73 Sailfish Dr COMM17-0023 Balance Report NEBB CERTIFIED TEST, ADJUST AND BALANCE REPORT DATE: 3/13/2019 PROJECT Mm's Oriental Market ADDRESS Atlantic Beach, Florida ARCHITECT ENGINEER HVAC CONTRACTOR HOLISTIC TEST & BALANCE 3614 LENOX AVE. JACKSONVILLE, FL 32254 (904) 900-1484 �\,tyst& ea�a�Oo r LDVD E.7FFElDAAN CERTIFICATION 2701 Exp.3131Y21 9 m HOLISTIC TEST & BALANCE PROJECT: Mimes Oriental Market DATE: 3/13/2019 LOCATION: Atlantic Beach, Florida FAN TEST SHEET SPECIFIED FAN- Hood #1 Fan-Hood #1 FAN# FAN# LOCATION Exhaust Supply TOTAL CFM 1600 1200 FAN RPM NS DID TOTAL SP 50 .125 MOTOR HP .50 .33 TEST MANUFACTURER FloAire FloAire MODEL# DU50H DMUA18 SERIAL # MOTOR MFG HSSA HSSA MOTOR HP 1/2 1/3 MOTOR RPM 1625 1625 MOTOR VOLTS 115/1v 115/1v MOTOR F.L.A. 8.4 4.5 i RUN AMPS 6.8 4.0 _ cm. ow LINE VOLTAGE 120 120 �±g TOTAL CFM 1680 1250 " - FAN RPM Variable D/D TOTAL S.P. .60 .45 NOTES: Riser: 12"x12" = 1.0ft2 = Test Vel = 1680 ft/min= 1680 cfm