1 Fleet Landing Blvd COMM18-0026 new dining facility permit QUO-01785-S0K1S0—3
1/22/2019
GAF Page 1 of 1
Fleet Landing(Plywood Deck), Atlantic Beach, FL 32233
SPECIFICATION:TFANI60
COMPONENT TYPE REQUIRED ATTACHMENT RATE OF APPLICATION
DECK Plywood 19/32"
EnergyGuard'".Tapered Polylso Insulation,
INSULATION 1 20 psi tapered,per Loose laid Per GAF'requirements
ASTM C1289 Type II,Class 1,Grade 2 plans
Size:4'x 4',1/4"slope
USG Securock®Brand Gypsum Fiber Roof
Simultaneously fastened
Board,1800 psi 1 fastener per 2.67 sq.ft.:
with:
ASTM 01278 Field:12 fasteners per 4'x 8'board
INSULATION 2 1 layer Drill-Tec"'814 Fastener
Size:5/8",4'x 8'LTTR:0.6 Perimeter:18 fasteners per 4'x 8'board
Drill-Tec'"3"Standard Steel Corner:24 fasteners per 4'x 8'board
Total LTTR:0.6 Plate
SINGLE PLY EverGuardr TPO 60 mil White Adhered with: 50-60 sq ft of installed membrane per gallon. Adhesive is
MEMBRANE ASTM 06878 1 ply EverGuardr#1121 Bonding applied to both substrate surface and the underside of the
Size:loft SRI:94 Adhesive membrane
50-60 sq ft of installed membrane per gallon. Adhesive is
applied to both substrate surface and the underside of the
FLASHING EverGuardr TPO 60 mil White Adhered with: membrane.Maximum flashing height is 54". A separate
MEMBRANE ASTM D6878 1 ply EverGuard°#1121 Bonding counterflashing is required for guarantees over 20 years.A
SRI:94 Adhesive layer of Dens Deck Prime or Securock Gypsum Fiber may be
attached to the wall prior to installing flashing membrane if
required.
GUARANTEE EverGuard`Diamond Pledge'"NDL Roof 20 years Guarantee fee applicable
Guarantee
Applicable Codes and Testing Information
Agency VALUE REPORT# PAGE# SYSTEM#
FBC -45.0 psf 5293-R31 11 W-34
This Cut Spec specification shall not waive,supersede or alter the requirements and recommendations found in the most current Application&Specification Manual(s)
referenced above,printed technical bulletins or specific correspondence drafted for this project by Field Services or Technical Services Manager, Each roof has unique
requirements. This specification is a graphic representation of products and their installation. To properly assess specific roofing needs,code compliance,system configurations
and warranty eligibility,contact Contractor Services, Note: Your Field Services or Technical Services Managers are the only employees who can approve any deviation from
GAF's published specification manuol(s). Always review the appropriate Application&Specification Manual which may contain information that is important for a successful
installation. Application&Specification Manuals and specimen copies of guarantee/warranty documents are avaiable at www.gaf.com. Any fastening pattern listed above is
provided solely as a courtesy and recommends that the uplift resistance requirements be verified by a design professional.Standard industry practices must be followed for cold
storage roofing design,building envelope specifications provided by the designer for sealing of all penetrations and edges must be followed. Adhesion testing must be performed
when using low rise foam adhesives to attach insulation or membrane directly to decks or existing roof materials.Any wet or damaged existing decking shall be removed and
replaced prior to reroofing.
This system shall be installed by a GAF Master Select Contractor.
All GAP and EverGuardr accessories shall be used where applicable.GAF'Perimeter Edge Metal shall be used where conditions exist. Every Extremes accessories are
required for TPO systems with 25 year guarantees and greater.
Average R-value for tapered insulation system varies,and total R-value listed above does not include tapered insulation.See tapered plans for min kness required and
average R-value for this project.
OA
ais@gaf.com Architectural Information Services 1-800-522-9224
T-
S,a,`pjye, City of Atlantic Beach APPLICATION NUMBER
!sBuilding Department (To be assigned by the Building Department.)
`-• 800 Seminole Floridaoad
b`r 4 c'� - /x�-•�
u- �V Atlantic Beach, For32233-5445 C� l [�
Phone(904)247-5826 • Fax(904)247-5845 Cq, C� �j
•<,;t qi? E-mail: building-dept@coab.us Date routed: ( t Z C� /1 (-,
City web-site: http://www.coab.us
APPLICATION REVIEW AND TRACKING FORM
Property Address: C)N.), e.. FL =€ 7- Li eisc(Department review required Yes No
>din� ) _
L0Tooynning &Zoning>
Applicant: �L.E S.Sic ��S c ��
Tree Administrator
Project: ,'(=,(,O -IThI N i c--
—ASI i (t L/ Public Works
Public Utilities
Public Safety
—a. ire Services
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St. Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: Approved. ❑Denied. ❑Not applicable
(Circle one.) Comments:
BUILDING
PLANNING &ZONING Reviewed by: Date:
TREE ADMIN. Second Review: ❑Approved as revised. ❑Denied. ❑Not applicable
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied. ['Not applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
Building Permit Application Updated 12/8/17
- 1 City of Atlantic Beach
800 Seminole Road,Atlantic Beach,FL 32233
Phone:(904)247-5826 Fax:(904)247-5845
Job Address:One Fleet Landing Boulevard,Atlantic Beach,FL 32233 Permit Number: C 0 M. N\ ' S. `2(�
0 Z Gj
Legal Description RE#
Valuation of Work(Replacement Cost)$._$ 3,961,600 Heated/Cooled SF >'A3O Non-Heated/Cooled 2.515
• Class of Work(Circle one): Ncw Addition Alteration Repair Move Demo Pool Window/Door
• Use of existing/proposed structure(s)(Circle one): ommercia Residential
• If an existing structure,is a fire sprinkler system installed?(Circle one): Yes No N A
• Submit a Tree Removal Permit Application if any trees are to be removed or Affidavit of No Tree Removal
Describe in detail the type of work to be performed:
New dining facility on the existing Fleet Landing Campus.
Florida Product Approval# See Product Approval Form for multiple products use product approval form
Property Owner Information
Name: Naval Continuing Care Retirement Foundation,Inc. Address: One Fleet Landing Boulevard
City Atlantic Beach State FL Zip 32233 Phone 904.246.9900 _
E-Mail jashby@fleetlanding.com
Owner or Agent(If Agent, Power of Attorney or Agency Letter Required) Joshua Ashby
Contractor Information
Narne of Company: Lecesse Construction Services, LLC, Qualifying Agent: Andrew Hislop
Address 5850 TG Lee Blvd, Suite 135 City Orlando Sate FL —_Lip 32822
Office Phone (401) 458-5555 Job Site/Contact Number_(401)8-12-9815 (Phil Malone) _
State Certification/Registrar or t;CGC1522451 E-Mail PRobinsonol-eoesseConstruction.com , .
Architect Name&Phone# AG Architecture (414)431-3131
Engineer's Name&Phone# McVeigh 3 Mangum (9O4) 4e3-5200 — -
Workers Compensation Charter Oak Fire Insurance Company EXP 12/1/2018
Exempt/u,surer/Lease Employees/Expiration Date
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all the I.kw fiegulatrioN
construction in this jurisdiction.I understand that a separate permit must be secured for ELECTRICAL WORK,PLUMB'I J ,StGP45, ,/r11.
WELLS, POOLS,FURNACES, BOILERS,HEATERS,TANKS,and AIR CONDITIONERS,etc.NOTICE:In addition to the requirements of this
permit,there may be additional'restrictions applicable to this property that may be found in the public records of this.county,and
there may be additional permits required from other governmental entities such as water management districts,state agencies,or
federal agencies.
OWNER'S AFFIDAVIT:I certify that all the foregoing information is accurate and that all work will be done ir compliance with all
applicable laws regulating construction and zoning.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT.
f 1
. _' J
Signa r of 1rner or Agent) (Signator of Contractor)`,
(includ' g contractor) et '
Signed and sworn to(or a 'rm ))before me this day of Signed and sworn to(or affirmed)before methIsm--'�day of
cFetrem ntt; tog ,by jOcI4 rlC�'}gy ,,tf,, / l,)'� ,by mak-tt it� �hCF�L?i1A
AL a
(Signa re of Notary) (Signature of fVntary)
[VJ Personally Known( f'(.Personally Known OR QONNAJ-SKINNER
dr Notary Public State of Florida Notary Public,State of New York
I I Produced Identifica Mary Faria I ]Produced Identification Reg.No,01SK6344520
Tvue of Identification. •
+� My Commission GG 226935 fvoe of Identification: Qualified In Monroe County
)#p,�o4e Expues m10/2022 Commission Expires 07/05/2020
Architecture
A Sense o j
Transmittal Community
TO City of Atlantic Beach
800 Seminole Road
Atlantic Beach, FL 32233
ATTN Building Department
DATE 27 September 2018 TRANSMISSION FedEx 1 of 2
PROJECT Fleet Landing PROJECT NO. 153001
Please see enclosed:
— (2)of the 4 Copies of the Fleet Landing Main Street Building Construction Documents
— Building Permit Application
— Product Approval Information Sheet
— (4)sets of Florida Building Code 6th Edition (2017)Energy Conservation
c1P--E" I ki‘
AS ()( kC‘`
_s
or\k rN5
SEP 2 8 2018
SIGNED ANDREW KORB, Project Manager
Architecture Engine e r i n g Planning
1 4 1 4 U N D E R W O O D AVENUE SUITE 3 0 1 W A U W A T O S A, WI 5 3 2 1 3.2 6 5 3
4 1 4.4 3 1 .3 1 3 1 TEL 414.431 .0531 FAX WWW.A G A R C H .C O M
Architecture
e
Transmittal A SensC of
Community
TO City of Atlantic Beach
800 Seminole Road
Atlantic Beach, FL 32233
ATTN Building Department
DATE 27 September 2018 TRANSMISSION FedEx 2 of 2
PROJECT Fleet Landing PROJECT NO. 153001
Please see enclosed:
— (2)of the 4 Copies of the Fleet Landing Main Street Building Construction Documents
SEP 282018
SIGNED ANDREW KORB, Project Manager
A r c b i t e c t u r e Engineering Planning
1 4 1 4 U N D E R W O O D AVENUE SUITE 3 0 1 W A U W A T O S A, WI 5 3 2 1 3 .2 6 5 3
4 1 4.4 3 1 .3 1 3 1 TEL 414.431 .0531 FAX WWW.A G A R C H.C O M
t�..,:\- j-1 City of Atlantic Beach APPLICATION NUMBER
S Building Department (To be assigned by the Building Department.)
800 Seminole Road /
Atlantic Beach, Florida 32233-5445 0C► \f \ I C� ` x7Z�O
*; Phone(904)247-5826 • Fax(904)247-5845 v
-`); i jr E-mail: building-dept@coab.us Date routed: 9 /7 U /1 p,
City web-site: http://www.coab.us
APPLICATION REVIEW AND TRACKING FORM
Property Address: f\D E FL &T tcwc/ti Department review required Yes No
,:uildin.
Applicant: L GC__G SSPOSS T J ooiri o0 .
ening 8 Zonin•
Tree Administrator
Project: V C-1,0 bt IV t Pte, �AO_I li L l t`/ Public Works
Public Utilities _
c- Public Safety _
ire ervices
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By__
Florida Dept.of Environmental Protection _ __
Florida Dept.of Transportation
St.Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department ' First Review: ❑Approved. [Denied. ❑Not applicable
(Circle one.) Comments:
BUILDING
PLANNING &ZONING Reviewed by: f---.-- Date: it,—q -/g
TREE ADMIN. Second Review: ['Approved as revised. ❑Denied. Not applicable
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. (Denied ['Not applicable
Comments:
Reviewed by: Date:
Revised 05/19/2017
Plan reviewed 10/9/2018
Returned for Corrections:
The plans submitted for review have been returned for corrections. Please correct and or provide the
additional requested information to obtain plans approval. When resubmitting corrected sheets, provide a
type written itemized narrative letter responding to our comments and directing the plans reviewer to the
sheets the changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER "WILL" RESULT IN
A RETURNED FOR CORRECTIONS PERMIT STATUS. Revised sheets should be clouded, clearly
showing areas were changes or corrections have occurred and re-inserted with the original set of
drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission
please make sure that written narrative is submitted under correspondence along with a "complete set"
(not just the revised sheets) of electronic documents. When submitting electronic plans, each discipline
shall upload a single PDF file containing multiple sheets rather than separate PDFs for each
sheet. Please re-upload in this fashion.
1. Fire Code specific code summary
The building code and fire code differ on occupancy types, uses, and occupant loads and can make the
proper application of the code difficult. For example the building code classifies restaurants under 50 as
business where the fire code classifies them as mercantile, thus the need separate code summaries.
Please provide in addition to normal building code summary a fire code specific summary based off the
Florida Fire Prevention Code (current edition) to include all the following information listed below. Failure
to provide accurate fire code summary may delay plans review approvals as we return plans for
corrections and clarifications.
Provide required Fire Code specific code summary: Please Reference 6"' Edition Florida Fire
Prevention Code Based on NFPA, 1 Fire Code 2015 Edition & NFPA 101 Life Safety Code 2015 Edition.
•Occupancy type sub-classification (per NFPA 101 6.1)
• Building construction type (per NFPA 101 8.2.1)
• Gross square footage
• Number of stories
• Building height
• Interior wall and ceiling finish requirements (per NFPA 101 10.2
•Allowable dead end limits
•Allowable Common path of travel limits
•Allowable travel distance limits
•Any fire protection systems (sprinkler, fire alarm, etc.)
•Statement from architect or engineers that their design to the best of their knowledge complies with the
6"' Edition Florida Fire Prevention Code (FFPC).
•Also all existing building must provide classification of rehabilitation work categories per NFPA 101 43.1
Provide classification of rehabilitation work categories per NFPA 101 43.1
This information is important because the level of rehabilitation work determines how the code will be
applied. The 6 rehabilitation work categories are as follows:
(1) Repair
(2) Renovation
(3) Modification
(4) Reconstruction
(5) Change of use or occupancy classification
(6) Addition
2. Life Safety Floor Plan:
The City of Jacksonville's Fire Marshal's Office requires the submittal of a Life Safety Floor Plan for
building permits for all new construction and existing building alterations in order to ascertain if occupancy
is currently code compliant and to assist fire inspector in performing Life Safety Inspections. Please
provide a Life Safety Plan to include all the following information on one page. If Life Safety Plan was
submitted and you are receiving this comment, it means that all of the required info listed below was not
included in your original submittal. It is understood that all listed items may not apply in your situation.
Required Occupant Load Calculation:
• Provide design occupant load using table 7.3.1.2 of NFPA 101 2015 edition. Area calculations should be
shown with graphic seating configurations or fixtures in order to substantiate occupant load chosen.
Exit Locations:
• Designate main entrance and all secondary exits. All required exits shall terminate at a "public way'.
Access to the public way shall be accessible and must be via a stable, firm, and slip resistant conveyance
such as a concrete sidewalk with a min. 5'x5' landing and 44" walkway. Multi story buildings should
designate area of rescue with required communication means. Separation of exits using the one half
(non-sprinkled) or one third (sprinkled) the diagonal distance rule should be shown on plans.
Required Egress Capacity:
• Egress inches for means of egress components (doors, stairs, etc.)
Required measurements: (Worst case only need be shown.)
• Dead end corridors measurements.
•Common path of travel measurements.
•Total travel distance to exits.
Required separation:
•Show all fire barriers, smoke barriers, and smoke partitions. All rated walls per new directive from
building official wall detail needs to include UL listing and needs to confirm by architect or engineer as
being accurate.
Required Lock Latch details:
• Lock/Latch details: Panic Hardware, Thumb turn lock, Key Lock with indicator and required signage.
Required Electrical Stop/Disconnect Details:
• Any required Emergency stops or Shunt trips.
• Main Electrical disconnects access/location.
Required markings of means of egress:
• Exit signs to include tactile exits signage.
Required fire extinguisher Locations:
• Locations per NFPA 10.
Required Emergency lighting:
•Show emergency illumination.
3. Occupant Load & Capacity of Means of Egress:
Please re-calculate occupant load as follows:
•
Occupant load is determined by the nature of the "use" of a building or space and the amount of space
available for that"use". NFPA 101, Table 7.3.1.2 has established occupant load factors for each"use".
The use of an area may differ from its occupancy classification. For example, a meeting room for fewer
than 50 people in an office building is not assembly occupancy; it is business occupancy, but its occupant
load is based on assembly.
An occupant load is established for use in sizing the means of egress systems and in determining
thresholds at which additional provisions, such as mandatory sprinklers, fire alarm, panic hardware etc.
become applicable.
Egress capacity and life safety features must be provided for the occupant load (expressed in number of
persons) determined by dividing each "use' area of the space by the appropriate occupant load factor.
The corresponding calculated occupant load must serve as the minimum starting point for egress sizing,
and required life safety features regardless of whether the building operator claims that the occupant load
will never reach the occupant load determined by calculation.
The occupant load in any building or portion thereof assigned for use is determined by dividing the floor
area assigned to that use by the occupant load factor for that use as specified in table 7.3.1.2 of NFPA
101 FFPC.
PLEASE CALCULATE OCCUPANT LOAD AS FOLLOWS:
1. Determine proper occupant load factor(s) to be used per table 7.3.1.2 of NFPA 101 for each use area..
2. Determine"net" or"gross" floor area to be calculated.
3. Calculate expected occupant load in table form showing each use area with each area added
separately to correspond with square footages. It is understood that some unoccupied areas such as
bathrooms, corridors, and small circulation areas in front of exits are not figured in net square footage or
occupant load calculations.
In table form on life safety plan delineated by cross hatching, contrasting color etc. list square footage for
each "use"area and occupant load factors being applied to its use. For"use" areas using gross square
footage the gross area of a space is defined as everything within its walls. For"use' areas using net
square footage, the area is determined by measuring all of the non-occupied spaces, and then
subtracting this area from the gross area and applying the appropriate"use" factor. In general, "net floor
area" is where the public is expected to or can assemble. Accessory areas such as bathrooms, corridors,
and small circulation areas in front of exits are not figured in net square footage or occupant load
calculations.
When dealing with a multiple use occupancy where both gross and net area figures are given for the
same building, calculations shall be made by applying the gross area figure to the gross area portion of
the building devoted to that"use"for which the gross area figure is specified and by applying the net area
figure to the net area portion of the building devoted to the use for which the net area figure is specified.
"Use" area square footage should correspond with your occupant load calculations minus any non-
occupied areas or spaces as mentioned above.
Frequently used occupant load factors with examples include:
•One person for every 7 square feet (concentrated use) Examples are dance floor, standing or waiting
areas, and rows of non-fixed chairs.
•One person for every 15 square feet (less concentrated use) Examples are non-fixed tables and chairs
in a restaurant or club.
•One person for every 18 linear inches of bench type seating.
•One person for every 24 linear inches of standing or sitting bar top space. Please allow for a 3 foot
buffer area measured perpendicularly along the length of the bar that will not be calculated in "use"area
to account for space taken up by chairs.
•One person for every fixed seat (seating that is secured to buildings structure).
• Designated waiting spaces should not encroach on required egress width of any exit and be restricted to
areas other than the required means of egress. Allowable waiting areas occupant load factor should be
based off use, not to exceed 1 person for every 5 sq. ft.
•One person for every 100 square feet in kitchens and employee service areas.
•One person for every 500 Square feet in storage for other than storage or mercantile occupancies.
Note: Please make sure that all'Use" areas are factored in and shown in occupant calculation. The
number calculated may or may not exceed number of actual chairs on floor plan. This number is worst
case scenario and to be used for sizing number of exits, egress inches, and fire protection features.
4. Determine and show required egress inches required vs what is provided for the calculated occupant
load. Provided should be equal to or greater than what is provided.
itA
3-00
yoAAEsco'
Q.
FSCUs'3�Q!'
MIGUEL Di PIERRI
Fire Safety Inspector/ CDN Reviewer
JFRD PREVENTION OFFICE
515 N.Julia St.,Jacksonville, Florida 32202
Office: 904-255-8561 cell: 904-763-1290— Email: DIPIERRI@COJ.NET
Printing :: CR479789 Page 1 of 1
Duval County,City Of Jacksonville
Michael Corrigan ,Tax Collector
231 E Forsyth Street
Jacksonville.Fl 32202
General Collection Receipt
Account No:CR479789 Date: 10/9/2018
User:Prevention,Fire Email:FirePrev!ii:coj.net
Feed the Homeless Application Fee
Name:A(i Arch
Address: 1414 underwood Ave
Description:Plan re%iew for Atlantic Bch comm 18.0026
TranCode I IodesCode I SubObject I GLAcct I Subsidso L'serCode I Project I ProjectDt1 ( Grant I GraatDtl I Docno I Amount
701 I ERODOI IAD I 34930 I I I I I 15000
Total Due:S150.101
Michael Corrigan ,Tax Collector
General Collections Receipt
City of Jacksonville, Duval County
Account No:CR479789 Date: 10'9/2018
Feed the Homeless Application Fee
Name_A G Arch
Address 1414 unden+wd Ase
Description Plan'Into..for Atlantic 13th comm 18 0026
Total Due:SI50.00
http://financeweb.coj.net/TCCR/printing.aspx?cr—CR479789 10/9/2018
a
a PRODUCT APPROVAL INFORMATION SHEET FOR THE CITY OF ATLANTIC BEACH,FLORIDA
Project Name: FLEET LANDING - MAIN STREET Permit #
Project Address: Fleet Landing, One Fleet Landing Boulevard, Atlantic Beach, FL. 32233
As required by Florida Statute 553.842 and Florida Administrative Code Rule 9B-72,please provide the information and product approval number(s)
for the building components listed below as applicable to the building construction project for the permit number listed above. You should contact
your product supplier if you do not know the product approval number for any of the applicable listed products. Information regarding statewide
roduct approval may be obtained at: www.floridabuildingz
Category/Subcategory j Manufacturer Product Description I Limitation of Use State# Local # I
A. EXTERIOR DOORS
1. Swinging Kal,uneer Gan,. SEE STOREFRONT FL8181-R8
2. Sliding
3. Sectional
4.Roll up
ASSA ABLOY 5E5AM Series Resilience"Automatic
5. Automatic
Entrance si,stems Inc. Sliding Glass Doors wBreakout 14-0529.11
6. Other Schlage Lock Comp. Swing Exterior Door.Metal
LLC FL4031-R9
B. WINDOWS
1. Single hung Anderson Silverline 2100/10 SINGLE HUNS, FL-14911.5
2. Horizontal slider
r. ,
3. Casement
4. Double hung
5. Fixed Anderson Silverline 2150 Fixed Windows FL-14911.5
6. Awning
7. Pass-through
8. Projected
9.Mullion
10.Wind breaker
11.Dual action
12.,Other
_ategory/Subcategory J Manufacturer Product Description Limitation of Use State# Local #
C. PANEL WALL
1. Siding
2. Soffits
3. EIFS
4. Storefronts K veneer Gomp. Storefront FLS-18-7-RS
5. Curtain walls
6. Wall louvers
7. Glass block
8. Membrane
9. Greenhouse
10. Synthetic stucco
11. Other
D. ROOFING PRODUCTS
1. Asphalt shingles
2. Underlayments
3. Roofing fasteners
4.Nonstructural metal roof Drexel Metas, Inc. I Metal Roofing FL-17678-R1
4
5. Built-up roofing
6. Modified bitumen
l j
7. Single ply roofmg
8. Roofingtiles eagr�c
le ooting Proaucts Concrete Roof Tiles
Florida LLG FL-7473-R8
9. Roofing insulation
10. Waterproofing
11. Wood shingles/shakes
•
12. Roofing slate
13. Liquid applied roofing
14. Cement-adhesive coats
15. Roof tile adhesive
16. Spray applied polyurethane
roof
17.
Category/Subcategory Manufacturer Product Description Limitation of Use State# Local #
E. SHUTTERS
1. Accordion
2. Bahama
3. Storm panels
4. Colonial
5. Roll-up
6. Equipment
7. Other
F. STRUCTURAL
COMPONENTS
1. Wood connector/anchor
2. Truss plates
3. Engineered lumber
4. Railing
5. Coolers-freezers
6. Concrete admixtures
7. Material
8. Insulation forms
9. Plastics
10. Deck-roof
11. Wall
12. Sheds
13. Other
G.SKYLIGHTS
1. Skylight
2. Other
Category/Subcategory Manufacturer Product Description Limitation of Use State# Local #
H.NEW EXTERIOR
ENVELOPE PRODUCTS
1.
2. 1
In addition to completing the above list of manufacturers, product description and State approval number for the products used on this project, the
Contractor shall maintain on the job site and available to the Inspector, a legible copy of each manufacturer's printed specifications and installation
instructions along with this Product Approval Sheet.
I certify that this product approval list is true and correct to the best of my knowledge. I further certify that use of different components other than the ones
listed in this document must be approved by the Building Official.
(ARCHITECT Name) (Print Name) Eugene Guszkowski, AIA attire)
IIS ,
Company Name: AG Architecture Inc.
Mailing Address: 1414 Underwood Avenue
City: Wauwatosa State: IN Zip Code: 53213
Telephone Number: ( 414 ) 431-3131 Fax Number: ( 414 ) 431-0531
Cell Phone Number: ( ) E-mail Address: ajkorboagarch.com