Loading...
120 Jackson Rd RES18-0397 Blower Door I D LBLOWER Permitsi:RE 5 IB' 3 `tl eo OR Blower Door Test Form Job Information Builder: Mathieu Builders Community: Lot a: Address: 120 Jackson Road unit a: City,State,Zip: Atlantic Beach, FL 32233 Air Infiltration Test Results CFM(50)= 1.5,10 Volume ACH(50)=CFM(50)X 60/Volume= 4_24 YJ Pass ❑ Fail Passing results must be 7 ACH/50/or less Certification of Test Results 8402.4.1.3 Testing.The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour in Climate Zones 1 and 2,3 air changes per hour in Climate Zones 3 through S.Testing shall be conducted with a blower door at a pressure or 0.2 inches w.g. (50 Pascals). Testing shall be conducted by either Individuals as defined in Section 553.993(5)or (7),F.S. or individuals licensed as set forth in Section 4a9.305(3)(f), (g),or(h) or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Authorized Third Party I hereby certify the above results and that I hold the below certification: _Class A or B A/C contractor or Mechanical contractor License No. RESNET approved HERS Rater or Residential Field Inspector Certification No.4579260 BPI approved Building Analyst, Energy Auditor,&IDL Certification No. Professional Engineer License No. Mechanical ventilation has been added: yes No Signature: Printed Name: David Atkinson Date: X12.10 Revised 5/5/2017