Loading...
1805 Mayport Rd hydrant flow test results �t May 15,2018 Chelsea Leonard 1805 Mayport Roar Property Owner RE: Fire Flow Test for 1805 Mayport Road Ms. Leonard: The City performed a flow test on the fire hydrant on Stanley Road,adjacent to 1805 Mayport Road(proposed Atlantic Beach Arts Market)with the following results: Location: Stanley Rd. &Mayport Rd. Test Date/Time: 5/15/18 8:41 AM Static Pressure: 50 psi Residual Pressure: 40 psi Test Flow Rate: 1,060 gpm Estimated Flow @ 20 psi: 1,919 gpm Tested by: Chris Walker, Division Director The above estimated flow at 20 psi is based on NFPA section 291,AW WA M-17. Should you need additional information,please call me at(904)247-5834 or email me at kmoore(alcoab.us. Sincerely, V ; r4' Kayle Moore,PE Public Utilities Director cc: Chris Walker,Division Director Dan Arlington, Building Departmentmoore.chelsea@att.net Public Utilities Department 902 Assisi Lane Jacksonville, FL 32233 (904)247-5834