1855 N Sherry Dr RES21-0010 Revision PacketRevision Request/Correction to Comments City of Atlantic Beach Building Department 8 00 Semin ol e Rd, Atl an t ic Be ach, FL 32 2 33 **ALL INFORMATION HIGHLIGHTED IN GRAV IS REQUIRED . Phone : (9 04) 24 7-5826 Email : Building-Dept@coab.us PERM IT #: RES21-0010 0 Revision to Issued Permit OR D Corrections to Comments Date: 01/25/2021 Project Address: 1855 SHERRY DR IVE N. ATLAN TI C BEAC H, FL 32233 Contractor/Contact Name: BILL BRYAN -------------------------------- Contact Phone: (904) 651 -5869 Email : coastlin eserv@comcast.net ------------- Description of Proposed Revision/ Corrections: alteration to kitch en area fra m ing, Drawi ngs Attached I_B_IL_L_B_R_Y_A_N _________ affirm the revision/correction to comments is inclusive of the proposed changes. (printed name) • Will proposed revision /corrections add additional square footage to origina l submittal? 0No D Yes (additional s.f. to be added: ____________ ) •~ill propose~ revision~c_o r rec~ions ad~ addi_t i~nal increase in building value to original submittal ? ~No D Yes (add1t1onal increase In building value:$ _________ ) (Contractor must sign i f increase in va luation) *Signature of Contractor/ Agent: ______________________ _ (Office Use Only) ~ Approved D Denied D Not Applicable to Department Perm it Fee Due $ ------ Revision/Plan Review Comments _____________________________ _ Department Review Required: Building Planning & Zoning Tree Admini strator Public Works Public Utilities Pub l ic Safety Fire Services Rev i ewed By Date Upda ted 10/1 7/18 Permit Number RES21-0010 Issued 01/08/2021 Contractor: Coastline Services of PVB, LLC William J Bryan State License# RR282811651 City of Atlantic Beach/ Attn: Mike Jones 01/23/21 Pursuant to your request, I am writing to explain the actions which led to Coastline Services' "Stop Work Notice" at 1855 Sherry Drive North. After opening the wait on January 11th, it came to our attention that there would need to be an alteration to framing if we were to completely remove soffits as indicated on the new kitchen floor plan provided by the designer. At the time, it appeared to me the framing adjustment was sufficient for the year the house was built. Unfortunately, I should have contacted the architect/engineer to visit the site and prepare the drawings/stamps needed along with a Revision Request/Correction form for the building department to review and approve before starting any alterations to framing. Coastline Services prides itself in staying in compliance with all city and state building codes, regulations and ethics. I accept full responsibility for this decision. I am sorry for any inconvenience this has caused. In the seventeen years Coastline Services has been in business, this is the first violation we've incurred. Coastline Services will make every effort to continue its long standing policy of excellence. Sincerely, William J. Bryan Coastline Services of PVB, LLC 382 4th Avenue South Jacksonville Beach, Florida 32250 904/651-5869 L I V I N G R O O M 2 S T O R Y S P A C E R E F - ' - ' < t : t : [ F K I T C H E N E X I S T I N G F L O O R P L A N W I G H T R E S I D E N C E 1 8 5 5 N O R T H S H E R R Y 9 " = L I V I N G R O O M r ~ I o : i K I T C H E N 1 - N E W F L O O R P L A N W I G H T R E S I D E N C E 1 8 5 5 N O R T H S H E R R Y A - 2 I= L I V I N G R O O M O P E N 3 ~===-= - 2 A 4 C X ) s t • R E M O V E E X I S T I N G H ~ D E R _ J _ J < ( I ~ l - l I I I I F L O O R F R A M I N G P L A N f 2 x l 0 S C A B L A P 4 8 " O . C . E X I S T I N G 2 X l 0 j O I S T 3 / 4 • P L Y W O O D . 1 I l l ~ - - - N E W ( 2 ) 2 X l 0 H E A D E R # 2 y . p . K I T C H E N L I V I N G R O O M T W O S T O R Y S P A C E N E W P O S T P T B A S E P L A T E S E C T I O N A T P O S T W I G H T R E S I D E N C E 1 8 5 5 N O R T H S H E R R Y A - 3 GENERAL NOTES EPOXY NOTES 1. CODES USED: 2020 FLORIDA BUILDING CODE, RESIDENTLAL EDTTION ANO EXISTING BUILDING EDITION, ACI, NOS, 1. ANCHOR BOlTS, REINFORCING STEEL, THREADED RODS, STAIR HANDRAILS, AND OTHER APAANDASCE7-10. EMBEDDED STEEL ITEMS SHAll BE SET INTO HARDENED CONCRETE WITH EPOXY OR EPOXY GROUT ONLY WHERE DETAILED ON THE DRAWINGS OR WHERE APPROVED BY THE ENGINEER 2. TiiE Al TERATIONS FOUND WITHIN THESE PLANS ARE DESIGNATED LEVEL 2 ALTERATIONS IN COMPLIANCE WITH SECTION301.1.20FTllEEXISTINGBUILDINGCODE. 2. MANUFACTURER'S DATA FOR ALL EPOXY AND EPOXY GROUT SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. ACCEPTABLE EPOXY PRODUCTS ARE: 3. ALL DESIGN, CONSTRUCTION ANO MATERIALS SHALL BE IN ACCORDANCE VilTH APPLICABLE CODES AND AUTHORITIES HAVING JURISDICTION OVER THE WORK. Hll Tl HY150. HIL Tl HSE2421, SIMPSON STRONG-TIE SET OR APPROVED EQUAL -4. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS AT THE JOB SITE PRIOR TO COMMENCING IN USING THE ABOVE PRODUCTS, FOLLOW STRICTLY THE MANUFACTURER'S SPECIFICATIONS CONSTRUCTION. AND DIRECTIONS FOR MlXING AND APPLICATION. HEED AU LABEL WARNINGS. INSTALL IN ACCORDANCE WITH APPLICABLE SAFETY LAWS. 5. DETAILS FOUND WITHIN THESE DRAWINGS SHA.ll. BE ASSUMED TO BE TYPICAL DETAILS FOR THIS JOB ONLY. DETAILS SHALL GOVERN CONSTRUCTION FOR THIS JOB UNLESS NOTED OTHERWISE ON THE PLANS. 3. All EPOXY ANO EPOXY GROUT SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH OF 8,000 PSI AND TENSILE STRENGTH OF 2,300 PSI. 6. SUBSURFACE SOIL CONDITIONS WERE NOT AVAILABLE AT THE TIME OF THIS DESIGN. THE OWNER SHALL PROVIDE 10 THE CONTRACTOR A REPORT OF THE SUBSURFACE CONDITIONS. SOIL PREPARATIONS NOTED IN SAID REPORT 4. ALL HOLES SHALL BE DRILLED WITH A DW..IETER NO LARGER THAN 1/8• GREATER THAN THE SHALL BE FOLLOWED UNLESS MORE STRINGENT DESIGN IS SPECIFIED WITHIN THESE PLANS, DESIGN OF THIS DIAMETER OF THE STEEL MEMBER BEING INSTALLED. STRUCTURE WAS PERFORMED ASSUMING 2500 PSF SOIL CAPACITY, 7. THE SCOPE OF WORK OF THIS PROJECT IS LIMITED TO THE CHANGES SHOWN ON THESE PLANS, THE SCOPE OF WORK SPECIF/CALLY EXCLUDES AffY AND AU ARCHITECTURAL, WATERPROOFING. MECHANICAL, PLUMBING OR ELECTRICAL WORK. 8. EXISTING STRUCTURES ARE SHO\VN ON DRAWINGS FOR CLARITY ONLY. VERIFY ALL EXISTING/NE½' ELEVATIONS AND TYPE OF CONSTRUCTION OF THOSE STRUCTURES, ANO NOTIFY ENGINEER IMMEOlATEL Y BEFORE BEGINNl~m NEW CONSTRUCTION OF ANY INTERFERENCES Nm/OR DISCREPANCIES THAT MIGHT EXIST BETWEEN CONSTRUCTION DOCUMENTS ANO/OR ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY BRACING/SHORING, TEMPORARY SUPPORTS AND OTHER SUCH ITEMS OR OTHER MEASURES NECESSARY TO PROTECT THE STRUCTURE AND ANY PERSONNEL DURING CONSTRUCTION. THE DESIGN ADEQUACY AND SAFETY OF ABOVE ITEMS ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR CONCRETE NOTES 5. ALL HOLES SHALL BE CLEANED WITH COMPRESSED AIR AND SHALL BE DRY PRIOR TO INSTALLATION OF EPOXY. HOLES SHALL BE FREE OF ALL DELETERIOUS MATERIAl SUCH AS LAITANCE. OUST, DIRT, AND Oil 6. CONTRACTOR PERFORMING EPOXY WORK SHALL BE AN APPROVED CONTRACTOR BY THE MANUFACTURER FURNISHING THE EPOXY MATERIALS, AND SHALL HAVE NO LESS THAN FIVE YEARS EXPERIENCE IN THE VARIOUS TYPES OF EPOXY RELATED WORK REQUIRED IN THIS PROJECT. A NOTARIZED CERTIFICATION FROM THE MANUFACTURER ATTESTING TO THE TRAINING SHALL BE SUBMITTED TO THE ENGINEER/ARCHITECT ALONG WITH THE PROPOSAL TO DO THE WORK. SHEATHING NOTES FOR WALL SHEA THING: 1, ALL REINFORCED CONCRETE WORK SHALL BE IN CONFORMANCE wm-1 ACI 316, LATEST EDmON, "BUILDING CODE 1. FOR STUCCO ANO STONE: MIN li° OSB OR PLYWOOD, SPAN RATING 32/16. INSTALLED REQUIREMENTS FOR REINFORCED CONCRETE". AND ACI 301, LATEST EOmON, ·sPECIFICATIONS FOR STRUCTURAL VERTICALLY, OR MIN ff OSB OR PL YINOOO, SPAN RATING 32/16, INSTALLED HORIZONTALLY, TO CONCRETE". WALL FRAMING, FASTEN WITH 8d NAILS AT 6" O.C, ON EDGE, 12" O.C. IN FIELD. 2. FOR AU OTHER VENEER: MIN {,_,· 0S8 OR Pl YWOOO, SPAN RATING 2-4116. INSTALLED 2. All CONCRETE SHALL BE NORMA.l WEIGHT CONCRETE, (145 PGF +/•) All CEMENT SHALL CONFORM TO ASTM C150, VERTICAU y OR HORJZONTALL Y, TO WALL FRAMING. FASTEN WITH 8d NAILS AT 6" O.C, ON EDGE, TYPE 1. MAXIMUM AGGREGATE SIZE SHAU BE 1½" INCHES FOR FOUNDATIONS, AND¾" FOR All SLABS AND SHALL 12" 0.C. IN FIELD (BLOCKED PANEL EDGES) OR 6' O.C. EDGE ANO FIELD (UNBLOCKED PANEL CONFORM TO ASTM C33. EDGES). 3. MINIMUM CONCRETE COMPRESSIVE STRENGTH OF ALL CONCRETE IS 3000 PSI AT 28 DAYS. 4. 4' 3000PSI CONCRETE SLAB WITH 6X6 W1.4 X W1.4 W,NM OR 112" FIBERMESH OVER A 6 Mil. VAPOR BARRIER ANO TERMITE TREA TEO SOIL. 3. FOR CURVED WALLS: TWO (2) LAYERS OF i' PLY'h'OOO. FASTEN WITH 10d NAILS AT 6" 0.C. ON EDGE ANO 12" 0.C IN FIELD. OUTER LAYER OF Pl YWOOO PANEL EDGES MUST BE LAPPED 24• MIN WITH INNER LAYER. SHIM FRAMING AS NEEDED FOR TIGHT FIT. FOR ROOF SHEA THING: 5. THE FILL BELOW THE FOUNDATION SHOULD BE FREE OF DEBRIS, ORGANIC MATERlAL. COHESIVE SOILS OR ANY 1. FOR SHINGLE ANO METAL ROOF: MIN f,; OSB OR PLYWOOD, SPAN RATING 2-4116, INSTALLED OTHER DELETERIOUS MATERlAL. SOIL MUST BE COMPACTED TO 95% MODIFIED PROCTOR MAXIMUM ORY DENSITY PERPENDICULAR TO ROOF FRAMING, FASTEN WITH Bd RING SHANK NAILS AT 6" 0.C ON EDGE, FOR nvo FEET BELOW THE BOTTOM OF THE FOOTING, 17 O.C. IN FIELD. 2. FOR TILE ROOF: MIN tl'"" Pl YINOOO, SPAN RATING 32/16, INSTALLED PERPENDICULAR TO ROOF 6. All REINFORCEMENT SHALL BE GRADE 40 DEFORMED BARS CONFORMING TO ASTr.\•A615. All CONCRETE FRAMING. FASTEN \VITH 8d RING SHANK NAILS AT 6' 0.C. ON EDGE, 17 0.C. IN FIELD. REJNFORCEMENT SHALL BE FABRICATED, INSTALLED, SUPPORTED ANO SPACED IN FORMS AND SECURED IN PLACE 3. SINGLE CLIP PANEL EDGES. INSTALL PANELS CONTINUOUS OVER nvo OR MORE SPANS WITH IN ACCORDANCE WITH ACI 315, "DETAILS ANO DETAILING OF CONCRETE REINFORCEMENT". STAGGERED ENO JOINTS. WHERE PANELS ARE INSTAUED OVER SINGLE SPANS DUE TO FIELD CONDITIONS, BLOCK PANELS AT 12" O.C. 7. CONTRACTOR SHALL VERIFY DIMENSIONS ANO LOCATIONS OF AU SLOTS, PIPE SLEEVES, ETC,, AS REQUIRED FOR MECHANICAL TRADES BEFORE CONCRETE IS PLACED B. VERTICAL ANO HORIZONTAL REINFORCEMENT WILL BE LAPPED FOR 36 BAR DIAMETERS OR 24·, \'iHICHEVER IS GREATER 9. CORNER REINFORCEMENT SHALL BE LAPPED 25". IO. REINFORCEMENT SHALL HAVE THE FOLLOWING COVER REQUIREMENTS; 10. 1. 3" FOR CONCRETE CAST AND PERMANENTLY EXPOSED TO EARTH 10.2. 2' FOR CONCRETE EXPOSED TO EARTH AND WEATI-IER 10.3. 1 1f2' FOR CONCRETE NOT EXPOSED TO WEATHER OR EARTH FOR THE PRIMARY REINFORCEMENT. 11 ONLY DIMENSIONS FOUND ON THE FOUNDATION PlAN BY ALEXANDER GRACE CONSUL TING, INC,, SHOULD BE USED FOR FLOOR DECKING: 1, MIN f T&G ass OR PLYWOOD. SPAN RATING -48/2-4, INSTALLED PERPENDICULAR TO FLOOR FRAMING. FASTEN WITH 8d NAILSAT6" O,C. ON EDGE, 12· O,C. IN FIELD. 2. USE OF APA RATED STUR0-1-FLOOR IS ALLOWED WITH A MINIMUM SPAN RATING OF -4812-4 ANO MINIMUM J· THICKNESS. FOR PORCH CEILING SHEATHING: 1. MIN f OSB OR PLY\VOOD, SPAN RATING 24f0, INSTALLED PERPENDICULAR TO CEILING FRAMING. FASTEN W1TH 8d NAILS AT 3· 0.C. ON EDGE, 12" O,C. IN FIELD. LOAD TABLE FOR FOUNDATION CONSTRUCTION. IF DIMENSIONS CAN NOT BE DETERMINED FROM FOUNDATION PLAN, CONTACT ROOF: THE ENGINEER OF RECORD. LIVE LOAD: COMPONENT AND CLADDING DESIGN PRESSURES 12. STEM WALL TO BE A MAXIMUM OF SIX (6) COURSES TALL CONTACT ENGINEER OF RECORD IF STEM WALL WILL DEAD LOAD: EXCEED SIX (6) COURSES IN HEIGHT. CEILING: 13. WHERE THREADED RODS ARE EMBEDDED 12" INTO STEM WALLS, THE TOP TWO COURSES OF STEM WALL MUST BE ~: ~~~:STORAGE: FILLED. DEAD LOAD: FRAMING NOTES FLOOR. 1, DESIGN OF WOOD COMPONENTS IN THIS STRUCTURE IS BASED ON THE 2020 FLORIDA BUILDING CODE, UVE LOAD. RESIDENTIAL EDITION AND THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION. DEAD LOAD: 2. DESIGN LOADING FOR THIS STRUCTURE IS FOUND IN THE LOAD TABLE ON THJS SHEET. 3. All FRAMING ANCHORS SHOWN ON PLANS ARE SIMPSON. ALTERNATE CONNECTORS ARE ACCEPTABLE PROVIDED EQUAL OR GREATER CAPACITIES ARE ACHIEVED. CONTACT ENGINEER OF RECORD IF EQUAL CAPACITIES ARE NOT APPARENT. 4. All WOOD DIRECTLY EXPOSED TO CONCRETE, MASONRY OR SOIL SHALL BE PRESSURE TREATED. 5. All WOOD OIRECTL Y EXPOSED TO WEATHER SHALL BE PRESSURE TREATED. 6. NAILS OR CONNECTORS EXPOSED TO \\IEATHER SHAU. BE GALVANIZED. 7. DIMENSION LUMBER 7 .1. All MEMBER SIZES GIVEN IN THE DRAWINGS ARE NOMINAL DIMENSIONS 7 .2. \\'HERE POSTS ARE CALLED OUT, HEADERS SHALL BEAR FULLY ON POSTS. 7.3. ALL BEAMS ANO JOISTS NOT BEARING ON SUPPORTING MEMBERS SHALL BE FRN,1ED WITH SIMPSON STRONG-TIE JOIST HANGERS OR EQUAL PER APPROVAL OF THE ENGINEER OF RECORD. THE JOIST HANGERS SHALL BE NAILED WITH NAILS MEETING THE DWJETER AND LENGTH PER THE DETAILS. 8. All NAILS SHALL BE COMMON NAILS, UNLESS OTHERWISE NOTED. NAIL SIZES ARE DEFINED BELOW, 8d""0.131"ll2·112" 10d= 0.148·x3" 12d=0.148"xJ..1/4" 16<l=0,162'xJ..112" 9. WHERE FRAMING DETAILS SHOW FOOTINGS, SEE FOOTING DETAILS ON THE FOUNDATION PLAN ANO/OR THE FOOTING DETAILS SHEET. 10. CONVENTIONAL FRN,llNG LUMBER IS 2x No.2 SYP UNLESS NOTED OTHERWISE. EXTERIOR WALL STUD SPACING BRITTLE FIWSH FLEXIBLE FINISH WALL HEIGHT (U360) WALL HEIGHT (Ul20) BEARING STUD SIZE ANO GRADE BFT 9 Fl 10FT CONDITION 11 FT 12 Fl BFT 9FT 10FT 11 Fl 2X4 SPF STUD 16 12 " / 16 16 ""ec" >, Otff 2X4 N0.2SPF 16 12 < STORY ">, 16 16 16 12 2X6 SPF STUD GRO OR N0.2 16 16 16 16 16 16 16 16 16 2X4 SPF STUD 16 12 " 16 12 ,· / / TWO 2X-4 N0.2 SPF 16 12 " / :/·, 16 16 12 '< STORY / 2X6 SPF STUD GRD OR N0.2 16 16 16 16 16 16 16 16 16 NOTES I. ALL NON.CORNER STUDS LOCATED IN WALL ENO ZONES TO BE DOUBLED, FASTEN STUDS TOGETHER WITH 12d COMMONS AT 8' 0.C. 2, NON-BEARING WALLS MAY BE FRMtEDWITH 2X STUDS AT 24' O.C. MAX. 12 FT 16 16 DECK LIVE LOAD; WIND LOADS: WIND SPEED: EXPOSURE: IMPORTANCE: BUILDING CATEGORY: ENCLOSED BUILDING· INTERIOR PRESSURE COEFFICIENT: ROOF PITCH: 20.0 PSF 7.0 PSF EFFECTIVE AREA, SF 0.0 PSF Q.20 ENO ZONES, PSF 24.4 -32.0 INTERIOR ZONES, PSF 24.4 ·26.6 30.0 PSF f-----4---\--~f----+-----! 5.0 PSF 20·50 40.0PSF 10.0 PSF 50.0 PSF 130 MPH C to II 0.18 NIA 50-100 100..200 22.9 -28.8 22.9 ·25.3 2L6 -27.2 2L6 ·24.0 20.8 .24.4 20.8 •22.9 I i rr---I !~--lL~__,I,___~ I -- SHEET INDEX ·I GENERAL NOTES Sl.01 .. FOU_ND/\TION PL/IN AND DFrAILS 82 01 FIRST LEVEL FRAMING PLAN AND . DETAILS (I)t~~.~RIOR BEARING FOOTING 11'-4" 5'-10" FIELD VERIFY~ FIELD VERIFY 1 ©il-7 :7-7 t+• j-l.~r·• t \_:, EX1;~1NGWALL ~ '•,., CENTERLINE ~ 1'"'"""-...._ TYP, . •., VERIFY OR INSTALL. FOUNDATION CENTER TO MATCH CENTER OF i:: =---~ POST ABOVE ~ ffi I EXISTING SLAB j r,,> -~ a: r-EXISTING // FOOTING. --I' ----., Ir--------- ' / ',,,_ ___ JI a~~-OND LEVEL FLOOR PLAN ~ 24'x24'x12" DEEP FOOTING \:.:_J WITH (3) #5 BARS EACH WAY THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY GEOFF GARTNER. PE, USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED WITHOUT THIS STATEMENT. (FAC 61G1S.23 005(0) & 61G1-16.005). i ~ ~ ~ if, ~ 0 z < l: ~ , > } is 8 ~ ~ ~ f;' ~ I ~ ~ ~ ~ ~ i ~ - (I) w w w .., () () > .., > z ii: ~ 0 .., Cl:'. w ~ .J w 0 u. er: (I) ci5 w :r: I t) w w Cf) ,,: w z Cl:'. I en :J I-Ii: t) I-I 0 i= (I) (!) z z 0 '.'I <( ~ "' I-0 ~ ,,: () & & s" i~ Iii; i~ ~ /j ,~ (/) z w :s (/) I-a.. _J 0 z <( z O I- _J -w ~~o woo zZZ w ::::> <( (9 0 LL u ~ i'l:3 g' ~11 ] ~5 II U) 8 E ~ <!) u~ ~ §~ j ~£ -< ! 0 < vi~~ N ~5 al !s1 ~p @~d S1 .01 LIVING ROOM HALL KITCHEN 0,}~.~T LEVEL WALL PLAN NEW BEAM. SEE PLAN. EXISTING FLOOR JOIST. FASTEN TO NEW BEN,1 WITHLUS28. G)~~S!ION AT BEAM ___,.------EXISTING WALL ABOVE. ~~-FASTEN BOTTOM PLATE TO NEW BEAM WITH SDWC15600AT 16" 0.C. 1:-_ J-"/ /i--:,~ NEW BEM1. SEE PLAN. -EXISTING FLOOR JOIST. FASTEN TO NEW BEAM WITHLUS28. 0~~S!ION AT WALL 0, S2.01 NEW3-PLY-, 9.25" LVL 0 I NEW4.PLY _/ 9.25"LVL EXISTING JOISTS -\ / 8 o~s_OND LEVEL FLOOR PLAN NEW BEAM. SEE PLAN AND NOTE NS2.01 FOR DETAILS. -----J\/Mi'f-----FLOOR JOISTIBEN,1 .-~ 7.PLYSTUDGROUP.SEE __ ,--,./ PLAN AND NOTE NS2.0I FOR DET AtlS. © ~~S_TION AT POST FRAMING NOTES AND LEGEND TOP AND BOTTOM PLATE MATERIAL: 2x No, 2 SYP, UNO. 2x No, 2 SPF, UNO. STUD MATERIAL: HEADERS: All HEADERS ARE (2) 2:w:6 No. 2 SYP WITH TWO KINGS ANO ONE CRIPPLE, UNO. FASTEN HEADER LUMBER TOGETHER USING (2) ROWS OF t&J (0.148~ X 3.S-) COMMON NAILS AT 12· ON CENTER. USE OSB SHIMS AS NECESSARY TO MAKE THE HEADER THICKNESS EQUAL TO THAT OF THE WALL TT IS IN. SEE TiiE HEADER DETAIL FOR FASTENING SPECIFICATIONS. UEADER NOTATION IS: ~---NUMBER OF PLIES IN HEADER ' NUMBER OF KING STUDS (2)~2:1 L L NUMBER OF CRIPPLE STUDS ------· SIZE OF DIMENSIONAL LUMBER PORCHJGLULAM BEAM ABBREVIATIONS: ICR INTERMEDIATE CRIPPLES REQUIRED. HEADER TO CRIPPLES WJTH SDWC15600 SCREWS. LVL 1,75" 'MDE 2.0E TRUSJOIST 2.0E MICROLAM LVL OR EQUIVALENT MIR MIRROR. MSR MACHINE STRESS RATED LUMBER. O.C. ON CENTER. OSB ORIENTED STRANO BOARD. SIM SIMILAR. SPF SPRUCE PINE FIR. SPH STRUCTURAL PANEL HEADER SYP SOUTI--lERN YELLOW PINE. TYP TYPICAL UNO UNLESS NOTED OTHERWISE. CANT CANTILEVER 0 0 VERIFY OR PLACE STUD GROUP UNDER BEAM BEARING. NUMBER OF STUDS EQUALS THAT OF BEAM PLY, MIN 2STUDS. FASTEN BEAM TO STUD GROUP WITH (2) MSTA24. FASTEN STUD GROUP TO FOOTING WITH L TT208. USE 10d NAILS IN All HOLES. IF THREADED ROD IS WITHIN 1T OF BEARING. NOL TT20B IS REQUIRED. ADO SCAB AT EACH EXISTING FLOOR JOIST. FASTEN TO JOIST WITH (2) ROWS OF SDS25300 AT 12" 0.C STAGGERED. FASTEN SCAB TO EXISTING BEAM/JOIST \VTTH LUS28. ___ .-~---SOS SCREWS AT 12" 0.C. STAGGERED. MINIMUM EDGE DISTANCE:: 2" MINIMUM END DISTANCE:: 2" SCREVI LENGTH PER TABLE; 2-PLY: SOS25312 3-PL Y: SOS25500 4-PLY; S0S25600 SCREWS STAGGERED EACH FACE. LVUBEAM. SEE PLAN FOR SPECIFICATIONS. 0~!:'-~_!1-PL Y FASTENING THIS ITEM HAS BEEN ELECTRONICALLY SIGNED ANO SEALED BY GEOFF GARTNER. PE, USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED WITHOUT THIS STATEMENT. (FAC61G15-23.005(O)& 6101-16.005). i ~ ~ ~ ~ ~ 0 z . 8 ~ , j a 8 ~ I e ~ @ ~ w i ~ ~ ~ 4 ~ ~ en w w (.) (.) > z 0:: w w 0 en U) w w z 0:: :J I-I-I ~ (9 ~ 0 (.) u (!) -< Sheet No. ~ .., .., et: ~ 0 .., >-.J et: u. et: w :r' J: () en <( w J: m ~ () 0 F z z 0 '.5 "' ~ ~ S2.01