1600 Selva Marina Drive 16-CNEW-954 (Fire) -,,. , N' ,SONf,' voi7lyS 0 'PEST ti E tsk.QQ Fire Plans Review Fire Prevention Division 214 N. Hogan Street, Room 281 Jacksonville, Florida 32202 April 26, 2016 RPC 1600 Selva Marina 16-CNEW-954 Fire Review Please correct or provide the following to obtain plans approval. When resubmitting corrected sheets, please provide a written narrative letter responding to our comments, along with clouded areas on revised sheets clearly showing areas where changes or corrections have occurred. The intended occupancy indicated on the submitted drawings conflicts with the 5th Edition Florida Fire Prevention Code, Section 6.1.2.1*. The combined occupancy load exceeds 50 or more persons, thus defining the occupancy as "Assembly". Provide the occupant load calculations in accordance with the 5th Edition Florida Fire prevention Code, Section 5th Edition Florida Fire Prevention Code, Section 12.2.4*, Section 12.2.4.1 The number of means of egress shall be in accordance with Section 7.4, other than exits for fenced outdoor assembly Provide exit tactile signs in accordance with the 5th Edition Florida Fire Prevention Code, Section 7.10.1.3 Provide light-frame truss type construction sign in accordance with Florida Statute 69A- 60.0081 4 1 0 i The location of the Kitchen Hood exhaust fan is not in compliance with NFPA 96, Section 7.8.3 (2011 Edition) Please provide proof of meeting minimum required fire flow requirements for proposed building per NFPA 1 18.4 and Table 18.4.5.1.2. This can be accomplished by contacting JEA and obtain hydrant flow test information conducted within the last 12 months and providing report with next submission. Flow data can also be obtained by private provider as long as it is witnessed by our office. Hydrant must be within 500' of proposed building measured via drivable fire department access road. 2