1631 ATLANTIC BEACH DR - NEW HOME STRUC. DRAWINGSDESIGN CRITERIA AND LOADS Building Code FASTENER TYPE Florida Building and Residential Codes, 6th Edition (2017) Code for Design Loads IZ - Interior Zone (psf) EZ - End Zone (psf) ANSI/ASCE 7-10 +24.61 -26.70 ROOF LOADING.. .............................................. Cd = 1.25 TOP CHORD LIVE LOAD..................................20 PSF TOP CHORD DEAD LOAD................................7 PSF BOTTOM CHORD LIVE LOAD +22.01 -24.09 ATTICS WITH LIMITED STORAGE ............... 20 PSF (PER FRC) ATTICS WITHOUT STORAGE ....................... 10 PSF -25.56 -30.74 (NON -CONCURRENT) BOTTOM CHORD DEAD LOAD........................5 PSF WIND LOADING ................................................. Cd = 1.60 ASCE 7-10, 3S GUST........................................130 MPH BASIC WIND SPEED 6" O.C. AT PANEL EDGES, 12" O.C. IN FIELD (BLOCKED HORIZONTAL PANEL EDGES) EXPOSURE CATEGORY .................................. C BUILDING CATEGORY ..................................... II ENCLOSURE CLASSIFICATION ...................... ENCLOSED INTERNAL PRESSURE COEFF........................ 0.18 C&C DESIGN PRESSURES .............................. (SEE TABLE 1) FLOOR LOADING..............................................Cd = 1.00 TOP CHORD LIVE LOAD..................................40 PSF TOP CHORD DEAD LOAD................................17 PSF BOTTOM CHORD LIVE LOAD .......................... 0 PSF BOTTOM CHORD DEAD LOAD........................5 PSF SPECIAL FLOOR (GAME ROOM) LOADING.... Cd = 1.00 TOP CHORD LIVE LOAD..................................60 PSF TOP CHORD DEAD LOAD................................17 PSF BOTTOM CHORD LIVE LOAD ...........................0 PSF BOTTOM CHORD DEAD LOAD. ......... . 5 PSF MAXIMUM FLOOR TRUSS SP.A,CJN <1,8° 0.Q DEFLECTION CRITERIA (1 ROOF TRUSSES .............................................. LL/240 (18)0.162"x22"IN TL/180 TL MAX 1" UP TO 40' SPAN OPEN WEB FLOOR TRUSSES/BEAMS.......... LL/360 FiTT41,2,(3 TL/240 MTS12 TL MAX 34" WOOD I JOISTS ............................................... LL/480 TL/240 6" EMBED ANCHOR TL MAX 2" NOTES: 1. CONCURRENTLY LOADED LIVE LOAD MAY BE REDUCED PER FBC 1605.3.1.1. TABLE 1: COMPONENT AND CLADDING DESIGN PRESSURES WINDOWS AND DOORS FASTENER TYPE EFFECTIVE WIND AREA ZONE DESIGNATION IZ - Interior Zone (psf) EZ - End Zone (psf) 0 - 20 ft2 +24.61 -26.70 +24.61 -32.95 21 - 50 ftz +23.42 -25.51 +23.42 -30.58 51 - 100 ftz +22.01 -24.09 +22.01 -27.74 101 - 200 fe +20.91 -23.00 VINYL SOFFIT MAX PRESSURE (psf) +20.91 +23.5 -25.56 -30.74 GARAGE DOOR PRESSURE SEE FRAMING PLAN END ZONE KEY MAP END ZONE: END ZONES SHALL BE TAKEN AS THE 1ST 4.0' PER IRC FIGURE R301.2 (7) I L� 1 ST FLOOR 4.0 FT END ZONE (TYP) [::�:DESIGNATION 2ND FLOOR 4.0 FT (Np)END ZONE __FDESIGNATION TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS NOTES 3, 4 FASTENER TYPE ACZA STUCCO AND DIRECTLY MIN 15/2" 32/16 SPAN RATED OSB OR PLYWOOD INSTALLED VERTICALLY OR (Y/6" 24/16 O z ADHERED STONE INSTALLED HORIZONTALLY) W/ 8d COMMON: 6" O.C. AT PANEL EDGES, 12" O.C. IN THE _ 8d RINGSHANK FIELD. 2x4 BLOCKING IS RECOMMENDED AT UNSUPPORTED PANEL EDGES. w Q (NOTE 6) 0.148" X w 10d 0.131" 3" 10d COMMON 0.148" U 12d COMMON MIN Z16 " 24/16 SPAN RATED OSB OR PLYWOOD INSTALLED VERTICAL OR HORIZONTAL Q ALL OTHER VENEER W/ 8d COMMON: 6" O.C. EDGES AND FIELD (UNBLOCKED HORIZONTAL PANEL EDGES); � ?� (NOTE 7) 6" O.C. AT PANEL EDGES, 12" O.C. IN FIELD (BLOCKED HORIZONTAL PANEL EDGES) ROOF DECK SHEATHING MIN 15/2" 32/16 SPAN RATED OSB OR PLYWOOD INSTALLED WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS W/ 8d RING SHANK NAILS: 6" O.C. AT PANEL EDGES, 12" IN (NOTES 1,2) O.C. IN THE FIELD, FLOOR DECK SHEATHING: 23/2" T&G OSB OR PLYWOOD W/ 10d COMMON: 6" O.0 AT PANEL EDGES, 12" O.C. IN THE (9) 10d COMMON (NOTE 5) FIELD. PORCH CEILING BOARD SHEATHING: MIN 3/" OSB OR PLYWOOD OR CDX INSTALLED PERPENDICULAR TO SUPPORTS W/ 8d BED EPDXY OR DTB- e Z COMMON: 3" O.C. AT PANEL EDGES, 12" O.C. IN THE FIELD. "SW' DESIGNATED SHEAR WALLS: MIN Z16" OSB OR PLYWOOD INSTALLED VERTICAL OR HORIZONTAL W/ 8d COMMON: 3" CS20 (NOTE 7) O.C. AT PANEL EDGES, 6" O.C. IN THE FIELD (UNBLOCKED HORIZONTAL PANEL EDGES), S REW ANCHOR 12" O.C. IN FIELD (BLOCKED HORIZONTAL PANEL EDGES). NOTES: 1. FOR SHEATHING THICKNESS GREATER THAN 15/2" CATEGORY (32/16 SPAN RATING), USE 10d RING SHANK NAILS IN LIEU OF 8d RING SHANK NAILS. (0.148" x 3" LONG). 2. COMMON NAILS IN WALL SHEATHING MAY BE SUBSTITUTED W/ 8d GALVANIZED BOX NAILS. 3. ZIP WALL SHEATHING IS AN ACCEPTABLE ALTERNATE FOR APA RATED WOOD STRUCTURAL PANEL. 4. ALL WOOD STRUCTURAL PANEL SHALL CONFORM TO THE MOST CURRENT APPLICABLE SPECIFICATION AND SUPPLEMENTS OF CURRENT APPROVED APA.MANF. SPECIFICATIONS. 5. FLOOR FASTENERS ARE MINIMUM REQUIRED FOR DIAPHRAGM DESIGN. FOR INCREASED FLOOR PERFORMANCE AND TO HELP REDUCE SQUEAKING, 8d RING SHANK NAILS OR 8d SCREW NAILS ARE RECOMMENDED. 6. 1532" 32/16 SPAN RATED OSB OR PLYWOOD WITH BLOCKED PANEL EDGES IS AN APA RECOMMENDATION PER APA TECHNICAL BULLETIN Q370 WHEN STUCCO LATH IS ATTACHED DIRECTLY TO OSB OR PLYWOOD.. SHOULD BUILDER SPECIFICATIONS ALLOW, MIN STRUCTURAL REQUIREMENTS ARE Z16" 24/16 SPAN RATING INSTALLED HORIZONTALLY OR VERTICALLY PER FLEXIBLE VENEER WALL SPECIFICATIONS. INCLUDES FULL AND PARTIAL H I T,y/ENEER APPLICATIONS.u­_,,,, 7. WOOD STRUCTURAL PANEL MAY BE INSTALLED VERTICALLY OR HORIZONTALLY W/UNBLOCKED HORIZONTAL PANEL EDGES. WOOD BLOCKING IS REQUIRED FOR SHEARWALLS LESS THAN 5' IN LENGTH. TABLE 3: MAXIMUM EXTERIOR WALL STUD SPACING (IN O.C.) 2x6N0.2SPF @MAX, 16"O.C.I TABLE 4: NAIL SIZE LEGEND NOTES 1, 2, 3, 4 FASTENER TYPE ACZA STANDARD CARBON STEEL DIAMETER LENGTH 8d COMMON 0.131" 2%" 8d RINGSHANK 0.113" 2-Y8" 10d x 1-Y2" 0.148" 1 %" 10d 0.131" 3" 10d COMMON 0.148" 3" 12d COMMON 0.148" 3-Y4" 16d SINKER 0.148" 3%" 16d COMMON 0.162" 34/2" TABLE 5: FASTENERS IN PRESSURE TREATED LUMBER PRESERVATIVE FASTENER TYPE ACZA STANDARD CARBON STEEL SODIUM BORATE (NOTE 1) STAINLESS CONNECTORS AND 1. SILL PLATES W/ SODIUM BORATE TREATMENTS BEARING ON FASTENERS REQUIRED. CONCRETE OVER VAPOR BARRIER ARE NOT DIRECTLY CONNECTORS MUST HAVE ALL OTHER PT Z -MAX, G120 OR TRIPLE ZINC (INCLUDING ACQ & MCQ) COATED FINISH. USP FASTENERS ALL FASTENERS MUST BE HOT ST -6 ...................... DIPPED GALVANIZED. NOTES: 1 ST LEVEL HOLD DOWN 2ND LEVEL STRAPPING 1. INSTALL 10d NAILS UNLESS OTHERWISE SPECIFIED. NOTES: 2. COMMON WIRE NAILS AND THREADED HARDENED STEEL NAILS 1. SILL PLATES W/ SODIUM BORATE TREATMENTS BEARING ON SHALL CONFORM TO THE NOMINAL SIZES SPECIFIED IN ASTM CONCRETE OVER VAPOR BARRIER ARE NOT DIRECTLY F1667. NOMINAL DIAMETER SIZES APPLY TO FASTENERS EXPOSED TO EARTH OR WEATHER AND HAVE BEEN PROVEN BEFORE APPLICATION OF PROTECTIVE COATING. TO BE NON -CORROSIVE TO CARBON STEEL FASTENERS. 3. WHEN A BORED HOLE IS REQUIRED TO PREVENT SPLITTING OF USP FASTENERS A WOOD DUE TO FASTENER PENETRATION, THE BORED HOLE ST -6 ...................... SHALL NOT EXCEED 75% OF THE NAIL OR SPIKE DIAMETER. ST -7 ...................... 4. THE NOMINAL DIAMETER AND LENGTH OF TYPICAL FASTENERS SPECIFIED FOR THIS PROJECT ARE AS LISTED IN TABLE 4. GREATER THAN 111" CONCRETE AND FOUNDATION NOTES SEE FLOOR PLAN 1. CONCRETE COMPRESSIVE STRENGTH FOR FOOTINGS= 2,500 PSI AT 28 DAYS (UNO). 2. CONCRETE COMPRESSIVE STRENGTH FOR SLAB = 2,500 PSI AT 28 DAYS (UNO). 3. ALL REINFORCING STEEL #3 AND BIGGER SHALL BE ASTM A615 GRADE 40 DEFORMED BARS (UNO). 4. ALL REINFORCING STEEL SHALL HAVE 90 DEGREE BEND AT CORNERS WITH A 24" LAP. 24" LONG #4 BAR IS RECOMMENDED TO BE INSTALLED AT ALL REENTRANT CORNERS. 5. FIBERMESH IS AN ACCEPTABLE ALTERNATIVE AND SHALL. NOT REQUIRE WWF. FIBER LENGTHS SHALL BE 1/2 INCH TO 2 INCHES IN LENGTH. DOSAGE AMOUNTS SHALL RANGE FROM 0.75 TO 1.5 POUNDS PER CUBIC YARD IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. SYNTHETIC FIBERS SHALL COMPLY WITH ASTM C1116. THE MANUFACTURER OR SUPPLIER SHALL PROVIDE CERTIFICATION OF COMPLIANCE WHEN REQUESTED BY THE BUILDING OFFICIAL. 6. MASONRY STEMWALL AND MONOLITHIC FOOTING ARE INTERCHANGEABLE. 7. EARTH AND EARTH FILL SUPPORTING SLABS ON GRADE IS ASSUMED TO HAVE A MINIMUM BEARING CAPACITY OF 2,000 psf IN ACCORDANCE WITH FRC 6TH EDITION (2017) TABLE R401.4.1, AND SHALL BE FREE OF ORGANIC MATERIAL AND COHESIVE SOILS. COMPACT THE FILL IN 12" LIFTS TO AT LEAST 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY. IT IS THE OWNER'S OR CONTRACTOR'S RESPONSIBILITY TO CONFIRM THESE ASSUMPTIONS. 8. CONCRETE FLOOR SLABS ON GRADE SHALL BE INSTALLED OVER A MINIMUM 6 MIL POLYETHYLENE VAPOR RETARDER WITH JOINTS LAPPED 6" AND SEALED OVER CLEAN, COMPACTED EARTH OR FILL WITH APPROVED CHEMICAL SOIL TREATMENT FOR PREVENTION OF SUBTERRANEAN TERMITES. 9. STEMWALLS OVER 4 COURSES TALL REQUIRE SPECIAL ATTENTION TO BRACING DURING CONSTRUCTION. CONTACT ENGINEER OF RECORD IF THIS CONDITION EXISTS. 10. TO CONTROL CRACKING, CUT 1" SAWCUTS IN THE SLAB' IN '! 15'x15' GRID WITHIN 12 HOURS OF CONCRETE PLACEMENT. CONTACT EOR FOR ALTERNATIVE METHODS. CONTROL JOINTS ARE NOT FEQUIRED WHEN WWF OR FIBERMESH ARE INCLUDED WITH CONCRETE WORK. 11. DO NOT SCALE FOOTING DIMENSIONS AND LOCATIONS FROM THE FOUNDATION PLAN. DO NOT DETERMINE FOOTING LOCATION FROM ARCHITECTURAL PLANS OR FRAMING PLAN. IF FOOTING �31ZE OR LOCATION IS NOT DETERMINATE FROM USE OF FOUNDATION PLAN ALONE, CONTACT THE ENGINEER OF RECORD. PRE-ENGINEERED TRUSSES & I -JOISTS 1. ROOF OR FLOOR TRUSSES FABRICATED TO ACHIEVE THE ROOF PLANES DEPICTED ON THE ARCHITECTURAL PLANS SHALL BE DESIGNED UNDER THE SUPERVISION OF A REGISTERED FLORIDA PROFESSIONAL ENGINEER. ENGINEERING SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH ANSI/TPI-2014 AND SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO FABRICATION. DESIGN CRITERIA IS LOCATED ON SHEET ST -1 OF THE PLAN SET. TEMPORARY BRACING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE LEFT IN PLACE AFTER CONSTRUCTION IS COMPLETE. 2. TRUSSES OR I -JOISTS SHALL BE DESIGNED TO MATCH THE ORIENTATION, SPAN DIRECTION, SPACING, BEARING LOCATION AND NAMING CONVENTION OF THE LAYOUT SHOWN HERE. 3. THE TRUSS ENGINEER SHALL PROVIDE ALL TRUSS TO TRUSS CONNECTION DESIGN AND SPECIFICATIONS AND SUBMIT THEM UNDER SIGN AND SEAL WITH THE TRUSS SHOP DRAWINGS. 4. TRUSS UPLIFTS HAVE BEEN CALCULATED BY THE ENGINEER OF RECORD AND TAKEN INTO CONSIDERATION DURING THE DESIGN OF THE UPLIFT RESTRAINT SYSTEM FOR THIS STRUCTURE. AS SU;H, THE REPORTED UPLIFTS ON THE TRUSS SHOP DRAWINGS MAY BE DISREGARDED. 5. CONNECT ALL TRUSSES TO TOP PLATE AS SPECIFIED ON THE TYPICAL WALL SECTION SHEET. 6. I -JOISTS FABRICATED TO ACHIEVE THE FLOOR PLANS DEPICTED ON THE ARCHITECTURAL PLANS SHALL BE DESIGNED AND SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO FABRICATION AND INSTALLATION. SEE DESIGN CRITERIA, THIS SHEET, MASONRY NOTES 1. ALL MASONRY UNITS SHALL HAVE fm = 1,500 PSI AND SHALL ERECTED IN RUNNING BOND WITH TYPE M OR S MORTAR OVER FULL BED. 2. ENGINEER OF RECORD RECOMMENDS, BUT DOES NOT REQUIRE, ALL RUNNING BOND MASONRY WALLS TO BE EQUIPPED w/ 9 GAUGE LADDER TYPE HORIZONTAL JOINT REINFORCEMENT AT EVERY OTHER COURSE. 3. SHOULD LIMITED AREAS OF STACK BOND MASONRY EXIST, EVERY OTHER COURSE SHALL BE EQUIPPED w/ 9 GAUGE LADDER TYPE HORIZONTAL JOINT REINFORCEMENT 4. ALL GROUT TO MIXED PER ASTM C476 STANDARDS. fc = 2,500 PSI. 5. VERTICAL WALL REINFORCING TO BE ASTM A615 GRADE 60 REBAR. 6. LAPS BETWEEN VERTICAL REINFORCING AND DOWELS TO 8E 25". 7. VERTICAL REINFORCING TO HAVE 10" STANDARD HOOK INTO BOND BEAM. DOWEL TO HAVE 10" STANDARD HOOK INTO FOOTING. 8. PRE -CAST MASONRY LINTELS: SEE "TYPICAL PRECAST LINTEL" DETAIL ON DOWEL AND LINTEL PLACEMENT PLAN, ST -3. 9. PROVIDE MOISTURE BARRIER FOR ALL UNTREATED LUMBER IN CONTACT WITH MASONRY OR CONCRETE. TABLE 7: METAL CONNECTOR SCHEDULE IVV 1 CJ. 1. EPDXY ANCHOR EMBED FOR HOLD-DOWN CONNECTORS ANCHORED IN CMU TO BE 12 -INCHES. OPTIONAL SIMPSON 2"x12" TITEN HD OR USP WEDGE BOLT+ IS AN ACCEPTABLE ALTERNATIVE ANCHOR INTO TOP OF MASONRY STEMWALL IN ALL CASES EXCEPT GARAGE RETURN HOLDDOWNS. 2. REFER TO FRAM( G NOTES THIS SHEET FOR ACRYLIC -TIE INSTALLATION SPECIFICATIONS. 3. PRODUCTS SELE TED USING SIMPSON 2015-2016 CATALOG AND USP PRODUCT CATALOG 57TH EDITION. PRODUCTS MAY BE SUBSTITUTED WITH EQUAL OR BETTER APPROVED ALTERNATES. REFER TO RESPECTIVE CATALOG FOR ADDITIONAL INSTALLATION INSTRUCTIONS. 4. IF CONNECTOR I NOT LISTED ABOVE, CONTACT EOR FOR SPECIFIC FASTENING REQUIREMENTS. 5. POSITIVE PLACEMENT GUN NAILS, 22" LONG, WITH EQUIVALENT DIAMETER TO COMMON NAILS SPECIFIED ABOVE MAY BE USED FOR ABU POST BASE ANCHORS, S18, AND MSTA FLAT STRAPS, TABLE 8: SPECIFIED SW WALLS NOTES 1, 2, 3, 4 END STUD GROUPS SW TYPE NUMBER OF STUDS SW1, SW2, SW3 2 SW4 3 1. KING/JACK STUDS MAY BE INCLUDED FOR STUD GROUP REQUIREMENT. S W 1 I I I I III /- MIIN 6T BLLOCK W,? (2) 10d OUD ADJACENT TO LD DOWN EEND STUD BE SUBSTITUTED W/ END STUDS CONNECTION (NOTES 5 6 7) SW TYPE 1 ST LEVEL HOLD DOWN 2ND LEVEL STRAPPING SP & SIMPSON CONNECTORS IN CORRESPONDING ROWS BELOW ARE EQUAL DTT2Z ALTERNATIVES AND MAY BE CONSIDERED INTERCHANGEABLE SIMPSON SIMPSON FASTENERS USP USP FASTENERS SIMPSON SIMPSON USP USP FASTENERS WALL SECTION SHEET ST -6 ...................... SECTIONS AND DETAILS ST -7 ...................... SECTIONS AND DETAILS FASTENERS GREATER THAN 111" SEE FLOOR PLAN SEE FLOOR PLAN (8))/4" 1 2" SDS SCREWS (3) 2x4 (2) 2x6 SEE FLOOR PLAN (8) Y4" x 12" WS15-GC 1,2,3 IN TUD2" 0 x 42" Y 23 WOOD SCREWS IN STUD (9) 10d COMMON (9) 10d COMMON DTT2Z E BED EPDXY OR DTB- e Z 2„ 0 x 42" EMBED EPDXY CS18 EACH END OF CS20 EACH END OF S REW ANCHOR OR SCREW ANCHOR STRAP STRAP (1 )0.162"x22"IN (18)0.162"x22"IN HTT41,2,3 ST D/BEAM/TRUSS FiTT41,2,(3 STUD/BEAM/TRUSS MTS12 (7) 1 O x 1 Y2" MTW12 (7) 1 O x 1 2" 0 6" EMBED ANCHOR 0 x 6" EMBED ANCHOR EACH END EACH END N CONCRETE IN CONCRETE (2E) 0.162" x 2 Y" I N (26) 0.162" x 2 2" IN 1,2 ,3 HTT5 ST D/BEAM/TRUSS 1.2,3 HTT45 STUD/BEAM/TRUSS MSTA24 (9) 10d COMMON MSTA24 (9) 10d COMMON X, 0 x 6" EMBED ANCHOR 5/" 0 x 6" EMBED ANCHOR EACH END EACH END IN CONCRETE IN CONCRETE (20) 4' x 3" SDS SCREWS (24) 3" WS IN STUD HDQ8-SDS3 I Z8„ STUD GROUP �HD8 GROUP MSTA36 (13) 10d COMMON MSTA36 13 1 Od COMMON ( ) Z8" 0 x 2" EMBED ANCHOR 7„ $ 0 x 12" EMBED ANCHOR EACH END EACH END I CONCRETE IN CONCRETE (38)'6d SINKERS INTO (38) 16d SINKERS INTO (11) 10d x 12" IN (11) 1 O x 1Y2" IN S'THD14 STUDS STAD14 STUDS HTS20 TRUSS/RAFTER HTW20 TRUSS/RAFTER ET EMBED IN WET EMBED IN (11) 1 O x 12" IN (11) 1 O r 12" IN CONCRETE CONCRETE STUD STUD (10) Od x 1 2" NAILS IN (10) 16d COMMON NAILS (5) 8d x 1 2" IN (5) 8d x1 2" IN LTT20B2 STUD LTS192 IN STUD H2.5T/ TRUSS RT7/ TRUSS 2" 0 6" EMBED EPDXY 2" 0 x6" EMBED EPDXY HA8 (5) 8o x 1 2" IN TOP RT7AT (5) 8d x 1 2" IN TOP OR CREW ANCHOR OR SCREW ANCHOR PLATE PLATE (5) 1 Od x1 2" IN (5) 1 Od x1 2" IN ABU44 (12) 1 d COMMON NAILS PAU4Q' (12) 16d COMMON NAILS H8 TRUSS RT8A TRUSS 0 7" EMBED EPDXY W 0 x 7" EMBED EPDXY 6 (5) 10d x 1 2" IN (5) 10d x 1 2" IN TOP PLATE TOP PLATE (12) 16d COMMON NAILS (12) 16d COMMON NAILS (9) 1 O x1 2" IN (8) 8d x1 2" IN ABU66 /„ 0 7" EMBED EPDXY PAU661 " O x 7" EMBED EPDXY TSP STUD LFTA6 STUD (12" E BED AT GARAGE (12" EMBED AT GARAGE (6) 10d x 1 2" IN (8) 8d x 1 2" IN DOOR RETURNS) DOOR RETURNS) PLATE PLATE HU48, (14) 16d COMMON IN HD48, (14) 16d COMMON IN (6) 10d COMMON ( 6 10 Y " N HUC48, HEADER HD481F, HEADER DSP IN TOP PLATE RSPT6-2 TOP PLATE HU28-2, (6) 10d COMMON IN BEAM -2 HD2S 2 (6) 10d COMMON IN BEAM COMMON jN OER HUC28-2 HD28 STUD/HEADER STUD/HEADER()10d1Y2" HU410, (18) 16d COMMON IN HD410, (18) 16d COMMON IN (26) 16d SINKER IN (28) 16d SINKER IN HUC410, HEADER HD4101F, HEADER WALL FRAMING WALL FRAMI HU210-2, (10) 10d COMMON IN HD210-2, (10) 10d COMMON IN LGT3 (12) SDS %" x 21" LUGT3 (12) WS25 Y4" x 2 2" HUC210-2 BEAM HD210-21F BEAM IN TRUSS IN TRUSS (4) %" 1 2" SDS SCREWS (4) Y4" x 12" WS 15 SCREWS HGA1 OKT IN (4) %" x RUSS/RAFTER 3" SDS SCREWS IN HGA10 IN TRUSS/ RAFTER (4) Y4" x 3" WS3 SCREWS IN SDWC14500, SDWC15600 NO USP EQUIVALENT TOP PLATE _ TOP PLATE TITEN HD DIA. & EMBED SPECIFIED WEDGE DIA. & EMBED SPECIFIED ON PLAN BOLT+ ON PLAN IVV 1 CJ. 1. EPDXY ANCHOR EMBED FOR HOLD-DOWN CONNECTORS ANCHORED IN CMU TO BE 12 -INCHES. OPTIONAL SIMPSON 2"x12" TITEN HD OR USP WEDGE BOLT+ IS AN ACCEPTABLE ALTERNATIVE ANCHOR INTO TOP OF MASONRY STEMWALL IN ALL CASES EXCEPT GARAGE RETURN HOLDDOWNS. 2. REFER TO FRAM( G NOTES THIS SHEET FOR ACRYLIC -TIE INSTALLATION SPECIFICATIONS. 3. PRODUCTS SELE TED USING SIMPSON 2015-2016 CATALOG AND USP PRODUCT CATALOG 57TH EDITION. PRODUCTS MAY BE SUBSTITUTED WITH EQUAL OR BETTER APPROVED ALTERNATES. REFER TO RESPECTIVE CATALOG FOR ADDITIONAL INSTALLATION INSTRUCTIONS. 4. IF CONNECTOR I NOT LISTED ABOVE, CONTACT EOR FOR SPECIFIC FASTENING REQUIREMENTS. 5. POSITIVE PLACEMENT GUN NAILS, 22" LONG, WITH EQUIVALENT DIAMETER TO COMMON NAILS SPECIFIED ABOVE MAY BE USED FOR ABU POST BASE ANCHORS, S18, AND MSTA FLAT STRAPS, TABLE 8: SPECIFIED SW WALLS NOTES 1, 2, 3, 4 END STUD GROUPS SW TYPE NUMBER OF STUDS SW1, SW2, SW3 2 SW4 3 1. KING/JACK STUDS MAY BE INCLUDED FOR STUD GROUP REQUIREMENT. S W 1 I I I I III /- MIIN 6T BLLOCK W,? (2) 10d OUD ADJACENT TO LD DOWN EEND STUD BE SUBSTITUTED W/ END STUDS CONNECTION (NOTES 5 6 7) SW TYPE 1 ST LEVEL HOLD DOWN 2ND LEVEL STRAPPING SW1 DTT2Z MSTA36/CS18 SW2 HTT4 (2) MSTA36/CS18 SW3 HTT5 (3) MSTA36/CS18 SW4 HDQ8 (4) MSTA36/CS18 BOTTOM PLATE ANCHOR SPACING (NOTE 71 SW TYPE MAX ANCHOR SPACING SW1 48" O.C. SW2, SW3, SW4 24" O.C. NOTES: 1. THE EXTERIOR WALLS ARE FULLY SHEATHED WITH OSB OR PLYWOOD. ALL TYPICAL EXTERIOR WALLS ARE SHEAR WALLS AND ARE PART OF THE BUILDING'S MAIN IND FORCE RESISTING SYSTEM. ADDITIONAL FRAMING AND HOLD-DOWNS ARE REQUIRED ONLY AS NOTED ON THE PLAN OR IF WALL SEGMENT I IDENTIFIED AS SW1, SW2, SW3, SW4, OR SWB ON THE PLAN. 2. ALL SW SHEAR W LL SHEATHING TO BE FASTENED TO FRAMING PER TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS. 3. SW SHEAR WALLS INDICATED ON PLAN WITH WINDOW AND DOOR OPENINGS WITHIN THE SHEARWALL REQUIRE STUD GROUP AND HOLD DOWNS ONLY AT EXTREME END OF DESIGNATED WALL OR PORTION THEREOF AS NOTED ON STRUCTURAL PLAN. 4. SWB - SEE "SWB-SPECIAL SHEAR WALL DETAIL", LOCATED ON THE DETAIL SHEET. 5. 2ND LEVEL "SW' S EAR WALLS - END STUDS OF SW WALL TO BE ANCHORED PER ONE OF THE FOLLOWING: • HOLD DO WITH FULL -HEIGHT 2" DIA. ROD TO SLAB. END STUDS TO BE CONTINOUSLY SUPPORTED THROUGH FLOOR SYSTEM TO SLAB. • 2ND LEVEL END STUDS TO MATCHING 1ST LEVEL STUD GROUP BELOW W/ STRAPPING AS NOTED. 1ST LEVEL STUD GROUP TO SLAB WITHHOLD DOWN. 6. DESIGNATED "SW' SHEARWALLS WITH A COMMON CORNER REQUIRE (1) HOLDDOWN, WHICH IS TO BE LARGEST OF THE TWO HOLDOWNS SPECIFIED, UNO. T SEE WALL SECTIO SHEET FOR RECOMMENDED BOTTOM PLATE ANCHOR OPTIONS. SEE TABLE 7 FOR HOLD-DOWN ANCHOR REQUIREMENTS. FRAMING NOTES 1. SIMPSONACRYLIC-TIE ADHESIVE OR EQUAL SHALL BE USED IN ALL DRILLED AND EPDXIED ANCHOR APPLICATIONS. ANCHORBOLT, THREADED ROD, OR DOWELED REINFORCING STEEL MAY BE EMBEDDED TO THE SPECIFIED DEPTH, IN A HOLE S SPECIFIED BY MANF (TYPICALLY 16" TO 8" GREATER THAN SPECIFIED ANCHOR DIAMETER). ADHESIVE/EPDXY MUST FI L THE HOLE IN THE CONCRETE AND WOOD BOTTOM PLATE. MANUFACTURER'S SPECIFICATIONS MUST BE FOLLOWED FOR PROPER INSTALLATION. 2. ALL LUM ER SPECIFIED ON DRAWINGS IS INTENDED FOR DRY USE ONLY, UNO. ALL WATERPROOFING AND FIRE SAFETY SYSTEM ARE THE RESPONSIBILITY OF THE CONTRACTOR AND ARE TO BE DESIGNED AND DETAILED BY OTHER. 3. ALL METAL CONNECTORS SPECIFIED ON PLAN ARE IN ADDITION TO FRAMING FASTENER REQUIREMENTS LISTED IN FLORIDA BUILDING CODE TABLE 2304.9.1. 4. BEAMS IDENTIFIED BY NUMBER ON PLAN ARE TO BE PROVIDED BY TRUSS MANUFACTURER. 5. FASTEN LL MULTI -PLY STUD COLUMNS AND CORNERS TOGETHER WITH (2) ROWS 10d @ 8" O.C. STAGGERED. UPPER LEVEL MULTI -PLY STUD GROUPS BELOW ALL GIRDER LOCATIONS TO BE CONTINUOUS THROUGH FLOOR SYSTEM O FOUNDATION. (NOT REQUIRED BELOW HEADER JACK/KING STUD GROUPS) 6. FASTEN LL STUDS TO BOTTOM AND TOP (PLATES WITH (4)8d TOE NAILS OR (2)16d COMMON END NAILS. 7. FASTEN LL TRUSSES AND RAFTERS TO TOP PLATES WITH (3)8d TOE NAILS. 8. ALL MUL _I -PLY TRUSS GIRDERS AND BEAMS TO HAVE SOLID STUD GROUP BELOW MATCHING GIRDER OR BEAM THICKNESS AND MATCHING WALL STUD SPECIFICATIONS AS NOTED ON STRUCTURAL PLAN, UNO. SHEET INDEX ST -1 ...................... STRUCTURAL SPECIFICATIONS ST -2 ...................... FOUNDATION PLAN ST -2.1 ................... MASONRY PLAN ST -3 ......................1 ST LEVEL STRUCTURAL FRAMING PLAN ST-3A....................1ST LEVEL ROOF FRAMING PLAN ST -4 ...................... 2ND LEVEL STRUCTURAL FRAMING PLAN ST-4A....................2ND LEVEL ROOF FRAMING PLAN ST-5.......................TYPICAL WALL SECTION SHEET ST -6 ...................... SECTIONS AND DETAILS ST -7 ...................... SECTIONS AND DETAILS �ldgl 1 OR "OR" SHALL MEAN THAT EITHER OPTION PROVIDED IS AN EQUAL ALTERNATIVE FOR THE APPLICATION SHOWN UNO UNLESS NOTED OTHERWISE ON PLAN OR DETAIL EOR ENGINEER OF RECORD EW EACH WAY OSB ORIENTED STRAND BOARD WSP WOOD STRUCTURAL PANEL SYP SOUTHERN YELLOW PINE SPF SPRUCE -PINE -FUR CONT CONTINUOUS O.C. ON CENTER LSL 1.55E TIMBERSTRAND LSL ENGINEERED LUMBER, 1 3/4" WIDE, UNO. (3 1/2" WIDE LSL BEAMS ARE EQUIVALENT TO 2 -PLY 1 3/4" BEAM) LVL 2.0E MICROLLAM LVL ENGINEERED LUMBER, 1 3/4" WIDE PSL 2.0E PARRALLAM PSL ENGINEERED LUMBER, 3 1/2" WIDE, UNO. SYS 42 PROPERLY RATED OPEN WEB HEADFR T.O.M. TOP OF MASONRY INTERIOR ROOF LOAD BEARING WALL; SPECIFICATIONS OUTLINED ON TYPICAL WALL SECTIONS, DETAIL SHEETS INTERIOR BEARING WALL WITH NO UPLIFT. NO UPLIFT ANCHORS REQUIRED. MINIMUM BOTTOM PLATE ANCHORAGE IS 2" ANCHOR @ 8'-0" O.C. (UNO ON FRAMING PLAN OR SW SPECIFICATIONS) STRUCTURAL WOOD BEAM FOUNDATION KEYNOTE CALLOUT STUD COLUMN KEYNOTE CALLOUT - NUMBER OF SDWC15600 CONNECTING TOP PLATE TO STUDS. NUMBER OF STUDS BELOW BEAM/GIRDER TRUSS. STUDS BOTTOM OF STUD COLUMN CONNECTION • 1ST LEVEL STUD COLUMN: HOLDDOWN REQUIRED AT BASE OF COLUMN • 2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL COLUMN TO 1ST LEVEL STUDS/HEADER/BEAM. "ANCHOR" REQUIRES BOTTOM PLATE ANCHOR WITHIN 3" OF STUD COLUMN NUMBER OF SDWC15450 CONNECTING STUDS TO BOTTOM PLATE HEADER STRAPPING KEYNOTE CALLOUT NUMBER OF STRAPS CONNECTING HEADER TO JACK STUD 1 MSTA24 TYPE OF STRAP CONNECTING HEADER TO JACK STUD 1 DTT2Z KING/JACK GROUP BOTTOM CONNECTION • 1ST LEVEL STUD GROUP: HOLDDOWN REQUIRED AT BASE OF STUD GROUP • 2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL STUD GROUP TO 1ST LEVEL STUDS/HEADER/BEAM. NUMBER OF HOLDDOWNS/STRAPS AT BASE OF KING/JACK GROUP HEADER FRAMING KEYNOTE CALLOUT NUMBER OF KING STUDS EACH SIDE OF OPENING NUMBER OF JACK STUDS EACH SIDE OF OPENING SIZE OF HEADER (ALL HEADERS TO BE NO.2 SYP) OR WSP NUMBER OF PLIES IN HEADER ENGINEERED LUMBER HEADER FRAMING KEYNOTE CALLOUT (2) 9 1/2" LSL-1/2 -� NUMBER OF KING STUDS EACH SIDE OF OPENING NUMBER OF JACK STUDS EACH SIDE OF OPENING HEADER MATERIAL (ALL HEADERS TO BE DESIGNATED AS LSL, LVL, PSL, OR SYS42) DEPTH OF HEADER NUMBER OF PLIES IN HEADER (1 3,4" WIDE UNO) HEADER FRAMING 1. ALL HEADER JACK AND KING STUDS SHALL BE FASTENED TO EACH OTHER WITH (2) ROWS 10d @ 8" O.C. STAGGERED. 2. WSP HEADERS ARE WOOD STRUCTURAL PANEL HEADERS AND HAVE THE FOLLOWING REQUIREMENTS: • SHEATHING TO MATCH SPECIFICATION FOR EXTERIOR WALLS, SEE TABLE 2. • ATTACH TO ALL FRAMING MEMBERS (KING STUD, TOP PLATE, HEADER SILL, CRIPPLES, ETC.) W/ 8d COMMON @ 3" O.C. • EITHER TOP OR BOTTOM PLY OF DBL TOP PLATE MUST SPAN CONTINUOUS OVER OPENING; SHEATHING MUST BE EDGE NAILED TO CONTINUOUS PLY OF PLATE • NO.2 SPF HEADER SILL INSTALLED ABOVE OPENING W/ (1) CRIPPLE STUD AT EACH END • WALL SHEATHING ABOVE OPENING MUST BE CONTINUOUS (OR PROPERLY SPLICED PER TYPICAL WALL SECTION SHEET) FROM TOP OF PLATE TO HEADER BELOW OR SILL PLATE ABOVE OPENING 3. FASTEN ALL MULTI -PLY HEADERS TOGETHER WITH (2) ROWS 1 Od @ 8" O.C., STAGGERED ALONG EACH EDGE. 4. FASTEN ALL HEADERS TO KING STUDS WITH (3)8d TOE NAILS. 5. IF HEADER NOT SPECIFIED, CONTACT ENGINEER OF RECORD. 6. LINO ON PLAN, MIN (1) SDWC15600 TOP PLT TO KING STUD AND (1) SDWC15450 KING STUD TO BOTTOM PLATE CONNECTION REQUIRED EACH SIDE OF OPENING (NO CONNECTION REQUIRED FOR OPENINGS AT FIRST FLOOR HEADER WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE. 7. TOP PLATE TO HEADER CONNECTION PER ONE OF THE FOLLOWING (NO CONNECTION REQUIRED FOR OPENINGS 39" OR LESS, AT WSP HEADERS, OR AT FIRST FLOOR HEADERS WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE: • TOP PLATE TO HDR W/ SDWC15600 @ MAX 32" O.C. AS SHOWN, "ALTERNATE SECTION (HEADERS),ST-5 • SPH w/ (12) 10d x 1-Y2" @ 16" O.C. OR • DSP w/ (14) 10d x 1%" @ 16" O.C. OR • FASTEN TRUSS DIRECTLY TO HEADER w/ MTS OR HTS w/ (14) 10d x 1-1/2" (OR EQUAL APPROVED BY EOR). TABLE 9: PLANK -ORIENTED HEADER REQUIREMENTS NOTE 6 (APPLICABLE TO ALL) TO MATCH WALL FRAMING SIZE AND GRADE, UNO. 2 2 STUDS U) u MAXIMUM 11' (NOTES 1,2) D p Of ADDITIONAL CLARITY FOR THE LOCATION OF THE STUD COLUMN GREATER THAN 48" IJP TO 75" (NOTE 3) (2) 2x4 2 ANCHOR � FD (3) 2x4 BOTTOM OF STUD COLUMN CONNECTION • 1ST LEVEL STUD COLUMN: HOLDDOWN REQUIRED AT BASE OF COLUMN • 2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL COLUMN TO 1ST LEVEL STUDS/HEADER/BEAM. "ANCHOR" REQUIRES BOTTOM PLATE ANCHOR WITHIN 3" OF STUD COLUMN NUMBER OF SDWC15450 CONNECTING STUDS TO BOTTOM PLATE HEADER STRAPPING KEYNOTE CALLOUT NUMBER OF STRAPS CONNECTING HEADER TO JACK STUD 1 MSTA24 TYPE OF STRAP CONNECTING HEADER TO JACK STUD 1 DTT2Z KING/JACK GROUP BOTTOM CONNECTION • 1ST LEVEL STUD GROUP: HOLDDOWN REQUIRED AT BASE OF STUD GROUP • 2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL STUD GROUP TO 1ST LEVEL STUDS/HEADER/BEAM. NUMBER OF HOLDDOWNS/STRAPS AT BASE OF KING/JACK GROUP HEADER FRAMING KEYNOTE CALLOUT NUMBER OF KING STUDS EACH SIDE OF OPENING NUMBER OF JACK STUDS EACH SIDE OF OPENING SIZE OF HEADER (ALL HEADERS TO BE NO.2 SYP) OR WSP NUMBER OF PLIES IN HEADER ENGINEERED LUMBER HEADER FRAMING KEYNOTE CALLOUT (2) 9 1/2" LSL-1/2 -� NUMBER OF KING STUDS EACH SIDE OF OPENING NUMBER OF JACK STUDS EACH SIDE OF OPENING HEADER MATERIAL (ALL HEADERS TO BE DESIGNATED AS LSL, LVL, PSL, OR SYS42) DEPTH OF HEADER NUMBER OF PLIES IN HEADER (1 3,4" WIDE UNO) HEADER FRAMING 1. ALL HEADER JACK AND KING STUDS SHALL BE FASTENED TO EACH OTHER WITH (2) ROWS 10d @ 8" O.C. STAGGERED. 2. WSP HEADERS ARE WOOD STRUCTURAL PANEL HEADERS AND HAVE THE FOLLOWING REQUIREMENTS: • SHEATHING TO MATCH SPECIFICATION FOR EXTERIOR WALLS, SEE TABLE 2. • ATTACH TO ALL FRAMING MEMBERS (KING STUD, TOP PLATE, HEADER SILL, CRIPPLES, ETC.) W/ 8d COMMON @ 3" O.C. • EITHER TOP OR BOTTOM PLY OF DBL TOP PLATE MUST SPAN CONTINUOUS OVER OPENING; SHEATHING MUST BE EDGE NAILED TO CONTINUOUS PLY OF PLATE • NO.2 SPF HEADER SILL INSTALLED ABOVE OPENING W/ (1) CRIPPLE STUD AT EACH END • WALL SHEATHING ABOVE OPENING MUST BE CONTINUOUS (OR PROPERLY SPLICED PER TYPICAL WALL SECTION SHEET) FROM TOP OF PLATE TO HEADER BELOW OR SILL PLATE ABOVE OPENING 3. FASTEN ALL MULTI -PLY HEADERS TOGETHER WITH (2) ROWS 1 Od @ 8" O.C., STAGGERED ALONG EACH EDGE. 4. FASTEN ALL HEADERS TO KING STUDS WITH (3)8d TOE NAILS. 5. IF HEADER NOT SPECIFIED, CONTACT ENGINEER OF RECORD. 6. LINO ON PLAN, MIN (1) SDWC15600 TOP PLT TO KING STUD AND (1) SDWC15450 KING STUD TO BOTTOM PLATE CONNECTION REQUIRED EACH SIDE OF OPENING (NO CONNECTION REQUIRED FOR OPENINGS AT FIRST FLOOR HEADER WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE. 7. TOP PLATE TO HEADER CONNECTION PER ONE OF THE FOLLOWING (NO CONNECTION REQUIRED FOR OPENINGS 39" OR LESS, AT WSP HEADERS, OR AT FIRST FLOOR HEADERS WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE: • TOP PLATE TO HDR W/ SDWC15600 @ MAX 32" O.C. AS SHOWN, "ALTERNATE SECTION (HEADERS),ST-5 • SPH w/ (12) 10d x 1-Y2" @ 16" O.C. OR • DSP w/ (14) 10d x 1%" @ 16" O.C. OR • FASTEN TRUSS DIRECTLY TO HEADER w/ MTS OR HTS w/ (14) 10d x 1-1/2" (OR EQUAL APPROVED BY EOR). TABLE 9: PLANK -ORIENTED HEADER REQUIREMENTS NOTE 6 (APPLICABLE TO ALL) 1. FOR OPENING WIDTHS GREATER THAN OR EQUAL TO 48", FASTEN PLANK HDR TO STUD GROUP WITH MIN (6) 1 Od TOE -NAILS AT EACH END. 2. WINDOWS WITH INTERMEDIATE JACK STUDS MAY BE TREATED AS SEPARATE OPENINGS. 3. FOR OPENING WIDTHS LESS THAN 48", A SINGLE 2x- PLATE IS SUFFICIENT. FASTEN PLATE TO STUDS WITH (3) 10d TOE -NAILS AT EACH END. 4. FOR PLATE HEIGHTS ABOVE 11% SEE FLOOR PLAN FOR PLANK -ORIENTED HEADER REQUIREMENT. 5. (*) HEADERS DESIGNATED WITH AN ASTERISK REQUIRE MIN 2x6 WALL FRAMING. 6. IN SITUATIONS WHERE PLATE HEIGHT ELEVATION VERSUS TOP OF OPENING ELEVATION DOES NOT PROVIDE FRAMING DEPTH ADEQUATE FOR PLANK ORIENTED HEADER TO BE INSTALLED, GRAVITY HEADER HAS BEEN SIZED TO RESIST OUT OF PLANE WIND LOADS. ANY SHIM MATERIAL BETWEEN TOP OF OPENING & BOTTOM OF HEADER SHALL BE FASTENED TO BOTTOM OF HEADER WITH (2) ROWS 0.131" 0 X 12" EMBED INTO HEADER @ 8" O.C. STAGGERED. REVIEWED FOR CODE COIV PLIANCE\ CITY OF ATLANTIC BEACH SEE PERMITS FOR ADDITIONAL REQUIREMENTS ARID CONDITIONS JI UL W J J z O U) Y U Q N O ,t' W tY O U Y 4 z O I- F - 7) U) LO ,It ao z .7❑ Q I in ❑ W� Q z LLC) moi? �Z13 0_j�� r }a° z �EJzz❑ QF -W W - 0 M < I < D O wwEo °WWw❑LJ IL wJ - ° C0 z ❑ a} w W N N m❑ z U W Q a t< 0 M I w W w F N w w W ❑ U Z FII'-MjI FwZW<L I- ❑ IL p w z F z w O Z❑ X° [E w a I w ° Q m ❑a�wwzp°Zmaa2w Q_ ZzaXtw-❑01-❑-IW 0 W EW°wXQZ<Fw�-w[7 w w�Qaw2Wo�]N wW z Zz)-Z<0-- X00 wz Z W° a m z N w Q z Q LU Z❑Uw[wD wwQ�FU 0 F I Z F v� z w D° W E ZUQ- U[Y❑I W°ZQ O n�?3Na-U]<0M�?an J LL z SHEET NO.: 0 ST -1 F - o STRUCTURAL SPECIFICATIONS 0 JOB NO.: U AT1496 Q ® SUBDIVISION: 0 Atlantic Beach LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom O Z DESIGNED: DAE/SDA w I- REVIEWED: w DBM a_ REVISIONS DATE m LU z O w Q z W :.A,PEXO 1- STRUCTURAL ENGINEERING F - _U LL �3�6sfi (A �� EiV ° c�a 10 714, 7 i REVIEWED SY. DATE: 5 -9' CYO w X w 12- Derek B. Murray, P.E. CMU/METAL CONNECTOR FNGINFFRING Q P.E. No. 71457 04-02-2018 CONTINUOUS ROUGH OPENING WIDTH STUCCO FINISH -L/360 FLEXIBLE FINISH -L/180 MAXIMUM 11' MAXIMUM 11' (NOTES 1,2) PLATE HEIGHT PLATE HEIGHT GREATER THAN 48" IJP TO 75" (NOTE 3) (2) 2x4 (2) 2x4 o GREATER THAN 75" UP TO 111" (2) 2x6* (3) 2x4 � GREATER THAN 111" SEE FLOOR PLAN SEE FLOOR PLAN U) 0 o GREATER THAN 48" UP TO 75" (NOTE 3) GREATER THAN 75" UP TO 111" GREATER THAN 111" (3) 2x4 (2) 2x6 SEE FLOOR PLAN (2) 2x4 (2) 2x6 SEE FLOOR PLAN 1. FOR OPENING WIDTHS GREATER THAN OR EQUAL TO 48", FASTEN PLANK HDR TO STUD GROUP WITH MIN (6) 1 Od TOE -NAILS AT EACH END. 2. WINDOWS WITH INTERMEDIATE JACK STUDS MAY BE TREATED AS SEPARATE OPENINGS. 3. FOR OPENING WIDTHS LESS THAN 48", A SINGLE 2x- PLATE IS SUFFICIENT. FASTEN PLATE TO STUDS WITH (3) 10d TOE -NAILS AT EACH END. 4. FOR PLATE HEIGHTS ABOVE 11% SEE FLOOR PLAN FOR PLANK -ORIENTED HEADER REQUIREMENT. 5. (*) HEADERS DESIGNATED WITH AN ASTERISK REQUIRE MIN 2x6 WALL FRAMING. 6. IN SITUATIONS WHERE PLATE HEIGHT ELEVATION VERSUS TOP OF OPENING ELEVATION DOES NOT PROVIDE FRAMING DEPTH ADEQUATE FOR PLANK ORIENTED HEADER TO BE INSTALLED, GRAVITY HEADER HAS BEEN SIZED TO RESIST OUT OF PLANE WIND LOADS. ANY SHIM MATERIAL BETWEEN TOP OF OPENING & BOTTOM OF HEADER SHALL BE FASTENED TO BOTTOM OF HEADER WITH (2) ROWS 0.131" 0 X 12" EMBED INTO HEADER @ 8" O.C. STAGGERED. REVIEWED FOR CODE COIV PLIANCE\ CITY OF ATLANTIC BEACH SEE PERMITS FOR ADDITIONAL REQUIREMENTS ARID CONDITIONS JI UL W J J z O U) Y U Q N O ,t' W tY O U Y 4 z O I- F - 7) U) LO ,It ao z .7❑ Q I in ❑ W� Q z LLC) moi? �Z13 0_j�� r }a° z �EJzz❑ QF -W W - 0 M < I < D O wwEo °WWw❑LJ IL wJ - ° C0 z ❑ a} w W N N m❑ z U W Q a t< 0 M I w W w F N w w W ❑ U Z FII'-MjI FwZW<L I- ❑ IL p w z F z w O Z❑ X° [E w a I w ° Q m ❑a�wwzp°Zmaa2w Q_ ZzaXtw-❑01-❑-IW 0 W EW°wXQZ<Fw�-w[7 w w�Qaw2Wo�]N wW z Zz)-Z<0-- X00 wz Z W° a m z N w Q z Q LU Z❑Uw[wD wwQ�FU 0 F I Z F v� z w D° W E ZUQ- U[Y❑I W°ZQ O n�?3Na-U]<0M�?an J LL z SHEET NO.: 0 ST -1 F - o STRUCTURAL SPECIFICATIONS 0 JOB NO.: U AT1496 Q ® SUBDIVISION: 0 Atlantic Beach LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom O Z DESIGNED: DAE/SDA w I- REVIEWED: w DBM a_ REVISIONS DATE m LU z O w Q z W :.A,PEXO 1- STRUCTURAL ENGINEERING F - _U LL �3�6sfi (A �� EiV ° c�a 10 714, 7 i REVIEWED SY. DATE: 5 -9' CYO w X w 12- Derek B. Murray, P.E. CMU/METAL CONNECTOR FNGINFFRING Q P.E. No. 71457 04-02-2018 4" CONCRETE SLAB W/ 6x6 W1.4 x W1.4 WWF OR FIBERMESH a - - - _a_ - - - - - ° 8" MIN 28" MAX 17 7 VAPOR BARRIER 12" MIN/ //\/0 FOOTING TO BEAR ON 6" OPT. EXTENSION IN BRICK FIRM UNDISTURBED SOIL LOCATIONS ON FND PLAN 12" UNDER 1 STORY WALL WITH (2)#4 OR (2)#5 CONT ADDITIONAL NO. 4 OR NO. 5 BAR IN BRICK LEDGE 16" UNDER 2 STORY WALL WITH (3)#4 OR (2)#5 CONT O)YO NOLITHIC FOOTING SECTION GROUND ADJACENT TO FTG SLOPES DOWN AND AWAY FROM STRUCTURE STEEPER THAN V-0" VERTICALLY PER 3'-0" HORIZONTALLY, CONTRACTOR HAS TWO CHOICES: 1. PRIOR TO CONSTRUCTION, SEEK GUIDANCE CF EOR TO PREVENT EROSION OF SOIL. 2. USE STEMWALL FOOTING (2) #4 OR (2) #5 CONTINUOUS 6x6 - W1.4 x W1.4 WWF OR FIBERMESH a A A \/\\ d / VAPOR BARRIER 16" 3 BEARING WALL FOOTING SECTION 4" CONCRETE SLAB W1 6x6 W1.4 x W1.4 WWF OR FIBERMESH 0'-0" A.F.F. -------a---� a d ` d \\ d 4 -- a - --------- d a / 8"x8" THICKENED 8" FTG AT STEP-DOWN, SEE PLAN CURB STEP SECTION 4 VARIES 8" MIN VAPOR BARRIER 6" 4" CONCRETE SLAB NO 4 OR NO 5 @ 18" O.C. W/ 6x6 W1.4 x W1.4 W! 9" BEND @BOTTOM WWF OR FIBERMESH VARIES 8 " MIN A - - - ° - ° a 28" MAX \� \\/ \X/�\/�\ /\j\ a e 12" M I N a / VAPOR BARRIER 6" OPT, EXTENSION IN BRICK LOCATIONS ON FND PLAN 12" UNDER 1 STORY WALL WITH (2)#4 OR (2)#5 CONT ADDITIONAL NO. 4 OR NO. 5 BAR IN BRICK LEDGE 16" UNDER 2 STORY WALL WITH (3)#4 OR (2)#5 CONT 5 GARAGE EXT WALL CURB SECTION IF GROUND ADJACENT TO FTG SLOPES DOWN AND AWAY FROM STRUCTURE STEEPER THAN V-0" VERTICALLY PER T-0" HORIZONTALLY, CONTRACTOR HAS TWO CHOICES: 1. PRIOR TO CONSTRUCTION, SEEK GUIDANCE OF EOR TO PREVENT EROSION OF SOIL. 2. USE STEMWALL FOOTING 4" CONCRETE SLAB W/-\ 6x6 W1.4 x W1.4 WWF OR FIBERMESH 0'-0" A.F.F. -d----a--------, VARIES a d e a e1 \ \ \ d L---------- IX, T„ 12" UNDER 1 STORY WALL BARRIER WITH (2)#4 OR (2)#5 CONT 16" UNDER 2 STORY WALL WITH (3)#4 OR (2)#5 CONT 6 BEARING CURB STEP SECTION CKENED 'LAN BEYOND AND FTG, SEE PLAN =N BACK ER 4 COURSES HIGH. SHOULD THIS CONDITION EXIST, RECOMMENDATIONS MAY BE OBTAINED FROM THE ENGINEER OF RECORD. 2. SCREW IN ANCHORS ALLOWED IN MONOLITHIC FOOTINGS ONLY. EPDXY ANCHORS MUST BE USED IN STEMWALL FOUNDATIONS v N LO 19 0 4'-4" 48'-0" 16-3" 15'-6" 16-3" _ ***NOTE*** BUILDER TO PROVIDE STEPS TO GRADE PER ARCH PLANS ------- --------------- --------------------- I � I L- _J L- __JL I 1 I 1 • 12" SQ. SOLID FILLED FORM & POUR 2 ® 1 CONC. PEDESTAL OR CMU BASE 1 I • (2) #5 FULL HEIGHT VERTICAL TO BEND AND TIE TO FTG (4) TOTAL I 2 REINFORCEMENT AT BOTTOM • (4) TOTAL Z I li If ( I II � 1 I ! - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - I �,-- ----- _-----------__ ----- N ---- �---------- --- NOTE3- - - I 6 OPT F_ 1 i T I I N I I 101I -- __—I I I■ I I I F_ I I 1 I I ■I I 3 I 1 I 1 I I 1 (I I I I 1 1 16'-2" I 5'-10" 26'-0" i I I I ■II 11 N II I I I I I■ I I I I I 2 3 I 1 I �■ -�-- — '—) ■I I 1 I I I I I I I I I ' I I II Q z w w? x o o I w w= w z o a W 11'-4" 10'-5" 5'-0" 200 I I I I I ■ 1 I OPT 6 2 I I o 6 PT BUILDER TO I I• ■ ■ ■ PROVIDE STEPS I __ __--- ------------- I PER ARCH PLANS I L - - I Bf"SICK LEDGE 19'-4" I L - -_- -_ ■ — — — — I ■ OPT PAVERS B o I 2 I BUILDER 2 D I— — —— J II L (2) TOTAL 2 f 1 I — I F_.-1 --� —T- - - - - - - - - - - - - - - - - I I I r OPT 6 2 7 `f' • 12" SQ. SOLID FILLED I FORM & POUR CONC. I PEDESTAL OR CMU BASE ■ I • (2) #5 FULL HEIGHT VERTICAL TO BEND AND L� TIE TO FTG OTAL REINFORCEMENT AT 4'-4" 10 -0" 5'-8" 3'-4" BOTTOM I I • ***NOTE*** ■ I I BUILDER TO PROVIDE i iSTEPS TO GRADE PER ARCH PLANS 7 0 UNDER DOOR1 I I I I it I I I I I s I I , I i 7 'WI LI N O - - ---------- -- I BRICK LEDGE:i FOUNDATION PLA 23'-4" 4'-0" 1 &_0" 16'-0" 56-4" 4'-0" 2 4'-0" 17'-0" " 1 ' 011 1/4 0 v O c 0 r GENERAL FOUNDATION NOTES 1. EARTH AND EARTH FILL SUPPORTING SLABS ON GRADE IS ASSUMED TO HAVE A MINIMUM BEARING CAPACITY OF 2,000 psf IN ACCORDANCE WITH FRC 6TH EDITION (2017) TABLE R401.4.1, AND SHALL BE FREE OF ORGANIC MATERIAL AND COHESIVE SOILS. COMPACT THE FILL IN 12" LIFTS TO AT LEAST 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY. IT IS THE OWNER'S OR CONTRACTOR'S RESPONSIBILITY TO CONFIRM THESE ASSUMPTIONS. 2. IF CONTRACTOR OR BUILDING OFFICIAL DETERMINES THAT THE SOIL IS NOT SUITABLE FOR 2,000 PSF BEARING CAPACITY, CONTACT EOR. ADDITIONAL FOUNDATION WORK MAY BE REQUIRED. 3. SLIDING GLASS DOOR FRAMES MUST BE RECESSED INTO THE SLAB IN ACCORDANCE WITH THE FLORIDA BUILDING CODE. CONSULT ARCHITECTURAL PLANS FOR LOCATION OF SLIDING GLASS DOORS. 4. MASONRY STEMWALL AND MONOLITHIC FOOTINGS ARE INTERCHANGEABLE. SEE DETAIL SHEETS FOR ALTERNATE STEMWALL SECTIONS. 5. 24" LONG # 4 BAR IS RECOMMENDED TO BE INSTALLED AT ALL RE-ENTRANT CORNERS, SEE "RE-ENTRANT CORNER DETAIL" THIS SHEET, FOUNDATION KEYNOTES: NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN A8"x8" DEEP THICKENED EDGE W/ (1)#4 CONT 12" DEEP FTG W/ #4 @ 12" EW B UNDER BOX COLUMN, FTG TO BE PROJECTED MIN 6" AS SHOWN 16"SQx12" DEEP FTG W/ •113)#4 EW A(3#4 24"SQx20" DEEP FTG W/ EW Q30"SQx20" DEEP FTG W/ (4)#4 EW E Q36"SQx20" DEEP FTG W/ F (4)#4 EW A48"SQx24" DEEP FTG W/ (5)#4 EW, T&B CONTROL JOINT (CJ) NOTES: 1. TIMING • CUTS MUST BE MADE THE SAME DAY AS PLACEMENT. AS SOON AS THE CONCRETE HAS SET ENOUGH TO ALLOW SAWCUTS WITHOUT RAVELING THE COURSE AGGREGATE FROM THE CUT, MAKE THE CUT. • CUTS MADE THE NEXT DAY OR AT SUBSEQUENT TIMES DO NOT PROVIDE ADEQUATE PROTECTION AGAINST "RANDOM" CRACKING. 2. DEPTH THE CUT SHOULD BEAT LEAST 1" DEEP, BUT NOT MORE THAN 1 '/d' DEEP. 3. SEALING a) cl THE CUTS SHOULD BE SEALED WITH A SEMI-RIGID EPDXY OR ACRYLIC 00 ADHESIVE SEALANT. JOINT SEALANT IS RECOMMENDED BUT NOT REQUIRED AT INTERIOR LOCATIONS. BACKER ROD IS NOT REQUIRED. tN CV C70 TYPICAL REINFORCING �I- I BARS AT THICKENED FOOTING, SEE PLAN ' d- MIN 24" LONG #4 OR #5 C14 BAR SET AT MID -DEPTH N co HOUSE SLAB O Cl) RE-ENTRANT CORNER DETAIL Q (RECOMMENDED) N PLAN VIEW, DETAIL TYPICAL @ ALL V' RE-ENTRANT CORNERS W 4" CONCRETE SLAB W/ 6x6 W1.4 x W1.4 WWF OR FIBER MESH 8" CMU CHAIR BLOCK W/ O TOP OF SLAB OIL 1 (1) #5 CONT. 0 �— ---- Y ---- -- I 48-`/ Q I VAPOR BARRIER #4 OR #5 VERT REINFORCING I /\\/\\� (/) UP TO 3 COURSES: 72" O.C. \\//\\/ I //\\//\\/ U- x o } 4 TO 5 COURSES: 48" O.C. ,`//\/ I /\/1 // W w z 2❑ ''\/ • ✓/�\/ r JIL 0 z It it LO w 0ao zw°�E_jzzo <Fww-QM<M<Dww ADDITIONAL #4 OR #5 IN wwLI �� �Nww❑w�,�o FOOTING TO BEAR ON FIRM\r . //�\ /\' BRICK LEDGE UNDISTURBED SOIL z � o a w F o W o�oa}wwHNNm❑ZIj VERTICAL REINFORCEMENT 4" OPT BRICK LEDGE z d w o w i- = 2 w z TO HAVE 6" BEND AT BOTTOM NOTED ON FND PLAN C) N � ❑ c 0 a o z L a z w 0, o z� W o Q z w w? x o o I w w= w z o a W CAST -IN-PLACE FOOTING SPECS m o o❑ 11 11 z F z In CI a 0 Z Q w❑ 1 -STORY: 8" x 16" W/(2) #4 OR (2)#5 CONT Q X p z Q w �` 2 -STORY: 10" x 20" W/(3) #4 OR (2) #5 CONT W E D W 1- z �- E wwz xQwLi¢� Wz W Z WffQMw2IW IL-QU:) WW z _Z<0 2 CMU STEMWALL SECTION z waU��zW❑ W°�¢mz 1. SPECIAL CARE SHOULD BE EXERCISED BY CONTRACTOR WHEN BACK W Q lQ�z3E�Q w ❑ 2 w w . m v z r FILLING BEHIND A STEM WALL, PARTICULARLY WHEN IT IS OVER 4 i? z- Q v w w- p W I- �LDQr�nw❑IOw0Z� COURSES HIGH. SHOULD THIS CONDITION EXIST, RECOMMENDATIONS o MAY BE OBTAINED FROM THE ENGINEER OF RECORD. O ❑ W . Q _j I . = o - f- ? 3 N a N ¢ o r7 F ? v v 2. SCREW IN ANCHORS ALLOWED IN MONOLITHIC FOOTINGS ONLY EPDXY _I ANCHORS MUST BE USED IN STEMWALL FOUNDATIONS. z SHEET NO.: o ST -2 H o FOUNDATION 0'-0" A.F.F. (BEYOND) U -BLOCK W/ D_ PLAN 4" FLOATING CONCRETE N (1) #5 CONT 0 JOB NO.: Q SLAB W/ 6x6 W1.4xW1.4 U WWF OR FIBERMESH , I Z �w , AT1496 w '— — L — — — �,'— • FINISH SUBDIVISION: a O GRADE o Atlantic Beach , �\�/�\�/�\�/%' /�\�/�� Q Country Club j\/j\/j\// /j LOT NO.: #4 OR #5 VERT REINFORCING Z_ 6 UP TO 3 COURSES: 72" O.C. 4 TO 5 COURSES: 48" O.C. a ° I a (D FLOOR PLAN: L- ----- o Custom \ — Z DESIGNED: FOOTING TO BEAR ON FIRM \ ' U DAE/SDA UNDISTURBED SOIL ADDITIONAL #4 OR #5 W IN BRICK LEDGE I- REVIEWED: VERT REINFORCEMENT TO 4" OPTBRICK LEDGE DBM HAVE 6" BEND @ BOTTOM 0- - NOTED ON FND PLAN Q REVISIONS DATE CAST -IN-PLACE FOOTING SPECS Q- - - --- 1 -STORY: 8" x 16" W/(2) #4 OR (2)#5 CONT 2 -STORY: 10" x 20" W/(3) #4 OR (2) #5 CONT CMU STEMWALL SECTION LU LU - 7 __�- >z 1. SPECIAL CARE SHOULD BE EXERCISED BY CONTRACTOR WHEN BACK FILLING BEHIND A STEM WALL, PARTICULARLY WHEN IT 'sS OVER 4 O COURSES HIGH. SHOULD THIS CONDITION EXIST, RECOMMENDATIONS LL1 MAY BE OBTAINED FROM THE ENGINEER OF RECORD. d 2. SCREW IN ANCHORS ALLOWED IN MONOLITHIC FOOTINGS ONLY. < EPDXY ANCHORS MUST BE USED IN STEMWALL FOUNDATIONS. U) EX a STRUCTU L ENGINEERING ,, � `SK k1l tl i��: 4 y d°°. tw e�ti� • ;� �tsb sx T1=1_d OFFICE C Y z U W X W D- `� Dark B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING P.E.N°.'1457 04-02-2018 10 F07 x 0'-8" 3'-8" 6-10" 3'-8" 4'-4" 4'-4" 3'-8" 3'-8" 14'-7" N CV ■ L-2 L-5 =L- L-6 L-2 ■ 0 ■ °° L-2 ■ 0 N ■ in ■ ------------------------------- c� ■ c? ------ --------II------------------------------- --------- --------------------- I I I I I I ■ I I I I I I I I I I I I 1 — I I I I I ---------- ---------- ---------- ---------- ---------- 1? ------------------- I I I I I I I 0 i� 171 L ■ 01' 1 3'-8" L-2 a - N 5'-0" 5'-0" 3'-8" 3'-0" LL®8 6'-8" L-7 T-2" Fx_ 1'-2" ❑C ❑C 0 ■ 0 LO ■ L-7 ti 4'-0" ■ V ■ 5'-2" ■ El ■ ■ 1 Alf = 1' Off - 0 " L9 ;T W J W U co W W 07 BOND BEAM REINFORCEMENT (SEE WALL SECTION) FILL SOLID TO BOND BEAM (1) #5 CONTININUOUS IN PRECAST LINTEL 8FX-1 B/1 T PRECAST LINTEL NOTES: 1. ALL PRECAST LINTELS GREATER THAN 4'-0" ARE TO HAVE ON #5 REBAR AT BOTTOM OF LINTEL 2.AREAS OF BLOCK ABOVE MASONRY OPENINGS ARE TO BE GROUTED SOLID TO TIE BEAM 3. BOND BEAM TO BE CONTINUOUS THROUGH OUT INCLUDING ABOVE MASONRY OPENINGS. SEE TYPICAL WALL SECTION FOR REINFORCEMENT. 4. CONSULT FLOOR PLAN & ELEVATIONS FOR EXACT COURSE COUNT ABOVE LINTEL 5. CONSULT CAST -CRETE INSTALLATION SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 6. UNLESS APPROVED OTHERWISE, ALL LINTELS TO HAVE MIN 4" BEARING AT EACH END. TYPICAL PRECAST LINTEL LINTEL SCHEDULE CAST -CRETE REINFORCED CONCRETE BEAM LINTELS (OR EQUIVALENT) LINTEL NO. MAX. CLEAR SPAN LINTEL DESCRIPTION COMMENTS L-1 16'-0" 8F48-1 B/1 T PRESTRESSED L-2 -6" 2'-8" 3'-10" L-3 3'-0" 8F48-1B/1T SERVICE DOOR L-4 in 8F24-0B/1T ■ 6'-2" 8F24-1B/1T L-6 14'-0" 8F24-1B/1T PRESTRESSED L-7 cn 8F24-1 B/1 T L-8 3'-4" 8F24-1B/1T FRONT DOOR ■ 2'-0" ■ v 0 ■ m■I L-2 a - N 5'-0" 5'-0" 3'-8" 3'-0" LL®8 6'-8" L-7 T-2" Fx_ 1'-2" ❑C ❑C 0 ■ 0 LO ■ L-7 ti 4'-0" ■ V ■ 5'-2" ■ El ■ ■ 1 Alf = 1' Off - 0 " L9 ;T W J W U co W W 07 BOND BEAM REINFORCEMENT (SEE WALL SECTION) FILL SOLID TO BOND BEAM (1) #5 CONTININUOUS IN PRECAST LINTEL 8FX-1 B/1 T PRECAST LINTEL NOTES: 1. ALL PRECAST LINTELS GREATER THAN 4'-0" ARE TO HAVE ON #5 REBAR AT BOTTOM OF LINTEL 2.AREAS OF BLOCK ABOVE MASONRY OPENINGS ARE TO BE GROUTED SOLID TO TIE BEAM 3. BOND BEAM TO BE CONTINUOUS THROUGH OUT INCLUDING ABOVE MASONRY OPENINGS. SEE TYPICAL WALL SECTION FOR REINFORCEMENT. 4. CONSULT FLOOR PLAN & ELEVATIONS FOR EXACT COURSE COUNT ABOVE LINTEL 5. CONSULT CAST -CRETE INSTALLATION SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 6. UNLESS APPROVED OTHERWISE, ALL LINTELS TO HAVE MIN 4" BEARING AT EACH END. TYPICAL PRECAST LINTEL LINTEL SCHEDULE CAST -CRETE REINFORCED CONCRETE BEAM LINTELS (OR EQUIVALENT) LINTEL NO. MAX. CLEAR SPAN LINTEL DESCRIPTION COMMENTS L-1 16'-0" 8F48-1 B/1 T PRESTRESSED L-2 3'-0" 8F24-1 B/1 T L-3 3'-0" 8F48-1B/1T SERVICE DOOR L-4 5'4" 8F24-0B/1T L-5 6'-2" 8F24-1B/1T L-6 14'-0" 8F24-1B/1T PRESTRESSED L-7 6'-5" 8F24-1 B/1 T L-8 6-1" 8F24-1B/1T FRONT DOOR L-9 2'-0" 8F24-1B/1T I NOTES I FM 1. NO.5 BAR VERTICAL DOWEL REQUIRED, TYP AS SHOWN 2. THIS DESIGN UTILIZES A (1) COURSE BOND BEAM 3.. ALL DIMENSIONS ARE APPROXIMATE, MAX SPACING OF 6'-0" O.C. (UNO) 0 NI C N 0 d' O O N N N M JILL N O d - w Cn I— O U Y Q Z O C0 'q -x0 Z 7w I- a W d U p a Z m 't LL 0 I C Y0 W w Ln UI❑❑z i_-ZUNp_�vu7p ~ Jap p zw_j _jzzD ��ww-_pm�<:1W O W W�> p N W W❑ U Z 0IL W( F -1w C) p� U) p❑ m a z w>- w z H❑ a i W w ❑ z U W Q a-< 0M I W W�� N W� w ❑ U Z a=�N°�F�zWa�. (n F F❑ a❑ p z a❑ Z a p❑ W a z� -❑ W _jp Q I m r�aW I �owpzpowz�noa7-W a w❑ I-❑- z LL W E-0 WPI-Za1-ww IL7 W w w z xaWLL z Wow, aaaFl-pUH10 ww z z w , I} 14 ❑- z a U❑ L7 Q W Z WOaj OQmz_N�Q�z3g�H W �❑�[�w01.- �2aw�U W 1=I°IZ�f-yjzwppljla--� z U a- U0�❑ I W p Z a . ❑ W a I- _j I ❑ J z3Nacna❑�71-?UU J z SHEET NO.: o ST -2.1 Q o MASONRY PLAN a. ry O JOB NO.: AT 1496 ® SUBDIVISION: o Atlantic Beach Q Country Club LOT NO.: z 6 FLOOR PLAN: a Custom O Z DESIGNED: C) DAE/SDA U-1 I•— REVIEWED: w DBM 0- REVISIONS DATE x CC1 d w Z Q w 2 Z AOL E/) PEX STR TURAL ENGINEERING $; s5 E t "4/E B �Yv Hn O „k 1457 a' xz M&,, Fri U w X w 0- Derek B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING ¢ P.E. No. 71457 04-02-2018 HUC210-2 (2) 2x12 11Y4" LVL 3S GIRDER FLOOR GIRDER 2 STUDS 0 0l O DTT J 2 STUDS 0 Luo - 2 STUDS Lu � - II DTT2Z 3S GIRDER FLOOR GIRDER 2 STUDS 0 0l O DTT J FLOOR GIRDER ------------ - 2 STUDS 0 Luo - 2 STUDS 0 0 O PcoJ�.vb �y -- LL FLOOR GIRDER ------------ - 2 STUDS 0 Luo p O � PcoJ�.vb �y J 2 STUDS J ------ FLORGIRDER 2 STUDS HTT4 LL _________ TRUSS GIRDER ------------ 2 STUDS w HTT5 Egli JUMP 0 � & AM 2x1 (2) 11 1/4" L IIII 1 MSTA24 1 HTT4 IIII IIII -- ---- --IIII M2 ST -6 SEE TYPICAL PORCH SHEATHING DETAIL. (2) 11 X" LVL IL====j (2) 11 X" LVL SEE TYPICAL PORCH SHEATHING DETAIL. MSTA24 DTT2Z III IIl IlI III III III IIl III IIl IIl IIl (Il Wlil IIII IIII --SOLID FRAME WITH 2x8 0111 No.2 SPF JACK STUDS 0III III LVL HDR UP, MIN (2) 2x8 LVL HDR UP, MIN (2) 48 JACKS EACH SIDE JACKS EACH SIDE I ----------------------------------------------------- 1 -------- --mo1 MSTA24 I 1 MSTA24 1 MSTA24 1 DTT27 I 1 DTT2Z 1 DTT2Z I I - 3 STUDS O w III 0 DTT2Z , Ir I I III I I III I I I III I I I I I I III I I I I III I I III - 3 STUDS 0 w 0 DTT2Z O III I I III I I I I III I I HUC410 N � HUC410 4x12 4x12 CEDAR i CEDAR GARAGE DOOR DESIGN WIND LOAD (PSF): +20.77/-23.25 4x12 CEDAR 6x6 NO.2 SYP PT POST, TYP (2) TOTAL FRAMING KEYNOTES (METAL CONNECTOR) NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN 1. MIN (2) INTERMEDIATE JACK STUDS REQUIRED BETWEEN OPENINGS. 2. SEE INTERIOR SHEARWALL DETAIL ON DETAIL SHEET. IN LOCATIONS WHERE INTERIOR SHEARWALLS HAVE VAULTED TOP PLATES, ALSO SEE INTERIOR SHEARWALL AT VAULTED TOP PLATE ON DETAIL SHEET. 3. ATTACH SW TO FLOOR DIAPHRAGM PER ONE OF THE FOLLOWING: A. IF FLOOR TRUSS ALIGNS ABOVE SW, ATTACH FLOOR TRUSS BOTTOM CHORD TO SW DBL TOP PLATE W/ 10d @ 3" O.C. B. FRAME AND SHEATH SW TO FLOOR DECK ABOVE. ATTACH FLOOR DECK TO SW DBL TOP PLATE W/ 10d 3" O.C. 4. PORCH BEAM FRAMING NOTES A. BEAM POCKET PORCH BEAMS AT TOP PLT ELEV NOTCH TOP OF BEAM 3" FOR BEAM PKT CONNECTION AT WALL, TOP OF BEAM ELEVATION EQUALS TOP OF TOP PLATE. 6x6 NO.2 SYP PT POST, B. SHIM BELOW PORCH BEAMS JUST ABOVE TOP PLT ELEV TYP (4) TOTAL PORCH BEAM TO TOP PLT W/ MTS12 OR MSTA24. C. POST DOWN PORCE BEAMS ABOVE TOP PLT ELEV PROVIDE DOUBLE STUD POST DOWN SUPPORT AT WALL FOR PORCH BEAMS. BEAM TO POST DOWN STUDS W/ HTS20 OR, MSTA24. POST DOWN STUDS TO STUDS BELOW W/ HTS 20 OR MSTA24. D. BEAM ATTACHED TO EXISTING FRAMING ATTACH PORCH BEAM TO EXISTING STUDS OR KING/JACK STUDS (2) 2x12 W/ SIMPSON HUC HANGER MATCHING PORCH BEAM DIMENSIONS. 5. SHEATH WALL CONTINUOUS TO SECOND FLOOR TOP PLATE PER TYPICAL WALL SECTION SHEET. 6. HIGH UPLIFT CONNECTION: • ROOF LEVEL STUD/HDR TO TOP PLATE W/ (1) SDWC15600 @ 16" O.C. O HUC210-2 . R2F OORCT06FLLOOR CONNECTION, SEE ST -5. PROVIDE "METAL FLAT STRAP 2ND LEVEL STUD TO 1 ST LEVEL STUD" @ 32" O.C. NO ALTERNATIVE AVAILABLE • 1ST LEVEL STUD TO BOTTOM PLATE W/.(1) SDWC15450 @ 16" O.C. OR (2) SDWC15450 @ 24" O.C. 7. PLANK -ORIENTED HEADER FRAMING A. FASTEN PLANK ORIENTED HEADER TO JACK KING GROUP W/ (2) A35 EACH SIDE OF OPENING, SEE PLANK HEADER FRAMING DETAIL, ON DETAIL SHEET. B. FASTEN PLANK ORIENTED HEADER TO JACK/KING GROUP WITH HORIZONTAL HTS16 STRAP EACH SIDE OF OPENING. C. PLANK -ORIENTED HEADER NOT REQUIRED, THIS LOCATION ONLY. STRUCTURAL-PSADIER"HAS BEEN CALCULATED TO RESIST THE OUT OF PLANE WIND LOAD. CIO 8. FASTEN SHEARWALL BOTTOM PLATE W/ 10d @ 3" O.C. C co co O Wilma O N U? ORN co O O d - N N N co LL LU J J_ Z O 07 Y U Q N O �t w I-__ Z) H Q_ 0 Y CK Q Z O H U) x p i Z 2❑ O_ Q ❑ W w m ❑ Z m Qp u] ❑WwQZ u7❑❑? HZUu70W0U� J W (3J a p Z J- m J Z Z C Q w w p m Q a Q❑ w L. O owIo pWJw LL ❑NNop pomEL Z w>WzO Z11❑a� ww�inU1 Zw w QEL L9 LoIwwto w� wF ❑ m Z ¢=�N�����azwaL ❑Q a oFZaz�aZ L.�❑xw�p Qp� M w I w w w m DQ�L)wzwwZw❑Q2w Z Z Q x�❑ p I- ❑- I W❑ z w EwpwxQwz<Fwwa5 Z Z Lj0.az�°-°F-zcri�WZ I} Z Q❑ -- a 0 Q W❑ Z wpa¢mZNEQFz3��Q w ZO�[9WC7] ff]WQ�UU 1-azzF�2nzwQ w1 ---E Z p Q- w a 0 I w p Z Q �nlwZEE 3LvamQot�w?nn J LL z SHEET NO.: o ST -3 I— Q STRUCTURAL PLAP O JOB NO.: Q AT1496 SUBDIVISION: o Atlantic Beach _J LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom O Z DESIGNED: 0 DA E/SDA w 1-- REVIEWED: w DBM 0- < REVISIONS DATE i- Cp w Z O w d Z U) PEX NSTRUCRAL ENGINEERING LL p PcoJ�.vb �y > '1 eAR `S �1{j J Fs w. 1/4°f _ 11 offLLJ X w n- Q Derek B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING P. EA No. 71457 0 N LO N 4'4" yVO- MTS 12 J05 J06 J07 J08 J08 J09 J09 FT01 FT02 (2) META12 OR (2) HTSM20,- SEE NOTE 8 J16 J16 J16 J16 J16 J16 J16 (2) META12 OR (2) HTSM20,- SEE NOTE 8 FT03 (2) META12 OR (2) HTSM20, SEE NOTE 8 FT04 T36 T36 T36 yv r b J11 J12 J14 T38 T39 T40 T41 T40 T39 T42 J14 J12 J11 OHO F01 F01 F01 F01 F04 F04 F04 F04 48' Q Ln (0 1- d Ln tSa C r 1` 1,- 00 00 00 00 00 00 00 00 00 0') O (. Ln [9c O O O r r r r r r r r r r r r r r r r N O O O ,® 2'0"4 1' T CN HM 2x6 NO.2 SYP ROOT FRAMING LEDGER, SEE NOTE 3 2x6 SYP RAFTERS T 16 @ MAX 24" O. -. r NOTE 1 T N r Q r Q Lf) r Q Ln r d Ln r 12d COMMON Q Ln r Q Ln r Ln rj PT 2x6................(3) T- r N r 16d COMMON PT 2x10 ..............(7) 16d COMMON PT 2x12 ..............(9) 16d COMMON - - FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3)'/4' x 4-'/" LONG #14 WOOD SCREWS PT 2x8 ................(5) %" x 4-'/" LONG #14 WOOD SCREWS PT 2x10 ..............(7) '/4' x 4-%" LONG #14 WOOD SCREWS MTS12 '/4' x 4-'/2' LONG #14 WOOD SCREWS • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON Q STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE SUPPORTING STUDS OR UPLIFT CONNECTORS. • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN 0 SUPPORTED RAFTERS. • FASTEN 2x6 NO.2 SYP COLLAR TIES FROM RAFTER TO RAFTER w ♦- WHERE APPLICABLE W/ MIN (6) 10d 11 "4 11„4 1"1"4 • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: U) � I I ---1 I J05 J06 J07 J08 J08 7' 7' — - i (2) META12 OR (2) HTSM20, SEE NOTE 8 ---- I -- LL M O (2) 11 " LVL H R UP J 10 J10 J 10 J10 J10 J10 J10 J10 J10 J 10 J10 10 J10 J10 r N _= z 1' HTS20 ---_- 2'0"4 DO DO N__ _== N o z N 53 (2) HT (2) MS (2) 20 OR A24 1 %4" L (2) 5 (2 S HDR U 0 OR 24 n r O FG04 �HHUS46 V r L-HHUS46 F05J10 (2) HTS20 LHHUS46 1'4" = r ^? (2) LHHUS46 HTS20 CO O (D r N L HHUS46 r HTS20 (2) HTS20 rnJ 0O HTS20 HTS20 N r t`''- O r O �- I� � it NO 10 HTS20 LL M W r N LHHUS46 0,, 2) HTS20 (2) MSTA24 R N N r N �H H U S46 �H H US46 1 �2"8 J10 = J r 1'2"8 L FG05 78 HTU26 T21 J10 N N DO DO DO N r -�-y (0 r "r N _ z N 2'0"4 1' T CN HM 2x6 NO.2 SYP ROOT FRAMING LEDGER, SEE NOTE 3 2x6 SYP RAFTERS T 16 @ MAX 24" O. -. r NOTE 1 T r N Ln In Ln Ln Ln Lt`s r r r ^-^ r r r r r-• r r r -OR • �021i1 23'4” 11 J12 J14 J14 J12 J11 0 9 7- 00 1` (O Ln 'I co co N N r H H H H h H H -7) 2x6 CEDAR RAFTERS @ MAX 24" O.C. • POST DOWN TO 46 CEDAR BEAM W/ HL33 • RIDGE TO POST W/ (2) H8 • POST TO HORIZONTAL BEAM W/ MSTA24 16' . I --17' J11 J12 J13 J13 J13 J12 J11 y�0 s 45r c'> v co N 1/411 = 1 1 Off ROOF FRAMING KEYNOTES NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN 1. PRE -MANUFACTURED SHEAR PANEL • INSTALL AS SHOWN ON LAYOUT ABOVE SW SPECIFIED ON FRAMING PLAN • SHEAR PANEL TO SW DBL TOP PLT W/ 10d @ 3" O.C. • FLOOR DECK TO SHEAR PANEL W/ 10d @ 3" O.C. • NOTE: IF PRE -MANUFACTURED SHEAR PANELS ARE NOT PROVIDED BY TRUSS MANUFACTURER, SEE "ELEVATION OF BOX -FRAME OVER SW' DETAIL, SEE DETAIL SHEET 2. TYPICAL BEARING BLOCK • BEARING BLOCK TO BE NO.2 SYP, MIN 48" LONG AND TO MATCH DIMENSION OF TRUSS MEMBER. • ATTACH BEARING BLOCK TO TRUSS VERTICAL OR TRUSS BOTTOM CHORD W/ (3) ROWS 10d @ 4" O.C. STAGGERED. 3. LEDGER FRAMING NOTES: • FASTEN LEDGER TO FRAMING/TRUSS VERTICALS AT EVERY SUPPORT WITH FASTENING SHOWN BELOW (MAX 24" O.C. SPACING) • ADDITIONAL FASTENERS MAY BE REQUIRED AT SPECIFIED LOCATIONS ON PLAN • SEE TABLE 5 ON S'-1EET ST -1/S1 FOR FASTENER PROTECTION AGAINST CORROSION • IN ACCORDANCE W/ FRC 507.2.1, EXTERIOR DECK LEDGERS SHALL BE SECURE TO WALL FRAMING WITH WOOD SCREWS AS INDICATED ABOVE. COMMON NAILS AT FLOOR FRAMING LEDGERS ARE FOR INTERIOR USE ONLY. ROOF FRAMING LEDGER: N r Q r Q Lf) r Q Ln r d Ln r 12d COMMON Q Ln r Q Ln r Ln rj PT 2x6................(3) T- r N r 16d COMMON PT 2x10 ..............(7) 16d COMMON PT 2x12 ..............(9) 16d COMMON - - FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3)'/4' x 4-'/" LONG #14 WOOD SCREWS PT 2x8 ................(5) %" x 4-'/" LONG #14 WOOD SCREWS PT 2x10 ..............(7) '/4' x 4-%" LONG #14 WOOD SCREWS PT 2x12 ..............(9) '/4' x 4-'/2' LONG #14 WOOD SCREWS • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON Q STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE SUPPORTING STUDS OR UPLIFT CONNECTORS. • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN 0 SUPPORTED RAFTERS. • FASTEN 2x6 NO.2 SYP COLLAR TIES FROM RAFTER TO RAFTER w ♦- WHERE APPLICABLE W/ MIN (6) 10d 11 "4 11„4 1"1"4 • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: U) � I I r N Ln In Ln Ln Ln Lt`s r r r ^-^ r r r r r-• r r r -OR • �021i1 23'4” 11 J12 J14 J14 J12 J11 0 9 7- 00 1` (O Ln 'I co co N N r H H H H h H H -7) 2x6 CEDAR RAFTERS @ MAX 24" O.C. • POST DOWN TO 46 CEDAR BEAM W/ HL33 • RIDGE TO POST W/ (2) H8 • POST TO HORIZONTAL BEAM W/ MSTA24 16' . I --17' J11 J12 J13 J13 J13 J12 J11 y�0 s 45r c'> v co N 1/411 = 1 1 Off ROOF FRAMING KEYNOTES NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN 1. PRE -MANUFACTURED SHEAR PANEL • INSTALL AS SHOWN ON LAYOUT ABOVE SW SPECIFIED ON FRAMING PLAN • SHEAR PANEL TO SW DBL TOP PLT W/ 10d @ 3" O.C. • FLOOR DECK TO SHEAR PANEL W/ 10d @ 3" O.C. • NOTE: IF PRE -MANUFACTURED SHEAR PANELS ARE NOT PROVIDED BY TRUSS MANUFACTURER, SEE "ELEVATION OF BOX -FRAME OVER SW' DETAIL, SEE DETAIL SHEET 2. TYPICAL BEARING BLOCK • BEARING BLOCK TO BE NO.2 SYP, MIN 48" LONG AND TO MATCH DIMENSION OF TRUSS MEMBER. • ATTACH BEARING BLOCK TO TRUSS VERTICAL OR TRUSS BOTTOM CHORD W/ (3) ROWS 10d @ 4" O.C. STAGGERED. 3. LEDGER FRAMING NOTES: • FASTEN LEDGER TO FRAMING/TRUSS VERTICALS AT EVERY SUPPORT WITH FASTENING SHOWN BELOW (MAX 24" O.C. SPACING) • ADDITIONAL FASTENERS MAY BE REQUIRED AT SPECIFIED LOCATIONS ON PLAN • SEE TABLE 5 ON S'-1EET ST -1/S1 FOR FASTENER PROTECTION AGAINST CORROSION • IN ACCORDANCE W/ FRC 507.2.1, EXTERIOR DECK LEDGERS SHALL BE SECURE TO WALL FRAMING WITH WOOD SCREWS AS INDICATED ABOVE. COMMON NAILS AT FLOOR FRAMING LEDGERS ARE FOR INTERIOR USE ONLY. ROOF FRAMING LEDGER: 2x6 ....................(4) 12d COk'MON 2x8 ....................(6) 12d COMMON 2x10 ..................(8) 12d COMMON 2x12 ..................(10) 12d COMMON FLOOR FRAMING LEDGER (W/ NAILS): PT 2x6................(3) 16d COMMON PT 2x8 ................(5) 16d COMMON PT 2x10 ..............(7) 16d COMMON PT 2x12 ..............(9) 16d COMMON - - FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3)'/4' x 4-'/" LONG #14 WOOD SCREWS PT 2x8 ................(5) %" x 4-'/" LONG #14 WOOD SCREWS PT 2x10 ..............(7) '/4' x 4-%" LONG #14 WOOD SCREWS PT 2x12 ..............(9) '/4' x 4-'/2' LONG #14 WOOD SCREWS 4. OVERFRAMING NOTES RAFTER SPAN SCHEDULE • ALL RAFTERS TO BE MIN. 2x6 NO.2 SYP @ 24" O.C. MAX. O.C. SPACING • ALL "SLEEPERS" TO BE PLANK -ORIENTED 2x8 NO.2 SYP MIN. • FASTEN "SLEEPERS" TO EACH TRUSS/RAFTER W/ (3) 16d 2x6 COMMONS MIN. 2x12 • EACH RAFTER TO "SLEEPER" W/ SIMPSON H3 UPLIFT 14'-5" CONNECTOR. 25'-6" •ALL RIDGE BOARDS TO BE 2x8 N0.2 SYP MIN. co • FASTEN 2x6 NO.2 SYP COLLAR TIES FROM RAFTER TO 22'-1" RAFTER WHERE APPLICABLE W/ (5) 10d COMMONS MIN. 10'-2" LMM co >111%CIOo N LO N 00 4 0 O O N N N U) co J RAFTER SPAN SCHEDULE O.C. SPACING LUMBER SIZE BUILDER IN ACCORDANCE WITH FRC R302.12. 2x6 2x8 2x10 2x12 12" 14'-5" 18'-3" 21'-8" 25'-6" 16" 12'-6" 15'-10" 18'-9" 22'-1" 24" 10'-2" 12'-11" 164" 18'-0" U 20 L.L./15 D. L. #2 SYP • ALL MEMBERS TO BE NO.2 SYP UNLESS NOTED OTHERWISE. LMM co >111%CIOo N LO N 00 4 0 O O N N N U) co J CEILING JOIST SPAN SCHEDULE O.C. SPACING LUMBER SIZE BUILDER IN ACCORDANCE WITH FRC R302.12. 2x4 2x6 2x8 2x10 12" 11'-10" 18'-8" 24'-7" 26-0" 16" 10'-9" 16-11" 21'-7" 25'-7" 24" 9'-3" 13'-11" 17'-7" 20'-11" U 10 L.L./5 D.L. #2 SYP • ALL MEMBERS TO BE NO.2 SYP UNLESS NOTED OTHERWISE. LMM co >111%CIOo N LO N 00 4 0 O O N N N U) co J RAFTERS 2x6 RAFTERS: (1) H2.5T TO TOP PLATE, (6) 12d COMMON TOENAILS TO RIDGENALLEY. 0 2x8 RAFTERS: (1) H2.5T TO TOP PLATE, (8) 12d COMMON (� TOENAILS TO RIDGENALLEY. 2x10 RAFTERS: (1) H2.5T TO TOP PLATE, (10) 12d COMMON Of TOENAILS TO RIDGENALLEY. a CEILING JOISTS z 2x JOIST: (3) 10d COMMON TOENAILS TO TOP 0 PLT/RAFTERS. ~ F- TJI CLG. JOIST: (3) 10d COMMON TOENAILS TO TOP PLATE/RAFTERS, 07 7. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS BELOW WALL I- w w Z 0 o ABOVE d aw o aza�ui • ATTACH BLOCKING TO TRUSSES W/ (4) 10d TOE -NAILS EACH END � Q p = n Y www p w Ui ❑❑Z FZUUlQw0Mw 8. IF USING (2) HTSM20, INSTALL (1) STRAP ON EACH FACE GF WALL. I` w } a w Z w D m Z Z ❑ (2) HTSM20 ON SAME SIDE OF WALL IS NOT PERMITTED AT THIS a WW - w m a m a ❑ W W LOCATION. waw❑ wwwww❑wwo� ❑ma FBF- }WZF❑ 9. • POST DOWN RIDGE BEAM TO MASONRY BELOW W/ (1) JACK/ (2) KING U) w a} w W FW J m ❑ Z U • RIDGE BEAM TO POST W/ (2) H8 91 U3 z a w o N❑ w I I w❑ z W • POST TO MASONRY W/ MSTAM24 (� � � ❑ a 0 a o Z a w z - ❑ a ZZWw- X w 10.• 2x10x12'-7" LONG NO.2 SYP SCAB TO TRUSS TOP CHORD W/ (2) ROWS w w w a I w ❑ w w a w 10d 6" O.C. STAGGERED. MINIMUM 3' LONG SPLICE, 5 TOTAL m 0 a w L3 U Z w w Z w a g w @ ( ) a W❑ I-❑ - Z • NARROW FACE OF SCAB TO (2) 2x8 NO.2 SYP POST W/ MSTA24 W i - w w z a F w m � 0 • (2) 2x8 NO.2 SYP POST TO SILL PLATE W/ H3 OR MSTAM24 w w w Q _ W w 1-1 p 4 ❑ N ' w w z Zw WaaZZJnnIwo 11.• (2) 2x8 SYP BLOCKING BETWEEN RAFTERS/ TRUSS TOP CHORD'S I } z< ❑ - _ a a •TOE NAILS EBLOCKING ACH ENDO RAFTERS/ TRUSS TOP CHORD'S W/ (4) 10d z w w D Q m Z N w a F z�� Q w Z❑ 2 - w:j0 I_ m w a a � U 0 2:I-IZI=Yz zw FOwW Z U a- U a❑ I W w Z a 0f- 3N a W a OC7 F? U J LL. SHEET NO.: o ST -3A ROOF FRAMING 0 PLAN 0 JOB NO.: Q AT 1496 SUBDIVISION: o Atlantic Beach LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom 0 Z DESIGNED: wDAE/SDA F- REVIEWED: DBM Q REVISIONS DATE m 0 w z 0 w z 07 Z) EX ry ASTRUENGINEERING OFFICE Cu"PY w Q _0 TRUSS ENGINEERINGNOTES: • UNLESS SPECIFICALLY NOTED ON TRUSS FRAMING PLAN, ALL o TRUSS TO TOP PLATE CONNECTIONS SHALL BE ACCORDING = TO THE TYPICAL WALL SECTION SHEET. v w • ALL EXTERIOR WALLS ARE HELD BACK 1/2" FOR SHEATHING. 17- X w a- Derek B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING Q P.E. N0.71457 LL 5. DRAFT STOPPING AT FLOOR TRUSSES TO BE PROVIDED BY LLl BUILDER IN ACCORDANCE WITH FRC R302.12. J J 6. CONVENTIONAL FRAMING NOTES • SEE "OVERFRAMING NOTES" ON ROOF FRAMING PLAN FOR z SPAN CHARTS AND ADDITIONAL NOTES. SPAN CHARTS MAY BE 0 USED FOR MEMBER SIZING UNLESS SIZE IS NOTED ON PLAN. U • ALL MEMBERS TO BE NO.2 SYP UNLESS NOTED OTHERWISE. U • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON Q STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE SUPPORTING STUDS OR UPLIFT CONNECTORS. • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN 0 SUPPORTED RAFTERS. • FASTEN 2x6 NO.2 SYP COLLAR TIES FROM RAFTER TO RAFTER w ♦- WHERE APPLICABLE W/ MIN (6) 10d • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: U) RAFTERS 2x6 RAFTERS: (1) H2.5T TO TOP PLATE, (6) 12d COMMON TOENAILS TO RIDGENALLEY. 0 2x8 RAFTERS: (1) H2.5T TO TOP PLATE, (8) 12d COMMON (� TOENAILS TO RIDGENALLEY. 2x10 RAFTERS: (1) H2.5T TO TOP PLATE, (10) 12d COMMON Of TOENAILS TO RIDGENALLEY. a CEILING JOISTS z 2x JOIST: (3) 10d COMMON TOENAILS TO TOP 0 PLT/RAFTERS. ~ F- TJI CLG. JOIST: (3) 10d COMMON TOENAILS TO TOP PLATE/RAFTERS, 07 7. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS BELOW WALL I- w w Z 0 o ABOVE d aw o aza�ui • ATTACH BLOCKING TO TRUSSES W/ (4) 10d TOE -NAILS EACH END � Q p = n Y www p w Ui ❑❑Z FZUUlQw0Mw 8. IF USING (2) HTSM20, INSTALL (1) STRAP ON EACH FACE GF WALL. I` w } a w Z w D m Z Z ❑ (2) HTSM20 ON SAME SIDE OF WALL IS NOT PERMITTED AT THIS a WW - w m a m a ❑ W W LOCATION. waw❑ wwwww❑wwo� ❑ma FBF- }WZF❑ 9. • POST DOWN RIDGE BEAM TO MASONRY BELOW W/ (1) JACK/ (2) KING U) w a} w W FW J m ❑ Z U • RIDGE BEAM TO POST W/ (2) H8 91 U3 z a w o N❑ w I I w❑ z W • POST TO MASONRY W/ MSTAM24 (� � � ❑ a 0 a o Z a w z - ❑ a ZZWw- X w 10.• 2x10x12'-7" LONG NO.2 SYP SCAB TO TRUSS TOP CHORD W/ (2) ROWS w w w a I w ❑ w w a w 10d 6" O.C. STAGGERED. MINIMUM 3' LONG SPLICE, 5 TOTAL m 0 a w L3 U Z w w Z w a g w @ ( ) a W❑ I-❑ - Z • NARROW FACE OF SCAB TO (2) 2x8 NO.2 SYP POST W/ MSTA24 W i - w w z a F w m � 0 • (2) 2x8 NO.2 SYP POST TO SILL PLATE W/ H3 OR MSTAM24 w w w Q _ W w 1-1 p 4 ❑ N ' w w z Zw WaaZZJnnIwo 11.• (2) 2x8 SYP BLOCKING BETWEEN RAFTERS/ TRUSS TOP CHORD'S I } z< ❑ - _ a a •TOE NAILS EBLOCKING ACH ENDO RAFTERS/ TRUSS TOP CHORD'S W/ (4) 10d z w w D Q m Z N w a F z�� Q w Z❑ 2 - w:j0 I_ m w a a � U 0 2:I-IZI=Yz zw FOwW Z U a- U a❑ I W w Z a 0f- 3N a W a OC7 F? U J LL. SHEET NO.: o ST -3A ROOF FRAMING 0 PLAN 0 JOB NO.: Q AT 1496 SUBDIVISION: o Atlantic Beach LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom 0 Z DESIGNED: wDAE/SDA F- REVIEWED: DBM Q REVISIONS DATE m 0 w z 0 w z 07 Z) EX ry ASTRUENGINEERING OFFICE Cu"PY w Q _0 TRUSS ENGINEERINGNOTES: • UNLESS SPECIFICALLY NOTED ON TRUSS FRAMING PLAN, ALL o TRUSS TO TOP PLATE CONNECTIONS SHALL BE ACCORDING = TO THE TYPICAL WALL SECTION SHEET. v w • ALL EXTERIOR WALLS ARE HELD BACK 1/2" FOR SHEATHING. 17- X w a- Derek B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING Q P.E. N0.71457 - 2 STUDS C J) 0 F- - CS18 MSTA24 SW3 NOTE 8 (2) 2x6-1/2 NOTE 1 (2) 2x6-1/2 1 11 1 (2) 2x6-1/2 STUD MSTAM3 0 wI 2 CS18S _====JIL=== ROOFGIRDER___________ (2) 2x6-1/2 NOTE 1 2 STUDS111- 0 MSTAM34112 (2) 2x6-1/2 SW2 NOTE 2, 8 DRAGLOADE TRUSS ROOF GIRDER— — — — (2) 2x12 x 11'-10" CONTINUOUS HEADER P2 ***SPECIAL FRAMING*** ST -6 PORTAL FRAME ***NOTE TO FRAMER*** DO NOT FLITCH BETWEEN PLIES OF (2) 2x12 HEADER, FUR OUT AT INTERIOR FACE OF WALL. NO ALTERNATIVE AVAILABLE. 2 STUDS 0 'cooI CS18 0 ____ 2 2 STUDS 0O --------- CS18 ry MBALLOON FRAME ABOVE ST -6 PER "M2" DETAIL 1 /4"= 11 Oto A FRAMING KEYNOTES (METAL CONNECTOR) NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN 1. MIN (2) INTERMEDIATE JACK STUDS REQUIRED BETWEEN OPENINGS. 2. SEE INTERIOR SHEARWALL DETAIL ON DETAIL SHEET. IN LOCATIONS WHERE INTERIOR SHEARWALLS HAVE VAULTED TOP PLATES, ALSO SEE INTERIOR SHEARWALL AT VAULTED TOP PLATE ON DETAIL SHEET. 3. ATTACH SW TO FLOOR DIAPHRAGM PER ONE OF THE FOLLOWING: A. IF FLOOR TRUSS ALIGNS ABOVE SW, ATTACH FLOOR TRUSS BOTTOM CHORD TO SW DBL TOP PLATE W/ 10d @ 3" O.C. B. FRAME AND SHEATH SW TO FLOOR DECK ABOVE. ATTACH FLOOR DECK TO SW DBL TOP PLATE W/ 10d 3" O.C. 4. PORCH BEAM FRAMING NOTES A. BEAM POCKET PORCH BEAMS AT TOP PLT ELEV NOTCH TOP OF BEAM 3" FOR BEAM PKT CONNECTION AT WALL. TOP OF BEAM ELEVATION EQUALS TOP OF TOP PLATE. B. SHIM BELOW PORCH BEAMS JUST ABOVE TOP PLT ELEV PORCH BEAM TO TOP PLT W/ MTS12 OR MSTA24. C. POST DOWN PORCH BEAMS ABOVE TOP PLT ELEV PROVIDE DOUBLE STUD POST DOWN SUPPORT AT WALL. FOR U 6 PORCH BEAMS. BEAM TO POST DOWN STUDS W/ HTS20 OR, MSTA24. POST DOWN STUDS TO STUDS BELOW W/ HTS20 OR MSTA24. D. BEAM ATTACHED TO EXISTING FRAMING ATTACH PORCH BEAM TO EXISTING STUDS OR KINGMACK STUDS W/ SIMPSON HUC HANGER MATCHING PORCH BEAM DIMENSIONS. 5. SHEATH WALL CONTINUOUS TO SECOND FLOOR TOP PLATE PER TYPICAL 00 0 WALL SECTION SHEET. 6. HIGH UPLIFT CONNECTION: • ROOF LEVEL STUD/HDR TO TOP PLATE W/ (1) SDWC15600 @ 16" O.C. .. OR (2) SDWC15600 @ 24" O.C. • FOR FLOOR -TO -FLOOR CONNECTION, SEE ST -5. PROVIDE "METAL Z FLAT STRAP 2ND LEVEL STUD TO 1ST LEVEL STUD" @ 32" O.C. NO . -... ALTERNATIVE AVAILABLE Cn • 1ST LEVEL STUD TO BOTTOM PLATE W/ (1) SDWC15450 @ 16" O.C. OR (2) SDWC15450 @ 24" O.C. 7. PLANK -ORIENTED HEADER FRAMING A. FASTEN PLANK ORIENTED HEADER TO JACK KING GROUP W/ (2) A35 U EACH SIDE OF OPENING, SEE PLANK HEADER FRAMING DETAIL, ON DETAIL SHEET. W B. FASTEN PLANK ORIENTED HEADER TO JACK/KING GROUP WITH HORIZONTAL HTS16 STRAP EACH SIDE OF OPENING. F- C. PLANK -ORIENTED HEADER NOT REQUIRED, THIS LOCATION ONLY. STRUCTURAL HEADER HAS BEEN CALCULATED TO RESIST THE OUT X OF PLANE WIND LOAD. 8. FASTEN SHEARWALL BOTTOM PLATE W/ 10d @ 3" O.C. C: co >*1 CIO CMU/METAL CONNECTOR ENGINEERING ■ a 0 NI U? N O O O N N N co N O NT W F- U) F- 0 U Y Q D_ Z O F- x 0 Y I� wW z 2 0 IL a ❑ � U ❑ Z a X N �1 3 Ul p I U Y i p w w L0 N❑❑ z � Z U to p W U to I QFww ?o_mQ�Q�wo ww O WW p[l1WW°NM z ❑ ww� -p ppm11� I-1Ktp>-wz� 0 U) pa a}wWFw_jm❑Z❑ WQ �at7uiIwWNI 5ww z ¢wFN❑Iw❑zU I❑¢ a� I -a w C/) �C/)Q� zF- zwLZLXp - p° pwWa2� ❑wwpaO� M c�aawWz°w°wzcnoa�w � z ax °C, Cl❑z W EE-nLj z < F w LLEbjwt� W w x Q U 1xw z� p U❑N w W z zw wII�z: �-zN1- z I>-zQ0--aU13[7¢wL9 LD ❑ Z zp❑¢mzNMQF-Z3zIa ww� a ¢ W Wz❑�❑wLg •tnwaWn- 0 IzFFYjzwppWla -- z U¢- U❑ I w p z¢ E ❑ wa J F- I ❑J O Ll F-z3Na.U)40 71-?UU i LL z SHEET NO.: o ST -4 F - Q STRUCTURAL PLAN O JOB NO.: Q AT1496 SUBDIVISION: o Atlantic Beach J Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom O Z DESIGNED: C) DAE/SDA LLI F- REVIEWED: LU DBM Q REVISIONS DATE i - CD W z O W 2 Q® Z U) LJ STRU(S\TURAL ENGINEERING U 6 00 0 .. Z ..�. . -... U W F- X W D_ Derek B. Murray, P.E. CMU/METAL CONNECTOR ENGINEERING P.E,No. 71457 T03 T04 T04 T04 T04 Cn T04 T04 T03 0 T02 2x6... ................. 310" 2x8 ....................(6) 12d COMMON 12'4" 12d COMMON --I 42" -I 12d COMMON FLOOR FRAMING LEDGER (W/ NAILS): MTS CO 12 PT 2x8 ................(5) B4 M S12� T05 16d COMMON FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3) %" x 4-'/2' LONG #14 WOOD SCREWS ST -6 %a" x 4'/z" LONG #14 WOOD SCREWS PT 2x10 ..............(7)'/4' x 4-Y2' LONG #14 WOOD SCREWS `° VO STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE (N C14 O� • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN J03 O O O O O O w ~ WHERE APPLICABLE W/ MIN (6) 10d U) • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: LLUST 1 S26, tiVO J01 r F- co E - o r i I _ .o . io i� d' d_. d I� ++ IL J01 2'4 L 10 �N Io �N p� , O 71L r LU T06 J03 L o J o rLUS26 T 7 LUS26, bo MT 12 CO `"' --- ) O M S12 T01 CD (N N N N O O O O T- f O /X QJ _ _ B4 f i T02 T03 T04 T04 T04 T04 Cn T04 T04 T03 0 T02 2x6... ................. (4) 12d COMMON 2x8 ....................(6) 12d COMMON 2x10 ..................(8) 12d COMMON - 12d COMMON FLOOR FRAMING LEDGER (W/ NAILS): MTS CO 12 PT 2x8 ................(5) 16d COMMON M S12� T05 16d COMMON FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3) %" x 4-'/2' LONG #14 WOOD SCREWS PT 2x8 ................(5) %a" x 4'/z" LONG #14 WOOD SCREWS PT 2x10 ..............(7)'/4' x 4-Y2' LONG #14 WOOD SCREWS `° %a" x 4-'/z" LONG #14 WOOD SCREWS STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE LLUS26 SUPPORTING STUDS OR UPLIFT CONNECTORS. T 0 LUS26, • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN J03 SUPPORTED RAFTERS. 'I NN • FASTEN 2x6 N0.2 SYP COLLAR TIES FROM RAFTER TO RAFTER w ~ WHERE APPLICABLE W/ MIN (6) 10d U) • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: LLUST 1 S26, J01 r F- co E - r i I _ .o . io d_. d I� IL 2'4 71L o o --- ) CD (N N N N O O O O T- f O /X QJ B4 f i ST -6 4'2" 12' 4'2" J01 J03 J03 LO J01 1/411 = 11 0" ROOF FRAMING KEYNOTES NOTES APPLICABLE ONLY WHERE SPECIFIED ON PLAN 1. PRE -MANUFACTURED SHEAR PANEL • INSTALL AS SHOWN ON LAYOUT ABOVE SW SPECIFIED ON FRAMING PLAN • SHEAR PANEL TO SW DBL TOP PLT W/ 10d @ 3" O.C. • FLOOR DECK TO SHEAR PANEL W/ 10d @ 3" O.C. • NOTE: IF PRE -MANUFACTURED SHEAR PANELS ARE NOT PROVIDED BY TRUSS MANUFACTURER, SEE "ELEVATION OF BOX -FRAME OVER SW" DETAIL, SEE DETAIL SHEET 2. TYPICAL BEARING BLOCK • BEARING BLOCK TO BE NO.2 SYP, MIN 48" LONG AND TO MATCH DIMENSION OF TRUSS MEMBER. • ATTACH BEARING BLOCK TO TRUSS VERTICAL OR TRUSS BOTTOM CHORD W/ (3) ROWS 10d @ 4" O.C. STAGGERED. 3. LEDGER FRAMING NOTES: • FASTEN LEDGER TO FRAMING/TRUSS VERTICALS AT EVERY SUPPORT WITH FASTENING SHOWN BELOW (MAX 24" O.C. SPACING) • ADDITIONAL FASTENERS MAY BE REQUIRED AT SPECIFIED LOCATIONS ON PLAN • SEE TABLE 5 ON SHEET ST -1/S1 FOR FASTENER PROTECTION AGAINST CORROSION • IN ACCORDANCE W/ FRC 507.2.1, EXTERIOR DECK LEDGERS SHALL BE SECURE TO WALL FRAMING WITH WOOD SCREWS AS INDICATED ABOVE. COMMON NAILS AT FLOOR FRAMING LEDGERS ARE FOR INTERIOR USE ONLY. ROOF FRAMING LEDGER: 2x6... ................. (4) 12d COMMON 2x8 ....................(6) 12d COMMON 2x10 ..................(8) 12d COMMON 2x12 ..................(10) 12d COMMON FLOOR FRAMING LEDGER (W/ NAILS): PT 2x6 ................(3) 16d COMMON PT 2x8 ................(5) 16d COMMON PT 2x10 ..............(7) 16d COMMON PT 2x12 .............(9) 16d COMMON FLOOR FRAMING LEDGER (W/ SCREWS): PT 2x6 ................(3) %" x 4-'/2' LONG #14 WOOD SCREWS PT 2x8 ................(5) %a" x 4'/z" LONG #14 WOOD SCREWS PT 2x10 ..............(7)'/4' x 4-Y2' LONG #14 WOOD SCREWS PT 2x12 ..............(9) %a" x 4-'/z" LONG #14 WOOD SCREWS 4. OVERFRAMING NOTES • ALL RAFTERS TO BE MIN. 2x6 NO.2 SYP @ 24" O.C. MAX. • ALL "SLEEPERS" TO BE PLANK -ORIENTED 2x8 NO.2 SYP MIN. • FASTEN "SLEEPERS" TO EACH TRUSS/RAFTER W/ (3) 16d COMMONS MIN. • EACH RAFTER TO "SLEEPER" W/ SIMPSON H3 UPLIFT CONNECTOR. • ALL RIDGE BOARDS TO BE 2x8 NO.2 SYP MIN. • FASTEN 2x6 NO.2 SYP COLLAR TIES FROM RAFTER TO RAFTER WHERE APPLICABLE W/ (5) 10d COMMONS MIN. 1 1 • 1 1 O d O CIO U) 07 �t N N co J RAFTER SPAN SCHEDULE O.C. SPACING LUMBER SIZE BUILDER IN ACCORDANCE WITH FRC R302.12. 2x6 2x8 2x10 2x12 12" 14'-5" 18'-3" 21'-8" 25'-6" 16" 12'-6" 15-10" 18'-9" 22'-1" 24" 10'-2" 12'-11" 15'-4" 18'-0" U 20 L.L.115 D.L. #2 SYP • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON 1 1 • 1 1 O d O CIO U) 07 �t N N co J CEILING JOIST SPAN SCHEDULE O.C. SPACING LUMBER SIZE BUILDER IN ACCORDANCE WITH FRC R302.12. 2x4 2x6 2x8 2x10 12" 11'-10" 18'-8" 24'-7" 26-0" 16" 10'-9" 16-11" 21'-7" 25'-7" 24" 9'-3" 13'-11" 1T-7" 20'-11" U 10 L.L./5 D.L. #2 SYP • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON 1 1 • 1 1 O d O CIO U) 07 �t N N co J RAFTERS F_ 2x6 RAFTERS: (1) H2.5T TO TOP PLATE, (6) 12d COMMON TOENAILS TO RIDGENALLEY. 2x8 RAFTERS: (1) H2.5T TO TOP PLATE, (8) 12d COMMON U TOENAILS TO RIDGENALLEY. Y 2x10 RAFTERS: (1) H2.5T TO TOP PLATE, (10) 12d COMMON ry TOENAILS TO RIDGENALLEY. Q IL CEILING JOISTS Z 2x JOIST: (3) 10d COMMON TOENAILS TO TOP 0 PLT/RAFTERS. I— TJI CLG. JOIST: (3) 10d COMMON TOENAILS TO TOP D PLATE/RAFTERS. U) LO 7. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS BELOW WALL r w Uj Z ❑ ABOVEd ar, ❑ QZ0�ui LO • ATTACH BLOCKING TO TRUSSES W/ (4) 10d TOE -NAILS EACH END Q p w Y o W W w p LO U10❑Z HZUUpw00 >. a 8. IF USING (2) HTSM20, INSTALL (1) STRAP ON EACH FACE OF WALL. I` p Z w 0 :� m J Z Z 0 (2) HTSM20 ON SAME SIDE OF WALL IS NOT PERMITTED AT THIS Q � w w - p m ¢ a Q ❑ w w LOCATION. DWWO �w�owNNo� 11� I -R IW 9 *POST UTS OWN RIDGE BEAM TO MASONRY BELOW W/ (1) JACK/ (2) KING W 0"' o ¢ - uZZ r w w N m w o •RIDGE BEAM TO POST W/ (2) H8 z Q w F rn ❑ w� I I w❑ z U • POST TO MASONRY W/ MSTAM24 U) � ❑ 4 p a 0 Z L a a o 10. • 2x6x12'-7" LONG NO.2 SYP SCAB TO TRUSS TOP CHORD W/ (2) ROWS m ) w W w I � p p D w p Q w 10d 6" O.C. STAGGERED. MINIMUM 3' LONG SPLICE, 5 TOTAL ED Q T U U Z w w z w 0 Q w • NARROW FACE OF SCAB TO (2) 2x4 N0.2 SYP POST W/(MSTA24 W z p w I'Q F w N L` a E • (2) 2x4 NO.2 SYP POST TO SILL PLATE W/ H3 OR MSTAM24 w w w z w < w O n ❑ m -w w 11. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS AND TOP OF z z I } Z Q 0 z ? a 13 ❑ L9< W o • ATTACH BLOCKING TO TRUSSES/ POSTS W/ 4 10d TOE -NAILS EACH POSTS z w w D Q m z m a Q H z 3� r Q ( ) w Z❑2t�wLID mwdEUU END n ��IzZ1YZZwr]pWh� Z U Q E U D I w p Z Q ❑W •<I -JI- -10_j O QUI- 3NMw<0M -?U0 J LL SHEET NO.: o ST -4A o ROOF FRAMING PLAN O JOB NO.: a AT1496 SUBDIVISION: o Atlantic Beach Country Club Q LOT NO.: z 6 FLOOR PLAN: j Custom O Z DESIGNED: DAE/SDA w I- REVIEWED: w DBM Q REVISIONS DATE m W Z 'S O w Q Z EX Cf) FIC Y STRUC RAL ENGINEERING TRUSS ENGINEERING NOTES: "�ndA LL IV • UNLESS SPECIFICALLY NOTED ON TRUSS FRAMING PLAN, AL TRUSS TO TOP PLATE CONNECTIONS SHALL BE ACCORDING TO THE TYPICAL WALL SECTION SHEET. • ALL EXTERIOR WALLS ARE HELD BACK 1/2" FOR SHEATHING. o -& • TRUSS T04 HAS BEEN DESIGNED TO ACCOUNT FOR DRAG s 3 y LOADS. v w I— x w M Derek B. Murray, P.E. CMCJ/METAL CONNECTOR ENGINEERING d P.E. N°.71457 U_ 5. DRAFT STOPPING AT FLOOR TRUSSES TO BE PROVIDED BY BUILDER IN ACCORDANCE WITH FRC R302.12. LLI J 6. CONVENTIONAL FRAMING NOTES J • SEE "OVERFRAMING NOTES" ON ROOF FRAMING PLAN FOR z SPAN CHARTS AND ADDITIONAL NOTES. SPAN CHARTS MAY BE O USED FOR MEMBER SIZING UNLESS SIZE IS NOTED ON PLAN. U) • ALL MEMBERS TO BE N0.2 SYP UNLESS NOTED OTHERWISE. U • ALL UNSPECIFIED RIDGES ARE CONSIDERED NON Q STRUCTURAL RIDGE BOARDS AND DO NOT REQUIRE SUPPORTING STUDS OR UPLIFT CONNECTORS. • ALL RIDGES BOARDS TO BE ONE SIZE LARGER THAN O SUPPORTED RAFTERS. 'I • FASTEN 2x6 N0.2 SYP COLLAR TIES FROM RAFTER TO RAFTER w ~ WHERE APPLICABLE W/ MIN (6) 10d U) • REQUIRED MEMBER CONNECTIONS ARE AS FOLLOWS: RAFTERS F_ 2x6 RAFTERS: (1) H2.5T TO TOP PLATE, (6) 12d COMMON TOENAILS TO RIDGENALLEY. 2x8 RAFTERS: (1) H2.5T TO TOP PLATE, (8) 12d COMMON U TOENAILS TO RIDGENALLEY. Y 2x10 RAFTERS: (1) H2.5T TO TOP PLATE, (10) 12d COMMON ry TOENAILS TO RIDGENALLEY. Q IL CEILING JOISTS Z 2x JOIST: (3) 10d COMMON TOENAILS TO TOP 0 PLT/RAFTERS. I— TJI CLG. JOIST: (3) 10d COMMON TOENAILS TO TOP D PLATE/RAFTERS. U) LO 7. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS BELOW WALL r w Uj Z ❑ ABOVEd ar, ❑ QZ0�ui LO • ATTACH BLOCKING TO TRUSSES W/ (4) 10d TOE -NAILS EACH END Q p w Y o W W w p LO U10❑Z HZUUpw00 >. a 8. IF USING (2) HTSM20, INSTALL (1) STRAP ON EACH FACE OF WALL. I` p Z w 0 :� m J Z Z 0 (2) HTSM20 ON SAME SIDE OF WALL IS NOT PERMITTED AT THIS Q � w w - p m ¢ a Q ❑ w w LOCATION. DWWO �w�owNNo� 11� I -R IW 9 *POST UTS OWN RIDGE BEAM TO MASONRY BELOW W/ (1) JACK/ (2) KING W 0"' o ¢ - uZZ r w w N m w o •RIDGE BEAM TO POST W/ (2) H8 z Q w F rn ❑ w� I I w❑ z U • POST TO MASONRY W/ MSTAM24 U) � ❑ 4 p a 0 Z L a a o 10. • 2x6x12'-7" LONG NO.2 SYP SCAB TO TRUSS TOP CHORD W/ (2) ROWS m ) w W w I � p p D w p Q w 10d 6" O.C. STAGGERED. MINIMUM 3' LONG SPLICE, 5 TOTAL ED Q T U U Z w w z w 0 Q w • NARROW FACE OF SCAB TO (2) 2x4 N0.2 SYP POST W/(MSTA24 W z p w I'Q F w N L` a E • (2) 2x4 NO.2 SYP POST TO SILL PLATE W/ H3 OR MSTAM24 w w w z w < w O n ❑ m -w w 11. • (2) 2x8 SYP BLOCKING BETWEEN TRUSS TOP CHORDS AND TOP OF z z I } Z Q 0 z ? a 13 ❑ L9< W o • ATTACH BLOCKING TO TRUSSES/ POSTS W/ 4 10d TOE -NAILS EACH POSTS z w w D Q m z m a Q H z 3� r Q ( ) w Z❑2t�wLID mwdEUU END n ��IzZ1YZZwr]pWh� Z U Q E U D I w p Z Q ❑W •<I -JI- -10_j O QUI- 3NMw<0M -?U0 J LL SHEET NO.: o ST -4A o ROOF FRAMING PLAN O JOB NO.: a AT1496 SUBDIVISION: o Atlantic Beach Country Club Q LOT NO.: z 6 FLOOR PLAN: j Custom O Z DESIGNED: DAE/SDA w I- REVIEWED: w DBM Q REVISIONS DATE m W Z 'S O w Q Z EX Cf) FIC Y STRUC RAL ENGINEERING TRUSS ENGINEERING NOTES: "�ndA LL IV • UNLESS SPECIFICALLY NOTED ON TRUSS FRAMING PLAN, AL TRUSS TO TOP PLATE CONNECTIONS SHALL BE ACCORDING TO THE TYPICAL WALL SECTION SHEET. • ALL EXTERIOR WALLS ARE HELD BACK 1/2" FOR SHEATHING. o -& • TRUSS T04 HAS BEEN DESIGNED TO ACCOUNT FOR DRAG s 3 y LOADS. v w I— x w M Derek B. Murray, P.E. CMCJ/METAL CONNECTOR ENGINEERING d P.E. N°.71457 TRUSS TO TOP PLATE W/ SIMPSON H2.5T, UNO ON PLAN 2E • EVERY OTHER STUD TO TOP PLATE W/ SP2 @ MAX 32" O.G. (OPTIONAL (2) SDWC16600 @ 32" O.C.) • EVERY KING STUD TO TOP PLATE W/ SP2 OR OPTIONAL (2) SDWC15600 TOP OF SHEATHING TO BE FLUSH WITH TOP OF DOUBLE TOP PLATE. TRUSS TO TOP PLATE W/ H2.5T TO OUTSIDE FACE OF TRUSS SHEATHING TO TOP PLT W/ 8d @ 3" O.C. %" BETWEEN TOP OF WOOD PANEL AND CENTER OF FASTENERS. �— PROPERLY WIND LOAD RATED SOFFIT MATERIAL CONTINUOUS @ PERIMETER. SEE TABLE 1: COMPONENT AND CLADDING DESIGN PRESSURES ON SHEET ST -1. FULL -HEIGHT VETICAL SHEATHING INSTALLED FROM SILL PLATE TO DOUBLE TOP PLT SHOWN (SEE "MIDWALL PANEL SPLICE DETAIL", THIS SHEET FOR ALT. SHEATHING ORIENTATION IYPICAL WALL SECTION AT ROOF STANDARD HEEL CONDITION AT WOOD -FRAMED WALL (THIS SECTION IS TYPICAL FOR ONE AND TWO STORY APPLICATIONS) EVERY OTHER STUD AND EVERY KING STUD TO FRAMING BELOW W/ MSTA36 OR CS16 (WHEN FLOOR SYSTEM EXCEEDS 16" DEPTH, USE CS16 EXCLUSIVELY) WOOD FLOOR TRUSS BY OTHERS (2) COURSE CMU BOND BEAM W/#5 CONTINUOUS EACH COURSE VERT. REINFORCING TO HAVE 6" BEND INTO BOND BEAM BOTTOM PLATE TO RIBBON BOARD W/ 10d COMMON @ 6" O.C. -- WALL SHEATHING TO BOTTOM \ PLATE W/ 8d COMMON @ 3" O.C. `--CONTINUOUS 2x4 RIBBON BOARD BETWEEN BOTTOM OF WOOD PANEL AND CENTER OF FASTENERS. MAX GAP BETWEEN BOTTOM OF PANEL AND TOP OF SLAB. SHEATHING TO 2x6 PT NO.2 SYP SILL PLATE W/ 8d COMMON @ 3" O.C. %" x 6" SIMPSON TITEN HD @ MAX 24" O.C. WITH 3" SQUARE x %" THICK WASHER (SEE "BOTTOM PLATE ANCHORS NOTES" ON TYPICAL WALL SECTION AT FOUNDATION) TYPICAL WALL SECTION AT FLOOR PERPENDICULAR FLOOR TRUSS CONDITION (THIS SECTION IS TYPICAL FOR TWO STORY APPLICATIONS) • EVERY OTHER STUD TO BOTTOM PLATE W/ SP1.(OPTIONAL (1) SDWC15450 @ 32" O.C. @ 2 STORY SECTIONS & (2) _ SDWC15450 @ 1 STORY SECTIONS) • EVERY KING STUD TO BOTTOM PLATE W/ SP1 OR OPTIONAL (1) SDWC15450 @ 2 STORY SECTIONS & (2) SDWC15450 @ 1 STORY SECTIONS a Q BOTTOM PLT ANCHOR It %" THREADED ROD W/ MIN 4" EMBED W/ z NUT & WASHER IN SIMPSON ACRYLIC -TIE �E ADHESIVE ANCHOR @ MAX 48" O.C. OR %" WEDGE BOLT W/ MIN 4)/2" EMBED W/ WASHER @ MAX 48" O.C. a a d a 4' d a BOTTOM PLATE ANCHOR NOTES j\ • EACH SILL PLATE SHALL HAVE A MIN. OF (2) BOTTOM PLATE ANCHORS. \\ a • INSTALL ANCHORS WITHIN 12" OF EACH END OF SEGMENT (BUTT JOINTS). 8" PARTIALLY GROUTED EXTERIOR CMU WALL W/ VERTICAL WALL REINFORCING PER TABLE 3A: MINIMUM CMU VERTICAL WALL REINFORCEMENT, ON SHEET ST -1 PROVIDE DOWELS TO MATCH VERTICAL WALL REINFORCING W/ MIN 24" LAP (IF DOWEL IS OMITTED OR IMPROPERLY INSTALLED, DRILL AND EPDXY DOWEL OF EQUAL SIZE W/ MIN. 6" EMBEDMENT IN MONOLITHIC, 12" EMBEDMENT IN MASONRY) - MONOLITHIC OR STEMWALL FOOTING PER FOUNDATION PLAN TYPICAL WALL SECTION AT FOUNDATION (THIS SECTION IS TYPICAL FOR ONE AND TWO STORY APPLICATIONS) TYPICAL 2 -STORY WALL SECTIONS THIS CONNECTION IS VALID FOR A 500# CAPACITY AND CAN BE SWITCHED OUT FROM THE SPECIFIED CONNECTION PER THE REPORTED UPLIFT ON THE TRUSS DRAWINGS. J LU w _ 0 w U) Q 2x NO 2 SYP BLOCKING TO FIT TIGHT BETWEEN I'RUSSES, (3)10d COMMON TOE -NAIL @ EACH END. BETWEEN TOP OF WOOD PANEL AND CENTER OF FASTENERS. PROPERLY WIND LOAD RATES SOFFIT MATERIAL CONT. @ PERIMETER. SEE WALL SHEATHING TO TOP PLATE___9 DESIGN CRITERIA. W/ 8d @ 3" O.C. 1(4) 0.148"x1. i' IN TRUSS VERTICAL. 2x4 NO.2 SYP BLOCK FOR TRUSS END GRAIN AILING INTO BOTTOM CONNECTION. (2) 0.131" x 3" EACH CHORD NOT ALLOWED. END. BLOCK REQUIRED ONLY IF (4) 0.148"x1.5" IN TOP PLT (AND BLOCK STRAP NAILING CANNOT BE IF NEEDED) ACHIEVED INTO DOUBLE TOP PLATE. MSTA12 (MIN) OR CS16 AT EACH TRUSS 2 2x6 NO 2 SYP BLOCKING AT FIRST (6)TRUSS BAYS FROM EACH CORNER OF BUILDING. EACH BLOCK TO HAVE (1)A35 TO TOP PLATE, TRUSS TO TOP PLATE CONNECTION W/ H2.5T TO OUTSIDE FACE OF TRUSS SEE "EXTERIOR WALL UPLIFT CONNECTION NOTES" IN TYPICAL WALL SECTION AT ROOF PROPERLY WIND LOAD RATED SOFFIT MATERIAL CONTINUOUS @ PERIMETER. SEE DESIGN CRITERIA. TOP OF SHEATHING TO BE FLUSH WITH TOP OF DOUBLE TOP PLATE, WALL SHEATHING TO TOP PLATE W/ 8d @ 3" O.C. %" BETWEEN TOP OF WOOD PANEL AND CENTER OF FASTENERS. ALT. WALL SECTION AT ROOF ALT. WALL SECTION AT ROOF RAISED HEEL CONDITION AT WOOD -FRAMED WALL CANTILEVER CONDITOIN AT WOOD -FRAMED WALL (THIS SECTION IS TYPICAL FOR ONE AND TWO STORY APPLICATIONS) (THIS SECTION IS TYPICAL FOR ONE AND TWO STORY APPLICATIONS) v 2x4 NO.2 SYP DIAGONAL BRACE @ 48" U.C. DIAGONAL BRACE TO FLOOR TRUSS OR DBL TOP PLATE W/ (3)10d COMMON TOE -NAILS AT EACH END. BOTTOM PLATE TO RIBBON BOARD W/ 10d COMMON @ 6" O.C. WALL SHEATHING TO BOTTOM 2M PLATE W/ 8d COMMON @ 3' J.C. CONTINUOUS 2x4 RIBBON BOARD '/z" BETWEEN BOTTOM OF WOOD PANEL AND CENTER OF FASTENERS. Y8" MAX GP BETWEEN —OF PANELAND OP OFSOM SLAB. SHEATHING TO 2x6 PT NO.2 SYP (2) COURSE CMU SILL PLATE W/ 8d COMMON 3" O.C. BOND BEAM W/#5 W %" OR 1 %" CONTINUOUS %" x 6" SIMPSON TITEN HD , MAX EACH COURSE 24" O.C. WITH 3" SQUARE x' " THICK 3 %6" WASHER (SEE "BOTTOM PLATE 1 15/6 ren ANCHORS NOTES" ON TYPICAL 33/4" VERT. REINFORCING TO " WALL SECTION AT FOUNDATION) 2 %d' HAVE 6 BEND INTO BOND BEAM ALT. WALL SECTION AT FLOOR PARALLEL FLOOR TRUSS CONDITION (THIS SECTION IS TYPICAL FOR TWO STORY APPLICATIONS) DIST. FROM DOORJAMB/ WINDOW TO BLOCK MIN. SCREW LENGTH DIST. FROM DOOR JAMB / WINDOW TO BLOCK MIN. SCR LENGTH W %" OR 1 %" PER MANUF. 3" 5" 1 %2' 3 %d' 3 %6" 5" 1 15/6 3 3/„ 33/4" 6„ 2 %d' 3;/4 TITEN OR TAPCONS SCREWS SEE TABLE ABOVE FOR LENGTH: • (2) ROWS %" DIA. @ 30" O.C. STAGGERED • (2) ROWS 3/6" DIA. @ 24" O.C. STAGGERED DOOR JAMB OR WINDOW ATTACH TO 2x- PER MANUFACTURER'S DETAILS I DISTANCE FROM BLOCK TO DOOR ® JAMB OR WINDOW, SEE TABLE v ABOVE (SHIM AS NEEDED TO PLUMB JAMB, DO NOT EXCEED %") 1x_ PT NAILER BUILT UP 2X ATTACHED TO MASONRY, (1) PLY 1x_ OR '/6" OSB MATERIAL MAY ATTACH TO WA DRYWALL 8" CMU WALL TYPICAL DOOR JAMB/WINDOW TO BLOC (TYPICAL FOR ALL MASONRY OPENINGS, UNO) BOTTOM PLATE TO BEAM (OR GIRDER) W/ 10d COMMON @ 6" O.C., UNO. WALL SHEATHING TO BOTTOM PLATE W/ 8d COMMON @ 3" O.C. MINIMUM 3" LAP MINIMUM FOR BEAMS. ' --[WALL SHEATHING TO BEAM (OR GIRDER TOP CHORD) W/ 8d COMMON @ 3" O.C. CENTERLINE OF FASTENERS TO BE 1 ''/2' ABOVE BOTTOM EDGE OF SHEATHING WOOD FLOOR *IMPORTANT* - FOR GIRDER TRUSS APPLICATIONS, —TRUSSES BY SHEATHING MUST CONTINUE TO BOTTOM EDGE OF ___OT�ERS TRUSS TOP CHORD. IF WALL SHEATHING IS NOT CONTINUOUS FROM SECOND FLOOR TOP PLATE TO FLOOR BEAM, THEN THE CONTRACTOR MUST STRAP THE WALL PER THE ALTERNATE STRAPPING METHOD BELOW. ALTERNATE STRAPPING METHOD FOR WALL TO BEAM (OR GIRDER) TYPICAL WALLS: EVERY OTHER STUD TO BE CONNECTED TO TOP PLATE WITH SPH4/6 AND TO BEAM/HEADER BELOW WITH MSTA36 (OR CS16) WITH (18)10d COMMON. KING STUDS: EACH KING STUD TO TOP PLT WITH SPH4/6 AND TO BEAM/HEADER BELOW WITH MSTA36 (OR CS16) WITH (18)10d COMMON. SHEARWALLS: DOUBLE STUD AT SHEARWALL ENDS TO BEAM/HEADER BELOW WITH (2) MSTA36 (OR CS 18) WITH (18)10d COMMON EACH. WHEN FLOOR SYSTEM EXCEEDS 16" DEPTH, USE SIMPSON CS16 EXCLUSIVELY ALT-. WALL SECTION AT FLOOR SECOND FLOOR TO BEAM CONNECTION (THIS SECTION IS TYPICAL FOR TWO STORY APPLICATIONS) 3/" DIA. ANCHOR W/ MIN 4" EMBED WITH NUT AND 3" SQUARE x %" THICK WASHER @ MAX 24" O.C. L LL NOTES 1. MINIMUM (2) ANCHORS REQUIRED IN ANY SEGMENT OF BOTTOM PLATE. AN ANCHOR MUST BE PRESENT WITHIN 12" OF THE END OF ANY PLATE. 2. ACCEPTABLE BOTTOM PLATE ANCHORS INCLUDE ATC, TITEN HD, HURRI-BOLT, ALL THREAD ROD. SCREW IN ANCHORS ALLOWED IN MONOLITHIC FOOTINGS ONLY. EPDXY ANCHORS MUST BE USED IN STEMWALL FOUNDATIONS. 3. ANCHOR EDGE DISTANCE TO BE 1%" REGARDLESS OF LATE SIZE. THE ANCHOR SHOULD NOT BE LOCATED IN THE CENTER OF BOTTOM PLATES GREATER THAN 2x4. %" x 6" SIMPSON TITEN HD @ MAX 24" O.C. WITH 3" SQUARE x'/d' THICK WASHER (SEE "BOTTOM PLATE ANCHORS NOTES" ON TYPICAL WALL SECTION AT FOUNDATION) TRUSS OR RAFTER TO SILL PLATE W/ H3 2x6 PT NO.2 SYP PLATE PROPERLY WIND LOAD RATED SOFFIT MATERIAL CONTINUOUS L PERIMETER. SEE TABLE 1: COMPONENT AND CLADDING DESIGN PRESSURES ON SHEET ST -1. (1) COURSE CMU BOND BEAM W/#5 CONTINUOUS AL F. WALL SECTION AT ROOF STANDARD HEEL CONDITION AT MASONRY WALL (THIS SECTION IS TYPICAL FOR ONE STORY APPLICATIONS) Z iu 0 �m Q UzUCU w rOb � C) o Uj < �wU)� YQI_Uj 00 3:0 m�w0 w °c z U�05 0- Z Un2EwU) w00w z —mz <I✓<w J UJ Uj in 03: LU a r U) U) z WALL SHEATHING TO TOP PLATE W/ 8d COMMON @ 3" O.C. PANEL SPLICE LOCATION PROVIDE BLOCKING TO FIT TIGHT BETWEEN STUDS OR PANEL JOINTS. BLOCKING TO BE 7/6" OSB OVER 2x4 NO.2 SYP W/ (2) 10d COMMON TOE NAILS AT EACH END. BOTTOM PLATE TO RIBBON BOARD W/ 10d COMMON @ 6" O.C. WALL SHEATHING TO BOTTOM PLATE W/ 8d COMMON @ 3" O.C. MIDWLLPNENSPLICE DETAIL o SCALE c1 3/" EDGE DISTANCE, REGARDLESS OF A d 'dT PLATE SIZE (2x6 WALL SHOWN) WALL SHEATHING TO PT SILL PLATE WITH 8d AT 3" O.C. —''/z" BETWEEN BOTTOM OF PANEL AND CENTER OF FASTENERS. MAX GAP BETWEEN BOTTOM OF PANEL AND TOP OF SLAB. —1 %" EDGE DISTANCE (REGARDLESS OF PLATE SIZE) WOOD -FRAMED WALL SECTION AT FOUNDATION (THIS SECTION IS TYPICAL FOR ONE AND TWO STORY APPLICATIONS) ALTERNATE WALL SECTIONS & TYPICAL DETAILS GENERAL NOTES APPLICABLE TO ALL: 1. ALL TOP PLATES ARE TO BE BUILT WITH (2)2x_ NO 2 SYP FASTENED W/(2) ROWS 10d @ 8" O.C. STAGGERED (UNO). MINIMUM 48" LAP W/ MINIMUM (20) 10d IN LAP. ADJUST TYPICAL NAIL SPACING AS NEEDED. 2. ALL EXTERIOR BOTTOM PLATES ARE TO BE 2x NO 2 SYP PT. 3. ALL INTERIOR BOTTOM PLATES ARE TO BE 2x NO. 2 SYP PT. 4. ALL INTERIOR LOAD BEARING WALL STUDS ARE TO BE MINIMUM 2x4 NO. 2 SPF @ 16" O.C. UNLESS NOTED OTHERWISE ON FRAMING PLAN. 5. FOR SHEATHING SIZE AND FASTENING, REFER TO TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS ON SHEET ST -1. 6. FOR EXTERIOR WALL STUD SIZE AND SPACING, REFER TO TABLE 3: MINIMUM EXTERIOR WALL STUD SIZES ON SHEET ST -1. 7. FOR EXTERIOR CMU WALL VERTICAL WALL REINFORCING, REFER TO TABLE 3A: MINIMUM CMU VERTICAL WALL REINFORCEMENT ON SHEET ST -1. 8. FOUNDATION INFORMATION ON THIS PAGE IS FOR GRAPHICAL DEPICTION ONLY. REFER TO FOUNDATION PLAN AND SECTIONS FOR FOUNDATION INFORMATION. 9. WALL SECTION AT FOUNDATION AND WALL SECTION AT ROOF ARE TYPICAL FOR ONE ND TWO STORY APPLICATIONS. Cn co O O N LO V_ C:N O ,I- 0 O CIO d' N N N M J LL W J J z O U) Y U Q N O 'I W F- F-- Y d z F- 0 U 'IT x° z �0 I- W w 'T 0- 0 4 . [] Qw Mn 0z� da 91 am" w° _uYH°Ww0 LO J O I Z W❑ ° °w O N S � w W -° m< j Q D W 0 O°aw0 Ww JQL,IjU7°0 W ° o MEL PF W � W Z I_D 07 zM0a>ww w, 0z0 W <1LI_< w1wto (nWwl-�wW W F 0 U It Z <=aQjaj�Fazw<L oWZ-zw�zox°y°� aWco = w °Q � zz x 0o1—n-:r oz w [rW°WxQz<Fwm_[x5 LU w1<xw2i.-DLjZw ww . Z z=�-z4ozzaUo0Qwo Z Ww0Qmz-aQFz3-�Q W Z02 -wZ mWQ�f-U Q =azo -z1<0 Qf6o <L °� �ZnQ�Hn�a=°ww O X01--?3:N'1w<0Mi -z00 J LL z SHEET NO.: o ST -5 o TYPICAL WALL SECTION Q JOB NO.: Q AT1496 SUBDIVISION: oAtlantic Beach LL Country Club Q LOT NO.: z 6 FLOOR PLAN: 0 custom O Z DESIGNED: U DA E/SDA w F- REVIEWED: DBM Q REVISIONS DATE m n w -- Z s O w Q z STRUGT L ENGINEERING (2) SDWC15600 OR (2) MSTA24 NO 2 SYP DOUBLE STUDS TO TOP PLATE TOP PLATE (2)MSTA36 TO INSIDE OR OUTSIDE FACE OF WALL NO 2 SYP DOUBLE TOP PLATE �— INSTALL DBL 2x- BLOCKING IN FIRST TWO STUD SPACES. FASTEN SHEATHING TO BLOCKING WITH 8d COMMONS @ 3" O.C. < i FASTEN STUDS TOGETHER WITH (2) ROWS 1 Od AT 8" O.C., STAGGERED, EDGE NAIL SHEATHING AT STUD GROUP, PER TABLE 2, ST -1 AND SW. THIS DOES NOT APPLY TO 45 -DEGREE OR 90 -DEGREE CORNERS. CHANGE IN PLATE HEIGHT NG SPF SCAB W/ (20) 1 Od TO ER STUD ONLY WHEN HOLD S ARE SPECIFIED ON PLAN. _.'F CORNER STUDS ALTERNATE CORNER DETAIL #5 CONT. o_ o J /— `r ! CORNERS WITH MIN. 24" LAP N #5 CONT. 8" CMU BOND BEAM BOND BEAM REINFORCING AT CORNERS MASONRY WALL .� GARAGE DOOR BUCK/JAMB TO CMU W/ (2) ROWS TITEN SCREWS OR TAPCONS'/d' x 4" LONG @ 12" O.C. STAGGERED WEATHER STRIPPING/STOP GARAGE DOOR ------- -------7 --------------J 2x6 SYP GOAL POST ATTACHED TO CMU W/ (2) ROWS TITEN NOTE: SCREWS OR TAPCONS'W x 4" IN LIEU OF SPECIFIED DECK SCREWS FOR LONG @ 12 " O.C. STAGGERED GOAL POST ATTACHMENT, THE GARAGE DOOR SUPPLIER MAY SPECIFY A FASTENING GARAGE DOOR TRACK ATTACHED —� PATTERN OF THE GARAGE DOOR TRACK PER MANUF WRITTEN DIRECTLY TO THE KING AND JACK STUDS, SPECIFICATIONS THROUGH THE GOAL POST. GARAGE DOOR JAMB DETAIL FASTEN 2x4 NO.2 SYP DIAGONAL BRACE TO BLOCKING W/ (6) 1 Od 2x6 NO 2 SYP DIAGONAL BRACE - (SEE PLAN FOR LENGTH) • UP TO 8FT SINGLE 2x6 ONLY • UP TO 20 FT, 2x6 W/ 2x6 T -BRACE FASTEN 2x6 NO.2 SYP "T -BRACE" TO DIAGONAL BRACE W/ 1 Od @ 3" O.C. 8'-0" OR AS SHOWN ON FLAN FASTEN (1) SIMPSON HGA10 BRACE CONNECTOR TO DIAGONAL BRACE TO GABLE VERTICAL 2x NO 2 SYP NAILER FASTENS[ DOUBLE TOP PLATE W/ 10d @ 3 O.C. AND TO (1) ADJACENT TRL BOTTOM CHORD W/ 10d @ 3" O. TRUSS BOTTOM CHORD SHEATHING TO STUDS PER, TABLE 2: WOOD STRUCTUR/ PANEL SHEATHING REQUIREMENTS, SHEET ST - 7/111, \1 PRE -MANUFACTURED JACK TRUSS GABLE ANGLE BRACING DETAIL AT JACK TRUSSES TOE -NAIL MIN 2x6 NO 2 SYP BLOCKING 2x4 NO.2 SYP BLOCKING BETWEEN DBL 2x4 NO. 2 SYP FASTENED TO BETWEEN TRUSS TOP CHORDS W/ OUTLOOKERS. FASTEN EACH WEB W/ 10d AT 6" O.C. FOR GABLE BRACE INSTALLATION. (3) 10d EACH END BLOCK TO ROOF DECK W/ 8d 2x4 LOWER ROOF DECK. 1 ROW COMMON @ 3" O.C. (1)2x4 GABLE VERTICAL MEMBER W/ (3) 1 Od ROOF DECK • FASTEN 2ND PLY TO 1ST PLY W/ 1 10d @ 6" O.C. 2x6 2x4 SYP OUTRIGGER @ 24" O.C. 1 ROW 2x4 (1)2x6 CLIP TO GABLE TOP CHORD W/ 2 ROWS Ix (1) H2.5T W/ (10) 8d x 1'/s" 2x8 K�X 1 ROW 2x6 24" LONG 2x4 NO. 2 SYP SCAB 2x8 GABLE TRUSS APPLIED TO GABLE VERTICAL (2)2x6* rl _ F ®� —I OR BLOCKING BETWEEN W Derek B. Murray, P.E. I I TRUSS WEBS W/ 1 Od AT 3" O.C. CMU�METAL CONNECTOR ENGINEERING I t 2x6 NO 2 SYP DIAGONAL BRACE I I FASTEN (1) SIMPSON HGA10 BRACE F CONNECTOR FROM TO EACH I DIAGONAL BRACE TO GABLE 8'-0" OR AS SHOWN ON FLAN FASTEN (1) SIMPSON HGA10 BRACE CONNECTOR TO DIAGONAL BRACE TO GABLE VERTICAL 2x NO 2 SYP NAILER FASTENS[ DOUBLE TOP PLATE W/ 10d @ 3 O.C. AND TO (1) ADJACENT TRL BOTTOM CHORD W/ 10d @ 3" O. TRUSS BOTTOM CHORD SHEATHING TO STUDS PER, TABLE 2: WOOD STRUCTUR/ PANEL SHEATHING REQUIREMENTS, SHEET ST - 7/111, \1 PRE -MANUFACTURED JACK TRUSS GABLE ANGLE BRACING DETAIL AT JACK TRUSSES ROOF DECK NAILER/BLOCKING FASTENED TO JACK W/ (3) 1 O TOE -NAILS 1) MAX. TRUSS SPACING= 24" O.C. 2) OUTLOOKERS, BLOCKING & CLIPS MAY BE OMITTED FROM OVERHANG PORTION OF DETAIL FOR NON -DROPPED GABLE TRUSSES W/ 12" OR LESS OVERHANGS. 3) L OR T BRACE VERTICAL REINFORCEMENT PER TRUSS ENGINEERING NOT SHOWN FOR CLARITY. 7Y4" MAX 2x4 NO.2 SYP CATS @ 12" O.C.- FASTENED TO DOUBLE TOP PLATE W/ (4) 1 O AND TO EACH ADJACENT TRUSS BOTTOM CHORD W/ (3) 1 O TOE -NAILS. TRUSS BOTTOM CHORD SHEATHING TO STUDS PER, - TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS, SHEET ST -1 16" MAX 2x4 NO.2 SYP NAILER TO TRUSS BOTTOM CHORD W/ 10d @ 3" O.C. TRUSS BOTTOM CHORD '/6" OSB SHEATHING FASTENED - TO NAILER W/ 1 O @ 3" O.C. AND TO DOUBLE TOP PLATE W/ 10d @ 3" O.C. SHEATHING TO STUDS PER, - TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS, SHEET ST -1 (1) DIAGONAL BRACE PER (10) TRUSSES APPLIED TO OPPOSITE SIDE OF WEBS. DIAGONAL BRACE APPLIED AT APPROXIMATE 45° ANGLE TO NO LESS THAN (3) TRUSSES. li II II II CONTINUOUS LATERAL RESTRAINT (CLR). QUANTITY AND LOCATION DEFINED BY TRUSS SHOP DRAWING. APPLIED TO EITHER IF LATERAL RESTRAINT MUST BE SIDE 11 11 WEBS I� MADE OF MORE THAN ONE PIECE, DO SO WITH OVERLAPPING BRACES LIKE THIS (TYP EVERYWHERE)_ TRUSSES NEEDING BRACING LATERAL BRACING - MULTIPLE TRUSSES 1. ALL RESTRAINT LUMBER SHOWN SHALL BE 2x4 NO.3 SPF OR BETTER (UNO) 2. SHOULD A SCENARIO ARISE THAT DOES NOT RESEMBLE THOSE INDICATED ABOVE, IMMEDIATELY CONTACT THE ENGINEER OF RECORD FOR APPROPRIATE BRACING DETAILS. 3. BRACING LUMBER SHALL INTERSECT THE WEBS OF THE BRACED TRUSS AT LOCATIONS INDICATED AS NEEDING BRACING ON THE INDIVIDUAL TRUSS DETAILS PRODUCED BY THE TRUSS ENGINEER. 4. ALL FASTENERS SHOWN ARE .131" x 3" LONG (UNO). 5. DESIGNED PER BCSI-133, 2007. T -BRACE FASTENED TO WEB W/ 10d AT 6" O.C. L -BRACE FASTENED TO WEB W/ 1 Od AT 6" O.C. VERTICAL/SCAB I �-�• DBL 2x4 NO. 2 SYP FASTENED TO SCAB BRACE FASTENED TO INTERIOR FACE OF GABLE TRUSS WEB W/ 10d AT 6" O.C. FOR GABLE BRACE INSTALLATION. 1 LOCATE MEMBER OPPOSITE 2x4 LOWER ROOF DECK. 1 ROW • FASTEN 1 ST PLY OF 2x4 TO EACH (1)2x4 GABLE VERTICAL MEMBER W/ (3) 1 Od \' • FASTEN 2ND PLY TO 1ST PLY W/ 1 10d @ 6" O.C. 2x6 J (n a- j, ROOF DECK NAILER/BLOCKING FASTENED TO JACK W/ (3) 1 O TOE -NAILS 1) MAX. TRUSS SPACING= 24" O.C. 2) OUTLOOKERS, BLOCKING & CLIPS MAY BE OMITTED FROM OVERHANG PORTION OF DETAIL FOR NON -DROPPED GABLE TRUSSES W/ 12" OR LESS OVERHANGS. 3) L OR T BRACE VERTICAL REINFORCEMENT PER TRUSS ENGINEERING NOT SHOWN FOR CLARITY. 7Y4" MAX 2x4 NO.2 SYP CATS @ 12" O.C.- FASTENED TO DOUBLE TOP PLATE W/ (4) 1 O AND TO EACH ADJACENT TRUSS BOTTOM CHORD W/ (3) 1 O TOE -NAILS. TRUSS BOTTOM CHORD SHEATHING TO STUDS PER, - TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS, SHEET ST -1 16" MAX 2x4 NO.2 SYP NAILER TO TRUSS BOTTOM CHORD W/ 10d @ 3" O.C. TRUSS BOTTOM CHORD '/6" OSB SHEATHING FASTENED - TO NAILER W/ 1 O @ 3" O.C. AND TO DOUBLE TOP PLATE W/ 10d @ 3" O.C. SHEATHING TO STUDS PER, - TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS, SHEET ST -1 (1) DIAGONAL BRACE PER (10) TRUSSES APPLIED TO OPPOSITE SIDE OF WEBS. DIAGONAL BRACE APPLIED AT APPROXIMATE 45° ANGLE TO NO LESS THAN (3) TRUSSES. li II II II CONTINUOUS LATERAL RESTRAINT (CLR). QUANTITY AND LOCATION DEFINED BY TRUSS SHOP DRAWING. APPLIED TO EITHER IF LATERAL RESTRAINT MUST BE SIDE 11 11 WEBS I� MADE OF MORE THAN ONE PIECE, DO SO WITH OVERLAPPING BRACES LIKE THIS (TYP EVERYWHERE)_ TRUSSES NEEDING BRACING LATERAL BRACING - MULTIPLE TRUSSES 1. ALL RESTRAINT LUMBER SHOWN SHALL BE 2x4 NO.3 SPF OR BETTER (UNO) 2. SHOULD A SCENARIO ARISE THAT DOES NOT RESEMBLE THOSE INDICATED ABOVE, IMMEDIATELY CONTACT THE ENGINEER OF RECORD FOR APPROPRIATE BRACING DETAILS. 3. BRACING LUMBER SHALL INTERSECT THE WEBS OF THE BRACED TRUSS AT LOCATIONS INDICATED AS NEEDING BRACING ON THE INDIVIDUAL TRUSS DETAILS PRODUCED BY THE TRUSS ENGINEER. 4. ALL FASTENERS SHOWN ARE .131" x 3" LONG (UNO). 5. DESIGNED PER BCSI-133, 2007. T -BRACE FASTENED TO WEB W/ 10d AT 6" O.C. L -BRACE FASTENED TO WEB W/ 1 Od AT 6" O.C. SINGLE TRUSS BRACING CONTINUOUS LATERAL RESTRAINT WU y 549 �✓���Afr BRACE SUBSTITUTE SCAB BRACE FASTENED TO WEB MEMBER SPECIFIED ALTERNATE BRACING WEB W/ 10d AT 6" O.C. SIZE CLR T OR L SCAB 2x4 3. INDIVIDUAL WEB BRACING MATERIAL TO BE SAME SIZE, SPECIES, AND 1 ROW 2x4 (1)2x4 2x4 2 ROWS 2x6 (2)2x4* 2x6 J (n a- j, 1 ROW 2x4 (1)2x6 2x6 2 ROWS 2x6 (2)2x4* 2x8 w 1 ROW 2x6 (1)2x8 2x8 2 ROWS 2x6 (2)2x6* SINGLE TRUSS BRACING FASTEN STUD TO CORNER STUD GROUP W/ (2) ROWS 1 Od @ 6" O.C. STAGGERED. OMIT NAILS AT BOTTOM 24" OF STUD FOR STRAP INSTALLATION OPTION 1 OPTION 2 OPTION 3 1. INDIVIDUAL WEB BRACING MAY BE USED WHEN CONTINUOUS LATERAL 549 �✓���Afr RESTRAINT (CLR) IS SPECIFIED ON A TRUSS DESIGN BUT AN ALTERNATIVE SCAB BRACE FASTENED TO WEB BRACING METHOD IS DESIRED. WEB W/ 10d AT 6" O.C. 2. INDIVIDUAL WEB BRACING MAY CONSIST OF T -BRACING, L -BRACING, OR *IF (2) BRACES ARE SCAB BRACING. REFER TO CHART AND DETAIL FOR MORE INFORMATION. REQUIRED, APPLY (1) BRACE 3. INDIVIDUAL WEB BRACING MATERIAL TO BE SAME SIZE, SPECIES, AND TO EACH FACE OF WEB. GRADE AS WEB TO BE BRACED. FASTEN STUD TO CORNER STUD GROUP W/ (2) ROWS 1 Od @ 6" O.C. STAGGERED. OMIT NAILS AT BOTTOM 24" OF STUD FOR STRAP INSTALLATION OPTION 1 OPTION 2 OPTION 3 0 = 549 �✓���Afr ED 0 INTERIOR SHEARWALL DETAIL"I (V = 1. FOR TRUSSES THAT SIT DIRECTLY ABOVE THE WALL, FASTEN TRUSS p BOTTOM CHORD TO DOUBLE TOP PLATE WITH 1 Od TOE -NAILS AT 4" O.C. w w 2. THIS INTERIOR SHEARWALL DETAIL IS INTENDED FOR USE IN AREAS WHERE Z THE SHEARWALL RUNS PARALLEL TO THE TRUSSES, THIS IS A PREFERREDOf a ALTERNATIVE TO FRAMING ABOVE THE PLATE LINE TO THE ROOF DECK. w of o_ Q WW U= J (n a- j, z �O wW zm TRUSSES PARALLEL TO WALL 2x4 SPF (MIN) NAILER FASTENED TOSILLPLTW/10d@3"0.C. TRUSSES PERPENDICULAR TO WALL: 2x4 SPF (MIN) BLOCKING BETWEEN EACH TRUSS. FASTEN TO SILL PLT W1 Od @ 4" O.C. ROOF DECK ROOF TRUSS OR RAFTER 2x4 SPF (MIN) BLOCKING BETWEEN EACH TRUSS. FASTENTO BEAM w/ 10d @ 4" O.C. TRUSS TO PORCH BEAM w/ SDWC15600 OR THICKER CDX OR OSB FASTENED TO TRUSSES, RAFTERS OR BLOCKING W/8d COMMONS @ 3" EDGE, 12" FIELD. TYPICAL PORCH SHEATHING DETAIL AT MASONRY EXTERIOR WALL 2x8 SPF STUDS FROM TOP— OF SILL PLATE TO 2ND LEVEL TOP PLATE @ 16" O.C. MAX PORCH BEAM PORCH BEAM TO POST: (1) MSTA24 POST TO SLAB: ABU POST BASE ANCHOR OR DTT2Z (UNLESS NOTED OTHERWISE) SHEATHING PER TABLE 2 ON STRUCTURAL SPECIFICATIONS SHEET 2x8 PT NO.2 SYP SILL PLATE TO MASONRY WALL W/ "4" SIMPSON TITEN HD @ MAX 24" O.C. W/ 3" SQUARE x %4 THICK WASHER (SEE "BOTTOM PLATE ANCHORS NOTES" ON "TYPICAL WALL SECTION AT FOUNDATION" ON TYPICAL. WALL SECTION SHEET) SHEATHING TO SILL PLATE W/ 8d @ 3" O.C. BOTTOM PLATE TO BEAM W/ (2) ROWS 1 Od @ 3" O.C., STAGGERED L ( I L i 2 JACK STUDS, 1 KING STUD 3 JACK STUDS (2) MSTA36 OR CS18 FASTEN SHEATHING TO FRAMING PORTAL PLAN VIEW MEMBERS W/ 8d COMMON @ 3" O.C. AS SHOWN (TYPICAL FOR EACH END OF PORTAL FRAME, NOT TO SCALE) I NO PANEL SPLICES I r HEADER TO BE CONTINUOUS TO KING STUD W/ NO FLITCH PLATE FASTEN SHEATHING W/ 8d COMMON GRID PATTERN @ 3" O.C. EACH WAY, AS SHOWN SHEAR PANEL TOP PLT TO HEADER W/ (2) ROWS 10d COMMON @ 3" O.C. STAGGERED JACK TO HEADER WITH (2) MSTA24, (4) TOTAL AS SHOWN 2x- BLOCKING AT PANEL SPLICE FOR EDGE NAILING, EDGE NAIL SHEATHING AT BLOCKING FASTEN ALL MULTI -PLY STUD GROUPS W/ (2) ROWS 1 Od COMMON @ 8" O.C., STAGGERED (2) SIMPSON MSTA36 OR CS18, (4) TOTAL @ EACH PORTAL END AS SHOWN tLtVH I IUIN VII --VV (TYPICAL FOR EACH END OF PORTAL FRAME) • FASTEN SHEATHING TO FRAMING MEMBERS W/ 8d COMMON @ 3" O.C., AS SHOWN • FASTEN SHEATHING W/ 8d COMMON GRID PATTERN @ 3" O.C. EACH WAY, AS SHOWN • FASTEN REMAINING SHEATHING W/ 8d COMMON @ 3" O.C. EDGE, 12" O.C. FIELD P2 PORTAL FRAME DETAIL Pik J ILL W J J > z O U) Y Q N O w W O U Y Q 0- z Z O 17- U) It >_ ❑ ? 0 ti w 0---,.,-Z— 0 ❑ IT Q� u�❑ aWL¢z LS7 M❑0� �ZDw0WUo� cFW❑ z1)M 1Q]w❑ O wWMo ❑WwWONwo� Z ❑ 0 m IE t p> w z❑ U) ❑ Q z w� w_j m❑ Z U W ¢a i._<00lwwNl-Nww w I- ❑ U Z Q=�Nw�0� azw< Cn Q 0 w w z w X❑ 2 p❑ ❑ w a M Clw J p Q I m ED<1113 WWzw0<7w � z Q x w❑❑❑— I L❑ Z w E w Ow X Q Z a Q x N- w [7 U W w I Q w w 2 F o❑ N • w w Z zI�ZQpzzaL�10LN7Qwz Z z 0 0 Lo Q m z N Q I Z 3 F Q wZ� -w w t W w_❑2L7wED N2� UU w w E �Z0<—HUa020w0Z< p Q 0 ❑U�z3NdUFJQ0C' 00 J Z SHEET NO.: o ST -6 I— o STRUCTURAL DETAILS O JOB NO.: Q U AT 1496 0 SUBDIVISION: o Atlantic Beach J LL Country Club Q LOT NO.: z 6 FLOOR PLAN: Custom O Z DESIGNED: C) DAE/SDA W F-- REVIEWED: w DBM W Q REVISIONS DATE X Q CD .� W Z> O w Q z U) A -PEN STR TURAL ENGINEERING 549 �✓���Afr ��/j�� t� .o�^qv�,. p E "aT � z z w I— x w W Derek B. Murray, P.E. � CMU�METAL CONNECTOR ENGINEERING P.E. No. 71457