705 ATLANTIC BLVD FIRE COMMENTS COMM19-0007 PG. 2Required Lock Latch details: • Lock/Latch details: Panic Hardware, Thumb turn lock, Key Lock with indicator and required signage. Required Electrical Stop/Disconnect Details: • Any required Emergency stops or Shunt trips. • Main Electrical disconnects access/location. Required markings of means of egress: Exit signs to include tactile exits signage. Required fire extinguisher Locations: • Locations per NFPA 1.0. Required Emergency lighting: Show emergency illumination. Required Lightweight Truss Signage: • Location of lightweight truss signage per FAC 69A-60.0081 (if applicable). Please see below for clarification to requirement. http_://www.coi.net/Departments/PIan nina-and-Develoo ment/Docs/BuiIdina-Inspection-Division/bulletin-f- 01-09-light-weight-truss-rule.aspx Also if occupancy is to have any permanent open flame devices such as fire pits, gas grills, patio heaters, gas lamps etc. they should be shown on life safety plan for approval. See NFPA 1 10.11 (separate fire permits will be required for installation of these features). Floor Layout Plan: Document on plans the floor arrangement of furnishing's or equipment to be used to substantiate the arrangement of means of egress and occupant load posting for each assembly area. Floor layout plan should show arrangement of means of egress per (NFPA 101 12.2.5). This layout shall constitute the only' acceptable arrangement unless plans are revised; or additional plans are submitted. Temporary deviations from approved layout plans are allowed as long as occupant load is not increased and arrangement of means of means of egress is maintained per NFPA 101 12.2.5.