900 Plaza Sea Oats Apts Fire Hydrant Test rr FORTITUDE FIRE PROTECTION 2430 University Blvd., West * Jacksonville, FL 32217 * 904-733-9008 www.fortitudefire.corn FIRE HYDRANT FLOW TEST Owner: Owner Phone Number: Owner Address: Property Being Evaluated: Sea Oats Apts Property Address: 900 Plaza Dr Atlantic Beach 32233 Date of Work: 4/15/2021 All responses refer to the current work (inspection, testing and maintenance) performed on this date. This work is (check one): E Annual ❑ Fifth Year 0 Existing ❑Repaired ❑ New Device 470 Part I — /1- Sarah Knapp 4/15/2021 Owner or Owner 0 -r or Owner Representative Printed Name Date ❑ Rep. Not Onsite Part II — Inspector's Section 1. Location of Hydrant: Bldg 2 2. Make / Model of Hydrant: Mueller A-421 3. Size of Hydrant: 4 1/2" 4. Color of Hydrant: Yellow 5. Is Hydrant housing accessible? 0 Yes ❑ No ❑ N/A 6. Housing free of external damage? 0 Yes ❑ No ❑ N/A 7. Is the operating wrench available? 0 Yes ❑ No ❑ N/A 8. Does associated piping appear to be free of leaks? 0 Yes ❑No ❑ N/A 9. Do all the control valve(s) appear to be open? 0 Yes ❑ No ❑ N/A 10. Is isolation valve accessible? 0 Yes No ❑ N/A 11. Free of leaks (external)? 0 Yes ❑ No ❑ N/A 12. Operating nut is in good condition? 0 Yes ❑ No ❑ N/A 13. Threads of nozzles ! caps in good condition? 0 Yes ❑ No ❑ N/A 14. Gaskets on caps in good condition? 0 Yes ❑ No ❑ N/A 15. Is Hydrant in normal open / closed position? 0 Yes ❑ No ❑ N/A 16. Does operating nut appear to work thru full range? 0 Yes ❑ No ❑ N/A 17. Water flowed for 60 seconds or until clear? 0 Yes ❑ No ❑ N/A 18. Free from foreign material in barrel? 0 Yes ❑ No ❑ N/A 19. Does Hydrant drain in 60 minutes or less? 0 Yes 0 No ❑ N/A 20. Hydrants requiring pumping identified? El Yes ❑ No 0 N/A 21. Threads/caps/stems/plugs lubricated? © Yes No J N/A 22. Has a 5-year flow test been performed per NFPA 25? Yes ❑No ❑ N/A Part II —Comments(any"NO°answers,test failures or other problems found with the hydrant inspection must be explained here. Also,note here any products noticed on the system that have been the subject to a recall or replacement program) ** See Diagram ** Part III — Recommendations (Not a part of the NFPA-25 inspection,the following items may need to be reviewed by a fire protection engineer) Part IV— Inspectors Information I state that the information on this form is correct at the time and place of my inspection and that all equipment tested at this time was left in operation conditional upon completion of this inspection except as noted in part Ill above. Date: 4/15/2021 Printed Name of Inspector: Ja ,o Kestner Signature of Inspector: License or Certificate Number(if applicable): FPI21-000025 Color of Tag Placed on System: fl Red 0 Green ❑Yellow rw-rPrP FORTITUDE - FIRE PROTECTION -® 2430 University Blvd., West * Jacksonville, FL 32217 * 904-733-9008 www.fortitudefire.com FIRE HYDRANT FLOW TEST Owner: Owner Phone Number: Owner Address: Property Being Evaluated: Sea Oats Apts Property Address: gfl(l Plaza fr Atlantic: Raarh :122'1'1 Date of Work: 4/15/2021 All responses refer to the current work (inspection, testing and maintenance) performed on this date. This work is (check one): E Annual ❑ Fifth Year El Existing ❑Repaired ❑ New Device Part I — Sarah Knapp 4/15/2021 Owner or Owner Owne -or. ner Representative Printed Name Date ❑ Rep. Not Onsite Part II — Inspector's Section 1. Location of Hydrant: Bldg 7 2. Make /Model of Hydrant: Mueller A-421 3. Size of Hydrant: 4 1/2" 4. Color of Hydrant: Yellow 5. Is Hydrant housing accessible? 0 Yes ❑ No ❑ N/A 6. Housing free of external damage? 0 Yes ❑ No ❑ N/A 7. Is the operating wrench available? 0 Yes ❑ No ❑ N/A 8. Does associated piping appear to be free of leaks? 0 Yes ❑No ❑ N/A 9. Do all the control valve(s) appear to be open? 0 Yes ❑No ❑ N/A 10. Is isolation valve accessible? 0 Yes ❑ No ❑ N/A 11. Free of leaks (external)? 0 Yes ❑ No ❑ N/A 12. Operating nut is in good condition? 0 Yes ❑ No ❑ N/A 13. Threads of nozzles / caps in good condition? 0 Yes ❑ No ❑ N/A 14. Gaskets on caps in good condition? 0 Yes ❑ No ❑ N/A 15. Is Hydrant in normal open / closed position? 0 Yes ❑ No ❑ N/A 16. Does operating nut appear to work thru full range? 0 Yes ❑ No ❑ N/A 17. Water flowed for 60 seconds or until clear? 0 Yes ❑ No ❑ N/A 18. Free from foreign material in barrel? 0 Yes ❑ No ❑ N/A 19. Does Hydrant drain in 60 minutes or less? 0 Yes ❑ No ❑ N/A 20. Hydrants requiring pumping identified? ❑ Yes ❑ No 0 N/A 21. Threads/caps/stems/ plugs lubricated? © Yes ❑ No ❑ N/A 22. Has a 5-year flow test been performed per NFPA 25? B Yes ❑No ❑ N/A Part II —Comments(any"NO"answers,test failures or other problems found with the hydrant inspection must be explained here. Also,note here any products noticed on the system that have been the subject to a recall or replacement program) ** See Diagram ** Part III — Recommendations (Not a part of the NFPA-25 inspection,the following items may need to be reviewed by a fire protection engineer) Part IV— Inspectors Information I state that the information on this form is correct at the time and place of my inspection and that all equipment tested at this time was left in operation conditional upon completion of this inspection except as noted in part Ill above. Date: 4/15/2021 Printed Name of Inspector: Ja o Kestner Signature of Inspector: License or Certificate Number (if applicable): FPI21-000025 Color of Tag Placed on System: ❑ Red 0 Green ❑Yellow ror rir 3RTITUDE FIRE PROTECTION -• 2430 University Blvd., West * Jacksonville, FL 32217 * 904-733-9008 www.fortitudefire.com FIRE HYDRANT FLOW TEST Owner: Owner Phone Number: Owner Address: Property Being Evaluated: Sea Oats Apts Property Address: 900 Plaza Dr Atlantic Beach 32233 Date of Work: 4/15/2021 All responses refer to the current work (inspection, testing and maintenance) performed on this date. This work is (check one): e Annual ❑ Fifth Year E Existing ❑Repaired ❑ New Device Part I — /1 Sarah Knapp 4/15/2021 Owner or Owner caner or Owner Representative Printed Name Date ❑ Rep. Not Onsite Part II — Inspector's Section 1. Location of Hydrant: Bldg 13 2. Make / Model of Hydrant: Mueller A-421 3. Size of Hydrant: 4 1/2" 4. Color of Hydrant: Yellow 5. Is Hydrant housing accessible? 0 Yes ❑ No ❑ N/A 6. Housing free of external damage? 0 Yes ❑ No ❑ N/A 7. Is the operating wrench available? 0 Yes ❑ No ❑ N/A 8. Does associated piping appear to be free of leaks? 0 Yes ❑No ❑ N/A 9. Do all the control valve(s) appear to be open? 0 Yes ❑No ❑ N/A 10. Is isolation valve accessible? 0 Yes ❑ No ❑ N/A 11. Free of leaks (external)? 0 Yes ❑ No ❑ N/A 12. Operating nut is in good condition? 0 Yes ❑ No ❑ N/A 13. Threads of nozzles /caps in good condition? 0 Yes ❑ No ❑ N/A 14. Gaskets on caps in good condition? ❑ Yes 0 No ❑ N/A 15. Is Hydrant in normal open / closed position? 0 Yes ❑ No ❑ N/A 16. Does operating nut appear to work thru full range? 0 Yes ❑ No ❑ N/A 17. Water flowed for 60 seconds or until clear? 0 Yes ❑ No ❑ N/A 18. Free from foreign material in barrel? 0 Yes ❑ No ❑ N/A 19. Does Hydrant drain in 60 minutes or less? 0 Yes 0 No ❑ N/A 20. Hydrants requiring pumping identified? 0 Yes ❑ No 0 N/A 21. Threads/caps/stems/plugs lubricated? ® Yes ❑ No ❑ N/A 22. Has a 5-year flow test been performed per NFPA 25? B Yes ❑No ❑ N/A Part II —Comments(any'NO"answers,test failures or other problems found with the hydrant inspection must be explained here. Also,note here any products noticed on the system that have been the subject to a recall or replacement program) Gaskets need to be replaced ** See Diagram ** Part III — Recommendations (Not a part of the NFPA-25 inspection,the following items may need to be reviewed by a fire protection engineer) Part IV— Inspectors Information I state that the information on this form is correct at the time and place of my inspection and that all equipment tested at this time was left in operation conditional upon completion of this inspection except as noted in part Ill above. Date: 4/15/2021 Printed Name of Inspector: Ja ,o Kestner Signature of Inspector: License or Certificate Number (if applicable): FPI21-000025 Color of Tag Placed on System: ❑ Red 0 Green 0 Yellow .1.111 ■ rr I- FORTITUDE FIRE PROTECTION —® 2430 University Blvd., West * Jacksonville, FL 32217 * 904-733-9008 www.fortitudefire.com FIRE HYDRANT FLOW TEST Owner: Owner Phone Number Owner Address: Property Being Evaluated: Sea Oats Apts Property Address: 900 Plaza Dr Atlantic Beach 32233 Date of Work: 4/15/2021 All responses refer to the current work (inspection, testing and maintenance) performed on this date. This work is (check one): EAnnual ❑ Fifth Year 0 Existing El Repaired ❑ New Device C-IPart I – 1 — Sarah Knapp 4/15/2021 Owner or Owner Owner or Owner Representative Printed Name Date ❑ Rep. Not Onsite Part II – Inspector's Section 1. Location of Hydrant: Entrance 2. Make / Model of Hydrant: Mueller A-421 3. Size of Hydrant: 4 1/2" 4. Color of Hydrant: Yellow 5. Is Hydrant housing accessible? 0 Yes ❑ No ❑ N/A 6. Housing free of external damage? 0 Yes ❑ No ❑ N/A 7. Is the operating wrench available? 0 Yes ❑ No ❑ N/A 8. Does associated piping appear to be free of leaks? 0 Yes ❑No ❑ N/A 9. Do all the control valve(s) appear to be open? 0 Yes ❑No ❑ N/A 10. Is isolation valve accessible? 0 Yes ❑ No ❑ N/A 11. Free of leaks (external)? 0 Yes ❑ No ❑ N/A 12. Operating nut is in good condition? 0 Yes ❑ No ❑ N/A 13. Threads of nozzles / caps in good condition? 0 Yes ❑ No El N/A 14. Gaskets on caps in good condition? ❑ Yes 0 No El N/A 15. Is Hydrant in normal open /closed position? 0 Yes ❑ No ❑ N/A 16. Does operating nut appear to work thru full range? 0 Yes ❑ No ❑ N/A 17. Water flowed for 60 seconds or until clear? 0 Yes ❑ No ❑ N/A 18. Free from foreign material in barrel? 0 Yes ❑ No ❑ N/A 19. Does Hydrant drain in 60 minutes or less? 0 Yes 0 No 0 N/A 20. Hydrants requiring pumping identified? Yes No 0 N/A 21. Threads/caps/stems/ plugs lubricated? ® Yes El No N/A 22. Has a 5-year flow test been performed per NFPA 25? E/ Yes No N/A Part II —Comments(any NO answers,test failures or other problems found with the hydrant inspection must be explained here. Also,note here any products noticed on the system that have been the subject to a recall or replacement program) Gaskets need to be replaced ** See Diagram ** Part III —Recommendations (Not a part of the NFPA-25 inspection,the following items may need to be reviewed by a fire protection engineer) Part IV— Inspectors Information I state that the information on this form is correct at the time and place of my inspection and that all equipment tested at this time was left in operation conditional upon completion of this inspection except as noted in part Ill above. Date: 4/15/2021 Printed Name of Inspector: JaSO Kestner 1 Signature of Inspector: 52, License or Certificate Number(if applicable): FPI21-000025 Color of Tag Placed on System: Red 0 Green Yellow