705 ATLANTIC BLVD. FIRE COMMENTS COMM19-0007 PG. 1City of Atlantic Beach
Building Department
r� 800 Seminole Road
j� Atlantic Beach, Florida 32233-5445
Phone (904) 247-5826 • Fax (904) 247 -5845
E -mail: building-dept@coab.us
City web -site: http://www.coab.us
APPLICATION NUMBER
(To be signed by the Building Department.)
Date routed: 3 11
APPLICATION REVIEW AND TRACKING FORM
Property Address: _70S
Applicant: V1 4()?_ I
Project:Rotg_D(24' n
Deartment review required Yes No
uild'
Planning & Zoning
Tree A nist-ratar _
Public Works
Public Utilities
Public Safety
re Services
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St. Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department
First Review:
[]Approved. �penied.
❑Not applicable
(Circle one.)
Comments:
BUILDING
PLANNING & ZONING
Reviewed by:
Date:
TREE ADMIN.
Second Review:
❑Approved as revised. ❑Denied.
❑Not applicable
PUBLIC WORKS
Comments:
PUBLIC UTILITIES
PUBLIC SAFETY
Reviewed by:
Date:
FIRE SERVICES
Third Review:
❑Approved as revised. ❑Denied.
❑Not applicable
Comments:
Reviewed by:
Date:
Revised 05/19/2017
COMM 19-0007
705 Atlantic By
Returned for Corrections:
The plans submitted for review have been returned for corrections. Please correct and or provide the
additional requested information to obtain plans approval. When resubmitting corrected sheets, provide a
type written itemized narrative letter responding to our comments and directing the plans reviewer to the
sheets the changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER "WILL" RESULT IN
A RETURNED FOR CORRECTIONS PERMIT STATUS. Revised sheets should be clouded, clearly
showing areas were changes or corrections have.occurred and re-inserted with the original set of
drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission
please make sure that written narrative is submitted under correspondence along with a "complete set"
(not just the revised sheets) of electronic documents. When submitting electronic plans, each discipline
shall upload a single PDF file containing multiple sheets rather than separate PDFs for each
sheet. Please re -upload in this fashion.
Key Plan:
Provide key plan of building showing adjacent occupancy type with required separation of occupancies
per 6th Edition FFPC, NFPA 101 Table 6.1.14.1.4.
Life Safety Floor Pian:
The City of Jacksonville's Fire Marshal's Office requires the submittal of a Life Safety Floor Plan for
building permits for all new construction and existing building alterations in order to ascertain if occupancy
is currently code compliant and to assist fire inspector in performing Life Safety Inspections. Please
provide a Life Safety Plan to include all the following information on one page. If Life Safety Plan was
submitted and you are receiving this comment, it means that all of the required info listed below was not
included in your original submittal. It is understood that all listed items may not apply in your situation.
Required Occupant Load Calculation:
• Provide design occupant load using table 7.3.1.2 of NFPA 101 2,015 edition. Area calculations should be
shown with graphic seating configurations or fixtures in order to substantiate occupant load chosen.
Exit Locations:
• Designate main entrance and all secondary exits. All required exits shall terminate at a "public way".
Access to the -public way shall be accessible and must be via a stable, firm, and slip resistant conveyance
such as a concrete sidewalk with a min. 5'x5' landing and 44" walkway. Multi story buildings should
designate area of rescue with required communication means. Separation of exits using the one half
(non -sprinkled) or one third (sprinkled) the diagonal distance rule should be shown on plans.
Required Egress Capacity:
• Egress inches for means of egress components (doors, stairs, etc.)
Required measurements: (Worst case only need be shown.)
• Dead end corridors measurements.
• Common path of travel measurements.
• Total travel distance to exits.
Required separation:
• Show all fire barriers, smoke barriers, and smoke partitions. All rated walls per.new directive from
building official wall detail needs to include UL.listing and needs to confirm by architect or engineer as
being accurate.