645 Plaza ACC19-0044 ShedNOTES: 1. BUILDING CODE: FLORIDA BUILDING CODE, 6th EDITION (2017) BUILDINGS ARE NOT FOR HIGH -VELOCITY HURRICANE ZONES (HVHZ; 2. DESIGN LOADING: WIND SPEED (T1609.3.1): V„n = 145 V.Sd = 112 EXPOSURE: C ROOF LIVE LOAD: 20 PSF ROOF DEAD LOAD: 10 PSF FLOOR LIVE LOAD: MIN. 50 PSF (SEE NOTE 5, DETAIL 1, SHEET 3) IMPORTANCE FACTOR: (IW): 1_0 RISK CATEGORY: I COMPONENT AND CLADDING: ROOF: +16 PSF / -28 PSI= ZONE 1 WIND PRESSURE (psf (ASD VALUES) +16 PSF / -47 PSI= ZONE 2 (BASED ON 10 SQ FT) +16 PSF / -70 PSI= ZONE 3 WALL: +28 PSF / -30 PSI= ZONE 4 +28 PSF / -37 PSI= ZONE 5 INTERNAL WIND PRESSURE COEFFICIENT: +0.18 /-0.18 (ENCLOSED BUILDING) FLORIDA BUILDING APPROVAL NUMBERS - 1. WINDOWS BY TAFCO CORP - FLORIDA BUILDING APPROVAL #FL20743.1-R1. 2. LP SMARTSIDE SIDING - FLORIDA BUILDING APPROVAL #FL.9190.6-R5. 3. SHINGLES BY OWENS CORNING - FLORIDA BUILDING APPROVAL #FL1 0674. 1 -R1 3. 4. ROOF UNDERLAYMENT BY WOODLAND INDUSTRIES INC. - FLORIDA BUILDING APPROVAL #FL17206.1-R4. 5. GULF COAST SUPPY AND MANUFACTURING METAL ROOK JG - FLORIDA BUILDING APPROVAL #FL11651-R3. 6. INNOVATIONS MANUFACTURING, INC. TRANSOM WINDOWS - FLORIDA BUILDING APPROVAL #FL17667.1-R1. 7. FLOOD SOLUTIONS, LLC FLOOD VENTS (IF REQ'D)- FLORIDA BUILDING APPROVAL #FL17588.1-R1. 8. OX PAPERBOARD MICHIGAN, LLC THERMO-PLY SHEATHIN ') - FLORIDA BUILDING APPROVAL #FL16391.1-R2. 9. TUFF SHED, INC DOORS - FLORIDA BUILDING APPROVAL #FL22202.1-R3, #FL22202.2-R3, #FL22202.3-R3, #FL22202.4-R3. 10. HDU HOLDOWNS BY SIMPSON STRONG -TIE - FLORIDA BUILDING APPROVAL #FL10441.4-R5. 11. SSTB ANCHOR BOLTS BY SIMPSON STRONG -TIE - FLORIDA BUILDING APPROVAL #FL13628.2-R4. TUFF SHED Storage Buildings & Garages TUFF SHED, MFG. FACILITIES Order #. UNINHABITED UTILITY SHED UP TO 12' WIDE x UP TO 24' LONG SR600, TR700, PR P.O. # OVERHANG OPTIONS A REFER TO THE TRUSS DESIGN FOR LUMBER SIZE, TRUSS SPACING AND PLATE SIZE (1) SIMPSON H2.5A TIE PER BEARING, (2) TOTAL PER TRUSS, �- COLLAR TIE REQUIRED ONLY AT INSTALLED PER MANUFA( T 12' WIDE SHEDS 12 FLORIDA APPROVED OWENS RAFTER TRUSS 4 CORNING OAKRIDGE 30 YEAR SHINGLES - #FL10674.1-R13 -OR- FLORIDA APPROVED GULF COAST SUPPLY AND MANUFACTURING METAL ROOFING - #FL11651-R3 SEE SHEET 3 FOR STEEL FLOOR WITH ANCHOR DETAIL OR FOUNDATION DETAIL UP TO 12' WIDE OBUILDING SECTION SCALE: N.T.S. WALL SHEATHING NAILING -- REFER TO SHEET 2 FOR WALL SHEATHING NAILING ROOF SHEATHING NAILING - 1. USE 0.113"0 X 2%8' HOT DIPPED GALVANIZED RING SHANK NAILS 2. NAILING: EDGE - @ 4" O.C. FIELD - @ 8" O.C. HEADER NAILING - 1. HEADER TO STUD - (4) 16d END NAIL 2. DOUBLE HEADER - 16d @ 16" O.C. STAGGERED FACE NAIL MAX WALL HEIGHT FOR EACH SHED: SR600 - 5'-8 1/4" (68 1/4") TR700 - 6-8 1/4" (80 1/4") PR - 6'-4 1/2" (76 1/2") Customer: Site Address: o.85802 Drawn By: PK Date: 8/15/16 STATE OF0 Checked By: 10 Date: �+ BuildingS lZe.WIDTH-LENGTH-HEIGHT SQ. FT AREA [Scale. N.T.S. THESE DRAWINGS AND THE DESIGN ARE THE PROPERTY OF TUFF SHED, INC. THESE DRAWINGS ARE FOR A BUILDING TO BE SUPPLIED AND BUILT BY TUFF SHED. ANY OTHER USE IS FORBIDDEN BY BOTH TUFF SHED AND THE ENGINEER OF RECORD SEE THE TRUSS CONNECTION DETAIL - DETAIL 2 WALL FRAMING TO BE 2x4 SPF #2 OR BETTER @ 16" O.C. IF BUILDING IS LOCATED IN A FLOOD ZONE THEN FLOOD VENTS AND PRESSURE TREATED STUDS ARE REQUIRED - MINIMUM (2) VENTS, (1) EACH ON OPPOSITE WALLS - ONE SQ INCH VENT FOR EVERY ONE SQ FT OF BUILDING TUFF SHED, INC. ENGINEERING DEPARTMENT COLIN SWAYSLAND, P.E. 177'7 S. HARRISON STREET DENVER, COLORADO 80210 (303) 753-8833 EXT. 96317 WALL TOP I TOE NAIL WITH (3) 6d NAILS, (2) ONE 'IDE, (1) OTHER 'IDE OTRUSS TO WALL CONNECTION DETAIL ROOF SHEATHING (7/16" OSB) FBC 2304.8.2 ASPHALTIC SHINGLES FBC 1507.2 OR METAL ROOF FBC 1507.4 FOR 4:12 ROOF SLOPE SCALE. N T.S. DRIP EDGE PER FBC 1507.2.9.3 ALL FASTENERS FBC 1507 REFERENCE NAILING NOTES OROOF ASSEMBLY DETAIL 'SCA tTt§1111/, , ,�`"MVV. ••�.��•E•"sF••.yo'': o.85802 ; STATE OF0 ' 10 = ROOF UNDERLAYMENT FBC 1507.1.1 FOR 4:12 ROOF SLOPE PANEL EDGE SUPPORTED BY PANEL EDGE CLIPS (H -CLIPS) TITLE DRAWING NO. BUILDING SECTIONS FL -PR -SR -TR -01 HEADER FRAMING DETAILS REV. LEVEL 01 FBC, 6th EDITION (2017) SHEET 145C PAGE 1 OF 4 SHEAR WALL NAILING NOTES: 1. USE 0.113"0 X 23/8" HOT DIPPED GALVANIZED RING SHANK NAILS 2. NAILING: EDGE - @ 3" O.C. FIELD - (cD_ 6" O.C. 3. NAILING IS FOR 3/9" SMARTSIDE PANEL OR 3/8" SMARTSIDE WITH FOIL BACKER. 4. NO SINGLE OPENING GREATER THAN 8'-0". 5. 6' WIDE X 6'-9' LONG, 8' WIDE X 8'-12' LONG BUILDINGS ARE BASED ON 3 -SIDED DIAPHRAGM. THE END WALL OPPOSITE OF THE WALL WITH OPENINGS MUST BE FULLY SHEATHED WITH NO OPENINGS. 6. THE DOOR END WALL SHALL SHEATHED ON BOTH SIDES WITH MINIMUM 3/8" SMARTSIDE FOR THE FOLLOWING SIZE BUILDINGS: 6.1. 10' WIDE X 20' LONG - 4' WIDE DOOR 6.2. 10' WIDE X 14'-20' LONG - 6' WIDE DOOR 6.3. 12' WIDE X 20'-24' LONG - 6' WIDE DOOR 7. ALL OTHER SIZES NOT LISTED IN NOTES 5 AND 6 WILL HAVE TYPICAL NAILING AS DESCRIBED IN NOTE 2. 12 4 2'-0" 6'-0" 2,-0" MIN MAX I MIN MAX. 12'-0" WALL A ELEVATION SCALE: 3116"= 1'-0" FLOOD VENT (AS REQ'D), MIN OF (2) VENTS, (1) EACH ON OPPOSITE WALLS, TOTAL VENT OPENING AREA (SQ. IN.) SHALL EXCEED SHED AREA (SQ. FT.), INSTALL ADDITIONAL VENTS AS REQ'D *DOORS AND/OR WINDOWS INSTALLED WITHIN T-0" OF WALL EDGE MUST BE RATED FOR ZONE 5 WIND PRESSURES (+28 PSF/-37 PSF) IVI/"V\. LT -V WALL B ELEVATION SCALE: 3/16" = 1'-0" DOUBLE TOP PLATE CRIPPLES (IF REQ.) HEADERS, SEE TABLE BELOW 2x4 WINDOW SILL FLOOR DECKING BASE PLATE FOR WINDOW OPENINGS UP TO 4'-0" OWINDOW HEADER DETAIL FOR SIDE WALLS SCALE: N.T.S. _..... ,.r.... CRIPPLE STUD HEADERS, SEE TABLE TRIMMER STUD MAX. 12'-0" WALL C ELEVATION SCALE: 3/16"= 1'-0" TUFF SHED Storage Buildings & Garages TUFF SHED, MFG. FACILITIES Order #. Customer: Site Address: Iding Size.WIDTH-LENGTH -I HEIGHT -SQ. ET. MAX. 24'-0" WALL D ELEVATION SCALE: 3/16"= 1'-0" P.O. # Drawn By: PK Date: 8/15/16 Checked By: Date: Scale: N.T.S THESE DRAWINGS AND THE DESIGN ARE THE PROPERTY OF TUFF SHED, INC. THESE DRAWINGS ARE FOR A BUILDING TO BE SUPPLIED AND BUILT BY TUFF SHED. ANY OTHER USE IS FORBIDDEN BY BOTH TUFF SHED AND THE ENGINEER OF RECORD. DOUBLE TOP PLATE CRIPPLES (IF REQ.) HEADERS, SEE TABLE BELOW KING STUD (1) TRIMMER FOR OPENINGS UP TO 6-0" (2) TRIMMERS FOR OPENINGS 6-1" TO 8'-0" BASE PLATE FLOOR DECKING FOR OPENINGS UP TO 8'-0" 2 DOOR HEADER DETAIL FOR SIDE WALLS SCALE: N.T.S. 2x4 TOP PLATE 2x4 SPF #2 2x6 SPF #2 4 HEIGHT LIMITATION ALTERNATIVE HEADER SCALE'. N.T.S. DOORIWINDOW HEADER SCHEDULE WALLS A AND C (END WALLS) OPENINGS UP TO 6-0" USE (2) 2x4 SPF #2 WALLS B AND D (SIDEWALLS) OPENINGS UP TO 4'-0" USE (2) 2x4 SPF #2 OPENINGS 4'-1" TO 6'-0" USE (2) 2x6 SPF #2 -OR- HEIGHT LIMITATION ALTERNATIVE - SEE DETAIL OPENINGS 6-1" TO 8'-0" USE (2) 2x8 SPF #2 THESE DRAWINGS ARE DESIGNED FOR VARIABLE DOOR AND WINDOW PLACEMENT AS INDICATED BY SHADED AREAS ON ELEVATIONS. MINIMUM SHEAR RETURN WALLS INDICATED ON ELEVATIONS. TUFF SHED, INC. ENGINEERING DEPARTMENT COLIN SWAYSLAND, P.E. 1777 S. HARRISON STREET DENVER, COLORADO 80210 (303) 753-8833 EXT. 96317 c�•' �' • a�a02 s _ No * �� �-ns•I�l \` R ''� A• •''*. ��.�\n '¢moi �,r TITLE DOOR DETAILS NAILING REQUIREMENTS FBC, 6th EDITION (2017) DRAWING NO. FL -PR -SR -TR -01 REV. LEVEL 01 1 ISHEET 2 I 145C PAGE 2 OF 4 F ALL DOORSAMNDOWS LOCATED; C? - = IN THIS AREA "� w i< J QQ J :` 2'-0" 6'-0" 2,-0" MIN MAX I MIN MAX. 12'-0" WALL A ELEVATION SCALE: 3116"= 1'-0" FLOOD VENT (AS REQ'D), MIN OF (2) VENTS, (1) EACH ON OPPOSITE WALLS, TOTAL VENT OPENING AREA (SQ. IN.) SHALL EXCEED SHED AREA (SQ. FT.), INSTALL ADDITIONAL VENTS AS REQ'D *DOORS AND/OR WINDOWS INSTALLED WITHIN T-0" OF WALL EDGE MUST BE RATED FOR ZONE 5 WIND PRESSURES (+28 PSF/-37 PSF) IVI/"V\. LT -V WALL B ELEVATION SCALE: 3/16" = 1'-0" DOUBLE TOP PLATE CRIPPLES (IF REQ.) HEADERS, SEE TABLE BELOW 2x4 WINDOW SILL FLOOR DECKING BASE PLATE FOR WINDOW OPENINGS UP TO 4'-0" OWINDOW HEADER DETAIL FOR SIDE WALLS SCALE: N.T.S. _..... ,.r.... CRIPPLE STUD HEADERS, SEE TABLE TRIMMER STUD MAX. 12'-0" WALL C ELEVATION SCALE: 3/16"= 1'-0" TUFF SHED Storage Buildings & Garages TUFF SHED, MFG. FACILITIES Order #. Customer: Site Address: Iding Size.WIDTH-LENGTH -I HEIGHT -SQ. ET. MAX. 24'-0" WALL D ELEVATION SCALE: 3/16"= 1'-0" P.O. # Drawn By: PK Date: 8/15/16 Checked By: Date: Scale: N.T.S THESE DRAWINGS AND THE DESIGN ARE THE PROPERTY OF TUFF SHED, INC. THESE DRAWINGS ARE FOR A BUILDING TO BE SUPPLIED AND BUILT BY TUFF SHED. ANY OTHER USE IS FORBIDDEN BY BOTH TUFF SHED AND THE ENGINEER OF RECORD. DOUBLE TOP PLATE CRIPPLES (IF REQ.) HEADERS, SEE TABLE BELOW KING STUD (1) TRIMMER FOR OPENINGS UP TO 6-0" (2) TRIMMERS FOR OPENINGS 6-1" TO 8'-0" BASE PLATE FLOOR DECKING FOR OPENINGS UP TO 8'-0" 2 DOOR HEADER DETAIL FOR SIDE WALLS SCALE: N.T.S. 2x4 TOP PLATE 2x4 SPF #2 2x6 SPF #2 4 HEIGHT LIMITATION ALTERNATIVE HEADER SCALE'. N.T.S. DOORIWINDOW HEADER SCHEDULE WALLS A AND C (END WALLS) OPENINGS UP TO 6-0" USE (2) 2x4 SPF #2 WALLS B AND D (SIDEWALLS) OPENINGS UP TO 4'-0" USE (2) 2x4 SPF #2 OPENINGS 4'-1" TO 6'-0" USE (2) 2x6 SPF #2 -OR- HEIGHT LIMITATION ALTERNATIVE - SEE DETAIL OPENINGS 6-1" TO 8'-0" USE (2) 2x8 SPF #2 THESE DRAWINGS ARE DESIGNED FOR VARIABLE DOOR AND WINDOW PLACEMENT AS INDICATED BY SHADED AREAS ON ELEVATIONS. MINIMUM SHEAR RETURN WALLS INDICATED ON ELEVATIONS. TUFF SHED, INC. ENGINEERING DEPARTMENT COLIN SWAYSLAND, P.E. 1777 S. HARRISON STREET DENVER, COLORADO 80210 (303) 753-8833 EXT. 96317 c�•' �' • a�a02 s _ No * �� �-ns•I�l \` R ''� A• •''*. ��.�\n '¢moi �,r TITLE DOOR DETAILS NAILING REQUIREMENTS FBC, 6th EDITION (2017) DRAWING NO. FL -PR -SR -TR -01 REV. LEVEL 01 1 ISHEET 2 I 145C PAGE 2 OF 4 #12-14 X 3" HEX HEAD WIDTH LENGTH QTY SELF -DRILLING SCREWS 1. STEEL SHED FOUNDATION: 6 10' 10'-16' 60OT125-054 -16 GAUGE STEEL TRACKS G140 ZINC COATED 3/4" APA OR TECO RATED 8 600S137-054 - 16 GAUGE STEEL JOISTS G140 ZINC COATED T&G FLOOR DECKING. 12' 20'-24' @ 24" O.C. 2X6 STEEL JOISTS n (SUPPLIER: ALLIED STUDCO (JOIST: 600S137-054 /TRACK: @ 24" OC 600T125-054) ICC ER -4943P. ® 2. 3/4" APA OR TECO RATED TONGUE AND GROOVE FLOOR #10 X 3/4" PAN r® DECKING. 24" MAX PANEL SPAN. STAGGER PANEL LAYOUT. HEAD SELF -DRILLING SCREWS (2 PER TAB) ® 3. FASTEN FLOOR DECKING TO JOIST &TRACKS USING r TYP. #8 x 1-5/8" ZINC PLATED SCREWS @ 12" O.C. VENT HOLES @ 24" OC. ® ® NO BLOCKING REQUIRED. ALL EDGES SHALL LIE ON FLOOR 8 JOISTS. STAGGER PANEL LAYOUT PER APA CONDITION 1. OPTIONAL LEVELING BLOCKS 4. FASTEN SOLE PLATE THROUGH FLOOR DECKING INTOIJOISTS 2X6 STEEL TRACK EACH END MIN. OR TRACKS WITH #12-14 X 3" GALVANIZED SELF -DRILLING CONCRETE FOUNDATION DETAIL i SCALE: N.T.S. SCREWS. REFERENCE SPACING CHART. BASE PLATE SCREW SPACING i 5. ALLOWABLE FLOOR LIVE LOAD: 75 PSF FOR STEEL JOISTS WIDTH SPACING CONTINUOUSLY SUPPORTED. 50 PSF FOR JOISTS ON BLOCKS 6-12' 8" O.C. AS SHOWN. 6. USE OPTIONAL CONCRETE BLOCKS AS REQUIRED TO LEVEL BUILDING: SUGGESTED SIZES: 2" x 8" x 16", 4" x 8" x 16", OR 8" x 8" x 16". OSTEEL SHED BASE DETAIL BLOCKS UNDER JOISTS SPACED @ 8'-0" O.C. MAXIMUM. BLOCKS UNDER TRACK SPACED @ 4'-0" O.C. MAXIMUM. SCALE: N.T.S. SIDING TRIM 3/8" CARRIAGE BOLT (GRADE 2) OT17SWB -OR- OT24SWB 91 1/2" HILTI KWIK BOLT TZ STUD 3/8" NYLON LOCK NUT BASEPLATE KWIK BOLT ANCHORS (INTO CONCRETE) RE: DETAIL 3 SHEET 3 WIDTH LENGTH QTY 6' 6'-9' 6 8' 8'-16 6 10' 10'-16' 6 10' 18'-20' 8 12' 12'-18' 8 12' 20'-24' 10 FLOOR PLY NOTES: 1. ANCHORS TO BE KWIK BOLT TZ, 304 SS. 2. PROVIDE (1) ANCHOR AT EACH OF THE (4) CORNERS. EQUALLY CD SPACE HALF OF THE REMAINING ANCHORS AT EACH OF THE (2) SIDEWALLS: STAINLESS STEEL 304 a v >- c� EMBEDMENT DEPTH = 2 3/8" STEEL SHED MIN. EDGE DISTANCE = 6" BASE ANCHOR SPACING: RE: KWIK 4" CONCRETE BOLT ANCHORS TABLE, SHEET 3 PAD (MIN) OSIDEWALL BRACKET DETAIL_ SCALE: N.T.S. Y OF THE REMAINING ANCHORS SQUALLY SPACED AT WALL B OF THE REMAINING ANCHORS E2QUALLY SPACED AT WALL D 3. PROVIDE (1) ANCHOR AT MID WALL FOR ALL 12 WIDE END WALLS. BLOCK TRIM SIDING ATTACH BRACKET TO STUD THRU HOLE IN ANCHOR PLATE WITH MIN. 3/8"0 x 6 1/2" CARRIAGE BOLT AND LOCKNUT (3) STUD CORNER AUGER ANCHOR COMPONENTS BY OLIVER TECHNOLOGIES • PART NUMBERS: OT3644GPMP- 5/8" X 36" (36" IMBED) GALVANIZED AUGER OTI7SWB - SIDEWALL BRACKET FOR USE WITH THRU BOLTS REPORT NO. LO-FJ90129-A -OR- OT24SWB - SIDEWALL BRACKET FOR USE WITH THRU BOLTS REPORT NO. LO-FJ90129-B • WORKING LOAD FOR ANCHOR SYSTEM IS 3,150 LBS WITH THE MAXIMUM LOAD OF 5,080 LBS SIDING TRIM ANCHOR BRACKET TO BE FLUSH WITH (4)AUGER ANCHOR DETAIL SCALE: N.T.S. UNHEATED SPACE ANCHOR BOLT & P.T. SILL PLATE PER NOTES BELOW AUGER ANCHOR NOTES 1. (1) AUGER ANCHOR SHALL BE PROVIDED AT EACH CORNER FOR A TOTAL OF (4) AUGER ANCHORS. 2. (1) ADDITIONAL AUGER ANCHOR SHALL BE PROVIDED AT EACH END OF EVERY DOOR OPENING FOR A TOTAL OF (2) ADDITIONAL AUGER ANCHORS AT EVERY DOOR OPENING. 3. (1) ADDITIONAL AUGER ANCHOR SHALL BE PROVIDED AT SIDEWALL MIDSPAN FOR SIDEWALLS 20' OR LONGER WITH NO OPENINGS. CONTINUOUS FOOTING NOTES 1. TOP OF SLAB TO BE 6" MIN. ABOVE GRADE. SLAB REINFORCEMENT SHALL BE WWF 6X6 W1.4xW1.4 . LOCATE AT MID -DEPTH OF SLAB. -OR- SLAB REINFORCEMENT SHALL BE FIBERMESH 150 OR BLENDED FIBERMESH150. FIBERMESH SHOULD BE DISPERSED UNIFORMLY THROUGH CONCRETE W/ MIN. 1 POUND PER CUBIC YARD OF CONCRETE. 2. ALL FOOTING FORMS SHALL BE INSPECTED FOR SIZE AND REINFORCING BEFORE POURING CONCRETE. 3. FOOTINGS SHALL BEAR ON UNDISTURBED NATURAL, COMPETENT SOIL, OR PROPERLY COMPACTED STRUCTURAL FILL. ALLOWABLE SOIL BEARING PRESSURE IS 1000 PSF AT 12" BELOW GRADE. 4. CONCRETE: MINIMUM 28 DAY COMPRESSIVE STRENGTH, fc = 2500 PSI. 5. REINFORCING STEEL: A615, GRADE 40 OR GRADE 60. ALL REINFORCING STEEL SHOWN TO BE CONTINUOUS MAY BE LAPPED A MINIMUM OF 38 BAR DIAMETERS OR 24" MINIMUM, WHICHEVER IS LARGER. 6. SEISMIC DESIGN CATEGORY: A A. ATTACH PRESSURE TREATED SOLE PLATE TO THE FOOTING USING 1/2" DIA X 12" LONG SIMPSON TITEN HD ANCHOR WITH OVERSIZED WASHERS. B. ANCHOR BOLTS SHALL BE EMBEDDED AT LEAST 7" INTO THE CONCRETE AND SHALL BE SPACED NOT MORE THAN 2' OC. C. THERE SHALL BE A MINIMUM OF 2 BOLTS PER SOLE PLATE PIECE WITH 1 BOLT LOCATED NOT MORE THAN 12" NOR LESS THAN 7 BOLT DIAMETERS FROM EACH END OF EACH PIECE. Order #. P.O. # THESE DRAWINGS AND THE ���`` j 0 A . •�Z . — DESIGN ARE THE PROPERTY TUFF SHED, INC. #��°•i�4�b,,.•••••.,,, L,4 ''fe TITLE DRAWING NO. 5HED Customer: Drawn By: PK OF TUFF SHED, INC. THESE ENGINEERING DEPARTMENT � � ; •' �\C EN S TUFF�'•. �� FL -PR -SR -TR -01 DRAWINGS ARE FORA DETAILS Date: 8/15/16 BUILDING TO BE SUPPLIED - No• REV. LEVEL 01 Storage Buildings &Garages Site Address: COLIN SWAYSLAND, P.E. F5802 AND BUILT BY TUFF SHED. TUFF SHED, MFG. FACILITIES = Checked By: ANY OTHER USE IS FORBIDDEN BY BOTH TUFF 1777 S. HARRISON STREET FBC, 6th EDITION 2017 SHEET STATE OF : �4"� ; ( ) Building SIZe.WIDTH-LENGTH - HEIGHT- SQ. FT. AREA Date. SHED AND THE ENGINEER OF DENVER, COLORADO 80210=y'��'•.• �,/ Scale: N.T.S. RECORD (303) 753-8833 EXT. 96317 t'��,;`'(C R •`��\�� 145C PAGE 3 OF 4 I/T1iIlit t1.V"I a v >- c� 1 3/4' FINISH GRADE #4 CONTINUOUS TOP & BOTTOM CONCRETE FLOOR - z i>, a--- a -.--- ---- v q a – - Z n SLAB REINFORCEMENT U3" CLR. PER NOTES BELOW - F- TYP. M 8 THICKENED SLAB MIN. 4 CONCRETE FOUNDATION DETAIL \ ___.... SCALE: N.T.S. ..t�111111II��/t.- AUGER ANCHOR NOTES 1. (1) AUGER ANCHOR SHALL BE PROVIDED AT EACH CORNER FOR A TOTAL OF (4) AUGER ANCHORS. 2. (1) ADDITIONAL AUGER ANCHOR SHALL BE PROVIDED AT EACH END OF EVERY DOOR OPENING FOR A TOTAL OF (2) ADDITIONAL AUGER ANCHORS AT EVERY DOOR OPENING. 3. (1) ADDITIONAL AUGER ANCHOR SHALL BE PROVIDED AT SIDEWALL MIDSPAN FOR SIDEWALLS 20' OR LONGER WITH NO OPENINGS. CONTINUOUS FOOTING NOTES 1. TOP OF SLAB TO BE 6" MIN. ABOVE GRADE. SLAB REINFORCEMENT SHALL BE WWF 6X6 W1.4xW1.4 . LOCATE AT MID -DEPTH OF SLAB. -OR- SLAB REINFORCEMENT SHALL BE FIBERMESH 150 OR BLENDED FIBERMESH150. FIBERMESH SHOULD BE DISPERSED UNIFORMLY THROUGH CONCRETE W/ MIN. 1 POUND PER CUBIC YARD OF CONCRETE. 2. ALL FOOTING FORMS SHALL BE INSPECTED FOR SIZE AND REINFORCING BEFORE POURING CONCRETE. 3. FOOTINGS SHALL BEAR ON UNDISTURBED NATURAL, COMPETENT SOIL, OR PROPERLY COMPACTED STRUCTURAL FILL. ALLOWABLE SOIL BEARING PRESSURE IS 1000 PSF AT 12" BELOW GRADE. 4. CONCRETE: MINIMUM 28 DAY COMPRESSIVE STRENGTH, fc = 2500 PSI. 5. REINFORCING STEEL: A615, GRADE 40 OR GRADE 60. ALL REINFORCING STEEL SHOWN TO BE CONTINUOUS MAY BE LAPPED A MINIMUM OF 38 BAR DIAMETERS OR 24" MINIMUM, WHICHEVER IS LARGER. 6. SEISMIC DESIGN CATEGORY: A A. ATTACH PRESSURE TREATED SOLE PLATE TO THE FOOTING USING 1/2" DIA X 12" LONG SIMPSON TITEN HD ANCHOR WITH OVERSIZED WASHERS. B. ANCHOR BOLTS SHALL BE EMBEDDED AT LEAST 7" INTO THE CONCRETE AND SHALL BE SPACED NOT MORE THAN 2' OC. C. THERE SHALL BE A MINIMUM OF 2 BOLTS PER SOLE PLATE PIECE WITH 1 BOLT LOCATED NOT MORE THAN 12" NOR LESS THAN 7 BOLT DIAMETERS FROM EACH END OF EACH PIECE. Order #. P.O. # THESE DRAWINGS AND THE ���`` j 0 A . •�Z . — DESIGN ARE THE PROPERTY TUFF SHED, INC. #��°•i�4�b,,.•••••.,,, L,4 ''fe TITLE DRAWING NO. 5HED Customer: Drawn By: PK OF TUFF SHED, INC. THESE ENGINEERING DEPARTMENT � � ; •' �\C EN S TUFF�'•. �� FL -PR -SR -TR -01 DRAWINGS ARE FORA DETAILS Date: 8/15/16 BUILDING TO BE SUPPLIED - No• REV. LEVEL 01 Storage Buildings &Garages Site Address: COLIN SWAYSLAND, P.E. F5802 AND BUILT BY TUFF SHED. TUFF SHED, MFG. FACILITIES = Checked By: ANY OTHER USE IS FORBIDDEN BY BOTH TUFF 1777 S. HARRISON STREET FBC, 6th EDITION 2017 SHEET STATE OF : �4"� ; ( ) Building SIZe.WIDTH-LENGTH - HEIGHT- SQ. FT. AREA Date. SHED AND THE ENGINEER OF DENVER, COLORADO 80210=y'��'•.• �,/ Scale: N.T.S. RECORD (303) 753-8833 EXT. 96317 t'��,;`'(C R •`��\�� 145C PAGE 3 OF 4 I/T1iIlit t1.V"I MIN (2) 2X STUDS. USE (3) 2X STUDS AT END WALL. a SDS1/4X3 SCREWS HEX NUT a HDU HOLDOWN a° a d a TREATED SILL PLATE a SSTB ANCHOR FOUNDATION SSTB & HDU INSTALLATION SCALE: N.T.S. HOLDOWN NOTES 1. (1) HOLDOWN SHALL BE PROVIDED AT EACH OF THE (4) CORNERS FOR A TOTAL OF (4) HOLDOWNS. 2. (1) ADDITIONAL HOLDOWN SHALL BE PROVIDED AT EACH END OF EVERY DOOR OPENING FOR A TOTAL OF (2) ADDITIONAL HOLDOWNS AT EVERY DOOR OPENING. 3. WHEN THE MINIMUM ALLOWABLE 2' -LONG SHEARWALLS ARE PROVIDED AT WALL A, THE FOLLOWING HOLDOWNS SHALL BE USED AT THE WALL A DOOR OPENING: 8' WIDE X 6'-10' LONG - 4' WIDE DOOR (2) HDU2, (1) AT EACH END OF OPENING 10' WIDE X 10'-20' LONG - 6' WIDE DOOR (2) HDU4, (1) AT EACH END OF OPENING 12' WIDE X 12'-24' LONG - 6' WIDE DOOR (2) HDU4, (1) AT EACH END OF OPENING 4. HDU2 HOLDOWNS SHALL BE USED AT ALL OTHER REQUIRED LOCATIONS. 5. HOLDOWNS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. 6. HOLDOWNS SHALL BE RE -TIGHTENED JUST PRIOR TO COVERING THE WALL FRAMING. C° 3X4 20 PLATES _ 3X4 20 GA PLATES 6' SPAN REACTIONS: T-0" 1 EACH SIDE civ 1 EACH SIDE r MAX. VERTICAL: 205 LBS. Date: 8/15/16 5-0 S,3 MAX. UPLIFT: -160 LBS. 8 r 1/16„ - 2 �4 12 a4 NOTE: 8524 EAST COLONIAL DRIVE TRUSS MAY BE USED ON BUILDING LENGTHS 0 18 0° UP TO 12FT UNLESS CEILING JOIST OR OTHER ° TENSION TIE IS PROVIDED. 00 6'-0" LO 788 -TUFF FF -TUFF 10' SPAN N 00 " 10'-0 REACTIONS: C14 MAX. VERTICAL: 510 LBS. MAX. UPLIFT: -250 LBS. 3X4 20 PLATES 00 3X4 20 GA PLATES M NOTE - 00 1 EACH SIDE 1 EACH SIDE r 6'-0" TRUSS MAY BE USED ON BUILDING LENGTHS °' 4-0' 11/16° UP TO 20FT UNLESS CEILING JOIST OR OTHER TENSION TIE IS PROVIDED. 12 12 �4 a 4 8' SPAN REACTIONS: - QD O0 3X6 20 GA MAX. VERTICAL: 255 LBS. ° PLATES MAX. UPLIFT: -195 LBS. w 8'-0" - 1 EACH SIDE NOTE: LO C\I 6'-0" TRUSS MAY BE USED ON BUILDING LENGTHS 04 UP TO 14FT UNLESS CEILING JOIST OR OTHER 12'-0" TENSION TIE IS PROVIDED. DESIGN LOADS: TOP CHORD LIVE LOAD = 20 PSF TOP CHORD DEAD LOAD = 10 PSF COLLAR TIE DEAD LOAD = 5 PSF NOTES: FBC, 6th EDITION (2017) ANSI/TPI 1-2007 TRUSSES TO BE SPACED @ 24" OC MATERIAL TO BE 2X4 SPRUCE PINE FIR GRADE #2 OR BETTER PLATES ARE TO BE PRESSED IN THE WOOD PER TPI. REF' MEMBER INCREASE: YES LUMBER D.O.L.: 1.25 WIND: ASCE 7-10,155 mph, Exposure C, D.O.L.=1.60 PLATES ARE MANUFACTURED BY EAGLE METAL PRODUCTS, ICC --ES #ESR -1082. TUFF SHED Order #. Customer: - P.O. # Drawn By: PK Storage Buildings & Garages - Date: 8/15/16 Site Address: SHED, MFG. FACILITIES - Checked By: nht(888) 8524 EAST COLONIAL DRIVE Date: ORLANDO, FL Building SIZe.WIDTH-LENGTH -HEIGHT -SQ.FT. AREA 788 -TUFF FF -TUFF STORE520 Scale: N.T.S. THESE DRAWINGS AND THE DESIGN ARE THE PROPERTY OF TUFF SHED INC. THESE DRAWINGS ARE FOR A BUILDING TO BE SUPPLIED AND BUILT BY TUFF SHED. ANY OTHER USE IS FORBIDDEN BY BOTH TUFF SHED AND THE ENGINEER OF RECORD ALL PERSONS FABRICATING, HANDLING, ERECTING OR INSTALLING THIS TRUSS ARE TO DO SO IN ACCORDANCE TO THE RECOMMENDATIONS OF THE LATEST VERSION OF THE BCSI. TUFF SHED, INC. ENGINEERING DEPARTMENT COLIN SWAYSLAND, P.E. 1777 S. HARRISON STREET DEN`✓ER, COLORADO 80210 (303) 753-8833 EXT. 96317 /NNo�. 85802 =_ �l-os�Ii- STATE OF I')' CMAAI REACTIONS: MAX. VERTICAL: 630 LBS. MAX. UPLIFT: -285 LBS. NOTE: TRUSS MAY BE USED ON BUILDING LENGTHS UP TO 24FT UNLESS CEILING JOIST OR OTHER TENSION TIE IS PROVIDED. MAXIMUM DEFLECTION (12 FT. SPAN) VERT LL: 0.06 in. VERT TL: 0.08 in. TITLE DRAWING NO. TRUSS DETAILS FL -PR -SR -TR -01 REV. LEVEL 01 1 FBC, 6th EDITION (2017) SHEET 4 145C PAGE 4 OF 4