70 W Dutton Island Rd RES20-0167 2nd submittal plan review commentsPermit Number: RES20-0167
Site Address: 70 W DUTTON ISLAND RD
City, State Zip Code: ATLANTIC BEACH, FL 32233
Applied: 6/16/2020 Approved:
Issued:
Parent Permit:
Parent Project:
Applicant: <NONE>
Owner: HIONIDES LUCKY
Contractor: <NONE>
Description: new single-family home
Finaled:
Status: AWAITING REVISION
Details:
LIST OF REVIEWS
SENT DATE RETURNED
DATE DUE DATE TYPE CONTACT STATUS REMARKS
Review Group: 2ND REVIEW
8/12/2020 8/12/2020 SUBMITTAL
COMPLETENESS Permit Tech APPROVED
Notes:
3 ATTACHMENTS - ZONING REQUIREMENTS & TOPO
8/12/2020 8/31/2020 8/26/2020 ZONING Zoning DENIED
Notes:
Duplicate Structures: Section 24-81(h) prohibits duplicate or externally similar structures within 500 feet of one another. In determining compliance
with this provision, a minimum of four (4) of the following characteristics shall be substantially different. The revised plans have met numbers 1 and 2
listed below. Two more must be met.
(1) Roof design and roof color.
(2) Exterior finish materials, excluding paint color.
(3) Window sizes and shape.
(4) Main entry door style and location.
(5) Number of stories.
(6) Attached/detached garage.
(7) Front or side entrance garage (if attached).
8/12/2020 8/13/2020 8/26/2020 BUILDING Building APPROVED
Notes:
Review Fee attached. Approval pending all department approvals.
Printed: Friday, 04 September, 2020 1 of 2
Permit Reviews
City of Atlantic Beach
8/12/2020 8/25/2020 8/26/2020 PUBLIC WORKS Public Works DENIED Also Reviewed by Steve
Swann-See Comments
Notes:
Comparing the pre-development survey submitted with the permit application revision with the site plan submitted with the original application
indicates that up to 1.5 feet of fill is proposed to be added to this lot. It appears that much of this fill has already been added to this site.
Sec. 24-70. - Land clearing and alteration of site grade or topography.
No lands shall be cleared, grubbed, filled, excavated or topographically altered by any means, and no vegetation on any parcel or lot disturbed, prior to
issuance of all required approvals and development permits authorizing such clearing or alteration. Except as required to meet coastal construction
codes as set forth within a valid permit from the Florida Department of Environmental Protection; or as required to meet applicable flood zone or
stormwater regulations pursuant to valid permits, the grade, elevation or topography of any parcel, development or redevelopment site shall not be
altered.
Review Group: AUTO
6/16/2020 6/16/2020 SUBMITTAL
COMPLETENESS Jennifer Johnston APPROVED
W/CONDITIONS
Notes:
received via FTP site, uploaded as 15 attachments; recorded NOC required prior to first inspection
6/16/2020 6/17/2020 6/26/2020 BUILDING Building APPROVED
Notes:
Pending all department approvals.
6/16/2020 8/3/2020 6/26/2020 PUBLIC UTILITIES Public Utilities APPROVED
W/CONDITIONS
Notes:
6/16/2020 6/26/2020 6/26/2020 PUBLIC WORKS Public Works DENIED
Notes:
Must provide a pre-development TOPO.
Provide construction site management plan including location of silt fence, dumpster, portable toilet. Right-of-Way Permit is required if using right-of-
way for construction parking.
6/16/2020 6/16/2020 6/26/2020 ZONING Zoning DENIED
Notes:
Duplicate Structures: Section 24-81(h) prohibits duplicate or externally similar structures within 500 feet of one another. In determining compliance
with this provision, a minimum of four (4) of the following characteristics shall be substantially different.
(1) Roof design and roof color.
(2) Exterior finish materials, excluding paint color.
(3) Window sizes and shape.
(4) Main entry door style and location.
(5) Number of stories.
(6) Attached/detached garage.
(7) Front or side entrance garage (if attached).
Printed: Friday, 04 September, 2020 2 of 2
Permit Reviews