Loading...
1600 PARK TER W - REVISION 2/1/18 • j�i.A.1`l . E f"-----./r. , I0 CITY OF ATLANTIC BEACH �� 800 SEMINOLE ROAD J :.r OFFICE ATLANTIC BEACH, FL 32233 C (904) 247-5800 ., piil9r BUILDING REVIEW COMMENTS Date: 2/1/2018 Permit#: 17-SFR-3329-01 Site Address: 1600 W PARK TER Review Status: DENIED RE#: 171966 0000 Applicant: Dream Finders Property Owner: STREIT,JILL&THOMAS J Email: cindy.collins@dreamfinders.com Email:jjstreit@hotmail.com Phone: Phone: THIS REVIEW IS ONE OF MULTIPLE DEPARTMENT REVIEWS. Revisions may not be submitted until ALL departments have completed their respective reviews. Revisions submitted MUST respond to EACH department review. Submittals that respond to only one or a few correction items will not be accepted. Correction Comments: 1. Revisions submitted for the changes to the energy calculations is not approved still do to the Manual S not being c pliant accordink Florida Energy Conservation Code—R403.7.1.2.1, exceeding the maximum allowable equipment cooling capacity ab• - the design cooling load. Building Mike Jones Building Inspector/Plans Examiner City of Atlantic Beach 800 Seminole Road Atlantic Beach, FL 32233 904.247.5844 Email:mjones@coab.us / 1 Cmot ided IQt ew Cornw•en11 2- / - I tI',,o/ Resubmittal Notes: All revisions and changes shall clearly stand out from the rest of the drawing on the sheet as a revision by way of completely encircling the change with "clouding".The revision shall also be identified as to the sequence of revision by indicating a triangle with the revision sequence number within it and located adjacent to the cloud.The revision date and revision sequence number shall also be indicated in a conspicuous location in the title block for each sheet on which a revision for that sequence occurs. For projects still in the initial review stage and permit pending, all sheets with revisions shall be inserted into each set of drawings.The original sheets must be clearly marked "VOID" but are to be left within the set of drawings. Complete new sets of drawings will not be accepted. ADDITIONAL ITEMS MAY BE REQUIRED DEPENDING UPON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW. OFFICE COPY CITY OF ATLANTIC BEACH " 1 '',` - 800 Seminole Road Atlantic Beach, Florida 32233 'kk: -. ) Telephone(904)247-5800 FAX(904)247-5845 fif319 r REVISION REQUEST SHEET OR CORRECTIONS TO REVIEW COMMENT Date: la-21,-17 Received by: Resubmitted: Permit Number:11-Seg.-3329 Original Plans Examiner: Project Name: 1%,00--- -TI,.. Project Address:►t.00-41c11-N Ce. coc.e. k Contractor( V& Cs0n,GS_l.l,c. m Contact Nae: ,cc , m€,,A.0._ Contact Phone :`IOt1►-lAcic-( 5t1 Contact ail: Revision/Plan Check/Permit Fee(s) Due: $ es a Description of Proposed Revision to Existing Permit: 1M.�u c)Ln. " .,►\-,A.4-if R eiloNv.n iNCiti dvNA— Additional Increase in Building Value: $ Lo o„r>,ha Additional S.F.';%p Site Plan Revised: Public W/U Approval: By signing belo. . (print name) nam_yS ce,c ,2. affirm that the above revision is inclusive . . , • proposed changes. 14, lel Signa if Contractor/Agent(Contractor must sign if increase in valuation) Date office Use Only Date: Approved: Refected: AV Notified by: __ Plan Review Comments: /ha Meal 3 c 0 0-pi iasci P- rar+r , exc." ,F,/ Lo_e; /.►•,^,lir UtC �., 2017 ? De artment review required Yes ' No f� uildi annin 8 Zo • flans Examiner Tree A ministrator Public Works Public Utilities y^ O/ Public Safety Date crested Oil bl6 Rev i Fire Services OFFICE COPY ,---=-------------- Vn ( .( CITY OF ATLANTIC BEACH "Y JAN 2 3 riU'i 800 Seminole Road Atlantic Beach,Florida 32233 REVISION REQUEST/CORRECTIONS TO PLAN REVIEW COMMENTS \—L3-/$ Date Revision to Issued Permit 1( Corrections to Comments Permit# 17— Sf f 33 Zcj —of Project Address i(0 00 NIK 4' rat e w 66 r Contractor/Contact Name 1- ivt f vet .XS Phone Email C,l ri • Col I t A S P Dfeuwtt ei S .Coy Description of Proposed Revision/Corrections: Permit Fee Due $ C--L atAie) R U ►tA--5 4-00 Com cte -F-Ofs r°° P ivi Additional Increase in Building Value $ Or Additional S.F. By signing below,I affirm the Revision is inclusive of the proposed changes. (printed name) Signature of Contractor/Agent(Contractor must sign if increase in valuation) Date (Office Use Only) Approved Denied Not Applicable to Department Revision/Plan Review Comments1 emirigewom De artment Review Required: / Building arming & Zoning r90-. Reviewed By Tree Administrator Public Worksi1•�O� Public Utilities et Public Safety Date Fire Services OFFICE COP Y FORM R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes,LLC Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval City,State.Zip: Jacksonville ,FL, Permit Number: 1 Owner: Dream Finders Homes,LLC Jurisdiction: 261300 Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2) 1. New construction or existing New(From Plans) 9. Wall Types(4721.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=23.0 4474.30 ft2 b.Frame-Wood,Adjacent R=23.0 246.67 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 5 d.N/A R= ft2 10.Ceiling Types (3858.0 sqft.) Insulation Area 5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 3858.00 ft2 6. Conditioned floor area above grade(ft2) 3858 b.N/A R= ft2 c. N/A R= ft2 Conditioned floor area below grade(ft2) 0 11.Ducts R ft2 7. Windows(697.0 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Main 6 707 • a. U-Factor: Dbl,U=0.36 600.97 ft2 b.Sup: Attic,Ret:Attic,AH:Attic 6 303 SHGC: SHGC=0.23 b. U-Factor: Dbl,U=0.62 96.00 ft2 12.Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.25 a.Central Unit 36.0 SEER:16.00 b.Central Unit 24.0 SEER:16.00 c. U-Factor: N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Heat Pump 36.0 HSPF:9.00 SHGC: b.Electric Heat Pump 24.0 HSPF:9.00 Area Weighted Average Overhang Depth: 5.916 ft. Area Weighted Average SHGC: 0.233 14.Hot water systems a.Natural Gas Tankless Cap: 1 gallons • 8. Floor Types (3858.0 sqft.) Insulation Area EF:0.800 • a.Slab-On-Grade Edge Insulation R=0.0 2318.00 ft2 b. Conservation features ' b.Floor Over Other Space R=0.0 865,00 ft2 None c.other(see details) R= 675.00 ft2 15.Credits Pstat Total Proposed Modified Loads: 83.48PASS Glass/Floor Area: 0.181 Total Baseline Loads: 113.57 . I hereby certify that the plans and specifications covered by Review of the plans and f�4,1' 10E Sx,1? ,. this calculation are in compliance with the Florida Energy specifications covered by this ti.- <'-a= ; 0°k Code. calculation indicates compliance u„ _ °'' 6' / with the Florida Energy Code. +t.rrnq '',, - '::� •„`.0 i"t " PREPARED BY: M 97 t.<7v. Before construction is completed ,,,,,, �°.-"•' DATE: 01 /11.4/ `d this building will be inspected for 0 '� l_o � ' compliance with Section 553.908 * `Y x Florida Statutes. '�1 ' I hereby certify that this building,as designed is' o fiance % C •• ••'s••,'''‘,.(C,. ..t,.. with the Florida Energy Code. ''` iQD ��4..+ OWNER/AGENT: tif BUILDING OFFICIAL: fri U,7,/ p� DATE: i ) I b I i$ DATE: 3-�/^ �/0 - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2017 PROJECT Title: Streit Residence 3858 Left S Bedrooms: 5 Address Type: Street Address Building Type: User Conditioned Area: 3858 Lot# Owner Name: Dream Finders Homes,LLC Total Stories: 2 Block/Subdivision: #of Units: i Worst Case: No PlatBook: Builder Name: Dream Finders Homes,LLC Rotate Angle: 0 Street:. Lot 2&23,Block 6 Cou i Permit Office: Duval Cross Ventilation: No County: Duval Jurisdiction: 261300 Whole House Fan: No City, State,Zip: Jacksonville , Family Type: Single-family FL, New/Existing: New(From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Jacksonville FL_JACKSONVILLE_INT 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume 1 Blockl 2318 23180 2 Block2 1540 13860 SPACES Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated 1 Main 2318 23180 Yes 3 2 1 Yes Yes Yes 2 2nd Floor 865 7785 No 2 2 1 Yes Yes Yes 3 Bonus Room 675 6075 No 1 1 1 Yes Yes Yes FLOORS V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio Main 264 ft 0 2318 ft2 ____ 0 0 1 2 Floor Over Other Space 2nd Floor ___ - 865 ft2 0 0 0 1 3 Floor over Garage Bonus Room ____ ____ 675 ft2 19 0 0 1 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Gable or Shed Metal 3598 ft2 998 ft2 Medium 0.6 N 0.9 No 20 33.7 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Unvented 0 2993 ft2 N N i 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5 1 FORM R405-2017 CEILING V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic(Unvented) Main 20 Blown 2318 ft2 0.11 Wood 2 Under Attic(Unvented) 2nd Floor 20 Blown 865 ft2 0.11 Wood 3 Under Attic(Unvented) Bonus Room 20 Blown 675 ft2 0.11 Wood WALLS / Adjacent Space Cavity Width Height Sheathing Framing Solar Below V # Ornt To WaiLType R-VaiuP Ft In Ft In ArPa R-vai"e Frartinn Ahsnr rradP°f 1 S Exterior Frame-Wood Main 23 61 0 10 0 610.0 ft2 0 0.23 0.6 0 2 S Garage Frame-Wood Main 23 24 8 10 0 246.7 ft2 0 0.23 0.01 0 _ 3 E Exterior Frame-Wood Main 23 59 8 10 0 596.7 ft2 0 0.23 0.6 0 _4 N Exterior Frame-Wood Main 23 61 0 10 0 610.0 ft2 0 0.23 0.6 0 _ 5 W Exterior Frame-Wood Main 23 59 8 10 0 596.7 ft2 0 0.23 0.6 0 _ 6 S Exterior Frame-Wood 2nd Floor 23 39 2 9 0 352.5 ft2 0 0.23 0.6 0 _ 7 E Exterior Frame-Wood 2nd Floor 23 23 4 9 0 210.0 ft2 0 0.23 0.6 0 _ 8 N Exterior Frame-Wood 2nd Floor 23 39 2 9 0 352.5 ft2 0 0.23 0.6 0 _ 9 W Exterior Frame-Wood 2nd Floor 23 23 4 9 0 210.0 ft 0 0.23 0.6 0 10 S Exterior Frame-Wood Bonus Room 23 24 0 9 0 216.0 ft2 0 0.23 0.6 0 11 E Exterior Frame-Wood Bonus Room 23 28 0 9 0 252.0 ft2 0 0.23 0.6 0 i I' _12 N Exterior Frame-Wood Bonus Room 23 24 0 9 0 216.0 ft2 0 0.23 0.6 0 13 W Exterior Frame-Wood Bonus Room 23 28 0 9 0 252.0 ft2 0 0.23 0.6 0 DOORS # Ornt Door Type Space Storms U-ValueFt Width In FHeight Area 1 W Wood Main None .4 3 8 24 ft2 • 2 S Wood Main None .4 2 8 8 21.3 ft2 �L WINDOWS Orientation shown is the entered,Proposed orientation. - • Wall Overhang # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 64.0 ft2 8 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 2 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 48.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 3 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 48.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 4 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 30.0 ft2 12 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 5 E 3 Vinyl Low-E Double Yes 0.62 0.25 N 96.0 ft2 12 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 6 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 18.7 ft2 10 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 7 N 12 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 8 W 13 Vinyl Low-E Double Yes 0.36 0.23 N 8.8 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 9 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 18.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 10 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 16.0 ft2 30 ft 8 in 1 ft 0 in Drapes/blinds Interior 5 11 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 5.0 ft2 30 ft 8 in 1 ft 0 in Drapes/blinds Interior 5 12 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 13 S 10 Vinyl Low-E Double Yes 0.36 0.23 N 15.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 14 S 6 Vinyl Low-E Double Yes 0.36 0.23 N 80.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2017 WINDOWS 1 Orientation shown is the entered, Proposed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 15 N 8 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 16 N 8 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 17 W 9 Vinyl Low-E Double Yes 0.36 0.23 N 8.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 18 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 14.2 ft2 8 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 19 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 3.6 ft2 1-ft 4 in 1 ft 0 in Drapes/blinds Interior 5 20 S 1 Vinyl Low-E Double Yes 0.36 0.23 N 14.2 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 21 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 21.3 ft2 23 ft 8 in 1 ft 0 in Drapes/blinds Interior 5 22 S 10 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 , 23 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 32.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 , 24 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 12.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 25 N 4 Vinyl Low-E Double Yes 0.36 0.23 N 18.0 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 26 E 3 Vinyl Low-E Double Yes 0.36 0.23 N 7.1 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 27 W 5 Vinyl Low-E Double Yes 0.36 0.23 N 7.1 ft2 1 ft 4 in 1 ft 0 in Drapes/blinds Interior 5 GARAGE V # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 684 ft2 684 ft2 92 ft 10 ft 1 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000305 3086.7 169.45 318.68 .2892 5 L. HEATING SYSTEM • # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split HSPF:9 36 kBtu/hr 1 sys#1 2 Electric Heat Pump/ None HSPF:9 24 kBtu/hr 2 sys#2 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER:16 36 kBtu/hr 1080 cfm 0.7 1 sys#1 2 Central Unit/ None SEER: 16 24 kBtu/hr 720 cfm 0.7 2 sys#2 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas Tankless Exterior 0.8 1 gal 60.9 gal 120 deg None 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5 ' FORM R405-2017 SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS / --Supply— —Return-- Air CFM 25 CFM25 HVAC# �/ # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Attic 6 707 ft2 Attic 240 ft2 Default Leakage Main (Default) (Default) 1 1 2 Attic 6 303 ft2 Attic 89 ft2 Default Leakage Attic (Default) (Default) 2 2 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Cooling Jan Feb Mar Apr Ma X Jun Jul Au Se Oct Nov Dec Venting lX]Jan ' Feb X Mar [X Apr May Jun Jul Aug Sep €X Oct [X Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling'(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 BO 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 -78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 II I 1/16/2018 12:50 PM EnergyGaugeO USA-FlaRes2017 Section R405.4.1 Compliant Software Page 5 of 5 FORM R405-2017 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD . ESTIMATED ENERGY PERFORMANCE INDEX* = 74 The lower the EnergyPerformance Index,the more efficient the home. Lot 2& 23, Block 6 Country Club Lane, Jacksonville , FL, 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Frame Wood,Exterior R=23.0 4474.30 ft2 b.Frame-Wood,Adjacent R=23.0 246.67 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 5 d.N/A R= ft2 10.Ceiling Types Insulation Area 5. Is this a worst case? No a.Roof Deck(Unvented) R=20.0 3858.00 ft2 6. Conditioned floor area(ft2) . 3858 b.N/A R= ft2 c.N/A R= ft2 7. Windows' Description Area ft2 a. U-Factor: Dbl,U=0.36 600.97 ft2 11.Ducts R a.Sup:Attic,Ret:Attic,AH:Main 6 707 SHGC: SHGC=0.23 b.Sup: Attic,Ret:Attic,AH:Attic 6 303 b. U-Factor: Dbl,U=0.62 96.00 ft2 SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 36.0 SEER:16.00 SHGC: b.Central Unit 24.0 SEER:16.00 d. U-Factor: N/A ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Heat Pump 36.0 HSPF:9.00 Area Weighted Average Overhang Depth: 5.916 ft. b.Electric Heat Pump 24.0 HSPF:9.00 Area Weighted Average SHGC: 0.233 8. Floor Types Insulation Area 14.Hot water systems Cap: 1 gallons a.Slab-On-Grade Edge Insulation R=0.0 2318.00 ft2 a.Natural Gas EF:0.8 b.Floor Over Other Space R=0.0 865.00 ft2 c.other(see details) R= 675.00 ft2 b. Conservation features None 15.Credits Pstat I • I certify that his home has comlied with the e for uilding Construction tthr ugh the above penergy saving Florida features which will be installed ll (orBexcce exceeded) °```p EKE s-rg A.,,, �,��,: Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: Lot 2&23, Block 6 Country Club Lane Permit Number: Jacksonville ,FL, MANDATORY REQUIREMENTS See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law (Section 553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found in Appendix RD. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. R402.4.1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1,as applicable to the method of construction.Where required by the code official,an approved third party shall inspect all components and verify compliance. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing • buildings in which the new construction is less than 85 percent of the building thermal envelope. • During testing: 1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures. 3. Interior doors,if installed at the time of the test,shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems,if installed at the time of the test,shall be turned off. 6. Supply and return registers,if installed at the time of the test,shall be fully open. R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907. R402.4.3 Fenestration air IeakageWindows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 L/s/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NERC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. • 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room,isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not more than 2.0 cfm(0.944 L/s).when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1:3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or (7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing(Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system,including the manufacturer's air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the entire system,including the manufacturer's air handler enclosure.Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause degradation of the material.Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory). Heated water circulation systems shall be in accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump.The system return pipe shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or Ul 515.Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1/16/2018 12:50 PM EnergyGaugee USA-FlaRes2017 -FBC 6th Edition(2017)Complian Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3%2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies(Mandatory). R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature setting range shall be from 100°F to 140°F(38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of combustion types of service water-heating systems to be turned off. R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar water-heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation including:Natural,Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole-house mechanical ventilation system fan efficacy. When installed to function as a whole-house mechanical ventilation system,fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. When installed to function as a whole-house mechanical ventilation system,fans shall meet the efficacy requirements of Table R403.6.1. 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable Indoor Air Quality,shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces.attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10 otherwise. R403.7 Heating and cooling equipment(Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMUIV (CFM) (CFM/WATT) (CFM) Range hoods Any 2.8 cfm/watt Any In-line fan Any 2.8 cfm/watt Any II Bathroom, utility room 10 1.4 cfm/watt <90 f� Bathroom,utility room 90 2.8 cfm/watt Any For SI: 1 cfm=28.3 L/min. a. When tested in accordance with HVI Standard 916 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space. Exceptions: 1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7:1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls(Mandatory) Snow-and ice-melting systems,supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F(10°C),and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F(4.8°C). R403.10 Pools and permanent spa energy consumption(Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation of such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors.Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating,computed over an operation season, is from site-recovered energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required. R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56.Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas(Mandatoryfhe energy consumption of electric-powered portable spas shall be controlled by the requirements of APSP-14. • SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps. Exception:Low-voltage lighting. • R404.1.1 Lighting equipment(Mandatory).Fuel gas lighting systems shall not have continuously burning pilot lights. • 1/16/2018 12:50 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Compile Page 5 of 5 2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes, LLC Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval City,State,Zip: Jacksonville , FL: Permit Number: Owner: Dream Finders Homes,LLC Jurisdiction: 261300 Design Location: FL,Jacksonville COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceiling/attic the insulation and anygaps in the air barrier shall be sealed. g p shall be aligned with the air barrier. Access openings,drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with sealed. a material having a thermal resistance of R-3 per inch Knee walls shall be sealed. minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows,skylights The space between window/door jambs and framing,and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above-garage subfloor decking,or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing,or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled by insulation that on Narrow cavities installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spacas. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated, Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall extend behind mein()and wiring Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air-sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall. Concealed When required to be sealed,concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover elates and walls or ceilinas a. In addition,inspection of log walls shall be in accordance with the provisions of ICC-400. 1/16/2018 12:51 PM EnergyGauge®USA-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1 FORM R405-2017 Envelope Leakage Test Report Performance FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Envelope Leakage Test Report Performance Method Project Name: Streit Residence 3858 Left S Builder Name: Dream Finders Homes,LLC Street: Lot 2&23,Block 6 Country Club Lane Permit Office: Duval City,State,Zip: Jacksonville , FL, Permit Number: Design Location: FL,Jacksonville Jurisdiction: 261300 Cond.Floor Area:: 3858 sq.ft. Cond.Volume: 37040 cu ft. Envelope Leakage Test Results Leakage Characteristics Regression Data: C: n: R: Single or Multi Point Test Data Required ACH(50)from HOUSE PRESSURE FLOW: FORM R405-2017 : -1 Pa cfm 2 Pa cfm Tested ACH(50) *: 3 Pa cfm *Tested leakage must be less than or equal to the 4 Pa cfm required ACH(50)shown on Form R405-2017 for 5 Pa cfm this building. If the tested ACH(50) is less than 3 the building must have a mechanical ventilation 6 Pa cfm system. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour in Climate Zones 1 and 2...Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7),Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f),(g),or(i)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: - 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2. Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3. Interior doors,if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Heating and cooling systems,if installed at the time of the test,shall be tumed off;and 6.Supply and return registers,if installed at the time of the test,shall be fully open. I hereby certify that the above envelope leakage Testing shall be conducted by either ;.- 4,cgg STAT-+� individuals as defined in Section ; ;..0 *�, performance results demonstrate compliance �* t.•• ••••%,�z :_ .� with Florida Energy Code requirements in 553.993(5)or(7), Florida Statutes or �t„ '` r • accordance with Section R402.4.1.2. individuals licensed as set forth in x : c• Section 489.105(3)(f), (g),or(i)or an a2 a approved third party.A written report of = • 1~ " the results of the test shall be signed '•.; r' SIGNATURE: by the third party conducting the test � ..,r.. r�• and provided to the code official. o 06 "" PRINTED NAME: BUILDING OFFICIAL: DATE: DATE: • 1/16/2018 12:51 PM EnergyGauge®USA-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1 Project Summary Date: 264/1644 (Rest of House) By: Renee Brown/SPG McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.com Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Notes: STREIT RESIDENCE Desi• n Information Weather: Jacksonville NAS, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 99 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 24 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 28167 Btuh Structure 21577 Btuh Ducts 3439 Btuh Ducts 4384 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31607 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load flittuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2591 Btuh Ducts 772 Btuh Central vent(0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 2318 2318 Equipment latent load :6 :tuh Volume (ft3) 23180 23180 Air changes/hour 0.23 0.12 Egiggrnent Total Load Sen+Lat) tuh Equiv.AVF (cfm) 90 48 Req. total capaci a . 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Trane Make Trane Trade TRANE Trade TRANE Model 4TWR7036B1 Cond 4TWR7036B1 AHRI ref 7599443 Coil TEM6A0C36H31++TDR AHRI ref 7599443 Efficiency 9.6 HSPF Efficiency 12.5 EER, 17 SEER Heating input Sensible cooling 25200 Btuh Heating output 32000 Btuh @ 47°F Latent cooling 10800 Btuh Temperature rise 24 °F Total cooling 36000 Btuh Actual air flow 1200 cfm Actual air flow 1200 cfm Air flow factor 0.038 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.89 Capacity balance point=32°F Backup: Input=9 kW, Output=31918 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wriptitsoft 2018-Jan-16 12:49:01 • - • Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1 ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S Project Summary Date: M a 2nd Floor By: Renee Brown/SPG McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web:www.mcgowansac corn Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Notes: STREIT RESIDENCE Desi• n Information Weather: Jacksonville NAS, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 99 °F Inside db 70 °F Inside db 75 °F Design TD 38 °F Design TD 24 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 13432 Btuh Structure 10552 Btuh Ducts 1886 Btuh Ducts 2473 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 15318 Btuh Use manufacturer's data y uteamwin multiplier 1. Infiltration tuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2385 Btuh Ducts 427 Btuh Central vent(0 cfm) 0 Btuh Heating Cooling (none) Area(ftp 1540 1540 Equipment latent load- tuh Volume (ft') 13716 13716 Air changes/hour 0.31 0.17 Equipment Total Load(Se.a+Lat) (.4 tuh Equiv.AVF(cfm) 72 38 Req.total capacity at 0.70 SHR 1.6 ton Heating Equipment Summary Cooling Equipment Summary Make Trane Make Trane Trade TRANE Trade TRANE Model 4TWR7024A1 Cond 4TWR7024A1 AHRI ref 7793615 Coil TEM6A0B24H21++TDR AHRI ref 7793615 Efficiency 8.5 HSPF Efficiency 12.5 EER, 17 SEER Heating input Sensible cooling 17500 Btuh Heating output 24000 Btuh @ 47°F Latent cooling 7500 Btuh Temperature rise 26 °F Total cooling 25000 Btuh Actual air flow 833 cfm Actual air flow 833 cfm Air flow factor 0.054 cfm/Btuh Air flow factor 0.064 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.82 Capacity balance point=21 °F Backup: Input=4 kW, Output= 15306 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrighisoti 2016-Jan-1612:49:01 Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2 Aftk ..eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S N A1r\ First Floor 6x12 tlldsrgWBf atOC �4 z 6 0 owner-...),:t, access 4" Q owners 8:10 8' 6 r_L 16x 16 12" 7- Rte.. 4"Fan 1 1 " 4x6 - :. 0 nest .% ,414" •• 6. • 4'Fan .� 9 86 4074.1 `I 1 4.4 z6 • ;1lJ 7 - 2x12 1' t0 - 8' 8x11 ��® 12x12 8- r 1. 4 � 12" • 4x8 • • 11 limor 4. 1 1 0 O•I an 1 ...o... � 1�� ....1 12" 12:6 12:6 j 106x.6 18210 106:.6 7' 24818 �- 9 6' 18 I „IMP5 ^ i 1,r,,,,.....t mtly 14x1486 a- 8. I Job#: McGowan's Heating & Air Conditioning Scale: 1 : 143 Performed by Renee Brown/SPG for: Page 1 Casey Conner 4850 Collins Road Comfort Builder by Wrightsoft 360 Corporate way.Suite 100 Orange Park,Fl 32073 18.0.08 RSU12270 Orange Park,FL 32073 Phone:904-278-0339 Fax:904-278-0366 2018-Jan-16 12:49:25 Phone:(904)644-7670 Fax:(904)239-3003 www.mcgowansac.com kore me owansac.com casey.conner@dreamfinders.com g y@ g ith Bonus single 2nd fl unit.rup N A.e Air* up 4"Fan 4' OM IOC -We! 10x6 .•• the toilet 5, P jeigi 16. f 10x6 UM .41!11111 '.6/ 1 11' !• !x8 12x6 tithe 12z 1201 _ future beth 5 mach 184 18 •:. �1 12• -. l0 x6 Milli12x6 12x6 12 xfi •0 xfi 5" �.. .. 10x58 7' store hall 16 x 1 .......) Mt6- Fir 9x4 1 14'la 12. 4 11111 — 12x12 I 10 xfi 9' 10x6 12x6mil 5.. 7" NIP 12x6 7' Job#: McGowan's Heating & Air Conditioning Scale: 1 : 143 Performed by Renee Brown/SPG for: Page 2 Casey Conner 4850 Collins Road Comfort Builder Uby1 27ghtsoft 360 Corporate Way,Suite 100 Orange Park,Fl 32073 18.0.08 RS20 Orange Park,FL 32073 Phone:904-278-0339 Fax:904-278-0366 Phone:(904)644-7670 Fax (904)239-3003 Bonus 12:49:25fln www.mcgowansac.com korey@mcgowansac.com ith Bonus single 2nd fl unit.rup casey.conner@dreamfinders.com Manual S Compliance Report Job. Date: X1°4 414 (Rest of House) By: Renee Brown/SPG McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road.Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web.www.mcgowansac.corn Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Cooling Equipment Design Conditions Outdoor design DB: 99.2°F Sensible gain: 23406 Btuh / Entering coil DB: 75.7°F Outdoor design WB: 80.2°F Latent gain: 7863 Btuh (/ Entering coil WB: 62.9°F Indoor design DB: 75.0°F Total gain: 31269 Btuh Indoor RH: 50% Estimated airflow: 1200 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Trane Model: 4TWR7036B1+TEM6A0C36H31++TDR Actual airflow: 1200 cfm Sensible capacity: 25200 Btuh 108%of load Latent capacity: 10800 Btuh 137%of load Total capacity: 36000 Btuh 1193/0 of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 31.7°F Heat loss: 31607 Btuh Entering coil DB: 69.7°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Trane Model: 4TWR7036B1+TEM6A0C36H31++TDR Actual airflow: 1200 cfm Output capacity: 32000 Btuh 101%of load Capacity balance: 32 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1200 cfm Output capacity: 9.4 kW 101%of load Temp. rise: 50 °F Meets all requirements of ACCA Manual S. wrightso t 2018-Jan-1612:49:01 Al� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1 ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S Manual S Compliance Report Job: Date: 6001e4 2nd Floor By: Renee Brown/SPG McGowan's Heating &Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.corn Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Cooling Equipment Design Conditions Outdoor design DB: 99.2°F Sensible gain: 13025 Btuh Entering coil DB: 75.8°F Outdoor design WB: 80.2°F Latent gain: 2812 Btuh Entering coil WB: 62.9°F Indoor design DB: 75.0°F Total gain: 15837 Btuh Indoor RH: 50% Estimated airflow: 833 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Trane Model: 4TWR7024A1+TEM6A0B24H21++TDR Actual airflow: 833 cfm Sensible capacity: 17500 Btuh 134%of load Latent capacity: 7500 Btuh 267%of load Total capacity: 25000 Btuh 158%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 31.7°F Heat loss: 15318 Btuh Entering coil DB: 69.7°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Trane Model: 4TWR7024A1+TEM6A0B24H21++TDR Actual airflow: 833 cfm Output capacity: 24000 Btuh 157%of load Capacity balance: 21 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 833 cfm Output capacity: 4.5 kW 100%of load Temp. rise: 19 °F Meets all requirements of ACCA Manual S. wrightsoft 2018-Jan-16 12:49:01 t Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2 AC ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S n , VI4 Duct System Summary Jo Date: ker6(,,4 -' (Rest of House) By: Renee Brown/SPG /� McGowan's Heating &Air Conditioning, Inc. 4850 Collins Road.Orange Park.Fl 32073 Phone.904-278-0339 Fax:904-278-0366 Email:koreylmcgowansac.corn Web:www.mcgowansac.corn Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Heating Cooling External static pressure 0.50 in H2O 0.50 in H2O Pressure losses 0.11 in H2O 0.11 in H2O Available static pressure 0.39 in H2O 0.39 in H2O Supply/return available pressure 0.280/0.110 in H2O 0.280/0.110 in H2O Lowest friction rate 0.084 in/100ft 0.084 in/100ft Actual air flow 1200 cfm 1200 cfm Total effective length (TEL) 466 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matt Ln (ft) Ln (ft) Trunk laundry C 1898 73 88 0.089 7.0 Ox 0 VIFx 75.4 240.0 st8 guest h 2632 100 97 0.086 7.0 Ox 0 VIFx 81.3 245.0 st8 bath 2 C 12 0 1 0.084 4.0 Ox 0 VIFx 89.3 245.0 st8 drop zone h 2718 103 68 0.089 7.0 Ox 0 VIFx 74.2 240.0 st8 pwdr c 12 0 1 0.132 4.0 Ox 0 VIFx 32.7 180.0 st7 foyer h 3515 133 133 0.128 8.0 Ox 0 VIFx 39.5 180.0 st7 family-A c 3849 155 178 0.106 9.0 Ox 0 VIFx 50.2 215.0 st6 family C 3849 155 178 0.113 9.0 Ox 0 VIFx 42.7 205.0 st6 butler C 8 0 0 0.130 4.0 Ox 0 VIFx 36.1 180.0 st7 pool bath h 1265 48 27 0.143 5.0 Ox 0 VIFx 31.5 165.0 st5 kitchen C 1422 49 66 0.154 6.0 Ox 0 VIFx 17.0 165.0 st5 kitchen-A C 1422 49 66 0.147 6.0 Ox 0 VIFx 25.4 165.0 st5 kitchen-B C 1422 49 66 0.161 6.0 Ox 0 VIFx 13.6 160.0 st5 wc-A c 12 0 1 0.084 4.0 Ox 0 VIFx 94.8 240.0 st8 wic h 968 37 23 0.134 5.0 Ox 0 VIFx 43.4 165.0 st4 owners bath h 2194 83 50 0.124 6.0 Ox 0 VIFx 55.5 170.0 st4 owners h 2185 83 79 0.135 6.0 Ox 0 VIFx 42.5 165.0 st4 owners-A h 2185 83 79 0.134 6.0 Ox 0 VIFx 43.6 165.0 st4 wrightsoft 2018-Jan-16 12:49:01 �^t.�C� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 1 /1COK ...eit Residence with Bonus single 2nd ft unit.rup Calc=MJ8 Front Door faces: S Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st6 Peak AVF 311 356 0.106 652 10.0 0 x 0 VinIFIx st5 st4 Peak AVF 286 232 0.124 524 10.0 0 x 0 VinIFIx stl st5 Peak AVF 504 580 0.106 738 12.0 0 x 0 VinIFIx stl st8 Peak AVF 276 254 0.084 351 12.0 0 x 0 VinIFIx st7 st7 Peak AVF 410 388 0.084 522 12.0 0 x 0 VinIFIx stl stl Peak AVF 1200 1200 0.084 550 20.0 0 x 0 ViniFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rsb3 Ox 0 479 407 131.4 0.084 610 12.0 Ox 0 VIFx rt1 rb7 Ox 0 721 793 90.0 0.122 449 18.0 Ox 0 VIFx ill Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rtl Peak AVF 1200 1200 0.084 550 ' 20.0 0 x 0 VinlFlx wrightsoft 2018-Jan-16 12:49:01 ��� Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 2 /R+M ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S Duct System Summary Date: � � 2nd Floor By: Renee Brown/SPG McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.com Project Information For: Casey Conner, Dream Finders Homes, LLC. 360 Corporate Way, Suite 100, Orange Park, FL 32073 Phone: (904)644-7670 Fax: (904)239-3003 Email: casey.conner@dreamfinders.com Heating Cooling External static pressure 0.50 in H2O 0.50 in H2O Pressure losses 0.11 in H2O 0.11 in H2O Available static pressure 0.39 in H2O 0.39 in H2O Supply/return available pressure 0.244/0.146 in H2O 0.244/0.146 in H2O Lowest friction rate 0.116 in/100ft 0.116 in/100ft Actual air flow 833 cfm 833 cfm Total effective length (TEL) 337 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk bed 3 c 1839 109 118 0.162 7.0 Ox 0 VIFx 20.7 130.0 st3 loft h 1093 59 58 0.121 6.0 Ox 0 VIFx 36.2 165.0 st9 loft-A h 1093 59 58 0.120 6.0 Ox 0 VIFx 38.0 165.0 st9 stairs up c 167 9 11 0.165 4.0 Ox 0 VIFx 22.6 125.0 st3 bath 3 c 980 59 63 0.120 6.0 Ox 0 VIFx 38.8 165.0 st9 bed 2 c 1406 73 90 0.121 7.0 Ox 0 VIFx 36.5 165.0 st9 wic 2 h 257 14 12 0.132 4.0 Ox 0 VIFx 19.8 165.0 st3 bath 4 h 920 50 42 0.163 5.0 Ox 0 VIFx 24.7 125.0 st3 wic 3 h 618 34 27 0.162 5.0 Ox 0 VIFx 20.0 130.0 st3 future bonus c 1127 54 72 0.125 6.0 Ox 0 VIFx 64.4 130.0 st2 future bonus-A c 1127 54 72 0.116: 6.0 Ox 0 VIFx 75.4 135.0 st2 store2 h 1333 72 59 0.126 6.0 Ox 0 VIFx 68.1 125.0 st2 stores h 2109 115 92 0.127 7.0 Ox 0 VIFx 66.6 125.0 st2 future bath 5 h 685 37 33 0.124 5.0 Ox 0 VIFx 66.5 130.0 st2 mech h 530 29 23 0.121 5.0 Ox 0 VIFx 71.7 130.0 st2 store hall c 64 4 4 0.125 4.0 Ox 0 VIFx 64.5 130.0 st2 Supply Trunk Detail Table Trunk Htg CIg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 366 355 0.116 466 12.0 0 x 0 VinIFIx st9 Peak AVF 251 268 0.120 341 12.0 0 x 0 VinIFIx st3 st3 Peak AVF 467 478 0.120 447 14.0 0 x 0 VinIFIx wrightsoft" 2018-Jan-1612:49:01 �tj- Comfort Builder by Wrightsoft 18.0.08 RSU12270 Page 3 IP ...eit Residence with Bonus single 2nd fl unit.rup Calc=MJ8 Front Door faces: S Return Branch Detail Table 1 I l I I I i I I I l I Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox 0 185 152 126.3 0.116 173 14.0 Ox 0 VIFx rt2 rb2 Ox 0 246 251 110.4 0.133 235 14.0 Ox 0 VIFx rt2 rb3 Ox 0 200 232 88.0 0.166 525 9.0 Ox 0 VIFx rt2 rb4 Ox 0 202 198 • 115.0 0.127 458 9.0 Ox 0 VIFx rt2 I i Return Trunk Detail Table l Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt2 Peak AVF 833 833 0.116 597 16.0 0 x 0 VinIFIx i I L _. . 1 wrightsoft 2018-Jan-16 12:49:01 Comfort Builder by Wrightsoft 18.0.08 RSU12270 Pae 4 A '..Cg ...eit Residence with Bonus single 2nd Fl unrt.rup Calc=MJ8 Front Door faces: S