461 Atlantic Blvd COMM17-0016 Revision Struc Att "ALL INFORMATION
Revision Request/Correction to Comments HIGHLIGHTED IN
City of Atlantic Beach Building Department GRAY IS REQUIRED.
800 Seminole Rd, Atlantic Beach, FL 32233
Phone: (904) 247-5826 Email: Building-Dept(epcoab.us PERMIT a:COAM 1) - OD I to
❑ Revision to issued Permit OR ��T Corrections to Comments Date:5_ _-z1-
0
Project Address: / 41-IMT.
contractor/Contact Name: \14
Contact Phone: `PO?/' 74-9- 0& A Email:
Description of Proposed Revision/Corrections:
Skj4tkVrA1 er ECIC
affirm the revision/correction to comments is inclusive of the proposed changes.
(printed name)
ill proposed revision/corrections add additional square footage to original submittal?
• 0 0 Yes(additional s.f.to be added: )
•
Will proposed revision/corrections add additional increase in building value to original submittal?
Vo 0•Yes(additional increase in buildingvalue:$ )Icontraaor must sign if increase in valuation)
-Signature of Contractor/Agent:
(Office Use Only)
Approved ❑ Denied // ❑ Not Applicable to Department Permit Fee Due
$V 00
Revision/PlanReview
L Comments Ifcdge ZJ- n Sd�TArd,-d RPtln-'O .
rl0 cv me/L7 s �A,r T �
i
Department Review Required:
wilding
Planning&Zoning Reviewed By
Tree Administrator
Public Works 31z-
Public
IZ
Public Utilities
Public Safety Date
Fire Services updahad to/v/1a
�G�((((��� REVISION OFFICE COPY
Lv SIGNED_ /)'too1/ 6
Alexander Grace Consulting, Inc.
March 14,2019
Mike Kleinschmidt
Design Cooperative, LLC
1032 Hendricks Ave.
Jacksonville, Fla. 32207
Re: Inspector Comments
ABBO,Atlantic Beach, FL
Job Number 18-10-0058
Dear Mike,
During city inspection of the above referenced structure, the inspector requested the EOR visit the site and address several
issues.Those issues are repeated in bold below with the response following.AGC performed the requested site visit on March
6 and followed up on requested work on March 13,2019.
1. Please provide a letter signedisealed/dated by EOR verifying site inspection and approving all to plates and
continuous uplift at all truss bearing points.
2. Please verify masonry anchor bolts/huts/washerslcounterbore for uplift
3. Continuous upliRat steel angleltek screw/nail detail.
On the first site visit,we viewed the top plates at the front wall, the steel beam between the dining room and kitchen,
and the rear wall of the kitchen. It is worth noting now that all trusses were fastened with (2) H2.5A clips, which is
significantly more than required for all trusses except the kitchen girders. Trusses B7, 88, B11, B12, 817 and B18
were the only trusses that required double clips.
a. The front wall has the dining room trusses and the front porch framing attached to it. The parch framing is
ledgered to the ends of the trusses. We verified the uplift force and applied it to the top plates, which am
fastened down with '/1" anchor bolts, countersunk and using a 1-1/2' diameter washer. This washer was not
sufficient.To remedy,AGC specified adding a 5/8'X8"wedge anchor with 2"washer at 32"o.c. I reviewed these
anchors on March 13 and found them to be installed per instruction.
b. The steel beam has the dining room trusses and kitchen trusses fastened to the tap plate. Verifying the uplifts
and the installation of the top plate anchor bolts,with 1-1/2"washers, this plate is installed sufficiently. No further
action is required.
c. The rear wall has the kitchen trusses fastened to the top plate,which is fastened to the steel angle. The plans
specified fastening the plate to the steel angle with 114" through bolts at 24" centers. During construction, a %°
TEK screw and 1-1/2"was used instead to fasten the lower plate to the angle.The upper top plate is fastened to
the lower plate with (2) rows of 10d nails at 16' o.c., per plan specifications. Due to the double Gipping of the
trusses to the wall noted above, this system is sufficient. The trusses are more than sufhdently fastened to the
top plate assembly, the top plate assembly is sufficiently fastened to the angle, and the angle is sufficiently
fastened to the wall. No further action is required.
As always,thank you for the opportunity to serve you. Please call if you have any further questions.
Sincerely,
ttttiltlliit'
Di rtall signed
(Ip,C Geoff y
by Geoff Gartner
* a _ Date: 2019.03.14
41coa P: ` Gartner 08:12:00 -04'00'
�ir4nntttt
Geoff Gartner, PE
FL 59328
3010Sout63"Street,Smt,C - J.<k.—jlle Bea UL32250 • 904-241-8010