1lJ
7 -
2x12 1' t0 -
8' 8x11
��® 12x12 8- r
1. 4 �
12"
•
4x8 •
•
11 limor
4. 1 1
0
O•I an
1 ...o... � 1�� ....1
12" 12:6 12:6
j 106x.6 18210 106:.6 7' 24818 �-
9 6' 18
I
„IMP5 ^
i
1,r,,,,.....t
mtly
14x1486
a- 8.
I
Job#: McGowan's Heating & Air Conditioning Scale: 1 : 143
Performed by Renee Brown/SPG for: Page 1
Casey Conner 4850 Collins Road Comfort Builder by Wrightsoft
360 Corporate way.Suite 100 Orange Park,Fl 32073 18.0.08 RSU12270
Orange Park,FL 32073 Phone:904-278-0339 Fax:904-278-0366
2018-Jan-16 12:49:25
Phone:(904)644-7670 Fax:(904)239-3003 www.mcgowansac.com kore me owansac.com
casey.conner@dreamfinders.com g y@ g ith Bonus single 2nd fl unit.rup
N
A.e
Air*
up
4"Fan 4'
OM
IOC
-We!
10x6 .••
the toilet 5,
P
jeigi 16. f
10x6 UM .41!11111
'.6/ 1 11'
!• !x8
12x6 tithe
12z 1201 _
future beth 5 mach 184 18 •:. �1 12• -.
l0 x6 Milli12x6 12x6 12 xfi
•0 xfi 5" �.. .. 10x58 7'
store hall 16 x 1
.......)
Mt6- Fir
9x4 1 14'la 12.
4
11111
— 12x12 I
10 xfi 9'
10x6
12x6mil
5..
7"
NIP
12x6
7'
Job#: McGowan's Heating & Air Conditioning Scale: 1 : 143
Performed by Renee Brown/SPG for: Page 2
Casey Conner 4850 Collins Road
Comfort Builder Uby1 27ghtsoft
360 Corporate Way,Suite 100
Orange Park,Fl 32073 18.0.08 RS20
Orange Park,FL 32073 Phone:904-278-0339 Fax:904-278-0366
Phone:(904)644-7670 Fax (904)239-3003 Bonus 12:49:25fln
www.mcgowansac.com korey@mcgowansac.com ith Bonus single 2nd fl unit.rup
casey.conner@dreamfinders.com
Manual S Compliance Report Job.
Date:
X1°4
414 (Rest of House) By: Renee Brown/SPG
McGowan's Heating & Air Conditioning, Inc.
4850 Collins Road.Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web.www.mcgowansac.corn
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Cooling Equipment
Design Conditions
Outdoor design DB: 99.2°F Sensible gain: 23406 Btuh / Entering coil DB: 75.7°F
Outdoor design WB: 80.2°F Latent gain: 7863 Btuh (/ Entering coil WB: 62.9°F
Indoor design DB: 75.0°F Total gain: 31269 Btuh
Indoor RH: 50% Estimated airflow: 1200 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Trane Model: 4TWR7036B1+TEM6A0C36H31++TDR
Actual airflow: 1200 cfm
Sensible capacity: 25200 Btuh 108%of load
Latent capacity: 10800 Btuh 137%of load
Total capacity: 36000 Btuh 1193/0 of load SHR: 70%
Heating Equipment
Design Conditions
Outdoor design DB: 31.7°F Heat loss: 31607 Btuh Entering coil DB: 69.7°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Trane Model: 4TWR7036B1+TEM6A0C36H31++TDR
Actual airflow: 1200 cfm
Output capacity: 32000 Btuh 101%of load Capacity balance: 32 °F
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 1200 cfm
Output capacity: 9.4 kW 101%of load Temp. rise: 50 °F
Meets all requirements of ACCA Manual S.
wrightso t 2018-Jan-1612:49:01
Al� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1
...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
Manual S Compliance Report Job:
Date:
6001e4 2nd Floor By: Renee Brown/SPG
McGowan's Heating &Air Conditioning, Inc.
4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.corn
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Cooling Equipment
Design Conditions
Outdoor design DB: 99.2°F Sensible gain: 13025 Btuh Entering coil DB: 75.8°F
Outdoor design WB: 80.2°F Latent gain: 2812 Btuh Entering coil WB: 62.9°F
Indoor design DB: 75.0°F Total gain: 15837 Btuh
Indoor RH: 50% Estimated airflow: 833 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Trane Model: 4TWR7024A1+TEM6A0B24H21++TDR
Actual airflow: 833 cfm
Sensible capacity: 17500 Btuh 134%of load
Latent capacity: 7500 Btuh 267%of load
Total capacity: 25000 Btuh 158%of load SHR: 70%
Heating Equipment
Design Conditions
Outdoor design DB: 31.7°F Heat loss: 15318 Btuh Entering coil DB: 69.7°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Trane Model: 4TWR7024A1+TEM6A0B24H21++TDR
Actual airflow: 833 cfm
Output capacity: 24000 Btuh 157%of load Capacity balance: 21 °F
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 833 cfm
Output capacity: 4.5 kW 100%of load Temp. rise: 19 °F
Meets all requirements of ACCA Manual S.
wrightsoft 2018-Jan-16 12:49:01
t Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2
AC ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
n , VI4 Duct System Summary Jo Date:
ker6(,,4 -' (Rest of House) By: Renee Brown/SPG
/� McGowan's Heating &Air Conditioning, Inc.
4850 Collins Road.Orange Park.Fl 32073 Phone.904-278-0339 Fax:904-278-0366 Email:koreylmcgowansac.corn Web:www.mcgowansac.corn
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0.11 in H2O 0.11 in H2O
Available static pressure 0.39 in H2O 0.39 in H2O
Supply/return available pressure 0.280/0.110 in H2O 0.280/0.110 in H2O
Lowest friction rate 0.084 in/100ft 0.084 in/100ft
Actual air flow 1200 cfm 1200 cfm
Total effective length (TEL) 466 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matt Ln (ft) Ln (ft) Trunk
laundry C 1898 73 88 0.089 7.0 Ox 0 VIFx 75.4 240.0 st8
guest h 2632 100 97 0.086 7.0 Ox 0 VIFx 81.3 245.0 st8
bath 2 C 12 0 1 0.084 4.0 Ox 0 VIFx 89.3 245.0 st8
drop zone h 2718 103 68 0.089 7.0 Ox 0 VIFx 74.2 240.0 st8
pwdr c 12 0 1 0.132 4.0 Ox 0 VIFx 32.7 180.0 st7
foyer h 3515 133 133 0.128 8.0 Ox 0 VIFx 39.5 180.0 st7
family-A c 3849 155 178 0.106 9.0 Ox 0 VIFx 50.2 215.0 st6
family C 3849 155 178 0.113 9.0 Ox 0 VIFx 42.7 205.0 st6
butler C 8 0 0 0.130 4.0 Ox 0 VIFx 36.1 180.0 st7
pool bath h 1265 48 27 0.143 5.0 Ox 0 VIFx 31.5 165.0 st5
kitchen C 1422 49 66 0.154 6.0 Ox 0 VIFx 17.0 165.0 st5
kitchen-A C 1422 49 66 0.147 6.0 Ox 0 VIFx 25.4 165.0 st5
kitchen-B C 1422 49 66 0.161 6.0 Ox 0 VIFx 13.6 160.0 st5
wc-A c 12 0 1 0.084 4.0 Ox 0 VIFx 94.8 240.0 st8
wic h 968 37 23 0.134 5.0 Ox 0 VIFx 43.4 165.0 st4
owners bath h 2194 83 50 0.124 6.0 Ox 0 VIFx 55.5 170.0 st4
owners h 2185 83 79 0.135 6.0 Ox 0 VIFx 42.5 165.0 st4
owners-A h 2185 83 79 0.134 6.0 Ox 0 VIFx 43.6 165.0 st4
wrightsoft 2018-Jan-16 12:49:01
�^t.�C� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1
/1COK ...eit Residence with Bonus single 2nd ft unit.rup Calc=MJ8 Front Door faces: S
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st6 Peak AVF 311 356 0.106 652 10.0 0 x 0 VinIFIx st5
st4 Peak AVF 286 232 0.124 524 10.0 0 x 0 VinIFIx stl
st5 Peak AVF 504 580 0.106 738 12.0 0 x 0 VinIFIx stl
st8 Peak AVF 276 254 0.084 351 12.0 0 x 0 VinIFIx st7
st7 Peak AVF 410 388 0.084 522 12.0 0 x 0 VinIFIx stl
stl Peak AVF 1200 1200 0.084 550 20.0 0 x 0 ViniFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rsb3 Ox 0 479 407 131.4 0.084 610 12.0 Ox 0 VIFx rt1
rb7 Ox 0 721 793 90.0 0.122 449 18.0 Ox 0 VIFx ill
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
rtl Peak AVF 1200 1200 0.084 550 ' 20.0 0 x 0 VinlFlx
wrightsoft 2018-Jan-16 12:49:01
��� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2
/R+M ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
Duct System Summary Date:
� � 2nd Floor By: Renee Brown/SPG
McGowan's Heating & Air Conditioning, Inc.
4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.com
Project Information
For: Casey Conner, Dream Finders Homes, LLC.
360 Corporate Way, Suite 100, Orange Park, FL 32073
Phone: (904)644-7670 Fax: (904)239-3003
Email: casey.conner@dreamfinders.com
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0.11 in H2O 0.11 in H2O
Available static pressure 0.39 in H2O 0.39 in H2O
Supply/return available pressure 0.244/0.146 in H2O 0.244/0.146 in H2O
Lowest friction rate 0.116 in/100ft 0.116 in/100ft
Actual air flow 833 cfm 833 cfm
Total effective length (TEL) 337 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk
bed 3 c 1839 109 118 0.162 7.0 Ox 0 VIFx 20.7 130.0 st3
loft h 1093 59 58 0.121 6.0 Ox 0 VIFx 36.2 165.0 st9
loft-A h 1093 59 58 0.120 6.0 Ox 0 VIFx 38.0 165.0 st9
stairs up c 167 9 11 0.165 4.0 Ox 0 VIFx 22.6 125.0 st3
bath 3 c 980 59 63 0.120 6.0 Ox 0 VIFx 38.8 165.0 st9
bed 2 c 1406 73 90 0.121 7.0 Ox 0 VIFx 36.5 165.0 st9
wic 2 h 257 14 12 0.132 4.0 Ox 0 VIFx 19.8 165.0 st3
bath 4 h 920 50 42 0.163 5.0 Ox 0 VIFx 24.7 125.0 st3
wic 3 h 618 34 27 0.162 5.0 Ox 0 VIFx 20.0 130.0 st3
future bonus c 1127 54 72 0.125 6.0 Ox 0 VIFx 64.4 130.0 st2
future bonus-A c 1127 54 72 0.116: 6.0 Ox 0 VIFx 75.4 135.0 st2
store2 h 1333 72 59 0.126 6.0 Ox 0 VIFx 68.1 125.0 st2
stores h 2109 115 92 0.127 7.0 Ox 0 VIFx 66.6 125.0 st2
future bath 5 h 685 37 33 0.124 5.0 Ox 0 VIFx 66.5 130.0 st2
mech h 530 29 23 0.121 5.0 Ox 0 VIFx 71.7 130.0 st2
store hall c 64 4 4 0.125 4.0 Ox 0 VIFx 64.5 130.0 st2
Supply Trunk Detail Table
Trunk Htg CIg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st2 Peak AVF 366 355 0.116 466 12.0 0 x 0 VinIFIx
st9 Peak AVF 251 268 0.120 341 12.0 0 x 0 VinIFIx st3
st3 Peak AVF 467 478 0.120 447 14.0 0 x 0 VinIFIx
wrightsoft" 2018-Jan-1612:49:01
�tj- Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 3
IP ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S
Return Branch Detail Table
1 I l I I I i I I I l I
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox 0 185 152 126.3 0.116 173 14.0 Ox 0 VIFx rt2
rb2 Ox 0 246 251 110.4 0.133 235 14.0 Ox 0 VIFx rt2
rb3 Ox 0 200 232 88.0 0.166 525 9.0 Ox 0 VIFx rt2
rb4 Ox 0 202 198 • 115.0 0.127 458 9.0 Ox 0 VIFx rt2
I
i
Return Trunk Detail Table
l
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
rt2 Peak AVF 833 833 0.116 597 16.0 0 x 0 VinIFIx
i I L _. . 1
wrightsoft 2018-Jan-16 12:49:01
Comfort Builder by Wrightsoft 18.0.08 RSU12270 Pae 4
A '..Cg
...eit Residence with Bonus single 2nd Fl unrt.rup Calc=MJ8 Front Door faces: S