73 Sailfish Dr COMM17-0023 Balance Report NEBB CERTIFIED TEST, ADJUST AND
BALANCE REPORT
DATE: 3/13/2019
PROJECT Mm's Oriental Market
ADDRESS Atlantic Beach, Florida
ARCHITECT
ENGINEER
HVAC CONTRACTOR
HOLISTIC TEST & BALANCE
3614 LENOX AVE.
JACKSONVILLE, FL 32254
(904) 900-1484
�\,tyst& ea�a�Oo
r
LDVD E.7FFElDAAN
CERTIFICATION
2701
Exp.3131Y21
9
m
HOLISTIC TEST & BALANCE
PROJECT: Mimes Oriental Market DATE: 3/13/2019
LOCATION: Atlantic Beach, Florida
FAN TEST SHEET
SPECIFIED
FAN- Hood #1 Fan-Hood #1 FAN# FAN#
LOCATION Exhaust Supply
TOTAL CFM 1600 1200
FAN RPM NS DID
TOTAL SP 50 .125
MOTOR HP .50 .33
TEST
MANUFACTURER FloAire FloAire
MODEL# DU50H DMUA18
SERIAL #
MOTOR MFG HSSA HSSA
MOTOR HP 1/2 1/3
MOTOR RPM 1625 1625
MOTOR VOLTS 115/1v 115/1v
MOTOR F.L.A. 8.4 4.5 i
RUN AMPS 6.8 4.0 _
cm. ow
LINE VOLTAGE 120 120 �±g
TOTAL CFM 1680 1250 " -
FAN RPM Variable D/D
TOTAL S.P. .60 .45
NOTES: Riser: 12"x12" = 1.0ft2 = Test Vel = 1680 ft/min= 1680 cfm