560 Sherry Dr Denied Bldg Review Comments 'r- l�, �' CITY OF ATLANTIC BEACH f 800 SEMINOLE ROAD ATLANTIC BEACH, FL 32233 (904) 247-5800 BUILDING REVIEW COMMENTS Date: 4/25/2019 Permit#: RESA18-0019 Site Address: 560 SHERRY DR Review Status: denied REM 170469 0000 Applicant: The FaverGray Company Property Owner: FAVER WILLIAM K ET AL Email: wfaver@favergray.com Email: Phone: 9042082000 Phone: 9043020534 THIS REVIEW IS ONE OF MULTIPLE DEPARTMENT REVIEWS. Revisions may not be submitted until ALL departments have completed their respective reviews. Revisions submitted MUST respond to EACH department review. Submittals that respond to only one or a few correction items will not be accepted. Correction Comments: 1. Design Information numbers for Sensible and Latent Cooling Equipment Sizing do not match the Manual S Cooling Equipment numbers under design conditions. They should. The small letter `n' on page I of the Design Information, under Sensible Cooling Equipment Load Sizing, across from `Use manufacturer's data', tells me the information was not put in correctly to the software system. Have your HVAC person call Tricia Higgins, 407-314-8495, and ask for help in getting the issue worked out. Her email is speedycalcs@yahoo.com Building Mike Jones Building Inspector/Plans Examiner City of Atlantic Beach 800 Seminole Road Atlantic Beach, FL 32233 (904) 247-5844 Email:mjones@coab.us Resubmittal Notes: All revisions and changes shall clearly stand out from the rest of the drawing on the sheet as a revision by way of completely encircling the change with "clouding".The revision shall also be identified as to the sequence of revision by indicating a triangle with the revision sequence number within it and located adjacent to the cloud. The revision date and revision sequence number shall also be indicated in a conspicuous location in the title block for each sheet on which a revision for that sequence occurs. For projects still in the initial review stage and permit pending, all sheets with revisions shall be inserted into each set of drawings.The original sheets must be clearly marked "VOID" but are to be left within the set of drawings. Complete new sets of drawings will not be accepted. ADDITIONAL ITEMS MAY BE REQUIRED DEPENDING UPON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW. Revision Request/Correction to Comments "ALL INFORMATION HIGHLIGHTED IN City of Atlantic Beach Building Department GRAY IS REQUIRED. 800 Seminole Rd, Atlantic Beach, FL 32233 ((�� Phone: (904) 247-5826 Email: 1\ Building-Dept@coab.us PERMIT �5ooM ❑ Revision to Issued Permit OR Corrections to Comments Date:_ Ll Iq N Project Address: �60 5he!'r•1 Dd'i4i, Contractor/Contact Name: i'� kh, �C((SP,•a 1Zt�Pi( Contact Phone: -� r Email: V�� � Description of Proposed Revision/Corrections: ffi m l S �,d CCAV S I affirm the revision/correction to comments is inclusive of the proposed changes. (printed name) • WWII proposed revision/corrections add additional square footage to original submittal? �No ❑ Yes (additional s.f. to be added: ) • Wi proposed revision/corrections add additional increase in building value to original submittal? No ❑*Yes (additional increase in building value: $ ) (Contractor must sign if increase in valuation) *Signature of Contractor/Agent: (Office Use Only) ❑ Approved ❑ Denied ❑ Not Applicable to Department Permit Fee Due �� Revision/Plan Review Comments_/,`4211 Va I S A yr*A Int y-% C1. Y-e 1-i%c-dVvle4,1� Department Review Required: �. uilding � anning&Zoning Reviewed By Tree Administrator Public Works Public Utilities 12- r/2-61 9 Public Safety Date Fire Services Updated 10/17/18 Load Short Form Job: Date: April 18,2018 Entire House By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL32207 Phone:9046266675 Email:whteys.air@grriail.com Web:whitleysheafinganclair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Information Htg Clg Infiltration Outside db(°F) 36 91 Method Simplified Inside db(°F) 68 75 Construction quality Average Design TD(°F) 32 16 Fireplaces 0 Daily range - M Inside humidity(%) 50 50 Moisture difference(gr/Ib) 26 52 HEATING EQUIPMENT COOLING EQUIPMENT Make Bryant Make Bryant Trade BRYANT HEATING AND COOLING SYS... Trade BRYANT HEATING AND COOLING SYS... Model 215BNA0180000A0 Cond 215BNA0180000A0 AHRI ref 9595724 Coil FV4CNF002L AHRI ref 9595724 Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER Heating input Sensible cooling 12390 Btuh Heating output 17600 Btuh @ 47°F Latent cooling 5310 Btuh Temperature rise 31 °F Total cooling 17700 Btuh Actual airflow 525 cfm Actual airflow 525 cffn Airflowfactor 0.029 cfmBtuh Airflowfactor 0.045 cfnBtuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Capacity balance point=37°F Backup: Input=5 kW, Output=17061 Btuh,100 AFLIE ROOM NAME Area Htg load Clg load Htg AVF CIgAVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Porch 160 4052 1765 116 79 Kitchen 160 2217 2339 63 105 BR1 121 1537 849 44 38 BR2 99 2326 1119 66 50 Hall 140 854 906 24 41 Bath 2 54 1405 536 40 24 Bath 1 54 922 374 26 17 MBR 252 1824 1413 52 63 Living/Dining 384 3227 2419 92 108 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wri htsoft' 2019-Apr-19 10:0529 9 RigFi-Suite®Universal 201717.0.23 RSU17328 Page 1 /4C0(>- ...nce\Faver Residence Load-Man S Compliance.np Calc=MJ8 Front Door faces:S Entire House 1424 18364 11720 525 525 Other equip loads 0 0 Equip.@ 0.96 RSM 11298 Latent cooling 3293 TOTALS 1424 18364 14592 525 525 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 2019-Apr-19 10:05:29 wrightsoft Right-Sate®Urrversal 2017 17.0.23 RSU17328 Page 2 ACUK nceTaver Residence Load-Man Complian oe.nup Calc=MJ8 Front Door faces:S Building Analysis Job: Load Calculation g Y Date: April 18,2018 Entire House By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL 32207 Phone:9046266675 Email:wMtieys.air@gmail.com Web:wi itleysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Component Btuh/ft2 Btuh %of load Walls 2.9 5167 28.1 Glazing 18.3 1098 6.0 Walls Infiltration Doors 12.5 526 2.9 Ceilings 1.4 2008 10.9 Floors 3.4 4889 26.6 Infiltration 2.5 4675 25.5 Ducts 0 0 Glazing Piping 0 0 Doors Humidification 0 0 Floors Ventilation 0 0 Ceilings Adjustments 0 Total 18364 100.0 Component Btuh/ft2 Btuh %of load Walls 2.2 3944 33.7 Glazing 21.0 1258 10.7 Internal Gains Doors 11.5 483 4.1 Walls, Ceilings 1.2 1689 14.4 Floors 0 0 0 Infiltration 0.8 1446 12.3 Ducts 0 0 Ventilation 0 0 Infiltration Internal gains 2900 24.7 Blower 0 0 Adjustments 0 Glazing Total 1 1 117201 100.01 Doors Ceilings Latent Cooling Load=3293 Btuh Overall U-value=0.090 Btuh/ft2-°F WARNING:window to floor area ratio=4.2%-less than 5%. i htsoftm 2019-Apr-1910:05:29 wr 9 Rigtt-Suite®Uriversal 201717.0.23 RSU17328 Page 1 .....-aver Residence Load-Man S Compliance.np Calc=MJ8 Front Door faces: S Load Calculation Component Constructions Date: April 18,2018 Entire House By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL 32207 Phone:9046266675 Email:wttitleys.air@gmail.com Web:wtitleysheatingandair.00m License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btu"T ft''F/Btuh Btullft' Btuh Btuhtft' Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2'k4" n 560 0.091 13.0 2.92 1636 2.23 1249 wood frm, 16"o.c.stud a 529 0.091 13.0 2.92 1545 2.23 1179 s 267 0.091 13.0 2.92 780 2.23 595 W 413 0.091 13.0 2.92 1206 2.23 921 all 1769 0.091 13.0 2.92 5167 2.23 3944 Partitions (none) Windows 1 D-clow.2 glazing,dr outr,air gas,wd frm mat,dr innr, 1/4"gap, 1/4"thk; n 24 0.570 0 18.3 439 21.0 503 1.5 ft overhang(4 ft window ht,0 ft sep.);6.67 ft head ht s 24 0.570 0 18.3 439 21.0 503 s 12 0.570 0 18.3 220 21.0 252 all 60 0.570 0 18.3 1098 21.0 1258 Doors 11 D0: Door,wd sc type s 21 0.390 0 12.5 263 11.5 242 W 21 0.390 0 12.5 263 11.5 242 all 42 0.390 0 12.5 526 11.5 483 Ceilings 176-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 1455 0.043 20.0 1.38 2008 1.16 1689 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 154 0.989 0 31.7 4889 0 0 1 wri htsoft° 2019-Apr-1910:05:29 �. 9 Rigtt-Stite@Uriversal20l7 17.0.23 RSU17328 Page 1 +� ...nceTaver Residence Load-Man Compliance.np Calc=MJ8 Frort Door faces: S Component Constructions Job: Load Calculation p Date: April 18,2018 Porch By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL 32207 Phone:9046266675 Email whOeys.air@gmail.com Web:wrtitleysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain fl' Btuhtft-'F ft''F/Btuh BtuhttF Btuh Btuh/fl' Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2"A4" n 224 0.091 13.0 2.92 654 2.23 499 wood frm, 16"o.c.stud a 115 0.091 13.0 2.92 336 2.23 256 W 94 0.091 13.0 2.92 275 2.23 210 all 433 0.091 13.0 2.92 1265 2.23 965 Partitions (none) Windows (none) Doors 11 D0: Door,wd sc type W 21 0.390 0 12.5 263 11.5 242 Ceilings 17B-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 179 0.043 20.0 1.38 247 1.16 208 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 36 0.989 0 31.7 1143 0 0 .c wri htsoft 2019-Apr-1910:05:29 9 Right-Sute®Urrversal2017 17.0.23 RSU17328 Page 2 ...nceTaver Residence Load-Man Compliance.np Calc=MA Frort Door faces: S Job: an Component Constructions Date: April 18,2018 .<, - =r •., '` Kitchen By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL 32207 Phone:9046266675 Email:whitleys.air@gmaiI-oom W eb:whitleysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,AtlantiC Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft`T ft�`F/Btuh BtuWft' Btuh Btu"' Btuh Walls 12C-0sw. Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2"A4" s 99 0.091 13.0 2.92 289 2.23 221 wood frm, 16"o.c.stud w 25 0.091 13.0 2.92 73 2.23 56 all 124 0.091 13.0 2.92 362 2.23 276 Partitions (none) Windows 1 D-c2ow.2 glazing,dr outr,air gas,wd frm mat,dr innr, 1/4"gap, 1/4"thk; s 24 0.570 0 18.3 439 21.0 503 1.5 ft overhang(4 ft window ht,0 ft sep.);6.67 ft head ht Doors 11 D0: Door,wd sc type s 21 0.390 0 12.5 263 11.5 242 Ceilings 1713-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 162 0.043 20.0 1.38 223 1.16 188 1/2"gypsum board int fnsh, 1"thkns Floors 22A-vvpl: Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 16 0.989 0 31.7 508 0 0 .� wri htsoft' 2019-Apr-1910:05:29 A 9 Ngtt-Sute@ Uriversal 2017 17.0.23 RSU17328 Page 3 .....aver Residence Load-Man S Compliance.rLp Calc=MJ8 Front Door faces:S Component Constructions Job: L(1�tCj Cal�.u��tLlJll p Date: April 18,2018 BR1 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksormlle.FL 32207 Phone:9046266675 Email:whUeys.air@gmail.com Web:whUeysheatirrgandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/lb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss CIg HTM Gain fl' Btufdfl?`F fl'-°FBtuh BUM Btuh Btu"' Btuh Walls 12C-0sw. Firm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2'X4" n 142 0.091 13.0 2.92 415 2.23 317 wood frm, 16"o.c.stud Partitions (none) Windows 1 D-c2ow.2 glazing,dr outr,air gas,wd frm mat,dr innr, 1/4"gap, 1/4"thk; n 12 0.570 0 18.3 220 21.0 252 1.5 ft overhang(4 ft window ht,0 ft sep.);6.67 ft head ht Doors (none) Ceilings 17B-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 122 0.043 20.0 1.38 169 1.16 142 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 11 0.989 0 31.7 349 0 0 wri htsoft 2019-Apr-1910:05:29 9 Rigti-Suite®Universal 2017 17.0.23 RSU17328 Page 4 ...noeTaver Residence Load-Man S Compliance.rtp Calc=MJ8 Front Door faces:S Component Constructions Job: %O��Cj �alClllc�ti(;i`: Date: April 18,2018 BR2 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksormlle,FL32207 Phone:9046266675 Email:whitleys.airCwgmail.com Web:whtleysheatingandair.00m License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Cig HTM Gain ft° BtutdO"F ft'-`FBtuh Btuhrfl' Btuh Btuh/ft' Btuh Walls 12C-0svv. Firm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2N4" n 114 0.091 13.0 2.92 333 2.23 254 wood firm, 16"o.c.stud e 127 0.091 13.0 2.92 370 2.23 282 all 241 0.091 13.0 2.92 703 2.23 536 Partitions (none) Windows 1 D-clow.2 glazing,dr outr,air gas,wd frm mat,dr innr, 1/4"gap, 1/4"thk; in 12 0.570 0 18.3 220 21.0 252 1.5 ft overhang(4 ft window ht,0 ft sep.);6.67 ft head ht Doors (none) Ceilings 17B-20al: Rf/dg ceiling,asphalt shingles roof mat,M cons,r-20 deck ins, 100 0.043 20.0 1.38 138 1.16 116 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd fir fnsh 20 0.989 0 31.7 635 0 0 Wrl htsoft" 2019-Apr-19 10:05:29 r� 9 Right-Stite®Urtiversal 2017 17.0.23 RSU17328 Page 5 /ems` .....aver Residence Load-Man S Compliance.np Calc=MJ8 Front Door faces: S Load Calculat.i011 Component Constructions Job: Date: April 18,2018 Hall By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St Augustine Road,Jacksorrolle,FL32207 Phone 9046266675 Email:wYrtieys.air@gmail.com Web:whtteysheatirgardair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain fl' BtuWT fl''F/Btuh Btuh/fl' Btuh BtUtff Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2A4" e 81 0.091 13.0 2.92 235 2.23 179 wood firm, 16"o.c.stud Partitions (none) Windows (none) Doors (none) Ceilings 1713-20al:Rf/clg ceiling,asphalt shingles roof mat,M cons,r-20 deck ins, 141 0.043 20.0 1.38 195 1.16 164 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl: Bg floor light dry soil,on grade depth,hrd wd fir fnsh 7 0.989 0 31.7 222 0 0 wri htsoft:. 2019-Apr-1910:05:29 ^1_ 9 Right-Suite©Uriversal 2017 17.0.23 RSU17328 Page 6 AC'Ch ._roe\Faver Residence Load-Man Compliance.rtp Calc=MJ8 Front Door faces:S Component Constructions Job: (,(kl ( ��c1�CU��1t1017 p Date: April 18,2018 Bath 2 By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksortville,FL 32207 Phone:9046266675 Email:wht1eys.air@gma0.com Web:w 0eysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grflb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain 1t' Btuh/fl�`F ft-'F/Btuh BtuhNF Btuh Btu"' Btuh Walls 12C-0sv, Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2k4" e 104 0.091 13.0 2.92 302 2.23 231 wood frm, 16"o.c.stud s 54 0.091 13.0 2.92 158 2.23 120 all 158 0.091 13.0 2.92 460 2.23 351 Partitions (none) Windows (none) Doors (none) Ceilings 17B-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 55 0.043 20.0 1.38 75 1.16 63 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 15 0.989 0 31.7 476 0 0 1 Wrl htsOft' 2019-Apr-1910:05:29 �_ 9 Rigtt-Suite®Uriversal 2017 17.0.23 RSU17328 Page 7 14CCA ...nce\Faver Residence Load-Man S Compliance.nq Calc=MJ8 Frort Door faces:S Component Constructions Job: Component Load Calculation Date: April 18,2018 Bath 1 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville.FL32207 Phone:9046266675 Email:vtitleys.air@gmail.com Web:wtitleysheatlngandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft'-°F ft'-°F/Btuh BtUWft' Btuh BtuNft' Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2'X4" e 104 0.091 13.0 2.92 302 2.23 231 wood frm, 16"o.c.stud Partitions (none) Windows (none) Doors (none) Ceilings 1713-20al:Rf/dg ceiling,asphalt shingles roof mat,M cons,r-20 deck ins, 55 0.043 20.0 1.38 75 1.16 63 1/2"gypsum board int fnsh, 1"thkns Floors 22A-\Npl:Bg floor,light dry soil,on grade depth,hrd vd flr fnsh 9 0.989 0 31.7 286 0 0 1 wri htsoft' 2019-Apr-1910:05:29 9 Rigti-Stite®Uriversal 2017 17.0.23 RSU17328 Page 8 A ...nceTaver Residence Load-Man S Compliance.rtp Calc=MJ8 Frort Door faces:S Component Constructions Job: Calculation p Date: April 18,2018 MBR By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road.Jacksonville,FL 32207 Phone:9046266675 Email:wMleys.air@gmail.com WebWritleysheatingandair com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30'N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' BtutJft�'F ft'-'FBtuh Btuwft' Btuh BtuNft' Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,2N4" s 114 0.091 13.0 2.92 333 2.23 254 wood frm, 16"o.c.stud w 18 0.091 13.0 2.92 53 2.23 40 all 132 0.091 13.0 2.92 386 2.23 294 Partitions (none) Windows 1 D-c2ow.2 glazing,cir outr,air gas,wd frm mat,dr innr, 1/4"gap, 1/4"thk; s 12 0.570 0 18.3 220 21.0 252 1.5 ft overhang(4 ft window ht,0 ft sep.);6.67 ft head ht Doors (none) Ceilings 176-2081:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 254 0.043 20.0 1.38 351 1.16 295 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 16 0.989 0 31.7 508 0 0 wri htsoft 2019-Apr-19 10: ge 9 9 Right-Sute®Urrversal 2017 17.0.23 RSU17328 Page 9 A+CA ...nce\Faver Residence Load-Man S Compliance.rnp Calc=MJ8 Front Door faces:S Component Constructions Job. Load Calculation p Date: April 18,2018 Living/Dining By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL32207 Phone:9046266675 Email:whtleys.air@gmail.com Web whitleysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Method Simplified Wet bulb(°F) - 77 Construction quality Average Wind speed(mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss CIg HTM Gain fl' BtuNftR'F ft-'F/Btuh BtuNfl' Btuh BtuNt` Btuh Walls 12C-0sw.Frm wall,vnl ext,r-13 cav ins,5/8"gypsum board int fnsh,TX4" n 80 0.091 13.0 2.92 234 2.23 178 wood frm, 16"o.c.stud W 276 0.091 13.0 2.92 806 2.23 615 all 356 0.091 13.0 2.92 1040 2.23 794 Partitions (none) Windows (none) Doors (none) Ceilings 17B-20al:Rf/dg ceiling,asphalt shingles roof mat,wd cons,r-20 deck ins, 388 0.043 20.0 1.38 535 1.16 450 1/2"gypsum board int fnsh, 1"thkns Floors 22A-wpl:Bg floor,light dry soil,on grade depth,hrd wd flr fnsh 24 0.989 0 31.7 762 0 0 wri htsoft° 2019-Apr-1910:05:29 9 Right-Sute®Unversal 2017 17.0.23 RSU17328 Page 10 rre\FaverResidenceLoad-ManSComplianoe.np Calc=MJ8 FrortDoor faces:S ,oad Calculation Project Summary Job: Date: April 18,2018 Entire House By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksonville,FL32207 Phone:9046266675 Email:whitleys.air@gmail.com Web:whtleysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Notes: Block Load for 50 sq.ftAddition-NOT TO MEET FULL ENERGY CODE 2017 Design Information Weather: Jacksonville/Craig,FL,US Winter Design Conditions Summer Design Conditions Outside db 36 °F Outside db 91 °F Inside db 68 °F Inside db 75 °F Design TD 32 °F Design TD 16 °F Daily range M Relative humidity 50 % Moisture difference 52 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 18364 Btuh Structure 11720 Btuh Ducts 0 Btuh Ducts 0 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 18364 Btuh Use manufacturer's data n Rate/swing multiplier 0.96 Infiltration Equipment sensible load 11_�__gR .Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3293 Btuh Ducts 0 Btuh Central vent(0 cf n) 0 Btuh Heating Cooling (none) Area(ft) 1424 1424 Equipment latent load 3293 Btuh Volume(ft') 16376 16376 Air changes/hour 0.45 0.23 Equipment Total Load(Sen+Lat) 14592 Btuh Equiv.AVF(cfm) 133 80 Req.total capacity at 0.70 SHR 1.3 ton Heating Equipment Summary Cooling Equipment Summary Make Bryant Make Bryant Trade BRYANT HEATING AND COOLING SYS... Trade BRYANT HEATING AND COOLING SYS... Model 215BNAO 1 80000A0 Cond 215BNA0180000A0 AHRI ref 9595724 Coil FV4CNF002L AHRI ref 9595724 Efficiency 8.5 HSPF Efficiency 12.5 EER,15 SEER Heating input Sensible cooling 12390 Btuh Heating output 17600 Btuh @ 47°F Latent cooling 5310 Btuh Temperature rise 31 °F Total cooling 17700 Btuh Actual airflow 525 cfm Actual airflow 525 cfm Air flow factor 0.029 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Capacity balance point=37°F IIn ut=p5 kW, Output=17061 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. WI'1 IIltS0lfit' 2019-Apr-1910:05:29 A� 9 Right-Sate@ Uriversal 2017 17.0.23 RSU17328 Page 1 ..nceTaver Residence Load-Man Compliance.np Calc=MA Front Door faces:S l' AED Assessment Job: Date: April 18,2018 Entire House By Joshua Whitley Whitley's Heating and Air, LLC 3371 Sl.Augustine Road,Jacksormlle,FL 32207 Phone:9046266675 Email:wtitieys.air@gmail.com Web:whitleysheatingardair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(gr/lb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Wet bulb(°F) - 77 Wind speed(mph) 15.0 7.5 Test for Adequate Exposure Hourly Glazing Load 2, 1, 1, 1, 1, 1, o - 8 9 10 11 12 13 14 1s 16 17 18 19 20 Maur W Day Maximum hourly glazing load exceeds average by 17.9%. House has adequate exposure diversity(AED), based on AED limit of 30%. AED excursion: 0 Btuh wri htsoft" 2019-Apr-1910:05:29 9 Riglt-Sute®Universal 2017 17.0.23 RSM Page 1 /4CCA ...rceTaver Residence Load-Man S Compliance.ru>p Calc=MJ8 Frort Door faces:S Load Calculation Right-J® Worksheet Job: Entire House Date: April 18,2018 By: Joshua Whitley Whitleys Heating and Air, LLC 3371 St-Augustine Road,Jacksonville,FL32207 Phone:9046266675 Email:whtieys.air@gmail.com Web:whtleysheatingandair.com License:CAC 1816441 1 Room name Entire House Porch 2 Exposed wall 154 0 ft 36.0 ft 3 Room height 11.5 It 115 ft heatl000l 4 Room dimensions 16.0 x 10.0 ft 5 Room area 1424.0 ft' 160 0 ft Ty Construction U-value Or HTM Area (ft') Load Area (ft) Load number (Btuh/ft'-`F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 612C-Osw 0.091 n 2.92 2.23 584 560 1636 1249 224 224 654 499 VL—G 1 D-c2ow 0.570 n 18.30 20.97 24 0 439 503 0 0 0 0 W 12C-0sw 0.091 e 2.92 2.23 529 529 1545 1179 115 1151 336 256 WW �� 12C-Osw 0.091 s 2.92 2.23 324 267 780 595 0 0 0 0 11 G 1 D-c2ow 0.570 s 18.30 20.97 24 24 439 503 0 0 0 0 G 1 D-c2ow 0.570 s 18.30 20.97 12 12 220 252 0 0 0 0 D 11DO 0.390 s 12.52 11.51 21 21 263 242 0 0 0 0 W 12C-Osw 0.091 w 292 2.23 434 413 1206 921 115 94 275 210 L--D 11 DO 0.390 w 12.52 11.51 21 21 263 24221 21 263 242 C 1713-20al 0.043 1.38 1.16 1455 1455 2008 1689 179 179 247 208 F 22A-v pl 0.989 31.75 000 1424 154 4889 0 160 36 1143 0 6 c)AED excursion 0 0 Envelope loss/gain 13688 7375 2918 1415 12 a) Infiltration 4675 1446 1134 351 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 2440 0 Subtotal(lines 6 to 13) 18364 11720 4052 1765 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 18364 11720 4052 1765 15 Dud loads 0% 0% 0 0 -0% 0% 0 0 Total room load 18364 11720 4052 1765 Air required(dm) 525 525 116 79 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �IG�P 41- wrightsOft' Right-SuteCUnversal 2017 17.0.23 RSU1 7328 2019-Apr-191Page1 _r�eFaver Residence Load-Man S Compliance.rup Calc=MJ8 Front Doorfaces: S 9 Load calculalloll Right-J(D Worksheet Job: Entire House Date: April 18,2018 By: Joshua Whitley WhitleVs Heating and Air, LLC 3371 St Augustine Road,Jacksoranlle,FL32207 Phone:9046266675 Email:whtleys.air@gmaii.com Web:whitleysheatingandair.com License:CAC 1816441 1 Room name Kitchen BR1 2 E)posed wal I 16.0 ft 11.0 ft 3 Room height 11.5 ft heaV000l 11.5 ft heaV000l 4 Room dimensions 16.0 x 10.0 ft 11.0 x 11.0 ft 5 Room area 160.0 ft' 121 D ft2 Ty Construction U-value or HTM Area (ftp) Load Area (ft2) Load number (Btuh/fh-°F) (Btuh/ft) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6ViJ 12C-osw 0.091 n 2.92 2.23 0 0 0 0 154 142 415 317 G 1 D-c2ow 0.570 n 18.30 20.97 0 0 0 0 12 0 220 252 W 12C-Osw 0.091 e 2.92 2.23 0 0 0 0 0 0 0 0 11 VL12C-Osa 0.091 s 2.92 2.23 144 99 289 221 0 0 0 0 G 1 D-c2ow 0.570 s 18.30 20.97 24 24 439 503 0 0 0 0 G 1 D-clow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 L—D 11 DO 0.390 s 12.52 11.51 21 21 263 242 0 0 0 0 W 12C-Osw 0.091 w 2.92 2.23 25 25 73 56 0 0 0 0 L—D 11 DO 0.390 w 12.52 11 51 0 0 0 0 0 0 0 0 C 1713-20al 0.043 1.38 116 162 162 223 188 122 122 169 142 F 22A-wpl 0 989 31.75 000 160 16 508 0 121 11 349 0 6 c)AE excursion 0 0 Envelope loss/gain 1795 1209 1152 710 12 a) Infiltration 422 131 385 119 b) Room venfilafion 0 0 0 0 13 Internal gains Occupants @ 230 0 0 0 0 Appliances/other 1000 20 Subtotal(lines6 to 13) 2217 2339 1537 849 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2217 2339 1537 849 15 Duct loads -0°% 0% 0 0 -0°/ 0% 0 0 Total room load 2217 2339 1537 849 Air required(cfm) 63 105 44 38 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 41- wright60ft' 2019-Apr-1910:05:29 At& Right-Suite®Universal 2017 17.0.23 RSU17328 Page 2 nce\Faver Residence Load-Man S Compliance.rup Calc=MJ8 Frori Door faces: S Load Calculation Right-J® Worksheet Job: Entire House Date: April 18,2018 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksorrnlle,FL 32207 Phone:9046266675 Email:whitleys.air@gmail.com Web:wPitleysheatingandaic.com License:CAC 1816441 1 Room name BR2 Hall 2 Exposed wall 20.0 ft 7.0 ft 3 Room height 11.5 ft heat/cool 11.5 ft heat/000l 4 Room dimensions 9.0 x 11.0 ft 20.0 x 70 ft 5 Room area 99.0 ft' 140.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft) Load number (Btuh/(N-°F) (Btuh/fF) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 612C-Osw 0.091 n 2.92 2.23 126 114 333 254 0 0 0 0 VL-G 1 D-c2ow 0.570 n 18.30 20.97 12 0 220 252 0 0 0 0 W 12C-Osw 0.091 e 2.92 2.23 127 127 370 282 81 81 235 179 12C-Osw 0.091 s 2.92 2.23 0 0 0 0 0 0 0 0 1 1 G 1 D-c2ow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 G 1 D-c2ow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 D 11 DO 0.390 s 12.52 11.51 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 w 2.92 2.23 0 0 0 0 0 0 0 0 1 D 11 DO 0.390 w 12.52 11.51 0 0 0 0 0 0 0 0 C 17B-20,1 0.043 1.38 1.16 100 100 138 116 141 141 195 164 F 22A-wpl 0.989 31.75 0.00 99 20 635 0 140 7 222 0 6 c)AED excursion 0 0 Envelope loss/gain 1695 904 652 344 12 a) Infiltration 631 195 201 62 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants @ 230 0 0 0 0 Appliances/other 20 500 Subtotal(lines 6 to 13) 2326 1119 854 906 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 00 0 0 14 Subtotal 2326 1119854 906 15 Dud loads _0% 0% 0 0 _0% 0% 0 0 Total room load 2326 1119 854 906 Air required(dm) 66 50 24 41 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _-P' Wrll9htSOft- Rigtt-Shite®Universal201717.0.23RSU17328 2019-Apr-1910:05:29 , 9 Page 3 nce\Paver Residence Load-Man S Compliance.np Calc=MJ8 FrortDoor faces:S Load Calculation Right-J® Worksheet Job: Entire House Date: April 18,2018 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksormlle,FL 32207 Phone:9046266675 Email:wltitleys.air@gmail.com Web:whfleysheafirgandair.com License:CAC 1816441 1 Room name Bath 2 Bath 1 2 Exposed wall 15.0 It 9.0 ft 3 Room height 11.5 It heat/000l 11 5 It heat/000l 4 Room dimensions 6.0 x 9.0 It 6.0 x 9.0 ft 5 Room area 54.0 ft 54.0 ft Ty Construction U-value Or HTM Area (ft') Load Area (ft) Load number (Btuh/ft7-`F (BtuW) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 12C-Osw 0.091 n 2.92 2.23 0 0 0 0 0 0 0 0 G 1 D-clow 0.570 n 18.30 20.97 0 0 0 0 0 0 0 0 W 12C-Osa 0.091 e 2.92 2.23 104 104 302 231 104 104 302 231 11 \� 12C-Osa 0.091 s 2.92 2.23 54 54 158 120 0 0 0 0 G 1 D-clow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 G 1 D-clow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 D 11 DO 0.390 s 12.52 11.51 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 w 2.92 223 0 0 0 0 0 0 0 0 �D 11 DO 0.390 w 12.52 11.51 0 0 0 0 0 0 0 0 C 17B 20a1 0.043 1.38 1 16 55 55 75 63 55 55 75 63 F 22A-wp1 0.989 31.75 000 54 15 476 0 54 9 286 0 6 c)AED excursion 0 0 Envelope loss/gain 1012 414 663 294 12 a) Infiltration 394 122 259 80 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants @ 230 0 00 0 Appliances/other 0 0 Subtotal(lines6 to 13) 1405 536 922 374 Less eAemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1405 536922 374 15 Dud loads -0°i, 0% 0 0 0°:a 0% 0 0 Total room load 1405 536 922 374 Air required(dm) 401 24 26 17 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -4j- wrightsoft' 2019-Apr-1910:05:29 AC A R gN-SuteO Urrversal 2017 17.0.23 RSU17328 Page 4 nce\Faver Residence Load-Man S Compliance.np Calc=MJ8 Front Door faces: S Load Calculation Right-J® Worksheet Job: Entire House Date: April 18,2018 By: Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road,Jacksorm Ile,FL 32207 P hone:904626667 5 Email:whtleys.air@gmail.com Web:whtleysheatingandair.com License:CAC 1816441 1 Room name MBR Living/Dining 2 Exposed wall 16.0 It 24.0 It 3 Room height 11.5 ft heat/cool 11.5 It heat/cool 4 Room dimensions 14.0 x 18.0 ft 16.0 x 24.0 ft 5 Room area 252.0 ft2 384.0 ft Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft`--°F) (Btuh/ftl) or perimeter (ft) (Btuh) or penmeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ViJ 12C-Osw 0.091 n 2.92 2.23 0 0 0 0 80 80 234 178 L—G 1 D-clow 0.570 n 18.30 20.97 0 0 0 0 0 0 0 0 W 12C-Osw 0.091 e 2.92 223 0 0 0 0 0 0 0 0 w 12C-Osa 0.091 s 2.92 2.23 126 114 333 254 0 0 0 0 11 �G 1 D-clow 0.570 s 18.30 20.97 0 0 0 0 0 0 0 0 G 1 D-c2ow 0.570 s 18.30 20.97 12 12 220 252 0 0 0 0 L—D 11 DO 0.390 s 12.52 11.51 0 0 0 0 0 0 0 0 W 12C-Osa 0.091 w 2.92 2.23 18 18 53 40 276 276 806 615 1—D 11 DO 0.390 w 12.52 11.51 0 0 0 0 0 0 0 0 C 178-20al 0.043 1.38 116 254 254 351 295 388 388 535 450 F 22A-wpl 0 989 31.75 0.00 252 16 508 0 384 24 762 0 6 c)AED excursion 0 0 Envelope loss/gain 1464 841 2337 1244 12 a) Infiltration 360 111 890 275 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Applianoes/other 0 900 Subtotal(lines6 to 13) 1824 1413 3227 2419 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1824 14133227 2419 15 Dud loads -0°/ 0% 0 0 0% 0°/ 0 0 Total room load 1824 1413 3227 2419 Air required(dm) 52 63 92 108 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigF7tSOfY' RighhSuteOUrrversal201717.0.23 RSU17328 2019-Apr-19 g 1 Page 9 e 5 rice\Faver Residence Load-Man S Compliance rrp Calc=MJ8 Frort Door faces: S Loads for Multiple Orientations Job: �: April 18,2018 Entire House By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St Augwtine Road,Jacksonville,FL32207 Phone:9046266675 Email:whitleys.air@gmail.com Web:whiteyshealingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atiantic Beach,FL 32233 Design Conditions Location: Indoor: Heating Cooling Jacksonville/Craig,FL,US Indoor temperature(°F) 68 75 Elevation: 43 ft Design TD(°F) 32 16 Latitude: 30°N Relative humidity(%) 50 50 Outdoor: Heating Cooling Moisture difference(grAb) 26.3 52.0 Dry bulb(°F) 36 91 Infiltration: Daily range(°F) - 17 ( M ) Wet bulb(°F) - 77 Wind speed(mph) 15.0 7.5 Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load(Btuh) 11298 12417 12640 12195 11298 12812 13277 12580 Latent Load(Btuh) 3293 3293 3293 3293 3293 3293 3293 3293 Total Load(Btuh) 14592 15711 15933 15489 14592 16105 16570 15874 Heating AVF(cfrrl) 525 525 525 525 525 525 525 525 Cool ingAVF(cf n) 525 525 525 525 525 525 525 525 Building Orientation Cooling Load 20000 15000 L J m f0 O J C 0 10000 O U m 5000- 0 - - — - -- - N NE E SE S SW W NW Direction Front Door faces Current Orientation: Front Door faces South Highest Cooling Load: Front Door faces West Calculations approved byACCA to meet all requirements of Manual J 8th Ed. C. wri htsoft` 2019-Apr-1910:05:29 ^� 9 Righ-Siite@ Uri\,ersal 201717.0.23 RSU17328 Page 1 ACC# ...ncetFaver Residence Load-Man Compliance.np Calc=MJ8 Front Door faces:S N Sheet 1 P "16 cfir 8" B B 44 cfrn 66 cfi,i 8" cfm 1 cfm 6" 6" 8" 7" Livin — 8 cm2 14 7 41 frn 4,. 5" 6" 54 cfm 7 frn A� Ba 1 26 cfi 6" 8' R63 cfm Kit6e 1n05,fin 5. Ba t2 40 cfi Garage Job#: Whitley's Heating and Air, LLC Scale: 1 :93 Performed by Joshua Whitley for: Page 1 William Kasey Faver 3371 St.Augustine Road Right-Suite®Universal 2017 560Sherry Drive Jacksonville,FL 32207 17.023RSU17328 Atlantic Beach,FL 32233 Phone:9046266675 2019-AV-1910:05:39 whitleysheatingandair.com Mitleys.air@gmail.com ence Load-Man S Compliance.rup Manual S Compliance Report Job: Date: April 18,2018 Entire House By. Joshua Whitley Whitley's Heating and Air, LLC 3371 St.Augustine Road.Jacksonville,FL32207 Phone:9046266675 Email:whibeys.air@gmail.com Web:whitieysheatingandair.com License:CAC 1816441 Project Information For: William Kasey Faver 560 Sherry Drive,Atlantic Beach,FL 32233 Cooling Equipment Design Conditions Outdoor design DB: 91.4°F Sensible gain: 11720 Btuh Entering coil DB: 75.0°F Outdoor design WB: 76.9°F Latent gain: 3293 Btuh Entering coil WB: 62.5°F Indoor design DB: 75.0°F Total gain: 15014 Btuh Indoor RH: 50% Estimated airflow: 525 drn Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Bryant Model: 215BNA0180000AO+FV4CNF002L Actual airflow: 525 cfm Sensible capacity: 12797 Btuh 109%of load Latent capacity: 3393 Btuh 103%of load Total capacity: 16190 Btuh 108%of load SHR: 79% Heating Equipment Design Conditions Outdoor design DB: 35.9°F Heat loss: 18364 Btuh Entering coil DB: 68.0°F Indoor design DB: 68.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Bryant Model: 215BNA0180000AO+FV4CNF002L Actual airflow: 525 cfm Output capacity: 14526 Btuh 79%of load Capacity balance: 37 °F Supplemental heat required: 3838 Btuh Economic balance: -99 °F Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 525 cfm Output capacity: 5.0 kW 93%of load Temp.rise: 50 °F Meets are all requirements ofACCA Manual S. wri htsoft• 2019-Apr-19 1 9 RigFt-Suite®Urrversal 201717.0.23 RSU17328 Page 1 / A ...noeTaver Residence Load-Man S Compliance.ru.p Calc=MJ8 Frort Door faces: S 1 Residential RPER 1 ,4CrK• • • (Loads, 15 Mar 09 Vaa� Header Information Contractor. Whitey's Heating and Air,LLC REQUIRED ATTACHMENTS ATTACHED Manual J1 Form(and supporting worksheets): Yes ❑ No ❑ Mechanical license: CAC 1816441 or MJ1AE Form"(and supporting worksheets): Yes ❑ No E] OEM performance data(heating,cooling,blower): Yes ❑ No E] Building plan#: Manual D Friction Rate Worksheet: Yes E] No Duct distribution sketch: Yes ❑ No Home address(Street or Lot#,Block,Subdivision): 560 Sherry Drive,Entire House HVAC LOAD CALCULATION (IRC M1401.3) Design Conditions Building Construction Information Winter Design Conditions Building Outdoor temperature: 36 °F Orientation: Front Door faces South Indoor temperature: 68 °F Hath,East west$O1tl''Northeast,Norerwest,SaUeast,Sm#vwest Total heat loss: 18364 Btuh Number of bedrooms: 1 Conditioned floor area: 1424 ft2 Summer Design Conditions Number of occupants: 2 Outdoor temperature: 91 °F Indoor temperature: 75 °F Windows Roof Grains difference: 52 grAb @ 50%RH Eave overhang depth: 1.5 ft Sensible heat gain: 12158 Btuh Internal shade: none Eave Blirds,ci apes,etc. Latent heat gain: 3416 Btuh Depth Window Total heat gain: 15574 Btuh Number of skylights: 0 EQUIPMENTHVAC • 40 Heating Equipment Data Cooling Equipment Data Blower Data Equipment type: SpIitASHP Equipment type: SplitASHP Heating cfm: 525 Furnace,Heat purnp,Boiler,etc. Air Cal oner,Heat pump,etc. Cooling dm: 525 Model: Bryant Model: Bryant Static pressure: 0.70 in H2O 215BNA0180000AO+FV4CNF002L 215BNAO 1 80000AO+FV4CN F002L Fans rated external staticpressure for desigr airflow Heating output capacity: 526 Btuh Total cooling capacity: 16190 Btuh Heat purnp6-capacity at winterdesigr aldoor tons Sensible cooling capacity: 12797 Btuh Aux.heating output capacity: 17061 Btuh Latent cooling capacity: 3393 Btuh DISTRIBUTIONHVAC DUCT •1 Design airflow. 525 cfm Longest supply duct: 146 ft Duct Materials Used Equipment design ESP: 0.70 in H2O Longest return duct: 135 ft Trunk duct: Sheet metal,Fiberglass board Total device pressure losses: 0 in H2O Total effective length(TEL): 281 It Available static pressure(ASP): 0.70 in H2O Friction rate: 0 040 in/100ft Branch duct: Round flex vinyl,Fiberglass board Mn Rate=ASP+(TELx 100} 1 declare the load calculation,equipment,equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractors printed name: Contractors signature: Date: MunicipalityReserved for County Town or Authority 'Home qualifies for MJ1AE Form based on Abridged Edition Checklist * wrightsoft' F?j9h_Stite®Uriversal20l7l7.0.23RSU17328 FORMS FLORIDA BUILDING CODE, ENERGY CONSERVATION Residential Building Thermal Envelope Approach FORM R402-2017 Climate Zone ❑ Scope:Compliance with Section R401.2(1)of the Florida Building Code, Energy Conservation,shall be demonstrated by the use of Form R402 for single-and multiple-family residences of three stories or less in height,additions to existing residential buildings,alterations, renovations and building systems in existing buildings,as applicable.To comply,a building must meet or exceed all of the energy efficiency requirements on Table R402A and all applicable mandatory requirements summarized in Table R402B of this form. If a building does not comply with this method,or by the UA Alternative method, it may still comply under Section R405 of the Florida Building Code, Energy Conservation. PROJECT NAME William Faver Home Addition BUILDER: AND ADDRESS: 560 Sherry Drive,Atlantic Beach,FL 32233 OWNER: William Kasey Faver PERMITTING OFFICE: JURISDICTION NUMBER: PERMIT NUMBER: General Instructions: 1.Fill In all the applicable spaces of the"To Be Installed"column on Table R402A with the information requested.All"To Be Installed"values must be equal to or more efficient than the required levels. 2.Complete page 1 based on the"To Be Installed"column Information. 3.Read the requirements of Table R402B and check each box to Indicate your intent to comply with all applicable Items. 4.Read,sign and date the"Prepared By"certification statement at the bottom of page 1.The owner or owner's agent must also sign and date the form. I 1. New construction,addition,or existing building 1. Addition 2. Single-family detached or multiple-family attached 2. Single Family 3. If multiple-family,number of units covered by this submission 3. N 4. Is this a worst case?(yes/no) 4. No 5. Conditioned floor area(sq.ft.) 5. 50 sq.ft 6. Windows,type and area a) U-factor: 6a. 0.40 b) Solar Heat Gain Coefficient(SHGC) 6b. 0.25 _ c) Area 6c. 20 sq,tt _ 7. Skylights a) U-factor: 7a. N/A b) Solar Heat Gain Coefficient(SHGC) 7b. N'A _ 8. Floor type,area or perimeter,and Insulation: a) Slab-on-grade(R-value) Ba. 50 sa.tt R=0.0 b) Wood,raised(R-value) 8b. NIA c) Wood,common(R-value) 8c. N/A d) Concrete,raised(R-value) 8d. N/A e) Concrete,common(R-value) Be. NA _- 9. Wall type and Insulation: a) Exterior: 1. Wood frame(Insulation R-value) 9a1, 126 sg.tt.R=13.0 2. Masonry(Insulation R-value) 9a2. N/A b) Adjacent: 1. Wood frame(Insulation R-value) 9bl. N/A 2. Masonry(Insulation R-value) 9b2. N/A 10. Ceiling type and Insulation a) Attic(Insulation R-value) 10a. NIA b) Single assembly(Insulation R-value) 10b. 63 sq.tt,R=36 11. Air distribution system: a) Duct location,insulation I la. Attic(Single Assembly),R=6 . b) AHU location llb. Attic(Single Assembly) c) Total duct leakage.Test report attached. 11c. Not Rea. efm/100 s.f. Yes❑ No 61 12. Cooling system: a)type 12a. Central Unit-Split b)efficiency 12b. 15 SEER 13. Heating system: a)type 13a. Central Unit-Split b)efficiency 13b. HSPF=8.5 14. HVAC sizing calculation:attached 14. Manual J Load Yes No❑ 15. Water heating system: a)type 15a. Electric b)efficiency 15b. EM-0.90 0.90 I hereby certify that the plans and specifications covered by this form are Review of plans and specifications covered by this form indicate In compliance with the Florida Building Code,Energy Conservation. compliance with the Florida Building Code,Energy Conservation.Before PREPARED BY: Joshua Whitley __ Date o,1�,9__ construction is complete,this building will be inspected for compliance in I hereby certify that this building is In compliance with the Florida Building accordance with Section 553.908,F.S. Code,Energy Conservation, CODE OFFICIAL: OWNER/AGENT: Date: Date: FLORIDA BUILDING CODE-ENERGY CONSERVATION,6th EDITION(2017) R-55 FORMS TABLE R402A BUILDING COMPONENT PRESCRIPTIVE REQUIREMENTS' INSTALLED VALUES Climate Zone 1 Climate Zone 2 Windows U-Factor=NR LI-Factor=0.40' U-Factor= SHGC=0.25 SHGC=0.25 SHGC= Skylights U-factor=0.75 U-factor=0.65 LI-factor= SHGC=0.30 SHGC=0.30 SHGC= Doors:Exterior door U-factor=NR LI-factor--0.40' U-factor= Floors: Slab-on-Grade NR NR Over unconditioned spaces` R-13 R-13 R-Value= Walls':Ext.and Adj. Frame R-13 R-13 R-Value= Mass Insulation on wall interior R-4 R-6 R-Value= Insulation on wall exterior R-3 R-4 R-Value= Ceilings' R=30 R=38 R-Value= Air infiltration Blower door test is required on the building envelope to verity leakage 5 1 ACH; Total leakage=ACH test report provided to code official. Test re rt attached? Yes❑ No❑ Air distribution system : Air handling unit Not allowed in attic Location: Duct R-value R-value Z R-8(supply in attics)or�t R-6(all other duct locations) R-Value= Air leakage': Duct test Postconstruction test Total leakage 5 4 cfm/100 s.f. Total leakage= cfm/100s.f. Rough-in test Total leakage 5 4 cfm/100 s.f.(air handier installed) Test report Attached? Yes❑ No❑ Total leakage<_3 cfm/100 s.f.(air handier not installed) Location: Ducts In conditioned space Test not required if all ducts and AHU are in conditioned space Air conditioning system: Minimum federal standard required by NAECA': Central system Room unit or PTAC '000 Btu1h SEEEER 14.0[from SEER= [fr m Table C403.2.3(3)) EER Other: See Tables C403.2.3(1)-(11) = Heating system: Minimum federal standard required by NAECA6: Heat pump<_65,000 Btu/h HSPF 8.2 HSPF= Gas furnace,non-weatherized AFUE 800k AFUE= Oil furnace,non-weatherized AFUE 83% AFUE= Other: Water heating system(storage type): Minimum federal standard required by NAECA': Electric' 40 gal:EF=0.92 Gallons= 50 gal:EF=0.90 EF= Gas fired' 40 gal:EF=0.59 Gallons= 50 gal:EF=0.58 EF= Other(describe): NR=No requirement. (1)Each component present in the As Proposed home must meet or exceed each of the applicable performance criteria in order to comply with this code using this method. (2)For impact rated fenestration complying with Section R301.2.1.2 of the Florida Building Code,Residential or Section 1609.1.2 of the Florida Building Code, Building, the maximum 17-factor shall be 0.65 in Climate Zone 2. An area-weighted average of 17-factor and SHGC shall be accepted to meet the requirements, or up to 15 square feet of glazed fenestration area are exempted from the U-factor and SHGC requirement based on Sections R402.3.1, R402.3.2 and R402.3.3. (3)One side-hinged opaque door assembly up to 24 square feet is exempted from this U-factor requirement. (4)R-values are for insulation material only as applied in accordance with manufacturer's installation instructions. For mass walls, the "interior of wall" requirement must be met except if at least 50 percent of the insulation required for the"exterior of wall"is installed exterior of,or integral to,the wall. (5)Ducts&AHU installed"substantially leak free"per Section R403.3.2.Test required by either individuals as defined in Section 553.993(5)or(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f), (g)or(i),Florida Statutes. The total leakage test is not required for ducts and air handlers located entirely within the building thermal envelope. (6)Minimum efficiencies are those set by the National Appliance Energy Conservation Act of 1987 for typical residential equipment and are subject to NAECA rules and regulations. For other types of equipment, see Tables C403.2.3(1-11) of the Commercial Provisions of the Florida Building Code, Energy Conservation. (7)For other electric storage volumes,minimum EF=0.97-(0.00132*volume). (8)For other natural gas storage volumes,minimum EF=0.67-(0.0019*volume). R-56 FLORIDA BUILDING CODE—ENERGY CONSERVATION,6th EDITION(2017) FORMS TABLE R402B MANDATORY REQUIREMENTS Component Section Summary of Requirement(s) Check Air leakage R402.4 To be caulked,gasketed,weatherstripped or otherwise sealed per Table R402.4.1.1.Recessed lighting:IC-rated as having<2.0 cfm tested to ASTM E 283. ' Windows and doors:0.3 cfm/sq.it.(swinging doors:0.5 c(m/sf)when tested to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440. ' Fireplaces:Tight-fitting flue dampers&outdoor combustion air. Programmable R403.12 A programmable thermostat is required for the primary heating or cooling system. thermostat ' R403.3.2 Ducts shall be tested as per Section R403.3.2 by either Individuals as defined In Section 553.993(5)or(7),Florida ' Air distribution system R403.3.4 Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes.Air handling units are not allowed in attics. ' Water heaters R403.5 Comply with efficiencies In Table C404.2.Hot water pipes insulated to>_R-3 to kitchen outlets,other cases. ' Circulating systems to have an automatic or accessible manual OFF switch.Heat trap required for vertical pipe risers. ' Swimming pools&spas R403.10 Spas and heated pools must have vapor-retardant covers or a liquid cover or other means proven to reduce heat ' loss except if 70%of heat from site-recovered energy.Ott/timer switch required.Gas heaters minimum thermal efficiency is 82%.Heat pump pool heaters minimum COP is 4.0. ' Cooling/heating R403.7 Sizing calculation performed&attached.Special occasion cooling or heating capacity requires separate system or ' equipment variable capacity system. Lighting equipment R404.1 At least 75%of permanently installed lighting fixtures shall be high-efficacy lamps. I FLORIDA BUILDING CODE—ENERGY CONSERVATION,6th EDITION(2017) R-57