1596 Maritime Oak Dr RES18-0358 dwgs 8TYPICAL WINDOW FLASHING METHOD "A-1" (ASTM E 2112-01) WINDOW INSTALLATION METHOD A-1 WEATHER RESITIVE BARRIER (WRB) APPLIED PRIOR TO THE WINDOW INSTALLATION. O FLASHING APPLIED OVER THE FACE OF THE MOUNTING FLANGE. _ �5 JAMB FLASHING APPLY CONT. SEAL TO THE MOUNTING — FLANGES AT THE TOP (HEAD) AND SIDES (JAMBS) OF WINDOW. EXTEND SEALANT AT JAMBS 8 %2' ABOVE THE R.O. AT HEAD. EMBED JAMB FLASHING INTO SEALANT AND FASTEN iN PLACE. (FLASHING GOES OVER SEALANT). SEAL THE WINDOW FRAME TO OPENING. APPLY A%" NOM. DIA. TO THE BACKSIDE (INTERIOR) OF THE WINDOW 16W �,� FLANGE, IN LINE WITH ANY 0 PRE -PUNCHED HOLES OR �tiP SLOTS. / @JAMB FLASHING I� EXTEND JAMB FLASHING TO OVERLAP SILL FLASHING. EXTEND JAMB FLASHING 8 %2' ABOVE ROUGH OPENING AT HEAD. TUCK TOP OF JAMB FLASHING UNDER THE FLAP OF WRB AT THE HEAD. SEE DIAGRAM. O 8 9" SECURE WRB AT HEAD FLASHING AT HEAD EXTENDS 1" BEYOND JAMB FLASHING. (7 HEAD FLASHING EMBED BOTTOM OF THE HEAD FLASHING AGAINST THE PREVIOUSLY APPLIED SEALANT (FLASHING GOES OVER SEALANT). EXTEND HEAD FLASHING BEYOND EACH JAMB 1 \ > FLASHING. FASTEN IN PLACE. 0 INTERIOR VIEW )P LEFT CORNER SEALANT OF WINDOW 35° `SILL FLASHING \ 911 (j)WEATHER RESISTANT BARRIER (WRB) CUT �� AT A 45 DEGREE ANGLE, CAREFULLY CUT LINE THE BARRIER ON A DIAGONAL. GENTLY RAISE THE TOP EDGE OF THE BARRIER UP AND TAPE THE TOP CORNERS AND CENTER TO THE EXTERIOR WRB SURFACE ABOVE. STEPS: SHIM AND ADJUST WINDOW TO ACHIEVE SQUARE, PLUMB, AND LEVEL CONDITION. USE CORROSION RESISTANT FASTENERS. FASTEN WINDOWS PER WINDOW MANUFACTURER SPECIFICATIONS J) IN WATER SHEDDING FASHION, ® APPLY BEAD OF SEALANT AT !l STARTING AT THE BASE OF THE I SIDE JAMBS. EXTEND 8 %2" 1 WALL & WORKING TOWARDS THE O APPLY JAMB FLASHING 1X WOOD TRIM TOP, INSTALL THE WRB TO THE CAULK Q U) DOOR STOP PER DOOR MANUF. w a0 FACE OF THE SHEATHING. © APPLY BEAD OF SEALANT AT HEAD 02 APPLY SILL FLASHING ON 15# FELT OVER O.S.B. APPLY HEAD FLASHING 03 APPLY BEAD OF SEALANT AT BACK ® REMOVE PREVIOUSLY APPLIED TAPE, A GALVANIZED 2 1/2" OF WINDOW FLANGE & SET METAL DRIP EDGE ALLOWING WRB TO LAY FLAT OVER VENTED WINDOW USING PAN HEAD SCREWS HEAD FLASHING. APPLY NEW 5/8" SHEETROCK TO FACILITATE INSPECTION. DBL 2x TOP PLATE W/ SHEATHING TAPE OVER DIAGONAL APPROVED HURRICANE ANCHOR AT ENDS OF EACH CUT - SEE DIAGRAM. SECTION A THROUGH WINDOW JAMB SEALANT BEAD BEHIND MOUNTING FLANGE. SEALANT BEAD BETWEEN - FLASHING AND MOUNTING FLANGE. WRB FLASHING EXTERIOR DOOR FLASHING WRAP WRB INTO OPENING 45° CUT--, WRB N 00 8 WRB ' REMOVE BOTTOM WRB FLAP MODIFIED "I" CUT IN WRB yl W INSTALL VULKUM AT THRESHOLD PER MFR. INSTRUCTIONS. INSTALL DOOR, SHIM DOOR TO LEVEL, PLUMB AND SQUARE DOOR IN OPENING. 0 I� FLASHING U) .I�ME !l CL almil I 0 0 1 do � -L-� WRB I I I I APPLY HEAD FLASHING, EXTENDING 10" BEYOND DOOR ROUGH OPENING. C TEMPORARILY TAPE UP TOP FLAP APPLY JAMB FLASHING TO BOTH SIDES OF DOOR FROM DOOR FRAME TO WRB, EXTENDING 8 1/2" ABOVE DOOR ROUGH OPENING. UNFOLD TOP FLAP AND COVER DIAGONAL CUT IN WRB WITH SHEATHING TAPE. NOTE: ALL FLASHING WILL BE SELF ADHERING AND ROLLED SMOOTH & FLAT WITH A J -ROLLER TYPICAL DOOR FLASHING HEADER FOAM INSULATION DOOR FRAME PER DOOR MANUF. WEATHER STRIPPING PER DOOR MANUF. THRESHOLD AND WEATHERSTRIPPING PER DOOR MANUF. INSTALL "Z" FLASHING OVER 1X TRIM IF DOOR IS NOT COVERED WITH OVERHANG OR PORCH EXTERIOR FINISH FLASHING U) C O.S.B. w 26 GA. GALVANIZED "Z" APPROVED HOUSE WRAP HOUSE � 0 0 WRAP DOWN TO DOOR FRAME SEAL w o WITH WATERPROOF TAPE w O 1X WOOD TRIM o CAULK Q U) DOOR STOP PER DOOR MANUF. w a0 z WEATHER STRIPPING PER DOOR w CHIMNEYS AND WALLS MEET MANUF. ROOF) HOLD 1/4" OFF CONCRETE CAULK UNDER THRESHOLD WITH NON -HARDENING WATERPROOF CAULK STEP DOWN TO OUTSIDE SURFACE TYPCIAL ROOF FLASHING C 26 GA. GALVANIZED "Z" FLASHING (WHERE EXTERIOR BUILDING PANELS JOIN HORIZONTALY) B 26 GA. GALVANIZED 5 X 5 ANGLE FLASHING (WHERE 12 SEE CHIMNEYS AND WALLS MEET FIBERGLASS SHINGLES ELEV� ROOF) ON 15# FELT OVER O.S.B. W/ 1/2" CLIPS 2X6 FASCIA 26 GA. PRE-ENGINEERED A GALVANIZED 2 1/2" TRUSSES @ 24" O.C. METAL DRIP EDGE INSULATION PER CODE VENTED 1/2 CEILING BOARD or HARDIE-SOFFIT@ 5/8" SHEETROCK DBL 2x TOP PLATE W/ APPROVED HURRICANE ANCHOR AT ENDS OF EACH TRUSS 24" WIDE -26 GAUGE ROLL VALLEY FLASHING AT ALL VALLEYS A 2 3/4" B C L 0 N N � CV 04 5" 3/8" or 5/8" 26 GA. GALVANIZED 26 GA. GALVANIZED 32 GA. GALVANIZED 2 1/2" MTL DRIP EDGE 5 X 5 ANGLE FLASHING "Z" FLASHING Q D w ti Z O tds F— Z_ true design studios LL 4745 SUTTON PARK CT., SUITE 402 JACKSONVILLE, FLORIDA 32224 W P 904.821.5200 F 904.992.8700 WWW.TRUEDESIGNSTUDIOS.NET U U) W Q z W } D .� LL 0 �--t o 07 v. z W Q V U) (D _ z_ Q D 14701 PHILIPS HWY, STE 300 Z JACKSONVILLE, FL 32256 Q www.dreamfindershomes.com < W U) 2 W W Q Lu C) U) c) O n z = 0 w pO U) 1- 0 w U) N 0 ATLANTIC BEACH COUNTRY CLUB O LOT 136 O O DUVAL COUNTY/FL p 0 PROJECT NO: Q 2018.003342 DATE: 04-25-18 0 DRAWN: JAC U CHKD: DWR R VV REVISIONS: F- F - 08 -23-18 KLH U Z 10-19-18 DWR 0 11-14-18 JBB U 11-28-18 DWR w O 01-08-19 DWR LL 0 W A500 07 F -- O z CONTINUOUS STARTER STRIP OVER FLASHING INSTALLED PER MANUF WRITTEN SPECS —2 MTL DRIP FLASHING W/ HEMMED EDGE SET IN CONT BED OF SEALANT SILL PLATE FIBERCEMENT LAP SIDING o OVER APPROVED HOUSEWRAP O INSTALLED PER MANUF O WRITTEN SPECIFICATIONS FIBERCEMENT LAP SIDING — EXTEND HOUSEWRAP OVER APPROVED HOUSEWRAP OVER NAILING FLANGE INSTALLED PER MANUF PROJECT NO: 2018.003342 WRITTEN SPECIFICATIONS MTL DRIP FLASHING W/ CONTINUOUS BEAD OF HEMMED EDGE SET IN CONT SEALANT at PERIMETER BED OF SEALANT 5/4x6 FIBER CEMENT _ HEADER (RE: _ STRUCT DWG,S) EXTEND HOUSEWRAP = OVER WINDOW FLANGE 2x2 OVER 5/4x6 FIBER CEMENT = SET IN CONTINUOUS BED OF SEALANT EXTEND 12" SELF -ADHERING = SILL SEAL MEMBRANE FLASHING OVER /4' JOINT W/ BACKER WINDOW FLANGE SET IN CONT ROD & SEALANT BED OF SEALANT MTL DRIP FLASHING W/ HEMMED EDGE SET IN CONT 1/2" BED OF SEALANT 02015 TRUE DESIGN STUDIOS INC 2x6 PT (RIP TO 5" NOP" 4x4 PT POST (RE: STRUCT DWGS) SCALE: 1%2" = l'-0" 5/4x8 TRIM (RIP TO 7" NOM)(TYP) %2' SHTHG (TYP) 2x4 PT WINDOW HEAD 02015 TRUE DESIGN STUDIOS INC. SCALE: 1Y2' = 1' 2x4 HANDRAIL (SLP TOP) 2x4 TRIM DECOR BALUSTERS PER BLDR SPEC 2x4 BOTTOM RAIL COLUMN FRAMING 6 RAILING 02015 TRUE DESIGN STUDIOS INC. SCALE- 1Y2" = 1'-0" �01 02015 TRUE DESIGN STUDIOS INC. SCALE: 1%2' = 1'-0" WINDOW JAMB 02015 TRUE DESIGN STUDIOS INC CV SCALE: 1%2" = l'-0" CERAMIC TILE EXTENU HUUSEWKAt OVER WINDOW SILL %4' JOINT W/ BACKER ROD & SEALANT 5/4x6 FIBER CEMENT (SLP TOP) FIBERCEMENT LAP SI OVER APPROVED HO INSTALLED PER MANI WRITTEN SPECIFICAI WINDOW SILL 02015 TRUE DESIGN STUDIOS INC. SCALE: 1Y2" WALL ASSEMBLY VINYL/WOOD/FIBER CEMENT SIDING (INSTALLED IN ACCORDANCE WITH CLADDING MANUFACTURER'S INSTALLATION RECOMMENDATIONS) SYSTEMS O SHEATHING WOOD OR Ll GA. METAL STUDS. CERAMIC TILE INSTALLED OVER "THIN -SET" ADHESIVE OVER MIN. 1/2" DensShield OR EQUIV. SKID RESISTANT FLOOR TILE INSTALLED OVER "THIN -SET" ADHESIVE ON MIN. 1 1/2" CEMENTITIOUS MUD SET -SLOP TO DRAIN (MIN 1" THICK AT DRAIN) WATERPROOFING NOTE: INSTALL JOINT MESH IN CORNERS AND SEAMS OF WALL BOARDS WITH "HYDROGUARD" WATER PROOFING OR EQUIV. COVER ALL SCREW HOLES AND PENETRATIONS WITH WATERPROOFING CAULK ALL CORNERS & JOINTS OF DISSIMILAR MATERIALS. RECESSED SHOWER DETAIL 1/8" GAP RECOMMEND[ AT PANEL EDGES ZIP SYSTEM O TAPE (II` OVER ALL JOINTS IN ZI SHEATHING.) OVERLAP TAPE A MINII 1" AT ALL T -JOINTS 1/8" GAP RECOMMENDI FASTEN ZIP SYSTEM CR ENGINEER-OF-RECOR[ Q w r X r r z O w z Of true design studios a- 4745 SUTTON PARK CT., SUITE 402 JACKSONVILLE, FLORIDA 32224 P 904.821.5200 F 904.992.8700 w w WWW.TRUEDESIGNSTUDIOS.NET Q U U) 0 w .� z 0 W D LL O � � a o LC) U) w J Q U) V z Q ry i Ur) V 14701 PHILIPS HWY, STE 300 z JACKSONVILLE, FL 32256 Q www.dreamfindershomes.com ry w 07 w _ w w Q w C) c) O U)C) C z = 0 w z X00O � w � o Q � � N ATLANTIC BEACH COUNTRY CLUB o LOT 136 O O DUVAL COUNTY/FL p 0 PROJECT NO: 2018.003342 Q z DATE: 04-25-18 Q DRAWN: JAC CHKD: DWR REVISIONS: F- 08-23-18 KLH to ZIP SYSTEMS ® SHEATHING WITH 10-19-18 DWR o 11-14-18 JBB U LAP SIDING AT SLAB ON GRADE 11-28-18 DWR o These construction details are provided to assist in the installation of Zip System ® product(s) 01-08-19 DWR U_ and may not apply to every situation. Manufacturer accepts no responsibility or liability for the 0 w use of these or other construction details. D 2 2 2019 U) A501 07 H O z NOTE: ALL PERMANENTLY INSTALLED INTERIOR AND EXTERIOR LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS AS PER FBC R404.1 @2018 TRUE DESIGN STUDIOS, INC. -VV/1LL 0-AJIVIiC LOC @ 9'-0" AFF 1st LEVEL ELECTRICAL PLAN SCALE: %4" = 1'-0" Q 0 w 7a O 0 tds z w true design studios 0- 4745 SUTTON PARK CT., SUITE 402 JACKSONVILLE, FLORIDA 32224 W P 904.821.5200 F 904.992.8700 WWW.TRUEDESIGNSTUDIOS.NET -I !^^ !U VJ W Q 'OdleZ 3 W LL O o O LO U) w J Q U cn O Z Q 0 1 (D 14701 PHILIPS HWY, STE 300 Z JACKSONVILLE, FL 32256 Q www.dreamfindershomes.com < 0 W U) W r f— W .__I LLJ U U) c) o 0. z= 0 w z o p O J w Q � j N � ATLANTIC BEACH COUNTRY CLUB O LOT 136 0 O DUVAL COUNTY/FLI O O PROJECT NO: O 2018.003342 z DATE: 04-25-18 `Q_ DRAWN: JAC `— CHKD: DWR U REVISIONS: 08-23-18 KLH Cn Z 10-19-18 DWR Q 11-14-18 JBB U 11-28-18 DWR w 01-08-19 DWR O 0 El 00 U) O z ELECTRICAL LEGEND SWITCH f� TV OUTLET THREE-WAY SWITCH SPEAKER FOUR-WAY SWITCH ,Oso THERMOSTAT $R RHEOSTAT *SD SMOKE DETECTOR DUPLEX CM CARBON MONOXIDE DETECTOR AFCI DUPLEX CEILING LIGHT �I GFCI DUPLEX RECESSED CEILING LIGHT COUNTERTOP DUPLEX RECESSED EYEBALL LIGHT (5CT SWITCHED DUPLEX WALL HUNG LIGHT 6 220 VOLT OUTLET EYEBALL LIGHT 220 6 QUADRUPLEX LANDSCAPING LIGHT CLNG 8 CEILING DUPLEX FLOODLIGHT FLOOR FLOOR DUPLEX � � VENT JUNCTION H° VENT AND LIGHT DB DOOR BELL °0 HEAT AND LIGHT C GARAGE DOOR PO HEAT AND VENT PH PHONE OUTLET Ho HEAT, VENT AND LIGHT NOTE: ALL PERMANENTLY INSTALLED INTERIOR AND EXTERIOR LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS AS PER FBC R404.1 @2018 TRUE DESIGN STUDIOS, INC. -VV/1LL 0-AJIVIiC LOC @ 9'-0" AFF 1st LEVEL ELECTRICAL PLAN SCALE: %4" = 1'-0" Q 0 w 7a O 0 tds z w true design studios 0- 4745 SUTTON PARK CT., SUITE 402 JACKSONVILLE, FLORIDA 32224 W P 904.821.5200 F 904.992.8700 WWW.TRUEDESIGNSTUDIOS.NET -I !^^ !U VJ W Q 'OdleZ 3 W LL O o O LO U) w J Q U cn O Z Q 0 1 (D 14701 PHILIPS HWY, STE 300 Z JACKSONVILLE, FL 32256 Q www.dreamfindershomes.com < 0 W U) W r f— W .__I LLJ U U) c) o 0. z= 0 w z o p O J w Q � j N � ATLANTIC BEACH COUNTRY CLUB O LOT 136 0 O DUVAL COUNTY/FLI O O PROJECT NO: O 2018.003342 z DATE: 04-25-18 `Q_ DRAWN: JAC `— CHKD: DWR U REVISIONS: 08-23-18 KLH Cn Z 10-19-18 DWR Q 11-14-18 JBB U 11-28-18 DWR w 01-08-19 DWR O 0 El 00 U) O z 40 NOTE: ALL PERMANENTLY INSTALLED INTERIOR AND EXTERIOR LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS AS PER FBC R404.1 A 2nd LEVEL ELECTRICAL PLAN ©2018 TRUE DESIGN STUDIOS, INC. ------------------------ I I I I I I I I I I L--� I I I - I F--, I I I I I I I I I I I I I i I i i i I I I I I I I I I I I I I I I I I I L— — — — — — — — — — — — — — — — — — — — — — — — — — SCALE: Y4" = l'-0" X z 0 0 W Z true design studios a 4745 SUTTON PARK CT., SUITE 402 LL JACKSONVILLE, FLORIDA 32224 wP 904,821.5200 F 904.992.8700 WWW.TRUEDESIGNSTUDIOS.NET —I Q C7 r) W f— Z 3F, 0 w 0 LL 0 r � U) L11 J or Q V z ry O U) 0 14701 PHILIPS HWY, STE 300 z JACKSONVILLE, FL 32256 www.dreamfindershomes.com Of 0 Uj w W r LU J W U C) � o U) zz ~ w 0 � z 00 J W � 0 Q Cif :D N 0 ATLANTIC BEACH COUNTRY CLUB O LOT 136 O O O DUVAL COUNTY/FL p O I PROJECT No: 0 2018.003342 O DATE. Z 04-25-18 0 DRAWN. JAC F— CHKD: DWR U D REVISIONS: Cif 1- 08-23-18 KLH U) 10-19-18 DWR z O 11-14-18 JBB U 11-28-18 DWR 01-08-19 DWR LL 0 W 0 U F_ 0 Z ELECTRICAL LEGEND SWITCH TV OUTLET THREE-WAY SWITCH O SPEAKER FOUR-WAY SWITCH THERMOSTAT $R RHEOSTAT *SD SMOKE DETECTOR DUPLEX $CM CARBON MONOXIDE DETECTOR AFCI DUPLEX CEILING LIGHT GFCI DUPLEX ', RECESSED CEILING LIGHT �CT COUNTERTOP DUPLEX � RECESSED EYEBALL LIGHT SWITCHED DUPLEX WALL HUNG LIGHT 6 220 220 VOLT OUTLET EYEBALL LIGHT 6 QUADRUPLEX LANDSCAPING LIGHT CLNG CEILING DUPLEX FLOODLIGHT FLOOR FLOOR DUPLEX VENT JUNCTION o VENT AND LIGHT DB DOOR BELL °0 HEAT AND LIGHT GD GARAGE DOOR ®0 HEAT AND VENT PH PHONE OUTLET Mo HEAT, VENT AND LIGHT NOTE: ALL PERMANENTLY INSTALLED INTERIOR AND EXTERIOR LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY LAMPS AS PER FBC R404.1 A 2nd LEVEL ELECTRICAL PLAN ©2018 TRUE DESIGN STUDIOS, INC. ------------------------ I I I I I I I I I I L--� I I I - I F--, I I I I I I I I I I I I I i I i i i I I I I I I I I I I I I I I I I I I L— — — — — — — — — — — — — — — — — — — — — — — — — — SCALE: Y4" = l'-0" X z 0 0 W Z true design studios a 4745 SUTTON PARK CT., SUITE 402 LL JACKSONVILLE, FLORIDA 32224 wP 904,821.5200 F 904.992.8700 WWW.TRUEDESIGNSTUDIOS.NET —I Q C7 r) W f— Z 3F, 0 w 0 LL 0 r � U) L11 J or Q V z ry O U) 0 14701 PHILIPS HWY, STE 300 z JACKSONVILLE, FL 32256 www.dreamfindershomes.com Of 0 Uj w W r LU J W U C) � o U) zz ~ w 0 � z 00 J W � 0 Q Cif :D N 0 ATLANTIC BEACH COUNTRY CLUB O LOT 136 O O O DUVAL COUNTY/FL p O I PROJECT No: 0 2018.003342 O DATE. Z 04-25-18 0 DRAWN. JAC F— CHKD: DWR U D REVISIONS: Cif 1- 08-23-18 KLH U) 10-19-18 DWR z O 11-14-18 JBB U 11-28-18 DWR 01-08-19 DWR LL 0 W 0 U F_ 0 Z