Attached is the fire flow test that was done within the year and the calculations for the fire protection. This information
was submitted for the original set of plans approved by the fire marshal and the City. Since nothing has changed with
the fire system, the calculations are the same. Let us know if you need any additional information.
to.Dl9-04
iq
January 4,2018
James M. Lucas, PE.
J. Lucas&Associates Inc.
1305 Cedar Street
Jacksonville, Florida 32207
RE: Fire Flow Tests on 11th St. Water Main for Selva Preserve
Dear Mr.Lucas:
The City performed a flow test on the fire hydrant at 11`h St.and Linkside Dr. with the following
results:
Location: 1lth Street and Linkside Drive
Test Date/Time: 10/2/17 11:24 AM
Static Pressure: 51 psi
Residual Pressure: 44 psi
Test Flow Rate: 1,100 gpm
Estimated Flow @ 20 psi: 2,456
Tested by: Chris Walker, Division Director
The above estimated flow at 20 psi are based on NFPA section 291,AWWA M-17.
Should you need additional information,please call me at(904)247-5874 or email me at
kmoore@coab.us.
Sincerely,
�� fit'• �cr�.
Kayle Moore,PE
Deputy Public Works Director
cc: Chris Walker, Division Director
Public Works Department 1200 Sandpiper Lane
Atlantic Beach, FL 32233
(904) 247-5834
NUMBER: 1413 J. LUCAS&ASSOCIATES,INC.
PROJECT SELVA PRESERVE 1/4/2018
WATERMAIN ANALYSIS
STATIC RESIDUAL FLOW PITOT TEST STAT-TP STAT-RES SORT CALC.
READING READING READING READING PRESS. FLOW
51 44 1100 42.49108 20 31 7 2.1044 2315
51 44 1100 42.49108 45.2 5.8 7 0.9091 1000
51 44 1100 42.49108 50.0 1.0 7 0.3780 416
51 44 1100 42.49108 48.0 3.0 7 0.6547 720
51 44 1100 42.49108 46.0 5.0 7 0.8452 930
51 44 1100 42.49108 45.0 6.0 7 0.9258 1018
EXISTING STATIC PRESSURE 51 LOCATION OF FIRE HYDRANT:
TEST HYDRANT: 11TH ST&
EXISTING RESIDUAL PRES. = 44 (AT HYDRANT) LINKSIDE DRIVE
RESIDUAL HYDRANT:
CALCULATED FLOW = 1100 GPM 1100
PITOT READING = 42.49108 PSI TEST: 10/2/2017
REQUIRED FIRE FLOW = 1000 GPM NO. OF PORTS 1
Q =750 GPM Q = 1000 GPM Q= 1500 GPM
C = 130 C= 130 C= 130
HL (6') = 43.6 '/1000 70 '/1000 157 '11000
HL (8') = 10.75 11000 18 11000 38.7 '/1000
HL (10")= 3.6 '/1000 6 11000 13 11000
HL (12")= 1.49 '/1000 2.5 '/1000 5.41 11000
HL (16")= 0.37 11000 0.61 11000 1.33 '/1000
HL (20")= 0.12 '/1001 0.2 '11000 0.5, ,( „ ,
HEAD LOSS FROM TEST HYDRANT TO FIRE CONNECTION ,����� ..M•.... 0,--..
LENGTH OF PIPE DIAMETER OF PIPE HEADLOSS �``,,��'� NSA~•.•'�0 i
NO.1 : 70
53 6 3.71 FT . *
666 8 11.99 FT . STA '.i a,0 10 0.00 FT ': � .•4Q1
0 12 0.00 FT O,((c•'••.i.,..IQ.P,.•'�,
0 16 0.00 FT s`.s�''NAL�N \.
0 20 0.00 FT ''•lanm„1«rt:,,
TOTAL HEAD LOSS 15.70 FT 6.80 PSI
RESIDUAL AT HYDRANT AT FIRE FLOW 45.2 PSI
NET RESIDUAL AT END OF PIPE 38.42 PSI
SYSTEM MEETS FIRE FLOW REQUIREMENTS