720 TRITON RD ERES19-0100 NEW SERV PERM ELECTRICAL LOAD CALCULATIONS FOR 720 TRITON RD. NEC 220-82 - NEW DWELLING (OPTIONAL METHOD) FLBC 2017 TABLE E3602.2: MINIMUM SERVICE LOAD LIGHTING & RECEPTACLES * (3VA/sf x 2,000sf area) 6,000 APPLIANCES (2x1,500VA) 3,000 WATER HEATER I (master bedroom) 18,000 4 TON AC AC 14,000 WASHER 1.5 kVA 1,500 WATER HEATER II (kitchen) 18,000 DRYER 5kVA 5,000 OVEN plus COOK TOP 9.0kVA 9,000 DISHWASHER 1.2kVA 1,200 MICROWAVE 1,500 GARBAGE DISPOSAL 500 REFRIGERATOR w. FREEZER 800 POOL panel (continuous load) - POOL PUMP: 240v, 10amps, 2,400 - SALT WATER CHLORINATOR: 240v, approx 5-8 amps 1,920 - POOL HEAT PUMP: 240v, 50 amps None - LP/NG POOL HEATER: 240v, 3 amps (future installation?) 720 - POOL LIGHTS: 12v, 3.5 watts each 7 - Stem wall lights (6 x 13W @120V) 78 POOL Total 5,125 DEMAND FACTORS: First 10KW @ 100% 10,000 Continuous @ 100% (A/C + pool panel) 19,125 REMAINDER AT 40% (54,500 x .40 =) 21,800 SERVICE LOAD (VA) 50,925 CURRENT (A) 212.2 DWELLING SERVICE LOAD (A): 298.2 * Heated area is - 2,000sf.; total area is - 2,700sf (incl. patio, carport, walkway) FLBC 2017 TABLE E3704.2(1 ) FEEDER LOAD CALCULATION TABLE E3704.2(1) load for SERVICE PANEL 1: Lighting and receptacles: 3VA/sf x 720sf=2,160VA (First 3K at 100%, the rest @ 35%) 2,160 Appliances and motors: WATER HEATER I (master bedroom) (assume power factor of 1) 18,000 Fixed motors: None Electric clothes dryer: (incl. in Subpanel 2) Cooking appliances: (incl. in Subpanel 2) Largest of heating or cooling load: • HVAC (4 TON AC AC @ 100%) 14,000 FEEDER LOAD (VA) 34,160 CURRENT (A) 142.3 SUB-PANEL 1 BREAKER (A) 150.0 TABLE E3704.2(1) load for SERVICE PANEL 2: Lighting and receptacles: LIGHTING (3VA/sq.ft x 1,280sf area) +650sf exterior: patio,car port,etc. 5,790 (Note: Exterior not required by code to be included) 2 x 1,500 Amp.for 20 Amp. breakers in kitchen (portable appliances) 3,000 3,000VA Total @ 100%first 3,000VA plus 35%the rest (5,790*.35=2,026VA) 5,026 Appliances and motors (>4, ©75% load factor): WATER HEATER II (kitchen) 18,000 WASHER 1.5 kVA 1,500 OVEN plus COOK TOP 9.OkVA 9,000 DISHWASHER 1.2kVA 1,200 MICROWAVE 1,500 GARBAGE DISPOSAL 500 REFRIGERATOR w. FREEZER 800 Total load of appliances and motors @ 100% 32,500 Total load of appliances and motors @ 75% 24,375 Fixed motors: None Electric clothes dryer: DRYER 5kVA 5,000 Cooking appliances (none rated >1.75 kVA) Largest of heating or cooling load (none) (incl. in Subpanel 1) FEEDER LOAD (VA) 34,401 CURRENT (A) 143.3 SUB-PANEL 1 BREAKER (A) 150.0 POOL SERVICE PANEL: - POOL PUMP: 5.4 amps @ 230V or 10.8 Amp @ 115V 1,242 - SALT WATER CHLORINATOR: 240v, approx 5-8 amps 1,920 - POOL HEAT PUMP: 240v, 50 amps None - LP/NG POOL HEATER: 240v, 3 amps (FUTURE?) 720 - POOL LIGHTS: 2 x 47W @12V each 1,128 Total pool equipment and pool lighting load 5,010 Stem wall lighting @ 100% 13 x 6=78 VA 78 DEMAND FACTORS: SERVICE LOAD (VA) 5,088 CURRENT (A) 21.2 POOL SERVICE PANEL BREAKER (A) 62 A per leg, 168 A max., 120, 240 V or 120, 208 V single phase, 60 Hz CONDUCTORS: • All conductor rated for 90°C (194°F) • Ungrounded service conductors in accordance with 2017 FLBC (Residential) E3603.1.1 with an ampacity of not less than 83 percent of the service rating. Service cable (from JEA transformer to house) is three single 350 MCM direct-buried cables: two for phase and one for neutral. 350 MCM XLP/USE-2/RHH/RHW-2 Building Wire Feeder cables: 2/0-2/0-2/0 w.-1/0 Ground AL (from Subpanel 1 and Subpanel 2 to main breaker panel) • Conductor rating: 150 A, ambient temp. adjustment 150*.96 = 145 Amp. Based on ASHRAE Temperature Tables for 35°C for Mayport, FL 8 ft ground rod installed at the main breaker panel @ > 2 feet from house footing. 10-3 NM-B (with ground) cable used for dryer. Lighting wire inside stem wall. • Use schedule 40 conduit and THHN wire: __,....iiiiiigamisigialaBli01' Southwire 300 ft. 14/3 BlackNVhite/Green Solid CU THHN Tri-Wire $78 Wire for underground burial from pool panel to main breaker panel: • .; 125 ft. 8/3 Gray Stranded CU UF-B W/G Wire • #8 AWG undgerground wire for lamp posts, pumps and other loads • UF outdoor direct burial wire is resistant to moisture and light • $162 per 125-foot coil. 140 feet needed? Fire alarm wire: Use the red wire for connection to other alarm units, black for hot, white for neutral, bare for ground. 250 ft. 14/3 Solid Romex SlMpull CU NM-B W/G Wire ----- E3803.7 Bushing. Rome;. siMpudr T A bushing, or terminal fitting, with an integral "0°°"""`""" 'U"' bushed opening shall be installed on the end of a conduit or other raceway that terminates underground where the conductors or cables emerge as a direct burial wiring method. A seal • incorporating the physical protection characteristics Designed for: of a bushing shall be considered equivalent to a • Fast Pulling bushing. [300.5(H)] • Easy Stripping • Tear Resistance • Reduced Burn-Through R Brand SIMpuIPRomexo Indoor Wire Copper NM-B Cable Nonmetallic-Sheathed Cable.600 Volt.Copper Conductors.Color-Coded Jacket.Four Conductor • Available With Two Neutrals. SlMpu!P Jacket Designed for Easier Pulling. APPLICATIONS Southwire Romex''' Brand SlMpu/P NM-B (nonmetallic-sheathed) cable may be used for both exposed and concealed work in normally dry locations at temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified in the National • Electrical Code. NM-B cable is primarily used in residential wiring as branch circuits for . outlets, switches, and other loads. NM-B cable may be run in air voids of masonry block or tile walls where such walls are not wet or damp locations. Voltage rating for NM-B cable is 600 volts. STANDARDS & REFERENCES Southwire Romex''Brand SlMpul(r'NM-B cable complies with the following: • Listed per UL Standard 719 • • UL 83 (Conductor Construction) • ASTM B-3 and B-8 • Federal Specification A-A-59544 • National Electrical Code, NFPA 70 • REACH/RoHS Compliant CONSTRUCTION • Southwire Romex®Brand Sl Mpue NM-B cable is manufactured as 2, 3, or 4 conductor cable, with a bare ground wire. Copper conductors are annealed (soft)copper. Stranded conductors are compressed stranded. Conductor insulation is 90°C-rated polyvinyl • chloride (PVC), nylon jacketed. Romex®Brand SlMpull®NM-B cable is designed for • easier pulling, resulting in easier installation.The cable jacket is color-coded for quick size identification; White - 14 AWG, Yellow- 12 AWG, Orange- 10 AWG, and Black-8 AWG and 6 AWG. )K -(t) 51-1-1' r' oWl—eX .a 4___,2,( • tit•• •�' Southwire Power of Connections.'"' ••' • ... 02018 Southwec Company.LLC.All rghts reserved.(dRegislered Trademark and'"f rademark of Soulhwrte Company,LLC.One Southwire Dove.Carrollton.GA 30119,USA 6113118 Rev 0 Printed from NIPSCO.com SERVICE ENTRANCE - UNDERGROUND 04-01-17 NIPSCO Single & Three Phase ER 19-270-P 200, & 320/400 Amp PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. PREVIOUS REVISION ORIGINATED PREVIOUS NUMBER 07-01-15 03-94 ER 1-220-B,07-12-93 ER 19-750.03-21-94 ER 19-755.03-21-94 LATEST REVISION: Updated specification on Approved 4 Jaw- 200 AMP Meter Sockets to make easier to understand. REFERENCE: / National Electrical Code (IEC/NEC), latest revision ER 5-500, 5-550, 7-500, 13-230, latest revision UL 414, latest revision ANSI C12.7, latest revision SPECIFICATION: -Wt#. UNDERGROUND INSTALLATION L�L t— i II fi _III 111 1E- II iJ ISI l 11111 11 IIutyei p IL Stt4 II 1i JI II I■II IMI II II IC r II If SOI *II IMI II IC l II I I II II II I 1111 II IIIC C III 11 CI II II 1■l1 ILII II IC II II III II I■/I I■11 II IC 11 The riser --- T C- ■I conduit Shall J 1I 0 MII ' ■C be installed I L.. in or the left ]I I� NI II 5' IL knock-out =- MC Or '' ■` 11 IN ■i I[ for pedestal P L style meter I i1 1 ■1 111 11 IL sockets 1 Meter Box, conduit, and j1 IE 3'-5' ■ associated hardware The riserprovided and installed conduit shall (see spec �1 it I ■I 1■-�I IL . � by the Customer be rigid steel 1i 1, 11— 1.8.14) See ER 5-500 and 5-550 or Schedule ■I 122'ta1 IL 1 IL 80, PVC 11 I 11 To neutral ■C Scon CI 1 ■I I■■M1 IC perductor IEC/NEC IC Final I 11 f ■I Service \-.Grode 1M11 1 II inmra[ I[ disconnecting - ■111e11 -_..-_.... ■I /means u=n� il�u=o- =1 'it.--11M a= Il a= --tea=IE o f `/ 11 1-11K I: IL-1 JL - ...I-I - -11= �Ilil�T u. � . I 1■I— ���' 18' Min. ---24' _ -1M / — u 1 \ \ l rp 4 _- Insulated LAII grounding Bushing per IEC/NEC t/ WINgifiallif 41) eGoe, pcme,e, DENOTES REVISION NORTHERN INDIANA PUBLIC SERVICE COMPANY Printed from NIPSCO.com 04-01-17 SERVICE ENTRANCE - UNDERGROUND ER 19-270-P Single & Three Phase NIPSCO PAGE 2 OF 6 200, & 320/400 Amp 1. GENERAL: 1.1 Residential electric and gas meters should both be located on the same side of the home within the front 1/3 to aid meter reading, testing and service, and to aid emergency response in the event of a fire or some other hazardous condition. 1.2 rhe riser conduit shall be installed in the left-most or right-most, bottom knockout of the meter box. For close lot lines, concrete, asphalt, or sites where our trenching equipment can not access; conduit shall be installed by the customer to a clear location in which NIPSCO will be able to install the service. 1.3 Bonding bushings and jumpers shall be used to maintain electrical continuity to service equipment enclosures when the entire concentric knockout is not removed. 1.4 The service disconnecting means shall be installed at a readily accessible location nearest the point of entrance of the service entrance conductors. 1.5 For grounding, refer to ER 7-500. 1.5.1 Ground rods and ground wires shall be installed a minimum of 24" away from the riser pipe to permit the installation and maintenance of service cables. 1.6 For larger service sizes or long service runs,customer<shallc,heck with Local Operating office,for required riser conduit size, and meter box needs. FOP conduit lengths in excess of 10' long, or in the case of conduit systems (any including elbows and/or couplings), refer to EU 2-160, for cable pulling requirements and conduit sizes. 1.7 Conduit& Conductor Recommendations: • Service Entrance Service Conduit(per IEC/NEC) Service Entrance Condggtors Size (See Notes below)' Grounding Service Entrance Residential .All Other (Cu Only) Riser Run ltp 3W 120/240V 'Services 100 Ams 2 Inch 1 '/2 or Cu #3 Cu #8 p (See 1.6) 2 Inch #2 Al #1 Al 2 '/2 Inch 2 Inch 2/0 Cu 3/0 Cu 200 Amps (See nch Y2 #4 2 Inch 4/0 Al 250 KCM Al 320/400 3 Inch 3 Inch 400 KCM Cu • .500 KCM Cu 1/0 Amps (See 1.6) 3 '/2 Inch 600 KCM Al 700 KCM Al Note: Approved service entrance cable,with weather-roof fittings, may be used-between socket and the general service disconnect, where permitted by local authority. All recommendations for conductor sizes assume a 75`C temperature rating. Larger; conductor sizes may be necessary if Iowerismperature ratings exist. Refer to IEC/NEC 310-16 for proper conductor sizes,.vari this case. The following are the recommended insulation types, based on 75'C minimum temperature rating: RH, RHH, RHW, THHW, THW, THWN, THHN, XHHW, USE. • • DENOTES REVISION NORTHERN INDIANA PUBLIC SERVICE COMPANY 0 • . • 0 . , M. • ,. 520 • / w l 1.1!- - - - I - ,,...,,... i. E. ..,:;>a F. G. • T10000RT, T40000RT Series e Control System with Transformer and Pow:A, or Load Center crus •All-in-one control power for pool/spa installation • Easy to wire • Can house additional Intermatic mechanisms and compo)lents • Heavy-duty Type 3R steel Indoor/Outdoor power and load centers Transformer Model# Description Mechanism Supply Voltage Watts Input Voltage,60 Hz Output Voltage E. T10004RT1 Power Center with T104M 240 VAC 100 120 VAC,1 Amp 12 or 13 VAC T10004RT3 Power Center with T104M 240 VAC 300 120 VAC,3 Amp 12, 13,or 14 VAC F. T40003RT3 Load Center with T103M 120 VAC 300 120 VAC,3 Amp 12, 13,or 14 VAC T40004RT1 Load Center with T104M 240 VAC 100 120 VAC, 1 Amp 1gor 13 VAC T40004RT3 Load Center with T104M 240 VAC 300 120 VAC,3 Amp 12, 13,or 14 VAC G. T40000RT3 Load Center Only — 300 120 VAC,3 Amp 12, 13,or 14 VAC .114 Ratings: Did You Know ? T10000RT Series: ' Power Center Rating:62 A per leg,168 A max.,120,240 VAC or Po208 VAC iphase,so Hz. May transformers that power LED's do not comply with • Power err Centerr Dimensions: ensions:12"(30.5 cm)H x 12"(30.5 cm)W x 4 '(1o.scm)D the NEC Code 680.23 requirements. The code states T40000RTSeries: transformers used for the supply of underwater luminaries Load Center Rating:100 A,120,240 VAC or 120,208 VAC single phase,60 Hi. rTt1J;t be listed and marked for pool and spa transformer Load Center Dimensions: 2034"(52.7 cm)H x 123A"(32.4 cm)W x OA"(10.8 cm)D S . Listed pool and spa transformers must comply with UL-379 and CSA TILB44A standards. Switch Rating: •30 A Resistive/Induclive,Tungsten or 1000 VA Pilot Duty each pole 120,208,240 VAC •2HP(24FtA),120VAC Umn-compliant transformers increase the potential for •5 HP(28 FLA),240 VAC Operating Temperature Range:-40°F to 130°F(-40°C to 54°C) SE:Vere injury and electrocution and raise liability concerns I! Warranty:1 year -fc r contractors and installers. See page 124 for further information on mechanisms. Wiring devices may be installed in this power or load center (order(4)21 T156A standoffs for mounting).See page 154. For replacement parts,trippers and accessories see page 153. www.intermatic.com 131