763 Atlantic Blvd COMM20-0012 12 of 26 E1-ELECTRICAL POWERGFCIGFCIGFCI/IGIGSWGFCI/WPGFCIIGGFCIGFCIJJGFCIGFCIHC HC 30 CONSULTCONSULTCONSULTMANAGERMEN'SWOMEN'SBREAKVAULTCLSUNISEXB.O.H.OPEN RETAILRETAILCOUNTERATMDISPLAY CASEDISPLAY CASEDISPLAY CASEDISPLAY CASEDISPLAY CASEDISPLAY CASEDISPLAY CASEHCHCJSWSWSWTVTVTVTVGFCIGFCIGFCIJGFCIGFCIGFCIJJJGFCI/WPJGFCI/WPJJJJJJJGFCI/WPGFCI/WPELECTRICAL NOTES:1. ALL LIGHTING AND RECEPTACLE CIRCUITS UP TO 74' IN LENGTH SHALL USE #12 WIRES MINIMUM, CIRCUITS FROM 75' UP TO 129' IN LENGTH SHALL USE #10 WIRES MINIMUM AND FROM 130' AND UP SHALL USE #8 WIRES MINIMUM UNLESS OTHERWISE SPECIFIED. 2. THESE DRAWINGS ARE DIAGRAMMATIC - REFER TO ARCHITECTURAL FOR EXACT HEIGHT, DIMENSIONS AND LOCATION.3. OPERATING AND MAINTENANCE MANUALS WILL BE PROVIDE TO OWNER BY ELECTRICAL CONTRACTOR AS REQUIRED PER SECTION C405.6.4 IN FBC-ENERGY CONSERVATION 6TH EDITION (2017).4. COORDINATE WITH OWNER FOR EXACT DATA/COMM REQUIREMENTS.5. INSTALL NEW FIRE ALARM DEVICES IN ACCORDANCE WITH NFPA 72 AND FLORIDA FIRE PREVENTION CODE( 6TH EDITIONS).6. IF PROJECT IS NOT CONNECTED TO A CENTRAL FIRE ALARM SYSTEM, PROVIDE LOCAL AUDIBLE/VISUAL SIGNALS UPON INITIATING TROUBLE.7. DIVISION 16 CONTRACTOR SHALL COORDINATE EXACT MECHANICAL REQUIREMENTS WITH DIVISION 15 DRAWINGS.8. THIS PROJECT IS IN COMPLIANCE WITH FBCEC 2017 SECTION C405.6.3, NEC 210.19(A)(1) WITH REGARDS TO VOLTAGE DROP FOR DOWNSTREAM BRANCH CIRCUITS, AND NEC 215.2 FOR FEEDER CONDUCTORS.THIS PROJECT IS IN COMPLIANCE WITH FBCEC 2017 SECTION C405.6.3 AND NEC 210.19 WITH REGARDS TO VOLTAGE DROP FOR BOTH DISTRIBUTION PANELS AND DOWNSTREAM BRANCH CIRCUITS.61012SERVICERTU-1EWH-1RECEPTFEEDER & BRANCH CONDUCTOR SCHED12LIGHTSDEVICETYPECONDUCTORDISTANCENEC TABLE 9, TABLE & EXAMPLESLOADING (A)% VOLTAGE DROPSEE RISER DIAGRAM5075257540308100.770.81.752.18MULTIPLIERWIRE SIZE ANDCONDUITSEE PANELSCHEDULEWPRTUMECH. EQUIPMENT POWER RISER DETAILTYPE TONSDISC.WIREGROUNDCONDUITex. RTU-140/3/60 D.ESEE PANEL SCHEDULE5.0RTU-2 25/3/60 D.E3.0 SEE PANEL SCHEDULENOTES:1. VERIFY NAMEPLATE RATINGS, LOCATIONS, AND POINT OF POWER CONNECTIONS PRIOR TO ROUGH-IN.2. DO NOT LOCATE DISCONNECT SWITCHES OVER UNIT ACCESS PANELS.3. PROVIDE A 3/4" EMPTY CONDUIT THROUGH INACCESSIBLE LOCATIONS(I.E. WALLS, UNDER SLAB) FOR CONTROL WIRING. COORDINATE WITH MECHANICAL PLANS.4. EQUIP. REQUIREMENTS ARE FOR MANUFACTURER AND MODEL NUMBER LISTED ON MECHANICAL PLANS. MECH. CONTRACTOR SHALL BARE ANY ADDITIONAL COST.DATAVOICECAT5 CABLECABLECAT5RUNCABLEVOICEDATA CABLE RUNCLOSETCOMMUNICATIONSPHONE KSUPHONE POSITIONMODULAR JACK AT EACHVOICE / DATA DOUBLENOTES: 1 - ALL COMPONENTS PROVIDED BY ELECTRICAL CONTRACTOR.2 - ALL JACKS TO BE LABELED VOICE AND/OR DATA. 3 - ALL JACKS TO BE NUMBERED TO CORRESPOND WITH PATCH PANEL.4 - PLENUM RATED CABLE TO BE USED AS REQUIRED BY CODE.5 - INSTALL 3/4" CONDUIT FROM THE BOX TO AREA ABOVE THE CEILING.VOICE / DATA WIRING SCHEMATICCAT5 PATCH PANEL IN SAME ROOM AS THE KEY SYSTEM UNIT. (TELEPHONE)POWER SYMBOL LEGENDDUPLEX OUTLET MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISE. BOX INDICATES FLUSH IN FLOOR OR CEILING AS SPECIFIED.DUPLEX/QUAD OUTLET MOUNTED HORIZONTALLY ABOVE COUNTERTOP OR BACKSPLASH 44" A.F.F. UNLESS NOTED OTHERWISEDUPLEX/QUAD OUTLET WITH GROUND FAULT INTERRUPTER, MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISE. BOX INDICATES FLUSH IN FLOOR OR CEILING AS SPECIFIED.DUPLEX/QUAD OUTLET WITH GROUND FAULT INTERRUPTER, MOUNTED HORIZONTALLY ABOVE COUNTERTOP OR BACKSPLASH 44" A.F.F. UNLESS NOTED OTHERWISEDUPLEX OUTLET WITH ISOLATED GROUND MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISE. BOX INDICATES FLUSH IN FLOOR OR CEILING AS SPECIFIED.SPECIAL PURPOSE OUTLET MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISE. VOLTAGE AND AMPERAGE AS NOTED ON PLANS.DUPLEX OUTLET MOUNTED DIRECTLY ABOVE SHOW WINDOW.SWITCH DUPLEX OUTLET MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISEDUPLEX OUTLET WITH WEATHERPROOF COVER AND GROUND FAULT INTERRUPTER MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISEQUAD OUTLET MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISE. BOX INDICATES FLUSH IN FLOOR OR CEILING AS SPECIFIED.TIME CLOCKLOS, PUSHBUTTON, DOORBELL BUZZER, OR SHUNT TRIP MOUNTED AT 42" A.F.F. UNLES NOTED OTHERWISE.DUPLEX OUTLET WITH GROUND FAULT INTERRUPTER AND ISOLATED GROUND, MOUNTED HORIZONTALLY ABOVE COUNTERTOP OR BACKSPLASH 44" A.F.F. UNLESS NOTED OTHERWISEJUNCTION BOX, FLUSH MOUNTED IN CEILING UNLESS NOTED OTHERWISE. STEM TCFUSED DISCONNECT SWITCHNON-FUSED DISCONNECT SWITCHELECTRICAL PANEL BOARDTELEPHONE BOARD (TB)ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)DATA OUTLET. INSTALL PULL WIRES.COMMUNICATION (VOICE) OUTLET. INSTALL PULL WIRES.DATA/VOICE OUTLET. INSTALL PULL WIRES.CONDUIT, LINES INDICATES WIRE QUANTITY.HOMERUN, A = PANEL DESIGNATION / 2,4,6 = CIRCUITSA-2,4,6CEILING SPEAKER.SECURITY CAMERA CEILING.HDMI OUTLET FOR MONITOR.HDMISSCSS=SMOKE DETECTOR - ALARM / S+co= DUAL COMBO SMOKE AND CARBON MONOXIDE DETECTORLOW VOLTAGE WIREcoCONTROLLED DUPLEX OR QUAD OUTLET MOUNTED 18" A.F.F. UNLESS NOTED OTHERWISEOVERHEAD PROJECTOR WITH SCREEN, SCREEN SIZE SHOWN ON PLANS#- DENOTES TYPE#X x YELECTRICAL TRANSFORMER. REFER TO PANEL SCHEDULE FOR INFORMATION.TELECTRICAL METER. REFER TO PANEL SCHEDULE FOR INFORMATION.MARC FLASH WARNING!WARNINGArc Flash and Shock Hazard Appropriate PPE RequiredCAUTION- SERIES COMBINATION SYSTEM RATED.XX.XXX AMPERES. IDENTIFIED REPLACEMENT COMPONENT REQUIREDNEC-110.16, 110.22NOTES:1. PROVIDE/INSTALL SIGN ON ALL EQUIPMENT PER ANSI, NEC AND OSHA. ANSI Z535.4-1998, PRODUCT SAFETY SIGNS ANDLABELS, PROVIDES GUIDELINES FOR THE DESIGN OF SAFETY SIGNS AND LABELS FOR APPLICATION TO PRODUCTS.2. REFER TO RISER DIAGRAM FOR SHORT CIRCUIT AMPERAGE INFORMATION.ABREVIATIONSNEUTRALELECTRIC WATER COOLEREWCAA/CACAFFAHUAWGCCUDISCELECEMEFEXFAAMPERESAIR CONDITIONINGALTERNATING CURRENTABOVE FINISHED FLOORAIR HANDLING UNITAMERICAN WIRE GAUGECONDUITCOPPERDISCONNECTELECTRICALEMERGENCYEXHAUST FANEXISTINGFIRE ALARMGGFIGNDHVACJKAICKVAKWKCMILNNANFNECNLNEMANFPAGROUNDGROUND FAULT INTERRUPTERGROUNDHEATING, VENTILATING ANDJUNCTION(THOUSAND) AMPEREKILOVOLT-AMPERESKILOWATTTHOUSANDS OF CIRCULAR MILSNOT APPLICABLENON-FUSEDNATIONAL ELECTRICAL CODENIGHT LIGHTNATIONAL ELECTRICALNATIONAL FIREPPNLPVCSPECTYPVWWPPOLEPANELBOARDPOLYVINYL CHLORIDESPECIFICATIONTYPICALVOLTSWIREWEATHERPROOFFIRE ALARM CONTROL PANELFACPNIGHT LIGHTNLAIR CONDITIONINGINTERRUPTING CAPACITYMANUFACTURERS ASSOC.PROTECTION ASSOC.I.G.ISOLATED GROUND-----------------------------------------LEDLIGHT EMITTING DIODE--TBDTO BE DETERMINED-WWATT-IDF BACKBOARD DETAIL#6 GREEN INSULATED GROUND CONDUCTOR IN A 1/2" CONDUIT TO BUILDING STEEL (OR NEAREST GROUNDING ELECTRODE POINT). LEAVE 8'-0" STACK AT BACKBOARD.ONE (1) 2" PVC CONDUIT TO BAR JOISTBACKBOARD 3/4" PLYWOOD 4'-0"W X 8'-0"HDEDICATED QUADRUPLEX RECEPTACLEFINISHED FLOORGROUNDING BUS BAR4"min-6"maxTelecommSIGN13' - 0"Panel A2A-13A-3A-5A-744A-13A-15555A-21A-23A-255A-24A-18A-22A-24A-16A-206A-41A-37,397A-27A-34A-348A-358A-36A-297A-31,339A-9A-171011A-11@floorA-37,399A-11A-11A-15A-15A-19A-176A-28A-26A-9A-9A-9A-16A-161011A-281011A-281011A-281011A-281011A-281011A-281011A-28EXISTING METER CENTERA-9A-2,4,6A-8,10,12FIELD VERIFY EXACT LOCATION, LOCATED ON ROOF99REVISIONSPROJECT NUMBER:ARCHITECTURE, DESIGN & DRAWING SERVICES# AA 26001108BRIAN P. FREDLEY, ASSOC. AIA, PROJECT MANAGERDALLAS B. PEACOCK, AIA, ARCHITECT# AR 0009706207 FAIRVIEW AVENUE, DAYTONA BEACH, FL, 32114PH: (386) 257-0502 FX: (386) 257-1050E-MAIL: bpfdesign@cfl.rr.com WEBSITE: bpfdesign.netDATE:SHT NO.ARCHITECT'S / ENGINEER'S SEALSCALE: AS SHOWN#1325 S. Bumby Ave. Orlando, Florida 32806PH: (407) 896 7411 / FX: (407) 896 7412EMAIL: epgroup@att.netCA#8126MTF2003903/19/2020CURALEAF ATLANTIC BEACH - INTERIOR MODIFICATION MEDICAL MARIJUANA FACILITYE-1ELECTRICAL PLAN - POWERGENERAL CONTRACTOR: T.B.DPROJECT LOCATION: 763 ATLANTIC BEACH BOULEVARD, UNIT 1, ATLANTIC BEACH, FL 32233OWNER/DEVELOPER: CURTIS BARKMAN, DIRECTOR OF PROJECT MANAGEMENT, PALLIATECH, INC., 301 EDGEWATER PLACE, SUITE 405, WAKEFIELD, MA 01880 PH:(781)451-0160MOHSEN FARAJI, P.E. 43599REFERENCE NOTESNumber Description1 J-BOX FOR FUTURE SIGN MOUNTED ABOVE CEILING. PULL WIRES ASREQUIRED PER TENANT PANEL SCHEDULE INTO J-BOX. COIL WIRES ANDSTOW IN J-BOX AND COVER FOR FUTURE SIGNAGE CONNECTION.COORDINATE LOCATION AND MOUNTING HEIGHT OF J-BOX WITHARCHITECTURAL ELEVATION DRAWINGS. CIRCUIT CONNECTED VIA TIMECLOCK CONTACTOR. CIRCUIT CALCULATE AS A CONTINUOUS LOAD2 SEE IDF BACKBOARD DETAIL FOR CONNECTION AND INSTALATION.3 PROVIDE CONDUITS FOR SERVICE PROVIDER ENTRANCE CABLES, SEE DATASERVICE DETAIL, FIELD VERIFY EXACT LOCATION PRIOR INSTALLATION.4 PROVIDE DUPLEX AC OUTLET WITH USB CHARGING AND FACEPLATE.5 RECEPTACLE LOCATED AT 7'-0" A.F.F. FOR TV AND DATA CONNECTION.PROVIDE COAXIAL OUTLET WITH FLUSH MOUNTED 4-11/16" SQUARE SINGLEGANG JUNCTION BOX. PROVIDE BLANK BUILDING STANDARD COVER PLATE.EXTEND 3/4" CONCEALED CONDUIT TO ABOVE ACCESIBLE CEILING ANDSTUB-OUT WITH PLASTIC BUSHING, OR AS NOTED. INSTALL PULL WIRE ORHDMI CABLE FOR TV SIGNAL. SHALL BE COORDINATED BY CONTRACTOR.6 PROVIDE OCCUPANCY SENSOR TO AUTOMATIC SHUT-OFF 50% CONTROLLEDRECEPTACLES AS NOTED, RECEPTACLES CONTROLLED SHALL BE LABELED.REFER TO LIGHTING/RECEPTACLE CONTROL AND WIRING DETAIL. REFER TOASHRAE 90.1-8.4.2 (2013), NEC 406.1(E) (2014).7 PROVIDE J-BOX FOR MECHANICAL EQUIPMENT, FIELD VERIFY EXACTLOCATION AND ELEVATION.8 PROVIDE J-BOX FOR FUTURE HAND DRYER DESIRED BY OWNER, FIELDVERIFY EXACT LOCATION.9 PROVIDE DISCONNECT FOR MECHANICAL EQUIPMENT, FIELD VERIFY EXACTLOCATION AND ELEVATION.10 PROVIDE CARD READER OUTSIDE, SEE SECURITY DOOR DETAIL, FIELDVERIFY EXACT LOCATION AND ELEVATION BY CONTRACTOR.11 PROVIDE J-BOX FOR SECURITY ACCESS DOOR, SEE SECURITY DOOR DETAIL,FIELD VERIFY EXACT LOCATION AND ELEVATION BY CONTRACTOR.1/4" = 1'-0"E-1101-Electrical-Power1/4" = 1'-0"E-1202-Electrical-Power