1805 Mayport Rd hydrant flow test results �t
May 15,2018
Chelsea Leonard
1805 Mayport Roar Property Owner
RE: Fire Flow Test for 1805 Mayport Road
Ms. Leonard:
The City performed a flow test on the fire hydrant on Stanley Road,adjacent to 1805 Mayport
Road(proposed Atlantic Beach Arts Market)with the following results:
Location: Stanley Rd. &Mayport Rd.
Test Date/Time: 5/15/18 8:41 AM
Static Pressure: 50 psi
Residual Pressure: 40 psi
Test Flow Rate: 1,060 gpm
Estimated Flow @ 20 psi: 1,919 gpm
Tested by: Chris Walker, Division Director
The above estimated flow at 20 psi is based on NFPA section 291,AW WA M-17.
Should you need additional information,please call me at(904)247-5834 or email me at
kmoore(alcoab.us.
Sincerely,
V ; r4'
Kayle Moore,PE
Public Utilities Director
cc: Chris Walker,Division Director
Dan Arlington, Building Departmentmoore.chelsea@att.net
Public Utilities Department 902 Assisi Lane
Jacksonville, FL 32233
(904)247-5834