ICC-ES Evaluation Report Reissued 02/2019
ICC-ES 1 (800) 423-6587 1 (562) 699-0543 1 www.icc-es.org This report is subject to renewal 02/2021.
DIVISION: 08 00 00—OPENINGS
SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VENTS
REPORT HOLDER:
SMART VENT PRODUCTS, INC.
EVALUATION SUBJECT:
SMART VENT" AUTO' AT ON FLOOD VENTS:
MODELS #1540-520; #1540--52 #1540-510; #I�410-511; #1540-570; #1540-574;
5
#154 -514
FLOOD VENT SEALING KIT #1540-526
ICC ICC ICC 000%"
0A
-2014 Recipient OfPrestigious western statesseismic Policy Council
(WSSPC)Award in EXceilence" A Subsidiary of NEM"'Me"
1CC-ES Evaluation Reports are not to be construed as representing aesthetics or any other altribufff not specif,cally
,of '
addressed, nor are they to he construed as an endorsement ofthe subject ofike report or a reeommendalio or,s u"
Acre is no warranty by ICC Evaluation Ser�iee, LLC, express or implied, as to anyfinding or other matter in this
report.oras to anyproduct covered by the report.
Copyright*2019 ICC Evaluation Service, -I-C. All rights reserved.
WWI
[CC-ES Evaluation Report ESR-2074
Reissued February 2019
This report is subject to renewal February 202 1.
wwrifricc-eigrgrg 1 (800)423-6587 1 (562)699-0543 A Subsidiary of the International Code Council"
DIVISION:08 00 00—OPENINGS Each unit is fabricated from stainless steel. Smart Vente
Section: 08 95 43—Vents[Foundation Flood Vents Automatic Foundation Flood Vents are available in
various models and sizes as described in Table 1. The
REPORT HOLDER: SmartVENTQ Stacking Model #1540-511 and FloodVENT"
Stacking Model #1540-521 units each contain two
SMART VENT PRODUCTS, INC. vertically arranged openings per unit.
EVALUATION SUBJECT: 3.2 Engineered Opening:
The FVs comply with the design principle noted in Section
SMART VENTe AUTOMATIC FOUNDATION FLOOD 2.7.2.2 and Section 2.7.3 of ASCE/SE1 24-14 [Section
VENTS:MODELS#1540-520;#1540-521;#154M10'#1540- 2.6.2.2 of ASCEISEI 24-05 (2012, 2009, 2006 IBC and
511;#1540-570;#1540,574;#1 54OZ24;#1540-514 IRC)l for a maximum rate of rise and fall of 5.0 feet per
FLOOD VIENTSEALING KIT#1540-526 hour(0.423 mr-ri In order to comply with the engineered
opening requirement of ASCEISEI 24, Smart Vent FVs
1.0 EVALUATION SCOPE must be installed in accordance with Section 4.0.
Compliance with the following codes: 3.3 Ventilation:
0 2018, 2015, 2012, 2009 and 2006 International Building The SmartVENTO Model #1540-510 and SmartVENTO
Code(IBC) Overhead Door Model#1540-514 both have screen covers
with '/4-inch-by-'14-inch (6.35 by 6.35 mm) openings,
m 2018, 2015, 2012, 2009 and 2006 International yielding 51 square inches(32 903 MM2)of net free area to
Residential CodeP(IRC) supply natural ventilation. The SmarlVENTa` Stacking
111 2018 International Energy Conservation Coffee(IECC) Model #1540-511 consists of two Model #1540-510 units
in one assembly, and provides 102 square inches
0 2013 Abu Dhabi International Building Code(ADIBC)' (65806 MM2)of net free area to supply natural ventilation.
'Th.ADIBC ia ba�ad.,the 2009 113G�M09 180 cod.sechone n0ananned Other FVs recognized in this report do not offer natural
in ths the in the ADIBC. ventilation.
Properties evaluated: 3.4 Flood Vent Sealing Kit:
0 Physical operation The Flood Vent Sealing Kit Model#1540-526 is used with
SmartVENTO Model #1540-520. It is a Homasote 440
III Water flow Sound Bamero (ESR-1374) insert with 21 – 2-inch-by-2-
2.0 USES inch(51 mrin x 51 mm)squares cut in it, See Figure 4.
The Smart Vento units are engineered mechanically 4.0 DESIGN AND INSTALLATION
operated flood vents (FVs) employed to equalize 4.1 SmariVENTO and FloodVENTO:
hydrostatic pressure on walls of enclosures subject to To and FIoodVENTg are designed to be
rising or failing flood waters. Certain models also allow SmartVEN
natural ventilation. installed into walls or overhead doom of existing or new
construction from the exterior side. Installation of the
3.0 DESCRIPTION vents must be in accordance with the manufachumer's
3.1 General: instructions, the applicable code and this report.
Installation clips allow mountii asonry and concrete
When subjected to rising water, the Smart Vento FVs walls of any thickness In Ap comply with the
internal floats are activated,then pivot open to allow flow in engineered opening design pnnZi d in Salon
either direction to equalize water level and hydrostatic 2.7.2.2 and 2 7 3 of ASCEISEI 2,Siotei.n 2.6.2.2 of
pressure from one side of the foundation to the other. The ASCE/SEI 24166 (2012, 2009, 200E1W!kIRC)], the
FV pivoting door is normally held in the closed position by Smart Vane FVs must be installed as follo;YIL It
a buoyant release device.When subjected to rising water, 0 With a minimum of two openings on diffe of
the buoyant release device causes the un t to un atc , 11?4
allowing the door to rotate out of the way and allow to . each enclosed area. P
The water level stabilizes, equalizing the lateral forces. 0 With a minimum of one FV for every 200 square
man midomonvoofthembjeclofthere,on—
w an,firoho,orookeroonerin this oeort or m le VProa�er,oreno/0 the oreen,
Cop"Ilt 0 M19 ICC Evaluation Seroce,LLC Al rights reearood, Pagel of 5
ESR-2074 I MostWidelyAccepted and Page 2 of 5
feet (186 M2) of enclosed area, except that the 5.2 The Smart Vents FVs must not be used in the place
SmartVENT6 Stacking Model #1540-511 and of"breakaway walls"in coastal high hazard areas, but
FloodVENT" Stacking Model #1540-521 must be are permitted for use in conjunction with breakaway
installed with a minimum of one FV for every walls in other areas.
400 square feet f37.2 M)of enclosed area. 6.0 EVIDENCE SUBMITTED
• Below the base flood elevation. 6.1 Data in accordance Wth the ICC-ES Acceptance
• With the bottom of the FV located a maximum of Criteria for Mechanically Operated Flood Vents
12 inches (305.4 mm) above the higher of the final (AC364), dated August 2015 (editorially revised
grade or floor and finished exterior grade immediately October2017).
under each opening. 6.2 Test report on air infiltration in accordance with ASTM
4.2 Flood Vent Sealing Kit E283.
The Flood Vent Sealing Kit Model 1540-526 is used in 7.0 IDENTIFICATION
conjunction with FloodVENTx Model #1540-520. When 7.1 The Smart VENTO models and the Flood Vent Sealing
installed and tested in accordance with ASTM E283. the Kit recognized in this report must be identified by a
FV and Flood Vent Sealing Kit assembly have an air label beanng the manufacturers name (Smartment
leakage rate of less than 0.2 cubic feet per minute per Products, Inc.),the model number,and the evaluation
lineal foot (18.56 I/min per lineal motor) at a pressure report number(ESR-2074).
differential of 1 pound per square foot (50 Pa) based on
12.58 lineal feet(3.8 lineal meters)contained by the Flood 7.2 The report holders contact information is the
Vent Sealing Kit. following:
5.0 CONDITIONS OF USE SMART VENT PRODUCTS,INC.
The Smart Vents FVs described in this report comply wth, 430 ANDBRO DRIVE,UNIT 1
PITMAN, NEW JERSEY 08071
or are suitable alternatives to what is specified in, those (877)441-8368
codes listed in Section 1.0 of this report, subject to the www.smartvent.corn
follovAng conditions InfoglIsmarltvent.com
5.1 The Smart Vents FVs must be installed in accordance
with this report, the applicable code and the
manufacturer's installation instructions. In the event of
a conflict,the instructions in this report govern.
TABLE I—MODEL SIZES
MODELNAME MODELNUMBER MODEL SIZE(in.) COVERAGE(sq.ft.)
FloodVENT' 1540-520 153/�"X 73/," 200
SmarIVENTO 1540-510 lele X 7 /,* 200
FloodVIENT'Overhead Door 154OZ24 1531."X 7314" 200
SmanVENTO Overhead Door 1540-514 15'1."X 73/�' 200
Wood Wall FloodVENT' 1540-570 14-X 83/�" 200
Wood Wall FloodVENT'Overhead Door 1540,574 14"X 83/," 200
SmartVENTO Stacker 1540,511 16'X 16" 4GO
FloodVenf*Stacker 1540-521 16"X 16" 400
For V: I I.h 25.4 1 square f0a m2
FIGU RE I—SMART VENT:MODEL 1540-510
ESR-2074 I Most Widely Accepted and Trusted Page 3 of 5
FIGURE 2—SMART VENT MODEL 1 M0420
f
FIGURE 3—SMART VENT: SHOWN WITH FLOOD DOOR PIVOTED OPEN
00
INTERIOR EXTERIOR
FIGURE LOOD VENT SEALING HIT
Most Widely Accepted and Trusted
ICC-ES Evaluation Report ESR-2074 CBC and CRC Supplement
Reissued February 2019
This report is subject to renewal February 202 1.
www.1cc-es.arn 1 (800)423-6587 1 (562)699-0543 A Subsidiary ofthe International Code Councilo
DIVISION: 08 00 00--OPENINGS
Section:08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMART VENT PRODUCTS,INC.
EVALUATION SUBJECT:
SMART VENTO AUTOMATIC FOUNDATION FLOOD VENTS:MODELS#1540-520;#1540-521;#1 54OZ1 0;#1540-511;#1540-
570;#1540-574;#1 540.52A;#1 54OZ14
FLOOD VENT SEALING Kff#1540-526
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that Smart Vermo Automatic Foundation Flood Vents,
recognized in ICC-ES master evaluation report ESR-2074, have also been evaluated for connplian� with cocles, noted
below.
Applicable code edition:
0 2016 California Building Code(CBC)
0 2016 California Residential Code(CRC)
2.0 CONCLUSIONS
2.1 CBC:
The Smart Vents Automatic Foundation Flood Vents, described in Sections 2.0 thmugh 7.0 of the master evaluation report
ESR-2074, comply wth 2016 CBC Chapter 12, provided the design and installation am in accordance with the 2015
International Building Code(IBC) pnovisions noted in the master report and the additional requirements of CBC Chapters
12, 16 and 16A,as applicable.
The products recognized in this supplement have not been evaluated under CBC Chapter 7A for use in the exterior design
and constnuction of new buildings ]mated in any Fire Hazard Seventy Zone within State Responsibility Areas or any
Wildland-Urban Interface Fire Area.
2.2 CRC:
The Smart Vene Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comp�with the 2016 CRC, provided the design and installation are in accordance With the 2015 Intemational
Residential Code (IRC)provisions noted in the master report.
The products recognized in this supplement have not been evaluated under 2016 CRG Chapter R337, for use in the
exterior design and construction of new buildings located in any Fire Hazard Severity Zone within State Responsibility Areas
or any Wildiand-Urban Interface Fire Area.
The products recognized in this supplement have not been evaluated for compliance with the Intemartion nd-Urban
Interface Code.
This supplement expires concumently with the master report,reissued February 2019.
00
'0�'
Ice-EsEnniumm"",omra alenne w&conermon,repleoneivilembeines orimembeemollemen not iveifievl(Y miireseml,norme lhom in he
Elm
mnmyj,,mg nember mailer in moy oiMer.orw wany,olmuctcoverellby the rnnu go �--
�pydghtC20l9lCCE�luafiw��,LLC. Alinghtsrenerved, Pae4oi`5
EVALUATION
SERVICE Most Widely Accepted and Trusted
ICC-ES Evaluation Report ESR-2074 FBC Supplement
Reissued February 2019
This report is subject to renewal February 2021.
wrivoAr.icc-es.org 1 (800)423-6587 1 (562)699-0543 A Subsidiary of the Intemational Code Coui
DIVISION:08 00 00—OPENINGS
Section:08 95 43—ventallounclation Flood Vents
REPORT HOLDER:
SMART VENT PRODUCTS,INC.
EVALUATION SUBJECT:
SMART VENTO AUTOMATIC FOUNDATION FLOOD VENTS:MODELS#1540-520;#1540-521;#1540-510;41540-511;
#1540,570;#1540�574;#1540-524;#1540-514
FLOOD VENT SEALING KIT#1540-526
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that Smart Vane Automate Foundation Flood Vents, recognized
in ICC-ES master report ESR-2074,have also been evaluated for Compliance with the coades noted below.
Applicable wide editions:
0 2017 Florida Building Code—Building
0 2017 Florida Building Code—Resaidential
2.0 CONCLUSIONS
The Smart Vane Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, wernply with the Florida Building Coda—Building and the FRC, provided the design and installation are in
accordance with the 2015 International Building Code provisions noted in the master report.
Use of the Smart Vane Autcanni Foundation Flood Vents has also been found to be in ciampliance with the High-Velocity
Hurricane Zone provisions of the Florida Building Code—Building and the Florida Building Codia—Residential.
For products failing under Florida Rule EN-3,visfificastion that the report holdef a quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being Conducted is the
responsibility of an approved validation entity(or the Code official when the report holder does not possess an approval by
the Commission).
This supplement expires Concurrently vath the master report,reissued February 2019.
0
01�'
YV
�1�00
ICC-ESE-J-fi�,�Ro.-I�al.51-.�aa
CoWgint 0 2019 ICC Evaluation Sconce.LLC. All rights maeriec, Page 5 of 5