306 2nd st HVAC 2013 CITY OF ATLANTIC BEACH
j 800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 13-00003434 Date 9/24/13
Property Address . . . . . . 306 2ND ST
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . RES SF DISTRICT
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
MORTON WILLIAM K ET AL DONALD CARTER PLUMBING INC
961 LEW BLVD P O BOX 735
ST.AUGUSTINE FL 320805462 CALLAHAN FL 32011
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 3/23/14
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
fOB ADDRESS: �U& ST PERMIT#
PROJECT VALUE $ 3Z.00 `eo ARI# 5 1-7 1 9 0'2- REQUIRED
_Air Handling Equipment Only Air Handling Unit & Condenser Condenser Only
STEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit _ _
Heat: Unit Quantity— BTU's Per Unit _ Seer Rating ,
Duct Systems: Total CFM REQUIRED
ZEPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity f Tons Per Unit 2-
Heat: Unit Quantity I BTU's Per Unit Zy_v� Seer Rating
Duct Systems: Total CFM REQUIRED
+IRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
+IRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
# Vented Wall Furnaces Refrigerator Condenser BTU's
# Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
)THER:
ermit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
its application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
ot. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
'roperty Owners Name� Phone Number 7_0
✓lechanical Company '„I wn n r" Office Phone2111 31 K5 Fax 24 t 37q S
;o. Address: ��S L City 3�X CA- State Zip32 1 SO
License Holder(Print): State Certification/Registration# CAU 39
Notarized Signature of License HolderD �----
�i ;.,, RICHARD TOMPKINS Before me this 2 3 day of 20
Commission#FF 040399
=; azz Expires July 29,2017
Bonded ThmTroy Fain inswame8WiW7019 Signature of Notary Public t
Job:
+ wrightsoft Project Summary Date: September 20,2013
Entire House By: Aaron Thacker
Donovan Heat&Air
315 6th Ave S, Jacksonville Beach, FL 32250 Phone 904-241-3785 Fax:904241-3745 Email:aaron@donownac.com Web:www.DonovarLAC.com
For: Bill Morton
306 2nd St,Atlantic Beach, FL 32233
Notes:
Design Information
Weather: Jacksonville Mayport Naval, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 39 OF Outside db 99 OF
Inside db 70 OF Inside db 75 OF
Design TD 31 OF Design TD 24 OF
Daily range L
Relative humidity 50
Moisture difference 69 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 10754 Btuh Structure 9911 Btuh
Ducts 1856 Btuh Ducts 3243 Btuh
Central vent(0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 12610 Btuh Use manufacturer's data n
Rate/swing multiplier 1.04
Infiltration Equipment sensible load 13680 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average 241 Btuh
Fireplaces 0 Structure 2241
Ducts 9W Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area (ft') 1140 1140 Equipment latent load 3158 Btuh
Volume (ft') 9120 9120
Air changes/hour 0.45 0.23 Equipment total load 16838 Btuh
Equiv.AVF (cfm) 68 35 Req. total capacity at 0.70 SHR 1.6 ton
Heating Equipment Summary Cooling Equipment Summary
Make Tempstar Make Tempstar
Trade 13 SEER N SERIES R41 OA HP Trade 13 SEER N
Cond N4H324A(G)KARIES R41 OA HP
Model N4H324A(G)KA` Coil FEM4P24"A
AHRI ref no3853298 AHRI ref no3853298
Efficiency 8 HSPF Efficiency 11.0 EER, 13 SEER
Heating input Sensible cooling 15820 Btuh
Heating output 23000 Btuh @ 47°F Latent cooling 6780 Btuh
Temperature rise 28 °F Total cooling 22600 Btuh
Actual air flow 753 cfm Actual air flow 753 cfm
Air flow factor 0.060 cfm/Btuh Air flow factor 0.057 cfm/Btuh
0 in H2O Static pressure 0 in H2O
Static pressure
Space thermostat Load sensible heat ratio 0.81
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
2013-Sep-23 07:35:55
' wrightsoft Right-Suite®Universal 8.0 24 RSU05995 Page 1
r' C;l'` C:\Users\Owner\Documents\Wrightsoft MVAC\Bogus 2 ton.rup Calc=MJ8 Front Door faces W