600 COASTAL OAK LN - REVISION 2/20/18 -/-' L 3 f _______________i, i CITY OF ATLANTIC BEACH 800 Seminole Road , % A 44 FEB2 0 Atlantic Beach,Florida 32233 ,�¢��-. 2018 . REVISION REQUEST/CORRECTIONS TO PLAN REVIEW COMMENTS Date 2/20/2018 Revision to Issued Permit X Corrections to Comments Permit# RES 17-0265 Project Address 600 Coastal Oak Lane Contractor/Contact Name Audrey Reg n l e r Phone 904.595.5243 Email aregnier@tollbrothers.com Description of Proposed Revision/Corrections: Permit Fee Due $ 5'O. 00 Added two windows in master bedroom. Plans and ecaics attached. Additional Increase in Building Value $ Additional S.F. Bysigning below, Audrey Regnier g g affirm the Revision is inclusive of the proposed changes. (printed name) 2/20/2018 ignature of ntractor/Ag t(Contractor must sign if increase in valuation) Date (Office Use Only) Approved )r Denied Not Applicable to Department Revision/Plan Review Comments lOrt f cr c/ tG pick- tip S ci L' CCif s'I'S/ Oa/ Pl"-e . Department Review Required: ildin )-- Planning & Zoning R iewcd By Tree Administrator Public Works Public Utilities 3/1/20/ k Public Safety Date Fire Services • FORM R405-2017 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method OFrProject Name: Captiva 3933 Left S Builder Name: Toll Brothers,Inc. • Street: Lot 144 Atlantic Beach CC Permit Office: Atlantic Beach r I City,State,Zip: Atlantic Beach ,FL, Permit Number: 'tom 1 O P Y Owner: Toll Brothers,Inc. Jurisdiction: 261300 VV Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2) • 1. New construction or existing New(From Plans) 9. Wall Types(4055.0 sqft.) Insulation Area 2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3836.70 ft2 b.Frame-Wood,Adjacent R=13.0 • 218.33 ft2 • ' 3. Number of units,if multiple family 1 • c.N/A R= ft2 4. Number of Bedrooms 5 d.N/A R= ft2 • 5. Is this a worst case? No 10.Ceiling Types (2997.0 sqft.) Insulation Area • a.Under Attic(Vented) R=38.0 2687.00 ft2 6. Conditioned floor area above grade(ft2) 3933 b.Under Attic(Vented) R=19.0 310.00 ft2 Conditioned floor area below grade(ft2) 0 i c.N/A R= ft2 ' 11.Ducts R ft2 • 7. Windows(467.1 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:2nd Floor 6 205 a. U-Factor: Dbl,U=0.34 467.11 ft2 b.Sup: Attic,Ret:Attic,AH:2nd Floor 6 186 SHGC: SHGC=0.27 b. U-Factor: N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: - a.Central Unit 18.0 SEER:14.00 • b.Central Unit 36.0 SEER:14.00 • c., U-Factor N/A ft2 • SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A •ft2 a.Electric Heat Pump 18.0 HSPF:8.20 • SHGC: _ -b.Electric Heat Pump 36.0 HSPF:8.20 . Area Weighted Average Overhang Depth: 5.626 ft. . Area Weighted Average SHGC: 0.270 14.Hot water systems 8. FloorTypes (3933.0 sqft.) Insulation Area a.Natural Gas Tankless Cap:1 gallons EF:0.800 - a.Slab-On-Grade Edge Insulation • R=0.0 2722.00 ft2 b. Conservation features b.Floor Over Other Space R=0.0 936.00 ft2 None ' c.other(see details) R= .275.00 ft2 15.Credits Pstat . Glass/Floor Area: 0.119 Total Proposed Modified.Loads: 92.93 Total Baseline Loads: 100.43 PAS I hereby certify that the plans and specifications covered by Review of the plans and s,��'��'1.14E Srg 7`'�',v,.. • this calculation are in compliance with the Florida Energy specifications covered by this o w r='.L �>s ;. O�'+t • Code. calculation indicates compliance /�i„r�0d';�'.' c4'```.'. n � with the Florida Energy Code. E llavt,.,,_' ?:.```��,;.�0 PREPARED BYE--" �-� �! ...._ ': -,;H,.t�.. -+`,�.�o��G'�uisi ro,,.� Before construction is completed w �, �I 041: DATE: o 2- -/ -20/8 . this buildingwill be inspected for ;?' '..-1111-....,• 1111. • "" u g 9 p ' Y compliance with Section 553.908 * .. Florida Statutes. 1 ..4----- 'r :•'� I I with reby the Floridalfy that this Energy building,oas designed, is in compliance 4;'-IA 0O•D� � �,;+' OWNER/A ENT: • - .4.-i L' BUILDING OFFICIAL: p- DATE: G)0// ' / DATE: 6 '3-1•a oiO - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. -Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2). OFFICE COPY REVISION BP# "ESI - . 65 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 CalifffSo4- / ,i •i ; Page 1 of 5 SIGNED CI i FORM R405-2017 PROJECT Title: Captiva 3933 Left S Bedrooms: 5_ Address Type: Street Address Building Type: User Conditioned Area: 3933 Lot# Owner Name: Toll Brothers,Inc. Total Stories: .2. Block/Subdivision: #of Units: 1 Worst Case: . No PlatBook: • Builder Name: Toll Brothers,Inc. Rotate Angle: 0 Street: Lot 144 Atlantic Beach Permit Office: Atlantic Beach Cross Ventilation: No County: Duval Jurisdiction: 261300 Whole House Fan: No City,State,Zip: Atlantic Beach , . • • Family Type: Single-family FL, New/Existing: New(From Plans) • Comment: • CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site •97.5% 2.5% Winter Summer Degree Days Moisture Range ,,/ FL,Jacksonville FL JACKSONVILLE_INT 32 93 70 75 1281 49 Medium BLOCKS Number Name Area Volume ' 1 Blockl 2722 27220 . . 2 Block2 1211 10899 • SPACES Number Name Area Volume Kitchen Occupants Bedrooms 1111 ID Finished Cooled Heated 1 Main 2722 27220 Yes 4 3 • 1 • Yes Yes Yes 2 , 2nd Floor 1211 10899 No 2 .2 1 Yes Yes Yes FLOORS • V✓ -# Floor Type Space Perimeter Perimeter R-Value Area Joist R�Value Tile Wood Carpet 1 Slab-On-Grade Edge lnsulatio - Main 204 ft 0 2722 ft2 _ 0 0 1 2 Floor Over Other Space 2nd. Floor ____ ___ 936 ft2 0 0 •0 1 / 3 Floor over Garage 2nd Floor ____ 275 ft2 0• 0 0 1 ROOF Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested 7 Tested Insul. (deg) 1 Gable or Shed Metal 3352 ft2 750 ft2 Medium 0.6 N 0.9 No 0 26.6 • ATTIC V # Type Ventilation Vent Ratio.(1 in) Area RBS IRCC • / 1- Full attic Vented 300 ' 2997 ft2 N N • • 2/19/2018 2:44 PM EnergyGaugeO USA-FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2017 CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type • 1 Under Attic(Vented) 2nd Floor 38 Blown 1022 ft2 0.11 Wood 2 Under Attic(Vented) Main 38 Blown 1665 ft2 0.11 Wood i 3 Under Attic(Vented) 2nd Floor 19 Blown 189 ft2 0.11 Wood i 4 Under Attic(Vented) • Main 19 Blown • 121 ft2 0.11 Wood E • • WALLS Adjacent Cavity Width Height Sheathing Framing Solar Below • . 44L-Clal tTo lnrall Type Space R_value Ft In Ft In Area R-va(lia Fraction atSnr r:radp% 1 S Exterior Frame-Wood 2nd Floor 19 23 .2 9 0 208.5 ft2• 0 . 0.23 • 0.6 0 1. 2 S Exterior Frame-Wood Main 19 22 8 10 0 .226.7 ft2 0 0.23 0.6 0 • T 3 E Exterior Frame-Wood 2nd Floor 19 58 6 9 0 . 526.5 ft2 . 0 0.23 0.6. 0 T 4 E Exterior Frame-Wood Main 19 84 6 10 0 845.0 ft2 0 0.23 0.6. 0 • 5 N Exterior Frame-Wood 2nd Floor 19 23 .2 9 0 208.5 ft2 0 0.23 0.6 0 ' 6 N Exterior Frame-Wood Main 19 45 0 10 0 450.0 ft2 0 0.23. 0.6 0 7 W Exterior Frame-Wood 2nd Floor 19 58 6 9 0, 526.5 ft2 0 0.23 0.6 0 • 8 W Exterior Frame-Wood Main 19 84 6 10 0 845.0 ft2 0 0.23 0.6 0 _ 9 S Garage Frame-Wood • Main 13 21 10 10 0 .218.3 ft2 0 0.23 0.6 . 0 DOORS # Ornt Door Type Space Storms U-Value Ft Width In Ft Height Area • , 1 S Insulated Main None .4 3 8 24 ft2 J 2 S Insulated Main None .4 2 8 8 21.3 ft2 _ WINDOWS Orientation shown is the entered,Pro.osed orientation. . o Wall Overhang J '# Ornt ID .Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 S 1 Vinyl. Low-E Double Yes 0.34 0.27 N 15.0 ft2 1-ft 4 in 2 ft 0 in None Exterior 5 .2 S 1 Vinyl Low-E Double Yes 0.34 0.27 N 4.0 ft2 7 ft 4 in 2 ft 0 in None Exterior 5 3 S 1 Vinyl Low-E Double Yes 0.34 0.27 N 17.8 ft2 7 ft 4 in 2-ft 0 in None Exterior 5 4 S 2 Vinyl Low-E Double Yes 0.34 0.27 N 16.0 ft2 14 tit in 2 ft 0 in None Exterior 5 5• S 2 Vinyl Low-E Double Yes 0.34 0.27 N 42.0 ft2 7 ft.4 in .2 ft 0 In Drapes/blinds Exterior 5 -17 6 E 4 Vinyl Low-E Double Yes - 0.34 0.27 N 12.0 ft2. 1 ft 4 in .2 ft 0 in None Exterior 5 7 E .4 Vinyl Low-E Double .Yes ' 0,34 0.27 N 4.0 ft2 1 ft 4 in .2 ft 0 in None• Exterior 5 • 8 E 4 Vinyl Low-E Double Yes 0.34 0.27 N 12.0 ft2 11 ft 0 in 2 ft 0 in None • Exterior 5 9 N 5 Vinyl Low-E Double Yes 0.34 0.27 N 15.0 ft2 1 ft 4 in 2 ft 0 in Drapes/blinds Exterior 5 , 10 N 6 Vinyl Low-E Double Yes 0.34 0.27 N 48.0 ft2 17 ft 6 in .2 ft 0 in None Exterior 5 11 N 6 Vinyl Low-E Double Yes 0.34 0.27 N 64.0 ft2 .9 ft 6 in .2 ft 0 in None Exterior 5 12 N 6 Vinyl Low-E Double Yes 0.34 0.27 N 60.0 ft2 1 ft 4 in 2 ft 0 in Drapes/blinds Exterior 5 • 13 N 6 Vinyl Low-E Double Yes 0.34 0.27 N 18.0 ft2 1 ft 4 in 2 ft 0 in None Exterior 5 14 W 7 Vinyl Low-E Double Yes 0.34 0.27 N 30.0 ft2 1 ft 4:in 2 ft 0 in• Drapes/blinds . Exterior 5 15 E 3 Vinyl Low-E Double Yes 0.34 0.27 N 30.0 ft2 1 ft 4 in 2 ft 0 In None Exterior 5 / 16 E 3 Vinyl Low-E Double Yes 0.34 0.27 N 15.0 ft2 1 ft 4 in 2 ft 0 in Drapes/blinds Exterior 5 17 W 8 Vinyl Low-E Double Yes 0.34 0.27 N 36.0 ft2 1 ft 4 in 2 ft 0 in None Exterior 5 ' 2/19/2018 2:44 PM. EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 3 of 5 FORM R405-2017 WINDOWS Orientation shown is the entered,Pro sosed orientation. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC' Imp 'Area Depth Separation Int Shade Screening 1- 18 W 8 Vinyl Low-E Double Yes 0.34 0.27 N 12.0 ft2 1 ft 4 in 2 ft 0 in None Exterior 5 19 S 1 Vinyl Low-E Double Yes 0.34 0.27 N 5.4 ft2 1 ft 4 in 2 ft 0 in None Exterior 5 20 S 1 Vinyl Low-E Double Yes 0.34 0.27 N 10.9 ft2 1 ft 4 in 2 ft 0 In Drapes/blinds Exterior 5 GARAGE • # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height . Exposed Wall Insulation 1 536 ft2 536 ft2 '64ft 9ft 1 INFILTRATION •' # Scope Method • SLA CFM 50 ELA EqLA ACH • ACH 50 1 Wholehouse Proposed ACH(50) .000431 • 4447.2 244.15 •459.15 . :4087 • 7 . . HEATING-SYSTEM • •# System Type Subtype Efficiency Capacity Block Ducts • 1 Electric Heat Pump/ None HSPF:8.2 '18 kBtu/hr 2 sys#1 7 2 Electric Heat Pump/ None HSPF:8.2 36 kBtu/hr 1 • sys#2 , COOLING SYSTEM '# System Type Subtype " Efficiency Capacity Alr Flow SHR Block Ducts • / 1 Central Unit/ Split SEER:14 18 kBtu/hr 540 cfm 0.7 2 sys#1 • 2 ' Central Unit/ Split ' SEER:14 36 kBtu/hr 1080 cfm 0.7 1 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation f 1. Natural Gas Tankless Exterior 0.8 1 gal 60.9,gal . 120 deg .. .... None . • I SOLAR HOT WATER SYSTEM • ' FSEC Collector Storage Cert# Company Name System Model# Collector Model# Area Volume FEF • - • __ None None ft2 DUCTS ----Supply— ---Return-- Air CFM 25 CFM25 HVAC# J # Location R-Value Area Location Area r Leakage Type . Handler 'TOT OUT QN RLF Heat Cool 1 Attic 6 205 ft2 Attic 154 ft2 Default Leakage 2nd Floor (Default) (Default) 1 .1 • / 2 Attic 6 186 ft2 Attic 86 ft2 Default Leakage 2nd Floor (Default) (Default) 2 2. • • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5 FORM R405-2017 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Coolin H Jan H Feb Mar ( Ar [ )Ma X Jun [X]Jul X Au (X]Se Oct Nov DecHeating Jan Feb �X�Mar [ Apr [ ]MaJun ' Jul AueOctNov XDecVentin Jan Feb X Mar [X Apr (( ]]May [ Jun [[ ]]Jul [ Aug [ 1]Sep [X Oct IX Nov [ Dec • Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 '4 5 • 6 7 8 • •9 10 11 12 • Cooling(WD) AM 78 78 78 78 78 78 78. 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 • Cooling(WEH) AM 78 78 78 •78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 • 68 ' 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 . 68 68 68 68 68 ' PM 68 68 • 68 • 68 68 68' 68 68 68 68 66 66 • . MECHANICAL VENTILATION Type . ' Supply CFM' Exhaust CFM Fan Watts HRV Heating System Run Time Cooling System .. None • 0 0 0 2-Electric Heat Pum. 0% 2-Central Unit • • • • • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 5 of 5 .FORM R405-2017 • ENERGY PERFORMANCELEVEL (EPL) DISPLAY CARD • I ESTIMATED ENERGY PERFORMANCE INDEX* = 93 . • The lower the.EnergyPerformance Index, the more efficient the home. Lot 144 Atlantic Beach CC, Atlantic Beach , FL, . 1. New construction or existing New(From Plans) 9. Wall Types . Insulation Area • .2. Single family or multiple family Single-family a.Frame-Wood,Exterior R=19.0 3836.70 ft2 • b.Frame-Wood,Adjacent R=13.0 218.33 ft2 3. Number of units,if multiple family 1 . ' c.N/A R= ft2 • 4. Number of Bedrooms 5 d.N/A R= ft2 5. Is this a worst case? No 10:Ceiling Types Insulation Area a.Under Attic(Vented) R=38.0 2687.00 ft2 •6. Conditioned floor.area(f12) 3933 b.Under Attic(Vented) R=19.0 • 310.00 ft2 _ ft2 • 7. Windows** Description Area 11. .N /A R R ft2 a. U-Factor: Dbl,U=0.34 467.11 ft2a.Sup:Attic, Ret:Attic,AH:2nd Floor .. 6 205 • SHGC: SHGC=0.27 b.Sup: Attic,Ret:Attic,AH:2nd Floor 6 186 ' b. U-Factor: N/A 'ft2 SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 18.0 SEER:14.00 SHGC: b.Central Unit 36.0 SEER:14.00 d. U-Factor: N/A ft2 13.Heating systems • kBtu/hr Efficiency SHGC: ' a.Electric Heat Pump 18.0 HSPF:8.20 • Area Weighted Average Overhang Depth: 5.626 ft. . ..b.Electric Heat Pump • 36.0 HSPF:8.20 Area Weighted Average SHGC: . 0.270 • 8. Floor Types Insulation Area 14.Hot water systems • a.Natural Gas Cap:1 gallons a.Slab-On-Grade Edge Insulation R=0.0 .2722.00 ft2EF:0.8 b.Floor Over Other Space R=0.0 936.00 ft2 c.other(see details) R= 275.00 ft2 b. Conservation features • None • 15.Credits Pstat • • I certify that this home has complied with the Florida Energy Efficiency Code for Building a�"""� " Construction through the above energy saving features which will be installed (or exceeded) �+;+�p `� Esrq .;,, in this home before final inspection. Otherwise, a new EPL Display Card will be completed t ;r'r Y based on installed Cod- compliant features. 'n„„ �;y ,--__ <°',�0. ot. ' ij W: `� 1" 4'nt;„ Z ii . Ti Builder Signature: 7 &L _ . Date: �/c�t�//�j � ' N ._. p Address of New Home: City/FL Zip: �1-I Gv►�1`0 > X4.4. ' -,..........,x,0+ L�.c� C o�,5fa ( ��� L✓t �` �� .. ga)334'c°b we ,,�+° *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Email EnergyGauge tech support at techsupport@energygauge.com or see the EnergyGauge website at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building i Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 2/19/2018 2:44 PM EnergyGauge®USA.-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: Lot 144 Atlantic Beach CC Permit Number: Atlantic Beach ,FL, • MANDATORY REQUIREMENTS See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level(EPL)display card(Mandatory). The building official shall require that an energy performance level(EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law (Section 553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and • nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components • installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects theplans and specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found In Appendix RD. R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4:1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4:1:1 and R402.4:1.2.The sealing methods between dissimilar materials shall allow for differential expansion and contraction. • R402.4:1.1 Installation.The components of the building thermal envelope as listed in Table R402.4.1.1 shall be Installed in accordance with the manufacturer's Instructions and the criteria listed In Table R402.4.1.1,as applicable to the method of construction.Where required by the code official,an approved third party shall inspect all components and verify compliance. • R402.4;1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not'exceeding seven air changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in • accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7), Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: • ' 1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures. - 3. Interior doors,if installed at the time of the test,shall be open. • 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems,if installed at the time of the test,shall be turned off. 6. Supply and return registers,if installed at the time of the test,shall be fully open. R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907. • R402.4.3 Fenestration air Ieakage.Windows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot(1.5 L/s/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 Us/m2),when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site-built windows,skylights and doors. • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel-burning appliances. In Climate•Zones&through 8,where open combustion air ducts provide combustion air to open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room,isolated from inside the thermal envelope.Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage • between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not • • more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)'pressure differential.All recessed• • • luminaires shall be sealed with a gasket or caulk between the housing and the interior•wall or ceiling covering. • • • • SECTION R403 SYSTEMS . • R403:1 Controls. R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403:3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section C403.2.9.2.of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. • Duct tightness shall be verified by testing in accordance with ANSIIRESNET/ICC 380 by either individuals as defined in Section 553.993(5)or (7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in accordance with Section R403.3.3. • R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ,R403:3:3 Duct testing(Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1• Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa)across the system,including the • manufacturer's air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the entire system,Including the manufacturer's air handler enclosure.Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party,conducting the test and provided to the code official. R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. • R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) or below 55°F(13°C)shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,including that caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause • • degradation of the material.Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory). Heated water circulation systems shall bein accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible. R403.5.1;1 Circulation systems. Heated water circulation.systems shall be provided with a circulation pump.The system return • pipe shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited. • Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the . occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515.Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017)Complian Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3-Y=inches(89 mm)In the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies(Mandatory). R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature • setting range shall be from 100°F to 140°F(38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of combustion types of service water-heating systems to be turned off. R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of . Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed. • Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy . factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,-Test Methods for Solar Collectors, and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors In Installed solar water-heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal;and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code,Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation including:Natural, Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1•Whole-house mechanical ventilation system fan efficacy: When installed to function as a whole-house mechanical • ventilation system,fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be. . powered by an electronically commutated motor. R403.6.2 Ventilation air. When installed to function as a whole-house mechanical ventilation system,fans shall meet the efficacy requirements of Table R403.6.1. 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable Indoor Air Quality,shall be the maximum rates allowed for residential applications. • • 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces,attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. • • • 3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10 otherwise. R403.7 Heating and cooling equipment(Mandatory). R403.7:1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that • affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency ratingequal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6:1 ' WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM , MINIMUM EFFICACY a AIRFLOW RATE MAXIMUM (CFM) (CFMNVATT) (CFM) . Range hoods Any 2.8 cfm/watt Any In-line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom,utility room 90 2.8 cfm/watt Any For SI: 1 cfm=28.3 L/min. a. When tested in accordance with HVI Standard 916 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complla Page 3 of 5 MANDATORY REQUIREMENTS . (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's • expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.• ; Exceptions: • 1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the • calculated total sensible load but'not less than 80 percent of that load. 2. When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of equipment may be sized in accordance with good design practice. R403.7;1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. • • R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section,R403.7.1. R403.7.1.2:3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1:3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.. .2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls(Mandatory) Snow-and ice-melting systems,supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F(10°C),and no precipitation is falling and an automatic or manual control that.will allow shutoff when the outdoor temperature is above 40°F(4.8°C). R403.10 Pools and permanent spa energy consumption(Mandatory). - The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an , integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation of•such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors.Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar-and waste-heat-recovery pool heating systems. 3. Where pumps are powered exclusively from on-site renewable generation. • R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. . Exception: Where more than 70 percent of the energy for heating,computed over an operation season,is from site-recovered energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required. R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard. • R403.11 Portable spas(Mandatorg)he energy consumption of electric-powered portable spas shall be controlled by the requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS • R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps. Exception:Low-voltage lighting. • R404.1.1 Lighting equipment(Mandatory).Fuel gas lighting systems shall not have continuously burning pilot lights. • • • • • • • • 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 5 of 5 2017-AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Captiva 3933 Left S . Builder Name: Toll Brothers,Inc. Street: Lot 144 Atlantic Beach CC Permit Office: Atlantic Beach City,State,Zip: Atlantic Beach ,FL, Permit Number: Owner: Toll Brothers,Inc. Jurisdiction: 261300 Design Location: FL,Jacksonville • COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA • General A'continuous air barrier shall be instated in the building envelope. Air-permeable insulation shall • The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks or joints in the air barrier shall be sealed. The air barrier In any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit Ceiling/attic the insulation and anygaps in the air barrier shall be sealed. 9 P shall be aligned with the air barrier. Access openings,drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. • Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with sealed. a material having a thermal resistance of R-3 per Inch Knee walls shall be sealed. minimum. Exterior thermal envelope Insulation for framed walls shall be installed in substantial contact and • continuous alignment with the air barrier. • Windows,skylights The space between window/door jambs and framing,and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of• Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above-garage subfloor decking,or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing,or continuous insulation installed on the underside of floor framing and extends from the • bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where,provided.instead of floor insulation,insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit,or narrow Narrow cavities cavities shall be filled by insulation that on Installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. - thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls,or insulation that on installation readily conforms to available space shall extend behind pining and wiring. Shower/tub The air barrier instated at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. • be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication • exterior walls boxes or air-sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall • be sealed to the sub-floor or drywall. Concealed When required to be sealed,concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire snrinkler cover plates and walls or ceilings. a.In addition,inspection of log walls shall be in accordance with the provisions of ICC-400. 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1 FORM R405-2017 Envelope Leakage Test Report Performance FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Envelope Leakage Test Report Performance Method Project Name: Captiva 3933 Left S Builder Name: Toll Brothers, Inc. Street: Lot 144 Atlantic Beach CC Permit Office: Atlantic Beach City,State,Zip: Atlantic Beach , FL, Permit Number: Design Location: FL,Jacksonville • Jurisdiction: 261300 • Cond.Floor Area:: 3933 sq.ft. Cond.Volume: 38119 cu ft. Envelope Leakage Test Results Leakage Characteristics Regression Data: • C: n: R: Single or Multi Point Test Data Required ACH(50)from • HOUSE PRESSURE FLOW: FORM R405-2017 : 1 Pa cfm 2 Pa cfm Tested ACH(50)': 3 Pa cfm *Tested leakage must be less than or equal to the 4 Pa cfm required ACH(50)shown on Form R405-2017 for 5 Pa cfm this building. If the tested ACH(50) is less than 3 • the building must have a mechanical ventilation 6 Pa cfm system. R402.4:1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour . In Climate Zones 1 and 2...Testing shall be conducted with a blower door at a pressure of 0.2 Inches w.g.(50 Pascals).Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7),Florida Statutes or Individuals licensed as set forth in Section 489.105(3)(f),(g),or(I)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing. shall be performed at any time after creation of all penetrations of the building thermal envelope. • During testing: 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration control measures; 2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration control measures; 3.Interior doors, if installed at the time of the test,shall be open; 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and • 6.Supply and return registers,if installed at the time of the test,shall be fully open. . 0 rr04"e...A, I hereby certify that the above envelope leakage Testing shall be conducted by either -OE XE.STA •,. performance results demonstrate compliance individuals as defined in Sectionti a" t • ©�; with Florida Energy Code requirements in 553.993(5)or(7), Florida Statutes or • ii�f `6 r�r `''• individuals licensed as set forth in , roo f, un Q accordance with Section R402.4.1.2. ; "110 • Section 489.105(3)(f), (g),or(i)or an approved third party.A written report of 1,0:' t, ; SIGNATURE: the results of.the test shall be signed * • by the third party conducting the test• 1 - S. 4' • and provided to the code official. °a 'pxj . . PRINTED NAME: � • BUILDING OFFICIAL: DATE: DATE: 2/19/2018 2:44 PM EnergyGauge®USA-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1 Project Summary Job: Lot 144 ABCC {. , , >�,,s, Date: :' 1St By: Saldie Guintivano �lfcrGtam�� " -" McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.corn Web:www.mcgowansac.corn .:=Fri til,.f�lrit atic►ii'c�;.._ . . . For: Toll Architecture Notes: Captiva Desi. mInformat Qi r' Weather: Jacksonville NAS, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 99 °F Inside db 75 °F Inside db 70 °F Design TD 43 °F Design TD 29 °F Daily range M Relative humidity 50 Moisture difference 71 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 24789 Btuh Structure 19843 Btuh Ducts 3744 Btuh Ducts 4560 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28533 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 22304 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3(partial)/1 Pressure/AVF 50 a/62 cfm Structure 883 Btuh Ducts 1119 Btuh Central vent(0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 2722 2722 Equipment latent load 6512 Btuh Volume(ft') 26923 26923 Air changes/hour 0.01 0.00 Equipment Total Load (Sen+Lat) 28816 Btuh Equiv.AVF (cfm) 3 2 Req. total capacity at 0.70 SHR 2.7 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model CH14NB0360000B0 Cond CH14NB0360000B0 AHRI ref 9162429 Coil FB4CNP036L AHRI ref 9162429 Efficiency 8.2 HSPF Efficiency 11.5 EER, 14 SEER Heating input ,Sensible cooling 23100 Btuh Heating output 33800 Btuh @ 47°F Latent cooling 9900 Btuh Temperature rise 29 °F Total cooling 33000 Btuh Actual air flow 1050 cfm Actual air flow 1050 cfm Air flow factor 0.037 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.92 Capacity balance point=29°F Backup: Input=8 kW, Output=27218 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2017-Oct-05 11:55:36 W rll[11tSofC" Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 1 ,rtCGtr. ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Project Summary Job: Lot 144 ABCC : r ;--' 2nd Date: By: Saldie Guintivano Aft-10a".� McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey©mcgowansac.com Web:www.mcgowansac.corn -�l ���.�.. �.����.�� �Qg.�� �: t�rca edt�lrfarrriatta ni.���_. � , �,m., ..> r For: Toll Architecture Notes: Captiva is n1 Weather: Jacksonville NAS, FL, US Winter Design Conditions Summer Design Conditions Outside db 32 °F Outside db 99 °F Inside db 75 °F Inside db 70 °F Design TD 43 °F Design TD 29 °F Daily range M Relative humidity 50 % Moisture difference 71 gr/Ib Heating Summary . Sensible Cooling Equipment Load Sizing Structure 10574 Btuh Structure 11230 Btuh Ducts 1271 Btuh Ducts 1702 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 11844 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load 12380 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3 partial)/ 1 Pressure/AVF 50 Pa/62 cfm Structure 465 Btuh Ducts 357 Btuh Central vent(0 cfm) 0 Btuh Heating Cooling (none) Area(ft2) 1211 1211 Equipment latent load 3099 Btuh Volume(ft3) 12015 12015 Air changes/hour 0.01 0.01 Equipment Total Load (Sen+Lat) 15479 Btuh Equiv.AVF (cfm) 2 1 Req.total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model CH14NB0180000A0 Cond CH14NB0180000A0 AHRI ref 9162108 Coil FB4CNP018L AHRI ref 9162108 Efficiency 8.2 HSPF Efficiency 11.5 EER, 14 SEER Heating input Sensible cooling 12460 Btuh Heating output 17600 Btu h @ 47°F Latent cooling 5340 Btuh Temperature rise 31 °F Total cooling 17800 Btuh Actual air flow 525 cfm Actual air flow 525 cfm Air flow factor 0.044 cfm/Btuh Air flow factor 0.041 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.94 Capacity balance point=23°F Backup: Input=4 kW, Output= 12206 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 6 wt"ightsoft: Comfort Builder by Wrightsoft 17.0.23 RSU03444 2017-Oct-0511:5ge 2 Page 2 ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S N . 13 Albk . 2nd Floor bed 4 12x6 12x12 7 9" ..r r - ,...........1 t14' Fi1S :beleII . 18 14 16x16 gl■ . e 14" Ink loft', 1 6 x 12 7" open to b>.w i 2-way 3"Fan stairNW LIJ bath 3:`' 12" 6 x 14 • bed3 i N /i ‘ 1st Floor 12x6 6 x 12 baster dining 7" 12x6 16x16 12x6 14" a• 7., 12" qre ■ 4x8 his d 4"hers 100 4x8 0O 6x12 14" EpowkwoSi kitchen 4 x 8 14x 64 5 1 " 0' 10" 3"Fan +++ m bath + 3"Fan 411111L161111114.1 µ'+18„ 10 x 6 5., to 24x188x4 Pantry. 10x6 618x4 16" 4" laundry6" 4, 6 x 11 stnk 2".. 5' 10 x 6 ra \ 12x12 a 3"Fan 10x10 hall s 11 s" study taus Il 3"Fan .•et th'z n 12 x 12 x4 910x6 ' 8x4�,.y, 5" 10x6 4" y 6 fOV 12 x 6 garage bed 2 Job#: Lot 144 ABCCMcGowan's Heating & Air Conditioning Scale: 1 : 11s Performed by Saldie Guintivano for: Page 2 Toll Architecture 4850 Collins Road Comfort Builder by Wrightsoft Orange Park,Fl 32073 17.0.23 RSU03444 Phone:904-278-0339 Fax:904-278-0366 2017-Oct-05 11:55:53 www.mcgowansac.com korey@mcgowansac.com ...Brothers\Captiva 3933 left S.rup Manual S Compliance Report Job: Lot 144 ABCC Date: 'fCc '�t,j3 Y 1St By: Saldie Guintivano McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web.www.mcgowansac.com For: Toll Architecture Cooling: Manual S Compliance Report Date: Lot 144 ABCC f j 2nd By: Saldie Guintivano A1ctocv�u - . McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:korey@mcgowansac.com Web:www.mcgowansac.com i �aJ +c °lnfrnn�t� n' . • For: Toll Architecture , O,QOling, quipmen Design Conditions Outdoor design DB: 99.2°F Sensible gain: 12380 Btuh Entering coil DB: 71.0°F Outdoor design WB: 80.2°F Latent gain: 3099 Btuh Entering coil WB: 59.0°F Indoor design DB: 70.0°F Total gain: 15479 Btuh Indoor RH: 50% Estimated airflow: 525 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NB0180000A0+FB4CNP018L Actual airflow: 525 cfm Sensible capacity: 12272 Btuh 99%of load Latent capacity: 3074 Btuh 99%of load Total capacity: 15346 Btuh 99%of load SHR: 80% HeatingEquipmen Design Conditions Outdoor design DB: 31.7°F Heat loss: 11844 Btuh Entering coil DB: 74.5°F Indoor design DB: 75.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH 14NB0180000A0+FB4CNP018L Actual airflow: 525 cfm Output capacity: 13189 Btuh 111%of load Capacity balance: 23 °F Supplemental heat required: 0 Btuh Economic balance: -32 °F Backup equipment type: Elec strip - Manufacturer: Model: Actual airflow: 525 cfm Output capacity: 3.6 kW 103%of load Temp. rise: 68 °F Meets are all requirements of ACCA Manual S. 2017-Oct-O5 11:55:36 WCtghtsaft. Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 2 ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Duct System Summary Job: Lot 144 ABCC '•;� r3 Date: J J J '�'' 1st Air---alBy: Saldie Guintivano McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax 904-278-0366 Email:korey@mcgowansac.com Web:www.mcgowansac.com i ^c �I 4 'u a{'.? ,M,.st,:' ' S''�s Y .e7e , ,.:: l ..r- ,Pr ie:C. nItif rr Itonio . Y t !,;;... .. For: Toll Architecture Heating Cooling External static pressure 0.50 in H2O 0.50 in H2O Pressure losses 0.11 in H2O 0.11 in H2O Available static pressure 0.39 in H2O 0.39 in H2O Supply/return available pressure 0.273/0.117 in H2O 0.273/0.117 in H2O Lowest friction rate 0.069 in/100ft 0.069 in/100ft Actual air flow 1050 cfm 1050 cfm Total effective length(TEL) 563 ftupp�y. rar� t� Ril �I _ Design Htg CIg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln(ft) Trunk bath 2 h 1459 54 46 0.073 5.0 Ox 0 VIFx 78.6 295.0 st10 bed 2 h 3836 141 91 0.075 - 7.0 Ox 0 VIFx 79.1 285.0 st10 dining C 3350 126 144 0.096 7.0 Ox 0 VIFx 50.3 235.0 st5 foyer h 1752 64 56 0.069 6.0 Ox 0 VIFx 93.5 300.0 st10 great C 1440 47 62 0.096 7.0 Ox 0 VIFx 50.5 235.0 st5 great-A c 1440 47 62 0.097 7.0 Ox 0 VIFx 45.2 235.0 st5 great-B c 1440 47 62 0.120 6.0 Ox 0 VIFx 31.5 195.0 st4 hers h 836 31 14 0.076 4.0 Ox 0 VIFx 72.5 285.0 st6 his c 11 0 0 0.080 4.0 Ox 0 VIFx 66.5 275.0 st6 kitchen c 3920 137 169 0.118 8.0 Ox 0 VIFx 36.1 195.0 st4 laundry C 1652 38 71 0.117 5.0 Ox 0 VIFx 38.9 195.0 st4 m bath h 1095 40 37 0.091 5.0 Ox 0 VIFx 55.1 245.0 st9 master h 3071 113 91 0.078 7.0 Ox 0 VIFx 64.2 285.0 st6 master-A h 3071 113 91 0.078 7.0 Ox 0 VIFx 69.9 280.0 st6 pantry-A C 120 3 5 0.121 4.0 Ox 0 VIFx 31.2 195.0 st4 sink 2 h 474 17 8 0.088 4.0 Ox 0 VIFx 61.1 250.0 st9 study c 852 30 37 0.117 6.0 Ox 0 VIFx 33.4 200.0 st4 we C 69 1 3 0.076 4.0 Ox 0 VIFx 74.6 285.0 st6 wic3 c 9 0 0 0.072 4.0 Oxo VIFx 81.6 295.0 st10 } wrl htsoft' 2017-Oct-05 11:55:36 1 '� � Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 1 ACC. ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st9 Peak AVF 317 238 0.069 582 10.0 0 x 0 VinIFIx st8 st4 Peak AVF 733 812 0.076 582 16.0 0 x 0 VinIFIx st2 st8 Peak AVF 317 238 0.069 582 10.0 0 x 0 VinIFIx st7 st2 Peak AVF 1050 1050 0.069 752 16.0 0 x 0 VinIFIx st7 Peak AVF 317 238 0.069 582 10.0 0 x 0 VinIFIx st2 st10 Peak AVF 260 193 0.069 588 9.0 0 x 0 VinIFIx st9 st6 Peak AVF 259 200 0.076 329 12.0 0 x 0 VinIFIx st5 st5 Peak AVF 478 468 0.076 448 14.0 0 x 0 VinIFIx st4 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb7 Ox 0 511 604 169.0 0.069 565 14.0 Ox 0 VIFx rt2 rb4 Ox 0 222 208 150.6 0.078 159 16.0 Ox 0 VIFx rt2 rb2 Ox 0 317 238 148.7 0.079 909 8.0 Ox 0 VIFx rt2 _ . . Return Trunk-Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt2 Peak AVF 1050 1050 0.069 594 18.0 0 x 0 VinIFIx _r wri htso ft 2017-Oct-05 11:5ge , 2„ �” �- � Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 2 .ACCN ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Duct System Summary Job: Lot 144 ABCC Date: ,��fc�� `oul ait� -‘t--.7;',. 2nd By: Saldie Guintivano McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax 904-278-0366 90 4-278-0366Email:koreyimcgowansac.com Web.www.mcgowansac.corn M-;�L, a `.+:F z. „i.i�. . ..�. ��vi_ ... ret«Ia , . .Pgjcnformaior For: Toll Architecture Heating Cooling External static pressure 0.50 in H2O 0.50 in H2O Pressure losses 0.11 in H2O 0.11 in H2O Available static pressure 0.39 in H2O 0.39 in H2O Supply/return available pressure 0.240/0.150 in H2O 0.240/0.150 in H2O Lowest friction rate 0.097 in/100ft 0.097 in/100ft Actual air flow 525 cfm 525 cfm Total effective length (TEL) 403 ft supplyIBranch.t etall Table` Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR - (in) (in) Matl Ln (ft) Ln(ft) Trunk • bath 3-A h 532 24 21 0.101 4.0 Ox 0 VIFx 36.3 200.0 st3 bed 3 c 3344 118 136 0.099 - 8.0 Ox 0 VIFx 43.2 200.0 st3 bed 4 h 2439 108 99 0.146 7.0 Ox 0 VIFx 19.0 145.0 st1 living c 2069 80 84 0.103 7.0 Ox 0 VIFx 32.6 200.0 st3 living-A c 2069 80 84 0.097 7.0 Ox 0 VIFx 42.8 205.0 st3 loft-A h 2603 115 102 0.145 7.0 Ox 0 VIFx 15.2 150.0 st1 Supply:TrUfI ,DatailTabie Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk • st3 Peak AVF 302 324 0.097 413 12.0 0 x 0 VinIFIx st1 st1 Peak AVF 525 525 0.097 491 14.0 0 x 0 VinIFIx Retu'rtr Branch Detail Table. Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb6 Ox 0 139 123 120.0 0.125 315 9.0 Ox 0 VIFx rt1 rb5 Ox 0 160 168 155.6 0.097 308 10.0 Ox 0 VIFx rt1 rb3 Ox 0 226 234 109.5 0.137 219 14.0 Ox 0 VIFx rt1 2017-Oct-05 11:55:36 *:. W rightsoft Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 3 Av K ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Return„Trun Defied Tble _. .,. _ Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt1 Peak AVF 525 525 0.097 491 14.0 0 x 0 ViniFlx • 2017-Oct-05 11:55:36 �L wrightsoft Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 4 ACC ..\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Static Pressure and Friction Rate Job: Lot 144 ABCC • Date: dyi t +ICGF 1st By: Saldie Guintivano �j McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax:904-278-0366 Email:koray@mcgowansac.com Web:www.mcgowansac.com rN=� Fja.. ...,. � .. nfor131'atiQna • ...>. For: Toll Architecture Available',Static';�Pressur , Heating Cooling (in H2O) (in H2O) External static pressure 0.50 0.50 Pressure losses Coil 0.06 0.0E Heat exchanger 0 0 Supply diffusers 0.02 0.02 Return grilles 0.03 0.02 Filter 0 0 Humidifier 0 0 Balancing damper 0 0 Other device 0 0 Available static pressure 0.39 0.39 Total Effective.lien.`th Supply Return (ft) (ft) Measured length of run-out 18 22 Measured length of trunk 75 17 Equivalent length of fittings 300 130 Total length 394 169 Total effective length 563 Friction Rats Heating Cooling (in/100ft) (in/100ft) Supply Ducts 0.069 OK 0.069 OK Return Ducts 0.069 OK 0.069 OK Fitting Equivalent Length Details Supply 11C=40,4AD=60, 11G=5, 11G=5, 11G=5, 11C=40, 11G=5, 111=10, 111=10, 11G=5, 11G=5, 111=10, USR1=100: TotalEL=300 Return 11C=40, 6L=20, 11G=5, 11G=5, 11G=5, 111=10, 111=10, 5E2=35:TotalEL=130 2017-Oct-05 11:55:36 - wrightsoft Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 1 ACCk ...\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S Static Pressure and Friction Rate Job: Lot 144 ABCC Date: ff(1A1p 2110 By: Saldie Guintivano II! McGowan's Heating & Air Conditioning, Inc. 4850 Collins Road,Orange Park,Fl 32073 Phone:904-278-0339 Fax 904-278-0366 Email:korey@mcgowansac.con,Web:www.mcgowansac.com t � �F/e /��/iT{, 0 ?t}, ., ,F.�y ,Y} ;.;.w°N yitMScP , ",'.'"3;. ;. . .€;',i-:.Projedt�;lnf rrn tiow:' For: Toll Architecture . 2,5 Available;$t,Pressure. Heating Cooling (in H2O) (in H2O) External static pressure 0.50 0.50 Pressure losses Coil 0.06 0.0E Heat exchanger 0 0 Supply diffusers 0.02 0.02 Return grilles 0.03 0.02 Filter 0 0 Humidifier 0 0 Balancing damper 0 0 Other device , 0 0 Available static pressure 0.39 0.39 Total. ffectiye,.Length Supply Return (ft) (ft) Measured length of run-out 13 40 Measured length of trunk 30 6 Equivalent length of fittings 205 110 Total length 248 156 Total effective length 403 - Friction:,Rate Heating Cooling (in/100ft) (in/100ft) Supply Ducts 0.097 OK 0.097 OK Return Ducts 0.097 OK 0.097 OK Fitting ;equivalent Length•Detells. Supply 4AD=60, 11C=40, 11 G=5, 11G=5, 11C=40, 11G=5, 11G=5, 1A=35, 11G=5, 11G=5:TotalEL=205 Return 6L=20, 11C=40, 11G=5, 11G=5, 5E2=35, 11 G=5:.TotalEL=110 t wri htso ai L 2017-Oct-05 11:55:36 Glk, Comfort Builder by Wrightsoft 17.0.23 RSU03444 Page 2 ..\Builders\Toll Brothers\Captiva 3933 left S.rup Calc=MJ8 Front Door faces: S