303 ATLANTIC BLVD - FIRE COMMENTS 8-9-18 . w
y+ r
14
CITY OF ATLANTIC BEACH
800 Seminole Road
, Atlantic Beach,Florida 32233
filt
REVISION REQUEST/CORRECTIONS TO PLAN REVIEW COMMENTS
Date 8-9-18 Revision to Issued Permit x Corrections to Comments Permit#17-CA D D-3210
Project Address 303 Atlantic Boulevard, Atlantic Beach, FL, 32233
Contractor/Contact Name River City Contractors, Alan Cottrill
Phone 904 422 5988 Email alan@rivercity-contractors.com
Description of Proposed Revision/Corrections: Permit Fee Due$
Change proposed ADA mechanical lift to ADA compliant ramp to satisfy code requirement for accessibility.This includes revision to
previous furniture layout.This plan does not change occupancy or number of seats as previously approved.
Additional Increase in Building Value$ $o Additional S.F. 0
By signing below,I Alan Cottrill affirm the Revision is inclusive of the proposed changes.
(printed name)
C 9
717--
Signature oContractor/Agenttracfor must sign if increase E."mvaluao
(Office Use Only),
AUG - =113
Approved Denied 'V N A licable to Department
—fes � �?u��lr.4 int
C`+y of At a,4.:... FL
Revision/Plan Review Comments
peprtment Review Required: ,'/J
<�uildin ..-v.=
-Planning &Zoning Reviewed By
Tree Administrator
Public Works
Public Utilities t' - Z2 7,p t%'
Public S fety Date
1
MIGUEL Di PIERRI
Fire Safety Inspector/ CDN Reviewer
JFRD PREVENTION OFFICE
515 N. Julia St.,Jacksonville, Florida 32202
Office: 904-255-8561 cell: 904-237-7212—Email: DIPIERRI@COJ.NET
8/22/2018
Returned for Corrections:
The plans submitted for review have been returned for corrections. Please correct or provide the
proceeding requested information to obtain plans approval. When resubmitting corrected sheets, please
provide a written narrative letter responding to our comments and directing the plans reviewer to the
sheets the changes have taken place. Failure to provide response letter"WILL" result in an immediate
return for corrections plans review submission. Revised sheets should be clouded clearly showing areas
were changes or corrections have occurred and re-inserted with the original set of drawings with old
sheets removed. Unbound plans will not be reviewed. If this is an electronic submission please make sure
that written narrative is submitted under correspondence along with a"complete set" (not just the revised
sheets) of electronic documents.
1. Provide required Fire Code specific code summary: (Florida is currently using the "2015 Florida
Fire Prevention Code Sixth Edition" effective Dec 315t, 2017 based off NFPA 1 and NFPA 101 2015
Edition.)
2. Required Lock Latch details:
• Lock/Latch details: Panic Hardware, Thumb turn lock, Key Lock with indicator and required
Signage.
3. Required markings of means of egress:
• Exit signs to include tactile exits signage.
4. Emergency Egress lighting & Marking of MOA:
7.8 Illumination of Means of Egress.
7.8.1.1* Illumination of means of egress shall be provided in accordance with Section 7.8 for every
building and structure where required in Chapters 11 through 43. For the purposes of
This requirement, exit access shall include only designated stairs, aisles, corridors, ramps, escalators,
and passageways leading to an exit. For the purposes of this requirement, exit discharge shall include
only designated stairs, aisles, corridors, ramps, escalators,
Walkways, and exit passageways leading to a public way.
Provide emergency egress lighting per NFPA 101 7.9.1 in all stairs, aisles, corridors, ramps, escalators &
passageways leading to an exit providing not less than 1.5 hours of backup lighting and an average of 1ft.
candle at any point and not less than 1/2 ft. candle along the path of egress. For the purposes of this
requirement, exit discharge shall include only designated stairs, aisles, corridors, ramps, escalators,
walkways, and exit passageways leading to a public way.
Provide Marking of Means of Egress (Exit Signs) to include all exits and exit access when exit or way to
reach the exit is not readily apparent per NFPA 101 7.10.1.2
Provide Exit Door Tactile signage (Raised Characters in Braille) per NFPA 101 7.10.1.3
5. Door Hardware:
Any door in a required means of egress from an area having an occupant load of 100 or more persons
shall be permitted to be provided with a latch or lock only if it is panic hardware or fire exit hardware.
P1;inting :: CR471949 Page 1 of 1
Duval County,City Of Jacksonville
Michael Corrigan ,Tax Collector
231 E.Forsyth Street
- Jacksonville,FL 32202
General Collection Receipt
Account No:CR471949 Date:8/22/2018
User:Prevention,Fire Email:FirePrev@coj.net
FIRE MARSHALL FEE FOR SERVICES PROVIDED
Name:COOP 303
Address:303 Atlantic Blvd
Description:Plan review# 1 Atlantic Bch
TranCode I IndexCode I SubObject I GLAcct I SubsidNo I UserCode I Project I ProjectDtl I Grant I GrantDtl I DocNo I Amount
701 I FRFP159FI I 34222 I I I I I I I I I 150.00
Total Due:$150.00
Michael Corrigan , Tax Collector
General Collections Receipt
City of Jacksonville,Duval County
Account No:CR471949 Date:8/22/2018
FIRE MARSHALL FEE FOR SERVICES PROVIDED
Name:COOP 303
Address:303 Atlantic Blvd
Description:Plan review#1 Atlantic Bch
Total Due:S150.00
http://fmanceweb.coj.net/TCCRlprinting.aspx?c1=CR471949 8/22/2018