303 ATLANTIC BLVD - PERMIT FIRE18-0002- --T- y - I r b I / i- b -1 9 10 -r- 1 1 12 A ..ri 1r.. �R X x A N as m U oT N1' a In N I ' N U CD N 0 f— O J a fD M X N 303 303 Atlantic Bvld. Atlantic Beach, FL 32233 GENERAL PROJECT NOTES 1) PROVIDE 120 VOLT DEDICATED CIRCUIT FOR FIRE ALARM SYSTEM BREAKER TO BE MARKED "FIRE ALARM CIRCUIT". BREAKER SHALL BE MARKED IN RED AND MUST HAVE A BREAKER LOCK INSTALLED ON IT. 2) CONDUIT AND BOXES INSTALLED BY ELECTRICAL CONTRACTOR UNDER SEPERATE CONTRACT AND ELECTRICAL PERMIT. 3) FIELD VERIFY LOCATION OF ALL TAMPER SWITCHES, FLOW SWITCHES, AND BACKFLOW TAMPER SWITCHES PRIOR TO CONNECTION. 4) FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH THE FOLLOWING CODES: 2017 FLORIDA FIRE PREVENTION CODE -6TH EDITION, FLORIDA SPECIFIC EDITION OF NFPA 1, NFPA 70 (2014) EDITION, NFPA 72 (2013) EDITION, FLORIDA SPECIFIC EDITION OF NFPA 101 (2015) EDITION. 5) ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED. 6) THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 7) THE LIGHT OUTPUT SHALL COMPLY WITH THE POLAR DISPERSION REQUIREMENTS OF ANSI/UL 1971, STANDARD FOR SAFETY SIGNALING DEVICES FOR HEARING IMPAIRED, OR EQUIVALENT. 8) ALL VISUAL NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED IN ACCORDANCE WITH NFPA 72:18.5 g) CLASS AND STYLE FOR ALL CIRCUITS ARE AS FOLLOWS: (1) INITIATING DEVICE CIRCUITS — CLASS B, STYLE A (2) SIGNALING LINE CIRCUITS — CLASS B, STYLE 4 (3) NOTIFICATION CIRCUITS — CLASS B, STYLE Y FLORIDA ADMINISTRATIVE CODE 61 G15-30.002-1 (8) SHOP DRAWINGS: DRAWINGS DEPICTING INSTALLATION MEANS AND METHODS, CATALOG INFORMATION ON STANDARD PRODUCTS, PREPARED BY A CONTRACTOR, MANUFACTURERS, OR PROFESSIONAL ENGINEERS FOR INCORPORATION INTO THE PROJECT WHICH ARE PREPARED BASED ON ENGINEERING DIRECTION CONTAINED IN ENGINEERING DOCUMENTS. SHOP DRAWINGS DO NOT REQUIRE THE SIGNATURE, DATE AND SEAL OF A PROFESSIONAL ENGINEER. DynaFire, Inc. has produced this set of shop drawings to meet the intent of FAC 61 G15-30.002-1 CIRCUIT DESCRIPTION FACP PANEL HORN, STROBE CIRCUIT NAC PANEL HORN, STROBE CIRCUIT CP = FACP NAC CIRCUITS B = REMOTE POWER SUPPLY NAC CIRCUITS LP 111-i uu u B1.11-1 j L DEVICE NUMBER CIRCUIT NUMBER TYPE OF PANEL / # DESIGNATION POWERING NOTIFICATION DEVICE SLC DEVICE DESCRIPTION MODULE INDICATOR �jEDEVICE NUMBER LOOP NUMBER L1M001 L1DO01 LOOP NUMBER DETECTOR INDICATOR DEVICE NUMBER SCOPE: INSTALL A CODE COMPLIANT REMOTE SUPERVISING STATION FIRE ALARM SYSTEM. 13x14-T15T 16-1 17X18r1 9 29 r 30 I 3,I -I FIRE ALAIRM EQUIPMENT LEGEND A QTYSYM DESCRIPTION MOUNTING P/N MFR BACK BOX B.B. SUPP 1 FACU FIRE ALARM CONTROL UNIT 72 AFF NFW2-100 NOTIFIER PROVIDED MANUFACTURER ©©©--- AC FIRE ©...©--. — 2ND FLOOR & ROOF LEVEL PLANS SMOKEDETECTOR FIRE ALARM PLAN — RISER SMOKE DETFCTOR ON CEILING OR WALL MOUNTED PER DRAWINGS NP -100 NOTIFIER 4" SQUARE BOX (2-1/8" DEEP) W/ ELECTRICAL 4 O PLAN — POINT TO POINT DETAILS W/ B21 OLP BASE SQUARE TO ROUND 1/2" RAISED P -RING (n WPB WEATHER-PROOF MANUAL PULL STATION 48" TO CENTER AFF NBG-12LOB NOTIFIER 4" SQUARE BOX (2-1/8" DEEP) W/ ELECTRICAL 1 U CD �-_, L L1 SINGLE GANG 1/2" RAISED P -RING T Q DM DUAL MONITOR MODULE AS SHOWN ON PLAN NDM-100 NOTIFIER 4" SQUARE BOX (2-1/8" DEEP) W/ EXTENSION RING ELECTRICAL 2 F- � w Q 6 ADDRESSABLE DUCT SMOKE DETECTOR INSTALLATION BY MECHANICAL CONTRACTOR DNRW NOTIFIER MOUNTED ON DUCTWORK PER NFPA 90A & 72 REQUIREMENTS ELECTRICAL W NP-10OR 4" SQUARE BOX W/ 1/2" MIN. FLEX TO DEVICE N 1 Wp WEATHER-PROOF HORN STROBE - WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF P2WK SYSTEM SENSOR 4" SQUARE BOX (2-1/8" DEEP) W/ ELECTRICAL cr) ° SINGLE GANG 1/2" RAISED P -RING m©m 1 F, M-1 ISOLATION MODULE FIELD DETERMINE N100 -ISO NOTIFIER 4" SQUARE BOX (2-1/8" DEEP) W/ EXTENSION RING ELECTRICAL 1 ss SURGE PROTECTION 120VAC = MIN. 3' AWAY FROM PROTECTED EQUIP. DTK-120HW DITEK 4" SQUARE BOX (2-1/8" DEEP) ELECTRICAL ©----© 120V MMMMMn- FIRE ALARM SYSTEM AC •1 ©----© JUNCTION BOX -PLAIN FACE AS SHOWN ON PLANS N/A / N/A 4" SQUARE BOX (2-1/8" DEEP) W/ ELECTRICAL W PLAIN FACE SEQUENCE OF OPERATIONS DRAWING INDEX FAO.0 �NNW & LEGEND WIRE TYPE MMMMMMMM FIRE ALARM • :/ ©©©--- FA2.0 FIRE ©...©--. — 2ND FLOOR & ROOF LEVEL PLANS SMOKEDETECTOR FIRE ALARM PLAN — RISER DETAIL -WATER 1 ©©©--- — BATTERY CALCULATIONS FA5.0 ©--©--- ALARM PLAN — POINT TO POINT DETAILS ©©©mmmMMMMMM (n � � G —r (D Q m J Q U CD �-_, L L1 T Q REVISIONS z O TAMPER SWITCH F- � w Q U L, (n Lv N 0 cr) mmm� m©m LLJ Q 00 \ ©----© --.---©- .. GROUND ©....© N mmmmmmnm - NOTIFICATION APPLIANCE SHORT ©----© MMMMMn- FIRE ALARM SYSTEM AC •1 ©----© MMMMMn- SEQUENCE OF OPERATIONS DRAWING INDEX FAO.0 COVER PAGE & LEGEND WIRE TYPE FA1.0 FIRE ALARM — IST FLOOR PLAN FA2.0 FIRE ALARM — 2ND FLOOR & ROOF LEVEL PLANS FA3.0 FIRE ALARM PLAN — RISER DETAIL FA4.0 FIRE ALARM — BATTERY CALCULATIONS FA5.0 FIRE ALARM PLAN — POINT TO POINT DETAILS FIRE ALARM CABLE LEGEND CABLE DESCRIPTION MANUF. WIRE TYPE S ADDRESSABLE (SLC) CIRCUIT WINDY CITY WIRE 2 Conductor 18go. FPLR (UL) B NOTIFICATION CIRCUIT WINDY CITY WIRE (2) 12ga. THHN FROM Qualifier: STEVEN HATCH LEAST 36" FROM ' DUCT RED = POSITIVE : BLUE = NEGATIVE A INITIATING CIRCUIT WINDY CITY WIRE (2) 14ga. THHN ' BELOW BUT NO LOWER ORANGE = POSITIVE : BLACK = NEGATIVE DEVICE INSTALLATION DETAIL 4x4-2-1/8 BOX 4x4-2-1/8 BOX ---Ax4-2-1/8 BOX \ PER DRAWINGS CEILING NAC DEVICE FIRE ALARM HORN/STROBE FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM 80" TO / MANUAL BOTTOM / PULL STATION OF LENS 60" TO CENTER 48" TO CENTER FINISHED - FLOOR - SMOKE DETECTOR INSTALLATION DETAIL 1C CONDUIT FIRESTOPPING DETAIL (FIRESTOPPING INSTALLED AND FURNISHED BY OTHERS) I A 11 A System No, W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr 1. Wall Assembly — The fire—rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A Studs — Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum= — 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specked in the individual U300 or U400 Series Designs in the UL Fire Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which A is installed. 2. Through Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within *elfifKstidsePwft. flipe5/8 in. conduit or tubing to be rigidly supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe — Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering — Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all—service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond both sides of wall surface. Longitudinal joints sealed with metal fasteners or factory—applied self—sealing lop (SSL) tape. The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering—Materials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. FII, Void or Cavity Material' — Sealant thickness of fill material applied within annulus Flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, at point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides Of wall. V W X 1-2 ' 3 ' 4 ' 5 ' 6 ' 7 ' 8 ' ' 10 ' 11 ' 12 —13 ' 14 ' 15 ' 16 ' —17 ' 18 ' 19 ' 20 ' 21 ' 22 ' 23 ' 24- ' 25 ' 26 1 27 1 28 1 29 1 30 1 31-1 Ad k% DYNAFiRE DY N ET j Wireless Alarm Monitoring DYNAFIRE INC. NEVER IN THIS AREA 109B Concord Drive CEILING MOUNTED SMOKE CASSELBERRY, FLORIDA 32707 DETECTOR MUST BE , E—MAIL: dynofire®dynafire. com FROM Qualifier: STEVEN HATCH LEAST 36" FROM ' DUCT STATE LICENSE # EF20000528 WALL MOUNTED SMOKE WEBSITE: WWW.DYNAFIRE.COM DETECTOR MUST BEAT PROJECT ' BELOW BUT NO LOWER N TO TOP OF DETECTOR r� (n 1C CONDUIT FIRESTOPPING DETAIL (FIRESTOPPING INSTALLED AND FURNISHED BY OTHERS) I A 11 A System No, W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr 1. Wall Assembly — The fire—rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A Studs — Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum= — 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specked in the individual U300 or U400 Series Designs in the UL Fire Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which A is installed. 2. Through Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within *elfifKstidsePwft. flipe5/8 in. conduit or tubing to be rigidly supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe — Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering — Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all—service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond both sides of wall surface. Longitudinal joints sealed with metal fasteners or factory—applied self—sealing lop (SSL) tape. The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering—Materials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. FII, Void or Cavity Material' — Sealant thickness of fill material applied within annulus Flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, at point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides Of wall. V W X 1-2 ' 3 ' 4 ' 5 ' 6 ' 7 ' 8 ' ' 10 ' 11 ' 12 —13 ' 14 ' 15 ' 16 ' —17 ' 18 ' 19 ' 20 ' 21 ' 22 ' 23 ' 24- ' 25 ' 26 1 27 1 28 1 29 1 30 1 31-1 Ad k% DYNAFiRE DY N ET j Wireless Alarm Monitoring DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 109B Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynofire®dynafire. com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT N L LJ r� (n � � G —r (D Q m J Q U CD �-_, L L1 T Q REVISIONS z O F- � w Q U L, (n Lv N 0 cr) LLJ Q 00 \ � N W SEAL upATA 41NUMBER: 5287FO5 IfLSP DATE: 3/12/18 &W N BY: Chad Matevia kKED BY: Wayne Clineman 9 ®Wayne Clineman � USHEET TITLES COVER PAGE & LEGEND SHEETNUMBER C c FAO.O 0 C C C F_ —2 r 314 1 5— 1 6T7 8 1-9_ 1 10 --- ►-11---r---12 A GO; DISHWASH 112 3T14T15---r-16—1 17—r-18T19--r--20—r— 21----r---22---T---23---7-24 I` �R M X 1 N ca S a m w z a J T 0 Ill =■ ■ 0 n N U N co 0 N O r N ° V E: . tm Cn w a a J a M x N 0 E cv X c d 2 3 4 5 6 7 X W X E S 1 FIRST FL OR PALO FIRE ALARM SCALE: 3/16" = 1'-0" ELECTRICIANS NOTES! TYPICAL FIRE ALARM NOTES: 1.) ALL CONDUIT 3/4" MINIMUM. 2.) CONDUIT ROUTING SHOWN IS FOR DIAGRAMMATIC PURPOSES ONLY. CONDUIT SHOWN DOES NOT REPRESENT EXACT LO;ATION. GENERAL NOTES 1.) f & SPECIFICATIONS. HEX NOTES 11Alarm Monitoring O1 / "' A/V DEVICE LOCATION. I DISHWASH 112 3T14T15---r-16—1 17—r-18T19--r--20—r— 21----r---22---T---23---7-24 I` �R M X 1 N ca S a m w z a J T 0 Ill =■ ■ 0 n N U N co 0 N O r N ° V E: . tm Cn w a a J a M x N 0 E cv X c d 2 3 4 5 6 7 X W X E S 1 FIRST FL OR PALO FIRE ALARM SCALE: 3/16" = 1'-0" ELECTRICIANS NOTES! TYPICAL FIRE ALARM NOTES: 1.) ALL CONDUIT 3/4" MINIMUM. 2.) CONDUIT ROUTING SHOWN IS FOR DIAGRAMMATIC PURPOSES ONLY. CONDUIT SHOWN DOES NOT REPRESENT EXACT LO;ATION. GENERAL NOTES 1.) REFER TO GENERAL NOTES & SPECIFICATIONS. HEX NOTES 11Alarm Monitoring O1 �R M X 1 N ca S a m w z a J T 0 Ill =■ ■ 0 n N U N co 0 N O r N ° V E: . tm Cn w a a J a M x N 0 E cv X c d 2 3 4 5 6 7 X W X E S 1 FIRST FL OR PALO FIRE ALARM SCALE: 3/16" = 1'-0" ELECTRICIANS NOTES! TYPICAL FIRE ALARM NOTES: 1.) ALL CONDUIT 3/4" MINIMUM. 2.) CONDUIT ROUTING SHOWN IS FOR DIAGRAMMATIC PURPOSES ONLY. CONDUIT SHOWN DOES NOT REPRESENT EXACT LO;ATION. GENERAL NOTES 1.) REFER TO GENERAL NOTES & SPECIFICATIONS. HEX NOTES 11Alarm Monitoring O1 COORDINATE WITH AHJ FOR A/V DEVICE LOCATION. O DO NOT INSTALL CONDUIT 14 BOTTOM OF BACK -CANS. 9 110 111 112 1 UP 2S H.C. RAMP @ 1:12 EGRESS RAMP LANDSCAPE PLANTER S L1 D002 WAIT 106 CLOSET 200 FIRE SPRINKLER RISER ROOM (SEE DETAIL) HOST 103 LlDO01 i--25---7-26---T--27----i-28----T— 29—X30 --T 31-1 A B C D FIRE SPRINKLER RISER ROOM TO BACKFLOW PREVENTOR A L1M030-WF TO TTB Ll M001 P L1M031-TS DM M A L1 M032 -TS FACP (CPI) 2 S 1,1M033 -TS L1D001 75cd Oj yWP / ° EOL CPl .l -1 �^ S B /:_nom \.. f L. Ci � DINING r�1 102 f , EXTERIOR BALCONY OVERHEAD x LANDSCAPE PLANTER ►A .lts� 2�� 7$ W _ t NO a.,. SHEET xc pr16NSAS?v,�f Yx,,z;, _- x 3 114 115 116 117 118 119 1 20 121 122 123 124 125 26 127 128 129 130 131-1 DYNAFIRE DYNET 11Alarm Monitoring DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 109B Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynafire®dynofire. com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT N IW m � LL Q m Q J Q (__D1I W � T � LL Q REVISIONS Z _O F � LLJ Q U Lj LiJ 0 Cn co LLJ Q 00 � � N ro Li SEAL DATA JOB NUMBER: 5287F05 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES SHOP DRAWING S�___ET NUMBER FA1.0L i C F— 2 r 3 r 4T54T5T 6 r 7 8 2 A FAN #3 STAIR 2011 OFFICE 204 .................. TU -3 VP JD013 S x W X f S T 0 a: 0 C14 O (-2-ROOF LEVEL �FA2.0) FIRE ALARM -5 V ✓1 ELECTRICIANS NOTES! 7' TYPICAL FIRE ALARM NOTES: N lAlarm MouitoriDg DYNAFIRE INC. MENS PHONE (407) 830-6500 — FAX (407) 831-1347 1.) ALL CONDUIT 3/4" MINIMUM. o CASSELBERRY, FLORIDA 32707 F2-05-1 T A 2.) CONDUIT ROUTING SHOWN IS FOR DIAGRAMMATIC WEBSITE: WWW.DYNAFIRE.COM PURPOSES ONLY. CONDUIT SHOWN DOES NOT LL.ti C13 0 REPRESENT EXACT LOCATION. W U ROOF BAR U) ZZZ Z" F20-81 U CD ......... ............ . . LL REVISIONS . .. .... .. ... . . R X x WOMENS LLJ F20sI U) C) U) L.Lj =D LLI 0 (/') V) SECOND LEVEL DINING LU F207] LLJ z 0 T 0 a: 0 C14 O (-2-ROOF LEVEL �FA2.0) FIRE ALARM -5 V V \A/ cr) xS T 2018 04 E EXCtp-rloly W4-,, S, X4S X01 x FFT# U- .2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 1 10 1 11 1 12 1 ),3 14 15 16 17 18 1 19 1 20 1 21 1 22 1 23 1 24 25 1 26 1 27 1 28 1 3lo 1 -31-1 AA DYNAFIRE S ELECTRICIANS NOTES! Wireless DY AdVET TYPICAL FIRE ALARM NOTES: N lAlarm MouitoriDg DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 1.) ALL CONDUIT 3/4" MINIMUM. CASSELBERRY, FLORIDA 32707 E—MAIL: d yn afire0d yna fire. com T A 2.) CONDUIT ROUTING SHOWN IS FOR DIAGRAMMATIC WEBSITE: WWW.DYNAFIRE.COM PURPOSES ONLY. CONDUIT SHOWN DOES NOT REPRESENT EXACT LOCATION. W U V \A/ cr) xS T 2018 04 E EXCtp-rloly W4-,, S, X4S X01 x FFT# U- .2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 1 10 1 11 1 12 1 ),3 14 15 16 17 18 1 19 1 20 1 21 1 22 1 23 1 24 25 1 26 1 27 1 28 1 3lo 1 -31-1 AA DYNAFIRE Wireless DY AdVET N lAlarm MouitoriDg DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 1096 Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: d yn afire0d yna fire. com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT cll� W E— m I U) U CD < W LL REVISIONS 0 LLJ C) U) L.Lj =D LLI 0 (/') V) LLJ 00 0 SEAL DATA JOB NUMBER: 52871`05 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES SHOP DRAWING SI --_-ET NUMBER FA2.0 f-1� — 2 ------ F-- 3---T-- 4r567----T--8----T-- 9--r-10--r-11—r--12--r-1 A RTU -1 RTU -2 FAN #3 R- L1D011 S L1M012 S S L1MO17 S L1 S .L WP S-� WP I St WP S J SOW P00� LEV�t L1D011 L1D012 L1D017 L: 2S K L S M L1M050 M ANSUL N 0 FIRE P B) 0 ii MQ r T 0 0 a �R Cl) X V N Q 3 d G1 a w Z a J U 6 6 a a l5T F: 0Oop h N 00 s N O r -o a, CL V W c� a a H W 0 J CL M X N ui E �X 3 14 15 16 17 18 19 110 111 112 11 3T14—X15—r--16----7-17--r-18----r-19----r-20T21- 1 22 23----r-24—I----25 r -26--r-27-- I 28--r--291-30--x-31-1 PHONE (407) 830-6500 — FAX (407) 831-1347 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynafire®dynafire.com Qualifier: STEVEN HATCH A WEBSITE: WWW.DYNAFIRE.COM PROJECT N �C-11 W B m U) U_ (n C J Q O iU W 0 U— D REVISIONS z 0 E � Q F RTU -4 RTU -5 S L1M014 S LIM016 RM RM ILL! 0 cn cn S WP S WP z z LLJ < 00F- � G LlDO14 LID016 � N H U-3 _._._._._._ VI013 I M I SEAL � I S JOB NUMBER: 5287FO5 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES WP RISER DETAIL SH ==T NUMBER FA3. 0 i L Z c LlDO04 J D013 I _._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._._ 2N01t0t OO S S S LlDO02 S S S S K Z 2 RM RM RM L16003 LIM020 LIM021 LIM022 EOL CP1.1-1 PRIMARY SECONDARY HAT WP RECALL RECALL LIGHT L 75cd 0 M LlDO01 - B S S Z DM DM LIM030-WF LlM032-TS LlM031-TS LIM033-TS N TO TTB S,B 0 ALARM CONTROL PANEL S NOTIFIER (NFW2-100). �CKBOX FURNISHED BY P DynaFire. 72 A.F.F. TO MEET UL REQUIREMENTS, p rs■■.. g°e p -IIS KNOCKOUT MUST BE USEDC7 ��o� Q FOR AC CONDUIT ENTRY ONLY I" °gym WP (NONPOWER—LIMITED). (TYP.) P L1M001 R 2 4 SURGE SUPPRESSOR(Bl) LjL S FOR 120VAC MAX (MODEL DTK-120HW) FURNISHED BY DynaFire. T 120 VAC ...... _._._. ...... _._._. ...... _.— _. ...... _._._. ...... _._._. ...... _._._. ...... _._._. ...... _._._. ------- U.—._._ FIRE ALARM FA4.0 RISER DETAIL V V LL JUN 0 7 2018 w Lri IV43 �.d`4�w�'�rvK it.A1'�.. 0 EXCEPTIONS A5 NONE ,,HEF r X 3 114 115 116 117118 119 120 121 122 123 124 125 126 127 128 129 130 131-] DYNAFIRE Wireless E T Manitoring DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynafire®dynafire.com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT N �C-11 W m U) U_ (n m J Q O iU W 0 U— Q REVISIONS z 0 � Q o rn w ILL! 0 cn cn LLJ < 00F- � � N SEAL DATA JOB NUMBER: 5287FO5 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES RISER DETAIL SH ==T NUMBER FA3. 0 i L c F_1� 2--3t4�-5r-6T7T8T9-T-10-T11T12r--13 A B C D H lD M X N N CL W rn 0 tT M S a m w z Q J NOTIFIER by Honeywell NFW2-100 Fire Alarm Control Quantity x[device current draw] =total current drawn itn el device (in amps) Main Circuit Board 1 x[0.00000]=0.00000 [0.00000]=0.00000 x[0.14500]=0.14500 P2WK75 1 x[0.00000]=0.00000 [0.15800]=0.15800 x[0.00000]=0.00000 NP -100 4 x [0.00030] = 0.00120 [0.00000] = 0.00000 x [0.00030] = 0.00120 N P-10OR 6 x [0.00030] = 0.00180 x [] = x [0.00030] = 0.00180 N D M-100 2 x [0.00075] = 0.00150 [0.00000] = 0.00000 x [0.00075] = 0.00150 14--i-00-ISO 1 x [0.00040] = 0.00040 [0.00000] = 0.00000 x [0.00040] = 0.00040 NOT-BG12LX 6 x[0.00030]=0.00180 [0.00000]=0.00000 x[0.00030]=0.00180 NC-10OR 6 x[0.00027] =0.00162 [0.00000] = 0.00000 x [0.00027] = 0.00162 D N R W 6 x [0.00000] = 0.00000 [0.00000] = 0.00000 x [0.00000] = 0.00000 Max Alarm Draw -All Addressable De 1 1 x[0.000001=0.00000 9 [0.400001 =0.40000 x[0.000001 =0.00000 Total (Amperes) 0.0083 AI 11 0.5580 AI 0.1533 (Total Primary Alarm Load -C2 1 1 1 x[0.55800] =0.558001 Wain Circuit Board 1 1 1 x[0.27500]=0.27500 NOTIFIER NFW2-100 Fire Alarm Control Protected Premises: Coop 303 Address: 303 Atlantic Bvld. CP1.1 Date: 2/22/2018 City: Atlantic Beach State: Fl Zip: 32233 Prepared By: DynaFire, Inc. Q Phone: 407-830-6500 Address: 113 Concord Drive T Email: engineering@dynafire.com City: Casselberry State: FL Zip: 32707 Clear Project Information AC Branch Current Requirements 3.00 AMPS 120 VAC check Current required by source to powerthe fire alarm system. Primary Standby Load 0.01 Amps Check Current load on the primary power su pply during non -alarm conditions. Primary Alarm Load 0.56 Arnps check Current load on the primary power supply during alarm conditions. Secondary Load Requirements F-4-507 Amp hours check Total Secondary Load from the calculation table below 6----r---17----F---19---T---20T 21T22T23124-►- -25T26--27-X28I29I30T 31-1 A B C D Current Draw Time (hours) Total (AH) Secondary Standby Load Required Standby Time 0.153 A x 24 hours 3.68 Secondary Alarm Load Required Alarm Time (hours) 0.833 A x 0.084 hours 0.07 0 Total Secondary Load 3.75 USA Canada Derating factor x 1.2 Secondary Load Requirements 4.50 AH Battery Selection 0 Amp Fours Select batteries from the list below. 7 AH BAT -1270 Battery (12 volt) r Two (- Four (two 12VDC sets in parallel) Battery Distribution Chart Shows amp -hour distribution of your selections. Secondary Alarm Load 1% Seconda Load Requirements AH ad (AH 'Derating 0 N O CP1.1 VDROP 0.116 USABLE 20.284 VDROP 0.000 USABLE I 20.400 U_ 125 14 4110 0.57% Q . Spare Battery Capacity (AH) * Derating o T 0.0M. Comments 6 Qualifier: STEVEN HATCH 1. Batteries will fit in the FACP cabinet. IL R ■ Secondary Standby Load 2. Selected battery size meets secondary load requirements. M 3. The selected batteries (7AH) are within the charger range of this a.LOT (� COOP 303 -� L� VJ NFW2-100 (CP1) - PER CIRCUIT LOADS & VOLTAGE DROP Spare Bathe Capacity 2.50 Battery Selection (AH I� N J � U CD �,�, Amp° Secondary Standby Load 4.42 Secondary Standby L U LL Seconda Alarm Load 0.08 [Secondary Alarm Loa co Check CP1.1 VDROP 0.116 USABLE 20.284 VDROP 0.000 USABLE I 20.400 r 125 14 4110 0.57% Q . Spare Battery Capacity (AH) * Derating 14 4110 0.0M. E-MAIL: dynafire®dynafire. com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 R ■ Secondary Standby Load PROJECT N C 11 Secondary Alarm Load (� COOP 303 -� L� VJ NFW2-100 (CP1) - PER CIRCUIT LOADS & VOLTAGE DROP Q m J � U CD �,�, Amp° LL Q REVISIONS draw:;; Z O S Device type each CP1.1 CP1.2 CP1.3 CP1.4 w Q (TEMPORAL HIGH) - Device type rr � HORNISTROBE WEATHERPROOF - WALL MOUNT U w P2WK @75CD 0.176 1 w 0 co rn T PER CIRCUIT DRAW 1 0.176 0 0 0 ,' TOTAL AMPS ON POWER SUPPLY 0.176 AMPS supply (7-18AH). � N VOLTAGE DROP CALCULATIONS OA Branch squired: Factor Factor AMP LOAD DISTANCE FROM SOURCE TO EOL WIRE GUAGE CIRCULAR MIL VOLTAGE DROP PERCENTAGE AMP LOAD TO DISTANCE WIRE GUAGE 3.00 A CIRCULAR MIL VOLTAGE DROP PERCENTAGE CP1.1 VDROP 0.116 USABLE 20.284 VDROP 0.000 USABLE I 20.400 0.176 125 14 4110 0.57% CP1.2 0 (AH) * Derating OA Branch squired: Factor Factor AMP LOAD DISTANCE FROM SOURCE TO EOL WIRE GUAGE CIRCULAR MIL VOLTAGE DROP PERCENTAGE AMP LOAD TO DISTANCE WIRE GUAGE 3.00 A CIRCULAR MIL VOLTAGE DROP PERCENTAGE CP1.1 VDROP 0.116 USABLE 20.284 VDROP 0.000 USABLE I 20.400 0.176 125 14 4110 0.57% CP1.2 0 0 14 4110 0.0M. V V aC�CSr3flyf��F rir, �* Pr'4A1P�gtirt���1 JUN 0 l Zai$ w X1..2 1`iv <:. y.. ,D loi'4 (CP1) (_2 FIRE ALARM CONTROL PANEL (CP1) XCEPTIONS A , -1 i PCL VOLTAGE DROP "-- X 1 14 1 15 1 16 117 1 18 119 120 121 122 123 124 1 25 126 127 1 28 1 29 130 1 31-1 ff DYNANRE VETWireless kIarm Monitoring DYNAFIRE INC. PHONE (407) 830-6500 - FAX (407) 831-1347 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E-MAIL: dynafire®dynafire. com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT N C 11 � W (� -� L� VJ Q m J � U CD �,�, W LL Q REVISIONS Z O F- � w Q rr � U w w 0 co rn L.Li Q 00 � � N ro w Of SEAL DATA JOB NUMBER: 5287FO5 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES SHOP DRAWING HE -T NUMBER FA4.0 U 14 1 17 -r- 8 r 9 r 10-r 11-----T12--r1 A TYPICAL SLC WIRING DETAIL B NOT-BG12LX+) SUPPLY SIDE MANUAL PULL STATION — � o m y/"�tz ADD111- ' A3aUa'1 0 LOOP 2(+) (-) D 300 (-) (+) ❑ mo TYPE LOOP ADDRESS E NP -100 HEAD WITH FROM FACP B21OLP BASE FLASHSCAN (� O NC-10OR O 1 ) RC2 O 9 0 2 TEN 8 5171, 3401 N22�,'3 N 7 2 RCI 45671, 6 z2 )j ONES 3 1 0 N01 5 4 co ADDRESS Q O O O NC-10OR RELAY MODULE NOT-BG12LX NP -100 TO CKT BEING CONTROLLED BY RELAY F MANUAL PULLSTATION SMOKE DETECTOR PLAN SYMBOL = [-P] PLAN SYMBOL = G H PER JOB INSTALLATION AND I WIRING DETAIL NC -100R RELAY PLAN SYMBOL = R M J U 0 K O I L M 14 AWG "B" CABLE H N FROM PREVIOUS DEVICE OR FACP W 0 P PER JOB INSTALLATION AND WIRING DETAIL m 0 v DO NOT PAM U- R (l T 0 a (DR Cl) X N Q O G/ dl n. S I" r v C� oT O o a 2 NMM-100P COIL a aTEST TEST COIL 0 [ 0 0 N LOOP / COMM - t t RA/RTS t t N U RTS N co s N N LLJ > I— m Cn U U) �' Ia V FROM PREVIOUS DEVICE OR FACP lel w c� a o_ O W J CL Cl)to X N 15 --"16 r- I / -18 I --19—r-20 27----T-28 I 29---T---30—i— ) I- FLASHSCAN D FDM-1 O m 9 00 8 3 SV V 011 (—� I 2 12 13 4 (+) 7 TENS ° ,s 2 4�5171, 6 21(!11 3 m 5 ONES �° 4 m ADDRESS EOL 47K, 1/2W FDM-1 MONITOR MODULE DRY CONTACT SWITCH FDM-1 DUAL MONITOR MODULE PLAN SYMBOL = [D -M] PER JOB INSTALLATION AND WIRING DETAIL /�000l D 000 0 0( 0 0010 0800 0000 0000 0000 0°00 0000 00 000 0( 000( 00 TO NEXT DEVICE OR OLR WALL MOUNT SRL ST OBE ONLY PLAN SYMBOL = E f0 V C /� d �-1 2 3 4 5 6 7 8 9 TO NEXT OR EC 10 111 112 11; El m LOOP ADDRESS DNR BASE W/ NP-10OR HEAD (IND ADAPTABLE) DNR DUCT DETECTOR PLAN SYMBOL = @2— 7���9 NMM-100P COIL 32// \\° '\1\�IIII✓/'/Iiz aTEST TEST COIL 1 X01514 3 IN/COMM + 0 0 OUT (CONV ONLY) LOOP / COMM - t t RA/RTS t t RA STATE LICENSE # EF20000528 RTS DNR DUCT DETECTOR PLAN SYMBOL = @2— 7���9 NMM-100P �///, 8 9 32// \\° '\1\�IIII✓/'/Iiz � � ADDRESS 32 1 X01514 3 F--1 p TENS LOOP ONES t t t t (—)YELLOW BLACK �—) VIOLET (+) I r (+)RED (+) RED TYPICAL CONNECTION DETAIL SK—MINIMON MONITOR MODULE EOL. 47K, 1/2W WEATHER PROOF PULLSTATION DRY CONTACT SWITCH )EVICE LR lTl WALL MOUNT 2RL HORN STROBE PLAN SYMBOL = O WEATHERPROOF BACK BOX WEATHERPROOF WALL MOUNT P2RK HORN STROBE PLAN SYMBOL = O NMM-100P MONITOR MODULE PLAN SYMBOL = [M -M] BLACK (—) lacksonvi!v5%. . � 2018 F-1 NO 13 Excp'1710%4 1N'C%. SHEET # C. X 3 114 115 116 117 118 119 120 121 122 123 124 125 1 26 1 27 128 129 130 131-1 I) % FIRE DY VEss N T I Alarm Monitoring DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-1347 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynafireOdynafire.com Qualifier: STEVEN HATCH STATE LICENSE # EF20000528 WEBSITE: WWW.DYNAFIRE.COM PROJECT N LLJ > I— m Cn U U) Q m J Q U CD W -{--, LL Q REVISIONS z 0 a Q U C w W Cn LJ - 00F Q � � N Li SEAL DATA JOB NUMBER: 5287FO5 ISSUE DATE: 3/12/18 DRAWN BY: Chad Matevia CHECKED BY: Wayne Clineman PM: Wayne Clineman SHEET TITLES BATTERY CALCULATIONS, RISER DETAIL & POINT TO POINT DETAILS SHEET NUMBER FA5-0 O