Loading...
303 ATLANTIC BLVD - SPRINKLER SYSTEM PERMIT rLy f. J � � 'S S CITY OF ATLANTIC BEACH , "' 800 SEMINOLE ROAD ATLANTIC BEACH, FL 32233 !Ji31> INSPECTION PHONE LINE 247-5814 FIRE - SUPPRESSION MUST CALL BY 4PM FOR NEXT DAY INSPECTION: 247-5814 PERMIT INFORMATION: PERMIT NO: FIRE18-0001 Description: install 65-head fire sprinkler system Estimated Value: 30000 Issue Date: 3/2/2018 Expiration Date: 8/29/2018 PROPERTY ADDRESS: Address: 303 ATLANTIC BLVD RE Number: 169729 0000 PROPERTY OWNER: Name: JUNKSHIRLEY Address: 915 13TH ST N JACKSONVILLE BEACH, FL 32250-3653 GENERAL CONTRACTOR INFORMATION: Name: Address: Phone: Name: FIRE SPRINKLER SERVICES NE FLA Address: PO BOX 23787 JACKSONVILLE, FL 32241 Phone: PERMIT INFORMATION: Please see attached conditions of approval. WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOU PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT. NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that may be found in the public records of this county, and there may be additional permits required from other governmental entities such as water management districts, state agencies, or federal agencies. * A notice of Commencement is only required for work exceeding an estimated value of $2,500. For HVAC work, a Notice of Commencement is only required when HVAC work exceeds and estimated value of$7,500. MECHANICAL PERMIT APPLICATION CITY OF ATLANTIC BEACH 800 Seminole Rd Atlantic Beach, FL 32233 FEB 2 6 2018 Ph(904) 247-5826 Fax (904)247-5845 91 ft_Gil-0ogr JOB ADDRESS: 3 0 3 4 (ten -c IS G,a PERMIT# PROJECT VALUE $ 3 Or U a v ARI# REQUIRED Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION Air Conditioning: Unit Quantity Tons Per Unit Heat: Unit Quantity BTU's Per Unit Seer Rating Duct Systems: Total CFM REQUIRED REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION Air Conditioning: Unit Quantity Tons Per Unit Heat: Unit Quantity_ BTU's Per Unit Seer Rating Duct Systems: Total CFM REQUIRED --,\ FIRE PREVENTION 6-1 fr Fire Sprinkler System Quantity 65- (Requires 3 sets of plans) Fire Standpipe Quantity (Requires 3 sets of plans) Underground Fire Main Value (Requires 3 sets of plans) Fire Hose Cabinets Quantity (Requires 3 sets of plans) Commercial Hoods Quantity (Requires 3 sets of plans) Fire Suppression Systems Quantity (Requires 3 sets of plans) FIRE PLACES MISCELLANEOUS: Prefabricated Fireplace Qty Automobile Lifts Gas Piping Outlets Boilers BTU's Elevators/Escalators ALL OTHER GAS PIPING Heat Exchanger Quantity of Outlets Pumps #Vented Wall Furnaces Refrigerator Condenser BTU's # Water Heaters Solar Collection Systems Tanks (gallons) Wells OTHER: milimmommumummimmomommommi Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction. Property Owners Name Co ap 703 .Tcv 0 L Phone Number Mechanical Company 1-i rt' .Ser k, St r v. GP 11.6 1 P t Office Phone 2-62.-/o02 Fax Co. Address: P•O,3o-10. Z?7g7 City k State PL Zip ?).24-/ License Holder(Print): Zre yLIN -04-,- r State Certification/Registration# /'Z2 o1Gaot Z°a2. o , -.-.." -T -, Rnse ', older .ice MY COMMISSION k G7 042984 �j I Before me this d LP day of Ft-b f +& i 20 XU EXPIRES:October 2i,2020 Li' - ,,nded Thru Notary Public Underomters :: Signature of Notary Public <-_ 4iic6 ImAIN OFFICE COP Approved By Permit Desk Building Department City of Atlantic Beach,FL Jacks°nvil/e �' ira p . , r18 tian t.7 F�8 2 2 20 Qoor _ Fire Protection by Computer Desiglsy "Cep ePri, ttrgt, oNsZS /1/04- Fire Sprinkler Serv. of NE FL P.O. Box 23787 Jacksonville, FL 32241 904-262-1002 Job Name : Kitchen Area Building : Coop Restaurant 303 Location : 303 Atlantic Blvd, Atlantic Beach, FL System : Wet Contract : Data File : Coop Restaurant 303.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fire Sprinkler Serv. of NE FL Page 1 Kitchen Area Date Hydraulic Design Information Sheet Name - Kitchen Area Date - 1-25-2018 Location - 303 Atlantic Blvd, Atlantic Beach, FL Building - Coop Restaurant 303 System No. - Wet Contractor - Contract No. - Calculated By - CEM Drawing No. - 1 of 1 Construction: ( ) Combustible (X) Non-Combustible Ceiling Height - 8-0 Occupancy - Assembly S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. (X) 1 ( ) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date M Area of Sprinkler Operation - 900 System Type Sprinkler/Nozzle • Density - .10 (X) Wet Make D Area Per Sprinkler - 130 Max ( ) Dry Model QR PD's E Elevation at Highest Outlet - 8-0 ( ) Deluge Size 1/2" S Hose Allowance - Inside - ( ) Preaction K-Factor 5.6 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.200 G Hose Allowance - Outside - 250 N Note Hydraulic area reduced per NFPA #13 codes Calculation Flow Required - 241.77 Press Required - 40.221 at Base of Riser Summary C-Factor Used: 120 Overhead 150 Underground W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 1-31-2017 Cap. - T Time of Test - 10:30 AM Rated Cap.- Elev.- E Static Press - 50 @ Press - R Residual Press - 43 Elev. - Well Flow - 1000 Proof Flow S Elevation - -4 U P Location - East Coast Drive & Ahern Street P L Source of Information - Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Water Supply Curve C Fire Sprinkler Serv. of NE FL Page 2 Kitchen Area Date City Water Supply: Demand: Cl -Static Pressure : 50 D1 - Elevation : 5.197 C2 - Residual Pressure: 43 D2- System Flow : 241.767 C2 - Residual Flow : 1000 D2- System Pressure : 43.683 Hose ( Demand ) : 250 D3-System Demand : 491.767 Safety Margin : 4.434 150 140 : ' • 130 p 120 ; ' R 110 i - E 100 S 90 S 80 - . I U70 . R 60 ' Cl E 50 ° u2 _ - C2 _ o - a 40 D3 30 20 10 100 200 300 400 500 600 700 800 900 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Fire Sprinkler Serv. of NE FL Page 3 Kitchen Area Date Fitting Legend Abbrev. Name '/2 % 1 1% 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 ✓ 90'Ell Firelock#001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 0 0 0 0 0 0 0 Y Mechanical Tee 2 4 5 6 8 10.5 12.5 15,5 0 22 0 0 0 0 0 0 0 0 0 0 Zce Colt C300 Vert Butt Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a *show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 --I O C W-{Co Co CO NJ-A CO NNN-+—CD Cr)CO CO N N N-+ -AO CnN CO r') - l.-+ ZZ 7 'D D D(TA W AONCO 0)C...)-,1 IQ -,ONOCA? -, O V(T SCO Cn WO '6 6 -1 CD ZZ m� • m C CD CD 3 CD U) m m7 c X I D =' CCD (1) CD ?A -,rn o 00 CD 0 CD 00000 CD 000 CD00000000 Co Co Co OOCOC)D CO CO 0D CO d CD O - 6CD CD 00)Q)0)0)0)0)0)0610 6660 m 6 CD CD 0)0 a 10)00100000000000 O C n OJ)OJ)OJ)C))OJ)OJ)C))C))C))6J)C))C))CD OJ)CD CD C))CD C)m m 6J)C CD ,C - C E1' Z 3 CP Cn CT Cn 6Cn Cn 6 Cn 66 '� m 3 o �mmC)C)) )m�6 i - m v 3 a ° - D cn° n Z aC) 0 3 C D 0 a n' 0 _ n- IA 2 CDAAA W CO CO CO CO CO NNNN N N-,-+ N-+N NN-+ -+-+ .n.'0 ii; -� CO NO W -A OO CD COW CO-+OCO CD CO CD OCO-+A?N-OO CD O '.C= O)AN ANO.A W WA'co O CO Cn,P;co W J J N A A CO CD CA A iD N N N O NW J Co 6 I� CO CP N N-+ ACn W-4 CO J 6 C-4 A -+COCA-+6 C CA CT CA -4-4 J A J CO CO CD CD CO 6)CP W c Cc n CD X CD O CD v C = D = = = = = = z = = = = = = = = 3 > > > > 7 7 7 > > 3 7 3 J > > > 7 3 J 3 7 = 7 7 CO CU N CU CU CO CO CU CU CU CU Cu CU CU CU CU CU N CU CU N D) D) CU SU N CU D1 OU Cu D1 CU N CU CU CU CU CU N CU 0 C. CD Cn v A 7 = O NCn 6 J J CD O CO CO J CO IIC 6 CU a_ O WOO Cn Cn A OOW Cn-+ CU * 3 — . -W CD CD JN J COO Z CO C CnCD O O O O O O O 0 0 0 0 1 CA p W Cn Cn CP Cn Cn Cn Cn Cn CP Cn CP O 00 J ___ 0 D co CO CO-+W CA COCD N--+CDCC)0 CD CD 0 0 O N O CO CD C D X)13 J J J J J J J J J J J .a N CD 6 6 6 6 b b 6 6 b b 0 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 5 Kitchen Area Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 1 18.18 1.049 0.0 2.667 10.534 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 2 18.18 0.1091 0.0 2.667 0.291 Vel = 6.75 0.0 18.18 9.670 K Factor= 5.85 4 17.58 1.049 0.0 2.667 9.854 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 5 17.58 0:1024 0.0 2.667 0.273 Vel = 6.53 0.0 17.58 8.972 K Factor= 5.87 7 18.37 1.049 0.0 2.667 10.763 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 8 18.37 0.1114 0.0 2.667 0.297 Vel = 6.82 0.0 18.37 9.905 K Factor= 5.84 10 18.00 1.049 0.0 2.667 10.332 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 11 18.0 0.1069 0.0 2.667 0.285 Vel = 6.68 0.0 18.00 9.462 K Factor= 5.85 13 18.82 1.049 0.0 2.667 11.290 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 14 18.82 0.1162 0.0 2.667 0.310 Vel = 6.99 0.0 18.82 10.445 K Factor= 5.82 15 19.47 1.049 0.0 2.667 12.085 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 16 19.47 0.1237 0.0 2.667 0.330 Vel = 7.23 0.0 19.47 11.260 K Factor= 5.80 19 27.59 1.049 0.0 2.667 24.276 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 20 27.59 0.2358 0.0 2.667 0.629 Vel = 10.24 0.0 27.59 23.750 K Factor= 5.66 21 27.59 1.049 0.0 2.667 24.276 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 22 27.59 0.2358 0.0 2.667 0.629 Vel = 10.24 0.0 27.59 23.750 K Factor= 5.66 25 25.83 1.049 0.0 2.667 21.271 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 26 25.83 0.2088 0.0 2.667 0.557 Vel = 9.59 0.0 25.83 20.673 K Factor= 5.68 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 6 Kitchen Area Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 27 25.01 1.049 0.0 2.667 19.939 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 28 25.01 0.1969 0.0 2.667 0.525 Vel = 9.28 0.0 25.01 19.309 K Factor= 5.69 30 25.34 1.049 0.0 2.667 20.474 K Factor= 5.60 to 120.0 0.0 0.0 -1.155 31 25.34 0.2017 0.0 2.667 0.538 Vel = 9.41 0.0 25.34 19.857 K Factor= 5.69 2 18.18 1.049 E 2.0 0.500 9.670 to 120.0 T 5.0 7,000 0.0 3 18.18 0.1091 0.0 7.500 0.818 Vel = 6.75 0.0 18.18 10.488 K Factor= 5.61 5 17.58 1.049 E 2.0 8.000 8.972 to 120.0 T 5.0 7.000 0.0 • 6 17.58 0.1025 0.0 15.000 1.538 Vel = 6.53 0.0 17.58 10.510 K Factor= 5.42 8 18.37 1.049 E 2.0 0.500 9.905 to 120.0 T 5.0 7.000 0.0 9 18.37 0.1112 0.0 7.500 0.834 Vel = 6.82 0.0 18.37 10.739 K Factor= 5.61 11 18.00 1.049 E 2.0 8.000 9.462 to 120.0 T 5.0 7.000 0.0 12 18.0 0.1071 0.0 15.000 1.606 Vel = 6.68 0.0 18.00 11.068 K Factor= 5.41 14 18.82 1.049 E 2.0 8.000 10.445 to 120.0 T 5.0 7.000 0.0 17 18.82 0.1163 0.0 15.000 1.744 Vel = 6.99 0.0 18.82 12.189 K Factor= 5.39 16 19.47 1.049 E 2.0 0.500 11.260 to 120.0 T 5.0 7.000 0.0 17 19.47 0.1239 0.0 7.500 0.929 Vel = 7.23 0.0 19.47 12.189 K Factor= 5.58 20 27.59 1.049 E 2.0 4.000 23.750 to 120.0 T 5.0 7.000 0.0 23 27.59 0.2360 0.0 11.000 2.596 Vel = 10.24 0.0 27.59 26.346 K Factor= 5.38 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 7 Kitchen Area Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes *"**** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 22 27.59 1.049 E 2.0 4.000 23.750 to 120.0 T 5.0 7.000 0.0 23 27.59 0.2360 0.0 11.000 2.596 Vel = 10.24 0.0 27.59 26.346 K Factor= 5.38 28 25.01 1.049 E 2.0 1.000 19.309 to 120.0 T 5.0 7.000 0.0 29 25.01 0.1968 0.0 8.000 1.574 Vel = 9.28 0.0 25.01 20.883 K Factor= 5.47 31 25.34 1.049 E 2.0 1.000 19.857 to 120.0 T 5.0 7.000 0.0 32 25.34 0.2015 0.0 8.000 1.612 Vet= 9.41 0.0 25.34 21.469 K Factor= 5.47 3 18.18 1.682 0.0 2.000 10.488 to 120.0 0.0 0.0 0.0 6 18.18 0.0110 0.0 2.000 0.022 Vet = 2.63 6 17.57 1.682 0.0 6.000 10.510 to 120.0 0.0 0.0 0.0 9 35.75 0.0382 0.0 6.000 0.229 Vel = 5.16 9 18.38 1.682 0.0 4.000 10.739 to 120.0 0.0 0.0 0.0 12 54.13 0.0822 0.0 4.000 0.329 Vel = 7.82 12 18.00 1.682 0.0 8.000 11.068 to 120.0 0.0 0.0 0.0 17 72.13 0.1401 0.0 8.000 1.121 Vel = 10.41 17 38.28 1.682 Y 9.9 49.000 12.189 to 120.0 0.0 9.900 0.0 18 110.41 0.3079 0.0 58.900 18.137 Vel = 15.94 0.0 110.41 30.326 K Factor= 20.05 23 55.18 1.682 Y 9.9 37.000 26.346 to 120.0 0.0 9.900 0.0 24 55.18 0.0854 0.0 46.900 4.004 Vel = 7.97 0.0 55.18 30.350 K Factor= 10.02 26 25.83 1.682 0.0 10.000 20.673 to 120.0 0.0 0.0 0.0 29 25.83 0.0210 0.0 10.000 0.210 Vet = 3.73 29 25.00 1.682 0.0 8.000 20.883 to 120.0 0.0 0.0 0.0 32 50.83 0.0732 0.0 8.000 0.586 Vel = 7.34 32 25.34 1.682 Y 9.9 48.000 21.469 to 120.0 0.0 9.900 0.0 33 76.17 0.1550 0.0 57.900 8.972 Vel = 11.00 Computer Programs by Hydratec Inc Route 111 Windham N H USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 8 Kitchen Area Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 76.17 30.441 K Factor= 13.81 18 110.41 4.26 0.0 7.000 30.326 to 120.0 0.0 0.0 0.0 24 110.41 0.0034 0.0 7.000 0.024 Vel = 2.49 24 55.19 4.26 0.0 13.000 30.350 to 120.0 0.0 0.0 0.0 33 165.6 0.0070 0.0 13.000 0.091 Vel = 3.73 33 76.17 4.26 V 8.954 30.000 30.441 to 120.0 0.0 8.954 0.0 34 241.77 0.0142 0.0 38.954 0.554 Vel = 5.44 34 0.0 4.26 V 8.954 6.000 30.995 to 120.0 0.0 8.954 0.0 35 241.77 0.0142 0.0 14.954 0.213 Vel = 5.44 35 0.0 4.26 V 8.954 4.667 31.208 to 120.0 0.0 8.954 2.021 TASR 241.77 0.0142 0.0 13.621 0.193 Vel = 5.44 TASR 0.0 4.26 Zce 0.0 5.000 33.422 to 120.0 0.0 0.0 6.727 * * Fixed Loss= 4.562 BASE 241.77 0.0144 0.0 5.000 0.072 Vel = 5.44 BASE 0.0 4.1 0.0 5.000 40.221 to 140.0 0.0 0.0 2.166 UG 241.77 0.0128 0.0 5.000 0.064 Vel = 5.88 UG 0.0 4.23 E 19.223 65.000 42.451 to 150.0 T 38.446 61.514 0.0 CONN 241.77 0.0097 G 3.845 126.514 1.232 Vel = 5.52 250.00 Qa = 250.00 491.77 43.683 K Factor= 74.41 Computer Programs by Hydratec Inc. Route 111 Windham N H. USA 03087 OFFICE COPY Approved By Permit Desk Building Department City of Atlantic Beach,FL REvi k iittf pra‘ elle Fira _ _ Fire Protection by Computer Design PI e ent• ®iv FEB ?Ai Z2018 CEpr doivs Fire Sprinkler Serv. of NE FL SiF�# /o JS As�o� ED P.O. Box 23787 Jacksonville, FL 32241 904-262-1002 Job Name : 2nd Floor Building : Coop Restaurant 303 Location : 303 Atlantic Blvd,Atlantic Beach, FL System : Wet Contract : Data File : Coop Restaurant 303.WXG Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fire Sprinkler Serv. of NE FL Page 1 2nd Floor Date Hydraulic Design Information Sheet Name - 2nd Floor Date - 1-25-2018 Location - 303 Atlantic Blvd, Atlantic Beach, FL Building - Coop Restaurant 303 System No. - Wet Contractor - Contract No. - Calculated By - CEM Drawing No. - 1 of 1 Construction: ( ) Combustible (X) Non-Combustible Ceiling Height - 10-0 Occupancy - Assembly S (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date M Area of Sprinkler Operation - 900 System Type Sprinkler/Nozzle Density - .10 (X) Wet Make D Area Per Sprinkler - Varies ( ) Dry Model QR PD's E Elevation at Highest Outlet - 21-4 ( ) Deluge Size 1/2" S Hose Allowance - Inside - ( ) Preaction K-Factor 5.6 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside - 100 N Note Hydraulic area reduced per NFPA #13 codes Calculation Flow Required - 168.73 Press Required - 34.394 at Base of Riser Summary C-Factor Used: 120 Overhead 150 Underground W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 1-31-2017 Cap. - T Time of Test - 10:30 AM Rated Cap.- Elev.- E Static Press - 50 @ Press - R Residual Press - 43 Elev. - Well Flow - 1000 Proof Flow S Elevation - -4 P Location - East Coast Drive & Ahern Street P L Source of Information - Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Water Supply Curve C Fire Sprinkler Serv. of NE FL Page 2 2nd Floor Date City Water Supply: Demand: Cl -Static Pressure : 50 D1 - Elevation : 10.972 C2 - Residual Pressure: 43 D2 - System Flow : 168.728 C2 - Residual Flow : 1000 D2 -System Pressure : 37.226 Hose ( Demand ) : 100 D3-System Demand : 268.728 Safety Margin : 12.158 150 140 130 p120 R110 E 100 S 90 S 80 U 70 R 60 Cl E 50 ° C2 40 n2 -0 30 D3 20 10 D1 ;, ...., 4_ . ., . . . . 100 200 300 400 500 600 700 800 900 FLOW ( NA1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Fire Sprinkler Serv. of NE FL Page 3 2nd Floor Date Fitting Legend Abbrev. Name Y '/e 1 11/n 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 ✓ 90'Ell Firelock#001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 0 0 0 0 0 0 0 X 90'Tee-BranchFirelock002 0 0 0 0 0 8.5 10.8 13 0 16 21 25 33 0 0 0 0 0 0 0 Y Mechanical Tee 2 4 5 6 8 10.5 12.5 15.5 0 22 0 0 0 0 0 0 0 0 0 0 Zce Colt C300 Vert Butt Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a *will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Fire Sprinkler Serv. of NE FL Page 4 2nd Floor Date Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 100 21.333 5.6 13.43 na 20.52 0.1 150 7.0 102 21.333 5.6 13.57 na 20.63 0.1 150 7.0 104 21.333 5.6 14.06 na 21.0 0.1 210 7.0 106 21.333 5.6 14.79 na 21.54 0.1 210 7.0 109 21.333 5.6 13.95 na 20.92 0.1 84 7.0 111 21.333 5.6 14.12 na 21.05 0.1 84 7.0 113 21.333 5.6 13.2 na 20.34 0.1 120 7.0 117 21.333 5.6 16.48 na 22.73 0.1 150 7.0 107 22.0 14.6 na 114 22.0 13.0 na 101 22.0 13.24 na 103 22.0 13.37 na 105 22.0 13.87 na 110 22.0 13.76 na 112 22.0 13.93 na 115 22.0 14.34 na 118 22.0 16.3 na 108 22.0 16.09 na 116 22.0 16.36 na 119 22.0 16.48 na 120 22.0 17.77 na 34 10.667 25.1 na 35 10.667 25.21 na TASR 6.0 27.34 na BASE 1.0 34.39 na UG -4.0 36.59 na CONN -4.0 37.23 na 100.0 The maximum velocity is 9.93 and it occurs in the pipe between nodes 119 and 120 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 5 2nd Floor Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 100 20.52 1.049 0.0 0.667 13.433 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 101 20.52 0.1379 0.0 0.667 0.092 Vel = 7.62 0.0 20.52 13.236 K Factor= 5.64 102 20.63 1.049 0.0 0.667 13.570 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 103 20.63 0.1379 0.0 0.667 0.092 Vel = 7.66 0.0 20.63 13.373 K Factor= 5.64 104 21.00 1.049 0.0 0.667 14.062 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 105 21.0 0.1439 0.0 0.667 0.096 Vel = 7.80 0.0 21.00 13.869 K Factor= 5.64 106 21.54 1.049 0.0 0.667 14.789 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 107 21.54 0.1499 0.0 0.667 0.100 Vel = 8.00 0.0 21.54 14.600 K Factor= 5.64 109 20.92 1.049 0.0 0.667 13.954 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 110 20.92 0.1424 0.0 0.667 0.095 Vel = 7.77 0.0 20.92 13.760 K Factor= 5.64 111 21.05 1.049 0.0 0.667 14.124 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 112 21.05 0.1424 0.0 0.667 0.095 Vel = 7.81 0.0 21.05 13.930 K Factor= 5.64 113 20.34 1.049 0.0 0.667 13.198 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 114 20.34 0.1334 0.0 0.667 0.089 Vel = 7.55 0.0 20.34 12.998 K Factor= 5.64 117 22.73 1.049 0.0 0.667 16.476 K Factor= 5.60 to 120.0 0.0 0.0 -0.289 118 22.73 0.1649 0.0 0.667 0.110 Vel = 8.44 0.0 22.73 16.297 K Factor= 5.63 107 21.54 1.049 E 2.0 3.000 14.600 to 120.0 Y 5.0 7.000 0.0 108 21.54 0.1492 0.0 10.000 1.492 Vel = 8.00 0.0 21.54 16.092 K Factor= 5.37 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 6 2nd Floor Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ****`** Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 114 20.34 1.049 E 2.0 3.000 12.998 to 120.0 T 5.0 7.000 0.0 115 20.34 0.1343 0.0 10.000 1.343 Vel = 7.55 0.0 20:34 14.341 K Factor= 5.37 101 20.52 1.682 0.0 10.000 13.236 to 120.0 0.0 0.0 0.0 103 20.52 0.0137 0.0 10.000 0.137 Vel = 2.96 103 20.63 1.682 0.0 10.000 13.373 to 120.0 0.0 0.0 0.0 105 41.15 0.0496 0.0 10.000 0.496 Vel = 5.94 105 21.00 1.682 Y 9.9 11.000 13.869 to 120.0 0.0 9.900 0.0 108 62.15 0.1064 0.0 20.900 2223 Vel = 8.97 0.0 - 62.15 16.092 K Factor= 15.49 110 20.92 1.682 0.0 12.000 13.760 to 120.0 0.0 0.0 0.0 112 20.92 0.0142 __ 0.0 12.000 0.170 Vel= 3.02 _ 112 21.04 1.682 0.0 8.000 13.930 to 120.0 0.0 0.0 0.0 115 41.96 0.0514 0.0 8.000 0.411 Vel = 6.06 115 20.35 1.682 Y 9.9 9.000 14.341 to 120.0 0.0 9.900 0.0 116 62.31 0.1069 0.0 18.900 2.020 Vet = 9.00 0.0 62.31 16.361 K Factor= 15.40 118 22.73 1.682 Y 9.9 1.000 16.297 to 120.0 0.0 9.900 0.0 119 22.73 0.0165 0.0 10.900 0.180 Vet = 3.28 0.0 22.73 16.477 K Factor= 5.60 108 83.69 2.635 0.0 13.000 16.092 to 120.0 0.0 0.0 0.0 116 83.69 0.0207 0.0 13.000 0.269 Vet = 4.92 116 62.31 2.635 0.0 2.000 16.361 to 120.0 0.0 0.0 0.0 119 146.0 0.0580 0.0 2.000 0.116 Vel = 8.59 119 22.73 2.635 0.0 17.000 16.477 to 120.0 0.0 0.0 0.0 120 168.73 0.0758 0.0 17.000 1.289 Vet = 9.93 120 0.0 2.635 V 5.903 11.333 17.766 to 120.0 X 14.827 20.730 4.908 34 168.73 0.0758 0.0 32.063 2.431 Vel = 9.93 34 0.0 4.26 V . 8.954 6.000 25.105 to 120 0 0.0 8.954 0.0 35 168.73 0 0073 0.0 14.954 0.109 Vel = 3.80 Computer Programs by Hydrates Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Fire Sprinkler Serv. of NE FL Page 7 2nd Floor Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 35 0.0 4.26 V 8.954 4.667 25.214 to 120.0 0.0 8.954 2.021 TASR 168.73 0.0073 0.0 13.621 0.100 Vel = 3.80 TASR 0.0 4.26 Zce 0.0 5.000 27.335 to 120.0 0.0 0.0 7.023 ** Fixed Loss =4.857 BASE 168.73 0.0072 0.0 5.000 0.036 Vel = 3.80 BASE 0.0 4.1 0.0 5.000 34.394 to 140.0 0.0 0.0 2.166 UG 168.73 0.0066 0.0 5.000 0.033 Vel = 4.10 UG 0.0 4.23 E 19.223 65.000 36.593 to 150.0 T 38.446 61.514 0.0 CONN 168.73 0.0050 G 3.845 126.514 0.633 Vel = 3.85 100.00 Qa = 100.00 268.73 37.226 K Factor= 44.04 Computer Programs by Hydratec Inc. Route 111 Windham N H. USA 03087