587 Timber Bridge Ln RES20-0116 8 of 10 truss dwgs_4 of 17NO JOB ID TRS ID DATE
TCLL 20 psf
TCDL 7 psf
BCLL 0 psf + NCLL 10 psf
BCDL 5 psf
ROOF LOADING (Cd=1.25)
TCLL 40 psf
TCDL 10 psf
BCLL 0 psf
BCDL 5 psf
FLOOR LOADING (Cd = 1.00)
This Package inlcudes 85 truss designs with individual date of design
Site Information
162-01 Atlantic Beach Country Club - FL-Duval
130MPH (3 second gust)\ASCE 7-10
MWFRS
WIND LOADING(Cd=1.6)
Enclosed Structure (0.18)
Exposure C
Occupancy Category II (Res)
FBC 2017 RES\TPI 2014
NO JOB ID TRS ID DATE NO JOB ID TRS ID DATE
John Merrill Homes
Structural Engineer of Record
Justin Lanier
PE No. 85166
9000 Regency Square BLVD, Suite 100
Jacksonville, FL 32211
B01186460 4/15/2020
GE01286460 4/15/2020
GE02386460 4/15/2020
GE03486460 4/15/2020
HJ01586460 4/15/2020
HJ02686460 4/15/2020
HJ03786460 4/15/2020
HJ04886460 4/15/2020
HJ05986460 4/15/2020
HJ061086460 4/15/2020
HJ071186460 4/15/2020
HJ081286460 4/15/2020
J011386460 4/15/2020
J01A1486460 4/15/2020
J021586460 4/15/2020
J02A1686460 4/15/2020
J031786460 4/15/2020
J041886460 4/15/2020
J051986460 4/15/2020
J062086460 4/15/2020
J072186460 4/15/2020
J082286460 4/15/2020
J092386460 4/15/2020
J102486460 4/15/2020
J112586460 4/15/2020
J122686460 4/15/2020
J12A2786460 4/15/2020
J132886460 4/15/2020
PB012986460 4/15/2020
PB023086460 4/15/2020
PB033186460 4/15/2020
PB043286460 4/15/2020
PB053386460 4/15/2020
PB063486460 4/15/2020
PB073586460 4/15/2020
T013686460 4/15/2020
T023786460 4/15/2020
T033886460 4/15/2020
T043986460 4/15/2020
T054086460 4/15/2020
T064186460 4/15/2020
T074286460 4/15/2020
T07A4386460 4/15/2020
T084486460 4/15/2020
T094586460 4/15/2020
T104686460 4/15/2020
T114786460 4/15/2020
T124886460 4/15/2020
T134986460 4/15/2020
T145086460 4/15/2020
T155186460 4/15/2020
T165286460 4/15/2020
T175386460 4/15/2020
T185486460 4/15/2020
T195586460 4/15/2020
T205686460 4/15/2020
T215786460 4/15/2020
T225886460 4/15/2020
T235986460 4/15/2020
T246086460 4/15/2020
T256186460 4/15/2020
T266286460 4/15/2020
T276386460 4/15/2020
T286486460 4/15/2020
T296586460 4/15/2020
T306686460 4/15/2020
T316786460 4/15/2020
T326886460 4/15/2020
T336986460 4/15/2020
T347086460 4/15/2020
T357186460 4/15/2020
T367286460 4/15/2020
Apex Technology is a ficticious name owned by Jax Apex Technology, Inc., a Florida
Corporation. Florida Engineer Business No. 7547 - 9000 Regency Square BLVD, Suite
100, Jacksonville, FL 32211 (904) 821-5200
The seal on this index sheet indicates acceptance of professional engineering
responsibility solely for the Truss Design Drawings listed above and attached. The
suitability and use of each drawing for any particualr building is the responsibility of the
Building Designer, per ANSI/TPI 1-2014 Section 2
With my seal affixed to this sheet, I hereby certify that this serves as an index sheet in
conformance with Rule 61G15-23.002(2) and 61G15-31.003 of the Florida Board of
Professional Engineers
4/15/2020
This document may be signed and sealed with original or Docusign digital signature by the
professional engineer identified in the adjacent professional engineer’s seal. Printed copies
of Docusign signature documents are not considered signed and sealed and the signature
must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
NO JOB ID TRS ID DATE
TCLL 20 psf
TCDL 7 psf
BCLL 0 psf + NCLL 10 psf
BCDL 5 psf
ROOF LOADING (Cd=1.25)
TCLL 40 psf
TCDL 10 psf
BCLL 0 psf
BCDL 5 psf
FLOOR LOADING (Cd = 1.00)
This Package inlcudes 85 truss designs with individual date of design
Site Information
162-01 Atlantic Beach Country Club - FL-Duval
130MPH (3 second gust)\ASCE 7-10
MWFRS
WIND LOADING(Cd=1.6)
Enclosed Structure (0.18)
Exposure C
Occupancy Category II (Res)
FBC 2017 RES\TPI 2014
NO JOB ID TRS ID DATE NO JOB ID TRS ID DATE
John Merrill Homes
Structural Engineer of Record
Justin Lanier
PE No. 85166
9000 Regency Square BLVD, Suite 100
Jacksonville, FL 32211
T377386460 4/15/2020
T387486460 4/15/2020
T397586460 4/15/2020
T407686460 4/15/2020
T417786460 4/15/2020
T427886460 4/15/2020
T437986460 4/15/2020
T43A8086460 4/15/2020
T448186460 4/15/2020
T458286460 4/15/2020
T468386460 4/15/2020
V018486460 4/15/2020
V028586460 4/15/2020
Apex Technology is a ficticious name owned by Jax Apex Technology, Inc., a Florida
Corporation. Florida Engineer Business No. 7547 - 9000 Regency Square BLVD, Suite
100, Jacksonville, FL 32211 (904) 821-5200
The seal on this index sheet indicates acceptance of professional engineering
responsibility solely for the Truss Design Drawings listed above and attached. The
suitability and use of each drawing for any particualr building is the responsibility of the
Building Designer, per ANSI/TPI 1-2014 Section 2
With my seal affixed to this sheet, I hereby certify that this serves as an index sheet in
conformance with Rule 61G15-23.002(2) and 61G15-31.003 of the Florida Board of
Professional Engineers
4/15/2020
This document may be signed and sealed with original or Docusign digital signature by the
professional engineer identified in the adjacent professional engineer’s seal. Printed copies
of Docusign signature documents are not considered signed and sealed and the signature
must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
Job # 86460 BEARING INFORMATION
WOODTRUSS
QTY SPAN DESCRIPTION REACTION UPLIFTBRG#
1 45'11"00 GE01 GABL 5.00/12 Pitch 1 -Ply 150.00434.651
480.001846.442
537.002061.593
131.00508.654
1 45'11"00 GE02 GABL 5.00/12 Pitch 1 -Ply 263.00838.381
470.001572.632
233.00828.853
1 22'09"00 GE03 GABL 5.00/12 Pitch 1 -Ply 211.00733.981
130.00364.302
166.00598.173
2 08'04"05 HJ01 HIP_JACK 3.54/12 Pitch 1 -Ply 97.00425.321
0.0069.902
125.00272.053
2 05'06"06 HJ02 HIP_JACK 3.54/12 Pitch 1 -Ply 47.00178.101
0.0027.422
10.0082.863
1 05'10"10 HJ03 HIP_JACK 3.54/12 Pitch 1 -Ply 82.00354.041
0.0033.452
55.00123.223
1 08'00"01 HJ04 HIP_JACK 3.54/12 Pitch 1 -Ply 92.00414.811
0.0064.692
114.00246.073
3 05'06"06 HJ05 HIP_JACK 3.54/12 Pitch 1 -Ply 45.00173.401
0.0082.982
21.0062.843
2 02'07"12 HJ06 HIP_JACK 3.54/12 Pitch 1 -Ply 139.00286.591
12.0061.362
20.0058.423
1 02'02"13 HJ07 HIP_JACK 3.54/12 Pitch 1 -Ply 141.00278.501
16.0069.842
23.0053.113
1 03'01"06 HJ08 HIP_JACK 3.54/12 Pitch 1 -Ply 134.00291.351
8.0051.732
25.0070.223
8 02'00"00 J01 JACK 5.00/12 Pitch 1 -Ply 71.00213.801
8.0037.792
17.0044.233
2 02'00"00 J01A JACK 5.00/12 Pitch 1 -Ply 12.0065.171
2.0027.672
26.0046.583
4 04'00"00 J02 JACK 5.00/12 Pitch 1 -Ply 70.00253.641
0.0051.012
49.0094.213
2 04'00"00 J02A JACK 5.00/12 Pitch 1 -Ply 26.00130.341
0.0056.202
54.0096.433
4 06'00"00 J03 EJACK 5.00/12 Pitch 1 -Ply 81.00310.781
0.0080.542
78.00143.673
6 07'11"00 J04 MONO 5.00/12 Pitch 1 -Ply 50.00369.421
Page 1 of 5
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
Job # 86460 BEARING INFORMATION
QTY SPAN DESCRIPTION REACTION UPLIFTBRG#
58.00253.112
2 02'00"00 J05 GABL 5.00/12 Pitch 1 -Ply 72.00225.401
6 06'00"00 J06 EJACK 5.00/12 Pitch 1 -Ply 81.00310.781
0.0022.282
73.00176.683
2 01'00"00 J07 JACK 5.00/12 Pitch 1 -Ply 103.00238.341
20.0068.772
51.00152.783
2 03'00"00 J08 JACK 5.00/12 Pitch 1 -Ply 66.00229.281
2.0035.752
33.0069.343
4 04'03"00 J09 EJACK 5.00/12 Pitch 1 -Ply 71.00260.351
0.0054.752
52.00100.403
1 04'03"00 J10 JACK 5.00/12 Pitch 1 -Ply 73.00240.331
17.0097.632
50.00113.263
3 05'09"00 J11 EJACK 5.00/12 Pitch 1 -Ply 53.00303.321
0.0076.892
49.00137.503
5 02'00"00 J12 JACK 5.00/12 Pitch 1 -Ply 83.00198.211
0.0030.002
30.0087.673
1 02'00"00 J12A JACK 5.00/12 Pitch 1 -Ply 25.0065.171
0.0030.002
21.0055.173
7 04'00"00 J13 EJACK 5.00/12 Pitch 1 -Ply 100.00244.391
0.0060.002
25.00110.333
1 09'03"08 PB01 GABL 8.00/12 Pitch 1 -Ply 164.00477.561
6 09'03"08 PB02 COMN 8.00/12 Pitch 1 -Ply 104.0084.101
138.00677.202
60.0077.063
1 11'03"08 PB03 COMN 8.00/12 Pitch 1 -Ply 99.0083.711
151.00706.692
62.00-71.843
7 11'03"08 PB04 COMN 8.00/12 Pitch 1 -Ply 166.00-140.631
204.00929.962
112.00-140.633
7 07'10"12 PB05 COMN 8.00/12 Pitch 1 -Ply 160.00200.911
174.00616.262
1 11'03"08 PB06 COMN 8.00/12 Pitch 1 -Ply 97.0082.471
152.00703.892
60.00-71.003
1 11'03"08 PB07 COMN 8.00/12 Pitch 1 -Ply 29.0053.291
196.00648.152
10.0053.293
1 45'11"00 T01 ATIC 5.00/12 Pitch 1 -Ply 156.00392.341
234.001942.722
209.001985.393
191.00555.854
Page 2 of 5
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
Job # 86460 BEARING INFORMATION
QTY SPAN DESCRIPTION REACTION UPLIFTBRG#
1 29'10"04 T02 ATIC 5.00/12 Pitch 1 -Ply 102.00557.191
261.001841.202
14.001145.113
1 29'08"12 T03 ATIC 5.00/12 Pitch 1 -Ply 99.00614.331
225.002807.612
1 31'08"12 T04 ATIC 5.00/12 Pitch 1 -Ply 383.001361.521
359.002336.332
1 31'08"12 T05 ATIC 5.00/12 Pitch 2 -Ply 274.001756.851
372.002631.532
1 31'10"04 T06 ATIC 5.00/12 Pitch 1 -Ply 106.001093.251
275.003309.242
212.00-543.663
5 25'06"02 T07 COMN 5.00/12 Pitch 2 -Ply 120.001604.871
252.001420.682
1 25'06"02 T07A SPEC 5.00/12 Pitch 2 -Ply 116.001608.411
250.001423.242
6 31'10"04 T08 ATIC 5.00/12 Pitch 1 -Ply 119.001166.011
218.002768.292
124.00392.283
1 49'11"00 T09 ATIC 5.00/12 Pitch 1 -Ply 183.001848.541
15.002409.302
190.001885.313
1 49'11"00 T10 ATIC 5.00/12 Pitch 1 -Ply 165.001867.531
11.002433.052
190.001901.883
1 20'00"08 T11 COMN 5.00/12 Pitch 1 -Ply 39.00843.151
278.001597.162
1 20'00"08 T12 COMN 5.00/12 Pitch 1 -Ply 299.00918.851
345.001604.542
1 18'00"08 T13 COMN 5.00/12 Pitch 1 -Ply 0.001892.331
279.001524.732
4 18'00"08 T14 COMN 5.00/12 Pitch 1 -Ply 0.00788.081
276.001524.732
3 47'11"00 T15 ATIC 5.00/12 Pitch 1 -Ply 167.001578.921
79.002873.952
171.001578.923
1 47'11"00 T16 ATIC 5.00/12 Pitch 1 -Ply 511.001975.991
833.003078.132
547.001972.413
1 45'11"00 T17 ATIC 5.00/12 Pitch 1 -Ply 486.002050.371
739.002731.642
519.001985.593
1 45'11"00 T18 COMN 5.00/12 Pitch 1 -Ply 132.00928.661
141.001906.752
126.00893.133
1 45'11"00 T19 COMN 5.00/12 Pitch 1 -Ply 154.00834.391
144.001815.272
122.00879.933
1 45'11"00 T20 COMN 5.00/12 Pitch 1 -Ply 282.00825.881
439.001829.892
259.00879.143
Page 3 of 5
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
Job # 86460 BEARING INFORMATION
QTY SPAN DESCRIPTION REACTION UPLIFTBRG#
1 45'11"00 T21 COMN 5.00/12 Pitch 1 -Ply 378.001232.211
814.002856.822
193.00578.073
1 31'06"08 T22 FLAT 0.00/12 Pitch 2 -Ply 2662.007816.861
3525.0010349.692
1 22'09"00 T23 SPEC 5.00/12 Pitch 1 -Ply 148.00527.311
262.00831.222
61.00280.453
1 22'09"00 T24 COMN 5.00/12 Pitch 1 -Ply 168.00784.881
267.001397.602
118.00271.413
5 17'09"08 T25 COMN 5.00/12 Pitch 1 -Ply 34.00724.491
162.00680.082
3 17'09"08 T26 COMN 5.00/12 Pitch 1 -Ply 32.00685.541
165.00592.412
1 17'09"08 T27 COMN 5.00/12 Pitch 1 -Ply 47.00685.451
167.00590.002
1 17'09"08 T28 COMN 5.00/12 Pitch 1 -Ply 66.00685.011
170.00587.132
1 17'09"08 T29 COMN 5.00/12 Pitch 1 -Ply 56.00684.711
161.00589.912
1 17'09"08 T30 COMN 5.00/12 Pitch 1 -Ply 58.00684.331
159.00590.292
1 17'09"08 T31 COMN 5.00/12 Pitch 1 -Ply 61.00683.951
156.00590.672
1 17'09"08 T32 COMN 5.00/12 Pitch 1 -Ply 65.00683.911
156.00591.192
1 17'09"08 T33 COMN 5.00/12 Pitch 1 -Ply 66.00683.661
152.00590.962
1 17'09"08 T34 COMN 5.00/12 Pitch 1 -Ply 263.00779.111
187.00598.332
1 15'09"08 T35 SPEC 5.00/12 Pitch 1 -Ply 307.001044.091
1 16'09"00 T36 COMN 5.00/12 Pitch 1 -Ply 204.00646.291
166.00545.772
1 16'09"00 T37 HIPS 5.00/12 Pitch 1 -Ply 196.00646.291
158.00545.772
1 16'09"00 T38 HIPS 5.00/12 Pitch 1 -Ply 333.001040.001
287.00936.162
1 16'09"00 T39 HIPS 5.00/12 Pitch 1 -Ply 178.00545.771
178.00545.772
1 16'09"00 T40 HIPS 5.00/12 Pitch 1 -Ply 187.00545.771
187.00545.772
1 16'09"00 T41 HIPS 5.00/12 Pitch 2 -Ply 354.001110.421
354.001110.422
1 09'05"00 T42 HIPS 5.00/12 Pitch 1 -Ply 160.00703.071
110.00599.942
3 26'02"08 T43 ATIC 5.00/12 Pitch 1 -Ply 84.001209.951
315.002111.512
1 26'02"08 T43A ATIC 5.00/12 Pitch 1 -Ply 85.002893.181
314.002104.722
Page 4 of 5
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
Job # 86460 BEARING INFORMATION
QTY SPAN DESCRIPTION REACTION UPLIFTBRG#
3 26'02"08 T44 ATIC 5.00/12 Pitch 1 -Ply 109.001378.041
257.001939.352
6 05'10"14 T45 FLAT 0.00/12 Pitch 1 -Ply 0.00767.371
0.00631.312
6 13'11"08 T46 COMN 8.00/12 Pitch 1 -Ply 143.00476.281
174.00588.782
1 25'03"00 V01 GABL 8.00/12 Pitch 1 -Ply 476.001766.961
1 22'10"09 V02 GABL 8.00/12 Pitch 1 -Ply 395.001546.601
Total of Trusses 183
Maximun Height 13'08"15
Page 5 of 5
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 4745 Sutton Park Court, Suite 402, Jacksonville, FL 32224 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier
Lumber
Floor Joist Header: 1.750"x16.0" 2.0E Microllam LVL
2.0E Microllam LVL design properties based on ICC
ES ESR-1387.
Nailnote
Nail Schedule:0.131"x3", min. nailsMember : _ Rows @ _.__" o.c. (Each Row)
Repeat nailing as each layer is applied. Use equalspacing between rows and stagger nails in each rowto avoid splitting.
*** Warning: Fastening of plies required***
Special Loads
------(Lumber Dur.Fac.=1.00 / Plate Dur.Fac.=1.00)PLT: From 15 plf at 0.00 to 15 plf at 12.08PLB: 2055 lb Conc. Load at 1.84
PLB: 2052 lb Conc. Load at 3.84, 5.84, 7.84, 9.8411.84
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Additional Notes
Full Height Blocking reinforcement required toprevent buckling of members over the bearings:bearing 1 located at 0.00'
Deflection meets L/480 live and L/360 total load.Creep increase factor for dead load is 1.50.
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 5432 /- /- /- /- /-
B 7064 /- /- /- /- /-
A Brg Width = 5.5 Min Req =2.0
B Brg Width = 13.5 Min Req =2.6
Bearings A & B Fcperp = 565psi.
Maximum Axial Forces Per Ply(lbs)
Chords Tens.Comp.
A - B 0 0
Loading Criteria (psf)
LL:0.00
DL:0.00
Des Ld:0.00
NCLL:0.00 Soffit:0.00Load Duration: 1.00Spacing: 24.0 "
Wind Criteria
Wind Std:NA
Speed:NA mph
Enclosure: NA
Category: NA
EXP: NAKzt: NA
Mean Height: NA ft
Top Edge DL: NA psf
Bot Edge DL: NA psf
MWFRS Parallel Dist: NA
C&C Dist a: NA ft
Loc. from endwall: NA
I: NA GCpi: NA
Wind Duration: NA
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
Defl/CSI Criteria
Deflection in loc L/defl L/#
VERT(LL):0.118 5.92 999 480
VERT(TL):0.187 5.92 774 360
Creep Factor: 1.5
VIEW Ver: 18.02.01A.0205.20
Max CSI:0.395
Job Number:86460
Pujadas Res.
Label:B01
Ply: 3
Qty:1
Wgt: 0.0 lbs
SEQN: 17570 / T80 / FLOO
FROM:DRW:
.../...04/15/2020
10'1"2
A B
12'1"1'4"2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 4745 Sutton Park Court, Suite 402, Jacksonville, FL 32224 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier
Lumber
Floor Joist Header: 1.750"x16.0" 2.0E Microllam LVL
2.0E Microllam LVL design properties based on ICC
ES ESR-1387.
Nailnote
Nail Schedule:0.131"x3", min. nailsMember : _ Rows @ _.__" o.c. (Each Row)
Repeat nailing as each layer is applied. Use equalspacing between rows and stagger nails in each rowto avoid splitting.
*** Warning: Fastening of plies required***
Special Loads
------(Lumber Dur.Fac.=1.00 / Plate Dur.Fac.=1.00)PLT: From 15 plf at 0.00 to 15 plf at 12.08PLB: 2055 lb Conc. Load at 1.84
PLB: 2052 lb Conc. Load at 3.84, 5.84, 7.84, 9.8411.84
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Additional Notes
Full Height Blocking reinforcement required toprevent buckling of members over the bearings:bearing 1 located at 0.00'
Deflection meets L/480 live and L/360 total load.Creep increase factor for dead load is 1.50.
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 5432 /- /- /- /- /-
B 7064 /- /- /- /- /-
A Brg Width = 5.5 Min Req =2.0
B Brg Width = 13.5 Min Req =2.6
Bearings A & B Fcperp = 565psi.
Maximum Axial Forces Per Ply(lbs)
Chords Tens.Comp.
A - B 0 0
Loading Criteria (psf)
LL:0.00
DL:0.00
Des Ld:0.00
NCLL:0.00 Soffit:0.00Load Duration: 1.00Spacing: 24.0 "
Wind Criteria
Wind Std:NA
Speed:NA mph
Enclosure: NA
Category: NA
EXP: NAKzt: NA
Mean Height: NA ft
Top Edge DL: NA psf
Bot Edge DL: NA psf
MWFRS Parallel Dist: NA
C&C Dist a: NA ft
Loc. from endwall: NA
I: NA GCpi: NA
Wind Duration: NA
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
Defl/CSI Criteria
Deflection in loc L/defl L/#
VERT(LL):0.118 5.92 999 480
VERT(TL):0.187 5.92 774 360
Creep Factor: 1.5
VIEW Ver: 18.02.01A.0205.20
Max CSI:0.395
Job Number:86460
Pujadas Res.
Label:B01
Ply: 3
Qty:1
Wgt: 0.0 lbs
SEQN: 17570 / T80 / FLOO
FROM:DRW:
.../...04/15/2020
10'1"2
A B
12'1"1'4"This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B3 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W6 2x4 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 6.75TC: From 57 plf at 6.75 to 57 plf at 7.48TC: From 55 plf at 7.48 to 55 plf at 38.44
TC: From 57 plf at 38.44 to 57 plf at 39.17TC: From 55 plf at 39.17 to 55 plf at 47.57BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 45.92BC: From 4 plf at 45.92 to 4 plf at 47.57
BC: 253 lb Conc. Load at 18.19,20.19,22.19,23.7325.73,27.73
Plating Notes
All plates are 3X4 except as noted.
(**) 16 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 32 0.15 2.77BC 75 2.86 45.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 435 /- /-/167 /150 /333
BF 1846 /- /-/828 /479 /-
BC 2062 /- /-/698 /537 /-
AY 509 /-21 /-/318 /130 /-
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
BF Brg Width = 5.5 Min Req =1.7
BC Brg Width = 5.5 Min Req =1.5
AY Brg Width = 5.5 Min Req =1.5
Bearings B, BF, BC, & AY Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 303 -354C - D 218 -463
D - E 489 -658
E - F 250 -262
F - G 591 -462
F - H 540 -437
G - J 566 -387
H - I 545 -442
I - K 277 -142
J - L 566 -334
K - M 279 -141
L - N 586 -307
M - O 280 -141
N - P 611 -284
O - Q 281 -141
P - S 528 -183
Q - R 283 -141
R - T 590 -1323
S - U 488 -125T - V 591 -1325
U - W 465 -122
V - X 592 -1328
W -Y 465 -121
X - Z 592 -1328
Y -AB 465 -121
Chords Tens.Comp.
Z -AA 592 -1328
AA-AC 592 -1328AB-AD 465 -121
AC-AE 592 -1328
AD-AG 465 -121
AE-AF 592 -1328
AF-AH 590 -1324
AG-AI 503 -129
AH-AJ 589 -1323
AI-AL 522 -182
AJ-AK 375 -175
AK-AM 378 -173
AL-AN 580 -279
AM-AO 379 -173
AN-AP 570 -302
AO-AQ 380 -173
AP-AR 565 -329
AQ-AS 382 -173
AR-AU 546 -387
AS-AT 415 -322AT-AV 410 -318
AU-AV 569 -463
AV-AW 279 -151
AW-AX 544 -695
AX-AY 262 -603
AY-AZ 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -BJ 11 -3
C -BI 450 -122
Chords Tens.Comp.
BF-BD 268 -366
BD-BC 422 -569
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.309 BJ 636 240
VERT(CL):0.515 BJ 381 180
HORZ(LL):0.146 BH - -
HORZ(TL):0.244 BH - -
Creep Factor: 2.0
Max TC CSI:0.818
Max BC CSI:0.797
Max Web CSI:0.887
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE01
Ply: 1
Qty:1
Wgt: 445.2 lbs
SEQN: 17459 / T1 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1
B3
W6
10'1"2A
B
C
D E F
G
H I
J
K
L
M
N
O
P
QR
S
T
U
V
W
X
Y
ZAA
AB
AC
AD
AE AF
AG
AH
AI
AJAK
AL
AM
AN
AO
AP
AQ
AR
AS AT
AU
AVAWAX
AY
AZ
BABBBCBD
BEBFBGBHBI
BJ
5 12
8
12
4X5(**)
3X4(**)
5X7(**)
5X7(**)3X4(**)
4X5(R)4X5(**)
4X5
5X7(**)
5X7(**)
6X8(**)
5X7(**)
5X5
5X7(**)5X7(**)
3X4(**)5X7(**)
6X8(**)
4X5(**)
16'6"4 12'10"8 16'6"4
10'11"8 1'4"
(TYP)
2'8"
6'9"
6'9"
7'5"12
8"12
8'0"1
6"5 12'3"8
4'3"7
18'9"5
6'5"13
22'11"8
4'2"3
27'1"11
4'2"3
33'7"8
6'5"13
37'10"15
4'3"7
39'2"
1'3"1
45'11"
6'9"
2'11"
2'11"
6'9"
3'10"
11'9"6
5'0"6
16'4"8
4'7"2
22'11"8
6'7"
29'6"8
6'7"
34'1"10
4'7"2
39'2"
5'0"6
45'11"
6'9"1'6"8 1'6"8
4"53'2"13'7"141'10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B3 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W6 2x4 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 6.75TC: From 57 plf at 6.75 to 57 plf at 7.48TC: From 55 plf at 7.48 to 55 plf at 38.44
TC: From 57 plf at 38.44 to 57 plf at 39.17TC: From 55 plf at 39.17 to 55 plf at 47.57BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 45.92BC: From 4 plf at 45.92 to 4 plf at 47.57
BC: 253 lb Conc. Load at 18.19,20.19,22.19,23.7325.73,27.73
Plating Notes
All plates are 3X4 except as noted.
(**) 16 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 32 0.15 2.77BC 75 2.86 45.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 435 /- /-/167 /150 /333
BF 1846 /- /-/828 /479 /-
BC 2062 /- /-/698 /537 /-
AY 509 /-21 /-/318 /130 /-
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
BF Brg Width = 5.5 Min Req =1.7
BC Brg Width = 5.5 Min Req =1.5
AY Brg Width = 5.5 Min Req =1.5
Bearings B, BF, BC, & AY Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 303 -354C - D 218 -463
D - E 489 -658
E - F 250 -262
F - G 591 -462
F - H 540 -437
G - J 566 -387
H - I 545 -442
I - K 277 -142
J - L 566 -334
K - M 279 -141
L - N 586 -307
M - O 280 -141
N - P 611 -284
O - Q 281 -141
P - S 528 -183
Q - R 283 -141
R - T 590 -1323
S - U 488 -125T - V 591 -1325
U - W 465 -122
V - X 592 -1328
W -Y 465 -121
X - Z 592 -1328
Y -AB 465 -121
Chords Tens.Comp.
Z -AA 592 -1328
AA-AC 592 -1328AB-AD 465 -121
AC-AE 592 -1328
AD-AG 465 -121
AE-AF 592 -1328
AF-AH 590 -1324
AG-AI 503 -129
AH-AJ 589 -1323
AI-AL 522 -182
AJ-AK 375 -175
AK-AM 378 -173
AL-AN 580 -279
AM-AO 379 -173
AN-AP 570 -302
AO-AQ 380 -173
AP-AR 565 -329
AQ-AS 382 -173
AR-AU 546 -387
AS-AT 415 -322AT-AV 410 -318
AU-AV 569 -463
AV-AW 279 -151
AW-AX 544 -695
AX-AY 262 -603
AY-AZ 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -BJ 11 -3
C -BI 450 -122
Chords Tens.Comp.
BF-BD 268 -366
BD-BC 422 -569
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.309 BJ 636 240
VERT(CL):0.515 BJ 381 180
HORZ(LL):0.146 BH - -
HORZ(TL):0.244 BH - -
Creep Factor: 2.0
Max TC CSI:0.818
Max BC CSI:0.797
Max Web CSI:0.887
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE01
Ply: 1
Qty:1
Wgt: 445.2 lbs
SEQN: 17459 / T1 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1
B3
W6
10'1"2A
B
C
D E F
G
H I
J
K
L
M
N
O
P
QR
S
T
U
V
W
X
Y
ZAA
AB
AC
AD
AE AF
AG
AH
AI
AJAK
AL
AM
AN
AO
AP
AQ
AR
AS AT
AU
AVAWAX
AY
AZ
BABBBCBD
BEBFBGBHBI
BJ
5 12
8
12
4X5(**)
3X4(**)
5X7(**)
5X7(**)3X4(**)
4X5(R)4X5(**)
4X5
5X7(**)
5X7(**)
6X8(**)
5X7(**)
5X5
5X7(**)5X7(**)
3X4(**)5X7(**)
6X8(**)
4X5(**)
16'6"4 12'10"8 16'6"4
10'11"8 1'4"
(TYP)
2'8"
6'9"
6'9"
7'5"12
8"12
8'0"1
6"5 12'3"8
4'3"7
18'9"5
6'5"13
22'11"8
4'2"3
27'1"11
4'2"3
33'7"8
6'5"13
37'10"15
4'3"7
39'2"
1'3"1
45'11"
6'9"
2'11"
2'11"
6'9"
3'10"
11'9"6
5'0"6
16'4"8
4'7"2
22'11"8
6'7"
29'6"8
6'7"
34'1"10
4'7"2
39'2"
5'0"6
45'11"
6'9"1'6"8 1'6"8
4"53'2"13'7"141'10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
BI-BH 250 -66
BH-BE 144 -49BG-BF 0 0
BC-BB 266 -278
BB-BA 378 -273BA-AY 501 -223
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
BJ- C 71 -19
D -BI 577 -608
BI- E 684 -585
E -BH 65 -250
BH- I 185 0
I -BE 319 -643
BE-BF 606 -1533
BE- R 481 -1262
R -BD 1506 -335
Webs Tens.Comp.
AA-BD 300 -539
BD-AJ 1793 -409
AJ-BC 529 -1351
BC-AS 380 -686
AS-BB 206 -31
BB-AW 114 -330
AW-BA 595 -667
AX-BA 654 -490
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
G - H 121 -122
J - K 100 -82
L - M 36 -38
N - O 30 -29
P - Q 172 -244
S - T 104 -139
U - V 58 -177W -X 18 -5
Y - Z 140 -236
Gables Tens.Comp.
AB-AC 145 -242
AD-AE 52 -13
AF-AG 80 -204
AH-AI 87 -112
AK-AL 165 -227
AM-AN 30 -34
AO-AP 36 -37AQ-AR 104 -120
AT-AU 122 -117
Job Number:86460
Pujadas Res.
Truss Label:GE01
Ply: 1
Qty:1
Wgt: 445.2 lbs
SEQN: 17459 / T1 / GABL
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W15 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 16 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 104 0.15 23.63BC 120 23.63 34.54BC 75 34.54 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be taken
during handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-5-8.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 838 /- /-/394 /262 /325
AO 1573 /- /-/774 /470 /-
AF 829 /- /-/488 /233 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5AOBrg Width = 5.5 Min Req =1.5
AF Brg Width = 5.5 Min Req =1.5
Bearings B, AO, & AF Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 636 -1457
C - D 642 -1315
D - E 537 -1074E - F 732 -1407
F - G 330 -208
G - H 144 -221
G - I 329 -53
H - J 139 -192
I - K 329 -51
J - M 120 -222
K - L 324 -51
L - N 396 -34
M - O 107 -251
N - P 393 -32
O - Q 126 -228
Chords Tens.Comp.
P - R 392 -32
Q - S 152 -203
R - T 392 -32
S - V 143 -181T - U 375 -27
U - X 360 -696
V - W 136 -163
W -Y 165 -226
X - Z 380 -687
Y -AA 108 -240
Z -AA 331 -638
AA-AB 325 -643
AB-AC 337 -935
AC-AD 447 -1132
AD-AE 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AQ 1290 -478
AQ-AP 1559 -649
AP-AO 693 -197AO-AM 0 0
AN-AJ 794 -208
Chords Tens.Comp.
AL-AK 0 0
AK-AI 11 -73
AJ-AH 783 -171AI-AG 27 -59
AG-AF 67 -18
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C -AQ 304 -36
AQ- D 235 -288
D -AP 303 -553
AP- E 567 -991AP- F 1384 -670
Webs Tens.Comp.
U -AH 194 -267
AS-AT 61 -33
AJ-AK 20 -10
AB-AH 545 -112AH-AI 252 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.16 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 6.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.184 AL 999 240
VERT(CL):0.432 AL 620 225
HORZ(LL):-0.042 M - -
HORZ(TL):0.069 M - -
Creep Factor: 2.0
Max TC CSI:0.521
Max BC CSI:0.988
Max Web CSI:0.956
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE02
Ply: 1
Qty:1
Wgt: 360.5 lbs
SEQN: 17472 / T46 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W15 10'1"2AB
C D E F G
H
I
J
KL
M
N
O
P
Q
R
S
TU
V
W
X
Y
Z
AAAB
AC
AD AE
AFAG
AHAIAJAKAL
AMANAOAPAQ
AR
AS
AT
5 12
8
12
4X5(**)
5X7(**)
5X7(**)6X8(**)
5X7(**)
6X8(**)
3X4(**)
4X5(R)
5X7(**)
5X7(**)
3X4(**)3X4(**)
3X4(**)5X7(**)
5X7(**)
H0510(**)
4X8
3X8
3X8(**)
23'8"12 22'2"4
21'8"8
1'4"
(TYP)
6'3"
6'3"
12'1"2
5'10"2
17'11"4
5'10"2
18'10"8
11"5
19'4"13
6"5 28'6"8
9'1"11
29'8"8
1'2"
34'3"6
4'6"14
34'6"8
3"2
41'2"
6'7"8
45'11"
4'9"
6'6"8
6'6"8
17'9"8
11'3"
23'10"8
6'1"
31'2"12
7'4"4
34'4"12
3'2"
41'3"12
6'11"
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"52'11"93'7"17'7"13'2"11'10'5"811'0"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W15 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 16 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 104 0.15 23.63BC 120 23.63 34.54BC 75 34.54 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be taken
during handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-5-8.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 838 /- /-/394 /262 /325
AO 1573 /- /-/774 /470 /-
AF 829 /- /-/488 /233 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5AOBrg Width = 5.5 Min Req =1.5
AF Brg Width = 5.5 Min Req =1.5
Bearings B, AO, & AF Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 636 -1457
C - D 642 -1315
D - E 537 -1074E - F 732 -1407
F - G 330 -208
G - H 144 -221
G - I 329 -53
H - J 139 -192
I - K 329 -51
J - M 120 -222
K - L 324 -51
L - N 396 -34
M - O 107 -251
N - P 393 -32
O - Q 126 -228
Chords Tens.Comp.
P - R 392 -32
Q - S 152 -203
R - T 392 -32
S - V 143 -181T - U 375 -27
U - X 360 -696
V - W 136 -163
W -Y 165 -226
X - Z 380 -687
Y -AA 108 -240
Z -AA 331 -638
AA-AB 325 -643
AB-AC 337 -935
AC-AD 447 -1132
AD-AE 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AQ 1290 -478
AQ-AP 1559 -649
AP-AO 693 -197AO-AM 0 0
AN-AJ 794 -208
Chords Tens.Comp.
AL-AK 0 0
AK-AI 11 -73
AJ-AH 783 -171AI-AG 27 -59
AG-AF 67 -18
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C -AQ 304 -36
AQ- D 235 -288
D -AP 303 -553
AP- E 567 -991AP- F 1384 -670
Webs Tens.Comp.
U -AH 194 -267
AS-AT 61 -33
AJ-AK 20 -10
AB-AH 545 -112AH-AI 252 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.16 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 6.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.184 AL 999 240
VERT(CL):0.432 AL 620 225
HORZ(LL):-0.042 M - -
HORZ(TL):0.069 M - -
Creep Factor: 2.0
Max TC CSI:0.521
Max BC CSI:0.988
Max Web CSI:0.956
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE02
Ply: 1
Qty:1
Wgt: 360.5 lbs
SEQN: 17472 / T46 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W15 10'1"2AB
C D E F G
H
I
J
KL
M
N
O
P
Q
R
S
TU
V
W
X
Y
Z
AAAB
AC
AD AE
AFAG
AHAIAJAKAL
AMANAOAPAQ
AR
AS
AT
5 12
8
12
4X5(**)
5X7(**)
5X7(**)6X8(**)
5X7(**)
6X8(**)
3X4(**)
4X5(R)
5X7(**)
5X7(**)
3X4(**)3X4(**)
3X4(**)5X7(**)
5X7(**)
H0510(**)
4X8
3X8
3X8(**)
23'8"12 22'2"4
21'8"8
1'4"
(TYP)
6'3"
6'3"
12'1"2
5'10"2
17'11"4
5'10"2
18'10"8
11"5
19'4"13
6"5 28'6"8
9'1"11
29'8"8
1'2"
34'3"6
4'6"14
34'6"8
3"2
41'2"
6'7"8
45'11"
4'9"
6'6"8
6'6"8
17'9"8
11'3"
23'10"8
6'1"
31'2"12
7'4"4
34'4"12
3'2"
41'3"12
6'11"
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"52'11"93'7"17'7"13'2"11'10'5"811'0"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
F -AO 393 -1142
AO-AN 438 -894L -AN 285 -360
AN- U 413 -1209
AR-AS 61 -33
AH-AC 306 -346
AH-AG 1011 -307AC-AG 141 -297
AG-AD 967 -325
AD-AF 434 -806
Maximum Gable Forces Per Ply (lbs)Gables Tens.Comp.
H - I 44 -43
J - K 107 -134
M - N 111 -136
O - P 28 -33
Q - R 39 -28
S -AR 59 -195
Gables Tens.Comp.
AR- T 54 -212
V -AS 49 -61
AT- X 20 -42
AT- W 1 -15
Y - Z 88 -90
Job Number:86460
Pujadas Res.
Truss Label:GE02
Ply: 1
Qty:1
Wgt: 360.5 lbs
SEQN: 17472 / T46 / GABL
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 22.75
BC 75 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right cantilever is exposed to wind
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is7-2-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AC 734 /- /-/415 /211 /173
Z 364 /- /-/251 /130 /-
AD 598 /- /-/285 /165 /-
Wind reactions based on MWFRS
AC Brg Width = 5.5 Min Req =1.5ZBrg Width = 5.5 Min Req =1.5
AD Brg Width = 5.5 Min Req =1.5
Bearings AC, Z, & AD Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 524 -971
C - D 549 -854
D - E 25 -227D - F 569 -712
E - G 62 -182
F - H 572 -713
G - J 96 -171
H - I 574 -716
I - K 543 -747
J - M 135 -162
K - L 544 -748
Chords Tens.Comp.
L - N 544 -748
M - O 154 -188
N - P 543 -747
O - R 111 -185P - Q 450 -520
Q - S 446 -515
R - T 56 -154
S - U 442 -513
T - U 57 -181
U - V 412 -639
V - W 388 -738
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
AC-AB 181 -171
AB-AA 885 -381
AA- Z 883 -378
Chords Tens.Comp.
Z - Y 879 -383
Y - X 21 -65
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B -AC 489 -713
B -AB 802 -344
C -AB 93 -43
AB- I 37 -56
I -AA 73 -37
Webs Tens.Comp.
Z - P 177 -271
P - Y 163 -423
Y - V 111 -115
Y - W 668 -262
W -X 350 -512
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
E - F 57 -30
G - H 64 -61
Gables Tens.Comp.
N - O 65 -73
Q - R 102 -146
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.115 F 999 240
VERT(CL):0.182 F 892 180
HORZ(LL):0.049 E - -
HORZ(TL):0.080 E - -
Creep Factor: 2.0
Max TC CSI:0.268
Max BC CSI:0.456
Max Web CSI:0.306
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE03
Ply: 1
Qty:1
Wgt: 172.2 lbs
SEQN: 17662 / T34 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D
E
F
G
HI
J
K L
M
N
O
P Q
R
S
T
U V
W
XYZAAABACAD
5 12
8
12
3X8
3X8(**)
4X4(**)
5X7(**)
3X4(**)
4X4
3X4(**)
5X7(**)
4X4(**)
4X5
13'6"12 8'10"12 3"8
7'4"8 1'4"(TYP)
4'9"
4'9"
5'3"5
6"5
11'4"8
6'1"3
18'
6'7"8
22'9"
4'9"
4'10"12
4'10"12
9'2"5
4'3"8
13'6"12
4'4"7
17'10"4
4'3"8
22'9"
4'10"121'6"8
1'2"53'2"17'2"142. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 22.75
BC 75 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Gable end supports 8" max rake overhang. Topchord must not be cut or notched.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right cantilever is exposed to wind
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is7-2-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AC 734 /- /-/415 /211 /173
Z 364 /- /-/251 /130 /-
AD 598 /- /-/285 /165 /-
Wind reactions based on MWFRS
AC Brg Width = 5.5 Min Req =1.5ZBrg Width = 5.5 Min Req =1.5
AD Brg Width = 5.5 Min Req =1.5
Bearings AC, Z, & AD Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 524 -971
C - D 549 -854
D - E 25 -227D - F 569 -712
E - G 62 -182
F - H 572 -713
G - J 96 -171
H - I 574 -716
I - K 543 -747
J - M 135 -162
K - L 544 -748
Chords Tens.Comp.
L - N 544 -748
M - O 154 -188
N - P 543 -747
O - R 111 -185P - Q 450 -520
Q - S 446 -515
R - T 56 -154
S - U 442 -513
T - U 57 -181
U - V 412 -639
V - W 388 -738
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
AC-AB 181 -171
AB-AA 885 -381
AA- Z 883 -378
Chords Tens.Comp.
Z - Y 879 -383
Y - X 21 -65
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B -AC 489 -713
B -AB 802 -344
C -AB 93 -43
AB- I 37 -56
I -AA 73 -37
Webs Tens.Comp.
Z - P 177 -271
P - Y 163 -423
Y - V 111 -115
Y - W 668 -262
W -X 350 -512
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
E - F 57 -30
G - H 64 -61
Gables Tens.Comp.
N - O 65 -73
Q - R 102 -146
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.115 F 999 240
VERT(CL):0.182 F 892 180
HORZ(LL):0.049 E - -
HORZ(TL):0.080 E - -
Creep Factor: 2.0
Max TC CSI:0.268
Max BC CSI:0.456
Max Web CSI:0.306
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:GE03
Ply: 1
Qty:1
Wgt: 172.2 lbs
SEQN: 17662 / T34 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D
E
F
G
HI
J
K L
M
N
O
P Q
R
S
T
U V
W
XYZAAABACAD
5 12
8
12
3X8
3X8(**)
4X4(**)
5X7(**)
3X4(**)
4X4
3X4(**)
5X7(**)
4X4(**)
4X5
13'6"12 8'10"12 3"8
7'4"8 1'4"(TYP)
4'9"
4'9"
5'3"5
6"5
11'4"8
6'1"3
18'
6'7"8
22'9"
4'9"
4'10"12
4'10"12
9'2"5
4'3"8
13'6"12
4'4"7
17'10"4
4'3"8
22'9"
4'10"121'6"8
1'2"53'2"17'2"14This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
J - K 59 -61
L - M 70 -82
S - T 61 -44
Job Number:86460
Pujadas Res.
Truss Label:GE03
Ply: 1
Qty:1
Wgt: 172.2 lbs
SEQN: 17662 / T34 / GABL
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1
Bot chord 2x4 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 8.36BC 99 0.15 8.36Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 5-10-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-9-14.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 425 /- /- /-/96 /-
D 70 /- /-/19 /- /-
C 272 /- /- /-/125 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -9
Chords Tens.Comp.
B - C 77 -63
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.020 D - -
HORZ(TL):0.031 D - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.429
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ01
Ply: 1
Qty:2
Wgt: 30.8 lbs
SEQN: 17505 / T9 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"8
A
B
C
D
3.54 12
3X4(A1T)
8'4"5
8'4"52'2"3
4"5 2'9"143'4"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1
Bot chord 2x4 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 8.36BC 99 0.15 8.36Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 5-10-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-9-14.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 425 /- /- /-/96 /-
D 70 /- /-/19 /- /-
C 272 /- /- /-/125 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -9
Chords Tens.Comp.
B - C 77 -63
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.020 D - -
HORZ(TL):0.031 D - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.429
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ01
Ply: 1
Qty:2
Wgt: 30.8 lbs
SEQN: 17505 / T9 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"8
A
B
C
D
3.54 12
3X4(A1T)
8'4"5
8'4"52'2"3
4"5 2'9"143'4"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 0 plf at -2.26 to 55 plf at -0.08TC: From 2 plf at -0.08 to 2 plf at 5.53BC: From 0 plf at -2.26 to 4 plf at -0.08
BC: From 2 plf at 0.00 to 2 plf at 5.53TC: 88 lb Conc. Load at 2.87BC: 39 lb Conc. Load at 2.87
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.53BC 45 0.15 3.92BC 18 4.02 5.53
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is1-11-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 178 /- /- /-/47 /-
E 27 /- /- /1 /- /-
D 83 /- /- /- /9 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5EBrg Width = 1.5 Min Req =-
D Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 18 -8
B - C 6 -30
Chords Tens.Comp.
C - D 23 -3
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 10 -1
Chords Tens.Comp.
C - E 3 -4
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
F - C 61 -7
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.038 F 999 240
VERT(CL):0.072 F 901 180
HORZ(LL):0.019 E - -
HORZ(TL):0.035 E - -
Creep Factor: 2.0
Max TC CSI:0.680
Max BC CSI:0.205
Max Web CSI:0.055
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ02
Ply: 1
Qty:2
Wgt: 25.2 lbs
SEQN: 17508 / T3 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'1"2
11'9"8
A
B
C
D
E
F
3.54 12
3X4(A1T)
3X4(**)
3X4
4'0"12
4'0"12
5'6"6
1'5"102'2"3 8"64"5 1'11"141'2'6"15HB 1'5"10
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 0 plf at -2.26 to 55 plf at -0.08TC: From 2 plf at -0.08 to 2 plf at 5.53BC: From 0 plf at -2.26 to 4 plf at -0.08
BC: From 2 plf at 0.00 to 2 plf at 5.53TC: 88 lb Conc. Load at 2.87BC: 39 lb Conc. Load at 2.87
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.53BC 45 0.15 3.92BC 18 4.02 5.53
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is1-11-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 178 /- /- /-/47 /-
E 27 /- /- /1 /- /-
D 83 /- /- /- /9 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5EBrg Width = 1.5 Min Req =-
D Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 18 -8
B - C 6 -30
Chords Tens.Comp.
C - D 23 -3
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 10 -1
Chords Tens.Comp.
C - E 3 -4
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
F - C 61 -7
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.038 F 999 240
VERT(CL):0.072 F 901 180
HORZ(LL):0.019 E - -
HORZ(TL):0.035 E - -
Creep Factor: 2.0
Max TC CSI:0.680
Max BC CSI:0.205
Max Web CSI:0.055
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ02
Ply: 1
Qty:2
Wgt: 25.2 lbs
SEQN: 17508 / T3 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'1"2
11'9"8
A
B
C
D
E
F
3.54 12
3X4(A1T)
3X4(**)
3X4
4'0"12
4'0"12
5'6"6
1'5"102'2"3 8"64"5 1'11"141'2'6"15HB 1'5"10
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.89BC 69 0.15 5.89Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 4-1-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-1-2.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 354 /- /- /-/81 /-
D 33 /- /-/13 /- /-
C 123 /- /- /-/55 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -12
Chords Tens.Comp.
B - C 35 -44
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.005 D - -
HORZ(TL):0.008 D - -
Creep Factor: 2.0
Max TC CSI:0.808
Max BC CSI:0.235
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ03
Ply: 1
Qty:1
Wgt: 22.4 lbs
SEQN: 17499 / T40 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'10"12
A
B
C
D
3.54 12
3X4(A1T)
5'10"10
5'10"102'2"3
4"5 2'1"22'8"32. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.89BC 69 0.15 5.89Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 4-1-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-1-2.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 354 /- /- /-/81 /-
D 33 /- /-/13 /- /-
C 123 /- /- /-/55 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -12
Chords Tens.Comp.
B - C 35 -44
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.005 D - -
HORZ(TL):0.008 D - -
Creep Factor: 2.0
Max TC CSI:0.808
Max BC CSI:0.235
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ03
Ply: 1
Qty:1
Wgt: 22.4 lbs
SEQN: 17499 / T40 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'10"12
A
B
C
D
3.54 12
3X4(A1T)
5'10"10
5'10"102'2"3
4"5 2'1"22'8"3This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 8.01BC 94 0.15 8.01Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 5-7-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-8-10.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 415 /- /- /-/92 /-
D 65 /- /-/17 /- /-
C 246 /- /- /-/113 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -9
Chords Tens.Comp.
B - C 70 -61
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.018 D - -
HORZ(TL):0.028 D - -
Creep Factor: 2.0
Max TC CSI:0.967
Max BC CSI:0.386
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ04
Ply: 1
Qty:1
Wgt: 30.8 lbs
SEQN: 17502 / T43 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'6"4
A
B
C
D
3.54 12
3X4(A1T)
8'0"1
8'0"12'2"3
4"5 2'8"103'3"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 8.01BC 94 0.15 8.01Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Hipjack supports 5-7-15 setback jacks with no webs.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-8-10.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 415 /- /- /-/92 /-
D 65 /- /-/17 /- /-
C 246 /- /- /-/113 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -9
Chords Tens.Comp.
B - C 70 -61
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.018 D - -
HORZ(TL):0.028 D - -
Creep Factor: 2.0
Max TC CSI:0.967
Max BC CSI:0.386
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ04
Ply: 1
Qty:1
Wgt: 30.8 lbs
SEQN: 17502 / T43 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'6"4
A
B
C
D
3.54 12
3X4(A1T)
8'0"1
8'0"12'2"3
4"5 2'8"103'3"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 0 plf at -2.26 to 55 plf at -0.08TC: From 2 plf at -0.08 to 2 plf at 5.53BC: From 0 plf at -2.26 to 4 plf at -0.08
BC: From 2 plf at 0.00 to 2 plf at 5.53TC: 110 lb Conc. Load at 2.87BC: 60 lb Conc. Load at 2.87
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.53BC 66 0.00 5.53Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-9-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 173 /- /- /-/45 /-
D 83 /- /-/12 /- /-
C 63 /- /- /-/21 /-
Wind reactions based on MWFRS
E Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 18 -8
Chords Tens.Comp.
B - C 18 -19
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 56 -132
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.766
Max BC CSI:0.480
Max Web CSI:0.009
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ05
Ply: 1
Qty:3
Wgt: 24.5 lbs
SEQN: 17485 / T26 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"8
A
B
C
DE
3.54 12
3X4
3X4
5'6"6
5'6"62'2"3 2'6"61'2"52'9"14HB 5'0"14
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 0 plf at -2.26 to 55 plf at -0.08TC: From 2 plf at -0.08 to 2 plf at 5.53BC: From 0 plf at -2.26 to 4 plf at -0.08
BC: From 2 plf at 0.00 to 2 plf at 5.53TC: 110 lb Conc. Load at 2.87BC: 60 lb Conc. Load at 2.87
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 5.53BC 66 0.00 5.53Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-9-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 173 /- /- /-/45 /-
D 83 /- /-/12 /- /-
C 63 /- /- /-/21 /-
Wind reactions based on MWFRS
E Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 18 -8
Chords Tens.Comp.
B - C 18 -19
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 56 -132
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.766
Max BC CSI:0.480
Max Web CSI:0.009
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ05
Ply: 1
Qty:3
Wgt: 24.5 lbs
SEQN: 17485 / T26 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"8
A
B
C
DE
3.54 12
3X4
3X4
5'6"6
5'6"62'2"3 2'6"61'2"52'9"14HB 5'0"14
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 2.64BC 30 0.15 2.64Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is1-1-10.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 287 /- /-/187 /138 /50
D 25 /-8 /-/24 /12 /-
C 58 /-11 /-/20 /19 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 17 -23
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.002 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.643
Max BC CSI:0.273
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ06
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17494 / T68 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"4
A
B
C
D
3.54 12
3X4(A1T)
2'7"12
2'7"122'2"3
4"5 1'1"101'8"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 2.64BC 30 0.15 2.64Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is1-1-10.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 287 /- /-/187 /138 /50
D 25 /-8 /-/24 /12 /-
C 58 /-11 /-/20 /19 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 17 -23
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.002 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.643
Max BC CSI:0.273
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ06
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17494 / T68 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"4
A
B
C
D
3.54 12
3X4(A1T)
2'7"12
2'7"122'2"3
4"5 1'1"101'8"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.16 2.24BC 25 0.15 2.24Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-0-0.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 279 /- /-/185 /140 /46
D 20 /-13 /-/26 /16 /-
C 47 /-13 /-/25 /23 /-
Wind reactions based on MWFRS
B Brg Width = 7.8 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 36 0
Chords Tens.Comp.
B - C 15 -20
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.605
Max BC CSI:0.246
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ07
Ply: 1
Qty:1
Wgt: 11.2 lbs
SEQN: 17535 / T11 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
10'9"10
A
B
C
D
3.54 12
3X4(**)
2'2"13
2'2"132'1"7
4"1 1'1'7"12. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.16 2.24BC 25 0.15 2.24Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-0-0.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 279 /- /-/185 /140 /46
D 20 /-13 /-/26 /16 /-
C 47 /-13 /-/25 /23 /-
Wind reactions based on MWFRS
B Brg Width = 7.8 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 36 0
Chords Tens.Comp.
B - C 15 -20
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.605
Max BC CSI:0.246
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ07
Ply: 1
Qty:1
Wgt: 11.2 lbs
SEQN: 17535 / T11 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
10'9"10
A
B
C
D
3.54 12
3X4(**)
2'2"13
2'2"132'1"7
4"1 1'1'7"1This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 3.12BC 36 0.15 3.12Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is1-3-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 291 /- /-/187 /133 /54
D 33 /- /-/23 /8 /-
C 70 /- /-/18 /24 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 20 -33
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.002 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.643
Max BC CSI:0.274
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ08
Ply: 1
Qty:1
Wgt: 14.0 lbs
SEQN: 17491 / T73 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'0"15
A
B
C
D
3.54 12
3X4(A1T)
3'1"6
3'1"62'2"3
4"5 1'3"51'10"62. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.22 3.12BC 36 0.15 3.12Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is1-3-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 291 /- /-/187 /133 /54
D 33 /- /-/23 /8 /-
C 70 /- /-/18 /24 /-
Wind reactions based on MWFRS
B Brg Width = 7.0 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 20 -33
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.002 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.643
Max BC CSI:0.274
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:HJ08
Ply: 1
Qty:1
Wgt: 14.0 lbs
SEQN: 17491 / T73 / HIP_
FROM:DRW:
.../...04/15/2020
10'1"2
11'0"15
A
B
C
D
3.54 12
3X4(A1T)
3'1"6
3'1"62'2"3
4"5 1'3"51'10"6This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00BC 22 0.15 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-2-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 214 /- /-/146 /71 /48
D 20 /-3 /-/16 /8 /-
C 44 /- /-/20 /16 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 17 -25
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.122
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J01
Ply: 1
Qty:8
Wgt: 8.4 lbs
SEQN: 17430 / T27 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"15
A
B
C
D
5 12
3X4(**)
2'
2'1'6"8
4"5 1'2"51'9"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00BC 22 0.15 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-2-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 214 /- /-/146 /71 /48
D 20 /-3 /-/16 /8 /-
C 44 /- /-/20 /16 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 17 -25
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.122
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J01
Ply: 1
Qty:8
Wgt: 8.4 lbs
SEQN: 17430 / T27 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"15
A
B
C
D
5 12
3X4(**)
2'
2'1'6"8
4"5 1'2"51'9"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 2.00BC 24 0.00 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-2-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 65 /- /-/33 /11 /29
C 28 /- /-/13 /1 /-
B 47 /- /-/24 /26 /-
Wind reactions based on MWFRS
A Brg Width = 1.5CBrg Width = 1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 18 -40
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 C - -
HORZ(TL):0.001 C - -
Creep Factor: 2.0
Max TC CSI:0.101
Max BC CSI:0.076
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J01A
Ply: 1
Qty:2
Wgt: 7.0 lbs
SEQN: 17436 / T41 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"15
A
B
C
5 12
3X4(**)
2'
1"8
1"8
2'1"8
2'
4"5 1'2"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 2.00BC 24 0.00 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-2-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 65 /- /-/33 /11 /29
C 28 /- /-/13 /1 /-
B 47 /- /-/24 /26 /-
Wind reactions based on MWFRS
A Brg Width = 1.5CBrg Width = 1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 18 -40
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 C - -
HORZ(TL):0.001 C - -
Creep Factor: 2.0
Max TC CSI:0.101
Max BC CSI:0.076
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J01A
Ply: 1
Qty:2
Wgt: 7.0 lbs
SEQN: 17436 / T41 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'11"15
A
B
C
5 12
3X4(**)
2'
1"8
1"8
2'1"8
2'
4"5 1'2"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.00BC 46 0.15 4.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 254 /- /-/160 /69 /78
D 51 /- /-/20 /- /-
C 94 /- /-/37 /48 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 36 -55
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.003 D - -
HORZ(TL):0.005 D - -
Creep Factor: 2.0
Max TC CSI:0.366
Max BC CSI:0.212
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J02
Ply: 1
Qty:4
Wgt: 16.8 lbs
SEQN: 17433 / T25 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
D
5 12
3X4(**)
4'
4'1'6"8
4"5 2'0"52'7"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.00BC 46 0.15 4.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 254 /- /-/160 /69 /78
D 51 /- /-/20 /- /-
C 94 /- /-/37 /48 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 36 -55
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.003 D - -
HORZ(TL):0.005 D - -
Creep Factor: 2.0
Max TC CSI:0.366
Max BC CSI:0.212
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J02
Ply: 1
Qty:4
Wgt: 16.8 lbs
SEQN: 17433 / T25 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
D
5 12
3X4(**)
4'
4'1'6"8
4"5 2'0"52'7"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 4.00BC 48 0.00 4.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 130 /- /-/66 /26 /58
C 56 /- /-/25 /- /-
B 96 /- /-/49 /54 /-
Wind reactions based on MWFRS
A Brg Width = 1.5CBrg Width = 1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -59
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.004 C - -
HORZ(TL):0.006 C - -
Creep Factor: 2.0
Max TC CSI:0.326
Max BC CSI:0.220
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J02A
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17439 / T33 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
5 12
3X4(**)
4'
1"8
1"8
4'1"8
4'
4"5 2'0"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 4.00BC 48 0.00 4.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 130 /- /-/66 /26 /58
C 56 /- /-/25 /- /-
B 96 /- /-/49 /54 /-
Wind reactions based on MWFRS
A Brg Width = 1.5CBrg Width = 1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -59
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.004 C - -
HORZ(TL):0.006 C - -
Creep Factor: 2.0
Max TC CSI:0.326
Max BC CSI:0.220
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J02A
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17439 / T33 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
5 12
3X4(**)
4'
1"8
1"8
4'1"8
4'
4"5 2'0"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 6.00BC 70 0.15 6.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 311 /- /-/187 /80 /107
D 81 /- /-/31 /- /-
C 144 /- /-/66 /78 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 55 -80
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.011 D - -
HORZ(TL):0.018 D - -
Creep Factor: 2.0
Max TC CSI:0.780
Max BC CSI:0.474
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J03
Ply: 1
Qty:4
Wgt: 22.4 lbs
SEQN: 17452 / T28 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"15
A
B
C
D
5 12
3X4(**)
6'
6'1'6"8
4"5 2'10"53'5"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 6.00BC 70 0.15 6.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 311 /- /-/187 /80 /107
D 81 /- /-/31 /- /-
C 144 /- /-/66 /78 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 55 -80
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.011 D - -
HORZ(TL):0.018 D - -
Creep Factor: 2.0
Max TC CSI:0.780
Max BC CSI:0.474
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J03
Ply: 1
Qty:4
Wgt: 22.4 lbs
SEQN: 17452 / T28 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"15
A
B
C
D
5 12
3X4(**)
6'
6'1'6"8
4"5 2'10"53'5"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 7.92BC 75 0.15 7.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is3-7-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 369 /- /-/216 /50 /98
D 253 /- /-/135 /58 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 1.5 Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 42 -115
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 33 -20
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - D 186 -188
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.021 D - -
HORZ(TL):0.034 D - -
Creep Factor: 2.0
Max TC CSI:0.773
Max BC CSI:0.458
Max Web CSI:0.321
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J04
Ply: 1
Qty:6
Wgt: 33.6 lbs
SEQN: 17446 / T19 / MONO
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
5 12
3X4(**)
3X4(**)
4X5(**)
7'11"
7'11"1'6"8
4"5 3'7"144'3"12. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 7.92BC 75 0.15 7.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is3-7-14.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 369 /- /-/216 /50 /98
D 253 /- /-/135 /58 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 1.5 Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 42 -115
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 33 -20
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - D 186 -188
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.021 D - -
HORZ(TL):0.034 D - -
Creep Factor: 2.0
Max TC CSI:0.773
Max BC CSI:0.458
Max Web CSI:0.321
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J04
Ply: 1
Qty:6
Wgt: 33.6 lbs
SEQN: 17446 / T19 / MONO
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
5 12
3X4(**)
3X4(**)
4X5(**)
7'11"
7'11"1'6"8
4"5 3'7"144'3"1This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(**) except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00
BC 22 0.15 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
1-2-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D*113 /- /-/71 /36 /24
Wind reactions based on MWFRS
D Brg Width = 24.0 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 15 -24
Maximum Bot Chord Forces Per Ply (lbs)Chords Tens.Comp.
B - D 175 -29
Maximum Gable Forces Per Ply (lbs)Gables Tens.Comp.
C - D 48 -44
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):-0.001 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.114
Max Web CSI:0.016
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J05
Ply: 1
Qty:2
Wgt: 9.8 lbs
SEQN: 17464 / T7 / GABL
FROM:DRW:
.../...04/15/2020
9'3"2
A
B
C
D
5 12
2'
1'10"
1'10"
2'
2"
1'10"
1'10"
2'
2"1'6"8
4"5 1'2"51'9"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(**) except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00
BC 22 0.15 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
1-2-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D*113 /- /-/71 /36 /24
Wind reactions based on MWFRS
D Brg Width = 24.0 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 15 -24
Maximum Bot Chord Forces Per Ply (lbs)Chords Tens.Comp.
B - D 175 -29
Maximum Gable Forces Per Ply (lbs)Gables Tens.Comp.
C - D 48 -44
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):-0.001 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.114
Max Web CSI:0.016
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J05
Ply: 1
Qty:2
Wgt: 9.8 lbs
SEQN: 17464 / T7 / GABL
FROM:DRW:
.../...04/15/2020
9'3"2
A
B
C
D
5 12
2'
1'10"
1'10"
2'
2"
1'10"
1'10"
2'
2"1'6"8
4"5 1'2"51'9"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 6.00BC 26 0.15 2.31BC 29 2.40 4.77BC 14 4.86 6.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 311 /- /-/187 /80 /107
F 22 /- /-/10 /- /-
E 177 /- /-/86 /73 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5FBrg Width = 1.5 Min Req =-
E Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 2 -83
Chords Tens.Comp.
C - D 31 -75
D - E 68 -64
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 8 -2
C - G 8 0
Chords Tens.Comp.
D - F 3 -5
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
H - C 51 -12
Webs Tens.Comp.
G - D 46 -3
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.132 H 534 240
VERT(CL):0.214 H 327 180
HORZ(LL):0.064 G - -
HORZ(TL):0.105 G - -
Creep Factor: 2.0
Max TC CSI:0.629
Max BC CSI:0.236
Max Web CSI:0.034
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J06
Ply: 1
Qty:6
Wgt: 28.0 lbs
SEQN: 17470 / T8 / EJAC
FROM:DRW:
.../...04/15/2020
9'3"2
11'1"2
11'9"15
A
B
C
D
E
F
G
H
5 12
3X4(**)
3X4(**)
3X4
3X4(**)
3X4
2'5"8
2'5"8
4'11"
2'5"8
6'
1'1"1'6"8
8"13
4"5 2'10"510"1'10"3'5"8HB 1'1"
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 6.00BC 26 0.15 2.31BC 29 2.40 4.77BC 14 4.86 6.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 311 /- /-/187 /80 /107
F 22 /- /-/10 /- /-
E 177 /- /-/86 /73 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5FBrg Width = 1.5 Min Req =-
E Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 2 -83
Chords Tens.Comp.
C - D 31 -75
D - E 68 -64
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 8 -2
C - G 8 0
Chords Tens.Comp.
D - F 3 -5
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
H - C 51 -12
Webs Tens.Comp.
G - D 46 -3
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.132 H 534 240
VERT(CL):0.214 H 327 180
HORZ(LL):0.064 G - -
HORZ(TL):0.105 G - -
Creep Factor: 2.0
Max TC CSI:0.629
Max BC CSI:0.236
Max Web CSI:0.034
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J06
Ply: 1
Qty:6
Wgt: 28.0 lbs
SEQN: 17470 / T8 / EJAC
FROM:DRW:
.../...04/15/2020
9'3"2
11'1"2
11'9"15
A
B
C
D
E
F
G
H
5 12
3X4(**)
3X4(**)
3X4
3X4(**)
3X4
2'5"8
2'5"8
4'11"
2'5"8
6'
1'1"1'6"8
8"13
4"5 2'10"510"1'10"3'5"8HB 1'1"
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 1.00BC 10 0.15 1.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is0-9-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 238 /- /-/176 /102 /34
D 9 /-23 /-/19 /20 /-
C 18 /-55 /-/42 /50 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 59 -31
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):-0.000 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.075
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J07
Ply: 1
Qty:2
Wgt: 5.6 lbs
SEQN: 17455 / T38 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'6"15
A
B
C
D
5 12
3X4(**)
1'
1'1'6"8
4"5 9"51'4"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 1.00BC 10 0.15 1.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is0-9-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 238 /- /-/176 /102 /34
D 9 /-23 /-/19 /20 /-
C 18 /-55 /-/42 /50 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 59 -31
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):-0.000 D - -
HORZ(TL):0.001 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.075
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J07
Ply: 1
Qty:2
Wgt: 5.6 lbs
SEQN: 17455 / T38 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
10'6"15
A
B
C
D
5 12
3X4(**)
1'
1'1'6"8
4"5 9"51'4"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 3.00BC 34 0.15 3.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-7-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 229 /- /-/149 /65 /63
D 36 /- /-/16 /1 /-
C 69 /- /-/21 /32 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 27 -54
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.109
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J08
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17458 / T36 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'4"15
A
B
C
D
5 12
3X4(**)
3'
3'1'6"8
4"5 1'7"52'2"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 3.00BC 34 0.15 3.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-7-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 229 /- /-/149 /65 /63
D 36 /- /-/16 /1 /-
C 69 /- /-/21 /32 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 27 -54
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.001 D - -
HORZ(TL):0.002 D - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.109
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J08
Ply: 1
Qty:2
Wgt: 12.6 lbs
SEQN: 17458 / T36 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'4"15
A
B
C
D
5 12
3X4(**)
3'
3'1'6"8
4"5 1'7"52'2"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.25BC 49 0.15 4.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-1-9.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 260 /- /-/163 /70 /82
D 55 /- /-/21 /- /-
C 100 /- /-/41 /52 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 39 -59
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.004 D - -
HORZ(TL):0.006 D - -
Creep Factor: 2.0
Max TC CSI:0.366
Max BC CSI:0.239
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J09
Ply: 1
Qty:4
Wgt: 18.2 lbs
SEQN: 17461 / T39 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
11'11"3
A
B
C
D
5 12
3X4(**)
4'3"
4'3"1'6"8
4"5 2'1"92'8"122. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.25BC 49 0.15 4.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-1-9.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 260 /- /-/163 /70 /82
D 55 /- /-/21 /- /-
C 100 /- /-/41 /52 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 39 -59
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.004 D - -
HORZ(TL):0.006 D - -
Creep Factor: 2.0
Max TC CSI:0.366
Max BC CSI:0.239
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J09
Ply: 1
Qty:4
Wgt: 18.2 lbs
SEQN: 17461 / T39 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
11'11"3
A
B
C
D
5 12
3X4(**)
4'3"
4'3"1'6"8
4"5 2'1"92'8"12This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at 0.00 to 55 plf at 4.25BC: From 5 plf at 0.00 to 5 plf at 4.25BC: 65 lb Conc. Load at 0.65BC: 130 lb Conc. Load at 2.65
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 4.25BC 49 0.15 4.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-1-9.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 240 /- /- /-/73 /-
C 98 /- /- /-/16 /-
B 113 /- /- /-/50 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5CBrg Width = 1.5 Min Req =-
B Brg Width = 1.5 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 44 -35
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.007 C - -
HORZ(TL):0.011 C - -
Creep Factor: 2.0
Max TC CSI:0.528
Max BC CSI:0.722
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J10
Ply: 1
Qty:1
Wgt: 14.0 lbs
SEQN: 17449 / T51 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'11"3
A
B
C
5 12
3X4(**)
4'3"
4'3"
4"5 2'1"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at 0.00 to 55 plf at 4.25BC: From 5 plf at 0.00 to 5 plf at 4.25BC: 65 lb Conc. Load at 0.65BC: 130 lb Conc. Load at 2.65
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 4.25BC 49 0.15 4.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-1-9.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 240 /- /- /-/73 /-
C 98 /- /- /-/16 /-
B 113 /- /- /-/50 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5CBrg Width = 1.5 Min Req =-
B Brg Width = 1.5 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 44 -35
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - C 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.007 C - -
HORZ(TL):0.011 C - -
Creep Factor: 2.0
Max TC CSI:0.528
Max BC CSI:0.722
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J10
Ply: 1
Qty:1
Wgt: 14.0 lbs
SEQN: 17449 / T51 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'11"3
A
B
C
5 12
3X4(**)
4'3"
4'3"
4"5 2'1"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 5.75BC 67 0.15 5.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 303 /- /-/183 /52 /74
D 77 /- /-/30 /- /-
C 137 /- /-/62 /48 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 53 -78
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.010 D - -
HORZ(TL):0.016 D - -
Creep Factor: 2.0
Max TC CSI:0.710
Max BC CSI:0.435
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J11
Ply: 1
Qty:3
Wgt: 22.4 lbs
SEQN: 17473 / T42 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'6"11
A
B
C
D
5 12
3X4(**)
5'9"
5'9"1'6"8
4"5 2'9"13'4"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 5.75BC 67 0.15 5.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 303 /- /-/183 /52 /74
D 77 /- /-/30 /- /-
C 137 /- /-/62 /48 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 53 -78
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - D 0 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):NA
VERT(CL):NA
HORZ(LL):0.010 D - -
HORZ(TL):0.016 D - -
Creep Factor: 2.0
Max TC CSI:0.710
Max BC CSI:0.435
Max Web CSI:0.000
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J11
Ply: 1
Qty:3
Wgt: 22.4 lbs
SEQN: 17473 / T42 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'6"11
A
B
C
D
5 12
3X4(**)
5'9"
5'9"1'6"8
4"5 2'9"13'4"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00BC 24 0.00 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 198 /- /-/148 /83 /-
D 30 /- /-/10 /- /-
C 55 /- /-/38 /29 /48
Wind reactions based on MWFRS
E Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 188 -44
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 455 -188
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):-0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.058
Max Web CSI:0.057
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J12
Ply: 1
Qty:5
Wgt: 10.5 lbs
SEQN: 17476 / T22 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
DE
5 12
3X4
3X8(**)
2'
2'1'6"8 1'8"131'2"52'0"5HB 1'6"8
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 1 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 2.00BC 24 0.00 2.00Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 198 /- /-/148 /83 /-
D 30 /- /-/10 /- /-
C 55 /- /-/38 /29 /48
Wind reactions based on MWFRS
E Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 188 -44
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 455 -188
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):-0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.581
Max BC CSI:0.058
Max Web CSI:0.057
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J12
Ply: 1
Qty:5
Wgt: 10.5 lbs
SEQN: 17476 / T22 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
C
DE
5 12
3X4
3X8(**)
2'
2'1'6"8 1'8"131'2"52'0"5HB 1'6"8
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 2.00BC 24 0.00 2.00
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D 65 /- /-/36 /24 /-
C 30 /- /-/10 /- /-
B 55 /- /-/24 /20 /29
Wind reactions based on MWFRS
D Brg Width = 5.5 Min Req =1.5CBrg Width = 1.5 Min Req =-
B Brg Width = 1.5 Min Req =-
Bearing D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 48 -21
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
D - C 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - D 106 -55
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 A 999 240
VERT(CL):0.000 A 999 180
HORZ(LL):-0.000 A - -
HORZ(TL):0.000 A - -
Creep Factor: 2.0
Max TC CSI:0.172
Max BC CSI:0.058
Max Web CSI:0.013
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J12A
Ply: 1
Qty:1
Wgt: 9.1 lbs
SEQN: 17482 / T20 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
CD
5 12
3X4
3X4
2'
2'1'8"131'2"52'0"5HB 1'6"8
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 2.00BC 24 0.00 2.00
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D 65 /- /-/36 /24 /-
C 30 /- /-/10 /- /-
B 55 /- /-/24 /20 /29
Wind reactions based on MWFRS
D Brg Width = 5.5 Min Req =1.5CBrg Width = 1.5 Min Req =-
B Brg Width = 1.5 Min Req =-
Bearing D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 48 -21
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
D - C 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - D 106 -55
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 A 999 240
VERT(CL):0.000 A 999 180
HORZ(LL):-0.000 A - -
HORZ(TL):0.000 A - -
Creep Factor: 2.0
Max TC CSI:0.172
Max BC CSI:0.058
Max Web CSI:0.013
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J12A
Ply: 1
Qty:1
Wgt: 9.1 lbs
SEQN: 17482 / T20 / JACK
FROM:DRW:
.../...04/15/2020
10'1"2
11'9"15
A
B
CD
5 12
3X4
3X4
2'
2'1'8"131'2"52'0"5HB 1'6"8
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.00BC 48 0.00 4.00
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 244 /- /-/169 /99 /-
D 60 /- /-/20 /- /-
C 110 /- /-/32 /25 /78
Wind reactions based on MWFRS
E Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 130 -50
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 286 -224
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):-0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.438
Max BC CSI:0.251
Max Web CSI:0.036
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J13
Ply: 1
Qty:7
Wgt: 18.9 lbs
SEQN: 17479 / T24 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"15
A
B
C
DE
5 12
3X4
4X5
4'
4'1'6"8 2'6"131'2"52'10"5HB 3'6"8
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x6 SP #2
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 4.00BC 48 0.00 4.00
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
E 244 /- /-/169 /99 /-
D 60 /- /-/20 /- /-
C 110 /- /-/32 /25 /78
Wind reactions based on MWFRS
E Brg Width = 5.5 Min Req =1.5DBrg Width = 1.5 Min Req =-
C Brg Width = 1.5 Min Req =-
Bearing E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
Chords Tens.Comp.
B - C 130 -50
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - D 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - E 286 -224
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 B 999 240
VERT(CL):0.000 B 999 180
HORZ(LL):-0.000 B - -
HORZ(TL):0.000 B - -
Creep Factor: 2.0
Max TC CSI:0.438
Max BC CSI:0.251
Max Web CSI:0.036
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:J13
Ply: 1
Qty:7
Wgt: 18.9 lbs
SEQN: 17479 / T24 / EJAC
FROM:DRW:
.../...04/15/2020
10'1"2
12'7"15
A
B
C
DE
5 12
3X4
4X5
4'
4'1'6"8 2'6"131'2"52'10"5HB 3'6"8
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.45 7.39BC 80 0.15 6.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is2-9-7.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B*69 /- /-/32 /24 /12
J /-110
H /-110
Wind reactions based on MWFRS
B Brg Width = 83.3 Min Req =-Bearing B is a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 15 0
B - C 19 -47
C - D 81 -46
Chords Tens.Comp.
D - E 81 -46
E - F 43 -53
F - G 15 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 50 -27
J - I 56 -30
Chords Tens.Comp.
I - H 56 -30
H - F 50 -31
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
C - J 111 -105
D - I 9 -48
Gables Tens.Comp.
H - E 111 -105
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 H 999 240
VERT(CL):0.001 H 999 180
HORZ(LL):-0.001 J - -
HORZ(TL):0.001 J - -
Creep Factor: 2.0
Max TC CSI:0.052
Max BC CSI:0.040
Max Web CSI:0.032
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB01
Ply: 1
Qty:1
Wgt: 37.8 lbs
SEQN: 17641 / T4 / GABL
FROM:DRW:
.../...04/15/2020
21'0"11A
B
C
D
E
F
G
HIJ
8
12
3X4(A1T)
4X4
3X4(A1T)
6'11"4
2'1"10
1'4"
(TYP)
3'5"10
3'5"10
6'11"4
3'5"10
6'11"4
6'11"4
4"32'7"152'9"72. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.45 7.39BC 80 0.15 6.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14015ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is2-9-7.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B*69 /- /-/32 /24 /12
J /-110
H /-110
Wind reactions based on MWFRS
B Brg Width = 83.3 Min Req =-Bearing B is a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 15 0
B - C 19 -47
C - D 81 -46
Chords Tens.Comp.
D - E 81 -46
E - F 43 -53
F - G 15 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 50 -27
J - I 56 -30
Chords Tens.Comp.
I - H 56 -30
H - F 50 -31
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
C - J 111 -105
D - I 9 -48
Gables Tens.Comp.
H - E 111 -105
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.000 H 999 240
VERT(CL):0.001 H 999 180
HORZ(LL):-0.001 J - -
HORZ(TL):0.001 J - -
Creep Factor: 2.0
Max TC CSI:0.052
Max BC CSI:0.040
Max Web CSI:0.032
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB01
Ply: 1
Qty:1
Wgt: 37.8 lbs
SEQN: 17641 / T4 / GABL
FROM:DRW:
.../...04/15/2020
21'0"11A
B
C
D
E
F
G
HIJ
8
12
3X4(A1T)
4X4
3X4(A1T)
6'11"4
2'1"10
1'4"
(TYP)
3'5"10
3'5"10
6'11"4
3'5"10
6'11"4
6'11"4
4"32'7"152'9"7This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 8.38BC 91 0.15 7.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-1-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-73 /-/84 /104 /82
B*86 /- /-/44 /17 /-
E -/-73 /-/39 /59 /-
B /-109
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 94.4 Min Req =-
E Brg Width = 5.6 Min Req =1.5
Bearings A, B, & E are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 131 -115
B - C 117 -142
Chords Tens.Comp.
C - D 117 -142
D - E 57 -43
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 62 -17
Chords Tens.Comp.
F - D 62 -17
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 7 -88
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.001 F 999 240
VERT(CL):0.002 F 999 180
HORZ(LL):-0.001 F - -
HORZ(TL):0.002 F - -
Creep Factor: 2.0
Max TC CSI:0.257
Max BC CSI:0.094
Max Web CSI:0.019
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:PB02
Ply: 1
Qty:6
Wgt: 32.2 lbs
SEQN: 17579 / T30 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
4X4
3X4
8"9 7'10"6 8"9
8"9
8"9
4'7"12
3'11"3
8'6"15
3'11"3
9'3"8
8"9
8"9
8"9
4'7"12
3'11"3
8'6"15
3'11"3
9'3"8
8"9
8"95"9
0"83'0"31"8 3'1"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 8.38BC 91 0.15 7.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-1-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-73 /-/84 /104 /82
B*86 /- /-/44 /17 /-
E -/-73 /-/39 /59 /-
B /-109
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 94.4 Min Req =-
E Brg Width = 5.6 Min Req =1.5
Bearings A, B, & E are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 131 -115
B - C 117 -142
Chords Tens.Comp.
C - D 117 -142
D - E 57 -43
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 62 -17
Chords Tens.Comp.
F - D 62 -17
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 7 -88
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.001 F 999 240
VERT(CL):0.002 F 999 180
HORZ(LL):-0.001 F - -
HORZ(TL):0.002 F - -
Creep Factor: 2.0
Max TC CSI:0.257
Max BC CSI:0.094
Max Web CSI:0.019
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:PB02
Ply: 1
Qty:6
Wgt: 32.2 lbs
SEQN: 17579 / T30 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
4X4
3X4
8"9 7'10"6 8"9
8"9
8"9
4'7"12
3'11"3
8'6"15
3'11"3
9'3"8
8"9
8"9
8"9
4'7"12
3'11"3
8'6"15
3'11"3
9'3"8
8"9
8"95"9
0"83'0"31"8 3'1"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-8-5.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 40 /-72 /-/84 /98 /70
B*72 /- /-/36 /15 /-
G 40 /-72 /-/46 /61 /-
B /-122
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 118 -105
B - C 169 -260
C - D 174 -173
Chords Tens.Comp.
D - E 174 -173
E - F 169 -260
F - G 56 -26
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 173 -60
Chords Tens.Comp.
H - F 173 -60
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 77 -109
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.014 E 999 240
VERT(CL):0.029 E 999 180
HORZ(LL):0.009 C - -
HORZ(TL):0.019 C - -
Creep Factor: 2.0
Max TC CSI:0.284
Max BC CSI:0.107
Max Web CSI:0.023
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB03
Ply: 1
Qty:1
Wgt: 36.4 lbs
SEQN: 17647 / T61 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12
3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
3'11"12
3'3"3
5'7"12
1'8"
7'3"12
1'8"
10'6"15
3'3"3
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"82'6"131"8 2'8"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-8-5.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 40 /-72 /-/84 /98 /70
B*72 /- /-/36 /15 /-
G 40 /-72 /-/46 /61 /-
B /-122
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 118 -105
B - C 169 -260
C - D 174 -173
Chords Tens.Comp.
D - E 174 -173
E - F 169 -260
F - G 56 -26
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 173 -60
Chords Tens.Comp.
H - F 173 -60
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 77 -109
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.014 E 999 240
VERT(CL):0.029 E 999 180
HORZ(LL):0.009 C - -
HORZ(TL):0.019 C - -
Creep Factor: 2.0
Max TC CSI:0.284
Max BC CSI:0.107
Max Web CSI:0.023
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB03
Ply: 1
Qty:1
Wgt: 36.4 lbs
SEQN: 17647 / T61 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12
3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
3'11"12
3'3"3
5'7"12
1'8"
7'3"12
1'8"
10'6"15
3'3"3
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"82'6"131"8 2'8"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-9-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-141 /-/126 /166 /101
B*94 /- /-/47 /21 /-
E -/-141 /-/72 /111 /-
B /-157
D /-134Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
E Brg Width = 5.6 Min Req =1.5
Bearings A, B, & E are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 181 -154
B - C 143 -189
Chords Tens.Comp.
C - D 142 -189
D - E 95 -73
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 85 -21
Chords Tens.Comp.
F - D 85 -21
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 9 -102
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.002 F 999 240
VERT(CL):0.003 F 999 180
HORZ(LL):-0.002 F - -
HORZ(TL):0.003 F - -
Creep Factor: 2.0
Max TC CSI:0.420
Max BC CSI:0.142
Max Web CSI:0.027
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB04
Ply: 1
Qty:7
Wgt: 42.0 lbs
SEQN: 17650 / T58 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
4X4
3X4
8"9 9'10"6 8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"83'8"31"8 3'9"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-9-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-141 /-/126 /166 /101
B*94 /- /-/47 /21 /-
E -/-141 /-/72 /111 /-
B /-157
D /-134Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
E Brg Width = 5.6 Min Req =1.5
Bearings A, B, & E are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 181 -154
B - C 143 -189
Chords Tens.Comp.
C - D 142 -189
D - E 95 -73
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 85 -21
Chords Tens.Comp.
F - D 85 -21
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 9 -102
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.002 F 999 240
VERT(CL):0.003 F 999 180
HORZ(LL):-0.002 F - -
HORZ(TL):0.003 F - -
Creep Factor: 2.0
Max TC CSI:0.420
Max BC CSI:0.142
Max Web CSI:0.027
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB04
Ply: 1
Qty:7
Wgt: 42.0 lbs
SEQN: 17650 / T58 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
4X4
3X4
8"9 9'10"6 8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"83'8"31"8 3'9"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(**) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 7.18
BC 84 0.15 7.18Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
3-9-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-149 /-/125 /160 /97
B*86 /- /-/58 /24 /-
B /-143
Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5BBrg Width = 86.2 Min Req =-
Bearings A & B are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 155 -191
B - C 66 -89
Chords Tens.Comp.
C - D 51 -39
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 2 -2
Chords Tens.Comp.
F - E 2 -2
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 83 -167
Webs Tens.Comp.
D - E 66 -67
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.002 F 999 240
VERT(CL):0.003 F 999 180
HORZ(LL):0.002 F - -
HORZ(TL):0.003 F - -
Creep Factor: 2.0
Max TC CSI:0.420
Max BC CSI:0.113
Max Web CSI:0.044
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB05
Ply: 1
Qty:7
Wgt: 35.0 lbs
SEQN: 17653 / T71 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
3X4(B1T)
4X4
3X4
7'10"12
8"9
8"9
5'7"12
4'11"3
7'10"12
2'3"
8"9
8"9 5'7"12
4'11"3
7'10"12
2'3"
0"8 2'2"33'8"31"8 3'9"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(**) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 7.18
BC 84 0.15 7.18Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
3-9-11.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A -/-149 /-/125 /160 /97
B*86 /- /-/58 /24 /-
B /-143
Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5BBrg Width = 86.2 Min Req =-
Bearings A & B are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 155 -191
B - C 66 -89
Chords Tens.Comp.
C - D 51 -39
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 2 -2
Chords Tens.Comp.
F - E 2 -2
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 83 -167
Webs Tens.Comp.
D - E 66 -67
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.002 F 999 240
VERT(CL):0.003 F 999 180
HORZ(LL):0.002 F - -
HORZ(TL):0.003 F - -
Creep Factor: 2.0
Max TC CSI:0.420
Max BC CSI:0.113
Max Web CSI:0.044
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB05
Ply: 1
Qty:7
Wgt: 35.0 lbs
SEQN: 17653 / T71 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C
D
E
F
8
12
3X4(B1T)
4X4
3X4
7'10"12
8"9
8"9
5'7"12
4'11"3
7'10"12
2'3"
8"9
8"9 5'7"12
4'11"3
7'10"12
2'3"
0"8 2'2"33'8"31"8 3'9"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-8-0.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 41 /-71 /-/82 /97 /69
B*71 /- /-/36 /15 /-
G 41 /-71 /-/45 /60 /-
B /-120
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 116 -104
B - C 168 -259
C - D 173 -173
Chords Tens.Comp.
D - E 173 -173
E - F 168 -259
F - G 56 -25
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 173 -60
Chords Tens.Comp.
H - F 173 -60
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 80 -112
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.014 E 999 240
VERT(CL):0.029 E 999 180
HORZ(LL):0.009 C - -
HORZ(TL):0.019 C - -
Creep Factor: 2.0
Max TC CSI:0.282
Max BC CSI:0.106
Max Web CSI:0.024
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB06
Ply: 1
Qty:1
Wgt: 36.4 lbs
SEQN: 17656 / T49 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12
3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
3'11"4
3'2"11
5'7"12
1'8"8
7'4"4
1'8"8
10'6"15
3'2"11
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"82'6"81"8 2'8"2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is2-8-0.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 41 /-71 /-/82 /97 /69
B*71 /- /-/36 /15 /-
G 41 /-71 /-/45 /60 /-
B /-120
Wind reactions based on MWFRSABrg Width = 5.6 Min Req =1.5
B Brg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 116 -104
B - C 168 -259
C - D 173 -173
Chords Tens.Comp.
D - E 173 -173
E - F 168 -259
F - G 56 -25
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 173 -60
Chords Tens.Comp.
H - F 173 -60
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 80 -112
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.014 E 999 240
VERT(CL):0.029 E 999 180
HORZ(LL):0.009 C - -
HORZ(TL):0.019 C - -
Creep Factor: 2.0
Max TC CSI:0.282
Max BC CSI:0.106
Max Web CSI:0.024
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB06
Ply: 1
Qty:1
Wgt: 36.4 lbs
SEQN: 17656 / T49 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12
3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
3'11"4
3'2"11
5'7"12
1'8"8
7'4"4
1'8"8
10'6"15
3'2"11
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"82'6"81"8 2'8"This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 53 /-46 /-/23 /28 /32
B*66 /- /-/30 /20 /-
G 53 /-46 /- /4 /9 /-
Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5BBrg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 47 -40
B - C 150 -211
C - D 129 -161
Chords Tens.Comp.
D - E 129 -161
E - F 150 -211
F - G 42 -30
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 160 -74
Chords Tens.Comp.
H - F 160 -74
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 168 -248
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.007 C 999 240
VERT(CL):0.013 C 999 180
HORZ(LL):0.004 C - -
HORZ(TL):0.009 C - -
Creep Factor: 2.0
Max TC CSI:0.293
Max BC CSI:0.092
Max Web CSI:0.050
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB07
Ply: 1
Qty:1
Wgt: 35.0 lbs
SEQN: 17659 / T15 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12 3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
1'11"4
1'2"11 5'7"12
3'8"8
9'4"4
3'8"8
10'6"15
1'2"11
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"81'2"81"8 1'4"2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #3
Bot chord 2x4 SP #3Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4(B1T) except as noted.
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -0.51 10.38
BC 115 0.15 9.72Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 53 /-46 /-/23 /28 /32
B*66 /- /-/30 /20 /-
G 53 /-46 /- /4 /9 /-
Wind reactions based on MWFRS
A Brg Width = 5.6 Min Req =1.5BBrg Width = 118 Min Req =-
G Brg Width = 5.6 Min Req =1.5
Bearings A, B, & G are a rigid surface.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 47 -40
B - C 150 -211
C - D 129 -161
Chords Tens.Comp.
D - E 129 -161
E - F 150 -211
F - G 42 -30
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 160 -74
Chords Tens.Comp.
H - F 160 -74
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - H 168 -248
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.007 C 999 240
VERT(CL):0.013 C 999 180
HORZ(LL):0.004 C - -
HORZ(TL):0.009 C - -
Creep Factor: 2.0
Max TC CSI:0.293
Max BC CSI:0.092
Max Web CSI:0.050
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:PB07
Ply: 1
Qty:1
Wgt: 35.0 lbs
SEQN: 17659 / T15 / COMN
FROM:DRW:
.../...04/15/2020
20'11"321'0"11A
B
C D E
F
G
H
8
12 3X4(**)3X4
3X4
3X4(**)
8"9 9'10"6 8"9
8"9
8"9
1'11"4
1'2"11 5'7"12
3'8"8
9'4"4
3'8"8
10'6"15
1'2"11
11'3"8
8"9
8"9
8"9
5'7"12
4'11"3
10'6"15
4'11"3
11'3"8
8"9
8"95"9
0"81'2"81"8 1'4"This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W5 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 32 0.15 2.77
BC 75 2.86 45.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 392 /- /-/171 /156 /337
V 1943 /- /-/774 /234 /-
P 1985 /- /-/524 /209 /-
M 556 /-28 /-/374 /190 /-
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
V Brg Width = 5.5 Min Req =1.9
P Brg Width = 5.5 Min Req =2.0
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, P, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 321 -360C - D 268 -382
D - E 484 -428
E - F 736 -270
F - G 392 -142
G - H 315 -766
Chords Tens.Comp.
H - I 315 -766
I - J 403 -154J - K 670 -144
K - L 616 -793
L - M 389 -738
M - N 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - Y 10 -4
C - X 307 -92
X - U 277 -256
W -V 0 0
V - T 519 -475
T - S 522 -311
Chords Tens.Comp.
S - R 1082 -93
R - Q 515 -288
Q - P 505 -436
P - O 236 -330
O - M 621 -262
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
Y - C 62 -24
D - X 474 -425
X - E 666 -553
E - U 371 -415
U - V 523 -1964
U - F 308 -1693
F - T 1207 -50
G - Z 75 -431
G -AC 823 -17
T -AA 57 -938Z -AA 74 -466
Webs Tens.Comp.
AB-AD 0 -1072
H -AC 5 -291
AC-AE 16 -19
AC- I 798 -7
AD- R 21 -278
AD-AF 0 -1040
R -AF 1099 0
AE-AF 98 -508
AE- I 98 -472
AF- Q 76 -976Q - J 1065 -83
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.249 Y 790 240
VERT(CL):0.437 Y 449 180
HORZ(LL):0.116 X - -
HORZ(TL):0.208 X - -
Creep Factor: 2.0
Max TC CSI:0.653
Max BC CSI:0.604
Max Web CSI:0.702
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T01
Ply: 1
Qty:1
Wgt: 350.0 lbs
SEQN: 17450 / T74 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1 W5
(a)
(a)(a)
(a)
(a)
10'1"2A
B
C
D
E
F
G H I
J
K
L
M
N
OPQRST
UVWX
Y
Z
AA AB
AC
AD
AE
AF
5 12
8
12
4X5(**)
3X4(**)
5X7(**)
4X5(R)4X5(**)
4X8
5X7(**)
4X4(R)
3X4(**)
5X5
4X5
4X8
4X5
3X4(**)
5X5
5X7(**)
5X7(**)
3X8
5X7(**)
5X7(**)
4X5(**)
16'6"4 12'10"8 16'6"4
6'9"
6'9"
10'10"4
4'1"4
16'7"14
5'9"10
18'3"
1'7"2
18'7"8
4"8 22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'3"2
1'7"2 35'8"4
6'5"2
39'2"
3'5"12
45'11"
6'9"
2'11"
2'11"
6'9"
3'10"
16'4"8
9'7"8
18'7"8
2'3"
21'3"13
2'8"5
22'11"8
1'7"1124'7"3
1'7"11
27'3"8
2'8"527'8"12
5"4
29'6"8
1'9"12 39'2"
9'7"8
45'11"
6'9"1'6"8 1'6"8
4"53'2"11'
8'8"9'2"98'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W5 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 32 0.15 2.77
BC 75 2.86 45.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 392 /- /-/171 /156 /337
V 1943 /- /-/774 /234 /-
P 1985 /- /-/524 /209 /-
M 556 /-28 /-/374 /190 /-
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
V Brg Width = 5.5 Min Req =1.9
P Brg Width = 5.5 Min Req =2.0
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, P, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 321 -360C - D 268 -382
D - E 484 -428
E - F 736 -270
F - G 392 -142
G - H 315 -766
Chords Tens.Comp.
H - I 315 -766
I - J 403 -154J - K 670 -144
K - L 616 -793
L - M 389 -738
M - N 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - Y 10 -4
C - X 307 -92
X - U 277 -256
W -V 0 0
V - T 519 -475
T - S 522 -311
Chords Tens.Comp.
S - R 1082 -93
R - Q 515 -288
Q - P 505 -436
P - O 236 -330
O - M 621 -262
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
Y - C 62 -24
D - X 474 -425
X - E 666 -553
E - U 371 -415
U - V 523 -1964
U - F 308 -1693
F - T 1207 -50
G - Z 75 -431
G -AC 823 -17
T -AA 57 -938Z -AA 74 -466
Webs Tens.Comp.
AB-AD 0 -1072
H -AC 5 -291
AC-AE 16 -19
AC- I 798 -7
AD- R 21 -278
AD-AF 0 -1040
R -AF 1099 0
AE-AF 98 -508
AE- I 98 -472
AF- Q 76 -976Q - J 1065 -83
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.249 Y 790 240
VERT(CL):0.437 Y 449 180
HORZ(LL):0.116 X - -
HORZ(TL):0.208 X - -
Creep Factor: 2.0
Max TC CSI:0.653
Max BC CSI:0.604
Max Web CSI:0.702
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T01
Ply: 1
Qty:1
Wgt: 350.0 lbs
SEQN: 17450 / T74 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1 W5
(a)
(a)(a)
(a)
(a)
10'1"2A
B
C
D
E
F
G H I
J
K
L
M
N
OPQRST
UVWX
Y
Z
AA AB
AC
AD
AE
AF
5 12
8
12
4X5(**)
3X4(**)
5X7(**)
4X5(R)4X5(**)
4X8
5X7(**)
4X4(R)
3X4(**)
5X5
4X5
4X8
4X5
3X4(**)
5X5
5X7(**)
5X7(**)
3X8
5X7(**)
5X7(**)
4X5(**)
16'6"4 12'10"8 16'6"4
6'9"
6'9"
10'10"4
4'1"4
16'7"14
5'9"10
18'3"
1'7"2
18'7"8
4"8 22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'3"2
1'7"2 35'8"4
6'5"2
39'2"
3'5"12
45'11"
6'9"
2'11"
2'11"
6'9"
3'10"
16'4"8
9'7"8
18'7"8
2'3"
21'3"13
2'8"5
22'11"8
1'7"1124'7"3
1'7"11
27'3"8
2'8"527'8"12
5"4
29'6"8
1'9"12 39'2"
9'7"8
45'11"
6'9"1'6"8 1'6"8
4"53'2"11'
8'8"9'2"98'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Z -AC 7 -34
AA- S 1120 0AA-AB 0 -1037
S -AB 10 -294
J - P 206 -1485
P - K 433 -532K - O 696 -536
L - O 473 -411
Job Number:86460
Pujadas Res.
Truss Label:T01
Ply: 1
Qty:1
Wgt: 350.0 lbs
SEQN: 17450 / T74 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 29.85BC 75 0.15 29.85
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 557 /- /-/297 /101 /338
O 1841 /- /-/545 /261 /-
J*426 /- /-/51 /5 /-
J /-143
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
O Brg Width = 5.5 Min Req =2.2
J Brg Width = 32.3 Min Req =-
Bearings B, O, & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 55 -744
C - D 177 -799D - E 356 -118
Chords Tens.Comp.
E - F 72 -61
F - G 48 -794
G - H 48 -794H - I 66 -52
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 627 -335
P - O 240 -207
O - N 8 -180
N - M 24 -47
Chords Tens.Comp.
M - L 1063 0
L - K 18 -49
K - J 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 233 -412
P - D 699 -231D - O 280 -533
O - E 200 -1324
E - N 928 -1
F - Q 11 -327
F - T 814 -5
N - R 0 -827
Q - R 11 -363
Q - T 2 -10
R - M 1066 0
R - S 0 -1012
M - S 19 -272
Webs Tens.Comp.
S - U 0 -1042
G - T 2 -298T - V 4 -30
T - H 828 -5
U - L 10 -296
U - W 0 -1007
L - W 1086 0
V - W 33 -421
V - H 33 -385
W -K 13 -880
K - I 87 -144
I - J 143 -129
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.045 G 999 240
VERT(CL):0.081 G 999 180
HORZ(LL):0.013 F - -
HORZ(TL):0.027 F - -
Creep Factor: 2.0
Max TC CSI:0.544
Max BC CSI:0.577
Max Web CSI:0.626
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T02
Ply: 1
Qty:1
Wgt: 267.4 lbs
SEQN: 17447 / T29 / ATIC
FROM:DRW:
.../...04/15/2020
(a)
(a)
(a)
(a)(a)
(a)
10'1"2A
B
C
D
E
F G H
I
JKLMNOP
Q
R S
T
U
V
W
5 12
8
12
3X4(**)
4X8(**)
5X5(**)5X7(**)
4X5
4X8
4X4
3X4(**)
4X4
4X4
4X8
4X5
3X4(**)
4X5
4X8
4X5(**)
16'6"4 13'4"
6'9"
6'9"
10'2"12
3'5"12
16'8"
6'5"4
18'3"
1'7"
18'7"8
4"8 22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'10"4
2'2"4
6'9"
6'9"
16'4"8
9'7"8
18'7"8
2'3"
21'3"13
2'8"5
22'11"8
1'7"11 24'7"3
1'7"11
27'3"8
2'8"5 27'7"
3"8
29'10"4
2'3"4
1'6"8
4"5 9'4"93'2"18'8"9'2"98'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 29.85BC 75 0.15 29.85
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 557 /- /-/297 /101 /338
O 1841 /- /-/545 /261 /-
J*426 /- /-/51 /5 /-
J /-143
Wind reactions based on MWFRSBBrg Width = 5.5 Min Req =1.5
O Brg Width = 5.5 Min Req =2.2
J Brg Width = 32.3 Min Req =-
Bearings B, O, & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 55 -744
C - D 177 -799D - E 356 -118
Chords Tens.Comp.
E - F 72 -61
F - G 48 -794
G - H 48 -794H - I 66 -52
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 627 -335
P - O 240 -207
O - N 8 -180
N - M 24 -47
Chords Tens.Comp.
M - L 1063 0
L - K 18 -49
K - J 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 233 -412
P - D 699 -231D - O 280 -533
O - E 200 -1324
E - N 928 -1
F - Q 11 -327
F - T 814 -5
N - R 0 -827
Q - R 11 -363
Q - T 2 -10
R - M 1066 0
R - S 0 -1012
M - S 19 -272
Webs Tens.Comp.
S - U 0 -1042
G - T 2 -298T - V 4 -30
T - H 828 -5
U - L 10 -296
U - W 0 -1007
L - W 1086 0
V - W 33 -421
V - H 33 -385
W -K 13 -880
K - I 87 -144
I - J 143 -129
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.045 G 999 240
VERT(CL):0.081 G 999 180
HORZ(LL):0.013 F - -
HORZ(TL):0.027 F - -
Creep Factor: 2.0
Max TC CSI:0.544
Max BC CSI:0.577
Max Web CSI:0.626
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T02
Ply: 1
Qty:1
Wgt: 267.4 lbs
SEQN: 17447 / T29 / ATIC
FROM:DRW:
.../...04/15/2020
(a)
(a)
(a)
(a)(a)
(a)
10'1"2A
B
C
D
E
F G H
I
JKLMNOP
Q
R S
T
U
V
W
5 12
8
12
3X4(**)
4X8(**)
5X5(**)5X7(**)
4X5
4X8
4X4
3X4(**)
4X4
4X4
4X8
4X5
3X4(**)
4X5
4X8
4X5(**)
16'6"4 13'4"
6'9"
6'9"
10'2"12
3'5"12
16'8"
6'5"4
18'3"
1'7"
18'7"8
4"8 22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'10"4
2'2"4
6'9"
6'9"
16'4"8
9'7"8
18'7"8
2'3"
21'3"13
2'8"5
22'11"8
1'7"11 24'7"3
1'7"11
27'3"8
2'8"5 27'7"
3"8
29'10"4
2'3"4
1'6"8
4"5 9'4"93'2"18'8"9'2"98'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 29.73BC 75 0.15 29.73
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 614 /- /-/287 /98 /321
V*268 /- /-/52 /21 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
V Brg Width = 125 Min Req =-Bearings A & V Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 184 -1101
B - C 86 -632
C - D 117 -100
Chords Tens.Comp.
D - E 48 -761
E - F 48 -761
F - G 73 -11
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - N 958 -448
N - M 954 -448
M - L 911 -457
L - K 21 -47
Chords Tens.Comp.
K - J 51 -165
J - I 22 -21
I - H 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
N - B 186 0
B - M 255 -563
M - C 393 -91
C - L 331 -654
D - O 110 -475
D - R 821 0L - P 100 -556
O - P 110 -511
O - R 4 -24
P - K 36 -182
P - Q 200 -37
K - Q 0 -340
Webs Tens.Comp.
Q - S 144 -37
E - R 1 -291
R - T 12 -4
R - F 787 -7
S - J 4 -374
S - U 202 -37J - U 42 -218
T - U 31 -448
T - F 31 -412
U - I 23 -474
I - G 67 -87
G - H 65 -40
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.039 E 999 240
VERT(CL):0.067 E 999 180
HORZ(LL):-0.020 F - -
HORZ(TL):0.036 F - -
Creep Factor: 2.0
Max TC CSI:0.555
Max BC CSI:0.378
Max Web CSI:0.366
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T03
Ply: 1
Qty:1
Wgt: 247.8 lbs
SEQN: 17442 / T55 / ATIC
FROM:DRW:
.../...04/15/2020
(a)
(a)(a)
(a)
10'1"2
A
B
C
D E F
G
HIJKLMN
O
P Q
R
S
T
U
V
5 12
8
12
3X4(**)
5X7(**)
5X5(**)
4X8
5X7(**)
3X4(**)
4X4
4X8 3X4(**)
4X4
4X8
3X4(**)
27'2"4 2'6"8
6'9"
6'9"
11'10"12
5'1"12
18'3"
6'4"4
18'7"8
4"8
22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'8"12
2'0"12
6'7"4
6'7"4
11'7"4
5'
18'7"8
7'0"4
21'3"13
2'8"5
22'11"8
1'7"11 24'7"3
1'7"11
27'3"8
2'8"5
27'7"
3"8 29'8"12
2'1"12
4"5 9'5"93'2"18'8"9'2"98'0"129'4"121'4"10'10"12. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 29.73BC 75 0.15 29.73
Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 18-7-8 to 27-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 614 /- /-/287 /98 /321
V*268 /- /-/52 /21 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
V Brg Width = 125 Min Req =-Bearings A & V Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 184 -1101
B - C 86 -632
C - D 117 -100
Chords Tens.Comp.
D - E 48 -761
E - F 48 -761
F - G 73 -11
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - N 958 -448
N - M 954 -448
M - L 911 -457
L - K 21 -47
Chords Tens.Comp.
K - J 51 -165
J - I 22 -21
I - H 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
N - B 186 0
B - M 255 -563
M - C 393 -91
C - L 331 -654
D - O 110 -475
D - R 821 0L - P 100 -556
O - P 110 -511
O - R 4 -24
P - K 36 -182
P - Q 200 -37
K - Q 0 -340
Webs Tens.Comp.
Q - S 144 -37
E - R 1 -291
R - T 12 -4
R - F 787 -7
S - J 4 -374
S - U 202 -37J - U 42 -218
T - U 31 -448
T - F 31 -412
U - I 23 -474
I - G 67 -87
G - H 65 -40
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.039 E 999 240
VERT(CL):0.067 E 999 180
HORZ(LL):-0.020 F - -
HORZ(TL):0.036 F - -
Creep Factor: 2.0
Max TC CSI:0.555
Max BC CSI:0.378
Max Web CSI:0.366
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T03
Ply: 1
Qty:1
Wgt: 247.8 lbs
SEQN: 17442 / T55 / ATIC
FROM:DRW:
.../...04/15/2020
(a)
(a)(a)
(a)
10'1"2
A
B
C
D E F
G
HIJKLMN
O
P Q
R
S
T
U
V
5 12
8
12
3X4(**)
5X7(**)
5X5(**)
4X8
5X7(**)
3X4(**)
4X4
4X8 3X4(**)
4X4
4X8
3X4(**)
27'2"4 2'6"8
6'9"
6'9"
11'10"12
5'1"12
18'3"
6'4"4
18'7"8
4"8
22'11"8
4'4"
27'7"
4'7"8
27'8"
1"
29'8"12
2'0"12
6'7"4
6'7"4
11'7"4
5'
18'7"8
7'0"4
21'3"13
2'8"5
22'11"8
1'7"11 24'7"3
1'7"11
27'3"8
2'8"5
27'7"
3"8 29'8"12
2'1"12
4"5 9'5"93'2"18'8"9'2"98'0"129'4"121'4"10'10"1This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T6 2x6 SP 2400f-2.0E:
Bot chord 2x4 SP #1 :B3, B4 2x4 SP #2:Webs 2x4 SP #3 :W9, W15, W16 2x4 SP #2::W14 2x4 SP #1::W17 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioning
requirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.73
BC 36 0.15 31.73Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 20-7-8 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1362 /- /-/551 /382 /340
M 2336 /- /-/412 /358 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.6
M Brg Width = 3.5 Min Req =2.4Bearings B & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 621 -2490
C - D 624 -2543
D - E 744 -3049
E - F 480 -2061
Chords Tens.Comp.
F - G 214 -1034
G - H 350 -1388
H - I 350 -1388
I - J 51 -28
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - S 2241 -767
S - R 4473 -1291R - Q 2739 -786
Q - P 3591 -739
Chords Tens.Comp.
P - O 3882 -794
O - N 961 -17N - M 612 -2435
M - L 63 -370
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - S 957 -218
S - D 599 -2185
D - R 511 -1725
R - E 392 -66E - Q 393 -1244
Q - F 951 -198
Q - U 354 -1954
F - U 422 -1150
G - T 201 0
G - W 543 -183
T - U 193 -11
T - W 264 -51
U - P 171 0
U - O 750 -2780
U - V 0 -558
O - V 879 -216
Webs Tens.Comp.
V - N 602 -3243
V - X 2820 -683
H - W 116 -367
W -Y 38 -200W -I 903 -273
N - X 1103 -177
X - M 438 -3428
X - Z 6389 -1149
M - K 1044 -5761
Y - Z 2310 -383
Y - I 2314 -383
Z - M 1512 -283
Z - K 6332 -1140
I - K 493 -2825
K - J 62 -34
K - L 47 -93
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.17 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.486 G 722 281
VERT(CL):0.864 G 406 281
HORZ(LL):0.195 N - -
HORZ(TL):0.347 N - -
Creep Factor: 2.0
Max TC CSI:0.806
Max BC CSI:0.999
Max Web CSI:0.918
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T04
Ply: 1
Qty:1
Wgt: 302.4 lbs
SEQN: 17439 / T53 / ATIC
FROM:DRW:
.../...04/15/2020
T6
B3
B4
W9
W14
W15
W16
W17
(a)
(a)
(a)
(a)
(a)
(a)
10'1"2A
B
C D
E
F
G H I
J
K
LMNOPQRS
T
U V
W
X
Y
Z
5 12
8
12
4X5(**)
4X5(**)
3X8
6X6(**)
4X5
5X7(**)
6X8(**)
4X5
5X7(**)
3X4(**)
8X8
5X7(**)
6X6
4X8
5X7
6X6
3X4(**)
4X10
6X12(**)(I)
H1010(**)
10X12(**)(I)
29'7"2'1"12
1'11"8
1'11"8
3'11"8
2'8'9"
4'9"8
13'10"12
5'1"12
20'3"
6'4"4
20'7"8
4"8
24'11"8
4'4"
29'7"
4'7"8
29'8"
1"
31'8"12
2'0"12
8'5"8
8'5"8
13'9"
5'3"8
20'7"8
6'10"8
23'3"13
2'8"5
24'11"8
1'7"1126'3"11
1'4"3
26'7"3
3"8 29'3"8
2'8"5
31'8"12
2'5"41'6"8
4"5 9'5"91'2"13'2"18'8"9'2"99'2"98'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T6 2x6 SP 2400f-2.0E:
Bot chord 2x4 SP #1 :B3, B4 2x4 SP #2:Webs 2x4 SP #3 :W9, W15, W16 2x4 SP #2::W14 2x4 SP #1::W17 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioning
requirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.73
BC 36 0.15 31.73Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 20-7-8 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1362 /- /-/551 /382 /340
M 2336 /- /-/412 /358 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.6
M Brg Width = 3.5 Min Req =2.4Bearings B & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 621 -2490
C - D 624 -2543
D - E 744 -3049
E - F 480 -2061
Chords Tens.Comp.
F - G 214 -1034
G - H 350 -1388
H - I 350 -1388
I - J 51 -28
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - S 2241 -767
S - R 4473 -1291R - Q 2739 -786
Q - P 3591 -739
Chords Tens.Comp.
P - O 3882 -794
O - N 961 -17N - M 612 -2435
M - L 63 -370
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - S 957 -218
S - D 599 -2185
D - R 511 -1725
R - E 392 -66E - Q 393 -1244
Q - F 951 -198
Q - U 354 -1954
F - U 422 -1150
G - T 201 0
G - W 543 -183
T - U 193 -11
T - W 264 -51
U - P 171 0
U - O 750 -2780
U - V 0 -558
O - V 879 -216
Webs Tens.Comp.
V - N 602 -3243
V - X 2820 -683
H - W 116 -367
W -Y 38 -200W -I 903 -273
N - X 1103 -177
X - M 438 -3428
X - Z 6389 -1149
M - K 1044 -5761
Y - Z 2310 -383
Y - I 2314 -383
Z - M 1512 -283
Z - K 6332 -1140
I - K 493 -2825
K - J 62 -34
K - L 47 -93
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.17 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.486 G 722 281
VERT(CL):0.864 G 406 281
HORZ(LL):0.195 N - -
HORZ(TL):0.347 N - -
Creep Factor: 2.0
Max TC CSI:0.806
Max BC CSI:0.999
Max Web CSI:0.918
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T04
Ply: 1
Qty:1
Wgt: 302.4 lbs
SEQN: 17439 / T53 / ATIC
FROM:DRW:
.../...04/15/2020
T6
B3
B4
W9
W14
W15
W16
W17
(a)
(a)
(a)
(a)
(a)
(a)
10'1"2A
B
C D
E
F
G H I
J
K
LMNOPQRS
T
U V
W
X
Y
Z
5 12
8
12
4X5(**)
4X5(**)
3X8
6X6(**)
4X5
5X7(**)
6X8(**)
4X5
5X7(**)
3X4(**)
8X8
5X7(**)
6X6
4X8
5X7
6X6
3X4(**)
4X10
6X12(**)(I)
H1010(**)
10X12(**)(I)
29'7"2'1"12
1'11"8
1'11"8
3'11"8
2'8'9"
4'9"8
13'10"12
5'1"12
20'3"
6'4"4
20'7"8
4"8
24'11"8
4'4"
29'7"
4'7"8
29'8"
1"
31'8"12
2'0"12
8'5"8
8'5"8
13'9"
5'3"8
20'7"8
6'10"8
23'3"13
2'8"5
24'11"8
1'7"1126'3"11
1'4"3
26'7"3
3"8 29'3"8
2'8"5
31'8"12
2'5"41'6"8
4"5 9'5"91'2"13'2"18'8"9'2"99'2"98'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1::B3 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W12, W13, W14 2x4 SP #2::W16 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @11.50" o.c.
Webs : 1 Row @ 4" o.c.Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.73
BC 65 0.15 31.73Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of3900 # ( 123.12 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 3900 123.12 TC 0.00 31.73
3900 349.25 BC 14.33 25.50Case 2: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50Case 3: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50
Case 4: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1510 /- /-/1757 /1733 /338
M 2632 /- /-/900 /850 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
M Brg Width = 3.5 Min Req =1.5Bearings B & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 18 0
B - C 1938 -2066
C - D 1689 -1803
D - E 2312 -2468
E - F 1643 -1739
Chords Tens.Comp.
F - G 986 -1004
G - H 270 -538
H - I 329 -718
I - J 617 -717
J - K 132 -515
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 1856 -1857
T - S 2769 -2721S - R 3712 -1604
R - Q 3837 -1357
Q - P 2781 -1034
Chords Tens.Comp.
P - O 916 -709
O - N 793 -1693N - M 977 -4238
M - L 923 -4031
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - T 753 -691
T - D 1058 -1112
D - S 185 -282S - E 482 -128
S - U 1353 -1961
E - U 683 -1329
F - U 469 -430
U - R 56 -22
U - Q 482 -945
U - V 508 -2482
Q - V 616 -237
V - P 621 -1995
V - X 43 -572
G - W 1000 -1122
H - W 178 -162
H - Z 545 -546
W -Z 966 -1085
Webs Tens.Comp.
P - X 300 -108
X - Y 63 -549
Y - O 109 -559Y -AA 83 -491
O -AA 2736 -580
I - Z 85 -190
Z -AB 105 -261
Z - J 620 -763
AA- N 215 -1174
AA-AC 2480 -750
N -AC 2376 -351
AB-AC 237 -163
AB- J 238 -166
AC- M 380 -991
AC- K 1565 -334
AC- L 4376 -1002
K - L 407 -1799
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 0.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.619 F 567 281
VERT(CL):1.068 F 329 281
HORZ(LL):0.262 O - -
HORZ(TL):0.452 F - -
Creep Factor: 2.0
Max TC CSI:0.837
Max BC CSI:0.990
Max Web CSI:0.988
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T05
Ply: 2
Qty:1
Wgt: 599.2 lbs
SEQN: 17809 / T69 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T4
B2
B3
W12
W13
W14
W16
(a)
(a)
10'1"2A
B
C D
E
F
G
H I J
K
LMNOPQRST
U V
W
X Y
Z
AA
AB
AC
5 12
8
12
3X4(**)
5X5(**)
5X5(**)
5X5(**)
4X10
8X8(**)
6X8
5X7(**)
4X5
4X5
5X7(**)
4X5
5X7
3X8
5X7
4X10
3X4(**)
H0514(I)
5X7(**)
4X8
6X10(**)
29'7"2'1"12
3'11"8
3'11"8
5'11"8
2'
8'9"
2'9"8
15'11"
7'2"
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
29'8"
4"8
31'8"12
2'0"12
4'3"
4'3"
8'7"4
4'4"4
15'9"4
7'2"
18'4"5
2'7"1
20'4"12
2'0"7
21'1"2
8"6 24'1"6
3'0"5
24'11"
9"10 26'11"11
2'0"11
29'3"8
2'3"13
29'5"4
1"1231'8"12
2'3"81'6"8
4"5 9'5"92'0"13'2"113'4"8
9'2"96'0"128'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1::B3 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W12, W13, W14 2x4 SP #2::W16 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @11.50" o.c.
Webs : 1 Row @ 4" o.c.Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.73
BC 65 0.15 31.73Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of3900 # ( 123.12 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 3900 123.12 TC 0.00 31.73
3900 349.25 BC 14.33 25.50Case 2: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50Case 3: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50
Case 4: 3900 123.12 TC 0.00 31.733900 349.25 BC 14.33 25.50
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1510 /- /-/1757 /1733 /338
M 2632 /- /-/900 /850 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
M Brg Width = 3.5 Min Req =1.5Bearings B & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 18 0
B - C 1938 -2066
C - D 1689 -1803
D - E 2312 -2468
E - F 1643 -1739
Chords Tens.Comp.
F - G 986 -1004
G - H 270 -538
H - I 329 -718
I - J 617 -717
J - K 132 -515
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 1856 -1857
T - S 2769 -2721S - R 3712 -1604
R - Q 3837 -1357
Q - P 2781 -1034
Chords Tens.Comp.
P - O 916 -709
O - N 793 -1693N - M 977 -4238
M - L 923 -4031
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - T 753 -691
T - D 1058 -1112
D - S 185 -282S - E 482 -128
S - U 1353 -1961
E - U 683 -1329
F - U 469 -430
U - R 56 -22
U - Q 482 -945
U - V 508 -2482
Q - V 616 -237
V - P 621 -1995
V - X 43 -572
G - W 1000 -1122
H - W 178 -162
H - Z 545 -546
W -Z 966 -1085
Webs Tens.Comp.
P - X 300 -108
X - Y 63 -549
Y - O 109 -559Y -AA 83 -491
O -AA 2736 -580
I - Z 85 -190
Z -AB 105 -261
Z - J 620 -763
AA- N 215 -1174
AA-AC 2480 -750
N -AC 2376 -351
AB-AC 237 -163
AB- J 238 -166
AC- M 380 -991
AC- K 1565 -334
AC- L 4376 -1002
K - L 407 -1799
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 0.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.619 F 567 281
VERT(CL):1.068 F 329 281
HORZ(LL):0.262 O - -
HORZ(TL):0.452 F - -
Creep Factor: 2.0
Max TC CSI:0.837
Max BC CSI:0.990
Max Web CSI:0.988
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T05
Ply: 2
Qty:1
Wgt: 599.2 lbs
SEQN: 17809 / T69 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T4
B2
B3
W12
W13
W14
W16
(a)
(a)
10'1"2A
B
C D
E
F
G
H I J
K
LMNOPQRST
U V
W
X Y
Z
AA
AB
AC
5 12
8
12
3X4(**)
5X5(**)
5X5(**)
5X5(**)
4X10
8X8(**)
6X8
5X7(**)
4X5
4X5
5X7(**)
4X5
5X7
3X8
5X7
4X10
3X4(**)
H0514(I)
5X7(**)
4X8
6X10(**)
29'7"2'1"12
3'11"8
3'11"8
5'11"8
2'
8'9"
2'9"8
15'11"
7'2"
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
29'8"
4"8
31'8"12
2'0"12
4'3"
4'3"
8'7"4
4'4"4
15'9"4
7'2"
18'4"5
2'7"1
20'4"12
2'0"7
21'1"2
8"6 24'1"6
3'0"5
24'11"
9"10 26'11"11
2'0"11
29'3"8
2'3"13
29'5"4
1"1231'8"12
2'3"81'6"8
4"5 9'5"92'0"13'2"113'4"8
9'2"96'0"128'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
Negative reaction(s) of -1733# MAX. Requires upliftconnection. See Maximum Reactions.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Job Number:86460
Pujadas Res.
Truss Label:T05
Ply: 2
Qty:1
Wgt: 599.2 lbs
SEQN: 17809 / T69 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T3, T4 2x6 SP
2400f-2.0E:Bot chord 2x4 SP 2400f-2.0EWebs 2x4 SP #3 :W5, W14 2x4 SP #2::W10, W13 2x4 SP #1::W11, W16 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Plating Notes
All plates are 3X4 except as noted.
(**) 13 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.85BC 31 0.15 31.85Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
Negative reaction(s) of -544# MAX. from a non-windload case requires uplift connection. See MaximumReactions.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1093 /- /-/453 /105 /285
N 3309 /- /-/879 /274 /-
K 293 /-544 /-/95 /212 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5NBrg Width = 5.5 Min Req =3.1
K Brg Width = -Min Req =-
Bearings B & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 471 -2052
C - D 554 -2452
D - E 50 -579E - F 192 -589
Chords Tens.Comp.
F - G 453 -1080
G - H 525 -1134
H - I 524 -1131
I - J 121 -298
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 1836 -722
T - S 1833 -720
S - R 5647 -1696
R - Q 5889 -1766
Q - P 2972 -631
Chords Tens.Comp.
P - O 616 -1353
O - N 1707 -6455
N - M 1494 -5630
M - L 1143 -4057
L - K 1055 -3774
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - T 50 -70C - S 975 -184
S - D 37 -208
S - U 907 -3217
D - U 686 -2141
E - U 363 -489
U - R 126 -35
U - Q 1060 -2693
U - V 656 -3052
Q - V 1283 -461
V - P 1296 -4488
V - X 1471 -666
F - W 875 -352
G - W 46 -128
G - Z 141 -274W -Z 851 -342
Webs Tens.Comp.
Y - O 383 -1762Y -AA 1949 -783
O -AA 5288 -1130
H - Z 126 -276
Z -AC 110 -359
Z - I 1143 -477
AA- N 414 -2327
AA-AB 7790 -1996
N -AB 464 -2321
AB- M 639 -126
AB-AD 5758 -1575
M -AD 353 -1578
AC-AD 247 -577
AC- I 245 -574
AD- L 317 -20AD- J 1027 -332
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.19 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.664 E 466 247
VERT(CL):1.140 E 271 247
HORZ(LL):0.296 E - -
HORZ(TL):0.513 E - -
Creep Factor: 2.0
Max TC CSI:0.778
Max BC CSI:0.966
Max Web CSI:0.955
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T06
Ply: 1
Qty:1
Wgt: 307.3 lbs
SEQN: 17758 / T56 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T3
T4
W5
W10
W11
W13
W14
W16
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C D
E
F
G H I
J
KLMNOPQRST
U V
W
X Y
Z
AA AB
AC
AD
5 12
8
12
4X4(**)
5X7(**)
5X5(**)6X10(**)
8X8(**)
8X12(**)
6X10(**)
4X10
4X5
5X7(**)
4X10
3X8
6X10(**)
5X7
6X12
4X8
3X8
4X4
3X4(**)
8X12(**)
H1010(**)
4X4(R)
6X8(**)
25'8"12 6'1"8
5'11"8
5'11"8
8'3"1
2'3"9
15'11"
7'7"15
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
29'8"
4"8
31'10"4
2'2"4
6'1"4
6'1"4
8'1"5
2'0"1
15'9"4
7'7"15
18'1"2
2'3"14
18'6"2
5"20'4"12
1'10"10
20'5"4
0"820'8"8
3"4
23'2"2
2'5"1023'5"6
3"4
24'11"
1'5"1025'5"8
6"8
25'11"8
6"27'5"4
1'5"12
27'9"4
4"29'3"8
1'6"4
29'5"4
1"1231'10"4
2'5"1'6"8
4"5 9'4"92'10"113'4"8
9'2"96'0"128'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T3, T4 2x6 SP
2400f-2.0E:Bot chord 2x4 SP 2400f-2.0EWebs 2x4 SP #3 :W5, W14 2x4 SP #2::W10, W13 2x4 SP #1::W11, W16 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Plating Notes
All plates are 3X4 except as noted.
(**) 13 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.85BC 31 0.15 31.85Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
Negative reaction(s) of -544# MAX. from a non-windload case requires uplift connection. See MaximumReactions.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1093 /- /-/453 /105 /285
N 3309 /- /-/879 /274 /-
K 293 /-544 /-/95 /212 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5NBrg Width = 5.5 Min Req =3.1
K Brg Width = -Min Req =-
Bearings B & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 471 -2052
C - D 554 -2452
D - E 50 -579E - F 192 -589
Chords Tens.Comp.
F - G 453 -1080
G - H 525 -1134
H - I 524 -1131
I - J 121 -298
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 1836 -722
T - S 1833 -720
S - R 5647 -1696
R - Q 5889 -1766
Q - P 2972 -631
Chords Tens.Comp.
P - O 616 -1353
O - N 1707 -6455
N - M 1494 -5630
M - L 1143 -4057
L - K 1055 -3774
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - T 50 -70C - S 975 -184
S - D 37 -208
S - U 907 -3217
D - U 686 -2141
E - U 363 -489
U - R 126 -35
U - Q 1060 -2693
U - V 656 -3052
Q - V 1283 -461
V - P 1296 -4488
V - X 1471 -666
F - W 875 -352
G - W 46 -128
G - Z 141 -274W -Z 851 -342
Webs Tens.Comp.
Y - O 383 -1762Y -AA 1949 -783
O -AA 5288 -1130
H - Z 126 -276
Z -AC 110 -359
Z - I 1143 -477
AA- N 414 -2327
AA-AB 7790 -1996
N -AB 464 -2321
AB- M 639 -126
AB-AD 5758 -1575
M -AD 353 -1578
AC-AD 247 -577
AC- I 245 -574
AD- L 317 -20AD- J 1027 -332
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.19 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.664 E 466 247
VERT(CL):1.140 E 271 247
HORZ(LL):0.296 E - -
HORZ(TL):0.513 E - -
Creep Factor: 2.0
Max TC CSI:0.778
Max BC CSI:0.966
Max Web CSI:0.955
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T06
Ply: 1
Qty:1
Wgt: 307.3 lbs
SEQN: 17758 / T56 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T3
T4
W5
W10
W11
W13
W14
W16
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C D
E
F
G H I
J
KLMNOPQRST
U V
W
X Y
Z
AA AB
AC
AD
5 12
8
12
4X4(**)
5X7(**)
5X5(**)6X10(**)
8X8(**)
8X12(**)
6X10(**)
4X10
4X5
5X7(**)
4X10
3X8
6X10(**)
5X7
6X12
4X8
3X8
4X4
3X4(**)
8X12(**)
H1010(**)
4X4(R)
6X8(**)
25'8"12 6'1"8
5'11"8
5'11"8
8'3"1
2'3"9
15'11"
7'7"15
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
29'8"
4"8
31'10"4
2'2"4
6'1"4
6'1"4
8'1"5
2'0"1
15'9"4
7'7"15
18'1"2
2'3"14
18'6"2
5"20'4"12
1'10"10
20'5"4
0"820'8"8
3"4
23'2"2
2'5"1023'5"6
3"4
24'11"
1'5"1025'5"8
6"8
25'11"8
6"27'5"4
1'5"12
27'9"4
4"29'3"8
1'6"4
29'5"4
1"1231'10"4
2'5"1'6"8
4"5 9'4"92'10"113'4"8
9'2"96'0"128'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
P - X 1416 -400
X - Y 1684 -726
AD- K 3984 -1113
J - K 374 -1091
Job Number:86460
Pujadas Res.
Truss Label:T06
Ply: 1
Qty:1
Wgt: 307.3 lbs
SEQN: 17758 / T56 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W5 2x8 SP #1::W8 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 15.38
TC 24 15.59 25.51BC 120 0.15 25.51Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is7-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1605 /- /-/586 /120 /314
K 1421 /- /-/471 /251 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 31 0
B - C 286 -1362
C - D 246 -1051
D - E 87 -191
Chords Tens.Comp.
F - G 1133 -3768
G - H 635 -2159
H - I 625 -2127
I - J 14 -4
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1196 -398
P - O 4094 -1235
O - N 4979 -1559
Chords Tens.Comp.
N - M 3542 -1064
M - L 2127 -625
L - K 2068 -610
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 119 -364
P - D 1086 -275
P - F 958 -3285
D - F 337 -1217
E - F 49 -25
F - O 42 -164F - N 456 -1298
Webs Tens.Comp.
N - G 770 -236
G - M 481 -1549
M - H 229 -67
L - I 425 -114
I - K 664 -2252
J - K 36 -6
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.572 F 532 480
VERT(CL):0.800 F 380 360
HORZ(LL):0.254 E - -
HORZ(TL):0.356 E - -
Creep Factor: 2.0
Max TC CSI:0.810
Max BC CSI:0.937
Max Web CSI:0.779
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T07
Ply: 2
Qty:5
Wgt: 298.2 lbs
SEQN: 17555 / T57 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
W5
W8(a)
10'1"2A
B
C
D
E
F G H I J
KLMNOP
5 12
8
12
3X4(**)
3X4
6X10(**)
6X8(**)
5X7(**)
8X12(**)(I)
3X4 4X4
4X5
4X5
3X4
3X4
4X8 3X4
5X7
25'6"2
8'0"2
8'0"2
12'1"
4'0"14
15'7"8
3'6"8
18'3"4
2'7"12
20'5"13
2'2"8
23'0"5
2'6"8
25'6"2
2'5"12
11'11"4
11'11"4
15'7"6
3'8"2
17'11"12
2'4"6
20'4"1
2'4"4
22'10"1
2'6"
25'6"2
2'8"1'6"8
4"5 1'4"5'4"117'9"18'4"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W5 2x8 SP #1::W8 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 15.38
TC 24 15.59 25.51BC 120 0.15 25.51Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is7-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1605 /- /-/586 /120 /314
K 1421 /- /-/471 /251 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 31 0
B - C 286 -1362
C - D 246 -1051
D - E 87 -191
Chords Tens.Comp.
F - G 1133 -3768
G - H 635 -2159
H - I 625 -2127
I - J 14 -4
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1196 -398
P - O 4094 -1235
O - N 4979 -1559
Chords Tens.Comp.
N - M 3542 -1064
M - L 2127 -625
L - K 2068 -610
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 119 -364
P - D 1086 -275
P - F 958 -3285
D - F 337 -1217
E - F 49 -25
F - O 42 -164F - N 456 -1298
Webs Tens.Comp.
N - G 770 -236
G - M 481 -1549
M - H 229 -67
L - I 425 -114
I - K 664 -2252
J - K 36 -6
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.572 F 532 480
VERT(CL):0.800 F 380 360
HORZ(LL):0.254 E - -
HORZ(TL):0.356 E - -
Creep Factor: 2.0
Max TC CSI:0.810
Max BC CSI:0.937
Max Web CSI:0.779
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T07
Ply: 2
Qty:5
Wgt: 298.2 lbs
SEQN: 17555 / T57 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
W5
W8(a)
10'1"2A
B
C
D
E
F G H I J
KLMNOP
5 12
8
12
3X4(**)
3X4
6X10(**)
6X8(**)
5X7(**)
8X12(**)(I)
3X4 4X4
4X5
4X5
3X4
3X4
4X8 3X4
5X7
25'6"2
8'0"2
8'0"2
12'1"
4'0"14
15'7"8
3'6"8
18'3"4
2'7"12
20'5"13
2'2"8
23'0"5
2'6"8
25'6"2
2'5"12
11'11"4
11'11"4
15'7"6
3'8"2
17'11"12
2'4"6
20'4"1
2'4"4
22'10"1
2'6"
25'6"2
2'8"1'6"8
4"5 1'4"5'4"117'9"18'4"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP 2400f-2.0E :B1 2x4 SP #2:Webs 2x4 SP #3 :W5 2x8 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.Use equal spacing between rows and stagger nails
in each row to avoid splitting.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 15.38
TC 24 15.59 25.51BC 120 0.15 25.51Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is7-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1608 /- /-/585 /116 /314
K 1423 /- /-/476 /249 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 31 0
B - C 297 -1378
C - D 322 -1311
D - E 81 -263
Chords Tens.Comp.
F - G 1104 -3711
G - H 617 -2122
H - I 608 -2090
I - J 5 -1
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1207 -408
P - O 3679 -1081
O - N 4640 -1418
Chords Tens.Comp.
N - M 3526 -1048
M - L 2090 -608
L - K 2030 -592
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 280 -69
P - D 187 -87
P - F 684 -2400
D - F 335 -1258
E - F 64 -53
F - O 39 -78F - N 337 -999
Webs Tens.Comp.
N - G 652 -199
G - M 481 -1566
M - H 229 -65
L - I 439 -116
I - K 647 -2218
J - K 49 -10
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.593 F 513 480
VERT(CL):0.830 F 366 360
HORZ(LL):0.261 E - -
HORZ(TL):0.367 E - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.943
Max Web CSI:0.695
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T07A
Ply: 2
Qty:1
Wgt: 310.8 lbs
SEQN: 17558 / T63 / SPEC
FROM:DRW:
.../...04/15/2020
B1
W5
(a)
10'1"2A
B
C D
E
F G H I J
KLMNOP
5 12
8
12
3X4(**)
4X5(**)
6X10(**)
5X5(**)
5X7(**)
8X12(**)(I)
3X4 6X10(**)
4X5
4X5
3X4
3X4
4X8
3X4(**)
6X6(**)
25'6"2
7'11"8
7'11"8
9'6"1
1'6"9
15'7"8
6'1"7
18'3"12
2'8"4
20'6"13
2'3"
23'1"13
2'7"
25'6"2
2'4"4
9'4"5
9'4"5
15'7"6
6'3"1
18'0"4
2'4"14
20'5"1
2'4"12
22'11"9
2'6"8
25'6"2
2'6"81'6"8
4"5 1'4"3'8"17'9"18'4"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP 2400f-2.0E :B1 2x4 SP #2:Webs 2x4 SP #3 :W5 2x8 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.Use equal spacing between rows and stagger nails
in each row to avoid splitting.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 15.38
TC 24 15.59 25.51BC 120 0.15 25.51Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
The overall height of this truss excluding overhang is7-9-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1608 /- /-/585 /116 /314
K 1423 /- /-/476 /249 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 31 0
B - C 297 -1378
C - D 322 -1311
D - E 81 -263
Chords Tens.Comp.
F - G 1104 -3711
G - H 617 -2122
H - I 608 -2090
I - J 5 -1
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1207 -408
P - O 3679 -1081
O - N 4640 -1418
Chords Tens.Comp.
N - M 3526 -1048
M - L 2090 -608
L - K 2030 -592
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 280 -69
P - D 187 -87
P - F 684 -2400
D - F 335 -1258
E - F 64 -53
F - O 39 -78F - N 337 -999
Webs Tens.Comp.
N - G 652 -199
G - M 481 -1566
M - H 229 -65
L - I 439 -116
I - K 647 -2218
J - K 49 -10
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.593 F 513 480
VERT(CL):0.830 F 366 360
HORZ(LL):0.261 E - -
HORZ(TL):0.367 E - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.943
Max Web CSI:0.695
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T07A
Ply: 2
Qty:1
Wgt: 310.8 lbs
SEQN: 17558 / T63 / SPEC
FROM:DRW:
.../...04/15/2020
B1
W5
(a)
10'1"2A
B
C D
E
F G H I J
KLMNOP
5 12
8
12
3X4(**)
4X5(**)
6X10(**)
5X5(**)
5X7(**)
8X12(**)(I)
3X4 6X10(**)
4X5
4X5
3X4
3X4
4X8
3X4(**)
6X6(**)
25'6"2
7'11"8
7'11"8
9'6"1
1'6"9
15'7"8
6'1"7
18'3"12
2'8"4
20'6"13
2'3"
23'1"13
2'7"
25'6"2
2'4"4
9'4"5
9'4"5
15'7"6
6'3"1
18'0"4
2'4"14
20'5"1
2'4"12
22'11"9
2'6"8
25'6"2
2'6"81'6"8
4"5 1'4"3'8"17'9"18'4"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x6 SP
2400f-2.0E:Bot chord 2x6 SP 2400f-2.0E :B4 2x4 SP2400f-2.0E:Webs 2x4 SP #3 :W11, W15 2x4 SP #1::W13 2x6 SP #2::W16 2x4 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.85
BC 45 0.15 31.85Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AE 1166 /- /-/498 /119 /282
N 2768 /- /0 /671 /217 /-
K 392 /-107 /-/55 /123 /-
Wind reactions based on MWFRS
AE Brg Width = 5.5 Min Req =1.5NBrg Width = 3.5 Min Req =2.6
K Brg Width = -Min Req =-
Bearings AE & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 442 -2279
C - D 347 -1873
D - E 2 -620E - F 168 -638
Chords Tens.Comp.
F - G 461 -1008
G - H 490 -1032
H - I 489 -1030
I - J 127 -336
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 2055 -764
T - S 2054 -765
S - R 6079 -1923
R - Q 6219 -1966
Q - P 3763 -913
Chords Tens.Comp.
P - O 280 -268
O - N 2567 -9640
N - M 1183 -4408
M - L 748 -2630
L - K 688 -2454
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
T - C 171 0C - S 205 -416
S - D 1435 -438
S - U 1381 -4537
D - U 616 -1841
E - U 286 -271
U - R 261 -553
U - Q 932 -2077
U - V 928 -3876
Q - V 1634 -562
V - P 1278 -4332
V - X 619 -410
F - W 715 -398
G - W 56 -34
G - Z 63 -193W -Z 705 -387
Webs Tens.Comp.
Y - O 145 -825Y -AA 796 -454
O -AA 4865 -1071
H - Z 112 -139
Z - I 952 -460
Z -AC 106 -311
AA- N 411 -2160
AA-AB 6156 -1613
N -AB 331 -1897
AB- M 1189 -278
AB-AD 4451 -1257
M -AD 432 -1744
I -AC 327 -670
AC-AD 331 -715
AD- L 196 0AD- J 1335 -504
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.19 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.533 E 577 246
VERT(CL):0.905 E 340 246
HORZ(LL):0.235 N - -
HORZ(TL):0.399 N - -
Creep Factor: 2.0
Max TC CSI:0.669
Max BC CSI:0.976
Max Web CSI:0.968
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T08
Ply: 1
Qty:6
Wgt: 307.3 lbs
SEQN: 17735 / T64 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2 B4
W11
W13
W15
W16(a)
(a)
(a)(a)
10'1"2A
B
C
D
E
F
G H I J
KLMNOPQRST
U V
W
X Y
Z
AA AB
AC
AD
AE
5 12
8
12
4X5(A1T)
8X12(**)
8X8(**)
8X12(**)
8X12(**)
6X8(**)
4X4(**)
5X7(**)
4X10 6X10
4X8
6X12(**)
3X8
4X5
4X5
3X4(**)
8X12(**)
4X5(**)
6X6(**)(I)
25'9"12 6'0"8
6'5"14
6'5"14
12'1"
5'7"2
15'11"
3'10"
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
31'10"4
2'6"12
6'4"2
6'4"2
11'11"4
5'7"2
17'11"4
6'
20'4"12
2'5"8
20'5"12
1"23'6"2
3'0"6
24'11"
1'4"1426'0"8
1'1"8
27'9"12
1'9"4 29'3"8
1'5"12
31'10"4
2'6"12
1'6"8
4"5 10'10"15'4"1113'4"8
9'2"96'0"128'0"129'4"121'4"11'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x6 SP
2400f-2.0E:Bot chord 2x6 SP 2400f-2.0E :B4 2x4 SP2400f-2.0E:Webs 2x4 SP #3 :W11, W15 2x4 SP #1::W13 2x6 SP #2::W16 2x4 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 31.85
BC 45 0.15 31.85Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 29-3-8: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AE 1166 /- /-/498 /119 /282
N 2768 /- /0 /671 /217 /-
K 392 /-107 /-/55 /123 /-
Wind reactions based on MWFRS
AE Brg Width = 5.5 Min Req =1.5NBrg Width = 3.5 Min Req =2.6
K Brg Width = -Min Req =-
Bearings AE & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 442 -2279
C - D 347 -1873
D - E 2 -620E - F 168 -638
Chords Tens.Comp.
F - G 461 -1008
G - H 490 -1032
H - I 489 -1030
I - J 127 -336
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - T 2055 -764
T - S 2054 -765
S - R 6079 -1923
R - Q 6219 -1966
Q - P 3763 -913
Chords Tens.Comp.
P - O 280 -268
O - N 2567 -9640
N - M 1183 -4408
M - L 748 -2630
L - K 688 -2454
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
T - C 171 0C - S 205 -416
S - D 1435 -438
S - U 1381 -4537
D - U 616 -1841
E - U 286 -271
U - R 261 -553
U - Q 932 -2077
U - V 928 -3876
Q - V 1634 -562
V - P 1278 -4332
V - X 619 -410
F - W 715 -398
G - W 56 -34
G - Z 63 -193W -Z 705 -387
Webs Tens.Comp.
Y - O 145 -825Y -AA 796 -454
O -AA 4865 -1071
H - Z 112 -139
Z - I 952 -460
Z -AC 106 -311
AA- N 411 -2160
AA-AB 6156 -1613
N -AB 331 -1897
AB- M 1189 -278
AB-AD 4451 -1257
M -AD 432 -1744
I -AC 327 -670
AC-AD 331 -715
AD- L 196 0AD- J 1335 -504
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.19 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.533 E 577 246
VERT(CL):0.905 E 340 246
HORZ(LL):0.235 N - -
HORZ(TL):0.399 N - -
Creep Factor: 2.0
Max TC CSI:0.669
Max BC CSI:0.976
Max Web CSI:0.968
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T08
Ply: 1
Qty:6
Wgt: 307.3 lbs
SEQN: 17735 / T64 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2 B4
W11
W13
W15
W16(a)
(a)
(a)(a)
10'1"2A
B
C
D
E
F
G H I J
KLMNOPQRST
U V
W
X Y
Z
AA AB
AC
AD
AE
5 12
8
12
4X5(A1T)
8X12(**)
8X8(**)
8X12(**)
8X12(**)
6X8(**)
4X4(**)
5X7(**)
4X10 6X10
4X8
6X12(**)
3X8
4X5
4X5
3X4(**)
8X12(**)
4X5(**)
6X6(**)(I)
25'9"12 6'0"8
6'5"14
6'5"14
12'1"
5'7"2
15'11"
3'10"
20'3"
4'4"
24'11"
4'8"
29'3"8
4'4"8
31'10"4
2'6"12
6'4"2
6'4"2
11'11"4
5'7"2
17'11"4
6'
20'4"12
2'5"8
20'5"12
1"23'6"2
3'0"6
24'11"
1'4"1426'0"8
1'1"8
27'9"12
1'9"4 29'3"8
1'5"12
31'10"4
2'6"12
1'6"8
4"5 10'10"15'4"1113'4"8
9'2"96'0"128'0"129'4"121'4"11'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
P - X 350 -143
X - Y 672 -432
AD- K 2701 -757
J - K 471 -1209
Job Number:86460
Pujadas Res.
Truss Label:T08
Ply: 1
Qty:6
Wgt: 307.3 lbs
SEQN: 17735 / T64 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2, T3, T6 2x6 SP
2400f-2.0E::T5 2x6 SP #2:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2::B4 2x4 SP #1::B5 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W11, W15 2x4 SP #2::W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 13 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 51.51
BC 103 0.15 25.96BC 44 25.96 30.99BC 75 30.99 31.38BC 44 31.38 32.91BC 75 32.91 49.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 36-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AP 1849 /- /-/683 /183 /339
AH 2409 /- /-/434 /14 /-
N 1885 /- /-/702 /189 /-
Wind reactions based on MWFRS
AP Brg Width = 5.5 Min Req =2.2AHBrg Width = 5.5 Min Req =2.6
N Brg Width = 5.5 Min Req =1.8
Bearings AP, AH, & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 1182 -4006
C - D 1083 -3639
D - E 780 -2647E - F 751 -2097
F - G 242 -552
G - H 452 -400
Chords Tens.Comp.
H - I 496 -851
I - J 476 -158
J - K 192 -380
K - L 756 -2112L - M 718 -2603
M - N 1164 -4106
N - O 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AB 3648 -983
AB-AA 3647 -985
AA- Z 7340 -1731
Z - Y 7524 -1771
Y - X 5877 -1064
X - W 3322 -483
W -V 32 -5
Chords Tens.Comp.
U - T 4 -1
T - S 1818 -292
S - R 4283 -542
R - Q 6013 -1267
Q - P 5813 -1234
P - N 3741 -976
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AB- C 167 -6
C -AA 213 -369
AA- D 1362 -320
AA-AC 1096 -4567
D -AC 759 -2215
E -AC 847 -105
AC- Z 219 -640
AC- Y 620 -1338
AC-AD 956 -4891
Y -AD 1158 -356
AD- X 734 -2695AD-AE 1412 -2012
Webs Tens.Comp.
AH-AJ 2008 -311
AI- I 416 -98
AI-AM 298 -1450
U -AJ 32 0
AJ- T 1730 -273
AJ-AK 1641 -337
T -AK 127 -692
I -AM 448 -850
AK- S 2546 -561
AK-AL 856 -2644
S -AL 197 -856AL-AN 813 -2773
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 4.99 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.490 L 589 245
VERT(CL):1.048 L 275 245
HORZ(LL):-0.192 L - -
HORZ(TL):0.431 L - -
Creep Factor: 2.0
Max TC CSI:0.913
Max BC CSI:0.978
Max Web CSI:0.970
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T09
Ply: 1
Qty:1
Wgt: 408.1 lbs
SEQN: 17489 / T54 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T5
T6
B2
B3
B4 B5W11
W12
W15
(a)
(a)(a)
(a)
(a)
10'1"2
10'11"10
A
B
C
D
E
F G H I J K
L
M
N O
PQRSTUVWXYZAAAB
AC AD AE
AF
AG AH
AI
AJ AK AL
AM
AN AO
AP
5 12
8
12
4X4(**)4X4(**)
8X12(**)
8X8(**)
4X5
8X12(**)
4X5
4X8
6X6(**)
4X8
6X8
6X10(**)
3X4(**)
8X8(**)
3X8
8X12(**)
4X10
6X6(**)
H0514(**)
H0612
4X4
8X8(**)
5X5
3X8(B1T)(I)
25'8"12 24'2"4
6'5"14
6'5"14
12'1"
5'7"2
15'11"
3'10"
20'3"
4'4"
23'3"
3'
28'9"5
5'6"5
31'8"
2'10"11
36'1"12
4'5"12
43'2"
7'0"4
49'11"
6'9"
6'4"2
6'4"2
11'11"4
5'7"2
17'11"11
6'0"7
18'3"11
4"
20'3"6
1'11"1120'5"10
2"4
20'6"8
0"1422'9"13
2'3"5
23'0"1
2"425'5"12
2'5"11
25'11"12
6"28'5"5
2'5"9
30'10"6
2'5"1
31'1"10
3"431'4"8
2"14
33'7"11
2'3"333'11"
3"5
36'1"12
2'2"12 43'2"
7'0"4
49'11"
6'9"1'6"8 1'6"8
4"55'4"113'2"120'1"6'0"126'0"128'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2, T3, T6 2x6 SP
2400f-2.0E::T5 2x6 SP #2:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2::B4 2x4 SP #1::B5 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W11, W15 2x4 SP #2::W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 13 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 51.51
BC 103 0.15 25.96BC 44 25.96 30.99BC 75 30.99 31.38BC 44 31.38 32.91BC 75 32.91 49.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 36-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AP 1849 /- /-/683 /183 /339
AH 2409 /- /-/434 /14 /-
N 1885 /- /-/702 /189 /-
Wind reactions based on MWFRS
AP Brg Width = 5.5 Min Req =2.2AHBrg Width = 5.5 Min Req =2.6
N Brg Width = 5.5 Min Req =1.8
Bearings AP, AH, & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 1182 -4006
C - D 1083 -3639
D - E 780 -2647E - F 751 -2097
F - G 242 -552
G - H 452 -400
Chords Tens.Comp.
H - I 496 -851
I - J 476 -158
J - K 192 -380
K - L 756 -2112L - M 718 -2603
M - N 1164 -4106
N - O 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AB 3648 -983
AB-AA 3647 -985
AA- Z 7340 -1731
Z - Y 7524 -1771
Y - X 5877 -1064
X - W 3322 -483
W -V 32 -5
Chords Tens.Comp.
U - T 4 -1
T - S 1818 -292
S - R 4283 -542
R - Q 6013 -1267
Q - P 5813 -1234
P - N 3741 -976
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AB- C 167 -6
C -AA 213 -369
AA- D 1362 -320
AA-AC 1096 -4567
D -AC 759 -2215
E -AC 847 -105
AC- Z 219 -640
AC- Y 620 -1338
AC-AD 956 -4891
Y -AD 1158 -356
AD- X 734 -2695AD-AE 1412 -2012
Webs Tens.Comp.
AH-AJ 2008 -311
AI- I 416 -98
AI-AM 298 -1450
U -AJ 32 0
AJ- T 1730 -273
AJ-AK 1641 -337
T -AK 127 -692
I -AM 448 -850
AK- S 2546 -561
AK-AL 856 -2644
S -AL 197 -856AL-AN 813 -2773
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 4.99 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.490 L 589 245
VERT(CL):1.048 L 275 245
HORZ(LL):-0.192 L - -
HORZ(TL):0.431 L - -
Creep Factor: 2.0
Max TC CSI:0.913
Max BC CSI:0.978
Max Web CSI:0.970
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T09
Ply: 1
Qty:1
Wgt: 408.1 lbs
SEQN: 17489 / T54 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T5
T6
B2
B3
B4 B5W11
W12
W15
(a)
(a)(a)
(a)
(a)
10'1"2
10'11"10
A
B
C
D
E
F G H I J K
L
M
N O
PQRSTUVWXYZAAAB
AC AD AE
AF
AG AH
AI
AJ AK AL
AM
AN AO
AP
5 12
8
12
4X4(**)4X4(**)
8X12(**)
8X8(**)
4X5
8X12(**)
4X5
4X8
6X6(**)
4X8
6X8
6X10(**)
3X4(**)
8X8(**)
3X8
8X12(**)
4X10
6X6(**)
H0514(**)
H0612
4X4
8X8(**)
5X5
3X8(B1T)(I)
25'8"12 24'2"4
6'5"14
6'5"14
12'1"
5'7"2
15'11"
3'10"
20'3"
4'4"
23'3"
3'
28'9"5
5'6"5
31'8"
2'10"11
36'1"12
4'5"12
43'2"
7'0"4
49'11"
6'9"
6'4"2
6'4"2
11'11"4
5'7"2
17'11"11
6'0"7
18'3"11
4"
20'3"6
1'11"1120'5"10
2"4
20'6"8
0"1422'9"13
2'3"5
23'0"1
2"425'5"12
2'5"11
25'11"12
6"28'5"5
2'5"9
30'10"6
2'5"1
31'1"10
3"431'4"8
2"14
33'7"11
2'3"333'11"
3"5
36'1"12
2'2"12 43'2"
7'0"4
49'11"
6'9"1'6"8 1'6"8
4"55'4"113'2"120'1"6'0"126'0"128'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
F -AF 693 -2289
G -AF 714 -261X -AE 456 -134
AE-AG 1432 -1937
AF- H 409 -794
AF-AI 267 -1528AG- W 240 -560
AG-AH 1392 -1845
W -AH 3392 -486
H -AI 368 -145
AH- V 53 -167
AM- J 765 -287
AM- K 771 -2426AN- R 526 -202
AN-AO 800 -2877
R -AO 734 -1744
AO- Q 219 0AO- L 598 -61
AO- M 686 -1915
AO- P 999 -2469
M - P 369 -83
Job Number:86460
Pujadas Res.
Truss Label:T09
Ply: 1
Qty:1
Wgt: 408.1 lbs
SEQN: 17489 / T54 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3, T4, T7 2x6 SP
2400f-2.0E::T6 2x6 SP #2:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2::B4 2x4 SP #1::B5 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W12, W16 2x4 SP #2::W13 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 14 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 51.51
BC 106 0.15 25.96BC 45 25.96 30.99BC 75 30.99 31.38BC 45 31.38 32.91BC 75 32.91 49.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 36-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AQ 1868 /- /-/670 /164 /341
AI 2433 /- /-/439 /10 /-
O 1902 /- /-/702 /189 /-
Wind reactions based on MWFRS
AQ Brg Width = 5.5 Min Req =2.2AIBrg Width = 5.5 Min Req =2.6
O Brg Width = 5.5 Min Req =1.8
Bearings AQ, AI, & O Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 1196 -4043
C - D 1184 -3844
D - E 1176 -4127E - F 800 -2723
F - G 745 -2131
G - H 245 -564
H - I 458 -399
Chords Tens.Comp.
I - J 501 -820
J - K 483 -147
K - L 200 -385
L - M 746 -2147M - N 704 -2635
N - O 1157 -4147
O - P 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AC 3683 -981
AC-AB 4967 -1306
AB-AA 7458 -1630
AA- Z 7646 -1668
Z - Y 5938 -991
Y - X 3336 -460
X - W 32 -5
Chords Tens.Comp.
V - U 4 -1
U - T 1810 -306
T - S 4306 -545
S - R 6066 -1282
R - Q 5865 -1248
Q - O 3780 -970
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C -AC 1364 -324
AC- D 490 -1764
D -AB 626 -1788
AB- E 2061 -542
AB-AD 1041 -4514
E -AD 727 -2348
F -AD 904 -130
AD-AA 201 -634
AD- Z 596 -1393
AD-AE 907 -4932Z -AE 1180 -337
Webs Tens.Comp.
AI- W 52 -171
AI-AK 2035 -305
AJ- J 270 -245
AJ-AN 286 -1373
V -AK 32 0
AK- U 1722 -286
AK-AL 1681 -325
U -AL 131 -689
J -AN 444 -970
AL- T 2577 -571AL-AM 860 -2632
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 4.99 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.489 F 628 245
VERT(CL):1.055 M 273 245
HORZ(LL):-0.189 M - -
HORZ(TL):0.430 M - -
Creep Factor: 2.0
Max TC CSI:0.935
Max BC CSI:0.985
Max Web CSI:0.982
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T10
Ply: 1
Qty:1
Wgt: 413.7 lbs
SEQN: 17495 / T65 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T3
T4 T6
T7
B2
B3
B4 B5W12W13
W16
(a)
(a)(a)
(a)
(a)
10'1"2
10'11"10
A B
C D
E
F
G H I J K L
M
N
O P
QRSTUVWXYZAAABAC
AD AE AF
AG
AH AI
AJ
AK AL AM
AN
AO AP
AQ
5 12
8
12
4X4(**)4X4(**)
5X7(**)
4X5(R)
8X8(**)
8X12(**)
6X8
3X8
8X12(**)
4X5
4X8
6X6(**)
4X8
6X8
6X12(**)
3X4(**)
8X8(**)
3X8
8X12(**)
H0510
6X6(**)
H0514(**)
H0612
4X4
8X8(**)
5X5
3X8(B1T)(I)
25'8"12 24'2"4
5'11"8
5'11"8
8'3"1
2'3"9
12'1"
3'9"15
15'11"
3'10"
20'3"
4'4"
23'3"
3'
28'9"5
5'6"5
31'8"
2'10"11
36'1"12
4'5"12
43'2"
7'0"4
49'11"
6'9"
6'3"
6'3"
11'11"4
5'8"4
17'11"11
6'0"7
18'3"11
4"
20'3"6
1'11"1120'5"10
2"4
20'6"8
0"1422'9"13
2'3"5
23'0"1
2"424'11"12
1'11"11
25'5"12
6"25'11"12
6"
28'5"5
2'5"9 30'10"2
2'4"13
31'1"10
3"831'4"8
2"14
33'7"11
2'3"333'11"
3"5
36'1"12
2'2"12 43'2"
7'0"4
49'11"
6'9"1'6"8 1'6"8
4"5
2'10"1 3'2"120'1"7'1"47'1"49'1"49'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3, T4, T7 2x6 SP
2400f-2.0E::T6 2x6 SP #2:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2::B4 2x4 SP #1::B5 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W12, W16 2x4 SP #2::W13 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 14 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 51.51
BC 106 0.15 25.96BC 45 25.96 30.99BC 75 30.99 31.38BC 45 31.38 32.91BC 75 32.91 49.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 36-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AQ 1868 /- /-/670 /164 /341
AI 2433 /- /-/439 /10 /-
O 1902 /- /-/702 /189 /-
Wind reactions based on MWFRS
AQ Brg Width = 5.5 Min Req =2.2AIBrg Width = 5.5 Min Req =2.6
O Brg Width = 5.5 Min Req =1.8
Bearings AQ, AI, & O Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 1196 -4043
C - D 1184 -3844
D - E 1176 -4127E - F 800 -2723
F - G 745 -2131
G - H 245 -564
H - I 458 -399
Chords Tens.Comp.
I - J 501 -820
J - K 483 -147
K - L 200 -385
L - M 746 -2147M - N 704 -2635
N - O 1157 -4147
O - P 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B -AC 3683 -981
AC-AB 4967 -1306
AB-AA 7458 -1630
AA- Z 7646 -1668
Z - Y 5938 -991
Y - X 3336 -460
X - W 32 -5
Chords Tens.Comp.
V - U 4 -1
U - T 1810 -306
T - S 4306 -545
S - R 6066 -1282
R - Q 5865 -1248
Q - O 3780 -970
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C -AC 1364 -324
AC- D 490 -1764
D -AB 626 -1788
AB- E 2061 -542
AB-AD 1041 -4514
E -AD 727 -2348
F -AD 904 -130
AD-AA 201 -634
AD- Z 596 -1393
AD-AE 907 -4932Z -AE 1180 -337
Webs Tens.Comp.
AI- W 52 -171
AI-AK 2035 -305
AJ- J 270 -245
AJ-AN 286 -1373
V -AK 32 0
AK- U 1722 -286
AK-AL 1681 -325
U -AL 131 -689
J -AN 444 -970
AL- T 2577 -571AL-AM 860 -2632
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 4.99 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.489 F 628 245
VERT(CL):1.055 M 273 245
HORZ(LL):-0.189 M - -
HORZ(TL):0.430 M - -
Creep Factor: 2.0
Max TC CSI:0.935
Max BC CSI:0.985
Max Web CSI:0.982
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T10
Ply: 1
Qty:1
Wgt: 413.7 lbs
SEQN: 17495 / T65 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T3
T4 T6
T7
B2
B3
B4 B5W12W13
W16
(a)
(a)(a)
(a)
(a)
10'1"2
10'11"10
A B
C D
E
F
G H I J K L
M
N
O P
QRSTUVWXYZAAABAC
AD AE AF
AG
AH AI
AJ
AK AL AM
AN
AO AP
AQ
5 12
8
12
4X4(**)4X4(**)
5X7(**)
4X5(R)
8X8(**)
8X12(**)
6X8
3X8
8X12(**)
4X5
4X8
6X6(**)
4X8
6X8
6X12(**)
3X4(**)
8X8(**)
3X8
8X12(**)
H0510
6X6(**)
H0514(**)
H0612
4X4
8X8(**)
5X5
3X8(B1T)(I)
25'8"12 24'2"4
5'11"8
5'11"8
8'3"1
2'3"9
12'1"
3'9"15
15'11"
3'10"
20'3"
4'4"
23'3"
3'
28'9"5
5'6"5
31'8"
2'10"11
36'1"12
4'5"12
43'2"
7'0"4
49'11"
6'9"
6'3"
6'3"
11'11"4
5'8"4
17'11"11
6'0"7
18'3"11
4"
20'3"6
1'11"1120'5"10
2"4
20'6"8
0"1422'9"13
2'3"5
23'0"1
2"424'11"12
1'11"11
25'5"12
6"25'11"12
6"
28'5"5
2'5"9 30'10"2
2'4"13
31'1"10
3"831'4"8
2"14
33'7"11
2'3"333'11"
3"5
36'1"12
2'2"12 43'2"
7'0"4
49'11"
6'9"1'6"8 1'6"8
4"5
2'10"1 3'2"120'1"7'1"47'1"49'1"49'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
AE- Y 700 -2745
AE-AF 1427 -1999G -AG 682 -2311
H -AG 672 -259
Y -AF 465 -127
AF-AH 1448 -1922AG- I 409 -911
AG-AJ 250 -1458
AH- X 243 -554
AH-AI 1408 -1831
X -AI 3407 -463
I -AJ 220 -293
T -AM 200 -866
AM-AO 815 -2762AN- K 725 -283
AN- L 745 -2443
AO- S 535 -206
AO-AP 800 -2867S -AP 746 -1775
AP- R 222 0
AP- M 592 -60
AP- N 687 -1926
AP- Q 972 -2476
N - Q 369 -80
Job Number:86460
Pujadas Res.
Truss Label:T10
Ply: 1
Qty:1
Wgt: 413.7 lbs
SEQN: 17495 / T65 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4, T5 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 23.71BC 75 0.15 20.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 19-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 843 /- /-/362 /39 /347
K 1597 /- /-/589 /278 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.9Bearings B & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 91 -1512
C - D 92 -1429
D - E 3 -1558
Chords Tens.Comp.
E - F 0 -1045
F - G 104 -362
G - H 175 -365
H - I 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1356 -570
P - O 1833 -546
O - N 1393 -408
Chords Tens.Comp.
N - M 3289 -755
M - L 3361 -771
L - K 12 -48
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 435 0
P - D 13 -592
D - O 185 -495
O - E 312 -80
E - N 194 -703
N - F 1170 -241N - Q 515 -2526
F - Q 388 -1268
G - Q 56 -159
Webs Tens.Comp.
Q - M 92 -28
Q - L 469 -1655
Q - R 341 -1851
L - J 2046 -381
R - L 112 -86
R - J 341 -1852J - H 578 -549
J - K 668 -1431
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.50 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.139 G 999 240
VERT(CL):0.261 G 915 191
HORZ(LL):-0.055 H - -
HORZ(TL):0.103 H - -
Creep Factor: 2.0
Max TC CSI:0.489
Max BC CSI:0.733
Max Web CSI:0.836
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T11
Ply: 1
Qty:1
Wgt: 171.5 lbs
SEQN: 17699 / T60 / COMN
FROM:DRW:
.../...04/15/2020
T4
T5
B2
(a)
10'1"2A
B
C D
E
F
G
H
I
J
KLMNOP
Q R
5 12
8
12
3X4(**)
4X4(**)
3X4
4X5(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8
3X4
3X4
H0510
6X6(**)
3X4(**)
3X8(**)
20'0"8
3'11"8
3'11"8
5'11"8
2'
8'9"
2'9"8
12'3"7
3'6"7
15'11"
3'7"9
20'0"8
4'1"8
4'3"
4'3"
8'5"8
4'2"8
12'2"4
3'8"12
15'9"4
3'7"
17'10"
2'0"12
20'0"8
2'2"81'6"8
4"5 10'8"62'0"13'2"113'1"1113'8"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4, T5 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 23.71BC 75 0.15 20.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 19-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 843 /- /-/362 /39 /347
K 1597 /- /-/589 /278 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.9Bearings B & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 91 -1512
C - D 92 -1429
D - E 3 -1558
Chords Tens.Comp.
E - F 0 -1045
F - G 104 -362
G - H 175 -365
H - I 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1356 -570
P - O 1833 -546
O - N 1393 -408
Chords Tens.Comp.
N - M 3289 -755
M - L 3361 -771
L - K 12 -48
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 435 0
P - D 13 -592
D - O 185 -495
O - E 312 -80
E - N 194 -703
N - F 1170 -241N - Q 515 -2526
F - Q 388 -1268
G - Q 56 -159
Webs Tens.Comp.
Q - M 92 -28
Q - L 469 -1655
Q - R 341 -1851
L - J 2046 -381
R - L 112 -86
R - J 341 -1852J - H 578 -549
J - K 668 -1431
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.50 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.139 G 999 240
VERT(CL):0.261 G 915 191
HORZ(LL):-0.055 H - -
HORZ(TL):0.103 H - -
Creep Factor: 2.0
Max TC CSI:0.489
Max BC CSI:0.733
Max Web CSI:0.836
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T11
Ply: 1
Qty:1
Wgt: 171.5 lbs
SEQN: 17699 / T60 / COMN
FROM:DRW:
.../...04/15/2020
T4
T5
B2
(a)
10'1"2A
B
C D
E
F
G
H
I
J
KLMNOP
Q R
5 12
8
12
3X4(**)
4X4(**)
3X4
4X5(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8
3X4
3X4
H0510
6X6(**)
3X4(**)
3X8(**)
20'0"8
3'11"8
3'11"8
5'11"8
2'
8'9"
2'9"8
12'3"7
3'6"7
15'11"
3'7"9
20'0"8
4'1"8
4'3"
4'3"
8'5"8
4'2"8
12'2"4
3'8"12
15'9"4
3'7"
17'10"
2'0"12
20'0"8
2'2"81'6"8
4"5 10'8"62'0"13'2"113'1"1113'8"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4, T5 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 23.71BC 75 0.15 20.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 19-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 919 /- /- /-/298 /-
K 1605 /- /- /-/345 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.9Bearings B & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -18
B - C 428 -1637
C - D 420 -1653
D - E 441 -1648
Chords Tens.Comp.
E - F 268 -1070
F - G 46 -134
G - H 175 -83
H - I 59 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1476 -378
P - O 2709 -776
O - N 1459 -383
Chords Tens.Comp.
N - M 3322 -566
M - L 3394 -577
L - K 9 -49
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 560 -134
P - D 399 -1221
D - O 395 -1242
O - E 296 -46
E - N 235 -779
N - F 1215 -233N - Q 378 -2551
F - Q 302 -1279
G - Q 56 -133
Webs Tens.Comp.
Q - M 94 0
Q - L 355 -1675
Q - R 253 -1865
L - J 2062 -283
R - L 97 -86
R - J 253 -1866J - H 225 -549
J - K 349 -1438
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.45 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.155 N 999 240
VERT(CL):0.292 N 818 191
HORZ(LL):-0.076 H - -
HORZ(TL):0.143 H - -
Creep Factor: 2.0
Max TC CSI:0.561
Max BC CSI:0.812
Max Web CSI:0.845
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T12
Ply: 1
Qty:1
Wgt: 168.7 lbs
SEQN: 17705 / T62 / COMN
FROM:DRW:
.../...04/15/2020
T4
T5
B2
(a)
10'1"2A
B
C D
E
F
G
H
I
J
KLMNOP
Q R512
8
12
3X4(**)
4X4(**)
4X4
5X5(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8(**)
3X4
3X4
H0510
6X6(**)
3X4(**)
4X5(**)
20'0"8
1'11"8
1'11"8
3'11"8
2'
8'9"
4'9"8
12'3"7
3'6"7
15'11"
3'7"9
20'0"8
4'1"8
8'5"8
8'5"8
12'2"4
3'8"12
15'9"4
3'7"
17'10"
2'0"12
20'0"8
2'2"81'6"8
4"5 10'8"61'2"13'2"113'1"1113'8"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4, T5 2x6 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 23.71BC 75 0.15 20.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 15-11-0 to 19-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 919 /- /- /-/298 /-
K 1605 /- /- /-/345 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.9Bearings B & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -18
B - C 428 -1637
C - D 420 -1653
D - E 441 -1648
Chords Tens.Comp.
E - F 268 -1070
F - G 46 -134
G - H 175 -83
H - I 59 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - P 1476 -378
P - O 2709 -776
O - N 1459 -383
Chords Tens.Comp.
N - M 3322 -566
M - L 3394 -577
L - K 9 -49
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - P 560 -134
P - D 399 -1221
D - O 395 -1242
O - E 296 -46
E - N 235 -779
N - F 1215 -233N - Q 378 -2551
F - Q 302 -1279
G - Q 56 -133
Webs Tens.Comp.
Q - M 94 0
Q - L 355 -1675
Q - R 253 -1865
L - J 2062 -283
R - L 97 -86
R - J 253 -1866J - H 225 -549
J - K 349 -1438
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.45 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.155 N 999 240
VERT(CL):0.292 N 818 191
HORZ(LL):-0.076 H - -
HORZ(TL):0.143 H - -
Creep Factor: 2.0
Max TC CSI:0.561
Max BC CSI:0.812
Max Web CSI:0.845
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T12
Ply: 1
Qty:1
Wgt: 168.7 lbs
SEQN: 17705 / T62 / COMN
FROM:DRW:
.../...04/15/2020
T4
T5
B2
(a)
10'1"2A
B
C D
E
F
G
H
I
J
KLMNOP
Q R512
8
12
3X4(**)
4X4(**)
4X4
5X5(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8(**)
3X4
3X4
H0510
6X6(**)
3X4(**)
4X5(**)
20'0"8
1'11"8
1'11"8
3'11"8
2'
8'9"
4'9"8
12'3"7
3'6"7
15'11"
3'7"9
20'0"8
4'1"8
8'5"8
8'5"8
12'2"4
3'8"12
15'9"4
3'7"
17'10"
2'0"12
20'0"8
2'2"81'6"8
4"5 10'8"61'2"13'2"113'1"1113'8"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP #2 :T4 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 8 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 21.71BC 31 0.00 18.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of3500 # ( 196.73 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.
Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 2: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 3: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 4: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-11-0 to 17-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
O 665 /- /-/1892 /1752 /335
H 1525 /- /-/569 /279 /-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =2.2
H Brg Width = 5.5 Min Req =1.8Bearings O & H Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 4254 -4625
B - C 2863 -3158
C - D 1984 -2102
Chords Tens.Comp.
D - E 1118 -1185
E - F 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - L 4268 -4244
L - K 4269 -4247
K - J 4021 -3991
Chords Tens.Comp.
J - I 2684 -2402
I - H 771 -778
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
L - B 155 -15
B - K 525 -546
K - C 905 -435
K - M 481 -2010
C - M 505 -1018
D - M 149 -130
M - J 99 -49
Webs Tens.Comp.
M - I 436 -1258
M - N 317 -1536
I - G 1699 -376
N - I 86 -94
N - G 317 -1537
G - E 580 -545
G - H 664 -1360
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.84 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.222 B 967 240
VERT(CL):0.202 D 999 180
HORZ(LL):-0.113 E - -
HORZ(TL):0.117 E - -
Creep Factor: 2.0
Max TC CSI:0.649
Max BC CSI:0.991
Max Web CSI:0.769
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T13
Ply: 1
Qty:1
Wgt: 154.7 lbs
SEQN: 17717 / T59 / COMN
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T4
(a)
10'1"2
A
B
C
D
E
F
G
HIJKL
M N
O
5 12
8 12
4X8(**)H0510(**)
H0612(**)
6X8(**)
8X8(**)
3X4
4X10
3X4
3X4
6X8(**)
5X5
3X4(**)
3X8(**)
18'0"8
6'9"
6'9"
10'3"7
3'6"7
13'11"
3'7"9
18'0"8
4'1"8
6'7"4
6'7"4
10'2"4
3'7"
13'9"4
3'7"
15'10"
2'0"12
18'0"8
2'2"8
4"5 10'8"63'2"113'1"112. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP #2 :T4 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 8 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 21.71BC 31 0.00 18.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of3500 # ( 196.73 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.
Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 2: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 3: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58Case 4: 3500 196.73 TC 0.15 18.043500 454.05 BC 9.88 17.58
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-11-0 to 17-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
O 665 /- /-/1892 /1752 /335
H 1525 /- /-/569 /279 /-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =2.2
H Brg Width = 5.5 Min Req =1.8Bearings O & H Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 4254 -4625
B - C 2863 -3158
C - D 1984 -2102
Chords Tens.Comp.
D - E 1118 -1185
E - F 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - L 4268 -4244
L - K 4269 -4247
K - J 4021 -3991
Chords Tens.Comp.
J - I 2684 -2402
I - H 771 -778
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
L - B 155 -15
B - K 525 -546
K - C 905 -435
K - M 481 -2010
C - M 505 -1018
D - M 149 -130
M - J 99 -49
Webs Tens.Comp.
M - I 436 -1258
M - N 317 -1536
I - G 1699 -376
N - I 86 -94
N - G 317 -1537
G - E 580 -545
G - H 664 -1360
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.84 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.222 B 967 240
VERT(CL):0.202 D 999 180
HORZ(LL):-0.113 E - -
HORZ(TL):0.117 E - -
Creep Factor: 2.0
Max TC CSI:0.649
Max BC CSI:0.991
Max Web CSI:0.769
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T13
Ply: 1
Qty:1
Wgt: 154.7 lbs
SEQN: 17717 / T59 / COMN
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T4
(a)
10'1"2
A
B
C
D
E
F
G
HIJKL
M N
O
5 12
8 12
4X8(**)H0510(**)
H0612(**)
6X8(**)
8X8(**)
3X4
4X10
3X4
3X4
6X8(**)
5X5
3X4(**)
3X8(**)
18'0"8
6'9"
6'9"
10'3"7
3'6"7
13'11"
3'7"9
18'0"8
4'1"8
6'7"4
6'7"4
10'2"4
3'7"
13'9"4
3'7"
15'10"
2'0"12
18'0"8
2'2"8
4"5 10'8"63'2"113'1"11This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Additional Notes
Negative reaction(s) of -1752# MAX. Requires upliftconnection. See Maximum Reactions.
Top chord overhangs have been checked only forloads as indicated. Overhangs not checked for manloads or long-term deflection.
The overall height of this truss excluding overhang is13-1-11.
Job Number:86460
Pujadas Res.
Truss Label:T13
Ply: 1
Qty:1
Wgt: 154.7 lbs
SEQN: 17717 / T59 / COMN
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2, T3 2x6 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 21.71BC 75 0.15 18.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-11-0 to 17-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 788 /- /-/337 /-/348
I 1525 /- /-/564 /275 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
I Brg Width = 5.5 Min Req =1.8Bearings B & I Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 0 -1306
C - D 0 -923
Chords Tens.Comp.
D - E 106 -366
E - F 173 -364
F - G 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - M 1153 -315
M - L 1150 -317
L - K 2984 -644
Chords Tens.Comp.
K - J 3053 -659
J - I 11 -46
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
M - C 162 0
C - L 178 -550
L - D 1006 -188
L - N 447 -2338
D - N 319 -1079
E - N 53 -171
N - K 99 -17
Webs Tens.Comp.
N - J 403 -1474
N - O 289 -1707
J - H 1890 -325
O - J 98 -95
O - H 289 -1708
H - F 577 -545
H - I 657 -1360
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.50 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.121 E 999 240
VERT(CL):0.229 E 939 180
HORZ(LL):0.050 E - -
HORZ(TL):0.095 E - -
Creep Factor: 2.0
Max TC CSI:0.489
Max BC CSI:0.937
Max Web CSI:0.769
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T14
Ply: 1
Qty:4
Wgt: 151.9 lbs
SEQN: 17696 / T21 / COMN
FROM:DRW:
.../...04/15/2020
T2
T3
(a)
10'1"2A
B
C
D
E
F
G
H
IJKLM
N O
5 12
8 12
3X4(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8
3X4
3X4
H0510
5X5
3X4(**)
3X8(**)
18'0"8
6'9"
6'9"
10'3"7
3'6"7
13'11"
3'7"9
18'0"8
4'1"8
6'7"4
6'7"4
10'2"4
3'7"
13'9"4
3'7"
15'10"
2'0"12
18'0"8
2'2"81'6"8
4"5 10'8"63'2"113'1"1113'8"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2, T3 2x6 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 21.71BC 75 0.15 18.04Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-11-0 to 17-9-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is13-1-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 788 /- /-/337 /-/348
I 1525 /- /-/564 /275 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
I Brg Width = 5.5 Min Req =1.8Bearings B & I Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 0 -1306
C - D 0 -923
Chords Tens.Comp.
D - E 106 -366
E - F 173 -364
F - G 0 -125
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - M 1153 -315
M - L 1150 -317
L - K 2984 -644
Chords Tens.Comp.
K - J 3053 -659
J - I 11 -46
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
M - C 162 0
C - L 178 -550
L - D 1006 -188
L - N 447 -2338
D - N 319 -1079
E - N 53 -171
N - K 99 -17
Webs Tens.Comp.
N - J 403 -1474
N - O 289 -1707
J - H 1890 -325
O - J 98 -95
O - H 289 -1708
H - F 577 -545
H - I 657 -1360
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.50 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.121 E 999 240
VERT(CL):0.229 E 939 180
HORZ(LL):0.050 E - -
HORZ(TL):0.095 E - -
Creep Factor: 2.0
Max TC CSI:0.489
Max BC CSI:0.937
Max Web CSI:0.769
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T14
Ply: 1
Qty:4
Wgt: 151.9 lbs
SEQN: 17696 / T21 / COMN
FROM:DRW:
.../...04/15/2020
T2
T3
(a)
10'1"2A
B
C
D
E
F
G
H
IJKLM
N O
5 12
8 12
3X4(**)
5X5(**)
8X8(**)
6X8(**)
8X8(**)
3X4
6X8
3X4
3X4
H0510
5X5
3X4(**)
3X8(**)
18'0"8
6'9"
6'9"
10'3"7
3'6"7
13'11"
3'7"9
18'0"8
4'1"8
6'7"4
6'7"4
10'2"4
3'7"
13'9"4
3'7"
15'10"
2'0"12
18'0"8
2'2"81'6"8
4"5 10'8"63'2"113'1"1113'8"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x6 SP #2:
:T3 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W9 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 49.51
BC 44 0.15 47.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Attic room loading from 13-11-0 to 34-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be taken
during handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1579 /- /-/606 /166 /338
S 2874 /- /-/504 /78 /-
L 1579 /- /-/617 /171 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.9SBrg Width = 5.5 Min Req =3.0
L Brg Width = 5.5 Min Req =1.9
Bearings B, S, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 967 -3330
C - D 552 -1993
D - E 642 -1704E - F 370 -744
F - G 675 -1261
Chords Tens.Comp.
G - H 675 -1261
H - I 370 -744
I - J 642 -1704
J - K 552 -1993K - L 965 -3330
L - M 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 3024 -771
X - W 5268 -1194
W -V 5418 -1233
V - U 3012 -745
U - T 2927 -788
T - S 659 -2274
Chords Tens.Comp.
S - R 668 -2274
R - Q 2927 -788
Q - P 3012 -745
P - O 5418 -1093
O - N 5268 -1069
N - L 3024 -793
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
C - X 396 -129
C - Y 635 -1732
X - Y 1295 -2494
D - Y 322 -153
Y - W 358 -14
Y - V 957 -2509
Y - Z 1847 -1974
V - Z 398 -171
Z -AB 1858 -1899
E -AA 394 -1387
F -AA 346 -83
F -AD 993 -421
AA-AD 377 -1317U -AB 634 -163
Webs Tens.Comp.
S -AF 386 -2848
AD-AH 377 -1317
AD- H 993 -421
AE- S 48 -516
AE-AF 6045 -1177
AF- R 1255 -250
AF-AG 3247 -757
R -AG 801 -3525
AG- Q 634 -163
AG-AI 1858 -1899
AH- H 345 -83
AH- I 394 -1387
AI- P 398 -171AI-AJ 1847 -1974
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.35 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.79 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.450 O 634 240
VERT(CL):0.991 W 288 228
HORZ(LL):0.201 D - -
HORZ(TL):0.460 D - -
Creep Factor: 2.0
Max TC CSI:0.865
Max BC CSI:0.989
Max Web CSI:0.848
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T15
Ply: 1
Qty:3
Wgt: 375.9 lbs
SEQN: 17529 / T48 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T3
T2
B2 B2
W9
(a)
(a)
(a)
(a)
10'1"2AB
C
D
E
F G H
I
J
K
L M
NOPQRSTUVWX
Y Z
AA
AB AC
AD
AE AF AG
AH
AI AJ
5 12
8
12
4X5(**)(I)
8X8(**)
6X10(**)
6X10
4X8
6X6(**)
4X10
6X8(**)
4X8
4X8
H0514
6X12(**)
4X8
6X8(**)
4X10
6X6(**)
4X8
6X10
8X8(**)
6X10(**)
4X5(**)(I)
23'8"12 24'2"4
6'9"
6'9"
13'11"
7'2"
18'3"
4'4"
23'11"8
5'8"8
29'8"
5'8"8
34'1"12
4'5"12
41'2"
7'0"4
47'11"
6'9"
6'9"
6'9"
13'9"4
7'0"4
16'1"5
2'4"1
18'4"12
2'3"7
18'9"14
5"221'2"7
2'4"9
23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
29'6"4
5"231'9"11
2'3"7
34'1"12
2'4"1
41'2"
7'0"4
47'11"
6'9"1'6"8 1'6"8
4"53'2"120'1"6'0"128'0"129'4"121'4"10'10"111'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x6 SP #2:
:T3 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W9 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 49.51
BC 44 0.15 47.77Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Attic room loading from 13-11-0 to 34-0-0: Live Load:40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be taken
during handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1579 /- /-/606 /166 /338
S 2874 /- /-/504 /78 /-
L 1579 /- /-/617 /171 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.9SBrg Width = 5.5 Min Req =3.0
L Brg Width = 5.5 Min Req =1.9
Bearings B, S, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 967 -3330
C - D 552 -1993
D - E 642 -1704E - F 370 -744
F - G 675 -1261
Chords Tens.Comp.
G - H 675 -1261
H - I 370 -744
I - J 642 -1704
J - K 552 -1993K - L 965 -3330
L - M 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 3024 -771
X - W 5268 -1194
W -V 5418 -1233
V - U 3012 -745
U - T 2927 -788
T - S 659 -2274
Chords Tens.Comp.
S - R 668 -2274
R - Q 2927 -788
Q - P 3012 -745
P - O 5418 -1093
O - N 5268 -1069
N - L 3024 -793
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
C - X 396 -129
C - Y 635 -1732
X - Y 1295 -2494
D - Y 322 -153
Y - W 358 -14
Y - V 957 -2509
Y - Z 1847 -1974
V - Z 398 -171
Z -AB 1858 -1899
E -AA 394 -1387
F -AA 346 -83
F -AD 993 -421
AA-AD 377 -1317U -AB 634 -163
Webs Tens.Comp.
S -AF 386 -2848
AD-AH 377 -1317
AD- H 993 -421
AE- S 48 -516
AE-AF 6045 -1177
AF- R 1255 -250
AF-AG 3247 -757
R -AG 801 -3525
AG- Q 634 -163
AG-AI 1858 -1899
AH- H 345 -83
AH- I 394 -1387
AI- P 398 -171AI-AJ 1847 -1974
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.35 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.79 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.450 O 634 240
VERT(CL):0.991 W 288 228
HORZ(LL):0.201 D - -
HORZ(TL):0.460 D - -
Creep Factor: 2.0
Max TC CSI:0.865
Max BC CSI:0.989
Max Web CSI:0.848
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T15
Ply: 1
Qty:3
Wgt: 375.9 lbs
SEQN: 17529 / T48 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T3
T2
B2 B2
W9
(a)
(a)
(a)
(a)
10'1"2AB
C
D
E
F G H
I
J
K
L M
NOPQRSTUVWX
Y Z
AA
AB AC
AD
AE AF AG
AH
AI AJ
5 12
8
12
4X5(**)(I)
8X8(**)
6X10(**)
6X10
4X8
6X6(**)
4X10
6X8(**)
4X8
4X8
H0514
6X12(**)
4X8
6X8(**)
4X10
6X6(**)
4X8
6X10
8X8(**)
6X10(**)
4X5(**)(I)
23'8"12 24'2"4
6'9"
6'9"
13'11"
7'2"
18'3"
4'4"
23'11"8
5'8"8
29'8"
5'8"8
34'1"12
4'5"12
41'2"
7'0"4
47'11"
6'9"
6'9"
6'9"
13'9"4
7'0"4
16'1"5
2'4"1
18'4"12
2'3"7
18'9"14
5"221'2"7
2'4"9
23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
29'6"4
5"231'9"11
2'3"7
34'1"12
2'4"1
41'2"
7'0"4
47'11"
6'9"1'6"8 1'6"8
4"53'2"120'1"6'0"128'0"129'4"121'4"10'10"111'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
AB- T 798 -3522
AB-AC 3247 -772T -AC 1254 -249
AC- S 385 -2848
AC-AE 6045 -1177
G -AD 178 -266
P -AJ 958 -2509
AJ- O 358 -14AJ- J 322 -150
AJ- K 633 -1732
AJ- N 1295 -2494
K - N 396 -129
Job Number:86460
Pujadas Res.
Truss Label:T15
Ply: 1
Qty:3
Wgt: 375.9 lbs
SEQN: 17529 / T48 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x6 SP 2400f-2.0E:
:T3 2x4 SP 2400f-2.0E:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2:Webs 2x4 SP #3 :W7, W9 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint, equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 17 plf at -1.65 to 17 plf at 6.75TC: From 44 plf at -1.65 to 44 plf at 49.57
TC: From 18 plf at 6.75 to 18 plf at 16.62TC: From 26 plf at 13.92 to 26 plf at 15.29TC: From 17 plf at 16.62 to 17 plf at 31.29TC: From 18 plf at 31.29 to 18 plf at 41.17TC: From 26 plf at 32.63 to 26 plf at 34.00TC: From 17 plf at 41.17 to 17 plf at 49.57PLT: From 22 plf at 15.67 to 22 plf at 32.25PLT: From 109 plf at 13.92 to 109 plf at 34.00BC: From 5 plf at -1.65 to 5 plf at 0.00BC: From 11 plf at 0.00 to 11 plf at 47.92BC: From 5 plf at 47.92 to 5 plf at 49.57TC: 47 lb Conc. Load at 46.34PLT: 200 lb Conc. Load at (17.50,11.39), (22.50,11.39)BC: 133 lb Conc. Load at 13.92,34.00BC: 20 lb Conc. Load at 46.34
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%
Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 49.51BC 52 0.15 47.77Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AK 1976 /- /-/770 /511 /333
AL 3078 /- /-/790 /833 /-
L 1972 /- /-/714 /547 /-
Wind reactions based on MWFRS
AK Brg Width = 5.5 Min Req =2.3ALBrg Width = 5.5 Min Req =3.3
L Brg Width = 5.5 Min Req =2.3
Bearings AK, AL, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 40 -18
B - C 1047 -4369
C - D 699 -2824
D - E 779 -2317E - F 536 -1217
F - G 1150 -2407
Chords Tens.Comp.
G - H 1150 -2407
H - I 583 -1203
I - J 773 -2324
J - K 713 -2810K - L 1232 -4198
L - M 40 -18
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 3992 -927
X - W 5853 -1929
W -V 5996 -1994
V - U 4316 -1556
U - T 4194 -1534
T - S 1060 -1464
Chords Tens.Comp.
S - R 703 -2061
R - Q 3243 -2104
Q - P 3359 -2130
P - O 5164 -2493
O - N 5049 -2411
N - L 3819 -1029
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
C - X 449 -196
C - Y 608 -2095
X - Y 1484 -2216
D - Y 656 -189
Y - W 416 -24
Y - V 939 -1864
Y - Z 1662 -2702
E -AA 500 -1728
V - Z 203 -310
Z -AB 1645 -2688
F -AA 456 -94
F -AD 1616 -767
AA-AD 499 -1603U -AB 811 -163
Webs Tens.Comp.
S -AF 1205 -2744
AD-AH 456 -1674
AD- H 1637 -695
AE- S 161 -604
AE-AF 5917 -1447
AF- R 957 -308
AF-AG 3600 -692
R -AG 1038 -3295
AG- Q 773 -203
AG-AI 2458 -1732
AH- H 468 -82
AH- I 455 -1803
AI- P 236 -255AI-AJ 2483 -1752
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 26.3 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.79 ft
Loc. from endwall: not in 14.13 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.398 G 717 240
VERT(CL):0.855 D 334 228
HORZ(LL):0.147 D - -
HORZ(TL):0.367 D - -
Creep Factor: 2.0
Max TC CSI:0.904
Max BC CSI:0.991
Max Web CSI:0.807
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T16
Ply: 1
Qty:1
Wgt: 423.5 lbs
SEQN: 17489 / T75 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T3
T2
B2
B3 B3
B2
W7
W9
W7
(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F G H
I
J
K
L
M
NOPQRSTUVWX
Y Z
AA
AB AC
AD
AE AF AG
AH
AI AJ
AK AL
5 12
8
12
4X4(**)4X4(**)
10X12(**)
8X8(**)
3X8
6X12
4X5
H0612(**)
4X4
4X10
8X8(**)
4X8
6X8
H0514
6X12(I)
4X8
8X8(**)
4X10
4X4
6X8(**)(I)
4X5
6X12
3X8
10X12(**)
8X8(**)
4X4(**)4X4(**)
23'8"12 24'2"4
6'9"
6'9"
13'11"
7'2"
16'7"8
2'8"8
23'11"8
7'4"
31'3"8
7'4"
34'1"12
2'10"4
41'2"
7'0"4
47'11"
6'9"
6'9"
6'9"
16'1"13
9'4"13
16'10"4
8"7
18'9"14
1'11"1021'2"7
2'4"9
23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
31'0"12
1'11"1031'9"3
8"7
34'1"12
2'4"9 41'2"
7'0"4
47'11"
6'9"1'6"8 1'6"8
4"53'2"120'1"6'0"126'11"128'3"121'4"9'9"110'4"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x6 SP 2400f-2.0E:
:T3 2x4 SP 2400f-2.0E:Bot chord 2x6 SP #2 :B2 2x6 SP 2400f-2.0E::B3 2x4 SP #2:Webs 2x4 SP #3 :W7, W9 2x6 SP #2:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint, equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 17 plf at -1.65 to 17 plf at 6.75TC: From 44 plf at -1.65 to 44 plf at 49.57
TC: From 18 plf at 6.75 to 18 plf at 16.62TC: From 26 plf at 13.92 to 26 plf at 15.29TC: From 17 plf at 16.62 to 17 plf at 31.29TC: From 18 plf at 31.29 to 18 plf at 41.17TC: From 26 plf at 32.63 to 26 plf at 34.00TC: From 17 plf at 41.17 to 17 plf at 49.57PLT: From 22 plf at 15.67 to 22 plf at 32.25PLT: From 109 plf at 13.92 to 109 plf at 34.00BC: From 5 plf at -1.65 to 5 plf at 0.00BC: From 11 plf at 0.00 to 11 plf at 47.92BC: From 5 plf at 47.92 to 5 plf at 49.57TC: 47 lb Conc. Load at 46.34PLT: 200 lb Conc. Load at (17.50,11.39), (22.50,11.39)BC: 133 lb Conc. Load at 13.92,34.00BC: 20 lb Conc. Load at 46.34
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%
Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 49.51BC 52 0.15 47.77Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AK 1976 /- /-/770 /511 /333
AL 3078 /- /-/790 /833 /-
L 1972 /- /-/714 /547 /-
Wind reactions based on MWFRS
AK Brg Width = 5.5 Min Req =2.3ALBrg Width = 5.5 Min Req =3.3
L Brg Width = 5.5 Min Req =2.3
Bearings AK, AL, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 40 -18
B - C 1047 -4369
C - D 699 -2824
D - E 779 -2317E - F 536 -1217
F - G 1150 -2407
Chords Tens.Comp.
G - H 1150 -2407
H - I 583 -1203
I - J 773 -2324
J - K 713 -2810K - L 1232 -4198
L - M 40 -18
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 3992 -927
X - W 5853 -1929
W -V 5996 -1994
V - U 4316 -1556
U - T 4194 -1534
T - S 1060 -1464
Chords Tens.Comp.
S - R 703 -2061
R - Q 3243 -2104
Q - P 3359 -2130
P - O 5164 -2493
O - N 5049 -2411
N - L 3819 -1029
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
C - X 449 -196
C - Y 608 -2095
X - Y 1484 -2216
D - Y 656 -189
Y - W 416 -24
Y - V 939 -1864
Y - Z 1662 -2702
E -AA 500 -1728
V - Z 203 -310
Z -AB 1645 -2688
F -AA 456 -94
F -AD 1616 -767
AA-AD 499 -1603U -AB 811 -163
Webs Tens.Comp.
S -AF 1205 -2744
AD-AH 456 -1674
AD- H 1637 -695
AE- S 161 -604
AE-AF 5917 -1447
AF- R 957 -308
AF-AG 3600 -692
R -AG 1038 -3295
AG- Q 773 -203
AG-AI 2458 -1732
AH- H 468 -82
AH- I 455 -1803
AI- P 236 -255AI-AJ 2483 -1752
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 26.3 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.79 ft
Loc. from endwall: not in 14.13 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.398 G 717 240
VERT(CL):0.855 D 334 228
HORZ(LL):0.147 D - -
HORZ(TL):0.367 D - -
Creep Factor: 2.0
Max TC CSI:0.904
Max BC CSI:0.991
Max Web CSI:0.807
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T16
Ply: 1
Qty:1
Wgt: 423.5 lbs
SEQN: 17489 / T75 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3 T3
T2
B2
B3 B3
B2
W7
W9
W7
(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F G H
I
J
K
L
M
NOPQRSTUVWX
Y Z
AA
AB AC
AD
AE AF AG
AH
AI AJ
AK AL
5 12
8
12
4X4(**)4X4(**)
10X12(**)
8X8(**)
3X8
6X12
4X5
H0612(**)
4X4
4X10
8X8(**)
4X8
6X8
H0514
6X12(I)
4X8
8X8(**)
4X10
4X4
6X8(**)(I)
4X5
6X12
3X8
10X12(**)
8X8(**)
4X4(**)4X4(**)
23'8"12 24'2"4
6'9"
6'9"
13'11"
7'2"
16'7"8
2'8"8
23'11"8
7'4"
31'3"8
7'4"
34'1"12
2'10"4
41'2"
7'0"4
47'11"
6'9"
6'9"
6'9"
16'1"13
9'4"13
16'10"4
8"7
18'9"14
1'11"1021'2"7
2'4"9
23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
31'0"12
1'11"1031'9"3
8"7
34'1"12
2'4"9 41'2"
7'0"4
47'11"
6'9"1'6"8 1'6"8
4"53'2"120'1"6'0"126'11"128'3"121'4"9'9"110'4"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Additional Notes
The maximum horizontal reaction is 333#
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is9-9-1.
Top Chord overhang(s) may be field trimmed.
AB- T 826 -3644
AB-AC 2970 -1070T -AC 1072 -239
AC- S 820 -3384
AC-AE 5917 -1447
G -AD 238 -364
P -AJ 819 -1899
AJ- O 446 -24AJ- J 625 -208
AJ- K 762 -1919
AJ- N 2119 -1581
K - N 354 -255
Job Number:86460
Pujadas Res.
Truss Label:T16
Ply: 1
Qty:1
Wgt: 423.5 lbs
SEQN: 17489 / T75 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T1 2x4 SP #1:
:T2 2x6 SP #2::T6 2x4 SP #2:Bot chord 2x6 SP #2 :B2, B5 2x6 SP 2400f-2.0E::B3 2x4 SP #2:Webs 2x4 SP #3 :W4, W11 2x4 SP #2::W9 2x6 SP #2::W10 2x4 SP #1::W12 2x8 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint, equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 17 plf at -1.65 to 17 plf at 6.75TC: From 44 plf at -1.65 to 44 plf at 47.57TC: From 18 plf at 6.75 to 18 plf at 13.92TC: From 17 plf at 13.92 to 17 plf at 34.00TC: From 18 plf at 34.00 to 18 plf at 41.17TC: From 17 plf at 41.17 to 17 plf at 47.57PLT: From 22 plf at 13.92 to 22 plf at 34.00PLT: From 109 plf at 13.92 to 109 plf at 23.96PLT: From 109 plf at 23.96 to 109 plf at 34.00BC: From 5 plf at -1.65 to 5 plf at 0.00BC: From 11 plf at 0.00 to 11 plf at 45.31BC: From 5 plf at 45.92 to 5 plf at 47.57PLT: 200 lb Conc. Load at (17.50,11.39), (22.50,11.39)
BC: 113 lb Conc. Load at 13.92,34.00
Plating Notes
All plates are 3X4 except as noted.
(**) 13 plate(s) require special positioning. Refer to
scaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 58 0.15 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AL 2050 /- /-/701 /485 /227
AM 2732 /- /-/668 /738 /-
AN 1986 /- /-/711 /519 /-
Wind reactions based on MWFRS
AL Brg Width = 5.5 Min Req =2.4AMBrg Width = 5.5 Min Req =2.8
AN Brg Width = 5.5 Min Req =5.5
Bearings AL, AM, & AN Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 40 -16
B - C 1095 -4552
C - D 774 -3043
D - E 1606 -4583E - F 2034 -5497
Chords Tens.Comp.
F - G 2034 -5497
G - H 1586 -4406
H - I 707 -2953
I - J 924 -3253J - K 40 -16
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - W 4158 -899
W -V 5604 -1703
V - U 5856 -1880
U - T 4420 -1401
T - S 4312 -1377
S - R 934 -586
Chords Tens.Comp.
R - Q 785 -1760
Q - P 2901 -2014
P - O 2976 -2030
O - N 3822 -2180
N - M 3710 -1937
M - L 213 -65
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - W 408 -162
C - Y 557 -1974
W -Y 1300 -1920
X - Y 738 -233
X - D 787 -209
X -AA 244 -281
Y - V 353 -18
Y - U 684 -1523
Y - Z 1506 -2703
D -AA 2359 -1060
U - Z 207 -328
Z -AB 1490 -2693
AA- E 247 -422
AA-AD 2295 -964T -AB 724 -159
Webs Tens.Comp.
AD- G 1205 -416
AD-AH 2209 -1063
AE- R 154 -575
AE-AF 5009 -1206
AF- Q 711 -244
AF-AG 3432 -758
Q -AG 794 -2387
G -AH 231 -430
AG- P 499 -181
AG-AI 2681 -1352
AH- H 2398 -990
AH-AJ 209 -506
AI- O 235 -337
AI-AK 2716 -1372O -AK 737 -907
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 26.3 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 14.13 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.552 F 518 240
VERT(CL):0.879 T 325 228
HORZ(LL):0.153 P - -
HORZ(TL):0.373 P - -
Creep Factor: 2.0
Max TC CSI:0.809
Max BC CSI:1.000
Max Web CSI:0.997
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T17
Ply: 1
Qty:1
Wgt: 424.9 lbs
SEQN: 17494 / T18 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1
T2
T2
T6
B2
B3 B3
B5
W4 W9
W10
W11 W12
(a)
(a)
(a)
10'1"2A
B
C
D E F G H
I
J K
LMNOPQRSTUVW
X
Y Z
AA
AB AC
AD
AE AF AG
AH
AI
AJ
AK
AL AM AN
5 12
8
12
4X4(**)4X4(**)
8X8(**)
8X8(**)
6X8
6X10(**)
4X4
H0612
4X4
4X8
5X7(**)
8X8(**)
4X8
6X8
H0510
8X12
3X8
8X8(**)
5X7(**)
3X8
H0612
H0612(**)
6X12
8X8(**)
8X12(**)
6X8(**)
23'8"12 22'2"4
6'9"
6'9"
13'10"8
7'1"8
13'11"
0"8
19'0"2
5'1"2
23'11"8
4'11"6
28'10"14
4'11"6
34'
5'1"2
34'0"8
0"8
41'2"
7'1"8
45'11"
4'9"
6'9"
6'9"
13'11"
7'2"
16'1"13
2'2"13
18'6"
2'4"318'9"14
3"14
21'2"7
2'4"9 23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
29'5"
3"1431'9"3
2'4"3
34'
2'2"13 41'3"12
7'3"12
45'3"12
4'
45'11"
7"41'6"8
1'6"8
4"5 1'2"53'2"120'1"6'0"125'1"126'5"121'4"7'11"18'6"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T1 2x4 SP #1:
:T2 2x6 SP #2::T6 2x4 SP #2:Bot chord 2x6 SP #2 :B2, B5 2x6 SP 2400f-2.0E::B3 2x4 SP #2:Webs 2x4 SP #3 :W4, W11 2x4 SP #2::W9 2x6 SP #2::W10 2x4 SP #1::W12 2x8 SP #1:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint, equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 17 plf at -1.65 to 17 plf at 6.75TC: From 44 plf at -1.65 to 44 plf at 47.57TC: From 18 plf at 6.75 to 18 plf at 13.92TC: From 17 plf at 13.92 to 17 plf at 34.00TC: From 18 plf at 34.00 to 18 plf at 41.17TC: From 17 plf at 41.17 to 17 plf at 47.57PLT: From 22 plf at 13.92 to 22 plf at 34.00PLT: From 109 plf at 13.92 to 109 plf at 23.96PLT: From 109 plf at 23.96 to 109 plf at 34.00BC: From 5 plf at -1.65 to 5 plf at 0.00BC: From 11 plf at 0.00 to 11 plf at 45.31BC: From 5 plf at 45.92 to 5 plf at 47.57PLT: 200 lb Conc. Load at (17.50,11.39), (22.50,11.39)
BC: 113 lb Conc. Load at 13.92,34.00
Plating Notes
All plates are 3X4 except as noted.
(**) 13 plate(s) require special positioning. Refer to
scaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 58 0.15 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc.
Loading
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AL 2050 /- /-/701 /485 /227
AM 2732 /- /-/668 /738 /-
AN 1986 /- /-/711 /519 /-
Wind reactions based on MWFRS
AL Brg Width = 5.5 Min Req =2.4AMBrg Width = 5.5 Min Req =2.8
AN Brg Width = 5.5 Min Req =5.5
Bearings AL, AM, & AN Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 40 -16
B - C 1095 -4552
C - D 774 -3043
D - E 1606 -4583E - F 2034 -5497
Chords Tens.Comp.
F - G 2034 -5497
G - H 1586 -4406
H - I 707 -2953
I - J 924 -3253J - K 40 -16
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - W 4158 -899
W -V 5604 -1703
V - U 5856 -1880
U - T 4420 -1401
T - S 4312 -1377
S - R 934 -586
Chords Tens.Comp.
R - Q 785 -1760
Q - P 2901 -2014
P - O 2976 -2030
O - N 3822 -2180
N - M 3710 -1937
M - L 213 -65
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - W 408 -162
C - Y 557 -1974
W -Y 1300 -1920
X - Y 738 -233
X - D 787 -209
X -AA 244 -281
Y - V 353 -18
Y - U 684 -1523
Y - Z 1506 -2703
D -AA 2359 -1060
U - Z 207 -328
Z -AB 1490 -2693
AA- E 247 -422
AA-AD 2295 -964T -AB 724 -159
Webs Tens.Comp.
AD- G 1205 -416
AD-AH 2209 -1063
AE- R 154 -575
AE-AF 5009 -1206
AF- Q 711 -244
AF-AG 3432 -758
Q -AG 794 -2387
G -AH 231 -430
AG- P 499 -181
AG-AI 2681 -1352
AH- H 2398 -990
AH-AJ 209 -506
AI- O 235 -337
AI-AK 2716 -1372O -AK 737 -907
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 26.3 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 14.13 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.552 F 518 240
VERT(CL):0.879 T 325 228
HORZ(LL):0.153 P - -
HORZ(TL):0.373 P - -
Creep Factor: 2.0
Max TC CSI:0.809
Max BC CSI:1.000
Max Web CSI:0.997
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T17
Ply: 1
Qty:1
Wgt: 424.9 lbs
SEQN: 17494 / T18 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T1
T2
T2
T6
B2
B3 B3
B5
W4 W9
W10
W11 W12
(a)
(a)
(a)
10'1"2A
B
C
D E F G H
I
J K
LMNOPQRSTUVW
X
Y Z
AA
AB AC
AD
AE AF AG
AH
AI
AJ
AK
AL AM AN
5 12
8
12
4X4(**)4X4(**)
8X8(**)
8X8(**)
6X8
6X10(**)
4X4
H0612
4X4
4X8
5X7(**)
8X8(**)
4X8
6X8
H0510
8X12
3X8
8X8(**)
5X7(**)
3X8
H0612
H0612(**)
6X12
8X8(**)
8X12(**)
6X8(**)
23'8"12 22'2"4
6'9"
6'9"
13'10"8
7'1"8
13'11"
0"8
19'0"2
5'1"2
23'11"8
4'11"6
28'10"14
4'11"6
34'
5'1"2
34'0"8
0"8
41'2"
7'1"8
45'11"
4'9"
6'9"
6'9"
13'11"
7'2"
16'1"13
2'2"13
18'6"
2'4"318'9"14
3"14
21'2"7
2'4"9 23'11"8
2'9"1
26'8"9
2'9"1
29'1"2
2'4"9
29'5"
3"1431'9"3
2'4"3
34'
2'2"13 41'3"12
7'3"12
45'3"12
4'
45'11"
7"41'6"8
1'6"8
4"5 1'2"53'2"120'1"6'0"125'1"126'5"121'4"7'11"18'6"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Additional Notes
The maximum horizontal reaction is 227#
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is7-11-1.
Top Chord overhang(s) may be field trimmed.
AB- S 840 -3358
AB-AC 2284 -880E -AD 1057 -460
S -AC 1001 -245
AC- R 829 -3240
AC-AE 5009 -1206F -AD 183 -318
R -AF 1069 -2222
H -AJ 680 -212
AJ-AK 628 -237AK- N 408 -25
AK- I 524 -933
AK- M 1980 -1191
I - M 173 -534M - J 2822 -715
J - L 685 -1937
Job Number:86460
Pujadas Res.
Truss Label:T17
Ply: 1
Qty:1
Wgt: 424.9 lbs
SEQN: 17494 / T18 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #1::B3 2x6 SP #2:Webs 2x4 SP #3 :W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 5X7(**) except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 85 0.15 23.52BC 120 23.52 35.81BC 75 35.81 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 929 /- /-/447 /131 /335
U 1907 /- /-/738 /141 /-
L 893 /- /-/515 /125 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5UBrg Width = 5.5 Min Req =1.9
L Brg Width = 5.5 Min Req =1.5
Bearings B, U, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 736 -1622
C - D 617 -1273
D - E 447 -620E - F 264 -188
Chords Tens.Comp.
F - G 402 -213
G - H 661 -1268
H - I 474 -1248
I - J 491 -1212J - K 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - W 1441 -609
W -V 791 -225
V - U 598 -165
U - S 0 0
T - P 381 0
Chords Tens.Comp.
R - Q 0 0
P - N 424 0
Q - O 0 -57
O - M 4 -50
M - L 91 -33
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - W 418 -608W -D 593 -230
D - V 137 -271
V - E 513 -65
E - U 331 -1090
U - T 370 -1116
T - F 421 -292
T - G 0 -805
G - N 1094 -414
Webs Tens.Comp.
P - Q 93 0N - O 210 0
N - H 279 -355
N - I 193 -143
N - M 1154 -362
I - M 172 -443
M - J 1013 -350
J - L 472 -857
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.406 R 656 240
VERT(CL):0.603 R 441 226
HORZ(LL):0.023 U - -
HORZ(TL):0.035 U - -
Creep Factor: 2.0
Max TC CSI:0.529
Max BC CSI:0.902
Max Web CSI:0.986
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T18
Ply: 1
Qty:1
Wgt: 312.9 lbs
SEQN: 17478 / T45 / COMN
FROM:DRW:
.../...04/15/2020
B2
B3 W12
(a)(a)
(a)
10'1"2AB
C
D E F
G
H
I
J K
LM
NOPQR
ST UVW
5 12
8
12
4X5(**)
3X4
3X4
4X4
6X8
3X4(**)3X4(**)
8X8(**)
3X4
3X4
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
12'3"
5'6"
18'
5'9"
23'9"
5'9"
29'8"8
5'11"8
35'9"12
6'1"4
41'2"
5'4"4
45'11"
4'9"
10'
10'
17'8"8
7'8"8
23'9"
6'0"8
31'2"12
7'5"12
35'8"
4'5"4
41'3"12
5'7"12
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"16'10"11'10'9"1111'4"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #1::B3 2x6 SP #2:Webs 2x4 SP #3 :W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 5X7(**) except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 85 0.15 23.52BC 120 23.52 35.81BC 75 35.81 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 929 /- /-/447 /131 /335
U 1907 /- /-/738 /141 /-
L 893 /- /-/515 /125 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5UBrg Width = 5.5 Min Req =1.9
L Brg Width = 5.5 Min Req =1.5
Bearings B, U, & L Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 736 -1622
C - D 617 -1273
D - E 447 -620E - F 264 -188
Chords Tens.Comp.
F - G 402 -213
G - H 661 -1268
H - I 474 -1248
I - J 491 -1212J - K 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - W 1441 -609
W -V 791 -225
V - U 598 -165
U - S 0 0
T - P 381 0
Chords Tens.Comp.
R - Q 0 0
P - N 424 0
Q - O 0 -57
O - M 4 -50
M - L 91 -33
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - W 418 -608W -D 593 -230
D - V 137 -271
V - E 513 -65
E - U 331 -1090
U - T 370 -1116
T - F 421 -292
T - G 0 -805
G - N 1094 -414
Webs Tens.Comp.
P - Q 93 0N - O 210 0
N - H 279 -355
N - I 193 -143
N - M 1154 -362
I - M 172 -443
M - J 1013 -350
J - L 472 -857
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.406 R 656 240
VERT(CL):0.603 R 441 226
HORZ(LL):0.023 U - -
HORZ(TL):0.035 U - -
Creep Factor: 2.0
Max TC CSI:0.529
Max BC CSI:0.902
Max Web CSI:0.986
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T18
Ply: 1
Qty:1
Wgt: 312.9 lbs
SEQN: 17478 / T45 / COMN
FROM:DRW:
.../...04/15/2020
B2
B3 W12
(a)(a)
(a)
10'1"2AB
C
D E F
G
H
I
J K
LM
NOPQR
ST UVW
5 12
8
12
4X5(**)
3X4
3X4
4X4
6X8
3X4(**)3X4(**)
8X8(**)
3X4
3X4
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
12'3"
5'6"
18'
5'9"
23'9"
5'9"
29'8"8
5'11"8
35'9"12
6'1"4
41'2"
5'4"4
45'11"
4'9"
10'
10'
17'8"8
7'8"8
23'9"
6'0"8
31'2"12
7'5"12
35'8"
4'5"4
41'3"12
5'7"12
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"16'10"11'10'9"1111'4"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B3 2x6 SP #2:Webs 2x4 SP #3 :W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 75 0.15 23.60
BC 120 23.60 35.69BC 75 35.69 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 834 /- /-/415 /153 /335
V 1815 /- /-/777 /144 /-
M 880 /- /-/509 /122 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5VBrg Width = 5.5 Min Req =1.8
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 717 -1364
C - D 576 -1013
D - E 521 -798E - F 503 -643
F - G 367 -248
Chords Tens.Comp.
G - H 357 -194
H - I 634 -1218
I - J 449 -1202
J - K 476 -1191K - L 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 1203 -583
X - W 669 -281
W -V 88 -69
V - T 0 0
U - Q 361 0
Chords Tens.Comp.
S - R 0 0
Q - O 401 0
R - P 0 -55
P - N 5 -48
N - M 89 -32
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - X 382 -526
D - X 321 -183
X - E 223 -118
E - W 227 -479
W -F 780 -278
F - V 416 -687
V - U 242 -1173
G - U 241 -287
U - H 24 -879
Webs Tens.Comp.
H - O 1074 -408
Q - R 93 0
O - P 207 0
O - I 277 -353
O - J 202 -156
O - N 1131 -342
J - N 163 -425
N - K 996 -338
K - M 463 -845
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.340 S 788 240
VERT(CL):0.539 S 497 225
HORZ(LL):-0.023 I - -
HORZ(TL):0.036 I - -
Creep Factor: 2.0
Max TC CSI:0.564
Max BC CSI:0.683
Max Web CSI:0.959
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T19
Ply: 1
Qty:1
Wgt: 308.7 lbs
SEQN: 17481 / T32 / COMN
FROM:DRW:
.../...04/15/2020
B3 W12
(a)
10'1"2AB
C
D E F
G
H
I
J
K L
MN
OPQRS
TU VWX
5 12
8
12
4X5(**)
5X7(**)
5X7(**)
6X8(**)
5X7(**)
6X8
5X7(**)
3X4(**)3X4(**)
8X8(**)
5X7(**)
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
10'3"
3'6"
16'
5'9"
21'9"
5'9"
23'8"12
1'11"12
29'8"8
5'11"12
35'8"4
5'11"12
41'2"
5'5"12
45'11"
4'9"
10'4"12
10'4"12
16'3"8
5'10"12
23'10"8
7'7"
31'2"12
7'4"4
35'6"8
4'3"12
41'3"12
5'9"4
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"15'6"11'10'9"1111'4"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B3 2x6 SP #2:Webs 2x4 SP #3 :W12 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 75 0.15 23.60
BC 120 23.60 35.69BC 75 35.69 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 834 /- /-/415 /153 /335
V 1815 /- /-/777 /144 /-
M 880 /- /-/509 /122 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5VBrg Width = 5.5 Min Req =1.8
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 717 -1364
C - D 576 -1013
D - E 521 -798E - F 503 -643
F - G 367 -248
Chords Tens.Comp.
G - H 357 -194
H - I 634 -1218
I - J 449 -1202
J - K 476 -1191K - L 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 1203 -583
X - W 669 -281
W -V 88 -69
V - T 0 0
U - Q 361 0
Chords Tens.Comp.
S - R 0 0
Q - O 401 0
R - P 0 -55
P - N 5 -48
N - M 89 -32
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - X 382 -526
D - X 321 -183
X - E 223 -118
E - W 227 -479
W -F 780 -278
F - V 416 -687
V - U 242 -1173
G - U 241 -287
U - H 24 -879
Webs Tens.Comp.
H - O 1074 -408
Q - R 93 0
O - P 207 0
O - I 277 -353
O - J 202 -156
O - N 1131 -342
J - N 163 -425
N - K 996 -338
K - M 463 -845
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.340 S 788 240
VERT(CL):0.539 S 497 225
HORZ(LL):-0.023 I - -
HORZ(TL):0.036 I - -
Creep Factor: 2.0
Max TC CSI:0.564
Max BC CSI:0.683
Max Web CSI:0.959
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T19
Ply: 1
Qty:1
Wgt: 308.7 lbs
SEQN: 17481 / T32 / COMN
FROM:DRW:
.../...04/15/2020
B3 W12
(a)
10'1"2AB
C
D E F
G
H
I
J
K L
MN
OPQRS
TU VWX
5 12
8
12
4X5(**)
5X7(**)
5X7(**)
6X8(**)
5X7(**)
6X8
5X7(**)
3X4(**)3X4(**)
8X8(**)
5X7(**)
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
10'3"
3'6"
16'
5'9"
21'9"
5'9"
23'8"12
1'11"12
29'8"8
5'11"12
35'8"4
5'11"12
41'2"
5'5"12
45'11"
4'9"
10'4"12
10'4"12
16'3"8
5'10"12
23'10"8
7'7"
31'2"12
7'4"4
35'6"8
4'3"12
41'3"12
5'9"4
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"15'6"11'10'9"1111'4"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B3 2x6 SP #2:Webs 2x4 SP #3 :W6 2x4 SP #2::W13 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 111 0.15 23.60BC 120 23.60 35.69BC 75 35.69 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 826 /- /-/396 /281 /335
V 1830 /- /-/797 /439 /-
M 879 /- /-/505 /258 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5VBrg Width = 5.5 Min Req =1.8
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 689 -1378
C - D 880 -1493
D - E 639 -1010E - F 639 -1010
F - G 358 -243
Chords Tens.Comp.
G - H 328 -178
H - I 621 -1215
I - J 436 -1200
J - K 466 -1190K - L 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 1212 -548
X - W 973 -404
W -V 399 -261
V - T 0 0
U - Q 360 0
Chords Tens.Comp.
S - R 0 0
Q - O 400 0
R - P 0 -54
P - N 5 -48
N - M 89 -32
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - X 402 -541
X - D 662 -398
D - W 177 -141
W -F 754 -232
E - W 219 -346
F - V 501 -798
V - U 266 -1231
G - U 250 -316
U - H 43 -905
Webs Tens.Comp.
H - O 1073 -407
Q - R 93 0
O - P 207 0
O - I 277 -353
O - J 204 -157
O - N 1129 -330
J - N 158 -424
N - K 995 -328
K - M 458 -844
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.336 S 796 240
VERT(CL):0.536 S 499 225
HORZ(LL):-0.030 I - -
HORZ(TL):0.047 I - -
Creep Factor: 2.0
Max TC CSI:0.505
Max BC CSI:0.980
Max Web CSI:0.957
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T20
Ply: 1
Qty:1
Wgt: 301.7 lbs
SEQN: 17484 / T31 / COMN
FROM:DRW:
.../...04/15/2020
B3
W6
W13
(a)
10'1"2AB
C
D E F
G
H
I
J
K L
MN
OPQRS
TU VWX
5 12
8
12
4X5(**)
5X7(**)
5X7(**)
6X8(**)
5X7(**)
6X8
5X7(**)
3X4(**)3X4(**)
8X8(**)
5X7(**)
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
8'3"
1'6"
14'
5'9"
19'9"
5'9"
23'8"12
3'11"12
29'8"8
5'11"12
35'8"4
5'11"12
41'2"
5'5"12
45'11"
4'9"
6'9"
6'9"
14'
7'3"
23'10"8
9'10"8
31'2"12
7'4"4
35'6"8
4'3"12
41'3"12
5'9"4
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"14'2"11'10'9"1111'4"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B3 2x6 SP #2:Webs 2x4 SP #3 :W6 2x4 SP #2::W13 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51
BC 111 0.15 23.60BC 120 23.60 35.69BC 75 35.69 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is10-9-11.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 826 /- /-/396 /281 /335
V 1830 /- /-/797 /439 /-
M 879 /- /-/505 /258 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5VBrg Width = 5.5 Min Req =1.8
M Brg Width = 5.5 Min Req =1.5
Bearings B, V, & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 689 -1378
C - D 880 -1493
D - E 639 -1010E - F 639 -1010
F - G 358 -243
Chords Tens.Comp.
G - H 328 -178
H - I 621 -1215
I - J 436 -1200
J - K 466 -1190K - L 37 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - X 1212 -548
X - W 973 -404
W -V 399 -261
V - T 0 0
U - Q 360 0
Chords Tens.Comp.
S - R 0 0
Q - O 400 0
R - P 0 -54
P - N 5 -48
N - M 89 -32
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - X 402 -541
X - D 662 -398
D - W 177 -141
W -F 754 -232
E - W 219 -346
F - V 501 -798
V - U 266 -1231
G - U 250 -316
U - H 43 -905
Webs Tens.Comp.
H - O 1073 -407
Q - R 93 0
O - P 207 0
O - I 277 -353
O - J 204 -157
O - N 1129 -330
J - N 158 -424
N - K 995 -328
K - M 458 -844
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.33 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 4.59 ft
Loc. from endwall: not in 13.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.336 S 796 240
VERT(CL):0.536 S 499 225
HORZ(LL):-0.030 I - -
HORZ(TL):0.047 I - -
Creep Factor: 2.0
Max TC CSI:0.505
Max BC CSI:0.980
Max Web CSI:0.957
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T20
Ply: 1
Qty:1
Wgt: 301.7 lbs
SEQN: 17484 / T31 / COMN
FROM:DRW:
.../...04/15/2020
B3
W6
W13
(a)
10'1"2AB
C
D E F
G
H
I
J
K L
MN
OPQRS
TU VWX
5 12
8
12
4X5(**)
5X7(**)
5X7(**)
6X8(**)
5X7(**)
6X8
5X7(**)
3X4(**)3X4(**)
8X8(**)
5X7(**)
4X10
3X8
3X8(**)
23'8"12 22'2"4
6'9"
6'9"
8'3"
1'6"
14'
5'9"
19'9"
5'9"
23'8"12
3'11"12
29'8"8
5'11"12
35'8"4
5'11"12
41'2"
5'5"12
45'11"
4'9"
6'9"
6'9"
14'
7'3"
23'10"8
9'10"8
31'2"12
7'4"4
35'6"8
4'3"12
41'3"12
5'9"4
45'11"
4'7"41'6"8 1'6"8
4"5 1'2"53'2"14'2"11'10'9"1111'4"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x4 SP #1:
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W11 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.25TC: From 28 plf at 4.25 to 28 plf at 21.31TC: From 55 plf at 21.31 to 55 plf at 27.29
TC: From 57 plf at 27.29 to 57 plf at 41.17TC: From 55 plf at 41.17 to 55 plf at 47.57BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.21BC: From 5 plf at 4.21 to 5 plf at 21.31
BC: From 10 plf at 21.31 to 10 plf at 45.92BC: From 4 plf at 45.92 to 4 plf at 47.57TC: 123 lb Conc. Load at 4.21TC: 100 lb Conc. Load at 5.06, 7.06, 9.06, 9.44TC: 113 lb Conc. Load at 11.44TC: 384 lb Conc. Load at 17.26TC: 137 lb Conc. Load at 19.31,21.31BC: 33 lb Conc. Load at 4.21BC: 55 lb Conc. Load at 5.06, 7.06, 9.06, 9.44BC: 98 lb Conc. Load at 11.44
BC: 142 lb Conc. Load at 17.26BC: 77 lb Conc. Load at 19.31,21.31
Plating Notes
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 47 0.15 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is7-7-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1232 /- /- /-/378 /-
P 2857 /- /- /-/813 /-
N 578 /- /- /-/192 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5PBrg Width = 5.5 Min Req =3.4
N Brg Width = 5.5 Min Req =1.5
Bearings B, P, & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -17
B - C 714 -2521
C - D 974 -3457
D - E 974 -3457E - F 301 -1394
F - G 268 -1283
Chords Tens.Comp.
G - H 2576 -765
H - I 2577 -765
I - J 251 -356
J - K 249 -347K - L 10 -253
L - M 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - S 2290 -642
S - R 2300 -637
R - Q 2211 -542
Chords Tens.Comp.
Q - P 166 -529
P - O 357 -1712
O - N 514 -168
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - S 137 0
C - R 1238 -353R - E 1389 -455
D - R 261 -524
E - Q 402 -1393
F - Q 88 -67
Q - G 2078 -550
G - P 758 -2594
Webs Tens.Comp.
P - I 495 -1468
H - P 122 -271I - O 1622 -430
J - O 215 -376
O - K 127 -319
K - N 217 -437
L - N 111 -299
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.231 D 999 240
VERT(CL):0.391 D 722 226
HORZ(LL):0.044 C - -
HORZ(TL):0.075 C - -
Creep Factor: 2.0
Max TC CSI:0.937
Max BC CSI:0.978
Max Web CSI:0.885
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T21
Ply: 1
Qty:1
Wgt: 249.9 lbs
SEQN: 17583 / T37 / COMN
FROM:DRW:
.../...04/15/2020
T2
W11 10'1"2AB
C D E F G H I
J
K
L M
NOPQRS
5 12
8
12
4X5(**)
5X7(**)
3X4
3X4
6X12(**)
5X7(**)
5X7(**)
6X10(**)
5X7 3X4
6X8(**)
6X8(**)
5X7(**)
6X8(**)
H0510(**)
3X4
3X8(**)
23'8"12 22'2"4
4'3"
4'3"
10'1"12
5'10"12
15'9"
5'7"4
17'3"
1'6"
20'6"12
3'3"12 23'8"12
3'2"
27'3"7
3'6"11
34'6"8
7'3"
41'2"
6'7"8
45'11"
4'9"
4'4"12
4'4"12
10'
5'7"4
17'4"12
7'4"12
23'8"12
6'4"
34'6"8
10'9"12
45'11"
11'4"81'6"8 1'6"8
4"5 1'2"52'1"92'9"13'2"17'7"18'2"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x4 SP #1:
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W11 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.25TC: From 28 plf at 4.25 to 28 plf at 21.31TC: From 55 plf at 21.31 to 55 plf at 27.29
TC: From 57 plf at 27.29 to 57 plf at 41.17TC: From 55 plf at 41.17 to 55 plf at 47.57BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.21BC: From 5 plf at 4.21 to 5 plf at 21.31
BC: From 10 plf at 21.31 to 10 plf at 45.92BC: From 4 plf at 45.92 to 4 plf at 47.57TC: 123 lb Conc. Load at 4.21TC: 100 lb Conc. Load at 5.06, 7.06, 9.06, 9.44TC: 113 lb Conc. Load at 11.44TC: 384 lb Conc. Load at 17.26TC: 137 lb Conc. Load at 19.31,21.31BC: 33 lb Conc. Load at 4.21BC: 55 lb Conc. Load at 5.06, 7.06, 9.06, 9.44BC: 98 lb Conc. Load at 11.44
BC: 142 lb Conc. Load at 17.26BC: 77 lb Conc. Load at 19.31,21.31
Plating Notes
(**) 12 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 47.51BC 47 0.15 45.92Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
WARNING: Furnish a copy of this DWG to theinstallation contractor. Special care must be takenduring handling, shipping and installation of trusses.See "WARNING" note below.
The overall height of this truss excluding overhang is7-7-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1232 /- /- /-/378 /-
P 2857 /- /- /-/813 /-
N 578 /- /- /-/192 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5PBrg Width = 5.5 Min Req =3.4
N Brg Width = 5.5 Min Req =1.5
Bearings B, P, & N Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -17
B - C 714 -2521
C - D 974 -3457
D - E 974 -3457E - F 301 -1394
F - G 268 -1283
Chords Tens.Comp.
G - H 2576 -765
H - I 2577 -765
I - J 251 -356
J - K 249 -347K - L 10 -253
L - M 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - S 2290 -642
S - R 2300 -637
R - Q 2211 -542
Chords Tens.Comp.
Q - P 166 -529
P - O 357 -1712
O - N 514 -168
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - S 137 0
C - R 1238 -353R - E 1389 -455
D - R 261 -524
E - Q 402 -1393
F - Q 88 -67
Q - G 2078 -550
G - P 758 -2594
Webs Tens.Comp.
P - I 495 -1468
H - P 122 -271I - O 1622 -430
J - O 215 -376
O - K 127 -319
K - N 217 -437
L - N 111 -299
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 4.59 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.231 D 999 240
VERT(CL):0.391 D 722 226
HORZ(LL):0.044 C - -
HORZ(TL):0.075 C - -
Creep Factor: 2.0
Max TC CSI:0.937
Max BC CSI:0.978
Max Web CSI:0.885
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T21
Ply: 1
Qty:1
Wgt: 249.9 lbs
SEQN: 17583 / T37 / COMN
FROM:DRW:
.../...04/15/2020
T2
W11 10'1"2AB
C D E F G H I
J
K
L M
NOPQRS
5 12
8
12
4X5(**)
5X7(**)
3X4
3X4
6X12(**)
5X7(**)
5X7(**)
6X10(**)
5X7 3X4
6X8(**)
6X8(**)
5X7(**)
6X8(**)
H0510(**)
3X4
3X8(**)
23'8"12 22'2"4
4'3"
4'3"
10'1"12
5'10"12
15'9"
5'7"4
17'3"
1'6"
20'6"12
3'3"12 23'8"12
3'2"
27'3"7
3'6"11
34'6"8
7'3"
41'2"
6'7"8
45'11"
4'9"
4'4"12
4'4"12
10'
5'7"4
17'4"12
7'4"12
23'8"12
6'4"
34'6"8
10'9"12
45'11"
11'4"81'6"8 1'6"8
4"5 1'2"52'1"92'9"13'2"17'7"18'2"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1
Bot chord 2x6 SP 2400f-2.0EWebs 2x4 SP #2 :W1, W2 2x6 SP #2::W4 2x4 SP #3:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 2 Rows @ 6.00" o.c. (Each Row)Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 27 plf at 0.00 to 27 plf at 31.54BC: From 5 plf at 0.00 to 5 plf at 31.54BC: 598 lb Conc. Load at 2.35BC: 591 lb Conc. Load at 4.35, 6.35BC: 884 lb Conc. Load at 8.35BC: 1358 lb Conc. Load at 10.36,12.36,16.36BC: 1355 lb Conc. Load at 14.36BC: 1447 lb Conc. Load at 18.36,20.36
BC: 985 lb Conc. Load at 22.35,24.35,26.35BC: 1072 lb Conc. Load at 28.35,29.06,31.06
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 31.54BC 117 0.00 31.54Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
The TC of this truss shall be braced with attachedspans at 24" oc in lieu of structural sheathing.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
End verticals not exposed to wind pressure.
Camber
Max JT VERT DEFL: LL: 0.29" DL: 0.17". See detail
DEFLCAMB1014 for camber recommendations.Provide for adequate drainage of roof.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
N 7817 /- /- /-/2662 /-
H 10350 /- /- /-/3524 /-
Wind reactions based on MWFRS
N Brg Width = 5.5 Min Req =4.1
H Brg Width = 3.5 Min Req =-Bearings N & H Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 0 0
B - C 1261 -3705
C - D 2092 -6144
Chords Tens.Comp.
D - E 2173 -6381
E - F 1441 -4232
F - G 0 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
N - M 3516 -1198
M - L 6009 -2047
L - K 7108 -2420
Chords Tens.Comp.
K - J 7108 -2420
J - I 6263 -2133
I - H 4016 -1368
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - N 41 -57
N - B 1743 -5118
B - M 3636 -1224
M - C 1201 -3525
C - L 2609 -877
L - D 494 -1449
D - K 1825 -609
Webs Tens.Comp.
D - J 372 -1092
J - E 2291 -769
E - I 1059 -3106
I - F 4166 -1405
F - H 1991 -5845
G - H 30 -57
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.09 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.15 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.291 K 999 302
VERT(CL):0.466 K 811 302
HORZ(LL):0.086 A - -
HORZ(TL):0.138 A - -
Creep Factor: 2.0
Max TC CSI:0.957
Max BC CSI:0.976
Max Web CSI:0.942
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T22
Ply: 2
Qty:1
Wgt: 527.8 lbs
SEQN: 17576 / T50 / FLAT
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W1
W2 W4 W4
W4 W4 W2
W1
BL1
(a)
(a)
(a)(a)
(a)
(a)
10'1"2
A B C D E F G
HIJKLMN
3X4
H0612(**)
8X8(**)
8X8(R)
5X7(**)
H1010(**)(I)
6X8(**)
4X8 H1010(**)(I)
5X7(**)
8X8(R)
8X8(**)3X4
H0612(**)
31'6"8
5'3"5
5'3"5
10'5"11
5'2"5
15'9"4
5'3"9
21'0"13
5'3"9
26'3"3
5'2"5
31'6"8
5'3"5
5'7"13
5'7"13
10'9"4
5'1"7
15'9"4
5'
20'9"4
5'
25'10"11
5'1"7
31'6"8
5'7"136'2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1
Bot chord 2x6 SP 2400f-2.0EWebs 2x4 SP #2 :W1, W2 2x6 SP #2::W4 2x4 SP #3:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 2 Rows @ 6.00" o.c. (Each Row)Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 27 plf at 0.00 to 27 plf at 31.54BC: From 5 plf at 0.00 to 5 plf at 31.54BC: 598 lb Conc. Load at 2.35BC: 591 lb Conc. Load at 4.35, 6.35BC: 884 lb Conc. Load at 8.35BC: 1358 lb Conc. Load at 10.36,12.36,16.36BC: 1355 lb Conc. Load at 14.36BC: 1447 lb Conc. Load at 18.36,20.36
BC: 985 lb Conc. Load at 22.35,24.35,26.35BC: 1072 lb Conc. Load at 28.35,29.06,31.06
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 31.54BC 117 0.00 31.54Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
The TC of this truss shall be braced with attachedspans at 24" oc in lieu of structural sheathing.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
End verticals not exposed to wind pressure.
Camber
Max JT VERT DEFL: LL: 0.29" DL: 0.17". See detail
DEFLCAMB1014 for camber recommendations.Provide for adequate drainage of roof.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
N 7817 /- /- /-/2662 /-
H 10350 /- /- /-/3524 /-
Wind reactions based on MWFRS
N Brg Width = 5.5 Min Req =4.1
H Brg Width = 3.5 Min Req =-Bearings N & H Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 0 0
B - C 1261 -3705
C - D 2092 -6144
Chords Tens.Comp.
D - E 2173 -6381
E - F 1441 -4232
F - G 0 0
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
N - M 3516 -1198
M - L 6009 -2047
L - K 7108 -2420
Chords Tens.Comp.
K - J 7108 -2420
J - I 6263 -2133
I - H 4016 -1368
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - N 41 -57
N - B 1743 -5118
B - M 3636 -1224
M - C 1201 -3525
C - L 2609 -877
L - D 494 -1449
D - K 1825 -609
Webs Tens.Comp.
D - J 372 -1092
J - E 2291 -769
E - I 1059 -3106
I - F 4166 -1405
F - H 1991 -5845
G - H 30 -57
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.09 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.15 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.291 K 999 302
VERT(CL):0.466 K 811 302
HORZ(LL):0.086 A - -
HORZ(TL):0.138 A - -
Creep Factor: 2.0
Max TC CSI:0.957
Max BC CSI:0.976
Max Web CSI:0.942
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T22
Ply: 2
Qty:1
Wgt: 527.8 lbs
SEQN: 17576 / T50 / FLAT
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
W1
W2 W4 W4
W4 W4 W2
W1
BL1
(a)
(a)
(a)(a)
(a)
(a)
10'1"2
A B C D E F G
HIJKLMN
3X4
H0612(**)
8X8(**)
8X8(R)
5X7(**)
H1010(**)(I)
6X8(**)
4X8 H1010(**)(I)
5X7(**)
8X8(R)
8X8(**)3X4
H0612(**)
31'6"8
5'3"5
5'3"5
10'5"11
5'2"5
15'9"4
5'3"9
21'0"13
5'3"9
26'3"3
5'2"5
31'6"8
5'3"5
5'7"13
5'7"13
10'9"4
5'1"7
15'9"4
5'
20'9"4
5'
25'10"11
5'1"7
31'6"8
5'7"136'This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Bearing Block(s)
Brg blocks:0.131"x3", min. nailsbrg x-loc #blocks length/blk #nails/blk wall plate2 31.250' 2 12" 14 SP StandardBrg block to be same size and species as chord.Refer to drawing CNNAILSP1014 for more information.
Additional Notes
Truss must be installed as shown with top chord up.
The overall height of this truss excluding overhang is6-0-0.
Job Number:86460
Pujadas Res.
Truss Label:T22
Ply: 2
Qty:1
Wgt: 527.8 lbs
SEQN: 17576 / T50 / FLAT
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #1 :B2 2x4 SP #2:Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 22.75BC 120 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is7-7-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
J 527 /- /-/274 /147 /185
H 831 /- /-/344 /262 /-
K 280 /- /-/153 /61 /-
Wind reactions based on MWFRS
J Brg Width = 5.5 Min Req =1.5HBrg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.5
Bearings J, H, & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 83 -255
C - D 93 -223
Chords Tens.Comp.
D - E 231 -34
E - F 98 -183
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
J - I 425 -144
I - H 147 -46
Chords Tens.Comp.
H - G 191 -30
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - J 248 -296
J - C 133 -342
C - I 277 -356
I - D 306 -58
Webs Tens.Comp.
D - H 234 -639
H - E 254 -309
E - G 70 -87
F - G 137 -192
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.012 C 999 240
VERT(CL):0.020 C 999 180
HORZ(LL):0.006 G - -
HORZ(TL):0.009 G - -
Creep Factor: 2.0
Max TC CSI:0.822
Max BC CSI:0.703
Max Web CSI:0.685
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T23
Ply: 1
Qty:1
Wgt: 141.4 lbs
SEQN: 17569 / T44 / SPEC
FROM:DRW:
.../...04/15/2020
B2
W1 W1
10'1"2
A
B
C
D
E
F
GHIJK
5 12
8
12
3X4
3X8(**)
5X7(**)
5X5(**)
4X8(**)
3X4
6X8(**)
3X4
3X8(**)
13'6"12 8'10"12 3"8
4'9"
4'9"
11'4"8
6'7"8
18'
6'7"8
22'9"
4'9"
11'2"12
11'2"12
13'6"12
2'4"
22'9"
9'2"41'6"8
1'2"53'2"17'7"12. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #1 :B2 2x4 SP #2:Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 22.75BC 120 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is7-7-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
J 527 /- /-/274 /147 /185
H 831 /- /-/344 /262 /-
K 280 /- /-/153 /61 /-
Wind reactions based on MWFRS
J Brg Width = 5.5 Min Req =1.5HBrg Width = 5.5 Min Req =1.5
K Brg Width = 5.5 Min Req =1.5
Bearings J, H, & K Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 0
B - C 83 -255
C - D 93 -223
Chords Tens.Comp.
D - E 231 -34
E - F 98 -183
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
J - I 425 -144
I - H 147 -46
Chords Tens.Comp.
H - G 191 -30
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - J 248 -296
J - C 133 -342
C - I 277 -356
I - D 306 -58
Webs Tens.Comp.
D - H 234 -639
H - E 254 -309
E - G 70 -87
F - G 137 -192
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.012 C 999 240
VERT(CL):0.020 C 999 180
HORZ(LL):0.006 G - -
HORZ(TL):0.009 G - -
Creep Factor: 2.0
Max TC CSI:0.822
Max BC CSI:0.703
Max Web CSI:0.685
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T23
Ply: 1
Qty:1
Wgt: 141.4 lbs
SEQN: 17569 / T44 / SPEC
FROM:DRW:
.../...04/15/2020
B2
W1 W1
10'1"2
A
B
C
D
E
F
GHIJK
5 12
8
12
3X4
3X8(**)
5X7(**)
5X5(**)
4X8(**)
3X4
6X8(**)
3X4
3X8(**)
13'6"12 8'10"12 3"8
4'9"
4'9"
11'4"8
6'7"8
18'
6'7"8
22'9"
4'9"
11'2"12
11'2"12
13'6"12
2'4"
22'9"
9'2"41'6"8
1'2"53'2"17'7"1This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 12.07TC: From 55 plf at 12.07 to 55 plf at 24.40
BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 12.07BC: From 10 plf at 12.07 to 10 plf at 22.75BC: From 4 plf at 22.75 to 4 plf at 24.40
TC: 173 lb Conc. Load at 4.01TC: 110 lb Conc. Load at 6.07, 8.07,10.07,12.07BC: 143 lb Conc. Load at 4.01BC: 60 lb Conc. Load at 6.07, 8.07,10.07,12.07
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 24.35
BC 75 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
O 785 /- /- /-/168 /-
L 1398 /- /- /-/266 /-
P 271 /-31 /- /-/117 /-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =1.5LBrg Width = 5.5 Min Req =1.6
P Brg Width = 9.0 Min Req =1.5
Bearings O, L, & P Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -17
B - C 155 -1033
C - D 89 -717
D - E 89 -717
Chords Tens.Comp.
E - F 484 -71
F - G 484 -71
G - H 148 -130
H - I 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
O - N 44 -1N - M 921 -124
M - L 164 -12
Chords Tens.Comp.
L - K 107 -128K - J 52 -6
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - O 175 -771
B - N 904 -125
C - N 88 0
C - M 38 -242D - M 120 -383
M - E 873 -120
Webs Tens.Comp.
E - L 128 -998
L - G 114 -563
F - L 152 -336
G - K 129 0K - H 93 -141
H - J 126 -252
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.022 N 999 240
VERT(CL):0.035 N 999 180
HORZ(LL):0.006 J - -
HORZ(TL):0.009 J - -
Creep Factor: 2.0
Max TC CSI:0.554
Max BC CSI:0.418
Max Web CSI:0.345
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T24
Ply: 1
Qty:1
Wgt: 140.0 lbs
SEQN: 17573 / T14 / COMN
FROM:DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D E F G
H
I
JKLMNOP
5 12
3X8
3X4
4X8(**)
4X4
3X4
5X7(**)
4X4 3X4
5X7(**)
4X8(**)
4X4
3X8
3X4
13'6"12 9'2"4
4'0"1
4'0"1
9'2"5
5'2"4
11'4"8
2'2"4
13'6"12
2'2"4
18'9"
5'2"4
22'9"
4'
4'0"1
4'0"1
9'2"5
5'2"4
13'6"12
4'4"7
18'9"
5'2"4
22'9"
4'1'6"8 1'6"8
1'2"52'10"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 12.07TC: From 55 plf at 12.07 to 55 plf at 24.40
BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 12.07BC: From 10 plf at 12.07 to 10 plf at 22.75BC: From 4 plf at 22.75 to 4 plf at 24.40
TC: 173 lb Conc. Load at 4.01TC: 110 lb Conc. Load at 6.07, 8.07,10.07,12.07BC: 143 lb Conc. Load at 4.01BC: 60 lb Conc. Load at 6.07, 8.07,10.07,12.07
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 24.35
BC 75 0.00 22.75Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
O 785 /- /- /-/168 /-
L 1398 /- /- /-/266 /-
P 271 /-31 /- /-/117 /-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =1.5LBrg Width = 5.5 Min Req =1.6
P Brg Width = 9.0 Min Req =1.5
Bearings O, L, & P Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - B 37 -17
B - C 155 -1033
C - D 89 -717
D - E 89 -717
Chords Tens.Comp.
E - F 484 -71
F - G 484 -71
G - H 148 -130
H - I 37 -17
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
O - N 44 -1N - M 921 -124
M - L 164 -12
Chords Tens.Comp.
L - K 107 -128K - J 52 -6
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - O 175 -771
B - N 904 -125
C - N 88 0
C - M 38 -242D - M 120 -383
M - E 873 -120
Webs Tens.Comp.
E - L 128 -998
L - G 114 -563
F - L 152 -336
G - K 129 0K - H 93 -141
H - J 126 -252
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.022 N 999 240
VERT(CL):0.035 N 999 180
HORZ(LL):0.006 J - -
HORZ(TL):0.009 J - -
Creep Factor: 2.0
Max TC CSI:0.554
Max BC CSI:0.418
Max Web CSI:0.345
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T24
Ply: 1
Qty:1
Wgt: 140.0 lbs
SEQN: 17573 / T14 / COMN
FROM:DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D E F G
H
I
JKLMNOP
5 12
3X8
3X4
4X8(**)
4X4
3X4
5X7(**)
4X4 3X4
5X7(**)
4X8(**)
4X4
3X8
3X4
13'6"12 9'2"4
4'0"1
4'0"1
9'2"5
5'2"4
11'4"8
2'2"4
13'6"12
2'2"4
18'9"
5'2"4
22'9"
4'
4'0"1
4'0"1
9'2"5
5'2"4
13'6"12
4'4"7
18'9"
5'2"4
22'9"
4'1'6"8 1'6"8
1'2"52'10"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 120 0.15 17.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 724 /- /-/371 /33 /275
F 680 /- /-/404 /162 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
F Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 96 -1122
Chords Tens.Comp.
C - D 42 -826
D - E 66 -104
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - G 980 -425
Chords Tens.Comp.
G - F 394 -191
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - G 255 -501
G - D 593 -129
Webs Tens.Comp.
D - F 306 -631
E - F 111 -119
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.19 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.039 C 999 240
VERT(CL):0.060 C 999 180
HORZ(LL):-0.022 E - -
HORZ(TL):0.035 E - -
Creep Factor: 2.0
Max TC CSI:0.491
Max BC CSI:0.743
Max Web CSI:0.244
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T25
Ply: 1
Qty:5
Wgt: 103.6 lbs
SEQN: 17592 / T81 / COMN
FROM:DRW:
.../...04/15/2020
(a)
(a)
10'1"2A
B
C
D
E
FG
5 12
8 12
3X4(**)
5X7(**)
5X5(**)
3X4
3X4(**)
4X5(R)
17'9"8
6'9"
6'9"
12'6"8
5'9"8
17'9"8
5'3"
9'9"8
9'9"8
17'9"8
8'1'6"8
4"5 10'6"63'2"111'1"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 120 0.15 17.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 724 /- /-/371 /33 /275
F 680 /- /-/404 /162 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
F Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 96 -1122
Chords Tens.Comp.
C - D 42 -826
D - E 66 -104
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - G 980 -425
Chords Tens.Comp.
G - F 394 -191
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - G 255 -501
G - D 593 -129
Webs Tens.Comp.
D - F 306 -631
E - F 111 -119
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.19 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.039 C 999 240
VERT(CL):0.060 C 999 180
HORZ(LL):-0.022 E - -
HORZ(TL):0.035 E - -
Creep Factor: 2.0
Max TC CSI:0.491
Max BC CSI:0.743
Max Web CSI:0.244
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T25
Ply: 1
Qty:5
Wgt: 103.6 lbs
SEQN: 17592 / T81 / COMN
FROM:DRW:
.../...04/15/2020
(a)
(a)
10'1"2A
B
C
D
E
FG
5 12
8 12
3X4(**)
5X7(**)
5X5(**)
3X4
3X4(**)
4X5(R)
17'9"8
6'9"
6'9"
12'6"8
5'9"8
17'9"8
5'3"
9'9"8
9'9"8
17'9"8
8'1'6"8
4"5 10'6"63'2"111'1"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.66Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
10-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 686 /- /-/367 /32 /275
G 592 /- /-/404 /165 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 0 -717
C - D 255 -1301
Chords Tens.Comp.
D - E 60 -732
E - F 85 -112
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 543 -314
C - K 1322 -639
Chords Tens.Comp.
K - I 1214 -580
I - H 532 -268
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - J 512 -884
K - J 678 -370
D - I 331 -714
I - E 482 -115
Webs Tens.Comp.
E - H 349 -691
H - G 335 -592
H - F 133 -149
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.19 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.392 J 535 240
VERT(CL):0.649 J 323 180
HORZ(LL):0.124 I - -
HORZ(TL):0.206 I - -
Creep Factor: 2.0
Max TC CSI:0.512
Max BC CSI:0.585
Max Web CSI:0.824
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T26
Ply: 1
Qty:3
Wgt: 107.8 lbs
SEQN: 17614 / T82 / COMN
FROM:DRW:
.../...04/15/2020
T2
B2
(a)
10'1"2A
B
C
D
E
F
G
HI
JK
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
17'9"8
6'1"4
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 10'6"63'2"111'1"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.66Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
10-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 686 /- /-/367 /32 /275
G 592 /- /-/404 /165 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 0 -717
C - D 255 -1301
Chords Tens.Comp.
D - E 60 -732
E - F 85 -112
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 543 -314
C - K 1322 -639
Chords Tens.Comp.
K - I 1214 -580
I - H 532 -268
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - J 512 -884
K - J 678 -370
D - I 331 -714
I - E 482 -115
Webs Tens.Comp.
E - H 349 -691
H - G 335 -592
H - F 133 -149
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.19 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.392 J 535 240
VERT(CL):0.649 J 323 180
HORZ(LL):0.124 I - -
HORZ(TL):0.206 I - -
Creep Factor: 2.0
Max TC CSI:0.512
Max BC CSI:0.585
Max Web CSI:0.824
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T26
Ply: 1
Qty:3
Wgt: 107.8 lbs
SEQN: 17614 / T82 / COMN
FROM:DRW:
.../...04/15/2020
T2
B2
(a)
10'1"2A
B
C
D
E
F
G
HI
JK
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
17'9"8
6'1"4
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 10'6"63'2"111'1"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/375 /46 /248
H 590 /- /-/371 /166 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 22 -717
C - D 320 -1299
Chords Tens.Comp.
D - E 116 -732
E - F 37 -113
F - G 5 -4
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 542 -321
C - L 1320 -664
Chords Tens.Comp.
L - J 1212 -602
J - I 533 -279
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 524 -884
L - K 678 -378
D - J 344 -712
J - E 482 -120
Webs Tens.Comp.
E - I 363 -692
I - H 330 -590
I - G 118 -145
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.393 K 533 240
VERT(CL):0.650 K 323 180
HORZ(LL):0.125 J - -
HORZ(TL):0.206 J - -
Creep Factor: 2.0
Max TC CSI:0.578
Max BC CSI:0.663
Max Web CSI:0.825
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T27
Ply: 1
Qty:1
Wgt: 105.0 lbs
SEQN: 17611 / T35 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
(a)
10'1"2A
B
C
D
E
F G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
16'3"8
4'7"4
17'9"8
1'6"
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 9'6"63'2"110'1"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-6-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/375 /46 /248
H 590 /- /-/371 /166 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 22 -717
C - D 320 -1299
Chords Tens.Comp.
D - E 116 -732
E - F 37 -113
F - G 5 -4
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 542 -321
C - L 1320 -664
Chords Tens.Comp.
L - J 1212 -602
J - I 533 -279
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 524 -884
L - K 678 -378
D - J 344 -712
J - E 482 -120
Webs Tens.Comp.
E - I 363 -692
I - H 330 -590
I - G 118 -145
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.393 K 533 240
VERT(CL):0.650 K 323 180
HORZ(LL):0.125 J - -
HORZ(TL):0.206 J - -
Creep Factor: 2.0
Max TC CSI:0.578
Max BC CSI:0.663
Max Web CSI:0.825
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T27
Ply: 1
Qty:1
Wgt: 105.0 lbs
SEQN: 17611 / T35 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
(a)
10'1"2A
B
C
D
E
F G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
16'3"8
4'7"4
17'9"8
1'6"
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 9'6"63'2"110'1"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is8-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/381 /66 /214
H 587 /- /-/331 /169 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 87 -716
C - D 408 -1298
Chords Tens.Comp.
D - E 187 -731
E - F 20 -112
F - G 5 -3
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 542 -330
C - L 1319 -699
Chords Tens.Comp.
L - J 1211 -636
J - I 532 -287
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 538 -883
L - K 677 -388
D - J 370 -711
J - E 481 -131
Webs Tens.Comp.
E - I 373 -691
I - H 322 -587
I - G 103 -142
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.394 K 532 240
VERT(CL):0.649 K 323 180
HORZ(LL):0.125 J - -
HORZ(TL):0.206 J - -
Creep Factor: 2.0
Max TC CSI:0.509
Max BC CSI:0.663
Max Web CSI:0.824
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T28
Ply: 1
Qty:1
Wgt: 102.2 lbs
SEQN: 17617 / T52 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E
F G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
14'3"8
2'7"4
17'9"8
3'6"
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 8'2"63'2"18'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is8-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/381 /66 /214
H 587 /- /-/331 /169 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 87 -716
C - D 408 -1298
Chords Tens.Comp.
D - E 187 -731
E - F 20 -112
F - G 5 -3
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 542 -330
C - L 1319 -699
Chords Tens.Comp.
L - J 1211 -636
J - I 532 -287
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 538 -883
L - K 677 -388
D - J 370 -711
J - E 481 -131
Webs Tens.Comp.
E - I 373 -691
I - H 322 -587
I - G 103 -142
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.394 K 532 240
VERT(CL):0.649 K 323 180
HORZ(LL):0.125 J - -
HORZ(TL):0.206 J - -
Creep Factor: 2.0
Max TC CSI:0.509
Max BC CSI:0.663
Max Web CSI:0.824
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T28
Ply: 1
Qty:1
Wgt: 102.2 lbs
SEQN: 17617 / T52 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E
F G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X5(**)
3X4
3X4
4X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
11'8"4
4'11"4
14'3"8
2'7"4
17'9"8
3'6"
2'6"5
2'6"5
3'5"
10"11
11'4"12
7'11"12
17'6"
6'1"4
17'9"8
3"8
1'6"8 1'4"5 8'2"63'2"18'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/370 /56 /238
H 590 /- /-/366 /160 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 32 -672
C - D 402 -1310
Chords Tens.Comp.
D - E 106 -622
E - F 146 -436
F - G 53 -69
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 493 -326
C - L 1329 -747
Chords Tens.Comp.
L - J 1231 -685
J - I 315 -169
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 531 -803
L - K 622 -385
D - J 462 -838
E - J 175 0
Webs Tens.Comp.
J - F 383 -237
F - I 324 -603
I - H 341 -590
I - G 84 -91
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.414 K 507 240
VERT(CL):0.684 K 307 180
HORZ(LL):0.132 J - -
HORZ(TL):0.218 J - -
Creep Factor: 2.0
Max TC CSI:0.554
Max BC CSI:0.566
Max Web CSI:0.597
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T29
Ply: 1
Qty:1
Wgt: 117.6 lbs
SEQN: 17620 / T78 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X7(**)
4X4(**)
3X8
5X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
12'3"8
5'6"8
14'3"8
2'
17'9"8
3'6"
2'6"5
2'6"5
3'5"
10"11
12'5"4
9'0"4
17'6"
5'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"16'10"69'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 685 /- /-/370 /56 /238
H 590 /- /-/366 /160 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 32 -672
C - D 402 -1310
Chords Tens.Comp.
D - E 106 -622
E - F 146 -436
F - G 53 -69
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 493 -326
C - L 1329 -747
Chords Tens.Comp.
L - J 1231 -685
J - I 315 -169
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 531 -803
L - K 622 -385
D - J 462 -838
E - J 175 0
Webs Tens.Comp.
J - F 383 -237
F - I 324 -603
I - H 341 -590
I - G 84 -91
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.414 K 507 240
VERT(CL):0.684 K 307 180
HORZ(LL):0.132 J - -
HORZ(TL):0.218 J - -
Creep Factor: 2.0
Max TC CSI:0.554
Max BC CSI:0.566
Max Web CSI:0.597
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T29
Ply: 1
Qty:1
Wgt: 117.6 lbs
SEQN: 17620 / T78 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4(R)
5X7(**)
4X4(**)
3X8
5X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
12'3"8
5'6"8
14'3"8
2'
17'9"8
3'6"
2'6"5
2'6"5
3'5"
10"11
12'5"4
9'0"4
17'6"
5'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"16'10"69'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/366 /58 /238
H 590 /- /-/370 /158 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 57 -751
C - D 409 -1329
Chords Tens.Comp.
D - E 199 -824
E - F 200 -632
F - G 78 -103
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 581 -350
C - L 1353 -755
Chords Tens.Comp.
L - J 1237 -688
J - I 570 -303
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 571 -948
L - K 722 -412
D - J 385 -692
E - J 363 -73
Webs Tens.Comp.
J - F 217 -111
F - I 385 -721
I - H 335 -590
I - G 123 -137
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.362 K 580 240
VERT(CL):0.597 K 351 180
HORZ(LL):0.115 I - -
HORZ(TL):0.190 I - -
Creep Factor: 2.0
Max TC CSI:0.474
Max BC CSI:0.690
Max Web CSI:0.646
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T30
Ply: 1
Qty:1
Wgt: 110.6 lbs
SEQN: 17623 / T77 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4
5X7(**)
4X4(**)
3X8
5X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
10'3"8
3'6"8
12'3"8
2'
17'9"8
5'6"
2'6"5
2'6"5
3'5"
10"11
10'5"4
7'0"4
17'6"
7'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"15'6"69'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/366 /58 /238
H 590 /- /-/370 /158 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 57 -751
C - D 409 -1329
Chords Tens.Comp.
D - E 199 -824
E - F 200 -632
F - G 78 -103
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 581 -350
C - L 1353 -755
Chords Tens.Comp.
L - J 1237 -688
J - I 570 -303
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 571 -948
L - K 722 -412
D - J 385 -692
E - J 363 -73
Webs Tens.Comp.
J - F 217 -111
F - I 385 -721
I - H 335 -590
I - G 123 -137
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.362 K 580 240
VERT(CL):0.597 K 351 180
HORZ(LL):0.115 I - -
HORZ(TL):0.190 I - -
Creep Factor: 2.0
Max TC CSI:0.474
Max BC CSI:0.690
Max Web CSI:0.646
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T30
Ply: 1
Qty:1
Wgt: 110.6 lbs
SEQN: 17623 / T77 / COMN
FROM:DRW:
.../...04/15/2020
T1
B2
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
3X4
5X7(**)
4X4(**)
3X8
5X5(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
10'3"8
3'6"8
12'3"8
2'
17'9"8
5'6"
2'6"5
2'6"5
3'5"
10"11
10'5"4
7'0"4
17'6"
7'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"15'6"69'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/362 /60 /238
H 591 /- /-/374 /156 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 123 -918
C - D 413 -1410
Chords Tens.Comp.
D - E 337 -1167
E - F 279 -939
F - G 103 -136
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 766 -416
C - L 1446 -757
Chords Tens.Comp.
L - J 1295 -677
J - I 988 -495
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 680 -1253
L - K 934 -487
D - J 323 -587
E - J 755 -291
Webs Tens.Comp.
J - F 125 -183
F - I 534 -1058
I - H 324 -591
I - G 161 -182
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.339 K 618 240
VERT(CL):0.560 K 374 180
HORZ(LL):0.110 I - -
HORZ(TL):0.181 I - -
Creep Factor: 2.0
Max TC CSI:0.956
Max BC CSI:0.775
Max Web CSI:0.448
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T31
Ply: 1
Qty:1
Wgt: 106.4 lbs
SEQN: 17626 / T76 / COMN
FROM:DRW:
.../...04/15/2020
B2
(a)
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
4X4
5X5(**)
4X4(**)
3X8
5X7(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
8'3"8
1'6"8
10'3"8
2'
17'9"8
7'6"
2'6"5
2'6"5
3'5"
10"11
8'5"4
5'0"4
17'6"
9'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"14'2"69'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/362 /60 /238
H 591 /- /-/374 /156 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 123 -918
C - D 413 -1410
Chords Tens.Comp.
D - E 337 -1167
E - F 279 -939
F - G 103 -136
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 766 -416
C - L 1446 -757
Chords Tens.Comp.
L - J 1295 -677
J - I 988 -495
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 680 -1253
L - K 934 -487
D - J 323 -587
E - J 755 -291
Webs Tens.Comp.
J - F 125 -183
F - I 534 -1058
I - H 324 -591
I - G 161 -182
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.339 K 618 240
VERT(CL):0.560 K 374 180
HORZ(LL):0.110 I - -
HORZ(TL):0.181 I - -
Creep Factor: 2.0
Max TC CSI:0.956
Max BC CSI:0.775
Max Web CSI:0.448
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T31
Ply: 1
Qty:1
Wgt: 106.4 lbs
SEQN: 17626 / T76 / COMN
FROM:DRW:
.../...04/15/2020
B2
(a)
10'1"2A
B
C
D
E F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X8
3X4(**)
4X4
5X5(**)
4X4(**)
3X8
5X7(**)
4X4
3X4(**)
17'9"8
6'9"
6'9"
8'3"8
1'6"8
10'3"8
2'
17'9"8
7'6"
2'6"5
2'6"5
3'5"
10"11
8'5"4
5'0"4
17'6"
9'0"12
17'9"8
3"8
1'6"8 1'4"5 9'2"63'2"14'2"69'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/359 /64 /240
G 591 /- /-/379 /155 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 154 -994
C - D 442 -1596
Chords Tens.Comp.
D - E 480 -1551
E - F 128 -167
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 851 -445
C - K 1626 -782
Chords Tens.Comp.
K - I 1459 -697
I - H 1791 -829
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - J 728 -1396
K - J 1030 -519
D - I 529 -152
I - E 209 -428
Webs Tens.Comp.
E - H 846 -1817
H - G 316 -591
H - F 198 -229
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.273 J 770 240
VERT(CL):0.450 J 466 180
HORZ(LL):0.096 H - -
HORZ(TL):0.159 H - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.841
Max Web CSI:0.856
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T32
Ply: 1
Qty:1
Wgt: 102.2 lbs
SEQN: 17629 / T66 / COMN
FROM:DRW:
.../...04/15/2020
T3
B2
(a)
10'1"2A
B
C
D E
F
G
HI
JK
5 12
8
12
3X4(**)
4X10
4X4(**)
4X4
4X4(**)
3X4
6X8(**)
5X5
3X4(**)
17'9"8
6'3"8
6'3"8
8'5"9
2'2"1
17'9"8
9'3"15
2'6"5
2'6"5
3'5"
10"11
6'7"
3'2"
17'6"
10'11"
17'9"8
3"8
1'6"8 1'4"5 9'2"62'11"129'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/359 /64 /240
G 591 /- /-/379 /155 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 154 -994
C - D 442 -1596
Chords Tens.Comp.
D - E 480 -1551
E - F 128 -167
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - J 851 -445
C - K 1626 -782
Chords Tens.Comp.
K - I 1459 -697
I - H 1791 -829
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - J 728 -1396
K - J 1030 -519
D - I 529 -152
I - E 209 -428
Webs Tens.Comp.
E - H 846 -1817
H - G 316 -591
H - F 198 -229
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.273 J 770 240
VERT(CL):0.450 J 466 180
HORZ(LL):0.096 H - -
HORZ(TL):0.159 H - -
Creep Factor: 2.0
Max TC CSI:0.838
Max BC CSI:0.841
Max Web CSI:0.856
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T32
Ply: 1
Qty:1
Wgt: 102.2 lbs
SEQN: 17629 / T66 / COMN
FROM:DRW:
.../...04/15/2020
T3
B2
(a)
10'1"2A
B
C
D E
F
G
HI
JK
5 12
8
12
3X4(**)
4X10
4X4(**)
4X4
4X4(**)
3X4
6X8(**)
5X5
3X4(**)
17'9"8
6'3"8
6'3"8
8'5"9
2'2"1
17'9"8
9'3"15
2'6"5
2'6"5
3'5"
10"11
6'7"
3'2"
17'6"
10'11"
17'9"8
3"8
1'6"8 1'4"5 9'2"62'11"129'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/356 /65 /239
H 591 /- /-/381 /152 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 141 -926
C - D 691 -1935
Chords Tens.Comp.
D - E 795 -2666
E - F 885 -3013
F - G 122 -163
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 775 -432
C - L 1981 -1062
Chords Tens.Comp.
L - J 1830 -980
J - I 1578 -782
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 706 -1272
L - K 947 -510
D - J 919 -111
J - E 260 -999
Webs Tens.Comp.
J - F 1600 -422
F - I 801 -1608
I - H 323 -591
I - G 192 -219
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.265 K 792 240
VERT(CL):0.437 K 480 180
HORZ(LL):0.095 D - -
HORZ(TL):0.156 D - -
Creep Factor: 2.0
Max TC CSI:0.930
Max BC CSI:0.772
Max Web CSI:0.722
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T33
Ply: 1
Qty:1
Wgt: 103.6 lbs
SEQN: 17632 / T83 / COMN
FROM:DRW:
.../...04/15/2020
T4
B2
(a)
10'1"2A
B
C
D E
F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X10
3X4(**)
4X4
4X4(**)
6X8(**)
5X5(**)
H0510(**)
5X5
3X4(**)
17'9"8
4'3"8
4'3"8
6'3"8
2'
8'9"
2'5"8
17'9"8
9'0"8
2'6"5
2'6"5
3'5"
10"11
17'6"
14'1"
17'9"8
3"8
1'6"8 1'4"5 9'2"62'1"123'2"19'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T4 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2 :B2 2x4 SP 2400f-2.0E:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 7 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79BC 39 0.15 3.27BC 120 3.27 17.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is
9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 684 /- /-/356 /65 /239
H 591 /- /-/381 /152 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
H Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 141 -926
C - D 691 -1935
Chords Tens.Comp.
D - E 795 -2666
E - F 885 -3013
F - G 122 -163
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - K 775 -432
C - L 1981 -1062
Chords Tens.Comp.
L - J 1830 -980
J - I 1578 -782
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - K 706 -1272
L - K 947 -510
D - J 919 -111
J - E 260 -999
Webs Tens.Comp.
J - F 1600 -422
F - I 801 -1608
I - H 323 -591
I - G 192 -219
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.265 K 792 240
VERT(CL):0.437 K 480 180
HORZ(LL):0.095 D - -
HORZ(TL):0.156 D - -
Creep Factor: 2.0
Max TC CSI:0.930
Max BC CSI:0.772
Max Web CSI:0.722
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T33
Ply: 1
Qty:1
Wgt: 103.6 lbs
SEQN: 17632 / T83 / COMN
FROM:DRW:
.../...04/15/2020
T4
B2
(a)
10'1"2A
B
C
D E
F
G
H
IJ
KL
5 12
8
12
3X4(**)
4X10
3X4(**)
4X4
4X4(**)
6X8(**)
5X5(**)
H0510(**)
5X5
3X4(**)
17'9"8
4'3"8
4'3"8
6'3"8
2'
8'9"
2'5"8
17'9"8
9'0"8
2'6"5
2'6"5
3'5"
10"11
17'6"
14'1"
17'9"8
3"8
1'6"8 1'4"5 9'2"62'1"123'2"19'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3 2x4 SP #1:
:T4 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 8.75TC: From 57 plf at 8.75 to 57 plf at 17.79BC: From 4 plf at -1.65 to 4 plf at 0.00
BC: From 10 plf at 0.00 to 10 plf at 17.79TC: 70 lb Conc. Load at 2.25BC: 33 lb Conc. Load at 2.25
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79
BC 89 0.15 17.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 779 /- /- /-/262 /-
G 598 /- /- /-/187 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 403 -1339
C - D 381 -1305
Chords Tens.Comp.
D - E 380 -1287
E - F 120 -165
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - I 1208 -355
I - H 1886 -573
Chords Tens.Comp.
H - G 1074 -343
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - I 352 -93
I - D 224 -696
D - H 237 -736
Webs Tens.Comp.
H - E 435 -7
E - G 360 -1126
F - G 103 -217
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.078 H 999 240
VERT(CL):0.129 H 999 180
HORZ(LL):-0.040 F - -
HORZ(TL):0.067 F - -
Creep Factor: 2.0
Max TC CSI:0.876
Max BC CSI:0.991
Max Web CSI:0.530
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T34
Ply: 1
Qty:1
Wgt: 100.8 lbs
SEQN: 17635 / T85 / COMN
FROM:DRW:
.../...04/15/2020
T3
T4
B2
(a)
(a)
10'1"2A
B
C D
E
F
GHI
5 12
8
12
3X4(**)
4X4(**)
3X4
4X4(**)
5X7(**)
6X8(**)
3X4(**)
4X5(R)
17'9"8
2'3"8
2'3"8
4'3"8
2'
8'9"
4'5"8
17'9"8
9'0"8
2'7"
2'7"
7'9"8
5'2"8
17'9"8
10'1'6"8
4"5 9'2"61'3"123'2"19'9"92. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T3 2x4 SP #1:
:T4 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #2 :B2 2x4 SP #1:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 8.75TC: From 57 plf at 8.75 to 57 plf at 17.79BC: From 4 plf at -1.65 to 4 plf at 0.00
BC: From 10 plf at 0.00 to 10 plf at 17.79TC: 70 lb Conc. Load at 2.25BC: 33 lb Conc. Load at 2.25
Plating Notes
(**) 6 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 17.79
BC 89 0.15 17.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 779 /- /- /-/262 /-
G 598 /- /- /-/187 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
G Brg Width = -Min Req =-Bearing B Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 403 -1339
C - D 381 -1305
Chords Tens.Comp.
D - E 380 -1287
E - F 120 -165
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - I 1208 -355
I - H 1886 -573
Chords Tens.Comp.
H - G 1074 -343
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - I 352 -93
I - D 224 -696
D - H 237 -736
Webs Tens.Comp.
H - E 435 -7
E - G 360 -1126
F - G 103 -217
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.078 H 999 240
VERT(CL):0.129 H 999 180
HORZ(LL):-0.040 F - -
HORZ(TL):0.067 F - -
Creep Factor: 2.0
Max TC CSI:0.876
Max BC CSI:0.991
Max Web CSI:0.530
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T34
Ply: 1
Qty:1
Wgt: 100.8 lbs
SEQN: 17635 / T85 / COMN
FROM:DRW:
.../...04/15/2020
T3
T4
B2
(a)
(a)
10'1"2A
B
C D
E
F
GHI
5 12
8
12
3X4(**)
4X4(**)
3X4
4X4(**)
5X7(**)
6X8(**)
3X4(**)
4X5(R)
17'9"8
2'3"8
2'3"8
4'3"8
2'
8'9"
4'5"8
17'9"8
9'0"8
2'7"
2'7"
7'9"8
5'2"8
17'9"8
10'1'6"8
4"5 9'2"61'3"123'2"19'9"9This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 15.79BC 75 0.15 15.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D*66 /- /-/39 /19 /20
Wind reactions based on MWFRS
D Brg Width = 189 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 48 -180
Chords Tens.Comp.
B - C 122 -166
Maximum Bot Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - E 114 -19
Chords Tens.Comp.
E - D 127 -11
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
E - B 163 -464
B - D 306 -133
Webs Tens.Comp.
C - D 190 -221
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.010 E 999 240
VERT(CL):0.023 E 999 180
HORZ(LL):-0.005 C - -
HORZ(TL):0.011 E - -
Creep Factor: 2.0
Max TC CSI:0.753
Max BC CSI:0.623
Max Web CSI:0.106
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T35
Ply: 1
Qty:1
Wgt: 82.6 lbs
SEQN: 17638 / T2 / SPEC
FROM:DRW:
.../...04/15/2020
T2
(a)
(a)
10'1"2
A
B
C
DE
5 12
8 12
3X4(**)
3X4
6X10(**)
3X4(**)
4X5(R)
15'9"8
6'9"
6'9"
15'9"8
9'0"8
6'7"4
6'7"4
15'9"8
9'2"4
4"5 9'2"63'2"12. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2 :T2 2x4 SP 2400f-2.0E:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 15.79BC 75 0.15 15.79Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is9-2-6.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
D*66 /- /-/39 /19 /20
Wind reactions based on MWFRS
D Brg Width = 189 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 48 -180
Chords Tens.Comp.
B - C 122 -166
Maximum Bot Chord Forces Per Ply (lbs)Chords Tens.Comp.
A - E 114 -19
Chords Tens.Comp.
E - D 127 -11
Maximum Web Forces Per Ply(lbs)Webs Tens.Comp.
E - B 163 -464
B - D 306 -133
Webs Tens.Comp.
C - D 190 -221
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.010 E 999 240
VERT(CL):0.023 E 999 180
HORZ(LL):-0.005 C - -
HORZ(TL):0.011 E - -
Creep Factor: 2.0
Max TC CSI:0.753
Max BC CSI:0.623
Max Web CSI:0.106
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T35
Ply: 1
Qty:1
Wgt: 82.6 lbs
SEQN: 17638 / T2 / SPEC
FROM:DRW:
.../...04/15/2020
T2
(a)
(a)
10'1"2
A
B
C
DE
5 12
8 12
3X4(**)
3X4
6X10(**)
3X4(**)
4X5(R)
15'9"8
6'9"
6'9"
15'9"8
9'0"8
6'7"4
6'7"4
15'9"8
9'2"4
4"5 9'2"63'2"1This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 120 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-10-3.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 646 /- /-/316 /203 /98
D 546 /- /-/241 /166 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 5.5 Min Req =1.5Bearings B & D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 351 -885
Chords Tens.Comp.
C - D 364 -885
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - E 750 -245
Chords Tens.Comp.
E - D 750 -245
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - E 279 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.025 E 999 240
VERT(CL):0.052 E 999 180
HORZ(LL):0.013 E - -
HORZ(TL):0.028 E - -
Creep Factor: 2.0
Max TC CSI:0.787
Max BC CSI:0.621
Max Web CSI:0.106
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T36
Ply: 1
Qty:1
Wgt: 64.4 lbs
SEQN: 17517 / T16 / COMN
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
E
5 12
3X4(**)
5X5(**)
5X5(**)
3X4(**)
16'9"
8'4"8
8'4"8
16'9"
8'4"8
8'4"8
8'4"8
16'9"
8'4"81'6"8
4"53'10"34'5"62. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 120 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-10-3.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 646 /- /-/316 /203 /98
D 546 /- /-/241 /166 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 5.5 Min Req =1.5Bearings B & D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 351 -885
Chords Tens.Comp.
C - D 364 -885
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - E 750 -245
Chords Tens.Comp.
E - D 750 -245
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - E 279 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.025 E 999 240
VERT(CL):0.052 E 999 180
HORZ(LL):0.013 E - -
HORZ(TL):0.028 E - -
Creep Factor: 2.0
Max TC CSI:0.787
Max BC CSI:0.621
Max Web CSI:0.106
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T36
Ply: 1
Qty:1
Wgt: 64.4 lbs
SEQN: 17517 / T16 / COMN
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
E
5 12
3X4(**)
5X5(**)
5X5(**)
3X4(**)
16'9"
8'4"8
8'4"8
16'9"
8'4"8
8'4"8
8'4"8
16'9"
8'4"81'6"8
4"53'10"34'5"6This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 120 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-8-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 646 /- /-/312 /195 /95
D 546 /- /-/236 /158 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 5.5 Min Req =1.5Bearings B & D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 308 -855
Chords Tens.Comp.
C - D 319 -855
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - E 715 -196
Chords Tens.Comp.
E - D 715 -196
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - E 287 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.033 E 999 240
VERT(CL):0.060 E 999 180
HORZ(LL):0.018 E - -
HORZ(TL):0.033 E - -
Creep Factor: 2.0
Max TC CSI:0.964
Max BC CSI:0.626
Max Web CSI:0.109
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T37
Ply: 1
Qty:1
Wgt: 64.4 lbs
SEQN: 17524 / T12 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
E
5 12
3X4(**)
4X8(**)
5X5(**)
3X4(**)
16'9"
8'
8'
16'9"
8'9"
16'9"
16'9"1'6"8
4"53'8"54'3"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 120 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-8-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 646 /- /-/312 /195 /95
D 546 /- /-/236 /158 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
D Brg Width = 5.5 Min Req =1.5Bearings B & D Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 308 -855
Chords Tens.Comp.
C - D 319 -855
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - E 715 -196
Chords Tens.Comp.
E - D 715 -196
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - E 287 0
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.033 E 999 240
VERT(CL):0.060 E 999 180
HORZ(LL):0.018 E - -
HORZ(TL):0.033 E - -
Creep Factor: 2.0
Max TC CSI:0.964
Max BC CSI:0.626
Max Web CSI:0.109
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T37
Ply: 1
Qty:1
Wgt: 64.4 lbs
SEQN: 17524 / T12 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C
D
E
5 12
3X4(**)
4X8(**)
5X5(**)
3X4(**)
16'9"
8'
8'
16'9"
8'9"
16'9"
16'9"1'6"8
4"53'8"54'3"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #1Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 100 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
#1 hip supports 6-0-0 jacks with no webs.
Left side jacks have 6-0-0 setback with 0-0-0 cantand 1-7-14 overhang. End jacks have 6-0-0 setbackwith 0-0-0 cant and 1-7-14 overhang. Right side jackshave 6-0-0 setback with 0-0-0 cant and 0-0-0overhang.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1040 /- /- /-/332 /-
E 936 /- /- /-/287 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
E Brg Width = 5.5 Min Req =1.5Bearings B & E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -16
B - C 582 -1829
Chords Tens.Comp.
C - D 540 -1906
D - E 587 -1839
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 1638 -512
Chords Tens.Comp.
F - E 1652 -518
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 394 -42
Webs Tens.Comp.
F - D 374 -33
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.067 F 999 240
VERT(CL):0.110 F 999 180
HORZ(LL):0.022 F - -
HORZ(TL):0.036 F - -
Creep Factor: 2.0
Max TC CSI:0.466
Max BC CSI:0.983
Max Web CSI:0.150
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T38
Ply: 1
Qty:1
Wgt: 71.4 lbs
SEQN: 17531 / T6 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C D
E
F
5 12
4X4(**)
4X4(**)
5X7(**)
4X4(**)
4X4(**)
16'9"
6'
6'
10'9"
4'9"
16'9"
6'
8'4"8
8'4"8
16'9"
8'4"81'6"8
4"52'10"53'5"82. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #1Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 5 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 16.75BC 100 0.15 16.60Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
#1 hip supports 6-0-0 jacks with no webs.
Left side jacks have 6-0-0 setback with 0-0-0 cantand 1-7-14 overhang. End jacks have 6-0-0 setbackwith 0-0-0 cant and 1-7-14 overhang. Right side jackshave 6-0-0 setback with 0-0-0 cant and 0-0-0overhang.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1040 /- /- /-/332 /-
E 936 /- /- /-/287 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
E Brg Width = 5.5 Min Req =1.5Bearings B & E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -16
B - C 582 -1829
Chords Tens.Comp.
C - D 540 -1906
D - E 587 -1839
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 1638 -512
Chords Tens.Comp.
F - E 1652 -518
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 394 -42
Webs Tens.Comp.
F - D 374 -33
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:0.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.067 F 999 240
VERT(CL):0.110 F 999 180
HORZ(LL):0.022 F - -
HORZ(TL):0.036 F - -
Creep Factor: 2.0
Max TC CSI:0.466
Max BC CSI:0.983
Max Web CSI:0.150
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T38
Ply: 1
Qty:1
Wgt: 71.4 lbs
SEQN: 17531 / T6 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2A
B
C D
E
F
5 12
4X4(**)
4X4(**)
5X7(**)
4X4(**)
4X4(**)
16'9"
6'
6'
10'9"
4'9"
16'9"
6'
8'4"8
8'4"8
16'9"
8'4"81'6"8
4"52'10"53'5"8This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 120 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-8-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 546 /- /-/207 /178 /75
E 546 /- /-/207 /178 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
E Brg Width = 5.5 Min Req =1.5Bearings A & E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 108 -202
B - C 438 -1120
Chords Tens.Comp.
C - D 438 -1120
D - E 108 -202
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 1096 -341
Chords Tens.Comp.
F - D 1096 -341
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 137 -24
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.267 C 723 240
VERT(CL):0.434 C 444 180
HORZ(LL):0.113 F - -
HORZ(TL):0.184 F - -
Creep Factor: 2.0
Max TC CSI:0.431
Max BC CSI:0.487
Max Web CSI:0.052
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T39
Ply: 1
Qty:1
Wgt: 63.0 lbs
SEQN: 17545 / T17 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2
A
B
C
D
EF
5 12
4X4(**)
8X8(**)
3X4
4X4(**)
16'9"
2'11"
2'11"
8'
5'1"
13'10"
5'10"
16'9"
2'11"
2'11"
2'11"
13'10"
10'11"
16'9"
2'11"2'11"4"1'4"52'8"53'8"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 120 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is3-8-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 546 /- /-/207 /178 /75
E 546 /- /-/207 /178 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
E Brg Width = 5.5 Min Req =1.5Bearings A & E Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 108 -202
B - C 438 -1120
Chords Tens.Comp.
C - D 438 -1120
D - E 108 -202
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - F 1096 -341
Chords Tens.Comp.
F - D 1096 -341
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - F 137 -24
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.267 C 723 240
VERT(CL):0.434 C 444 180
HORZ(LL):0.113 F - -
HORZ(TL):0.184 F - -
Creep Factor: 2.0
Max TC CSI:0.431
Max BC CSI:0.487
Max Web CSI:0.052
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T39
Ply: 1
Qty:1
Wgt: 63.0 lbs
SEQN: 17545 / T17 / HIPS
FROM:DRW:
.../...04/15/2020
10'1"2
A
B
C
D
EF
5 12
4X4(**)
8X8(**)
3X4
4X4(**)
16'9"
2'11"
2'11"
8'
5'1"
13'10"
5'10"
16'9"
2'11"
2'11"
2'11"
13'10"
10'11"
16'9"
2'11"2'11"4"1'4"52'8"53'8"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 113 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 546 /- /-/215 /187 /55
F 546 /- /-/215 /187 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
F Brg Width = 5.5 Min Req =1.5Bearings A & F Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 117 -202
B - C 675 -1391
C - D 641 -1358
Chords Tens.Comp.
D - E 676 -1391
E - F 118 -202
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - G 1400 -613
Chords Tens.Comp.
G - E 1400 -614
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - G 114 -138
Webs Tens.Comp.
G - D 114 -138
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.240 G 805 240
VERT(CL):0.390 G 494 180
HORZ(LL):0.099 G - -
HORZ(TL):0.161 G - -
Creep Factor: 2.0
Max TC CSI:0.434
Max BC CSI:0.972
Max Web CSI:0.044
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T40
Ply: 1
Qty:1
Wgt: 65.8 lbs
SEQN: 17548 / T5 / HIPS
FROM:DRW:
.../...04/15/2020
T2
10'1"2
A
B
C D
E
FG
5 12
4X4(**)
4X5(**)
3X4
4X5(**)
4X4(**)
16'9"
2'11"
2'11"
6'
3'1"
10'9"
4'9"
13'10"
3'1"
16'9"
2'11"
2'11"
2'11"
8'4"8
5'5"8
13'10"
5'5"8
16'9"
2'11"2'11"4"
4"51'10"51'2'10"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 113 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 546 /- /-/215 /187 /55
F 546 /- /-/215 /187 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
F Brg Width = 5.5 Min Req =1.5Bearings A & F Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 117 -202
B - C 675 -1391
C - D 641 -1358
Chords Tens.Comp.
D - E 676 -1391
E - F 118 -202
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - G 1400 -613
Chords Tens.Comp.
G - E 1400 -614
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - G 114 -138
Webs Tens.Comp.
G - D 114 -138
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.240 G 805 240
VERT(CL):0.390 G 494 180
HORZ(LL):0.099 G - -
HORZ(TL):0.161 G - -
Creep Factor: 2.0
Max TC CSI:0.434
Max BC CSI:0.972
Max Web CSI:0.044
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T40
Ply: 1
Qty:1
Wgt: 65.8 lbs
SEQN: 17548 / T5 / HIPS
FROM:DRW:
.../...04/15/2020
T2
10'1"2
A
B
C D
E
FG
5 12
4X4(**)
4X5(**)
3X4
4X5(**)
4X4(**)
16'9"
2'11"
2'11"
6'
3'1"
10'9"
4'9"
13'10"
3'1"
16'9"
2'11"
2'11"
2'11"
8'4"8
5'5"8
13'10"
5'5"8
16'9"
2'11"2'11"4"
4"51'10"51'2'10"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC: From 55 plf at 0.00 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 12.75TC: From 55 plf at 12.75 to 55 plf at 16.75BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 12.74BC: From 10 plf at 12.74 to 10 plf at 16.75TC: 260 lb Conc. Load at 4.01,12.74TC: 177 lb Conc. Load at 6.06, 8.06, 8.69,10.69BC: 50 lb Conc. Load at 4.01,12.74BC: 22 lb Conc. Load at 6.06, 8.06, 8.69,10.69
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 101 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 1110 /- /- /-/353 /-
G 1110 /- /- /-/353 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
G Brg Width = 5.5 Min Req =1.5Bearings A & G Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 67 -209
B - C 1009 -3070
C - D 1120 -3444
Chords Tens.Comp.
D - E 1120 -3444
E - F 1009 -3070
F - G 67 -209
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 3262 -1067
Chords Tens.Comp.
H - F 3262 -1067
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - H 187 -54
D - H 127 -285
Webs Tens.Comp.
H - E 187 -54
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.473 D 408 240
VERT(CL):0.761 D 253 180
HORZ(LL):0.157 C - -
HORZ(TL):0.253 C - -
Creep Factor: 2.0
Max TC CSI:0.819
Max BC CSI:0.976
Max Web CSI:0.071
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T41
Ply: 2
Qty:1
Wgt: 134.4 lbs
SEQN: 17566 / T13 / HIPS
FROM:DRW:
.../...04/15/2020
T2
10'1"2
A
B
C D E
F
GH
5 12
6X6(**)
5X5(**)3X4
3X8
5X5(**)
6X6(**)
16'9"
2'11"
2'11"
4'
1'1"
8'4"8
4'4"8
12'9"
4'4"8
13'10"
1'1"
16'9"
2'11"
2'11"
2'11"
8'4"8
5'5"8
13'10"
5'5"8
16'9"
2'11"2'11"4"
4"5
1'0"5
1'2'0"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP 2400f-2.0E :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Nailnote
Nail Schedule:0.131"x3", min. nailsTop Chord: 1 Row @12.00" o.c.Bot Chord: 1 Row @12.00" o.c.Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nailsin each row to avoid splitting.
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)
TC: From 55 plf at 0.00 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 12.75TC: From 55 plf at 12.75 to 55 plf at 16.75BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 12.74BC: From 10 plf at 12.74 to 10 plf at 16.75TC: 260 lb Conc. Load at 4.01,12.74TC: 177 lb Conc. Load at 6.06, 8.06, 8.69,10.69BC: 50 lb Conc. Load at 4.01,12.74BC: 22 lb Conc. Load at 6.06, 8.06, 8.69,10.69
Plating Notes
(**) 4 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -2.92 13.83BC 101 0.08 10.84Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-0-5.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 1110 /- /- /-/353 /-
G 1110 /- /- /-/353 /-
Wind reactions based on MWFRS
A Brg Width = 5.5 Min Req =1.5
G Brg Width = 5.5 Min Req =1.5Bearings A & G Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 67 -209
B - C 1009 -3070
C - D 1120 -3444
Chords Tens.Comp.
D - E 1120 -3444
E - F 1009 -3070
F - G 67 -209
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - H 3262 -1067
Chords Tens.Comp.
H - F 3262 -1067
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - H 187 -54
D - H 127 -285
Webs Tens.Comp.
H - E 187 -54
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.473 D 408 240
VERT(CL):0.761 D 253 180
HORZ(LL):0.157 C - -
HORZ(TL):0.253 C - -
Creep Factor: 2.0
Max TC CSI:0.819
Max BC CSI:0.976
Max Web CSI:0.071
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T41
Ply: 2
Qty:1
Wgt: 134.4 lbs
SEQN: 17566 / T13 / HIPS
FROM:DRW:
.../...04/15/2020
T2
10'1"2
A
B
C D E
F
GH
5 12
6X6(**)
5X5(**)3X4
3X8
5X5(**)
6X6(**)
16'9"
2'11"
2'11"
4'
1'1"
8'4"8
4'4"8
12'9"
4'4"8
13'10"
1'1"
16'9"
2'11"
2'11"
2'11"
8'4"8
5'5"8
13'10"
5'5"8
16'9"
2'11"2'11"4"
4"5
1'0"5
1'2'0"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 5.42TC: From 55 plf at 5.42 to 55 plf at 9.42
BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 5.41BC: From 10 plf at 5.41 to 10 plf at 9.42TC: 173 lb Conc. Load at 4.01, 5.41
BC: 143 lb Conc. Load at 4.01, 5.41
Plating Notes
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 9.42
BC 75 0.00 9.42Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
I 703 /- /- /-/160 /-
G 600 /- /- /-/109 /-
Wind reactions based on MWFRS
I Brg Width = 5.5 Min Req =1.5
G Brg Width = 5.5 Min Req =1.5Bearings I & G Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 147 -883
C - D 114 -777
Chords Tens.Comp.
D - E 114 -777
E - F 146 -883
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
I - H 80 -3
Chords Tens.Comp.
H - G 82 -19
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - I 172 -671
B - H 732 -113
D - H 114 0
Webs Tens.Comp.
H - F 718 -97
F - G 122 -568
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.021 E 999 240
VERT(CL):0.037 E 999 180
HORZ(LL):-0.005 E - -
HORZ(TL):0.008 E - -
Creep Factor: 2.0
Max TC CSI:0.283
Max BC CSI:0.200
Max Web CSI:0.279
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T42
Ply: 1
Qty:1
Wgt: 57.4 lbs
SEQN: 17513 / T23 / HIPS
FROM:DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D E
F
GHI
5 12
3X8
3X4
3X4(**)3X4
4X8
3X4(**)
4X4
3X4
9'5"
4'
4'
5'5"
1'5"
9'5"
4'
4'8"8
4'8"8
9'5"
4'8"81'6"81'2"52'10"52. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.25 / Plate Dur.Fac.=1.25)TC: From 55 plf at -1.65 to 55 plf at 4.00TC: From 28 plf at 4.00 to 28 plf at 5.42TC: From 55 plf at 5.42 to 55 plf at 9.42
BC: From 4 plf at -1.65 to 4 plf at 0.00BC: From 10 plf at 0.00 to 10 plf at 4.01BC: From 5 plf at 4.01 to 5 plf at 5.41BC: From 10 plf at 5.41 to 10 plf at 9.42TC: 173 lb Conc. Load at 4.01, 5.41
BC: 143 lb Conc. Load at 4.01, 5.41
Plating Notes
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 9.42
BC 75 0.00 9.42Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Wind
Wind loads and reactions based on MWFRS.
Additional Notes
The overall height of this truss excluding overhang is2-10-5.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
I 703 /- /- /-/160 /-
G 600 /- /- /-/109 /-
Wind reactions based on MWFRS
I Brg Width = 5.5 Min Req =1.5
G Brg Width = 5.5 Min Req =1.5Bearings I & G Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 -17
B - C 147 -883
C - D 114 -777
Chords Tens.Comp.
D - E 114 -777
E - F 146 -883
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
I - H 80 -3
Chords Tens.Comp.
H - G 82 -19
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - I 172 -671
B - H 732 -113
D - H 114 0
Webs Tens.Comp.
H - F 718 -97
F - G 122 -568
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.021 E 999 240
VERT(CL):0.037 E 999 180
HORZ(LL):-0.005 E - -
HORZ(TL):0.008 E - -
Creep Factor: 2.0
Max TC CSI:0.283
Max BC CSI:0.200
Max Web CSI:0.279
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T42
Ply: 1
Qty:1
Wgt: 57.4 lbs
SEQN: 17513 / T23 / HIPS
FROM:DRW:
.../...04/15/2020
W1 W1
10'1"2
A
B
C D E
F
GHI
5 12
3X8
3X4
3X4(**)3X4
4X8
3X4(**)
4X4
3X4
9'5"
4'
4'
5'5"
1'5"
9'5"
4'
4'8"8
4'8"8
9'5"
4'8"81'6"81'2"52'10"5This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T1 2x4 SP #1:
:T2 2x6 SP 2400f-2.0E:Bot chord 2x4 SP #1 :B2, B4 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W2, W4 2x4 SP #2::W9 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21
BC 98 0.15 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1210 /- /-/496 /84 /282
J 2112 /- /-/485 /314 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
J Brg Width = 5.5 Min Req =2.0Bearings B & J Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 353 -2436
C - D 20 -519
D - E 48 -370
Chords Tens.Comp.
E - F 218 -457
F - G 266 -525
G - H 24 -95
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - N 2201 -675
N - M 6913 -1934
M - L 7151 -1999
Chords Tens.Comp.
L - K 5151 -1026
K - J 2556 -314
J - I 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - N 733 -144
C - O 618 -1983
N - O 1270 -4764
D - O 281 -180
O - M 120 -6
O - L 928 -1882O - P 1040 -5098
E - Q 353 -236
L - P 691 -286
P - K 709 -2562
P - R 288 -2469
Webs Tens.Comp.
F - Q 127 -146
Q - G 929 -404
Q - S 195 -686
K - R 614 -142
R - J 473 -3185
R - T 733 -201G - S 343 -744
J - H 482 -123
S - T 348 -801
T - J 345 -922
H - I 70 -257
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.704 D 408 240
VERT(CL):1.217 D 236 229
HORZ(LL):0.357 D - -
HORZ(TL):0.620 D - -
Creep Factor: 2.0
Max TC CSI:0.690
Max BC CSI:0.991
Max Web CSI:0.957
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T43
Ply: 1
Qty:3
Wgt: 243.6 lbs
SEQN: 17495 / T67 / ATIC
FROM:DRW:
.../...04/15/2020
T1
T2
B2 B4
W2
W4
W9
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F G H
IJKLMN
O P
Q
R
S
T
5 12
8
12
4X5(**)
8X8(**)
6X12(**)
3X4
H0514(I)
3X4
3X4
4X5
4X8
4X5(**)
4X4
H0514(**)
5X7
4X4
3X4(**)
3X4(**)
6X10(**)
4X5(R)
3X4(**)
24'5"1'9"8
6'9"
6'9"
13'10"12
7'1"12
18'3"
4'4"4
23'11"4
5'8"4
26'2"8
2'3"4
6'9"
6'9"
13'9"
7'
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T1 2x4 SP #1:
:T2 2x6 SP 2400f-2.0E:Bot chord 2x4 SP #1 :B2, B4 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W2, W4 2x4 SP #2::W9 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 9 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21
BC 98 0.15 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00
windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1210 /- /-/496 /84 /282
J 2112 /- /-/485 /314 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.5
J Brg Width = 5.5 Min Req =2.0Bearings B & J Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 353 -2436
C - D 20 -519
D - E 48 -370
Chords Tens.Comp.
E - F 218 -457
F - G 266 -525
G - H 24 -95
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - N 2201 -675
N - M 6913 -1934
M - L 7151 -1999
Chords Tens.Comp.
L - K 5151 -1026
K - J 2556 -314
J - I 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - N 733 -144
C - O 618 -1983
N - O 1270 -4764
D - O 281 -180
O - M 120 -6
O - L 928 -1882O - P 1040 -5098
E - Q 353 -236
L - P 691 -286
P - K 709 -2562
P - R 288 -2469
Webs Tens.Comp.
F - Q 127 -146
Q - G 929 -404
Q - S 195 -686
K - R 614 -142
R - J 473 -3185
R - T 733 -201G - S 343 -744
J - H 482 -123
S - T 348 -801
T - J 345 -922
H - I 70 -257
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.704 D 408 240
VERT(CL):1.217 D 236 229
HORZ(LL):0.357 D - -
HORZ(TL):0.620 D - -
Creep Factor: 2.0
Max TC CSI:0.690
Max BC CSI:0.991
Max Web CSI:0.957
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T43
Ply: 1
Qty:3
Wgt: 243.6 lbs
SEQN: 17495 / T67 / ATIC
FROM:DRW:
.../...04/15/2020
T1
T2
B2 B4
W2
W4
W9
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F G H
IJKLMN
O P
Q
R
S
T
5 12
8
12
4X5(**)
8X8(**)
6X12(**)
3X4
H0514(I)
3X4
3X4
4X5
4X8
4X5(**)
4X4
H0514(**)
5X7
4X4
3X4(**)
3X4(**)
6X10(**)
4X5(R)
3X4(**)
24'5"1'9"8
6'9"
6'9"
13'10"12
7'1"12
18'3"
4'4"4
23'11"4
5'8"4
26'2"8
2'3"4
6'9"
6'9"
13'9"
7'
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x6 SP
2400f-2.0E::T3 2x4 SP #1:Bot chord 2x4 SP 2400f-2.0E :B1 2x4 SP #1::B3 2x4 SP #2:Webs 2x4 SP #3 :W3, W5 2x4 SP #2::W10 2x4 SP 2400f-2.0E::Lt Slider 2x6 SP #2: BLOCK LENGTH = 2.200'
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21
BC 27 0.29 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of5600 # ( 213.71 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 5600 213.71 TC 0.00 26.21
5600 456.37 BC 0.46 12.88Case 2: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88Case 3: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88
Case 4: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
X 1217 /- /-/2893 /2857 /282
M 2105 /- /-/938 /912 /-
Wind reactions based on MWFRS
X Brg Width = 5.5 Min Req =3.4
M Brg Width = 5.5 Min Req =2.0Bearings X & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 6571 -6852
C - D 6032 -6300
D - E 5983 -6255
E - F 4887 -5042
Chords Tens.Comp.
F - G 2803 -2849
G - H 457 -551
H - I 1120 -1026
I - J 1388 -1351
J - K 420 -422
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - Q 5833 -5825
Q - P 6805 -2185P - O 7045 -1992
Chords Tens.Comp.
O - N 5090 -1020
N - M 2517 -306M - L 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - Q 525 -500
Q - E 735 -626
Q - R 2469 -4696
E - R 1128 -1933
F - R 821 -774R - P 125 -42
R - O 927 -1838
R - S 1036 -5034
G - T 2196 -2318
O - S 677 -287
S - N 734 -2541
S - U 282 -2428
Webs Tens.Comp.
H - T 905 -909
T - I 1457 -1391
T - V 637 -792
N - U 601 -142
U - M 470 -3150U - W 738 -339
I - V 1264 -1139
J - V 419 -649
M - K 534 -281
V - W 866 -845
W -M 864 -973
K - L 113 -265
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.704 F 405 240
VERT(CL):1.219 F 234 228
HORZ(LL):0.454 O - -
HORZ(TL):0.638 F - -
Creep Factor: 2.0
Max TC CSI:0.723
Max BC CSI:0.991
Max Web CSI:0.970
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T43A
Ply: 1
Qty:1
Wgt: 254.1 lbs
SEQN: 17526 / T10 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3
B1
B3
W3
W5
W10
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F
G
H I J K
LMNOPQ
R S
T
U
V
W
X
5 12
8
12
3X4(**)6X10(**)
H0514(**)(I)
H1010(**)
4X5
H0514(I)
6X6(**)
4X5
4X8
4X5(**)
4X4
H0514(**)
5X7
4X4
4X4
3X4(**)
6X10(**)
4X5(R)
3X4(**)
24'5"1'9"8
4'0"7
4'0"7
6'9"
2'8"9
13'10"12
7'1"12
18'3"
4'4"4
21'2"14
2'11"14
23'11"4
2'8"6
26'2"8
2'3"4
6'7"4
6'7"4
13'9"
7'1"12
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP 2400f-2.0E :T2 2x6 SP
2400f-2.0E::T3 2x4 SP #1:Bot chord 2x4 SP 2400f-2.0E :B1 2x4 SP #1::B3 2x4 SP #2:Webs 2x4 SP #3 :W3, W5 2x4 SP #2::W10 2x4 SP 2400f-2.0E::Lt Slider 2x6 SP #2: BLOCK LENGTH = 2.200'
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
All plates are 3X4 except as noted.
(I) - plates so marked were sized using 0%Fabrication Tolerance, 0 degrees RotationalTolerance, and/or zero Positioning Tolerance.
(**) 10 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21
BC 27 0.29 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Truss transfers a maximum horizontal load of5600 # ( 213.71 plf ) along top chord, from eitherdirection, to supports where indicated. Diaphragm andconnections are to be designed by Engineer of Record.Drag Loads: Force(#) (PLF) Mbr Start EndCase 1: 5600 213.71 TC 0.00 26.21
5600 456.37 BC 0.46 12.88Case 2: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88Case 3: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88
Case 4: 5600 213.71 TC 0.00 26.215600 456.37 BC 0.46 12.88
Drag loads applied to wind load cases parallel totruss.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,
Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
X 1217 /- /-/2893 /2857 /282
M 2105 /- /-/938 /912 /-
Wind reactions based on MWFRS
X Brg Width = 5.5 Min Req =3.4
M Brg Width = 5.5 Min Req =2.0Bearings X & M Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 6571 -6852
C - D 6032 -6300
D - E 5983 -6255
E - F 4887 -5042
Chords Tens.Comp.
F - G 2803 -2849
G - H 457 -551
H - I 1120 -1026
I - J 1388 -1351
J - K 420 -422
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - Q 5833 -5825
Q - P 6805 -2185P - O 7045 -1992
Chords Tens.Comp.
O - N 5090 -1020
N - M 2517 -306M - L 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
D - Q 525 -500
Q - E 735 -626
Q - R 2469 -4696
E - R 1128 -1933
F - R 821 -774R - P 125 -42
R - O 927 -1838
R - S 1036 -5034
G - T 2196 -2318
O - S 677 -287
S - N 734 -2541
S - U 282 -2428
Webs Tens.Comp.
H - T 905 -909
T - I 1457 -1391
T - V 637 -792
N - U 601 -142
U - M 470 -3150U - W 738 -339
I - V 1264 -1139
J - V 419 -649
M - K 534 -281
V - W 866 -845
W -M 864 -973
K - L 113 -265
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Varies by Ld Case
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.704 F 405 240
VERT(CL):1.219 F 234 228
HORZ(LL):0.454 O - -
HORZ(TL):0.638 F - -
Creep Factor: 2.0
Max TC CSI:0.723
Max BC CSI:0.991
Max Web CSI:0.970
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T43A
Ply: 1
Qty:1
Wgt: 254.1 lbs
SEQN: 17526 / T10 / ATIC
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
T2
T3
B1
B3
W3
W5
W10
(a)(a)
(a)
(a)
(a)
10'1"2A
B
C
D
E
F
G
H I J K
LMNOPQ
R S
T
U
V
W
X
5 12
8
12
3X4(**)6X10(**)
H0514(**)(I)
H1010(**)
4X5
H0514(I)
6X6(**)
4X5
4X8
4X5(**)
4X4
H0514(**)
5X7
4X4
4X4
3X4(**)
6X10(**)
4X5(R)
3X4(**)
24'5"1'9"8
4'0"7
4'0"7
6'9"
2'8"9
13'10"12
7'1"12
18'3"
4'4"4
21'2"14
2'11"14
23'11"4
2'8"6
26'2"8
2'3"4
6'7"4
6'7"4
13'9"
7'1"12
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Right cantilever is exposed to wind
Additional Notes
Full Height Blocking reinforcement required toprevent buckling of members over the bearings:bearing 2 located at 23.96'
Negative reaction(s) of -2857# MAX. Requires upliftconnection. See Maximum Reactions.
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Job Number:86460
Pujadas Res.
Truss Label:T43A
Ply: 1
Qty:1
Wgt: 254.1 lbs
SEQN: 17526 / T10 / ATIC
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1 :T2 2x6 SP 2400f-2.0E:
:T4 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #1 :B2, B4 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W2, W4 2x4 SP #2::W9 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21BC 98 0.15 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1378 /- /-/536 /108 /282
I 1939 /- /-/457 /256 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.6
I Brg Width = 5.5 Min Req =1.8Bearings B & I Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 453 -2856
C - D 0 -947
D - E 122 -726
Chords Tens.Comp.
E - F 229 -507
F - G 262 -510
G - H 105 -459
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - N 2588 -767
N - M 6820 -1916
M - L 7044 -1978
Chords Tens.Comp.
L - K 5274 -1059
K - J 2883 -396
J - I 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - N 659 -126
C - O 628 -2022
N - O 1159 -4287
D - O 253 -141
O - M 127 -2
O - L 878 -1668O - P 983 -4847
E - Q 11 -288
L - P 606 -265
P - K 659 -2357
P - R 286 -2437
Webs Tens.Comp.
F - Q 109 -34
Q - G 521 -304
Q - S 185 -645
K - R 597 -140
R - J 462 -3122
R - T 702 -193G - S 308 -593
J - H 2323 -530
S - T 313 -648
T - J 310 -769
H - I 484 -2141
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.713 D 438 250
VERT(CL):1.231 D 253 250
HORZ(LL):0.354 D - -
HORZ(TL):0.614 D - -
Creep Factor: 2.0
Max TC CSI:0.688
Max BC CSI:0.968
Max Web CSI:0.948
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T44
Ply: 1
Qty:3
Wgt: 243.6 lbs
SEQN: 17502 / T72 / ATIC
FROM:DRW:
.../...04/15/2020
T2
T4
B2 B4
W2
W4
W9
(a)(a)
(a)
(a)
(a)(a)
(a)
10'1"2A
B
C
D
E
F G H
IJKLMN
O P
Q
R
S
T
5 12
8
12
4X5(**)
8X8(**)
6X12(**)
3X4
8X12(**)
3X4
3X4
4X5
5X5
4X5(**)
3X4
H0514(**)
5X7
3X4
3X4(**)
3X4(**)
6X10(**)
5X7(**)
3X8(**)
26'2"8
6'9"
6'9"
13'10"12
7'1"12
18'3"
4'4"4
23'11"4
5'8"4
26'2"8
2'3"4
6'9"
6'9"
13'9"
7'
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"42. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #1 :T2 2x6 SP 2400f-2.0E:
:T4 2x4 SP 2400f-2.0E:Bot chord 2x4 SP #1 :B2, B4 2x4 SP 2400f-2.0E:Webs 2x4 SP #3 :W2, W4 2x4 SP #2::W9 2x4 SP 2400f-2.0E:
Lumber value set "13B" uses design values
approved 1/30/2013 by ALSC
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Plating Notes
(**) 11 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -1.60 26.21BC 98 0.15 26.21Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Collar-tie braced with continuous lateral bracing at24" oc. or rigid ceiling.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Attic room loading from 13-10-12 to 23-11-4: LiveLoad: 40 PSF. Dead Load: 10 PSF Ceiling: 10 PSF,Kneewalls: 10 PSF
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Right end vertical not exposed to wind pressure.
Additional Notes
The overall height of this truss excluding overhang is10-10-1.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
B 1378 /- /-/536 /108 /282
I 1939 /- /-/457 /256 /-
Wind reactions based on MWFRS
B Brg Width = 5.5 Min Req =1.6
I Brg Width = 5.5 Min Req =1.8Bearings B & I Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 37 0
B - C 453 -2856
C - D 0 -947
D - E 122 -726
Chords Tens.Comp.
E - F 229 -507
F - G 262 -510
G - H 105 -459
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - N 2588 -767
N - M 6820 -1916
M - L 7044 -1978
Chords Tens.Comp.
L - K 5274 -1059
K - J 2883 -396
J - I 0 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
C - N 659 -126
C - O 628 -2022
N - O 1159 -4287
D - O 253 -141
O - M 127 -2
O - L 878 -1668O - P 983 -4847
E - Q 11 -288
L - P 606 -265
P - K 659 -2357
P - R 286 -2437
Webs Tens.Comp.
F - Q 109 -34
Q - G 521 -304
Q - S 185 -645
K - R 597 -140
R - J 462 -3122
R - T 702 -193G - S 308 -593
J - H 2323 -530
S - T 313 -648
T - J 310 -769
H - I 484 -2141
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: > 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE, HS
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.713 D 438 250
VERT(CL):1.231 D 253 250
HORZ(LL):0.354 D - -
HORZ(TL):0.614 D - -
Creep Factor: 2.0
Max TC CSI:0.688
Max BC CSI:0.968
Max Web CSI:0.948
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:T44
Ply: 1
Qty:3
Wgt: 243.6 lbs
SEQN: 17502 / T72 / ATIC
FROM:DRW:
.../...04/15/2020
T2
T4
B2 B4
W2
W4
W9
(a)(a)
(a)
(a)
(a)(a)
(a)
10'1"2A
B
C
D
E
F G H
IJKLMN
O P
Q
R
S
T
5 12
8
12
4X5(**)
8X8(**)
6X12(**)
3X4
8X12(**)
3X4
3X4
4X5
5X5
4X5(**)
3X4
H0514(**)
5X7
3X4
3X4(**)
3X4(**)
6X10(**)
5X7(**)
3X8(**)
26'2"8
6'9"
6'9"
13'10"12
7'1"12
18'3"
4'4"4
23'11"4
5'8"4
26'2"8
2'3"4
6'9"
6'9"
13'9"
7'
16'11"
3'2"
18'6"8
1'7"8
20'5"15
1'11"7 23'11"4
3'5"5
26'2"8
2'3"41'6"8
4"5 10'10"13'2"110'0"8
9'2"96'0"108'0"129'4"121'4"11'5"4This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.00 / Plate Dur.Fac.=1.00)TC: From 100 plf at 0.00 to 100 plf at 5.91BC: From 10 plf at 0.00 to 10 plf at 5.91TC: 749 lb Conc. Load at 2.42
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 5.91BC 71 0.00 5.91Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
The TC of this truss shall be braced with attachedspans at 24" oc in lieu of structural sheathing.
Hangers / Ties
Recommended hanger connections are based onmanufacturer tested capacities and calculations.Conditions may exist that require differentconnections than indicated. Refer to manufacturer
publication for additional information.
(J) Hanger Support Required, by othersBearing E (5'7"14, 10'1"2) LUS26Supporting Member: (3)1.75x16 2.0E Microllam LVL(4) 0.148"x3" nails into supportingmember,(3) 0.148"x3" nails into supportedmember.
Additional Notes
Truss must be installed as shown with top chord up.
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
H 767 /- /- /- /- /-
E 631 /- /- /- /- /-
H Brg Width = -Min Req =-
E Brg Width = -Min Req =-
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 0 -31
B - C 0 -1154
Chords Tens.Comp.
C - D 1 -12
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
H - G 1172 0
G - F 1154 0
Chords Tens.Comp.
F - E 1137 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - H 2 -88
H - B 0 -1298
B - G 0 -158
Webs Tens.Comp.
F - C 170 0
C - E 0 -1281
D - E 52 -71
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:NA
Speed:NA mph
Enclosure: NA
Category: NA
EXP: NAKzt: NA
Mean Height: NA ft
TCDL: NA psf
BCDL: NA psf
MWFRS Parallel Dist: NA
C&C Dist a: NA ft
Loc. from endwall: NA
I: NA GCpi: NA
Wind Duration: NA
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.022 G 999 480
VERT(CL):0.039 G 999 360
HORZ(LL):0.008 A - -
HORZ(TL):0.015 A - -
Creep Factor: 2.0
Max TC CSI:0.835
Max BC CSI:0.640
Max Web CSI:0.308
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T45
Ply: 1
Qty:6
Wgt: 29.4 lbs
SEQN: 17567 / T79 / FLAT
FROM:DRW:
.../...04/15/2020
W1
W1
10'1"2
A B C D
EFGH
3X4
4X4
4X4
3X4 3X4
4X4 3X4
4X4
5'10"14
1'11"2
1'11"2
3'11"12
2'0"10
5'10"14
1'11"2
2'0"14
2'0"14
3'10"
1'9"2
5'10"14
2'0"141'4"2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2Webs 2x4 SP #3 :W1 2x6 SP #2:
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Special Loads
------(Lumber Dur.Fac.=1.00 / Plate Dur.Fac.=1.00)TC: From 100 plf at 0.00 to 100 plf at 5.91BC: From 10 plf at 0.00 to 10 plf at 5.91TC: 749 lb Conc. Load at 2.42
Plating Notes
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.00 5.91BC 71 0.00 5.91Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
The TC of this truss shall be braced with attachedspans at 24" oc in lieu of structural sheathing.
Hangers / Ties
Recommended hanger connections are based onmanufacturer tested capacities and calculations.Conditions may exist that require differentconnections than indicated. Refer to manufacturer
publication for additional information.
(J) Hanger Support Required, by othersBearing E (5'7"14, 10'1"2) LUS26Supporting Member: (3)1.75x16 2.0E Microllam LVL(4) 0.148"x3" nails into supportingmember,(3) 0.148"x3" nails into supportedmember.
Additional Notes
Truss must be installed as shown with top chord up.
The overall height of this truss excluding overhang is1-4-0.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
H 767 /- /- /- /- /-
E 631 /- /- /- /- /-
H Brg Width = -Min Req =-
E Brg Width = -Min Req =-
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 0 -31
B - C 0 -1154
Chords Tens.Comp.
C - D 1 -12
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
H - G 1172 0
G - F 1154 0
Chords Tens.Comp.
F - E 1137 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
A - H 2 -88
H - B 0 -1298
B - G 0 -158
Webs Tens.Comp.
F - C 170 0
C - E 0 -1281
D - E 52 -71
Loading Criteria (psf)
TCLL:40.00
TCDL:10.00
BCLL:0.00
BCDL:5.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std:NA
Speed:NA mph
Enclosure: NA
Category: NA
EXP: NAKzt: NA
Mean Height: NA ft
TCDL: NA psf
BCDL: NA psf
MWFRS Parallel Dist: NA
C&C Dist a: NA ft
Loc. from endwall: NA
I: NA GCpi: NA
Wind Duration: NA
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: No
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.022 G 999 480
VERT(CL):0.039 G 999 360
HORZ(LL):0.008 A - -
HORZ(TL):0.015 A - -
Creep Factor: 2.0
Max TC CSI:0.835
Max BC CSI:0.640
Max Web CSI:0.308
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T45
Ply: 1
Qty:6
Wgt: 29.4 lbs
SEQN: 17567 / T79 / FLAT
FROM:DRW:
.../...04/15/2020
W1
W1
10'1"2
A B C D
EFGH
3X4
4X4
4X4
3X4 3X4
4X4 3X4
4X4
5'10"14
1'11"2
1'11"2
3'11"12
2'0"10
5'10"14
1'11"2
2'0"14
2'0"14
3'10"
1'9"2
5'10"14
2'0"141'4"This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP #2 :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -3.29 12.67BC 75 0.09 10.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is6-6-15.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 476 /- /-/209 /143 /222
F 589 /- /-/270 /174 /-
Wind reactions based on MWFRS
A Brg Width = 3.5 Min Req =1.5
F Brg Width = 3.5 Min Req =1.5Bearings A & F Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 92 -253
B - C 174 -449
Chords Tens.Comp.
C - D 229 -515
D - E 68 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - G 399 -137
C - G 116 -52
G - D 404 -128
Webs Tens.Comp.
G - F 17 -10
D - F 332 -575
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 20.96 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.386 424 240
VERT(CL):0.602 272 180
HORZ(LL):0.266 - -
HORZ(TL):0.445 - -
Creep Factor: 2.0
Max TC CSI:0.954
Max BC CSI:0.333
Max Web CSI:0.163
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T46
Ply: 1
Qty:6
Wgt: 71.4 lbs
SEQN: 17561 / T47 / COMN
FROM:DRW:
.../...04/15/2020
T2
17'5"14
19'5"14
A
B
C
D
E
FG
8
12
3X4(B1)
5X5(**)
3X4
3X4
4X5(**)
13'11"8
3'3"8
3'3"8
9'4"
6'0"8
13'11"8
4'7"8
3'3"8
3'3"8
9'7"8
6'4"
13'11"8
4'4"2'
4"5 1'5"154'6"152'6'6"152. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x6 SP #2 :T2 2x4 SP #2:
Bot chord 2x4 SP #2Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
(**) 2 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeter
edge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 -3.29 12.67BC 75 0.09 10.67Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
The overall height of this truss excluding overhang is6-6-15.
Top Chord overhang(s) may be field trimmed.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
A 476 /- /-/209 /143 /222
F 589 /- /-/270 /174 /-
Wind reactions based on MWFRS
A Brg Width = 3.5 Min Req =1.5
F Brg Width = 3.5 Min Req =1.5Bearings A & F Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 92 -253
B - C 174 -449
Chords Tens.Comp.
C - D 229 -515
D - E 68 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - G 399 -137
C - G 116 -52
G - D 404 -128
Webs Tens.Comp.
G - F 17 -10
D - F 332 -575
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 20.96 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.386 424 240
VERT(CL):0.602 272 180
HORZ(LL):0.266 - -
HORZ(TL):0.445 - -
Creep Factor: 2.0
Max TC CSI:0.954
Max BC CSI:0.333
Max Web CSI:0.163
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.20
Job Number:86460
Pujadas Res.
Truss Label:T46
Ply: 1
Qty:6
Wgt: 71.4 lbs
SEQN: 17561 / T47 / COMN
FROM:DRW:
.../...04/15/2020
T2
17'5"14
19'5"14
A
B
C
D
E
FG
8
12
3X4(B1)
5X5(**)
3X4
3X4
4X5(**)
13'11"8
3'3"8
3'3"8
9'4"
6'0"8
13'11"8
4'7"8
3'3"8
3'3"8
9'7"8
6'4"
13'11"8
4'4"2'
4"5 1'5"154'6"152'6'6"15This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #3:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 25.10
BC 120 0.00 25.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
8-7-13.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
S*70 /- /-/28 /19 /9
Wind reactions based on MWFRS
S Brg Width = 303 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 124 -197
B - C 106 -169
C - D 93 -142
D - E 77 -114
E - F 62 -87
F - G 57 -70
G - H 77 -60
H - I 122 -57I - J 123 -69
Chords Tens.Comp.
J - K 123 -69
K - L 122 -57
L - M 77 -60
M - N 61 -74
N - O 66 -91
O - P 81 -118
P - Q 96 -146
Q - R 110 -173R - S 128 -201
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A -AI 174 -107
AI-AH 177 -110
AH-AG 178 -112
AG-AF 179 -113
AF-AE 179 -114
AE-AD 180 -115
AD-AC 181 -115
AC-AB 182 -116
AB-AA 180 -116
Chords Tens.Comp.
AA- Z 184 -119
Z - Y 183 -118
Y - X 183 -118
X - W 182 -117
W -V 182 -116
V - U 181 -115
U - T 180 -113
T - S 178 -110
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AJ-AK 18 0
Webs Tens.Comp.
AK-AL 18 0
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
B -AI 84 -87
C -AH 62 -71
D -AG 58 -75
E -AF 58 -75
F -AE 58 -75
G -AD 60 -75
H -AC 79 -73
Gables Tens.Comp.
AL-AA 15 -101
AL- K 27 -94
Z - L 79 -73
Y - M 60 -75
X - N 58 -75
W -O 58 -75
V - P 58 -75
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 17.15 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.004 J 999 240
VERT(CL):0.006 J 999 239
HORZ(LL):-0.004 G - -
HORZ(TL):0.005 H - -
Creep Factor: 2.0
Max TC CSI:0.071
Max BC CSI:0.118
Max Web CSI:0.129
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:V01
Ply: 1
Qty:1
Wgt: 191.8 lbs
SEQN: 17586 / T70 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
B2
12'8"3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
TUVWXYZAAABACADAEAFAGAHAI
AJ AK
AL
8
12
3X4(**)
4X4
5X5(**)
3X4(**)
25'3"
1'11"8 1'4"
(TYP)
12'7"8
12'7"8
25'3"
12'7"8
25'3"
25'3"
2"138'7"132. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #3:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 25.10
BC 120 0.00 25.25Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
8-7-13.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
S*70 /- /-/28 /19 /9
Wind reactions based on MWFRS
S Brg Width = 303 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 124 -197
B - C 106 -169
C - D 93 -142
D - E 77 -114
E - F 62 -87
F - G 57 -70
G - H 77 -60
H - I 122 -57I - J 123 -69
Chords Tens.Comp.
J - K 123 -69
K - L 122 -57
L - M 77 -60
M - N 61 -74
N - O 66 -91
O - P 81 -118
P - Q 96 -146
Q - R 110 -173R - S 128 -201
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A -AI 174 -107
AI-AH 177 -110
AH-AG 178 -112
AG-AF 179 -113
AF-AE 179 -114
AE-AD 180 -115
AD-AC 181 -115
AC-AB 182 -116
AB-AA 180 -116
Chords Tens.Comp.
AA- Z 184 -119
Z - Y 183 -118
Y - X 183 -118
X - W 182 -117
W -V 182 -116
V - U 181 -115
U - T 180 -113
T - S 178 -110
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AJ-AK 18 0
Webs Tens.Comp.
AK-AL 18 0
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
B -AI 84 -87
C -AH 62 -71
D -AG 58 -75
E -AF 58 -75
F -AE 58 -75
G -AD 60 -75
H -AC 79 -73
Gables Tens.Comp.
AL-AA 15 -101
AL- K 27 -94
Z - L 79 -73
Y - M 60 -75
X - N 58 -75
W -O 58 -75
V - P 58 -75
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 17.15 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.004 J 999 240
VERT(CL):0.006 J 999 239
HORZ(LL):-0.004 G - -
HORZ(TL):0.005 H - -
Creep Factor: 2.0
Max TC CSI:0.071
Max BC CSI:0.118
Max Web CSI:0.129
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:V01
Ply: 1
Qty:1
Wgt: 191.8 lbs
SEQN: 17586 / T70 / GABL
FROM:
Page 1 of 2
DRW:
.../...04/15/2020
B2
12'8"3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
TUVWXYZAAABACADAEAFAGAHAI
AJ AK
AL
8
12
3X4(**)
4X4
5X5(**)
3X4(**)
25'3"
1'11"8 1'4"
(TYP)
12'7"8
12'7"8
25'3"
12'7"8
25'3"
25'3"
2"138'7"13This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
I -AJ 27 -94
AJ-AB 13 -101J -AK 0 -47
U - Q 62 -71
T - R 84 -88
Job Number:86460
Pujadas Res.
Truss Label:V01
Ply: 1
Qty:1
Wgt: 191.8 lbs
SEQN: 17586 / T70 / GABL
FROM:
Page 2 of 2
DRW:
.../...04/15/2020
This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.
2. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #3:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 21.68
BC 75 0.00 21.83Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
7-3-13.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AE*68 /- /-/26 /17 /9
Wind reactions based on MWFRS
AE Brg Width = 274 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 98 -150
B - C 71 -114
C - D 60 -87
D - E 44 -59
E - F 49 -50
F - G 93 -46
G - H 102 -62
Chords Tens.Comp.
H - I 102 -62
I - J 93 -46
J - K 58 -60
K - L 59 -74
L - M 74 -101
M - N 86 -129
N - O 112 -164
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A -AA 147 -87
AA- Z 151 -90Z - Y 153 -91
Y - X 154 -92
X - W 155 -93
W -V 156 -94
V - U 155 -94
Chords Tens.Comp.
U - T 156 -95
T - S 155 -95S - R 157 -104
R - Q 156 -103
Q - P 156 -102
P - O 154 -99
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AB-AC 16 -1
Webs Tens.Comp.
AC-AD 16 -1
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
B -AA 105 -126
C - Z 52 -58
D - Y 59 -76
E - X 60 -75
F - W 77 -72
G -AB 40 -99
AB- V 23 -108
H -AC 0 -34
Gables Tens.Comp.
AD- U 24 -108
AD- I 40 -99
T - J 77 -72
S - K 60 -75
R - L 59 -76
Q - M 52 -58
P - N 105 -127
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 17.82 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.003 H 999 240
VERT(CL):0.004 P 999 206
HORZ(LL):-0.003 F - -
HORZ(TL):0.004 F - -
Creep Factor: 2.0
Max TC CSI:0.063
Max BC CSI:0.099
Max Web CSI:0.094
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:V02
Ply: 1
Qty:1
Wgt: 149.8 lbs
SEQN: 17589 / T84 / GABL
FROM:DRW:
.../...04/15/2020
B2
14'0"3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
PQRSTUVWXYZAA
AB AC
AD
AE
8
12
3X4(**)
4X4
5X5(**)
3X4(**)
22'4"4
2'11"1'4"(TYP)
6"5
6"5
11'5"4
10'11"
22'4"4
10'11"
22'10"9
6"5
6"5
6"5
22'4"4
21'9"15
22'10"9
6"57'3"132. Apex Technology is a fictitious name owned by Jax Apex Technology Inc., Florida Corporation. Florida Engineer
Business No. 7547 - 9000 Regency Square BLVD, Suite 100, Jacksonville, FL 32211 - 904.821.5200
NOTES:
1. This drawing is not sufficient alone for installation. Additional instructions accompanying this truss drawing, include BCSI 1-03,
should be used in conjunction with the architectural plans during installation.
PE No. 60839 PE No. 58544 PE No. 71457 PE No. 85166 PE No. 88590
Michael G Kozlowski Jeffrey P Arneson Derek B Murray Justin Lanier Russell T Dukes
Lumber
Value Set: 13B (Effective 6/1/2013)
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP #3:Webs 2x4 SP #3
Lumber value set "13B" uses design valuesapproved 1/30/2013 by ALSC
Plating Notes
All plates are 3X4 except as noted.
(**) 3 plate(s) require special positioning. Refer toscaled plate plot details for special positioningrequirements.
Plate positions consider a 0.50 inch truss perimeteredge distance.
Purlins
In lieu of structural panels or rigid ceiling use purlinsto laterally brace chords as follows:Chord Spacing(in oc) Start(ft) End(ft)TC 24 0.15 21.68
BC 75 0.00 21.83Apply purlins to any chords above or below fillersat 24" OC unless shown otherwise above.
Loading
Truss passed check for 20 psf additional bottomchord live load in areas with 42"-high x 24"-wideclearance.
Bottom chord checked for 10.00 psf non-concurrentlive load.
Truss designed for unbalanced load using 0.00/1.00windward/leeward factors.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Additional Notes
See DWGS A14030ENC101014 & GBLLETIN1014 forgable wind bracing and other requirements.
The overall height of this truss excluding overhang is
7-3-13.
Maximum Reactions (lbs), or *=PLF
Gravity Non-Gravity
Loc R+/ R- / Rh / Rw / U / RL
AE*68 /- /-/26 /17 /9
Wind reactions based on MWFRS
AE Brg Width = 274 Min Req =-
Bearing A Fcperp = 565psi.
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A - B 98 -150
B - C 71 -114
C - D 60 -87
D - E 44 -59
E - F 49 -50
F - G 93 -46
G - H 102 -62
Chords Tens.Comp.
H - I 102 -62
I - J 93 -46
J - K 58 -60
K - L 59 -74
L - M 74 -101
M - N 86 -129
N - O 112 -164
Maximum Bot Chord Forces Per Ply (lbs)
Chords Tens.Comp.
A -AA 147 -87
AA- Z 151 -90Z - Y 153 -91
Y - X 154 -92
X - W 155 -93
W -V 156 -94
V - U 155 -94
Chords Tens.Comp.
U - T 156 -95
T - S 155 -95S - R 157 -104
R - Q 156 -103
Q - P 156 -102
P - O 154 -99
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
AB-AC 16 -1
Webs Tens.Comp.
AC-AD 16 -1
Maximum Gable Forces Per Ply (lbs)
Gables Tens.Comp.
B -AA 105 -126
C - Z 52 -58
D - Y 59 -76
E - X 60 -75
F - W 77 -72
G -AB 40 -99
AB- V 23 -108
H -AC 0 -34
Gables Tens.Comp.
AD- U 24 -108
AD- I 40 -99
T - J 77 -72
S - K 60 -75
R - L 59 -76
Q - M 52 -58
P - N 105 -127
Loading Criteria (psf)
TCLL:20.00
TCDL:7.00
BCLL:0.00
BCDL:5.00
Des Ld:32.00
NCBCLL:10.00
Soffit:2.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-10
Speed:130 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 17.82 ft
TCDL: 4.2 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:FBC 2017 RES
TPI Std:2014
Rep Fac: Yes
FT/RT:30(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.003 H 999 240
VERT(CL):0.004 P 999 206
HORZ(LL):-0.003 F - -
HORZ(TL):0.004 F - -
Creep Factor: 2.0
Max TC CSI:0.063
Max BC CSI:0.099
Max Web CSI:0.094
Mfg Specified Camber:
VIEW Ver: 18.02.01A.0205.19
Job Number:86460
Pujadas Res.
Truss Label:V02
Ply: 1
Qty:1
Wgt: 149.8 lbs
SEQN: 17589 / T84 / GABL
FROM:DRW:
.../...04/15/2020
B2
14'0"3
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
PQRSTUVWXYZAA
AB AC
AD
AE
8
12
3X4(**)
4X4
5X5(**)
3X4(**)
22'4"4
2'11"1'4"(TYP)
6"5
6"5
11'5"4
10'11"
22'4"4
10'11"
22'10"9
6"5
6"5
6"5
22'4"4
21'9"15
22'10"9
6"57'3"13This item may be digitally signed and sealed with a digital signature. Printed copies of digitally signed documents are not considered signed and sealed and the signature must be verified on any electronic copies.