Loading...
1805 MAYPORT RD - FIRE REVIEW 6/7/18 t S tO N j'I � rr, -::::::, .41,-! /011 SC Et ��` `� Fire Plans Review Fire Prevention Division 214 N. Hogan Street, Room 281 Jacksonville, Florida 32202 June 7, 2018 Chelsea Leonard 1805 Mayport Road COMM 18-0011 The Drawings submitted for permitting have been reviewed and Returned for Corrections. Please correct or provide the proceeding requested information to obtain plans approval. When resubmitting corrected sheets, please provide a written narrative letter responding to our comments and directing the plans reviewer to the sheets the changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER "WILL" RESULT IN A RETURNED FOR CORRECTIONS PERMIT STATUS. Revised sheets should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission please make sure that written narrative is submitted under correspondence along with a "complete set" (not just the revised sheets) of electronic documents. 1.)Fire Code Specific Code Summary The building code and fire code differ on occupancy types and uses and can make the proper application of the code difficult. Please provide in addition to normal building code summary a fire code specific summary based off the Florida Fire Prevention Code (current edition) to include all the following information listed below. Failure to provide accurate fire code summary may delay plans review approvals as we return plans for corrections and clarifications. • Occupancy type sub-classification (per NFPA 101 6.1) • Building construction type (per NFPA 101 8.2.1) • Gross square footage • Number of stories • Building height • Interior wall and ceiling finish requirements • Allowable dead end limits • Allowable Common path of travel limits • Allowable travel distance limits • Any fire protection systems (sprinkler, fire alarm, etc.) • Statement from architect or engineers that their design to the best of their knowledge complies with the 6th Edition Florida Fire Prevention Code (FFPC). Also all existing building must provide classification of rehabilitation work categories per NFPA 10143.1 2)The City of Jacksonville's Fire Marshal's Office requires the submittal of a life safety plan for building permits for all new construction and existing building alterations in order to ascertain if occupancy is currently code compliant and to assist fire inspector in performing Life Safety Inspections. Please provide a Life Safety Plan to include all the following information on one page. If Life Safety Plan was submitted and you are receiving this comment, it means that all of the required info listed below was not included in your original submittal. It is understood that all listed items may not apply in your situation. Required measurements: (Worst case only need be shown.) • Dead end corridors measurements. • Common path of travel measurements. • Total travel distance to exits. Required Lock Latch details: • Lock/Latch details: Panic Hardware, Thumb turn lock, Key Lock with indicator and required signage. Required Occupant Load Calculation: • Calculated occupant load using table 7.3.1.2 of NFPA 101 2015 edition. Required Egress Inches: • Egress inches for means of egress components (doors, stairs, etc.) Required Number of Exits: • All required exits shall terminate at a "public way". Access to the public way shall be via a stable, firm, and slip resistant conveyance such as a concrete sidewalk with a min. 5'x5' landing and 44" walkway. Required Exit Separation Distance: Separation of exits using the one half(non-sprinkled) or one third (sprinkled) the diagonal distance rule. Required Electrical Stop/Disconnect Details: • Any required Emergency stops or Shunt trips. • Main Electrical disconnects access/location. Required markings of means of egress: • Exit signs to include tactile exits signage. Required fire extinguisher Locations: • Locations per NFPA 10 to include K class fire extinguisher locations in kitchens. Required Emergency lighting: • Show emergency illumination. Required Lightweight Truss Signage: • Location of lightweight truss signage per FAC 69A-60.0081. (if applicable). Please see below for clarification to requirement. http://www.coi.net/Departments/Planning-and-Development/Docs/Building-Inspection-Division/bulletin-f-01- 09-light-weight-truss-rule.aspx.