1895 Atlantic Beach Dr - Form Board Elevation Cert FORM BOARD ELEVATION CERTIFICATE
Date --3, - ig - Permit Number: lt /-?- o &o
Address: � s
All American Surveyors Work Order # zz 3y
Required Slab Elevation on City Approved Site Plan:
/2 . -'/v
Actual Elevation of Form Board or Grade Stake:
Survey Company:
ALL AMERICAN SURVEYORS OF FLORIDA INC.
3751 San Jose Place, Suite 15
Jacksonville FL 32257 Work Phone: 904-279-0088
Signature of Surveyor: (PartyChief)
UNIVERSAL UES Project No: 0910.1400187.0000
Workorder No: 201401-1
ENGINEERING SCIENCES Report Date: 4/9/2018
Consultants In:Geotechnical Engineering-Environmental Sciences
Geophysical Services-Construction Materials Testing-Threshold Inspection
ED Building Inspection-Plan Review-Building Code Administration
5561 Florida Mining Blvd So.,Jacksonville, 32257 • P: 904-296-0757 - F: 904-296-0748 �S / _ c)iG S
In-Place Density Test Report
v
Client: UES Technician: Talley Tomlin
160 Cape May Avenue
Ponte Vedra, FL 32081 Date Tested: 04/09/2018
Project: Atlantic Beach Country Club
Area Tested house pad 57 ) - 4 /I �c/ ^�r Type of Test;
Material: �— t! /� Field: ASTM D-6938 Nuclear Gauge Metho
Reference Datum: 0 = Top of Fill Laboratory: ASTM D1557 Modified Proctor
The tests below meet the minimum 95% relative soil compaction requirement of Laboratory Proctor maximum dry density.
Maximum ptimum Field Dry Field Soil Fill
Test Density Moisture Density Moisture Compaction Depth Pass(inch) or Fail
No. Location of Test Range (pcf) (%) (pcf) ("dot' (%)
1 15 ft. from south corner 0-1 ft 103.3 14.3 97.9 4.8 95 N/A Pas:
2 10 ft. from north corner 0-1 ft 103.3 14.3 98.7 3.7 96 N/A Pas-
3 15 ft. from east corner 0-1 ft 103.3 14.3 98.2 4.3 95 N/A Pas:
4 10 ft. from west corner 0-1 ft 103.3 14.3 98.5 4.0 95 N/A Pas