403 Atlantic Dwgs2r ---------- _VAC GENERAL NOTES � 0 1. PROVIDE A COMPLETE HEATING, AND AIR CONDITIONING SYSTEM AS SHOWN ON DRAWINGS AND MEETING THE REQUIREMENTS OF FLORIDA BUILDING CODE - MECHANICAL AND APPLICABLE STATE AND LOCAL CODES. OBTAIN ALL PERMITS AND NECESSARY CERTIFICATES. SEE SPECIFICATION FOR ADDITIONAL INFORMATION AND REQUIREMENTS. I 2. COORDINATE PIPING, DUCTWORK AND EQUIPMENT LOCATION WITH PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 3. DO NOT INSTALL PIPING AND DUCTWORK ABOVE ELECTRICAL PANELS AND ELECTRICAL EQUIPMENT WHEN PROHIBITED BY CODES. COORDINATE ELECTRICAL PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. I 4. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. (ROUGH WORK WILL BE REJECTED). 5. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED GALVANIZED SHEET METAL. ALL RETURN AIR AND TRANSFER AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH ACOUSTIC DUCT LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR OPENING SIZE. INCREASE DUCT SIZE TO ALLOW FOR DUCT LINER THICKNESS. ALL EXHAUST AIR AND OUTSIDE INTAKE AIR DUCTWORK SHALL BE UN -INSULATED GALVANIZED SHEET METAL. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 6. DUCT INSULATION SHALL BE REQUIRED THICKNESS TO PROVIDE MINIMUM THERMAL RESISTANCE "R" OF 6.0 WHEN DUCT IS LOCATED WITHIN BUILDING AND ON NON -AIR CONDITIONED SIDE OF BUILDING INSULATION AND "R" OF 4.2 WHEN DUCT IS LOCATED ON AIR CONDITIONED SIDE OF BUILDING INSULATION. ALL "R" VALUES ARE "AS -INSTALLED" MINIMUMS. I I 7. DO NOT MAKE ANY CHANGES IN DESIGN WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT. CHANGES IN DESIGN MEANS ANY CHANGE WHICH WILL AFFECT THE CAPACITY, RELIABILITY, OPERATION OR SAFETY OF THE SYSTEMS OR ANY PARTS THEREOF, INCLUDING CHANGES WHICH MAY BE REQUIRED TO CONFIRM TO LOCAL REGULATIONS OR CODES. 8. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT. I 10. SEE ARCHITECTURAL REFLECTED CEILING FOR EXACT LOCATION OF CEILING DIFFUSERS. 11. PRIOR TO FABRICATION OF HVAC DUCT WORK FOR FIELD INSTALLATION, FIELD VERIFY EXISTING ROOF JOIST SPACING, JOIST OPENING SIZE AND LOCATION. IF EXISTING STRUCTURAL CONDITIONS DO NOT PROVIDE SUFFICIENT SPACE FOR PROPER DUCT INSTALLATION, REPORT THIS MATTER TO THE ARCHITECT IMMEDIATELY. (DO NOT FABRICATE DUCT WORK UNTIL FURTHER INSTRUCTIONS ARE ISSUED BY THE ARCHITECT). 12. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR. L- - - - - - - - - - - - - - - - - - - - - - - - J HVAC FLAG NOTES: 0 G-3, 4' LENGTH, 2 SLOTS. 200 CFM. Q G-9, 24X16 N. ® G-2, 24X12 N MODULE. 18X6 NECK. 565 ® WALLCAP. O5 G-2, 8"0 NECK. © G-6, 22X22 IN DOOR. 0 G-7, 6X4, 20 CFM. Q 8"0 OA DUCT FROM GOOSENECK ON ROOF O9 10"0 OA DUCT FROM GOOSENECK ON ROC 10 MOTORIZED DAMPER CFM SET TO 95 CFM. 11 MOTORIZED DAMPER CFM SET TO 215 12 G-2, 8X8 NECK. 140 CFM. PROVIDE WITH 13 SUPPLY DUCT SHALL TRAVEL WITHIN GYP EQUIPMENT SCHEDULE - DIFFUSERS, GRILLES & REGISTERS NOTES: SEE ALL AND ARCH. REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS. FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN -INS WITH AIR SCOOP BALANCE DAMPER. NECK SIZE AS SHOWN ON THE DRAWINGS. APPROVED MANUFACTURER: PRICE (EXCEPT AS NOTED *) EQUIP. NO. MOUNTING TYPE MODEL NUMBER ACCESSORIES/REMARKS G-1 LAY -IN CEILING (SUPPLY) SCD (24X24) (1)(4) G-2 LAY -IN CEILING (RETURN) PDDR (24X24) (1) G-3 LINEAR (SUPPLY) SDS (2)(3)(5) G-4 LAY -IN CEILING (EXHAUST) PDDR (1) G-5 SURFACE (RETURN) 630 (2) G-6 DOOR (TRANSFER) ATG 100 G-7 SURFACE (SUPPLY) CVD (2) G-8 SURFACE (SUPPLY) AL271 (2) (6) LIMA MANUFACTURER G-9 SURFACE (RETURN) 530 74.7W (1) WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY -IN TYPE DIFFUSER. (2) PROVIDE WITH FACE OPERABLE DAMPER. (3) LINEAR DIFFUSER SHALL BE PROVIDED WITH SDB SUPPLY PLENUM BY PRICE. (4) WHERE USED IN GYP BOARD CEILINGS, DUCT -MOUNTED DAMPER SHALL BE ACCESSIBLE BY LIFTING DIFFUSER OUT OF ANGLE -FRAME FOR ACCESS TO ABOVE -CEILING AREA. (5) LINEAR DIFFUSER SHALL BE 2 -SLOT MODEL. ONE SLOT SHALL BE SET TO HORIZONTAL PATTERN, OTHER SHALL BE SET TO VERTICAL PATTERN. (6) PROVIDE SQUARE TO ROUND NECK ADAPTER. EQUIPMENT SCHEDULE — FAN APPROVED MANUFACTURER LOREN COOK CO. EQUIPMENT NUMBER EF -1 EF -2 EF -3 EF -4 MOUNTING TYPE 33192 CEILING CEILING CEILING CEILING (904) 264-5570 FAX:(904) 278-2646 THOMAS ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD DAVID R. TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL Wa DRIVE DIRECT DIRECT DIRECT DIRECT FAN RPM 965 965 765 905 M CFM 70 70 70 100 0 S. P. .4 .4 .2 .2 °' m HP 51.4W 51.4W 47.7W 74.7W MOTOR VOLTS/PHASE 115V/1 115V/1 115V/1 115V/1 MODEL NUMBER GC -142 GC -142 GC -142 GC -144 ACCESSORIES/REMARK (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(6) NOTE: (1): BACK DRAFT DAMPER (2): SPEED CONTROLLER (3): UNIT MOUNTED DISCONNECT (4: WALL CAP (5 : EXHAUST FAN SHALL BE CONTROLLED BY WALLSWITCH. (6): EXHAUST FAN SHALL BE CONTROLLED BY THERMOSTAT. POWER ON AT 807, SHUTDOWN AT 777. HVAC LEGEND AHU CU 119 2 SA RA EA BD 0 R T) 0 CFM. DAMPER IN NECK SOFFIT. AIR HANDLING UNIT CONDENSING UNIT EXHAUST FAN NEW DUC NEW DUC DUCT TRANSITION SUPPLY AIR RETURN AIR EXHAUST AIR BALANCING DAMPER NEW SUPPLY DIFFUSER NEW RETURN GRILLE NEW LINEAR DIFFUSER RELOCATED EXISTING THERMOSTAT DUCT -MOUNTED SMOKE DETECTOR MOTORIZED DAMPER -------------- ,HVAC ADDITIONAL BID AND DEMOL17 1. MECHANICAL CONTRACTOR SHALL INSPECT EXISTING THREE 5 -TON SPLIT I I SYSTEMS AND DETERMINE' SYSTEM IN WORST FUNCTIONAL STATE. REMOVE THIS CONDENSER UNIT AND ITS ASSOCIATED AIRHANDLER. MAKE EQUIPMENT AVAILABLE TO BUILDING OWNER PRIOR TO DISPOSAL. DISPOSE OF EQUIPMENT IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS. 2. MECHANICAL CONTRACTOR SHALL INSPECT, SERVICE, AND REPAIR AS REQUIRED ALL REMAINING MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. 3. RELOCATE EXISTING AIRHANDLERS TO LOCATIONS INDICATED AND RE -TAG EQUIPMENT TO MATCH NEW DESIGNATION AS REQUIRED. 4. COORDINATE WITH ELECTRICAL CONTRACTOR AND PROVIDE CONDENSATE PUMPS AT NEW AIRHANDLER LOCATIONS AND DISPOSE OF CONDENSATE AT EXISTING CONDENSATE DISPOSAL LOCATION. L— — — — — — — — - — — — — — — — — — — — — — — — — J WALL TYPE LEGEND NON RATED: 1 HR. RATED: — — — 2 HR. RATED: — — — 7/31/17 2822M1.01 ROBERT L. HINKLE PE 29302 POWELL & HINKLE ENGINEERING, P.A. M N �El\\'Bi W 1409 KINGSLEY AVENUE, BLDG 12A GALTON P & H LANE C. MOK PE 33192 ORANGE PARK, FLORIDA 32073 R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 SEAL Hi N0.48076 ,o's• STATE O Eck, '•....��°. PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M N �El\\'Bi W N ch -j a, Z U- U) Z 0 c00 -i-� V U (,r m N 0 0 z� 0 CD 0 Wa L Y � Q J Lo o a V N N M w co -9 E Q 0 0 c V L °' m Z C G >cu -> c c �? o Y co O d' U f6 co � N � M o U)� 0 Zw o o cu LL a� c ti rn > o rn � N M "j: o W M F_ PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M N Z� W N ch -j J U- C' Z = U (,r w m 0 z� 0 Wa J LL Y � Q J � o a V (D> Z w Q J Q Z J O m V W Z C G Lu LL_ Q co O d' PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH r ---------- _VAC GENERAL NOTES l 0 1. PROVIDE A COMPLETE HEATING, AND AIR CONDITIONING SYSTEM AS SHOWN ON DRAWINGS AND MEETING THE REQUIREMENTS OF FLORIDA BUILDING CODE – MECHANICAL AND APPLICABLE STATE AND LOCAL CODES. i OBTAIN ALL PERMITS AND NECESSARY CERTIFICATES. SEE SPECIFICATION FOR ADDITIONAL INFORMATION AND REQUIREMENTS. I 2. COORDINATE PIPING, DUCTWORK AND EQUIPMENT LOCATION WITH PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 3. DO NOT INSTALL PIPING AND DUCTWORK ABOVE ELECTRICAL PANELS AND ELECTRICAL EQUIPMENT WHEN PROHIBITED BY CODES. COORDINATE ELECTRICAL PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. ( 4. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. (ROUGH WORK WILL BE REJECTED). 5. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED GALVANIZED SHEET METAL. ALL RETURN AIR AND TRANSFER AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH ACOUSTIC DUCT LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR OPENING SIZE. INCREASE DUCT SIZE TO ALLOW FOR DUCT LINER THICKNESS. ALL EXHAUST AIR AND OUTSIDE INTAKE AIR DUCTWORK SHALL BE UN–INSULATED GALVANIZED SHEET METAL. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 16. DUCT INSULATION SHALL BE REQUIRED THICKNESS TO PROVIDE MINIMUM THERMAL RESISTANCE "R" OF 6.0 WHEN DUCT IS LOCATED WITHIN BUILDING AND ON NON–AIR CONDITIONED SIDE OF BUILDING INSULATION AND "R" OF 4.2 WHEN DUCT IS LOCATED ON AIR CONDITIONED SIDE OF BUILDING INSULATION. ALL "R" VALUES ARE "AS–INSTALLED" MINIMUMS. I I 7. DO NOT MAKE ANY CHANGES IN DESIGN WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT. CHANGES IN DESIGN MEANS ANY CHANGE WHICH WILL AFFECT THE CAPACITY, RELIABILITY, OPERATION OR SAFETY OF THE SYSTEMS OR ANY PARTS THEREOF, INCLUDING CHANGES WHICH MAY BE REQUIRED TO CONFIRM TO LOCAL REGULATIONS OR CODES. 8. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT. I 10. SEE ARCHITECTURAL REFLECTED CEILING FOR EXACT LOCATION OF CEILING DIFFUSERS. 11. PRIOR TO FABRICATION OF HVAC DUCT WORK FOR FIELD INSTALLATION, FIELD VERIFY EXISTING ROOF JOIST SPACING, JOIST OPENING SIZE AND LOCATION. IF EXISTING STRUCTURAL CONDITIONS DO NOT PROVIDE SUFFICIENT SPACE FOR PROPER DUCT INSTALLATION, REPORT THIS MATTER TO THE ARCHITECT IMMEDIATELY. (DO NOT FABRICATE DUCT WORK UNTIL FURTHER INSTRUCTIONS ARE ISSUED BY THE ARCHITECT). 12. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR. L— — — — — — — — — — — — — — — — — — — — — — — — J HVAC FLAG NOTES: 01 G-3, 4' LENGTH, 2 SLOTS. 200 CFM. O G-9, 24X16 N. O3 G-2, 24X12 N MODULE. 18X6 NECK. ® WALLCAP. O5 G-2, 8"0 NECK. © G-6, 22X22 IN DOOR. 07 G-7, 6X4, 20 CFM. i5 CFM. ® 8"0 OA DUCT FROM GOOSENECK ON ROOF. 0 10"0 OA DUCT FROM GOOSENECK ON ROOF. 10 MOTORIZED DAMPER CFM SET TO 95 11 MOTORIZED DAMPER CFM SET TO 215 �,FM. 12 G-2, 8X8 NECK. 140 CFM. PROVIDE WIjTH DAMPER IN NECK 13 SUPPLY DUCT SHALL TRAVEL WITHIN EQUIPMENT SCHEDULE - DIFFUSERS, GRILLES & REGISTERS NOTES: SEE ALL AND ARCH. REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS. FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN–INS WITH AIR SCOOP BALANCE DAMPER. NECK SIZE AS SHOWN ON THE DRAWINGS. APPROVED MANUFACTURER: PRICE (EXCEPT AS NOTED *) EQUIP. NO. MOUNTING TYPE MODEL NUMBER ACCESSORIES/REMARKS G-1 LAY–IN CEILING (SUPPLY) SCD (24X24) 1 (4) G-2 LAY–IN CEILING (RETURN) PDDR (24X24) (1) G-3 LINEAR (SUPPLY) SDS (2)(3)(5) G-4 LAY–IN CEILING (EXHAUST) PDDR (1) G-5 SURFACE (RETURN) 630 (2) G-6 DOOR (TRANSFER) ATG 70 G-7 SURFACE (SUPPLY) CVD (2) G-8 SURFACE (SUPPLY) AL271 (2) (6) LIMA MANUFACTURER G-9 SURFACE (RETURN) 530 47.7W (1) WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY–IN TYPE DIFFUSER. (2) PROVIDE WITH FACE OPERABLE DAMPER. (3) LINEAR DIFFUSER SHALL BE PROVIDED WITH SDB SUPPLY PLENUM BY PRICE. (4) WHERE USED IN GYP BOARD CEILINGS, DUCT–MOUNTED DAMPER SHALL BE ACCESSIBLE BY LIFTING DIFFUSER OUT OF ANGLE–FRAME FOR ACCESS TO ABOVE–CEILING AREA. (5) LINEAR DIFFUSER SHALL BE 2–SLOT MODEL. ONE SLOT SHALL BE SET TO HORIZONTAL PATTERN, OTHER SHALL BE SET TO VERTICAL PATTERN. (6) PROVIDE SQUARE TO ROUND NECK ADAPTER. EQUIPMENT SCHEDULE - FAN APPROVED MANUFACTURER LOREN COOK CO. EQUIPMENT NUMBER EF -1 EF -2 EF -3 EF -4 MOUNTING TYPE PE CEILING CEILING CEILING CEILING PE TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL 56121 DRIVE DIRECT DIRECT DIRECT DIRECT FAN RPM 965 965 765 905 U CFM 70 70 70 100 z J S. P. .4 .4 .2 .2 o u HP 51.4W 51.4W 47.7W 74.7W MOTOR VOLTS/PHASE 115V/1 115V/1 115V/1 115V/1 MODEL NUMBER GC -142 GC -142 GC -142 GC -144 ACCESSORIES/REMARK (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(6) NOTE: (1): BACK DRAFT DAMPER (2): SPEED CONTROLLER (3): UNIT MOUNTED DISCONNECT (4: WALL CAP (5�: EXHAUST FAN SHALL BE CONTROLLED BY WALLSWITCH. (6): EXHAUST FAN SHALL BE CONTROLLED BY THERMOSTAT. POWER ON AT 807, SHUTDOW�l AT 777. HVAC LEGEND AHU CU EF SA RA EA BD 0 R T) O SOFFIT. AIR HA DLING UNIT CONDE14SING UNIT EXHAUST FAN NEW DUCT NEW FLEXIBLE DUCT NEW DUCT DUCT IRANSITION SUPPLY AIR RETURN AIR EXHAU T AIR BALAN 'ING DAMPER NEW SUPPLY DIFFUSER NEW RETURN GRILLE NEW LINEAR DIFFUSER RELOCATED EXISTING THERMOSTAT DUCT–MOUNTED SMOKE DETECTOR MOTORIZED DAMPER G HVAC ADDITIONAL BID AND DEMOLIT 1. MECHANICAL CONTRACTOR SHALL INSPECT EXISTING THREE 5–TON SPLIT I SYSTEMS AND DETERMINE SYSTEM IN WORST FUNCTIONAL STATE. REMOVE THIS CONDENSER UNIT AND ITS ASSOCIATED AIRHANDLER. MAKE EQUIPMENT AVAILABLE TO BUILDING OWNER PRIOR TO DISPOSAL. DISPOSE OF EQUIPMENT IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS. 2. MECHANICAL CONTRACTOR SHALL INSPECT, SERVICE, AND REPAIR AS REQUIRED ALL REMAINING MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. 3. RELOCATE EXISTING AIRHANDLERS TO LOCATIONS INDICATED AND RE–TAG EQUIPMENT TO MATCH NEW DESIGNATION AS REQUIRED. 4. COORDINATE WITH ELECTRICAL CONTRACTOR AND PROVIDE CONDENSATE PUMPS AT NEW AIRHA DLER LOCATIONS AND DISPOSE OF CONDENSATE AT EXISTING CONDENSATE DISPOSAL LOCATION. L— — — — ————————————— — — — — — J WALL TYPE LEGEND NON RATED: 1 HR. RATED: — — — 2 HR. RATED: — 7/31/17 2822M1.01 POWELL & HINKLE ENGINEERING, P.A. ROBERT L. HINKLE PE 29302 & 1409 KINGSLEY AVENUE, BLDG 12A GALTON C. MOK PE 33192 P H ORANGE PARK, FLORIDA 32073 LANE R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS M. ELDER PE 56121 ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD A. MATHEWS PE 59418 ca �2E DAVID R. SPELL JR. PE 54729 SEAL No. 48076 1 10 STATE O `; ' U) o 0 -�--+ U cr W m N 0 aJ ZLLJ 0 a = C) L U c� w m � Lo O N N J LLQ M � Q ca �2E Q ♦ 1 0 LL- 0 vi U W L cu m n � Q z J ca = c a� VW Lu o u Z U cu LL Q O 0 N � M N ~ O o � rn Z = o x co co LL. CD � c rn > rn rn N M CD CD M W M � PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M M N Z cr W N co _j aJ ZLLJ tL a = C) OC U c� w m � z O Wa J LLQ Y Q � Q � Q ♦ 1 � Z W Z Q z J O m = U VW Lu Z Jg LL Q M O �t PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH r _VAC GENERAL N-0—TES — � 1. PROVIDE A COMPLETE HEATING, AND AIR CONDITIONING SYSTEM AS SHOWN ON DRAWINGS AND MEETING THE REQUIREMENTS OF FLORIDA BUILDING CODE - MECHANICAL AND APPLICABLE STATE AND LOCAL CODES. OBTAIN ALL PERMITS AND NECESSARY CERTIFICATES. SEE SPECIFICATION FOR I ADDITIONAL INFORMATION AND REQUIREMENTS. I 2. COORDINATE PIPING, DUCTWORK AND EQUIPMENT LOCATION WITH PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 3. DO NOT INSTALL PIPING AND DUCTWORK ABOVE ELECTRICAL PANELS AND ELECTRICAL EQUIPMENT WHEN PROHIBITED BY CODES. COORDINATE ELECTRICAL PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. i 4. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. (ROUGH WORK WILL BE REJECTED). 5. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED GALVANIZED SHEET METAL. ALL RETURN AIR AND TRANSFER AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH ACOUSTIC DUCT LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR OPENING SIZE. INCREASE DUCT SIZE TO ALLOW FOR DUCT LINER THICKNESS. ALL EXHAUST AIR AND OUTSIDE INTAKE AIR DUCTWORK SHALL BE UN -INSULATED GALVANIZED SHEET METAL. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 6. DUCT INSULATION SHALL BE REQUIRED THICKNESS TO PROVIDE MINIMUM THERMAL RESISTANCE "R" OF 6.0 WHEN DUCT IS LOCATED WITHIN BUILDING AND ON NON -AIR CONDITIONED SIDE OF BUILDING INSULATION AND "R" OF 4.2 WHEN DUCT IS LOCATED ON AIR CONDITIONED SIDE OF BUILDING INSULATION. ALL "R" VALUES ARE "AS -INSTALLED" MINIMUMS. I 7. DO NOT MAKE ANY CHANGES IN DESIGN WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT. CHANGES IN DESIGN MEANS ANY CHANGE WHICH WILL AFFECT THE CAPACITY, RELIABILITY, OPERATION OR SAFETY OF THE SYSTEMS OR ANY PARTS THEREOF, INCLUDING CHANGES WHICH MAY BE REQUIRED TO CONFIRM TO LOCAL REGULATIONS OR CODES. I 8. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT. I 10. SEE ARCHITECTURAL REFLECTED CEILING FOR EXACT LOCATION OF CEILING DIFFUSERS. 11. PRIOR TO FABRICATION OF HVAC DUCT WORK FOR FIELD INSTALLATION, FIELD VERIFY EXISTING ROOF JOIST SPACING, JOIST OPENING SIZE AND LOCATION. IF EXISTING STRUCTURAL CONDITIONS DO NOT PROVIDE SUFFICIENT SPACE FOR PROPER DUCT INSTALLATION, REPORT THIS MATTER TO THE ARCHITECT IMMEDIATELY. (DO NOT FABRICATE DUCT WORK UNTIL FURTHER INSTRUCTIONS ARE ISSUED BY THE ARCHITECT). 12. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR. L- - - - - - - - - - - - - - - - - - - - - - - - J HVAC FLAG NOTES: O1 G-3, 4' LENGTH, 2 SLOTS. 200 CFM. O G-9, 24X16 N. O3 G-2, 24X12 N MODULE. 18X6 NECK. 56 ® WALLCAP. O5 G-2, 8"0 NECK. © G-6, 22X22 IN DOOR. O G-7, 6X4, 20 CFM. ® 8"0 OA DUCT FROM GOOSENECK ON RO 90 10"0 OA DUCT FROM GOOSENECK ON R 10 MOTORIZED DAMPER CFM SET TO 95 CF 11 MOTORIZED DAMPER CFM SET TO 215 C i CFM. 12 G-2, 8X8 NECK. 140 CFM. PROVIDE WIT DAMPER IN NECK 13 SUPPLY DUCT SHALL TRAVEL WITHIN G) EQUIPMENT SCHEDULE - DIFFUSERS, GRILLES &c REGISTERS NOTES: SEE ALL AND ARCH. REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS. FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN -INS WITH AIR SCOOP BALANCE DAMPER. NECK SIZE AS SHOWN ON THE DRAWINGS. APPROVED MANUFACTURER: PRICE (EXCEPT AS NOTED *) EQUIP. NO. MOUNTING TYPE MODEL NUMBER ACCESSORIES/REMARKS G-1 LAY -IN CEILING (SUPPLY) SCD (24X24) (1)(4) G-2 LAY -IN CEILING (RETURN) PDDR (24X24) (1) G-3 LINEAR (SUPPLY) SDS (2)(3)(5) G-4 LAY -IN CEILING (EXHAUST) PDDR (1) G-5 SURFACE (RETURN) 630 (2) G-6 DOOR (TRANSFER) ATG 70 G-7 SURFACE (SUPPLY) CVD (2) G-8 SURFACE (SUPPLY) AL271 (2) (6) LIMA MANUFACTURER G-9 SURFACE (RETURN) 530 47.7W (1) WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY -IN TYPE DIFFUSER. (2) PROVIDE WITH FACE OPERABLE DAMPER. (3) LINEAR DIFFUSER SHALL BE PROVIDED WITH SDB SUPPLY PLENUM BY PRICE. (4) WHERE USED IN GYP BOARD CEILINGS, DUCT -MOUNTED DAMPER SHALL BE ACCESSIBLE BY LIFTING DIFFUSER OUT OF ANGLE -FRAME FOR ACCESS TO ABOVE -CEILING AREA. (5) LINEAR DIFFUSER SHALL BE 2 -SLOT MODEL. ONE SLOT SHALL BE SET TO HORIZONTAL PATTERN, OTHER SHALL BE SET TO VERTICAL PATTERN. (6) PROVIDE SQUARE TO ROUND NECK ADAPTER. EQUIPMENT SCHEDULE — FAN I APPROVED MANUFACTURER LOREN COOK CO. EQUIPMENT NUMBER EF -1 EF -2 EF -3 EF -4 MOUNTING TYPE NEW FLEXIBLE CEILING CEILING CEILING CEILING MECHANICAL EQUIPMENT AFTER DEMOLITION WORK TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL MOTORI DRIVE DIRECT DIRECT DIRECT DIRECT FAN RPM 965 965 765 905 M CFM 70 70 70 100 ` 0C) S. P. .4 .4 .2 .2 cuc m HP 51.4W 51.4W 47.7W 74.7W MOTOR VOLTS/PHASE 115V/1 115V/1 115V/1 115V/1 MODEL NUMBER GC -142 GC -142 GC -142 GC -144 ACCESSORIES/REMARK (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(6) NOTE: (1): BACK DRAFT DAMPER (2): SPEED CONTROLLER (3): UNIT MOUNTED DISCONNECT (4): WALL CAP (5): EXHAUST FAN SHALL BE CONTROLLED BY WALLSWITCH. (6): EXHAUST FAN SHALL BE CONTROLLED BY THERMOSTAT. POWER ON AT 807, SHUTDOWN AT 777. HVAC LEGEND SOFFIT. AHU AIR HANDLING UNIT CU CONDENSING UNIT EF EXHAUST FAN NEW DU -_T NEW FLEXIBLE DUCT NEW DU T DUCT TRANSITION SA SUPPLY AIR RA RETURN AIR EA EXHAUS[ AIR BD BALANC NG DAMPER ® NEW SU PLY DIFFUSER E SYSTEM IN WORST FUNCTIONAL STATE. REMOVE NEW RETURN GRILLE o NEW LINEAR DIFFUSER R i T RELOCA ED EXISTING THERMOSTAT REQUIRED ALL REMAIN114G MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. O DUCT -MOUNTED SMOKE DETECTOR MO MOTORI ED DAMPER CU IF - - cu— HVAC ADDITIOI�IAL BID AND DEMOLII 1. MECHANICAL CONTR CTOR SHALL INSPECT EXISTING THREE 5 -TON SPLIT SYSTEMS AND DETERMI E SYSTEM IN WORST FUNCTIONAL STATE. REMOVE THIS CONDENSER UNIT AND ITS ASSOCIATED AIRHANDLER. MAKE EQUIPMENT AVAILABLE TO BUILDING OWNER PRIOR TO DISPOSAL. DISPOSE OF EQUIPMENT IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS. 2. MECHANICAL CONTRACTOR SHALL INSPECT, SERVICE, AND REPAIR AS REQUIRED ALL REMAIN114G MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. PE PE PE 3. RELOCATE EXISTING AIRHANDLERS TO LOCATIONS INDICATED AND RE -TAG EQUIPMENT TO MATCH NEW DESIGNATION AS REQUIRED. 4. COORDINATE WITH E ECTRICAL CONTRACTOR AND PROVIDE CONDENSATE PUMPS AT NEW AIRHA DLER LOCATIONS AND DISPOSE OF CONDENSATE AT EXISTING CONDENSATE DISPOSAL LOCATION. L — — — — — —— ——————————— — — — — —� WALL TYPE LEGEND NON RATED: 1 HR. RATED: — — 2 HR. RATED: 7/31/17 2822M1.01 ROBERT L. HINKLE PE 29302 POWELL & HINKLE ENGINEERING, P.A. M M N Z� W 1409 KINGSLEY AVENUE, BLDG 12A GALTON P & H LANE C. MOK PE 33192 ORANGE PARK, FLORIDA 32073 R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 R. Ht .. E No.48076 • STATE O `` • C i PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M M N Z� W N co -j J H U) z U co co -4--+ V 0') N CD p zF- ¢¢o W g L 12tf Q J L0 � U(D N N Q W Z M Q co O m = ` 0C) 0 V W wz L cuc m g (3) c', m C �? o N Y U C6 C) N u') M N ~ L' -� N O C/) o rn Z� O `o LL. =3 � ti rn > rn rn N <- rn W M 2 PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M M N Z� W N co -j J H z U = a m p zF- W g LL 12tf Q J � � U(D z Q W Z Q z J O m = U V W wz W g ILL Q M O Nt PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH F HVAC GENERAL NOTES I 1. PROVIDE A COMPLETE HEATING, AND AIR CONDITIONING SYSTEM AS SHOWN ON DRAWINGS AND MEETING THE REQUIREMENTS OF FLORIDA BUILDING CODE — MECHANICAL AND APPLICABLE STATE AND LOCAL CODES. OBTAIN ALL PERMITS AND NECESSARY CERTIFICATES, SEE SPECIFICATION FOR I ADDITIONAL INFORMATION AND REQUIREMENTS. 2. COORDINATE PIPING, DUCTWORK AND EQUIPMENT LOCATION WITH PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 3. DO NOT INSTALL PIPING AND DUCTWORK ABOVE ELECTRICAL PANELS AND ELECTRICAL EQUIPMENT WHEN PROHIBITED BY CODES. COORDINATE ELECTRICAL PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. (ROUGH WORK WILL BE REJECTED). 5. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED GALVANIZED SHEET METAL. ALL RETURN AIR AND TRANSFER AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH ACOUSTIC DUCT LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR OPENING SIZE. INCREASE DUCT SIZE TO ALLOW FOR DUCT LINER THICKNESS. ALL EXHAUST AIR AND OUTSIDE INTAKE AIR DUCTWORK SHALL BE UN—INSULATED GALVANIZED SHEET METAL. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 16. DUCT INSULATION SHALL BE REQUIRED THICKNESS TO PROVIDE MINIMUM THERMAL RESISTANCE "R" OF 6.0 WHEN DUCT IS LOCATED WITHIN BUILDING AND ON NON—AIR CONDITIONED SIDE OF BUILDING INSULATION AND "R" OF 4.2 WHEN DUCT IS LOCATED ON AIR CONDITIONED SIDE OF BUILDING INSULATION. ALL "R" VALUES ARE "AS—INSTALLED" MINIMUMS. I I 7. DO NOT MAKE ANY CHANGES IN DESIGN WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT. CHANGES IN DESIGN MEANS ANY CHANGE WHICH WILL AFFECT THE CAPACITY, RELIABILITY, OPERATION OR SAFETY OF THE SYSTEMS OR ANY PARTS THEREOF, INCLUDING CHANGES WHICH MAY BE REQUIRED TO CONFIRM TO LOCAL REGULATIONS OR CODES. 8. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT. I 10. SEE ARCHITECTURAL REFLECTED CEILING FOR EXACT LOCATION OF CEILING DIFFUSERS. 11. PRIOR TO FABRICATION OF HVAC DUCT WORK FOR FIELD INSTALLATION, FIELD VERIFY EXISTING ROOF JOIST SPACING, JOIST OPENING SIZE AND LOCATION. IF EXISTING STRUCTURAL CONDITIONS DO NOT PROVIDE SUFFICIENT SPACE FOR PROPER DUCT INSTALLATION, REPORT THIS MATTER TO THE ARCHITECT IMMEDIATELY. (DO NOT FABRICATE DUCT WORK UNTIL FURTHER INSTRUCTIONS ARE ISSUED BY THE ARCHITECT). 12. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR. L— — — — — — — — — — — — — — — — — --- — — — — J HVAC FLAG NOTES: 0 G-3, 4' LENGTH, 2 SLOTS. 200 CFM. O G-9, 24X16 N. O3 G-2, 24X12 N MODULE. 18X6 NECK. 5 ® WALLCAP. O5 G-2, 8"0 NECK. (D G-6, 22X22 IN DOOR. O G-7, 6X4, 20 CFM. 35 CFM. ® 8"0 OA DUCT FROM GOOSENECK ON R�)OF. 0 10"0 OA DUCT FROM GOOSENECK ON ROOF. 10 MOTORIZED DAMPER CFM SET TO 95 11 MOTORIZED DAMPER CFM SET TO 215 12 G-2, 8X8 NECK. 140 CFM. PROVIDE WITH DAMPER IN NECK 13 SUPPLY DUCT SHALL TRAVEL WITHIN EQUIPMENT SCHEDULE — DIFFUSERS, GRILLES & REGISTERS NOTES: SEE ALL AND ARCH. REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS, FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN—INS WITH AIR SCOOP BALANCE DAMPER. NECK SIZE AS SHOWN ON THE DRAWINGS. APPROVED MANUFACTURER: PRICE (EXCEPT AS NOTED *) EQUIP. NO. MOUNTING TYPE MODEL NUMBER ACCESSORIES/REMARKS G-1 LAY—IN CEILING (SUPPLY) SCD (24X24) (1)(4) G-2 LAY—IN CEILING (RETURN) PDDR (24X24) (1) G-3 LINEAR (SUPPLY) SDS (2)(3)(5) G-4 LAY—IN CEILING (EXHAUST) PDDR (1) G-5 SURFACE (RETURN) 630 (2) G-6 DOOR (TRANSFER) ATG 70 G-7 SURFACE (SUPPLY) CVD (2) G-8 SURFACE (SUPPLY) AL271 (2) (6) LIMA MANUFACTURER G-9 SURFACE (RETURN) 530 47.7W (1) WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY—IN TYPE DIFFUSER. (2) PROVIDE WITH FACE OPERABLE DAMPER. (3) LINEAR DIFFUSER SHALL BE PROVIDED WITH SDB SUPPLY PLENUM BY PRICE. (4) WHERE USED IN GYP BOARD CEILINGS, DUCT—MOUNTED DAMPER SHALL BE ACCESSIBLE BY LIFTING DIFFUSER OUT OF ANGLE—FRAME FOR ACCESS TO ABOVE—CEILING AREA. (5) LINEAR DIFFUSER SHALL BE 2—SLOT MODEL. ONE SLOT SHALL BE SET TO HORIZONTAL PATTERN, OTHER SHALL BE SET TO VERTICAL PATTERN. (6) PROVIDE SQUARE TO ROUND NECK ADAPTER. EQUIPMENT SCHEDULE — FAN APPROVED MANUFACTURER LOREN COOK CO. EQUIPMENT NUMBER EF -1 EF -2 EF -3 EF -4 MOUNTING TYPE IN ACCORDANCE WITH CEILING CEILING CEILING CEILING MECHANICAL EQUIPMENT AFTER DEMOLITION WORK TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL NEW DESIGNATION AS REQUIRED. DRIVE DIRECT DIRECT DIRECT DIRECT FAN RPM 965 965 765 905 U CFM 70 70 70 100 zo Jm S. P. .4 .4 .2 .2 oEn HP 51.4W 51.4W 47.7W 74.7W MOTOR VOLTS/PHASE 115V/1 115V/1 115V/1 115V/1 MODEL NUMBER GC -142 GC -142 GC -142 GC -144 ACCESSORIES/REMARK (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(6) NOTE: (1): BACK DRAFT DAMPER (2): SPEED CONTROLLER (3): UNIT MOUNTED DISCONNECT (4): WALL CAP (5): EXHAUST FAN SHALL BE CONTROLLED BY WALLSWITCH. (6): EXHAUST FAN SHALL BE CONTROLLED BY THERMOSTAT. POWER ON AT 807, SHUTDOWII AT 777. HVAC LEGEND AHU CU EF SA RA R � T) O SOFFIT. Q AIR HANDLING UNIT CONDE SING UNIT EXHAU 3T FAN NEW DUCT NEW FLEXIBLE DUCT NEW DUCT CU -1 DUCT RANSITION 1— SUPPL AIR 'I RETURN AIR EXHAUST AIR BALANCING DAMPER NEWSUPPLY DIFFUSER NEW R=TURN GRILLE NEW LINEAR DIFFUSER RELOCATED EXISTING THERMOSTAT DUCT— OUNTED SMOKE DETECTOR MOTOR ZED DAMPER HVAC ADDITIONAL BID AND DEMOLIT 1. MECHANICAL CONTRACTOR SHALL INSPECT EXISTING THREE 5—TON SPLIT I SYSTEMS AND DETERMINE SYSTEM IN WORST FUNCTIONAL STATE. REMOVE THIS CONDENSER UNII AND ITS ASSOCIATED AIRHANDLER. MAKE EQUIPMENT AVAILABLE TO BUILDING OWNER PRIOR TO DISPOSAL. DISPOSE OF EQUIPMENT IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS. 2. MECHANICAL CONTRACTOR SHALL INSPECT, SERVICE, AND REPAIR AS REQUIRED ALL REMAINING MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. PE PE PE 3. RELOCATE EXISTING AIRHANDLERS TO LOCATIONS INDICATED AND RE—TAG EQUIPMENT TO MATCH NEW DESIGNATION AS REQUIRED. 4. COORDINATE WITH ELECTRICAL CONTRACTOR AND PROVIDE CONDENSATE PUMPS AT NEW AIRH NDLER LOCATIONS AND DISPOSE OF CONDENSATE AT EXISTING CONDENSATE DISPOSAL LOCATION. L- - - - -- -----------------� WALL TYPE LEGEND NON RATED: 1 HR. RATED: — — — 2 HR. RATED: — 7/31/17 2822M1.01 ROBERT L. HINKLE PE 29302 POWELL & HINKLE ENGINEERING, P.A. C.0 +� U ry W 1409 KINGSLEY AVENUE, BLDG 12A GALTON P & H LANE C. MOK PE 33192 ORANGE P ARK, FLORIDA 320'73 R. HINKLE PE 480'76 (904) 264-5570 FAX:(904) 278-2646 THOMAS ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 SEAL No. 48076 STATE O f O ' 1DNA1� PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH C.0 +� U ry W a' N CD J z 0 a. Lu 0 U w 0 V) N N z U. M Q Q J cu .0 o Q V 0 U W L (6 m L Q zo Jm cu> �� c c a? Uwz Lu oEn U LL co o N � M N � cn � 0 Mo co ID > rn N M CY C) M W MF_ PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M N Z ry W N co J z LL a. Lu 0 U w 0 zc) f— z U. Y Q Q Q J � o Q V � j z W Q J Q zo Jm U Uwz Lu Jg LL Q M O PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH SUPPORT DUCT FROM STRUCTURE DO NOT LAY ON LIGHT FIXTURES OR CEILING. PRE -INSULATED FLEX DUCT INSULATED MECH. PLENUM SHEET METAL SCREW AT 9"t O.C.; CAULK AND SEAL AROUND SCREW HEADS AFTER INSTALLATION ROOF CURB FLASHING ROOF CURB, SE ARC ITECT. DWG. ORD TAILS. PROVIDE PLENUM EXTENTION WHEN NEEDED. SLOT DIFFUSER DETAIL - LINEAR DIFFUSER N.T.S. TRANSITION DUCT TO SUIT FAN OUTLET DUCT HANGER STRAPS FLEX. CONN. (TYP.) (SECURE TO STRUCTURE) STRUCTURE ---� SEE PLAN FOR DUCT SIZE DUCT SECURE W/SHEET / METAL SCREWS CEILING (TYP. FOR 8) CEILING FAN, SEE PLAN FOR LOCATION CEILING GRILLE AND SCHEDULE FOR SIZE INTEGRAL WITH FAN O PRE -WIRED, FACTORY MOUNTED SPEED CONTROLLER ACCESSABLE INSIDE FAN HOUSING. O UNIT MOUNTED DISCONNECT SWITCH. TYPICAL CEILING FAN MOUNTING DETAIL N.T.S. CAULK TO PROVIDE WATER TIGHT SEAL. WALL CAP WITH BUILT-IN DAMPER & BIRDSCREEN. DETAIL - WALL CAP N.T.S. NTS 3/8" BOLT (TYP.) OA DUCT BD Te RA DUCT TS -H }� (D 15° INSECT SCREEN 45' CAULK AND SEAL JOINTS AROUND FLASHING ROOF SEE UNISTRU T DETAIL -VIBRATION ISOLATORS - 3/8" ALL TREAD- RA READ- AHU UNIT ACCESS PANEL EZ TRAP INC. MODEL EZT 200 INLINE CONDENSATE OVERFLOW SWITCH. CONNECT TO AHU TO SHUT OFF UNIT WHEN WATER FILLS TRAP ABOVE INLET. BALL VALVE PER EQUIPMENT MANUFACTURER'S A/C UNIT _ �� REQUIREMENT SPIN -IN FITTING WITH AIR SCOOP AND LOCKING DAMPER SUPPLY DUCT INSULATION - isCONDENSATE TO FLOOR DRAIN. SLOPE TOWARD DRAIN. PVC CONDENSATE TRAP (MIN. 4" DEEP OR PER EQUIP. MANUFACTURER'S REQUIREMENTS) CONDENSATE TRAP DETAIL WITH FLOAT SWITCH N.T.S. ATTACH STRAP H BLDG. STRUCTURE WITt BOLT AND LOCK 1 FLEXIBLE CONNECTOR (TYP.) -Z SA DUCT O _,-2" x 1" UNISTRUT, FOR 1 TON AHU. CONDENSATE DRAIN LINE REFRIGERANT LINES MINIMUM 18 GAGE STAINLESS STEEL OR MINIMUM 1/8" THICK FIBERGLASS TO FORM A 6" DEEP MINIMUM SEAMLESS SECONDARY DRAIN AN WITH FORMED AND SEALED CORNERS. EXTEND 4" BEYOND UNIT ON ALL SIDES. PROVIDE FLOATS ITCH TO SHUT DOWN UNIT AS SECONDARY DRAIN PAN FILLS. NOT TO SCALE HVAC BRANCH DUCT, SEE PLAN FOR SIZE AND LOCATION. N.T.S. CEILING ANDLER C11' INSULATED SDUCT, SEE PLAFOR SIZSUPPORT DUCT FROM STRUCTURE, DO NOT` HVAC SUPPL AIR LAY ON LIGHT DUCT FROM AHU, FIXTURES OR CEILING. SEE PLAN FCR SIZE AND LOCATION PRE -INSULATED FLEX. DUCT FROM MAIN SA DUCT TO SA OUTLET SEE PLAN FOR LOCATION PRE -INSULATED FLEX. DUCT, SEE PLAN FOR SIZE I� I S1 DUCTWORK PER SMACNA STANDARDS SUPPORT DUCT FROM STRUCTURE WITH HANGER STRAP II II II I� II I INSULATED SPIN -IN FITTING WITH AIR SCOOP AND LOCKING DAMPER INSULATION SUPPORT DUCT FROM STRUCTURE DO NOT LAY ON LIGHT FIXTURES OR CEILING. PRE -INSULATED FLEX. DUCT DIFFUSER DIFFUSER INSTALLATION DETAIL N.T.S. ATTACH STRAP HANGER TO BLDG. STRUCTURE WITH ANCHOR BOLT AND LOCK WASHER - TYP. STRAP HANGER FOR HVAC DUCTWORK PER SMACNA STANDARDS RECT. DUCT WITH WIDTH OF 22" AND SMALLER, SEE PLAN FOR SIZE AND LOCATION DETAIL - DUCT SUPPORT NOT TO SCALE I RETURN DUCT INSULATION RECT. DUCT WITH WIDTH OF 24" OR LARGER, SEE PLAN FOR SIZE AND LOCATION LOAD RATED FASTENER FOR STRAP HANGER PER SMACNA STANDARDS WALL TYPE LEGEND NON RATED: 1 HR. RATED: — — — — 2 HR. RATED: - INSULATION LAY -IN CEILING - PRE -INSULATED FLEX. DUCT RA DUCT, SEE PLAN FOR SIZE RA GRILLE, SEE PLAN FOR SIZE AND LOCATION RA GRILLE INSTALLATION DETAIL N.T.S. 7/31/17 � ON2822M2.01 ROBERT L. HINKL PE 29302 POWELL & HINKLE ENGINEERING, P.A. co co -f-0 1409 KINGSLEY AVENUE, BLDG 12A GALTON P & H LANE C. MOK PE 33192 ORANGE PARK, FLORIDA 32073 R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS ENGINEERING CORPORATION FLA. REG. EB -4577 RICHARD DAVID R. M. ELDER A. MATHEWS SPELL JR. PE PE PE 56121 59418 54729 SEAL R. E . . A � 0.48076 .o STATE4F ,c c� •.. ,LORI A' it, ,yt L- W co co -f-0 m N W CD J W U a U Q W (Dm z W 0 N N J M Q E Z 0 0 a =Z � U v cz cu m i W > co ca •> c c a? o cnU Q _j LL Q cu 0 co � EoN M N ~_ L s •sN C\- O O cn ZX 0 o ca cn LL• a> =3m ti >c rn rn Q N coo rn W co co PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M2.1 M co N N co W J LL J W U a U Q W (Dm z W 0 wZ J �g Q Z Z W a =Z o -i = V <0 W W z W J Q _j LL Q 0 PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M2.1 F - HVAC GENERAL NOTES I I 1. PROVIDE A COMPLETE HEATING, AND AIR CONDITIONING SYSTEM AS SHOWN ON DRAWINGS AND MEETING THE REQUIREMENTS OF FLORIDA BUILDING CODE - MECHANICAL AND APPLICABLE STATE AND LOCAL CODES. OBTAIN ALL PERMITS AND NECESSARY CERTIFICATES. SEE SPECIFICATION FOR ADDITIONAL INFORMATION AND REQUIREMENTS. 2. COORDINATE PIPING, DUCTWORK AND EQUIPMENT LOCATION WITH PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 3. DO NOT INSTALL PIPING AND DUCTWORK ABOVE ELECTRICAL PANELS AND ELECTRICAL EQUIPMENT WHEN PROHIBITED BY CODES. COORDINATE ELECTRICAL PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. 4. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. (ROUGH WORK WILL BE REJECTED). 5. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED GALVANIZED SHEET METAL. ALL RETURN AIR AND TRANSFER AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL WITH ACOUSTIC DUCT LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR OPENING SIZE. INCREASE DUCT SIZE TO ALLOW FOR DUCT LINER THICKNESS. ALL EXHAUST AIR AND OUTSIDE INTAKE AIR DUCTWORK SHALL BE UN -INSULATED GALVANIZED SHEET METAL. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 6. DUCT INSULATION SHALL BE REQUIRED THICKNESS TO PROVIDE MINIMUM THERMAL RESISTANCE "R" OF 6.0 WHEN DUCT IS LOCATED WITHIN BUILDING AND ON NON -AIR CONDITIONED SIDE OF BUILDING INSULATION AND "R" OF 4.2 WHEN DUCT IS LOCATED ON AIR CONDITIONED SIDE OF BUILDING INSULATION. ALL "R" VALUES ARE "AS -INSTALLED" MINIMUMS. I I 7. DO NOT MAKE ANY CHANGES IN DESIGN WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT. CHANGES IN DESIGN MEANS ANY CHANGE WHICH WILL AFFECT THE CAPACITY, RELIABILITY, OPERATION OR SAFETY OF THE SYSTEMS OR ANY PARTS THEREOF, INCLUDING CHANGES WHICH MAY BE REQUIRED TO CONFIRM TO LOCAL REGULATIONS OR CODES. 8. IF ANY DEPARTURES FROM THE DRAWINGS AND SPECIFICATIONS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ARCHITECT. I 10. SEE ARCHITECTURAL REFLECTED CEILING FOR EXACT LOCATION OF CEILING DIFFUSERS. 11. PRIOR TO FABRICATION OF HVAC DUCT WORK FOR FIELD INSTALLATION, FIELD VERIFY EXISTING ROOF JOIST SPACING, JOIST OPENING SIZE AND LOCATION. IF EXISTING STRUCTURAL CONDITIONS DO NOT PROVIDE SUFFICIENT SPACE FOR PROPER DUCT INSTALLATION, REPORT THIS MATTER TO THE ARCHITECT IMMEDIATELY. (DO NOT FABRICATE DUCT WORK UNTIL FURTHER INSTRUCTIONS ARE ISSUED BY THE ARCHITECT). 12. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR. L- - - - - - - - - - - - - - - - - - - - - - - - J HVAC FLAG NOTES: 01 G-3, 4' LENGTH, 2 SLOTS. 200 CFM. O G-9, 24X16 N. O G-2, 24X12 N MODULE. 18X6 NECK. 56`. ® WALLCAP. Q G-2, 8"0 NECK. Q G-6, 22X22 IN DOOR. (DG -7, 6X4, 20 CFM. ® 8"0 OA DUCT FROM GOOSENECK ON ROC CFM. 9O 10"0 OA DUCT FROM GOOSENECK ON ROOF. 10 MOTORIZED DAMPER CFM SET TO 95 CFNI. 11 MOTORIZED DAMPER CFM SET TO 215 CFM. 12 G-2, 8X8 NECK. 140 CFM. PROVIDE WITF 11 DAMPER IN NECK 13 SUPPLY DUCT SHALL TRAVEL WITHIN EQUIPMENT SCHEDULE - DIFFUSERS, GRILLES & REGISTERS NOTES: SEE ALL AND ARCH. REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS. FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN -INS WITH AIR SCOOP BALANCE DAMPER. NECK SIZE AS SHOWN ON THE DRAWINGS. APPROVED MANUFACTURER: PRICE (EXCEPT AS NOTED *) EQUIP. NO. MOUNTING TYPE MODEL NUMBER ACCESSORIES/REMARKS G-1 LAY -IN CEILING (SUPPLY) SCD (24X24) 1)(4) G-2 LAY -IN CEILING (RETURN) PDDR (24X24) (1) G-3 LINEAR (SUPPLY) SDS (2)(3)(5) G-4 LAY -IN CEILING (EXHAUST) PDDR (1) G-5 SURFACE (RETURN) 630 (2) G-6 DOOR (TRANSFER) ATG 70 G-7 SURFACE (SUPPLY) CVD 2) G-8 SURFACE (SUPPLY) AL271 (2) (6) LIMA MANUFACTURER G-9 SURFACE (RETURN) 530 47.7W (1) WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY -IN TYPE DIFFUSER. (2) PROVIDE WITH FACE OPERABLE DAMPER. (3) LINEAR DIFFUSER SHALL BE PROVIDED WITH SDB SUPPLY PLENUM BY PRICE. (4) WHERE USED IN GYP BOARD CEILINGS, DUCT -MOUNTED DAMPER SHALL BE ACCESSIBLE BY LIFTING DIFFUSER OUT OF ANGLE -FRAME FOR ACCESS TO ABOVE -CEILING AREA. (5) LINEAR DIFFUSER SHALL BE 2 -SLOT MODEL. ONE SLOT SHALL BE SET TO HORIZONTAL PATTERN, OTHER SHALL BE SET TO VERTICAL PATTERN. (6) PROVIDE SQUARE TO ROUND NECK ADAPTER. EQUIPMENT SCHEDULE - FAN APPROVED MANUFACTURER LOREN COOK CO. EQUIPMENT NUMBER EF -1 EF -2 EF -3 EF -4 MOUNTING TYPE AHU AIR HANDLING CEILING CEILING CEILING CEILING FAN " TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL 56121 DRIVE DIRECT DIRECT DIRECT DIRECT FAN RPM 965 965 765 905 DAMPER CFM 70 70 70 100 DIFFUSER S. P. .4 .4 .2 .2 D DAMPER HP 51.4W 51.4W 47.7W 74.7W MOTOR VOLTS/PHASE 115V/1 115V/1 115V/1 115V/1 MODEL NUMBER GC -142 GC -142 GC -142 GC -144 ACCESSORIES/REMARK (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(5) (1)(2)(3)(4)(6) NOTE: (1): BACK DRAFT DAMPER (2): SPEED CONTROLLER (3): UNIT MOUNTED DISCONNECT 4): WALL CAP (5): EXHAUST FAN SHALL BE CONTROLLED BY WALLSWITCH. (6): EXHAUST FAN SHALL BE CONTROLLED BY THERMOSTAT. POWER ON AT 807, SHUTDOWN AT 77°F. SOFFIT. C WALL TYPE LEGEND NON RATED: P & H 1 HR. RATED: - - - 2 HR. RATED: - ENGINEERIN 7/31/17 2822M1.01 OH POWELL & HINKLE ENGINEERING, P.A. CU..- 2 L. HINKLE , HVAC LEGEND 1409 KINGSLEY AVENUE, BLDG 12A GALTON C. MOK AHU AIR HANDLING UNIT CU CONDENSING UNIT EF EXHAUST FAN " NEW DUCT (904) 264-5570 FAX:(904) 278-2646 NEW FLE IBLE DUCT NEW DUCT 56121 G CORPORATION FLA. REG. EB -4577 CU -1 DUCT TR NSITION i - I I SA SUPPLY AdR I f I fi RA RETURN AIR--- EA EXHAUST AIR BD BALANCING DAMPER ® NEW SUPPLY DIFFUSER ' NEW RETURN GRILLE NEW LINEAR DIFFUSER R T) RELOCATED EXISTING THERMOSTAT OS DUCT -MOUNTED SMOKE DETECTOR OM MOTORIZ D DAMPER Z HVAC ADDITIONAL BID AND DEMOLITION NOTES: 1. MECHANICAL CONTRACTOR SHALL INSPECT EXISTING THREE 5 -TON SPLIT SYSTEMS AND DETERMINE SYSTEM IN WORST FUNCTIONAL STATE. REMOVE THIS CONDENSER UNIT AND ITS ASSOCIATED AIRHANDLER. MAKE EQUIPMENT AVAILABLE TO BUILDING OWNER PRIOR TO DISPOSAL. DISPOSE OF EQUIPMENT IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS. 2. MECHANICAL CONTRA TOR SHALL INSPECT, SERVICE, AND REPAIR AS REQUIRED ALL REMAININ3 MECHANICAL EQUIPMENT AFTER DEMOLITION WORK IS COMPLETED. 3. RELOCATE EXISTING AIRHANDLERS TO LOCATIONS INDICATED AND RE -TAG EQUIPMENT TO MATCH NEW DESIGNATION AS REQUIRED. 4. COORDINATE WITH EL CTRICAL CONTRACTOR AND PROVIDE CONDENSATE PUMPS AT NEW AIRHAN LER LOCATIONS AND DISPOSE OF CONDENSATE AT EXISTING CONDENSATE ISPOSAL LOCATION. L- - - - - -- ----------- - - - - - J WALL TYPE LEGEND NON RATED: P & H 1 HR. RATED: - - - 2 HR. RATED: - ENGINEERIN 7/31/17 2822M1.01 OH POWELL & HINKLE ENGINEERING, P.A. ROBERT L. HINKLE PE 29302 1409 KINGSLEY AVENUE, BLDG 12A GALTON C. MOK PE 33192 ORANGE PARK, FLORIDA 32073 LANE R. HINKLE PE 48076 (904) 264-5570 FAX:(904) 278-2646 THOMAS M. ELDER PE 56121 G CORPORATION FLA. REG. EB -4577 RICHARD A. MATHEWS PE 59418 fB DAVID R. SPELL JR. PE 54729 SEAL `��� eee C •. i G i • No.48076 STATE O41 PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH 00 -f-0 0C14 Ie W o 0 J zLjj 0 CD C)= i U w m z (j N N F- Z J LL M Q Q fB E 0 0 U- 0 c/i _ z Z cuU m � Q J cu c o Lu o Y Z U T g 0 O N U') M N ti O o o Z 0 o X cu c/5 LL_ ID � ti > M rn rn Q v N M 0 rn W MF_ cn PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH M M N Z Ie W N m _j J zLjj ILL C)= U w m z (j F- Z J LL � w Q Q _ z Z z � Q J m U Lu W Z W g M O PROJECT NO. 17032 ISSUE DATE: 8-02-17 REVISIONS: DRAWN BY: JLH